Variable frequency drive (HVAC) · BACnet points list
Contemporary Controls Yaskawa E7 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Yaskawa E7: 589 objects (72 AI, 310 AO, 187 BI, 20 BO), but only 50 polled by default (inverter status bits and the main monitors). Run/stop, direction, fault reset and multi-function input commands, the frequency reference and PID setpoint, fault contents bits and a long parameter list are in the profile but unpolled.
This page lists 589 BACnet objects for the Contemporary Controls Yaskawa E7 via BASgatewayLX — 330 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Yaskawa E7 via BASgatewayLX
- Equipment
- Variable frequency drive (HVAC)
- Equipment type
- VFDs & pumps
- BACnet objects
- 589 (330 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- E7 drive, Yaskawa E7 Modbus, CIMR-E7
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Yaskawa E7 via BASgatewayLX
Enable and write the run command (BO 1) and frequency reference (AO 12) for control, then read the inverter status bits, output frequency, current and power.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Command 0 = Stop 1 = Run | Run/stop command (1 = run) | Command |
| AO 12 | Frequency Reference | Frequency reference | Command |
| BO 4 | Command Fault reset | Fault reset | Command |
| BI 25 | Inverter Status @ RUN | Drive running | Read |
| BI 28 | Inverter Status Inverter Ready | Inverter ready | Read |
| AI 202 | Output Frequency | Output frequency, Hz | Read |
| AI 203 | Output Current | Output current, A | Read |
| AI 206 | Output Power | Output power, kW | Read |
| BI 29 | Inverter Status Minor Fault | Minor fault (alarm) active | Read |
| BI 30 | Inverter Status Major Fault | Major fault active | Read |
Enable & remote start
The drive must take its run command and frequency reference from serial communication (b1-01 / b1-02 set to serial per the E7 manual) before BO 1 and AO 12 act. These command objects are unpolled in the published profile; tick them first.
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Run, reference and reset objects are unpolled by default; enable them before mapping.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Yaskawa E7 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | Command 0 = Stop 1 = Run | Modbus 400002 bit 0; not polled by default | Command | ||
| BO | 2 | Command 0 = Forward 1 = Reverse | Modbus 400002 bit 1; not polled by default | Command | ||
| BO | 3 | Command External Fault | Modbus 400002 bit 2; not polled by default | Command | ||
| BOmin | 4 | Command Fault reset | Modbus 400002 bit 3; not polled by default | Command | ||
| BO | 5 | Command ComNet (0 = bl-01 = pre-selected source | Modbus 400002 bit 4; not polled by default | Command | ||
| BO | 6 | Command ComCtrl (0 = bl-02 = pre-selected source | Modbus 400002 bit 5; not polled by default | Command | ||
| BO | 7 | Command Multi-Function Input 1 | Modbus 400002 bit 6; not polled by default | Command | ||
| BO | 8 | Command Multi-Function Input 2 | Modbus 400002 bit 7; not polled by default | Command | ||
| BO | 9 | Command Multi-Function Input 3 | Modbus 400002 bit 8; not polled by default | Command | ||
| BO | 10 | Command Multi-Function Input 4 | Modbus 400002 bit 9; not polled by default | Command | ||
| BO | 11 | Command Multi-Function Input 5 | Modbus 400002 bit 10; not polled by default | Command | ||
| AOmin | 12 | Frequency Reference | Modbus 400003; not polled by default | Hz | Command | |
| AO | 13 | PID Setpoint | Modbus 400007; not polled by default | Command | ||
| AO | 14 | Analog Output 1 Setting | Modbus 400008; not polled by default | V | Command | |
| AO | 15 | Analog Output 2 Setting | Modbus 400009; not polled by default | V | Command | |
| BO | 16 | Outputs Multi-Function Output 1 | Modbus 400010 bit 0; not polled by default | Command | ||
| BO | 17 | Outputs Multi-Function Output 2 | Modbus 400010 bit 1; not polled by default | Command | ||
| BO | 18 | Outputs Multi-Function Output 3 | Modbus 400010 bit 2; not polled by default | Command | ||
| BO | 19 | Outputs Fault Relay Output | Modbus 400010 bit 6; not polled by default | Command | ||
| BO | 20 | Outputs Fault Relay N.C. | Modbus 400010 bit 7; not polled by default | Command | ||
| BO | 21 | Command Selection PID Value 0006h is used | Modbus 400016 bit 1; not polled by default | Command | ||
| BO | 22 | Command Selection Simultaneous Terminal S5 Enable* | Modbus 400016 bit 12; not polled by default | Command | ||
| BO | 23 | Command Selection Simultaneous Terminal S6 Enable* | Modbus 400016 bit 13; not polled by default | Command | ||
| BO | 24 | Command Selection Simultaneous Terminal S7 Enable* | Modbus 400016 bit 14; not polled by default | Command | ||
| BImin | 25 | Inverter Status @ RUN | Modbus 400017 bit 0 | Read | ||
| BI | 26 | Inverter Status @ Reset Signal | Modbus 400017 bit 3 | Read | ||
| BI | 27 | Inverter Status Speed Agree | Modbus 400017 bit 4 | Read | ||
| BImin | 28 | Inverter Status Inverter Ready | Modbus 400017 bit 5 | Read | ||
| BImin | 29 | Inverter Status Minor Fault | Modbus 400017 bit 6 | Read | ||
| BImin | 30 | Inverter Status Major Fault | Modbus 400017 bit 7 | Read | ||
| BI | 31 | Inverter Status @ ComRef | Modbus 400017 bit 14 | Read | ||
| BI | 32 | Inverter Status @ ComCtrl | Modbus 400017 bit 15 | Read | ||
| BI | 33 | Operator Status OPE | Modbus 400018 bit 0; not polled by default | Read | ||
| BI | 34 | Operator Status ERR | Modbus 400018 bit 1; not polled by default | Read | ||
| BI | 35 | Operator Status PRG Mode | Modbus 400018 bit 2; not polled by default | Read | ||
| BI | 36 | Operator Status 0 - Operator 1 - PC | Modbus 400018 bit 3; not polled by default | Read | ||
| BI | 37 | OPE E7 drive kVA Setting Error | Modbus 400019 bit 1; not polled by default | Read | ||
| BI | 38 | OPE Parameter Setting Out of Range | Modbus 400019 bit 2; not polled by default | Read | ||
| BI | 39 | OPE Multi-Function Input Selection | Modbus 400019 bit 3; not polled by default | Read | ||
| BI | 40 | OPE Run Command Selection Error - Option board missing | Modbus 400019 bit 5; not polled by default | Read | ||
| BI | 41 | OPE Control Method Selection Error - PG Opt Missing | Modbus 400019 bit 6; not polled by default | Read | ||
| BI | 42 | OPE Multi-Function Analog Input Select Error | Modbus 400019 bit 7; not polled by default | Read | ||
| BI | 43 | OPE Function Selection Error for current coPID | Modbus 400019 bit 8; not polled by default | Read | ||
| BI | 44 | OPE PID Control Setup Error | Modbus 400019 bit 9; not polled by default | Read | ||
| BI | 45 | OPE V/F Parameter/Pattern Setting Error | Modbus 400019 bit 10; not polled by default | Read | ||
| BI | 46 | OPE Carrier Frequency Parameter Setting Error | Modbus 400019 bit 11; not polled by default | Read | ||
| AI | 47 | Inverter Product Code | Modbus 400020; not polled by default | Read | ||
| BI | 48 | Fault Contents 1 @ Fuse | Modbus 400021 bit 0; not polled by default | Read | ||
| BI | 49 | Fault Contents 1 @ Main Circuit Undervohage | Modbus 400021 bit 1; not polled by default | Read | ||
| BI | 50 | Fault Contents 1 @ Control Circuit Undervoltage | Modbus 400021 bit 2; not polled by default | Read | ||
| BI | 51 | Fault Contents 1 @ MC Error | Modbus 400021 bit 3; not polled by default | Read | ||
| BI | 52 | Fault Contents 1 @ Ground Fauh | Modbus 400021 bit 5; not polled by default | Read | ||
| BI | 53 | Fault Contents 1 @ Over Current | Modbus 400021 bit 6; not polled by default | Read | ||
| BI | 54 | Fault Contents 1 @ Overvohage | Modbus 400021 bit 7; not polled by default | Read | ||
| BI | 55 | Fault Contents 1 @ Inverter Overheat | Modbus 400021 bit 8; not polled by default | Read | ||
| BI | 56 | Fault Contents 1 @ Inverter Overheat Warning | Modbus 400021 bit 9; not polled by default | Read | ||
| BI | 57 | Fault Contents 1 @ Motor Overload | Modbus 400021 bit 10; not polled by default | Read | ||
| BI | 58 | Fault Contents 1 @ Inverter Overload | Modbus 400021 bit 11; not polled by default | Read | ||
| BI | 59 | Fault Contents 1 @ Overtorque I | Modbus 400021 bit 12; not polled by default | Read | ||
| BI | 60 | Fault Contents 1 @ Overtorque 2 | Modbus 400021 bit 13; not polled by default | Read | ||
| BI | 61 | Fault Contents 1 @ Braking Resistor Fault | Modbus 400021 bit 14; not polled by default | Read | ||
| BI | 62 | Fault Contents 1 @ Braking resistor Overheat | Modbus 400021 bit 15; not polled by default | Read | ||
| BI | 63 | Fault Contents 2 @ External Fault 3 | Modbus 400022 bit 0; not polled by default | Read | ||
| BI | 64 | Fault Contents 2 @ External Fault 4 | Modbus 400022 bit 1; not polled by default | Read | ||
| BI | 65 | Fault Contents 2 @ External Fault 5 | Modbus 400022 bit 2; not polled by default | Read | ||
| BI | 66 | Fault Contents 2 @ External Fault 6 | Modbus 400022 bit 3; not polled by default | Read | ||
| BI | 67 | Fault Contents 2 @ External Fault 7 | Modbus 400022 bit 4; not polled by default | Read | ||
| BI | 68 | Fault Contents 2 @ Overspeed | Modbus 400022 bit 7; not polled by default | Read | ||
| BI | 69 | Fault Contents 2 @ Excessive Speed Bias | Modbus 400022 bit 8; not polled by default | Read | ||
