Power and energy meter · BACnet points list

Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the GE PQMII: 531 objects (118 AI, 413 BI), 38 polled by default (currents, voltages, power, PF, demand and frequency). Hundreds of switch, relay, LED and alarm status bits and energy, harmonic and setup values are unpolled.

This page lists 531 BACnet objects for the Contemporary Controls GE Multilin PQMII via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
GE Multilin PQMII via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
531 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter
Source document
BASgatewayLX Modbus device profile GE_PQMII_Power_Meter_Lite · GE_PQMII_Power_Meter_Lite_LX.csv
Download CSV 531 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls GE Multilin PQMII via BASgatewayLX

Integration in brief

Map 3-phase real power, 3-phase positive real energy and average line voltage first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 463 Phase Real Power3-phase real powerRead
AI 943 Phase Positive Real Energy Used3-phase positive real energyRead
AI 24Average Line VoltageAverage line voltageRead
AI 4Average CurrentAverage currentRead
AI 493 Phase Power Factor3-phase power factorRead
AI 116FrequencyFrequencyRead
AI 1063 Phase Real Power Demand3-phase real power demandRead
BI 139Alarm RelayAlarm relayRead

Network setup

Watch out for

Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

531 of 531 shown
Type
AnalogBinary
Show
Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet Points List
DescriptionStates
AI1Phase A CurrentModbus 400577ARead
AI2Phase B CurrentModbus 400578ARead
AI3Phase C CurrentModbus 400579ARead
AImin4Average CurrentModbus 400580ARead
AI5Neutral CurrentModbus 400581ARead
AI6Current UnbalanceModbus 400582%Read
AI7Phase A Current - MinimumModbus 400583; not polled by defaultARead
AI8Phase B Current - MinimumModbus 400584; not polled by defaultARead
AI9Phase C Current - MinimumModbus 400585; not polled by defaultARead
AI10Neutral Current - MinimumModbus 400586; not polled by defaultARead
AI11Current Unbalance - MinimumModbus 400587; not polled by default%Read
AI12Phase A Current - MaximumModbus 400588; not polled by defaultARead
AI13Phase B Current - MaximumModbus 400589; not polled by defaultARead
AI14Phase C Current - MaximumModbus 400590; not polled by defaultARead
AI15Neutral Current - MaximumModbus 400591; not polled by defaultARead
AI16Current Unbalance - MaximumModbus 400592; not polled by default%Read
AI17Voltage VanModbus 400641VRead
AI18Voltage VbnModbus 400643VRead
AI19Voltage VcnModbus 400645VRead
AI20Average Phase VoltageModbus 400647VRead
AI21Voltage VabModbus 400649VRead
AI22Voltage VbcModbus 400651VRead
AI23Voltage VcaModbus 400653VRead
AImin24Average Line VoltageModbus 400655VRead
AI25Voltage UnbalanceModbus 400657; not polled by default%Read
AI26Voltage Van - MinimumModbus 400658; not polled by defaultVRead
AI27Voltage Vbn - MinimumModbus 400660; not polled by defaultVRead
AI28Voltage Vcn - MinimumModbus 400662; not polled by defaultVRead
AI29Voltage Vab - MinimumModbus 400664; not polled by defaultVRead
AI30Voltage Vbc - MinimumModbus 400666; not polled by defaultVRead
AI31Voltage Vca - MinimumModbus 400668; not polled by defaultVRead
AI32Voltage Unbalance - MinimumModbus 400670; not polled by default%Read
AI33Voltage Van - MaximumModbus 400671; not polled by defaultVRead
AI34Voltage Vbn - MaximumModbus 400673; not polled by defaultVRead
AI35Voltage Vcn - MaximumModbus 400675; not polled by defaultVRead
AI36Voltage Vab - MaximumModbus 400677; not polled by defaultVRead
AI37Voltage Vbc - MaximumModbus 400679; not polled by defaultVRead
AI38Voltage Vca - MaximumModbus 400681; not polled by defaultVRead
AI39Voltage Unbalance - MaximumModbus 400683; not polled by default%Read
AI40Va Phasor AngleModbus 400744; not polled by default°Read
AI41Vb Phasor AngleModbus 400745; not polled by default°Read
AI42Vc Phasor AngleModbus 400746; not polled by default°Read
AI43Ia Phasor AngleModbus 400747; not polled by default°Read
AI44Ib Phasor AngleModbus 400748; not polled by default°Read
AI45Ic Phasor AngleModbus 400749; not polled by default°Read
AImin463 Phase Real PowerModbus 400753kWRead
AI473 Phase Reactive PowerModbus 400755kVARRead
AI483 Phase Apparent PowerModbus 400757kVARead
AImin493 Phase Power FactorModbus 400759PFRead
AI50Phase A Real PowerModbus 400760kWRead
AI51Phase A Reactive PowerModbus 400762kVARRead
AI52Phase A Apparent PowerModbus 400764kVARead
AI53Phase A Power FactorModbus 400766PFRead
AI54Phase B Real PowerModbus 400767kWRead
AI55Phase B Reactive PowerModbus 400769kVARRead