| BI | 70 | Fault Contents 2 @ PG Line Interruption | Modbus 400022 bit 9; not polled by default | Read | ||
| BI | 71 | Fault Contents 2 @ Input Phase Fault | Modbus 400022 bit 10; not polled by default | Read | ||
| BI | 72 | Fault Contents 2 @Output Phase Fault | Modbus 400022 bit 11; not polled by default | Read | ||
| BI | 73 | Fault Contents 2 @ Overheat | Modbus 400022 bit 12; not polled by default | Read | ||
| BI | 74 | Fault Contents 2 @ Operator Bypass Fault | Modbus 400022 bit 13; not polled by default | Read | ||
| BI | 75 | Fault Contents 2 @ EEPROM Write Fault | Modbus 400022 bit 14; not polled by default | Read | ||
| BI | 76 | Fault Contents 2 @ Motor Overheat Fauh | Modbus 400022 bit 15; not polled by default | Read | ||
| BI | 77 | Fault Contents 3 @ Communications Fault | Modbus 400023 bit 0; not polled by default | Read | ||
| BI | 78 | Fault Contents 3 @ Communications Option Fault | Modbus 400023 bit 1; not polled by default | Read | ||
| BI | 79 | Fault Contents 3 @ SI-F/G Communication Fault | Modbus 400023 bit 2; not polled by default | Read | ||
| BI | 80 | Fault Contents 3 @ SI-F/G Fault | Modbus 400023 bit 3; not polled by default | Read | ||
| BI | 81 | Fault Contents 3 @ Control Fauh | Modbus 400023 bit 4; not polled by default | Read | ||
| BI | 82 | Fault Contents 3 @ Zero Servo Fault | Modbus 400023 bit 5; not polled by default | Read | ||
| BI | 83 | Fault Contents 3 @ Communications Option External Fault | Modbus 400023 bit 6; not polled by default | Read | ||
| BI | 84 | Fault Contents 3 @ PID Feedback Error | Modbus 400023 bit 7; not polled by default | Read | ||
| BI | 85 | Fault Contents 3 @ Undertorque I | Modbus 400023 bit 8; not polled by default | Read | ||
| BI | 86 | Fault Contents 3 @ Undertorque 2 | Modbus 400023 bit 9; not polled by default | Read | ||
| BI | 87 | Fault Contents 3 @ High Slip braking Overload | Modbus 400023 bit 10; not polled by default | Read | ||
| BI | 88 | CPF Contents 1 @ Base Block Circuit Error | Modbus 400024 bit 2; not polled by default | Read | ||
| BI | 89 | CPF Contents 1 @ EEPROM Error | Modbus 400024 bit 3; not polled by default | Read | ||
| BI | 90 | CPF Contents 1 @ CPU Internal A/D Converter Error | Modbus 400024 bit 4; not polled by default | Read | ||
| BI | 91 | CPF Contents 1 @ CPU External A/D Converter Error | Modbus 400024 bit 5; not polled by default | Read | ||
| BI | 92 | CPF Contents 1 @ Option Card Connection Error | Modbus 400024 bit 6; not polled by default | Read | ||
| BI | 93 | CPF Contents 2 @ Option Card A/D Converter Error | Modbus 400025 bit 0; not polled by default | Read | ||
| BI | 94 | CPF Contents 2 @ Option Card Self-Diagnostic error | Modbus 400025 bit 1; not polled by default | Read | ||
| BI | 95 | CPF Contents 2 @ Option Card Option Code Error | Modbus 400025 bit 2; not polled by default | Read | ||
| BI | 96 | CPF Contents 2 @ Option Card DP-RAM Error | Modbus 400025 bit 3; not polled by default | Read | ||
| BI | 97 | Minor Fault Contents 1 Undervoltage | Modbus 400026 bit 0; not polled by default | Read | ||
| BI | 98 | Minor Fault Contents 1 Overvoltage | Modbus 400026 bit 1; not polled by default | Read | ||
| BI | 99 | Minor Fault Contents 1 Inverter Overheat | Modbus 400026 bit 2; not polled by default | Read | ||
| BI | 100 | Minor Fault Contents 1 Inverter Overheat Warning | Modbus 400026 bit 3; not polled by default | Read | ||
| BI | 101 | Minor Fault Contents 1 Overtorque I | Modbus 400026 bit 4; not polled by default | Read | ||
| BI | 102 | Minor Fault Contents 1 Overtorque 2 | Modbus 400026 bit 5; not polled by default | Read | ||
| BI | 103 | Minor Fault Contents 1 2-wire Sequence Input Fault | Modbus 400026 bit 6; not polled by default | Read | ||
| BI | 104 | Minor Fault Contents 1 Baseblock | Modbus 400026 bit 7; not polled by default | Read | ||
| BI | 105 | Minor Fault Contents 1 External Fault 3 | Modbus 400026 bit 8; not polled by default | Read | ||
| BI | 106 | Minor Fault Contents 1 External Fault 4 | Modbus 400026 bit 9; not polled by default | Read | ||
| BI | 107 | Minor Fault Contents 1 External Fault 5 | Modbus 400026 bit 10; not polled by default | Read | ||
| BI | 108 | Minor Fault Contents 1 External Fault 6 | Modbus 400026 bit 11; not polled by default | Read | ||
| BI | 109 | Minor Fault Contents 1 External Fault 7 | Modbus 400026 bit 12; not polled by default | Read | ||
| BI | 110 | Minor Fault Contents 1 Overspeed | Modbus 400026 bit 15; not polled by default | Read | ||
| BI | 111 | Minor Fault Contents 2 Excessive Speed Bias | Modbus 400027 bit 0; not polled by default | Read | ||
| BI | 112 | Minor Fault Contents 2 PG Line Interruption | Modbus 400027 bit 1; not polled by default | Read | ||
| BI | 113 | Minor Fault Contents 2 Operator Bypass Fault | Modbus 400027 bit 2; not polled by default | Read | ||
| BI | 114 | Minor Fault Contents 2 Communications Fault | Modbus 400027 bit 3; not polled by default | Read | ||
| BI | 115 | Minor Fault Contents 2 Communications Option Fault | Modbus 400027 bit 4; not polled by default | Read | ||
| BI | 116 | Minor Fault Contents 2 Waiting for Communications | Modbus 400027 bit 5; not polled by default | Read | ||
| BI | 117 | Minor Fault Contents 2 Motor Overload | Modbus 400027 bit 6; not polled by default | Read | ||
| BI | 118 | Minor Fault Contents 2 Inverter Overload | Modbus 400027 bit 7; not polled by default | Read | ||
| BI | 119 | Minor Fault Contents 2 Sl-F/G Communication Fault | Modbus 400027 bit 8; not polled by default | Read | ||
| BI | 120 | Minor Fault Contents 2 SI-F/G Fault | Modbus 400027 bit 9; not polled by default | Read | ||
| BI | 121 | Minor Fault Contents 2 Motor Switch | Modbus 400027 bit 10; not polled by default | Read | ||
| BI | 122 | Minor Fault Contents 2 PID Feedback Error | Modbus 400027 bit 11; not polled by default | Read | ||
| BI | 123 | Minor Fault Contents 2 Waiting for Communications | Modbus 400027 bit 12; not polled by default | Read | ||
| BI | 124 | Minor Fault Contents 2 Undertorque 1 | Modbus 400027 bit 13; not polled by default | Read | ||
| BI | 125 | Minor Fault Contents 2 Undertorque 2 | Modbus 400027 bit 14; not polled by default | Read | ||
| BI | 126 | Minor Fault Contents 2 Communication Test Fault | Modbus 400027 bit 15; not polled by default | Read | ||
| BI | 127 | Minor Fault Contents 3 Motor Overheat Alarm | Modbus 400028 bit 0; not polled by default | Read | ||
| BI | 128 | Minor Fault Contents 3 E7 drive Not Enabled | Modbus 400028 bit 1; not polled by default | Read | ||
| BI | 129 | Fault Contents @ Overcurrent/Ground Fault | Modbus 400034 bit 0; not polled by default | Read | ||
| BI | 130 | Fault Contents @ Overvoltage | Modbus 400034 bit 1; not polled by default | Read | ||
| BI | 131 | Fault Contents @ Inverter Overload | Modbus 400034 bit 2; not polled by default | Read | ||
| BI | 132 | Fault Contents @ Overheat Fault | Modbus 400034 bit 3; not polled by default | Read | ||
| BI | 133 | Fault Contents @ Braking Resistor Fault | Modbus 400034 bit 4; not polled by default | Read | ||
| BI | 134 | Fault Contents @ Fuse Fault | Modbus 400034 bit 5; not polled by default | Read | ||
| BI | 135 | Fault Contents @ PID Feedback Fault | Modbus 400034 bit 6; not polled by default | Read | ||
| BI | 136 | Fault Contents @ External Fault | Modbus 400034 bit 7; not polled by default | Read | ||
| BI | 137 | Fault Contents @ Hardware Fault | Modbus 400034 bit 8; not polled by default | Read | ||
| BI | 138 | Fault Contents @ Overload/Overtorque | Modbus 400034 bit 9; not polled by default | Read | ||
| BI | 139 | Fault Contents @ Excessive Speed Deviation | Modbus 400034 bit 10; not polled by default | Read | ||
| BI | 140 | Fault Contents @ Undervoltage | Modbus 400034 bit 11; not polled by default | Read | ||
| BI | 141 | Fault Contents (UVl) or (UV2) or (UV3) or Power Off | Modbus 400034 bit 12; not polled by default | Read | ||
| BI | 142 | Fault Contents @ Input/Output Phase Fault | Modbus 400034 bit 13; not polled by default | Read | ||
| BI | 143 | Fault Contents @ Communications Error | Modbus 400034 bit 14; not polled by default | Read | ||
| BI | 144 | Fault Contents @ Operator Error | Modbus 400034 bit 15; not polled by default | Read | ||
| BI | 145 | Data Link Status @ Data Writing | Modbus 400035 bit 0; not polled by default | Read | ||
| BI | 146 | Data Link Status Data Limit Fault | Modbus 400035 bit 3; not polled by default | Read | ||
| BI | 147 | Data Link Status @ Data Compatibility fault | Modbus 400035 bit 4; not polled by default | Read | ||
| BI | 148 | Inverter Status RUN | Modbus 400033 bit 0 | Read | ||
| BI | 149 | Inverter Status Reverse | Modbus 400033 bit 1 | Read | ||
| BI | 150 | Inverter Status Inverter Ready | Modbus 400033 bit 2 | Read | ||
| BI | 151 | Inverter Status Fault | Modbus 400033 bit 3 | Read | ||
| BI | 152 | Inverter Status Data Setting Error | Modbus 400033 bit 4 | Read | ||
| BI | 153 | Inverter Status Multi-Function Output 1 | Modbus 400033 bit 5 | Read | ||
| BI | 154 | Inverter Status Multi-Function Output 2 | Modbus 400033 bit 6 | Read | ||
| BI | 155 | Inverter Status Multi-Function Output 3 | Modbus 400033 bit 7 | Read | ||
| AI | 156 | Frequency Reference | Modbus 400036 | Hz | Read | |
| AI | 157 | Output Frequency | Modbus 400037 | Hz | Read | |
| AI | 158 | Output Power | Modbus 400040 | Read | ||
| AI | 159 | Torque Command | Modbus 400041 | Read | ||
| BI | 160 | Sequence Input Status Terminal I Closed | Modbus 400044 bit 0; not polled by default | Read | ||
| BI | 161 | Sequence Input Status Terminal 2 Closed | Modbus 400044 bit 1; not polled by default | Read | ||
| BI | 162 | Sequence Input Status Terminal 3 Closed | Modbus 400044 bit 2; not polled by default | Read | ||
| BI | 163 | Sequence Input Status Terminal 4 Closed | Modbus 400044 bit 3; not polled by default | Read | ||
| BI | 164 | Sequence Input Status Terminal 5 Closed | Modbus 400044 bit 4; not polled by default | Read | ||
| BI | 165 | Sequence Input Status Terminal 6 Closed | Modbus 400044 bit 5; not polled by default | Read | ||
| BI | 166 | Sequence Input Status Terminal 7 Closed | Modbus 400044 bit 6; not polled by default | Read | ||
| BI | 167 | Inverter Status @RUN | Modbus 400045 bit 0 | Read | ||
| BI | 168 | Inverter Status Zero Speed | Modbus 400045 bit 1 | Read | ||
| BI | 169 | Inverter Status Speed Agree | Modbus 400045 bit 2 | Read | ||
| BI | 170 | Inverter Status Random Speed Agree | Modbus 400045 bit 3 | Read | ||
| BI | 171 | Inverter Status Frequency Detect 1 | Modbus 400045 bit 4 | Read | ||
| BI | 172 | Inverter Status Frequency Detect 2 | Modbus 400045 bit 5 | Read | ||
| BI | 173 | Inverter Status Inverter Ready | Modbus 400045 bit 6 | Read | ||
| BI | 174 | Inverter Status Undervoltage | Modbus 400045 bit 7 | Read | ||
| BI | 175 | Inverter Status Baseblock | Modbus 400045 bit 8 | Read | ||
| BI | 176 | Inverter Status Frequency Reference Not From Communications | Modbus 400045 bit 9 | Read | ||
| BI | 177 | Inverter Status Command Reference Not From Communications | Modbus 400045 bit 10 | Read | ||
| BI | 178 | Inverter Status Overtorque | Modbus 400045 bit 11 | Read | ||
| BI | 179 | Inverter Status Loss of Frequency reference | Modbus 400045 bit 12 | Read | ||
| BI | 180 | Inverter Status Fault Retry | Modbus 400045 bit 13 | Read | ||
| BI | 181 | Inverter Status Fault | Modbus 400045 bit 14 | Read | ||
| BI | 182 | Inverter Status Communications Timeout | Modbus 400045 bit 15; not polled by default | Read | ||
| BI | 183 | Multi-Function Output Status Multi-Function Output 1 | Modbus 400046 bit 0; not polled by default | Read | ||
| BI | 184 | Multi-Function Output Status Multi-Function Output 2 | Modbus 400046 bit 1; not polled by default | Read | ||
| BI | 185 | Multi-Function Output Status Multi-Function Output 3 | Modbus 400046 bit 2; not polled by default | Read | ||
| AI | 186 | Main Circuit DC Voltage | Modbus 400050; not polled by default | Read | ||
| AI | 187 | Torque | Modbus 400051; not polled by default | Read | ||
| AI | 188 | Output Power | Modbus 400052; not polled by default | Read | ||
| AI | 189 | PID Feedback Level | Modbus 400057; not polled by default | Read | ||
| AI | 190 | PID Input Level | Modbus 400058; not polled by default | Read | ||
| AI | 191 | PID Output Level | Modbus 400059; not polled by default | Read | ||
| AI | 192 | CPU | Modbus 400060; not polled by default | Read | ||
| AI | 193 | Flash ID | Modbus 400061; not polled by default | Read | ||
| BI | 194 | Communications Error CRC Error | Modbus 400062 bit 0; not polled by default | Read | ||
| BI | 195 | Communications Error Data Length Error | Modbus 400062 bit 1; not polled by default | Read | ||
| BI | 196 | Communications Error Parity Error | Modbus 400062 bit 3; not polled by default | Read | ||
| BI | 197 | Communications Error Overrun Error | Modbus 400062 bit 4; not polled by default | Read | ||
| BI | 198 | Communications Error Framing Error | Modbus 400062 bit 5; not polled by default | Read | ||
| BI | 199 | Communications Error Timeout | Modbus 400062 bit 6; not polled by default | Read | ||
| AI | 200 | kVA Setting | Modbus 400063 | Read | ||
| AI | 201 | Frequency Reference | Modbus 400065 | Hz | Read | |
| AImin | 202 | Output Frequency | Modbus 400066 | Hz | Read | |
| AImin | 203 | Output Current | Modbus 400067 | A | Read | |
| AI | 204 | Output Voltage | Modbus 400070 | V | Read | |
| AI | 205 | DC Bus Voltage | Modbus 400071 | V | Read | |
| AImin | 206 | Output Power | Modbus 400072 | kW | Read | |
| BI | 207 | Input Terminal Status Fwd Run (Terminal S1) | Modbus 400074 bit 0; not polled by default | Read | ||
| BI | 208 | Input Terminal Status Rev Run (Terminal S2) | Modbus 400074 bit 1; not polled by default | Read | ||
| BI | 209 | Input Terminal Status Terminal S3 | Modbus 400074 bit 2; not polled by default | Read | ||
| BI | 210 | Input Terminal Status Terminal S4 | Modbus 400074 bit 3; not polled by default | Read | ||
| BI | 211 | Input Terminal Status Terminal S5 | Modbus 400074 bit 4; not polled by default | Read | ||
| BI | 212 | Input Terminal Status Terminal S6 | Modbus 400074 bit 5; not polled by default | Read | ||
| BI | 213 | Input Terminal Status Terminal S7 | Modbus 400074 bit 6; not polled by default | Read | ||
| BI | 214 | Output Terminal Status Multi-function Output 1 | Modbus 400075 bit 0; not polled by default | Read | ||
| BI | 215 | Output Terminal Status Multi-function Output 2 | Modbus 400075 bit 1; not polled by default | Read | ||
| BI | 216 | Output Terminal Status Multi-function Output 3 | Modbus 400075 bit 2; not polled by default | Read | ||
| BI | 217 | Output Terminal Status Fault Output | Modbus 400075 bit 7; not polled by default | Read | ||
| BI | 218 | E7 drive Operation Status FWD RUN | Modbus 400076 bit 0 | Read | ||
| BI | 219 | E7 drive Operation Status Zero Speed | Modbus 400076 bit 1 | Read | ||
| BI | 220 | E7 drive Operation Status REV RUN | Modbus 400076 bit 2 | Read | ||
| BI | 221 | E7 drive Operation Status Reset | Modbus 400076 bit 3 | Read | ||
| BI | 222 | E7 drive Operation Status Speed Agree | Modbus 400076 bit 4 | Read | ||
| BI | 223 | E7 drive Operation Status E7 drive Ready | Modbus 400076 bit 5 | Read | ||
| BI | 224 | E7 drive Operation Status Minor Fault | Modbus 400076 bit 6 | Read | ||
| BI | 225 | E7 drive Operation Status Major Fault | Modbus 400076 bit 7 | Read | ||
| AI | 226 | Elapsed Time | Modbus 400077; not polled by default | h | Read | |
| AI | 227 | Flash ID | Modbus 400078; not polled by default | Read | ||
| AI | 228 | Terminal A1 Input Voltage | Modbus 400079; not polled by default | % | Read | |
| AI | 229 | Terminal A2 Input Voltage | Modbus 400080; not polled by default | % | Read | |
| AI | 230 | Motor Secondary Current (Iq) | Modbus 400082; not polled by default | % | Read | |
| AI | 231 | Output Frequency After Soft Start | Modbus 400084; not polled by default | Hz | Read | |
| AI | 232 | PID Feedback Value | Modbus 400088; not polled by default | % | Read | |
| AI | 233 | CPU Number | Modbus 400092; not polled by default | Read | ||
| AI | 234 | kWh | Modbus 400093; not polled by default | kWh | Read | |
| AI | 235 | MWh | Modbus 400094; not polled by default | MWh | Read | |
| AI | 236 | First Parameter Causing an OPE Fault | Modbus 400098; not polled by default | Read | ||
| AI | 237 | PID Input | Modbus 400100; not polled by default | % | Read | |
| AI | 238 | PID Output | Modbus 400101; not polled by default | % | Read | |
| AI | 239 | PID Setpoint | Modbus 400102; not polled by default | % | Read | |
| BI | 240 | Communication Error Code CRC Error | Modbus 400103 bit 0; not polled by default | Read | ||
| BI | 241 | Communication Error Code Data Length Error | Modbus 400103 bit 1; not polled by default | Read | ||
| BI | 242 | Communication Error Code Parity Error | Modbus 400103 bit 3; not polled by default | Read | ||
| BI | 243 | Communication Error Code Over-run Error | Modbus 400103 bit 4; not polled by default | Read | ||
| BI | 244 | Communication Error Code Framing Error | Modbus 400103 bit 5; not polled by default | Read | ||
| BI | 245 | Communication Error Code Timeout Error | Modbus 400103 bit 6; not polled by default | Read | ||
| AI | 246 | FAN Elapsed Time | Modbus 400104; not polled by default | Read | ||
| AI | 247 | Actual Fin Temp | Modbus 400105; not polled by default | °C | Read | |
| AI | 248 | AUTO Mode Fref | Modbus 400115; not polled by default | % | Read | |
| AI | 249 | HAND Mode Fref | Modbus 400116; not polled by default | % | Read | |
| AI | 250 | PI Feedback 2 | Modbus 400117; not polled by default | % | Read | |
| AI | 251 | Current Fault | Modbus 400129; not polled by default | Read | ||
| AI | 252 | Previous Fault | Modbus 400130; not polled by default | Read | ||
| AI | 253 | Frequency Reference @ Previous Fault | Modbus 400131; not polled by default | Hz | Read | |
| AI | 254 | Output Frequency @ Previous Fault | Modbus 400132; not polled by default | Hz | Read | |
| AI | 255 | Output Current @ Previous Fault | Modbus 400133; not polled by default | A | Read | |
| AI | 256 | Output Voltage @t Previous Fault | Modbus 400135; not polled by default | V | Read | |
| AI | 257 | DC Bus Voltage @ Previous Fault | Modbus 400136; not polled by default | V | Read | |
| AI | 258 | Output Power @ Previous Fault | Modbus 400137; not polled by default | kW | Read | |
| AI | 259 | Torque Reference @ Previous Fault | Modbus 400138; not polled by default | % | Read | |
| AI | 260 | Input Terminal Status @ Previous Fault | Modbus 400139; not polled by default | Read | ||
| AI | 261 | Output Terminal Status @ Previous Fault | Modbus 400140; not polled by default | Read | ||
| AI | 262 | E7 drive Operation Status @ Previous Fault | Modbus 400141; not polled by default | Read | ||
| AI | 263 | Elapsed Time @ Previous Fault | Modbus 400142; not polled by default | h | Read | |
| AI | 264 | Most Recent Fault | Modbus 402049; not polled by default | Read | ||
| AI | 265 | 2nd Most Recent Fault | Modbus 402050; not polled by default | Read | ||
| AI | 266 | 3rd Most Recent Fault | Modbus 402051; not polled by default | Read | ||
| AI | 267 | 4th Most Recent Fault | Modbus 402052; not polled by default | Read | ||
| AI | 268 | Elapsed Time @ Most Recent Fault | Modbus 402059; not polled by default | h | Read | |
| AI | 269 | Elapsed Time @ 2nd Most Recent Fault | Modbus 402060; not polled by default | h | Read | |
| AI | 270 | Elapsed Time @ 3rd Most Recent Fault | Modbus 402061; not polled by default | h | Read | |
| AI | 271 | Elapsed Time @ 4th Most Recent Fault | Modbus 402062; not polled by default | h | Read | |
| AI | 272 | 5th Most Recent Fault | Modbus 402053; not polled by default | Read | ||
| AI | 273 | 6th Most Recent Fault | Modbus 402054; not polled by default | Read | ||
| AI | 274 | 7th Most Recent Fault | Modbus 402055; not polled by default | Read | ||
| AI | 275 | 8th Most Recent Fault | Modbus 402056; not polled by default | Read | ||
| AI | 276 | 9th Most Recent Fault | Modbus 402057; not polled by default | Read | ||
| AI | 277 | 10th Most Recent Fault | Modbus 402058; not polled by default | Read | ||
| AI | 278 | Elapsed Time @ 5th Most Recent Fault | Modbus 402063; not polled by default | h | Read | |
| AI | 279 | Elapsed Time @ 6th Most Recent Fault | Modbus 402064; not polled by default | h | Read | |
| AI | 280 | Elapsed Time @ 7th Most Recent Fault | Modbus 402065; not polled by default | h | Read | |
| AI | 281 | Elapsed Time @ 8th Most Recent Fault | Modbus 402066; not polled by default | h | Read | |
| AI | 282 | Elapsed Time @ 9th Most Recent Fault | Modbus 402067; not polled by default | h | Read | |
| AI | 283 | Elapsed Time @ 10th Most Recent Fault | Modbus 402068; not polled by default | h | Read | |
| AO | 284 | Select Language | Modbus 400257; not polled by default | Command | ||
| AO | 285 | Access Level | Modbus 400258; not polled by default | Command | ||
| AO | 286 | Init Parameters | Modbus 400260; not polled by default | Command | ||
| AO | 287 | Enter Password | Modbus 400261; not polled by default | Command | ||
| AO | 288 | User Param 1 | Modbus 400263; not polled by default | Command | ||
| AO | 289 | User Param 2 | Modbus 400264; not polled by default | Command | ||
| AO | 290 | User Param 3 | Modbus 400265; not polled by default | Command | ||
| AO | 291 | User Param 4 | Modbus 400266; not polled by default | Command | ||
| AO | 292 | User Param 5 | Modbus 400267; not polled by default | Command | ||
| AO | 293 | User Param 6 | Modbus 400268; not polled by default | Command | ||
| AO | 294 | User Param 7 | Modbus 400269; not polled by default | Command | ||
| AO | 295 | User Param 8 | Modbus 400270; not polled by default | Command | ||
| AO | 296 | User Param 9 | Modbus 400271; not polled by default | Command | ||
| AO | 297 | User Param 10 | Modbus 400272; not polled by default | Command | ||
| AO | 298 | User Param 11 | Modbus 400273; not polled by default | Command | ||
| AO | 299 | User Param 12 | Modbus 400274; not polled by default | Command | ||
| AO | 300 | User Param 13 | Modbus 400275; not polled by default | Command | ||
| AO | 301 | User Param 14 | Modbus 400276; not polled by default | Command | ||
| AO | 302 | User Param 15 | Modbus 400277; not polled by default | Command | ||
| AO | 303 | User Param 16 | Modbus 400278; not polled by default | Command | ||
| AO | 304 | User Param 17 | Modbus 400279; not polled by default | Command | ||
| AO | 305 | User Param 18 | Modbus 400280; not polled by default | Command | ||
| AO | 306 | User Param 19 | Modbus 400281; not polled by default | Command | ||
| AO | 307 | User Param 20 | Modbus 400282; not polled by default | Command | ||
| AO | 308 | User Param 21 | Modbus 400283; not polled by default | Command | ||
| AO | 309 | User Param 22 | Modbus 400284; not polled by default | Command | ||
| AO | 310 | User Param 23 | Modbus 400285; not polled by default | Command | ||
| AO | 311 | User Param 24 | Modbus 400286; not polled by default | Command | ||
| AO | 312 | User Param 25 | Modbus 400287; not polled by default | Command | ||
| AO | 313 | User Param 26 | Modbus 400288; not polled by default | Command | ||
| AO | 314 | User Param 27 | Modbus 400289; not polled by default | Command | ||
| AO | 315 | User Param 28 | Modbus 400290; not polled by default | Command | ||
| AO | 316 | User Param 29 | Modbus 400291; not polled by default | Command | ||
| AO | 317 | User Param 30 | Modbus 400292; not polled by default | Command | ||
| AO | 318 | User Param 31 | Modbus 400293; not polled by default | Command | ||
| AO | 319 | User Param 32 | Modbus 400294; not polled by default | Command | ||
| AO | 320 | Reference Source | Modbus 400385; not polled by default | Command | ||
| AO | 321 | Run Source | Modbus 400386; not polled by default | Command | ||
| AO | 322 | Stopping Method | Modbus 400387; not polled by default | Command | ||
| AO | 323 | Reverse Oper | Modbus 400388; not polled by default | Command | ||
| AO | 324 | LOC/REM RUN Sel | Modbus 400390; not polled by default | Command | ||
| AO | 325 | RUN CMD at PRG | Modbus 400391; not polled by default | Command | ||
| AO | 326 | L/R Select@Drive | Modbus 400392; not polled by default | Command | ||
| AO | 327 | Wait to Run Time | Modbus 400480; not polled by default | s | Command | |
| AO | 328 | HAND Fref Source | Modbus 400481; not polled by default | Command | ||
| AO | 329 | DCInj Start Freq | Modbus 400394; not polled by default | Hz | Command | |
| AO | 330 | DCInj Current | Modbus 400395; not polled by default | % | Command | |
| AO | 331 | DCInj Time@Start | Modbus 400396; not polled by default | s | Command | |
| AO | 332 | DCInj Time@Stop | Modbus 400397; not polled by default | s | Command | |
| AO | 333 | DCInj P Gain | Modbus 400398; not polled by default | Command | ||
| AO | 334 | DCInj Intgl Time | Modbus 400399; not polled by default | ms | Command | |
| AO | 335 | DCInj Limit | Modbus 400400; not polled by default | % | Command | |
| AO | 336 | Preheat Current | Modbus 400482; not polled by default | % | Command | |
| AO | 337 | SpdSrch at Start | Modbus 400402; not polled by default | Command | ||
| AO | 338 | SpdSrch Current | Modbus 400403; not polled by default | % | Command | |
| AO | 339 | SpdSrch Dec Time | Modbus 400404; not polled by default | s | Command | |
| AO | 340 | SpdSrch V/F | Modbus 400405; not polled by default | % | Command | |
| AO | 341 | Search Delay | Modbus 400406; not polled by default | s | Command | |
| AO | 342 | Srch Im Lvl I | Modbus 400407; not polled by default | Command | ||
| AO | 343 | Srch Im Lvl2 | Modbus 400408; not polled by default | Command | ||
| AO | 344 | Srch ACR P Gain | Modbus 400409; not polled by default | Command | ||
| AO | 345 | Srch ACR I Time | Modbus 400410; not polled by default | ms | Command | |
| AO | 346 | Srch Detect Comp | Modbus 400411; not polled by default | Command | ||
| AO | 347 | Srch Mthd Sw Lvl | Modbus 400412; not polled by default | Command | ||
| AO | 348 | Srch I Deadband | Modbus 400413; not polled by default | Command | ||
| AO | 349 | Bidir Search Sel | Modbus 400415; not polled by default | Command | ||
| AO | 350 | Delay-ON Timer | Modbus 400420; not polled by default | s | Command | |
| AO | 351 | Delay-OFF Timer | Modbus 400421; not polled by default | s | Command | |
| AO | 352 | PI Mode | Modbus 400422; not polled by default | Command | ||
| AO | 353 | P Gain | Modbus 400423; not polled by default | Command | ||
| AO | 354 | PI I Time | Modbus 400424; not polled by default | s | Command | |
| AO | 355 | PI I Limit | Modbus 400425; not polled by default | % | Command | |
| AO | 356 | PI Limit | Modbus 400427; not polled by default | % | Command | |
| AO | 357 | PI Offset | Modbus 400428; not polled by default | % | Command | |
| AO | 358 | PI Delay Time | Modbus 400429; not polled by default | s | Command | |
| AO | 359 | Output Level Sel | Modbus 400430; not polled by default | Command | ||
| AO | 360 | Output Gain | Modbus 400431; not polled by default | Command | ||
| AO | 361 | Output Rev Sel | Modbus 400432; not polled by default | Command | ||
| AO | 362 | Fb los Det Sel | Modbus 400433; not polled by default | Command | ||
| AO | 363 | Fb los Det Lvl | Modbus 400434; not polled by default | % | Command | |
| AO | 364 | Fb los Det Time | Modbus 400435; not polled by default | s | Command | |
| AO | 365 | Sleep Level | Modbus 400436; not polled by default | Hz | Command | |
| AO | 366 | Sleep Time | Modbus 400437; not polled by default | s | Command | |
| AO | 367 | Acc/Dec Time | Modbus 400438; not polled by default | s | Command | |
| AO | 368 | PI Setpoint Sel | Modbus 400477; not polled by default | Command | ||
| AO | 369 | PI Setpoint | Modbus 400478; not polled by default | % | Command | |
| AO | 370 | Setpoint Scaling | Modbus 400483; not polled by default | Command | ||
| AO | 371 | PI Sleep Source | Modbus 400484; not polled by default | Command | ||
| AO | 372 | Snooze Level | Modbus 400485; not polled by default | % | Command | |
| AO | 373 | Snooze DelayTime | Modbus 400486; not polled by default | s | Command | |
| AO | 374 | Wake-Up Level | Modbus 400487; not polled by default | % | Command | |
| AO | 375 | Setpoint Boost | Modbus 400488; not polled by default | % | Command | |
| AO | 376 | Max Boost Time | Modbus 400489; not polled by default | s | Command | |
| AO | 377 | Snooze Feedback | Modbus 400490; not polled by default | % | Command | |
| AO | 378 | PI Feedback SqRt | Modbus 400491; not polled by default | Command | ||
| AO | 379 | PI Fb SqRt Gain | Modbus 400492; not polled by default | Command | ||
| AO | 380 | PI Out Moni SqRt | Modbus 400493; not polled by default | Command | ||
| AO | 381 | Energy Save Sel | Modbus 400461; not polled by default | Command | ||
| AO | 382 | Energy Save COEF | Modbus 400464; not polled by default | Command | ||
| AO | 383 | kW Filter Time | Modbus 400465; not polled by default | ms | Command | |
| AO | 384 | Search V Limit | Modbus 400466; not polled by default | % | Command | |
| AO | 385 | E-Sav V Low Liml | Modbus 400467; not polled by default | % | Command | |
| AO | 386 | E-Sav V Low Lim2 | Modbus 400468; not polled by default | % | Command | |
| AO | 387 | E-Sav V Up Liml | Modbus 400469; not polled by default | % | Command | |
| AO | 388 | E-Sav V Up Lim2 | Modbus 400470; not polled by default | % | Command | |
| AO | 389 | Srch V Step 100% | Modbus 400471; not polled by default | % | Command | |
| AO | 390 | Srch V Step 5% | Modbus 400472; not polled by default | % | Command | |
| AO | 391 | Srch V Avg Time | Modbus 400473; not polled by default | ms | Command | |
| AO | 392 | Srch kW Hold Wth | Modbus 400474; not polled by default | % | Command | |
| AO | 393 | Accel Time I | Modbus 400513; not polled by default | s | Command | |
| AO | 394 | Decel Time I | Modbus 400514; not polled by default | s | Command | |
| AO | 395 | Accel Time 2 | Modbus 400515; not polled by default | s | Command | |
| AO | 396 | Decel Time 2 | Modbus 400516; not polled by default | s | Command | |
| AO | 397 | Fast Stop Time | Modbus 400521; not polled by default | s | Command | |
| AO | 398 | Acc/Dec SW Freq | Modbus 400523; not polled by default | Hz | Command | |
| AO | 399 | SCrv Acc @ Start | Modbus 400524; not polled by default | s | Command | |
| AO | 400 | SCrv Acc @ End | Modbus 400525; not polled by default | s | Command | |
| AO | 401 | Torq Comp Gain | Modbus 400534; not polled by default | Command | ||
| AO | 402 | Torq Comp Time | Modbus 400535; not polled by default | ms | Command | |
| AO | 403 | Normal Duty Sel | Modbus 400548; not polled by default | Command | ||
| AO | 404 | CarrierFreq Sel | Modbus 400549; not polled by default | Command | ||
| AO | 405 | CarrierFreq Max | Modbus 400550; not polled by default | kHz | Command | |
| AO | 406 | CarrierFreq Min | Modbus 400551; not polled by default | Command | ||
| AO | 407 | CarrierFreq Gain | Modbus 400552; not polled by default | Command | ||
| AO | 408 | PWM Method | Modbus 400553; not polled by default | Command | ||
| AO | 409 | Phase SW level | Modbus 400554; not polled by default | Command | ||
| AO | 410 | PWM on Time | Modbus 400555; not polled by default | Command | ||
| AO | 411 | Reference 1 | Modbus 400641; not polled by default | Hz | Command | |
| AO | 412 | Reference 2 | Modbus 400642; not polled by default | Hz | Command | |
| AO | 413 | Reference 3 | Modbus 400643; not polled by default | Hz | Command | |
| AO | 414 | Reference 4 | Modbus 400644; not polled by default | Hz | Command | |
| AO | 415 | Jog Reference | Modbus 400659; not polled by default | Hz | Command | |
| AO | 416 | Ref Upper Limit | Modbus 400650; not polled by default | % | Command | |
| AO | 417 | Ref Lower Limit | Modbus 400651; not polled by default | % | Command | |
| AO | 418 | Ref1 Lower Limit | Modbus 400660; not polled by default | % | Command | |
| AO | 419 | Jump Freq 1 | Modbus 400661; not polled by default | Hz | Command | |
| AO | 420 | Jump Freq 2 | Modbus 400662; not polled by default | Hz | Command | |
| AO | 421 | Jump Freq 3 | Modbus 400663; not polled by default | Hz | Command | |
| AO | 422 | Jump Bandwidth | Modbus 400664; not polled by default | Hz | Command | |
| AO | 423 | MOP Ref Memory | Modbus 400665; not polled by default | Command | ||
| AO | 424 | Trim Control Lvl | Modbus 400666; not polled by default | Command | ||
| AO | 425 | Input Voltage | Modbus 400769; not polled by default | V | Command | |
| AO | 426 | V/F Selection | Modbus 400771; not polled by default | Command | ||
| AO | 427 | Max Frequency | Modbus 400772; not polled by default | Hz | Command | |
| AO | 428 | Max Voltage | Modbus 400773; not polled by default | V | Command | |
| AO | 429 | Base Frequency | Modbus 400774; not polled by default | Hz | Command | |
| AO | 430 | Mid Frequency A | Modbus 400775; not polled by default | Hz | Command | |
| AO | 431 | Mid Vohage A | Modbus 400776; not polled by default | V | Command | |
| AO | 432 | Min Frequency | Modbus 400777; not polled by default | Hz | Command | |
| AO | 433 | Min Vohage | Modbus 400778; not polled by default | V | Command | |
| AO | 434 | Mid Frequency B | Modbus 400779; not polled by default | Hz | Command | |
| AO | 435 | Mid Voltage B | Modbus 400780; not polled by default | V | Command | |
| AO | 436 | Base Vohage | Modbus 400781; not polled by default | V | Command | |
| AO | 437 | Motor Rated FLA | Modbus 400783; not polled by default | A | Command | |
| AO | 438 | Motor Rated Slip | Modbus 400784; not polled by default | Hz | Command | |
| AO | 439 | No-Load Current | Modbus 400785; not polled by default | A | Command | |
| AO | 440 | Term Resistance | Modbus 400787; not polled by default | Ω | Command | |
| AO | 441 | Tcomp Iron Loss | Modbus 400792; not polled by default | W | Command | |
| AO | 442 | Mtr Rated Power | Modbus 400793; not polled by default | kW | Command | |
| AO | 443 | Comm Bus Fit Sel | Modbus 400931; not polled by default | Command | ||
| AO | 444 | EFO Detection | Modbus 400932; not polled by default | Command | ||
| AO | 445 | EFO Fault Action | Modbus 400933; not polled by default | Command | ||
| AO | 446 | Not Labeled | Modbus 400935; not polled by default | Command | ||
| AO | 447 | Terminal S3 Sel | Modbus 401025; not polled by default | Command | ||
| AO | 448 | Terminal S4 Sel | Modbus 401026; not polled by default | Command | ||
| AO | 449 | Terminal S5 Sel | Modbus 401027; not polled by default | Command | ||
| AO | 450 | Terminal S6 Sel | Modbus 401028; not polled by default | Command | ||
| AO | 451 | Terminal S7 Sel | Modbus 401029; not polled by default | Command | ||
| AO | 452 | TermMl-M2 Sel | Modbus 401036; not polled by default | Command | ||
| AO | 453 | Term M3-M4 Sel | Modbus 401037; not polled by default | Command | ||
| AO | 454 | Terminal A1 Gain | Modbus 401042; not polled by default | % | Command | |
| AO | 455 | Terminal A1 Bias | Modbus 401043; not polled by default | % | Command | |
| AO | 456 | Term A2 Signal | Modbus 401048; not polled by default | Command | ||
| AO | 457 | Terminal A2 Sel | Modbus 401049; not polled by default | Command | ||
| AO | 458 | Terminal A2 Gain | Modbus 401050; not polled by default | % | Command | |
| AO | 459 | Terminal A2 Bias | Modbus 401051; not polled by default | % | Command | |
| AO | 460 | Filter Avg Time | Modbus 401052; not polled by default | s | Command | |
| AO | 461 | TA1/A2 Select | Modbus 401053; not polled by default | Command | ||
| AO | 462 | Terminal FM Sel | Modbus 401054; not polled by default | Command | ||
| AO | 463 | Terminal FM Gain | Modbus 401055; not polled by default | % | Command | |
| AO | 464 | Terminal FM Bias | Modbus 401056; not polled by default | % | Command | |
| AO | 465 | Terminal AM Sel | Modbus 401057; not polled by default | Command | ||
| AO | 466 | Terminal AM Gain | Modbus 401058; not polled by default | % | Command | |
| AO | 467 | Terminal AM Bias | Modbus 401059; not polled by default | % | Command | |
| AO | 468 | AO Level Selectl | Modbus 401060; not polled by default | Command | ||
| AO | 469 | AO Level Select2 | Modbus 401061; not polled by default | Command | ||
| AO | 470 | Serial Comm Adr | Modbus 401062; not polled by default | Command | ||
| AO | 471 | Serial Baud Rate | Modbus 401063; not polled by default | Command | ||
| AO | 472 | Serial Com Sel | Modbus 401064; not polled by default | Command | ||
| AO | 473 | Serial Fault Sel | Modbus 401065; not polled by default | Command | ||
| AO | 474 | Serial Fit Dtct | Modbus 401066; not polled by default | Command | ||
| AO | 475 | Transmit WaitTIM | Modbus 401067; not polled by default | ms | Command | |
| AO | 476 | RTS Control Sel | Modbus 401068; not polled by default | Command | ||
| AO | 477 | Protocol Select | Modbus 401077; not polled by default | Command | ||
| AO | 478 | CE Detect Time | Modbus 401078; not polled by default | s | Command | |
| AO | 479 | MOL Fault Select | Modbus 401153; not polled by default | Command | ||
| AO | 480 | MOL Time Const | Modbus 401154; not polled by default | min | Command | |
| AO | 481 | Mtr OH Alarm Sel | Modbus 401155; not polled by default | Command | ||
| AO | 482 | Mtr OH Fault Sel | Modbus 401156; not polled by default | Command | ||
| AO | 483 | Mtr Temp Filter | Modbus 401157; not polled by default | s | Command | |
| AO | 484 | PwrL Selection | Modbus 401158; not polled by default | Command | ||
| AO | 485 | PwrL Ridethru t | Modbus 401159; not polled by default | s | Command | |
| AO | 486 | PwrL Baseblock t | Modbus 401160; not polled by default | s | Command | |
| AO | 487 | PwrL V/F Ramp t | Modbus 401161; not polled by default | s | Command | |
| AO | 488 | PUV Det Level | Modbus 401162; not polled by default | V | Command | |
| AO | 489 | StallP Accel Sel | Modbus 401168; not polled by default | Command | ||
| AO | 490 | StallP Accel Lvl | Modbus 401169; not polled by default | % | Command | |
| AO | 491 | StallP CHP Lvl | Modbus 401170; not polled by default | % | Command | |
| AO | 492 | StallP Decel Sel | Modbus 401171; not polled by default | Command | ||
| AO | 493 | StallP Run Sel | Modbus 401172; not polled by default | Command | ||
| AO | 494 | StallP Run Level | Modbus 401173; not polled by default | % | Command | |
| AO | 495 | StallP Gain | Modbus 401174; not polled by default | Command | ||
| AO | 496 | StallP Intg Time | Modbus 401175; not polled by default | ms | Command | |
| AO | 497 | Decel Time Coef | Modbus 401176; not polled by default | Command | ||
| AO | 498 | StallP Decel Lvl | Modbus 401177; not polled by default | % | Command | |
| AO | 499 | Spd Agree Level | Modbus 401178; not polled by default | Hz | Command | |
| AO | 500 | Spd Agree Width | Modbus 401179; not polled by default | Hz | Command | |
| AO | 501 | RefLoss Sel | Modbus 401182; not polled by default | Command | ||
| AO | 502 | Fref at Floss | Modbus 401219; not polled by default | % | Command | |
| AO | 503 | Num of Restarts | Modbus 401183; not polled by default | Command | ||
| AO | 504 | Restart Sel | Modbus 401184; not polled by default | Command | ||
| AO | 505 | Max Restart Time | Modbus 401185; not polled by default | s | Command | |
| AO | 506 | Restart Mode Sel | Modbus 401220; not polled by default | Command | ||
| AO | 507 | Torq Det 1 Sel | Modbus 401186; not polled by default | Command | ||
| AO | 508 | Torq Det 1 Lvl | Modbus 401187; not polled by default | % | Command | |
| AO | 509 | Torq Det 1 Time | Modbus 401188; not polled by default | s | Command | |
| AO | 510 | DB Resistor Prot | Modbus 401198; not polled by default | Command | ||
| AO | 511 | OH Pre-Alarm Lvl | Modbus 401199; not polled by default | °C | Command | |
| AO | 512 | OH Pre-Alarm Sel | Modbus 401200; not polled by default | Command | ||
| AO | 513 | OK1 Fault Level | Modbus 401201; not polled by default | °C | Command | |
| AO | 514 | Ph Loss In Sel | Modbus 401202; not polled by default | Command | ||
| AO | 515 | Ph Loss In Lvl | Modbus 401203; not polled by default | % | Command | |
| AO | 516 | Ph Loss Out Sel | Modbus 401204; not polled by default | Command | ||
| AO | 517 | Ph Loss Out Lvl | Modbus 401205; not polled by default | % | Command | |
| AO | 518 | Ground Fault Sel | Modbus 401206; not polled by default | Command | ||
| AO | 519 | Fan On/Off Sel | Modbus 401207; not polled by default | Command | ||
| AO | 520 | Fan Delay Time | Modbus 401208; not polled by default | Command | ||
| AO | 521 | Ambient Temp | Modbus 401209; not polled by default | °C | Command | |
| AO | 522 | UV3 Detect | Modbus 401210; not polled by default | Command | ||
| AO | 523 | Inverter OL Sel | Modbus 401211; not polled by default | Command | ||
| AO | 524 | 0L2 Sel @ L-Spd | Modbus 401212; not polled by default | Command | ||
| AO | 525 | Low Spd 0L2 Freq | Modbus 401213; not polled by default | Command | ||
| AO | 526 | 0L2 OHz Gain | Modbus 401214; not polled by default | Command | ||
| AO | 527 | Soft CLA Sel | Modbus 401215; not polled by default | Command | ||
| AO | 528 | Fref During OH | Modbus 401216; not polled by default | % | Command | |
| AO | 529 | Hunt Prev Select | Modbus 401409; not polled by default | Command | ||
| AO | 530 | Hunt Prev Gain | Modbus 401410; not polled by default | Command | ||
| AO | 531 | Hunt Prev Time | Modbus 401411; not polled by default | ms | Command | |
| AO | 532 | Hunt Prev Limit | Modbus 401412; not polled by default | % | Command | |
| AO | 533 | HSB Decel Width | Modbus 401417; not polled by default | % | Command | |
| AO | 534 | HSB Current Ref | Modbus 401418; not polled by default | % | Command | |
| AO | 535 | HSB DwelTim@Stp | Modbus 401419; not polled by default | s | Command | |
| AO | 536 | HSB OL Time | Modbus 401420; not polled by default | s | Command | |
| AO | 537 | HSB V/F Gain | Modbus 401421; not polled by default | % | Command | |
| AO | 538 | Spd Agr Current | Modbus 401422; not polled by default | % | Command | |
| AO | 539 | Spd Agree Time | Modbus 401423; not polled by default | ms | Command | |
| AO | 540 | HSB V Lvl 1 | Modbus 401424; not polled by default | % | Command | |
| AO | 541 | HSB V Lvl2 | Modbus 401425; not polled by default | % | Command | |
| AO | 542 | HSB RI Comp Coef | Modbus 401426; not polled by default | % | Command | |
| AO | 543 | HSB RI Comp Tim | Modbus 401427; not polled by default | ms | Command | |
| AO | 544 | Prohib HSB Decel | Modbus 401428; not polled by default | Hz | Command | |
| AO | 545 | Inv Rate Current | Modbus 401489; not polled by default | A | Command | |
| AO | 546 | DCCT Gain | Modbus 401490; not polled by default | Command | ||
| AO | 547 | AVR Selection | Modbus 401487; not polled by default | Command | ||
| AO | 548 | AVR Time | Modbus 401488; not polled by default | ms | Command | |
| AO | 549 | ON-Delay Time | Modbus 401499; not polled by default | Command | ||
| AO | 550 | ON-Delay Comp | Modbus 401500; not polled by default | Command | ||
| AO | 551 | IGBT Volt Drop | Modbus 401501; not polled by default | V | Command | |
| AO | 552 | Pwr Angle Filt 1 | Modbus 401502; not polled by default | ms | Command | |
| AO | 553 | Pwr Angle Filt 2 | Modbus 401503; not polled by default | ms | Command | |
| AO | 554 | DCCT Filter Time | Modbus 401507; not polled by default | Command | ||
| AO | 555 | Soft CLA Gain | Modbus 401508; not polled by default | Command | ||
| AO | 556 | Soft CLA Filter | Modbus 401509; not polled by default | ms | Command | |
| AO | 557 | Soft CLA Level 1 | Modbus 401510; not polled by default | % | Command | |
| AO | 558 | Soft CLA Level2 | Modbus 401511; not polled by default | % | Command | |
| AO | 559 | Soft CLA SW Freq | Modbus 401512; not polled by default | Hz | Command | |
| AO | 560 | Soft CLA Level3 | Modbus 401513; not polled by default | % | Command | |
| AO | 561 | OnDelay Comp Lvl | Modbus 401514; not polled by default | % | Command | |
| AO | 562 | IGBT Gain | Modbus 401515; not polled by default | Command | ||
| AO | 563 | Aging Test Mode | Modbus 401516; not polled by default | Command | ||
| AO | 564 | User Monitor Sel | Modbus 401281; not polled by default | Command | ||
| AO | 565 | Power-On Monitor | Modbus 401282; not polled by default | Command | ||
| AO | 566 | Display Scaling | Modbus 401283; not polled by default | Command | ||
| AO | 567 | LCD Contrast | Modbus 401285; not polled by default | Command | ||
| AO | 568 | Monitor Mode Sel | Modbus 401304; not polled by default | Command | ||
| AO | 569 | 2nd Monitor Sel | Modbus 401305; not polled by default | Command | ||
| AO | 570 | 3rd Monitor Sel | Modbus 401306; not polled by default | Command | ||
| AO | 571 | Local/Remote Key | Modbus 401286; not polled by default | Command | ||
| AO | 572 | Oper STOP Key | Modbus 401287; not polled by default | Command | ||
| AO | 573 | User Defaults | Modbus 401288; not polled by default | Command | ||
| AO | 574 | Inverter Model # | Modbus 401289; not polled by default | Command | ||
| AO | 575 | Operator M.O.P. | Modbus 401290; not polled by default | Command | ||
| AO | 576 | Oper Detection | Modbus 401291; not polled by default | Command | ||
| AO | 577 | Elapsed Time Set | Modbus 401292; not polled by default | Command | ||
| AO | 578 | Elapsed Time Run | Modbus 401293; not polled by default | Command | ||
| AO | 579 | Init Mode Sel | Modbus 401294; not polled by default | Command | ||
| AO | 580 | Fan ON Time Set | Modbus 401295; not polled by default | Command | ||
| AO | 581 | FLT Trace Init | Modbus 401297; not polled by default | Command | ||
| AO | 582 | PUF Cont det Sel | Modbus 401298; not polled by default | Command | ||
| AO | 583 | kWh MonitorClear | Modbus 401299; not polled by default | Command | ||
| AO | 584 | Oper HAND Key | Modbus 401300; not polled by default | Command | ||
| AO | 585 | Copy Funtion Sel | Modbus 401302; not polled by default | Command | ||
| AO | 586 | Read Allowable | Modbus 401303; not polled by default | Command | ||
| AO | 587 | Tuning Mode Sel | Modbus 401794; not polled by default | Command | ||
| AO | 588 | Mtr Rated Power | Modbus 401795; not polled by default | kW | Command | |
| AO | 589 | Rated Current | Modbus 401797; not polled by default | A | Command |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Yaskawa E7 point IDs by name
BO1Command 0 = Stop 1 = RunBO2Command 0 = Forward 1 = ReverseBO3Command External FaultBO4Command Fault resetBO5Command ComNet (0 = bl-01 = pre-selected sourceBO6Command ComCtrl (0 = bl-02 = pre-selected sourceBO7Command Multi-Function Input 1BO8Command Multi-Function Input 2BO9Command Multi-Function Input 3BO10Command Multi-Function Input 4BO11Command Multi-Function Input 5AO12Frequency ReferenceAO13PID SetpointAO14Analog Output 1 SettingAO15Analog Output 2 SettingBO16Outputs Multi-Function Output 1BO17Outputs Multi-Function Output 2BO18Outputs Multi-Function Output 3BO19Outputs Fault Relay OutputBO20Outputs Fault Relay N.C.BO21Command Selection PID Value 0006h is usedBO22Command Selection Simultaneous Terminal S5 Enable*BO23Command Selection Simultaneous Terminal S6 Enable*BO24Command Selection Simultaneous Terminal S7 Enable*BI25Inverter Status @ RUNBI26Inverter Status @ Reset SignalBI27Inverter Status Speed AgreeBI28Inverter Status Inverter ReadyBI29Inverter Status Minor FaultBI30Inverter Status Major FaultBI31Inverter Status @ ComRefBI32Inverter Status @ ComCtrlBI33Operator Status OPEBI34Operator Status ERRBI35Operator Status PRG ModeBI36Operator Status 0 - Operator 1 - PCBI37OPE E7 drive kVA Setting ErrorBI38OPE Parameter Setting Out of RangeBI39OPE Multi-Function Input SelectionBI40OPE Run Command Selection Error - Option board missingBI41OPE Control Method Selection Error - PG Opt MissingBI42OPE Multi-Function Analog Input Select ErrorBI43OPE Function Selection Error for current coPIDBI44OPE PID Control Setup ErrorBI45OPE V/F Parameter/Pattern Setting ErrorBI46OPE Carrier Frequency Parameter Setting ErrorAI47Inverter Product CodeBI48Fault Contents 1 @ FuseBI49Fault Contents 1 @ Main Circuit UndervohageBI50Fault Contents 1 @ Control Circuit UndervoltageBI51Fault Contents 1 @ MC ErrorBI52Fault Contents 1 @ Ground FauhBI53Fault Contents 1 @ Over CurrentBI54Fault Contents 1 @ OvervohageBI55Fault Contents 1 @ Inverter OverheatBI56Fault Contents 1 @ Inverter Overheat WarningBI57Fault Contents 1 @ Motor OverloadBI58Fault Contents 1 @ Inverter OverloadBI59Fault Contents 1 @ Overtorque IBI60Fault Contents 1 @ Overtorque 2BI61Fault Contents 1 @ Braking Resistor FaultBI62Fault Contents 1 @ Braking resistor OverheatBI63Fault Contents 2 @ External Fault 3BI64Fault Contents 2 @ External Fault 4BI65Fault Contents 2 @ External Fault 5BI66Fault Contents 2 @ External Fault 6BI67Fault Contents 2 @ External Fault 7BI68Fault Contents 2 @ OverspeedBI69Fault Contents 2 @ Excessive Speed BiasBI70Fault Contents 2 @ PG Line InterruptionBI71Fault Contents 2 @ Input Phase FaultBI72Fault Contents 2 @Output Phase FaultBI73Fault Contents 2 @ OverheatBI74Fault Contents 2 @ Operator Bypass FaultBI75Fault Contents 2 @ EEPROM Write FaultBI76Fault Contents 2 @ Motor Overheat FauhBI77Fault Contents 3 @ Communications FaultBI78Fault Contents 3 @ Communications Option FaultBI79Fault Contents 3 @ SI-F/G Communication FaultBI80Fault Contents 3 @ SI-F/G FaultBI81Fault Contents 3 @ Control FauhBI82Fault Contents 3 @ Zero Servo FaultBI83Fault Contents 3 @ Communications Option External FaultBI84Fault Contents 3 @ PID Feedback ErrorBI85Fault Contents 3 @ Undertorque IBI86Fault Contents 3 @ Undertorque 2BI87Fault Contents 3 @ High Slip braking OverloadBI88CPF Contents 1 @ Base Block Circuit ErrorBI89CPF Contents 1 @ EEPROM ErrorBI90CPF Contents 1 @ CPU Internal A/D Converter ErrorBI91CPF Contents 1 @ CPU External A/D Converter ErrorBI92CPF Contents 1 @ Option Card Connection ErrorBI93CPF Contents 2 @ Option Card A/D Converter ErrorBI94CPF Contents 2 @ Option Card Self-Diagnostic errorBI95CPF Contents 2 @ Option Card Option Code ErrorBI96CPF Contents 2 @ Option Card DP-RAM ErrorBI97Minor Fault Contents 1 UndervoltageBI98Minor Fault Contents 1 OvervoltageBI99Minor Fault Contents 1 Inverter OverheatBI100Minor Fault Contents 1 Inverter Overheat WarningBI101Minor Fault Contents 1 Overtorque IBI102Minor Fault Contents 1 Overtorque 2BI103Minor Fault Contents 1 2-wire Sequence Input FaultBI104Minor Fault Contents 1 BaseblockBI105Minor Fault Contents 1 External Fault 3BI106Minor Fault Contents 1 External Fault 4BI107Minor Fault Contents 1 External Fault 5BI108Minor Fault Contents 1 External Fault 6BI109Minor Fault Contents 1 External Fault 7BI110Minor Fault Contents 1 OverspeedBI111Minor Fault Contents 2 Excessive Speed BiasBI112Minor Fault Contents 2 PG Line InterruptionBI113Minor Fault Contents 2 Operator Bypass FaultBI114Minor Fault Contents 2 Communications FaultBI115Minor Fault Contents 2 Communications Option FaultBI116Minor Fault Contents 2 Waiting for CommunicationsBI117Minor Fault Contents 2 Motor OverloadBI118Minor Fault Contents 2 Inverter OverloadBI119Minor Fault Contents 2 Sl-F/G Communication FaultBI120Minor Fault Contents 2 SI-F/G FaultBI121Minor Fault Contents 2 Motor SwitchBI122Minor Fault Contents 2 PID Feedback ErrorBI123Minor Fault Contents 2 Waiting for CommunicationsBI124Minor Fault Contents 2 Undertorque 1BI125Minor Fault Contents 2 Undertorque 2BI126Minor Fault Contents 2 Communication Test FaultBI127Minor Fault Contents 3 Motor Overheat AlarmBI128Minor Fault Contents 3 E7 drive Not EnabledBI129Fault Contents @ Overcurrent/Ground FaultBI130Fault Contents @ OvervoltageBI131Fault Contents @ Inverter OverloadBI132Fault Contents @ Overheat FaultBI133Fault Contents @ Braking Resistor FaultBI134Fault Contents @ Fuse FaultBI135Fault Contents @ PID Feedback FaultBI136Fault Contents @ External FaultBI137Fault Contents @ Hardware FaultBI138Fault Contents @ Overload/OvertorqueBI139Fault Contents @ Excessive Speed DeviationBI140Fault Contents @ UndervoltageBI141Fault Contents (UVl) or (UV2) or (UV3) or Power OffBI142Fault Contents @ Input/Output Phase FaultBI143Fault Contents @ Communications ErrorBI144Fault Contents @ Operator ErrorBI145Data Link Status @ Data WritingBI146Data Link Status Data Limit FaultBI147Data Link Status @ Data Compatibility faultBI148Inverter Status RUNBI149Inverter Status ReverseBI150Inverter Status Inverter ReadyBI151Inverter Status FaultBI152Inverter Status Data Setting ErrorBI153Inverter Status Multi-Function Output 1BI154Inverter Status Multi-Function Output 2BI155Inverter Status Multi-Function Output 3AI156Frequency ReferenceAI157Output FrequencyAI158Output PowerAI159Torque CommandBI160Sequence Input Status Terminal I ClosedBI161Sequence Input Status Terminal 2 ClosedBI162Sequence Input Status Terminal 3 ClosedBI163Sequence Input Status Terminal 4 ClosedBI164Sequence Input Status Terminal 5 ClosedBI165Sequence Input Status Terminal 6 ClosedBI166Sequence Input Status Terminal 7 ClosedBI167Inverter Status @RUNBI168Inverter Status Zero SpeedBI169Inverter Status Speed AgreeBI170Inverter Status Random Speed AgreeBI171Inverter Status Frequency Detect 1BI172Inverter Status Frequency Detect 2BI173Inverter Status Inverter ReadyBI174Inverter Status UndervoltageBI175Inverter Status BaseblockBI176Inverter Status Frequency Reference Not From CommunicationsBI177Inverter Status Command Reference Not From CommunicationsBI178Inverter Status OvertorqueBI179Inverter Status Loss of Frequency referenceBI180Inverter Status Fault RetryBI181Inverter Status FaultBI182Inverter Status Communications TimeoutBI183Multi-Function Output Status Multi-Function Output 1BI184Multi-Function Output Status Multi-Function Output 2BI185Multi-Function Output Status Multi-Function Output 3AI186Main Circuit DC VoltageAI187TorqueAI188Output PowerAI189PID Feedback LevelAI190PID Input LevelAI191PID Output LevelAI192CPUAI193Flash IDBI194Communications Error CRC ErrorBI195Communications Error Data Length ErrorBI196Communications Error Parity ErrorBI197Communications Error Overrun ErrorBI198Communications Error Framing ErrorBI199Communications Error TimeoutAI200kVA SettingAI201Frequency ReferenceAI202Output FrequencyAI203Output CurrentAI204Output VoltageAI205DC Bus VoltageAI206Output PowerBI207Input Terminal Status Fwd Run (Terminal S1)BI208Input Terminal Status Rev Run (Terminal S2)BI209Input Terminal Status Terminal S3BI210Input Terminal Status Terminal S4BI211Input Terminal Status Terminal S5BI212Input Terminal Status Terminal S6BI213Input Terminal Status Terminal S7BI214Output Terminal Status Multi-function Output 1BI215Output Terminal Status Multi-function Output 2BI216Output Terminal Status Multi-function Output 3BI217Output Terminal Status Fault OutputBI218E7 drive Operation Status FWD RUNBI219E7 drive Operation Status Zero SpeedBI220E7 drive Operation Status REV RUNBI221E7 drive Operation Status ResetBI222E7 drive Operation Status Speed AgreeBI223E7 drive Operation Status E7 drive ReadyBI224E7 drive Operation Status Minor FaultBI225E7 drive Operation Status Major FaultAI226Elapsed TimeAI227Flash IDAI228Terminal A1 Input VoltageAI229Terminal A2 Input VoltageAI230Motor Secondary Current (Iq)AI231Output Frequency After Soft StartAI232PID Feedback ValueAI233CPU NumberAI234kWhAI235MWhAI236First Parameter Causing an OPE FaultAI237PID InputAI238PID OutputAI239PID SetpointBI240Communication Error Code CRC ErrorBI241Communication Error Code Data Length ErrorBI242Communication Error Code Parity ErrorBI243Communication Error Code Over-run ErrorBI244Communication Error Code Framing ErrorBI245Communication Error Code Timeout ErrorAI246FAN Elapsed TimeAI247Actual Fin TempAI248AUTO Mode FrefAI249HAND Mode FrefAI250PI Feedback 2AI251Current FaultAI252Previous FaultAI253Frequency Reference @ Previous FaultAI254Output Frequency @ Previous FaultAI255Output Current @ Previous FaultAI256Output Voltage @t Previous FaultAI257DC Bus Voltage @ Previous FaultAI258Output Power @ Previous FaultAI259Torque Reference @ Previous FaultAI260Input Terminal Status @ Previous FaultAI261Output Terminal Status @ Previous FaultAI262E7 drive Operation Status @ Previous FaultAI263Elapsed Time @ Previous FaultAI264Most Recent FaultAI2652nd Most Recent FaultAI2663rd Most Recent FaultAI2674th Most Recent FaultAI268Elapsed Time @ Most Recent FaultAI269Elapsed Time @ 2nd Most Recent FaultAI270Elapsed Time @ 3rd Most Recent FaultAI271Elapsed Time @ 4th Most Recent FaultAI2725th Most Recent FaultAI2736th Most Recent FaultAI2747th Most Recent FaultAI2758th Most Recent FaultAI2769th Most Recent FaultAI27710th Most Recent FaultAI278Elapsed Time @ 5th Most Recent FaultAI279Elapsed Time @ 6th Most Recent FaultAI280Elapsed Time @ 7th Most Recent FaultAI281Elapsed Time @ 8th Most Recent FaultAI282Elapsed Time @ 9th Most Recent FaultAI283Elapsed Time @ 10th Most Recent FaultAO284Select LanguageAO285Access LevelAO286Init ParametersAO287Enter PasswordAO288User Param 1AO289User Param 2AO290User Param 3AO291User Param 4AO292User Param 5AO293User Param 6AO294User Param 7AO295User Param 8AO296User Param 9AO297User Param 10AO298User Param 11AO299User Param 12AO300User Param 13AO301User Param 14AO302User Param 15AO303User Param 16AO304User Param 17AO305User Param 18AO306User Param 19AO307User Param 20AO308User Param 21AO309User Param 22AO310User Param 23AO311User Param 24AO312User Param 25AO313User Param 26AO314User Param 27AO315User Param 28AO316User Param 29AO317User Param 30AO318User Param 31AO319User Param 32AO320Reference SourceAO321Run SourceAO322Stopping MethodAO323Reverse OperAO324LOC/REM RUN SelAO325RUN CMD at PRGAO326L/R Select@DriveAO327Wait to Run TimeAO328HAND Fref SourceAO329DCInj Start FreqAO330DCInj CurrentAO331DCInj Time@StartAO332DCInj Time@StopAO333DCInj P GainAO334DCInj Intgl TimeAO335DCInj LimitAO336Preheat CurrentAO337SpdSrch at StartAO338SpdSrch CurrentAO339SpdSrch Dec TimeAO340SpdSrch V/FAO341Search DelayAO342Srch Im Lvl IAO343Srch Im Lvl2AO344Srch ACR P GainAO345Srch ACR I TimeAO346Srch Detect CompAO347Srch Mthd Sw LvlAO348Srch I DeadbandAO349Bidir Search SelAO350Delay-ON TimerAO351Delay-OFF TimerAO352PI ModeAO353P GainAO354PI I TimeAO355PI I LimitAO356PI LimitAO357PI OffsetAO358PI Delay TimeAO359Output Level SelAO360Output GainAO361Output Rev SelAO362Fb los Det SelAO363Fb los Det LvlAO364Fb los Det TimeAO365Sleep LevelAO366Sleep TimeAO367Acc/Dec TimeAO368PI Setpoint SelAO369PI SetpointAO370Setpoint ScalingAO371PI Sleep SourceAO372Snooze LevelAO373Snooze DelayTimeAO374Wake-Up LevelAO375Setpoint BoostAO376Max Boost TimeAO377Snooze FeedbackAO378PI Feedback SqRtAO379PI Fb SqRt GainAO380PI Out Moni SqRtAO381Energy Save SelAO382Energy Save COEFAO383kW Filter TimeAO384Search V LimitAO385E-Sav V Low LimlAO386E-Sav V Low Lim2AO387E-Sav V Up LimlAO388E-Sav V Up Lim2AO389Srch V Step 100%AO390Srch V Step 5%AO391Srch V Avg TimeAO392Srch kW Hold WthAO393Accel Time IAO394Decel Time IAO395Accel Time 2AO396Decel Time 2AO397Fast Stop TimeAO398Acc/Dec SW FreqAO399SCrv Acc @ StartAO400SCrv Acc @ EndAO401Torq Comp GainAO402Torq Comp TimeAO403Normal Duty SelAO404CarrierFreq SelAO405CarrierFreq MaxAO406CarrierFreq MinAO407CarrierFreq GainAO408PWM MethodAO409Phase SW levelAO410PWM on TimeAO411Reference 1AO412Reference 2AO413Reference 3AO414Reference 4AO415Jog ReferenceAO416Ref Upper LimitAO417Ref Lower LimitAO418Ref1 Lower LimitAO419Jump Freq 1AO420Jump Freq 2AO421Jump Freq 3AO422Jump BandwidthAO423MOP Ref MemoryAO424Trim Control LvlAO425Input VoltageAO426V/F SelectionAO427Max FrequencyAO428Max VoltageAO429Base FrequencyAO430Mid Frequency AAO431Mid Vohage AAO432Min FrequencyAO433Min VohageAO434Mid Frequency BAO435Mid Voltage BAO436Base VohageAO437Motor Rated FLAAO438Motor Rated SlipAO439No-Load CurrentAO440Term ResistanceAO441Tcomp Iron LossAO442Mtr Rated PowerAO443Comm Bus Fit SelAO444EFO DetectionAO445EFO Fault ActionAO446Not LabeledAO447Terminal S3 SelAO448Terminal S4 SelAO449Terminal S5 SelAO450Terminal S6 SelAO451Terminal S7 SelAO452TermMl-M2 SelAO453Term M3-M4 SelAO454Terminal A1 GainAO455Terminal A1 BiasAO456Term A2 SignalAO457Terminal A2 SelAO458Terminal A2 GainAO459Terminal A2 BiasAO460Filter Avg TimeAO461TA1/A2 SelectAO462Terminal FM SelAO463Terminal FM GainAO464Terminal FM BiasAO465Terminal AM SelAO466Terminal AM GainAO467Terminal AM BiasAO468AO Level SelectlAO469AO Level Select2AO470Serial Comm AdrAO471Serial Baud RateAO472Serial Com SelAO473Serial Fault SelAO474Serial Fit DtctAO475Transmit WaitTIMAO476RTS Control SelAO477Protocol SelectAO478CE Detect TimeAO479MOL Fault SelectAO480MOL Time ConstAO481Mtr OH Alarm SelAO482Mtr OH Fault SelAO483Mtr Temp FilterAO484PwrL SelectionAO485PwrL Ridethru tAO486PwrL Baseblock tAO487PwrL V/F Ramp tAO488PUV Det LevelAO489StallP Accel SelAO490StallP Accel LvlAO491StallP CHP LvlAO492StallP Decel SelAO493StallP Run SelAO494StallP Run LevelAO495StallP GainAO496StallP Intg TimeAO497Decel Time CoefAO498StallP Decel LvlAO499Spd Agree LevelAO500Spd Agree WidthAO501RefLoss SelAO502Fref at FlossAO503Num of RestartsAO504Restart SelAO505Max Restart TimeAO506Restart Mode SelAO507Torq Det 1 SelAO508Torq Det 1 LvlAO509Torq Det 1 TimeAO510DB Resistor ProtAO511OH Pre-Alarm LvlAO512OH Pre-Alarm SelAO513OK1 Fault LevelAO514Ph Loss In SelAO515Ph Loss In LvlAO516Ph Loss Out SelAO517Ph Loss Out LvlAO518Ground Fault SelAO519Fan On/Off SelAO520Fan Delay TimeAO521Ambient TempAO522UV3 DetectAO523Inverter OL SelAO5240L2 Sel @ L-SpdAO525Low Spd 0L2 FreqAO5260L2 OHz GainAO527Soft CLA SelAO528Fref During OHAO529Hunt Prev SelectAO530Hunt Prev GainAO531Hunt Prev TimeAO532Hunt Prev LimitAO533HSB Decel WidthAO534HSB Current RefAO535HSB DwelTim@StpAO536HSB OL TimeAO537HSB V/F GainAO538Spd Agr CurrentAO539Spd Agree TimeAO540HSB V Lvl 1AO541HSB V Lvl2AO542HSB RI Comp CoefAO543HSB RI Comp TimAO544Prohib HSB DecelAO545Inv Rate CurrentAO546DCCT GainAO547AVR SelectionAO548AVR TimeAO549ON-Delay TimeAO550ON-Delay CompAO551IGBT Volt DropAO552Pwr Angle Filt 1AO553Pwr Angle Filt 2AO554DCCT Filter TimeAO555Soft CLA GainAO556Soft CLA FilterAO557Soft CLA Level 1AO558Soft CLA Level2AO559Soft CLA SW FreqAO560Soft CLA Level3AO561OnDelay Comp LvlAO562IGBT GainAO563Aging Test ModeAO564User Monitor SelAO565Power-On MonitorAO566Display ScalingAO567LCD ContrastAO568Monitor Mode SelAO5692nd Monitor SelAO5703rd Monitor SelAO571Local/Remote KeyAO572Oper STOP KeyAO573User DefaultsAO574Inverter Model #AO575Operator M.O.P.AO576Oper DetectionAO577Elapsed Time SetAO578Elapsed Time RunAO579Init Mode SelAO580Fan ON Time SetAO581FLT Trace InitAO582PUF Cont det SelAO583kWh MonitorClearAO584Oper HAND KeyAO585Copy Funtion SelAO586Read AllowableAO587Tuning Mode SelAO588Mtr Rated PowerAO589Rated Current
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Yaskawa_E7_Drive_a_LX.csv; the profile maps the registers in the Yaskawa E7 Modbus technical manual (https://www.ccontrols.com/support/dp/TME711.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 50 of the 589 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Frequency Reference; PID Setpoint; Inverter Status Speed Agree...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Yaskawa E7 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Yaskawa E7 via BASgatewayLX
How many BACnet points does the Contemporary Controls Yaskawa E7 via BASgatewayLX have?
This list has 589 BACnet objects: 72 analog inputs, 310 analog outputs, 187 binary inputs, 20 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Yaskawa E7 via BASgatewayLX BACnet points are writable?
330 of the 589 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Yaskawa E7 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Yaskawa_E7_Drive_a (Yaskawa_E7_Drive_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Yaskawa_E7_Drive.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Yaskawa E7 via BASgatewayLX?
Start with BO 1 Command 0 = Stop 1 = Run (Run/stop command (1 = run)); AO 12 Frequency Reference (Frequency reference); BO 4 Command Fault reset (Fault reset); BI 25 Inverter Status @ RUN (Drive running); BI 28 Inverter Status Inverter Ready (Inverter ready); AI 202 Output Frequency (Output frequency, Hz); AI 203 Output Current (Output current, A); AI 206 Output Power (Output power, kW); BI 29 Inverter Status Minor Fault (Minor fault (alarm) active); BI 30 Inverter Status Major Fault (Major fault active).
How do I enable BMS control of the Contemporary Controls Yaskawa E7 via BASgatewayLX?
The drive must take its run command and frequency reference from serial communication (b1-01 / b1-02 set to serial per the E7 manual) before BO 1 and AO 12 act. These command objects are unpolled in the published profile; tick them first.
How do I check these points on the real Yaskawa E7 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Yaskawa_E7_Drive_a · Yaskawa_E7_Drive_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.