AI56Phase B Apparent PowerModbus 400771kVARead
AI57Phase B Power FactorModbus 400773PFRead
AI58Phase C Real PowerModbus 400774kWRead
AI59Phase C Reactive PowerModbus 400776kVARRead
AI60Phase C Apparent PowerModbus 400778kVARead
AI61Phase C Power FactorModbus 400780PFRead
AI623 Phase Real Power - MinimumModbus 400781; not polled by defaultkWRead
AI633 Phase Reactive Power - MinimumModbus 400783; not polled by defaultkVARRead
AI643 Phase Apparent Power - MinimumModbus 400785; not polled by defaultkVARead
AI653 Phase Power Factor - MinimumModbus 400787; not polled by defaultPFRead
AI663 Phase Real Power - MaximumModbus 400788; not polled by defaultkWRead
AI673 Phase Reactive Power - MaximumModbus 400790; not polled by defaultkVARRead
AI683 Phase Apparent Power - MaximumModbus 400792; not polled by defaultkVARead
AI693 Phase Power Factor - MaximumModbus 400794; not polled by defaultPFRead
AI70Phase A Real Power - MinimumModbus 400795; not polled by defaultkWRead
AI71Phase A Reactive Power - MinimumModbus 400797; not polled by defaultkVARRead
AI72Phase A Apparent Power - MinimumModbus 400799; not polled by defaultkVARead
AI73Phase A Power Factor - MinimumModbus 400801; not polled by defaultPFRead
AI74Phase A Real Power - MaximumModbus 400802; not polled by defaultkWRead
AI75Phase A Reactive Power - MaximumModbus 400804; not polled by defaultkVARRead
AI76Phase A Apparent Power - MaximumModbus 400806; not polled by defaultkVARead
AI77Phase A Power Factor - MaximumModbus 400808; not polled by defaultPFRead
AI78Phase B Real Power - MinimumModbus 400809; not polled by defaultkWRead
AI79Phase B Reactive Power - MinimumModbus 400811; not polled by defaultkVARRead
AI80Phase B Apparent Power - MinimumModbus 400813; not polled by defaultkVARead
AI81Phase B Power Factor - MinimumModbus 400815; not polled by defaultPFRead
AI82Phase B Real Power - MaximumModbus 400816; not polled by defaultkWRead
AI83Phase B Reactive Power - MaximumModbus 400818; not polled by defaultkVARRead
AI84Phase B Apparent Power - MaximumModbus 400820; not polled by defaultkVARead
AI85Phase B Power Factor - MaximumModbus 400822; not polled by defaultPFRead
AI86Phase C Real Power - MinimumModbus 400823; not polled by defaultkWRead
AI87Phase C Reactive Power - MinimumModbus 400825; not polled by defaultkVARRead
AI88Phase C Apparent Power - MinimumModbus 400827; not polled by defaultkVARead
AI89Phase C Power Factor - MinimumModbus 400829; not polled by defaultPFRead
AI90Phase C Real Power - MaximumModbus 400830; not polled by defaultkWRead
AI91Phase C Reactive Power - MaximumModbus 400832; not polled by defaultkVARRead
AI92Phase C Apparent Power - MaximumModbus 400834; not polled by defaultkVARead
AI93Phase C Power Factor - MaximumModbus 400836; not polled by defaultPFRead
AImin943 Phase Positive Real Energy UsedModbus 400977; not polled by defaultkWhRead
AI953 Phase Negative Real Energy UsedModbus 400979; not polled by defaultkWhRead
AI963 Phase Positive React. Energy UsedModbus 400981; not polled by defaultRead
AI973 Phase Neg Reactive Energy UsedModbus 400983; not polled by defaultRead
AI983 Phase Apparent Energy UsedModbus 400985; not polled by defaultkWhRead
AI993 Phase Energy Used in Last 24 hModbus 400987; not polled by defaultRead
AI1003 Phase Energy Cost Since ResetModbus 400989; not polled by defaultRead
AI1013 Phase Energy Cost Per DayModbus 400991; not polled by defaultRead
AI102Phase A Current DemandModbus 401025ARead
AI103Phase B Current DemandModbus 401026ARead
AI104Phase C Current DemandModbus 401027ARead
AI105Neutral Current DemandModbus 401028ARead
AImin1063 Phase Real Power DemandModbus 401029kWRead
AI1073 Phase React Power DemandModbus 401031kVARRead
AI1083 Phase Apparent Power DemandModbus 401033kVARead
AI109Phase A Current Demand - MaximumModbus 401035; not polled by defaultARead
AI110Phase B Current Demand - MaximumModbus 401036; not polled by defaultARead
AI111Phase C Current Demand - MaximumModbus 401037; not polled by defaultARead
AI112Neutral Current Demand - MaximumModbus 401038; not polled by defaultARead
AI1133 Phase Real Power Dmd - MaxModbus 401039; not polled by defaultkWRead
AI1143 Phase React Power Dmd - MaxModbus 401041; not polled by defaultkVARRead
AI1153 Phase Apparent Power Dmd - MaxModbus 401043; not polled by defaultkVARead
AImin116FrequencyModbus 401089HzRead
AI117Frequency MinimumModbus 401090; not polled by defaultHzRead
AI118Frequency MaximumModbus 401091; not polled by defaultHzRead
BI119Switch A Input StatusModbus 400513 bit 8; not polled by defaultRead
BI120Switch B Input StatusModbus 400513 bit 9; not polled by defaultRead
BI121Switch C Input StatusModbus 400513 bit 10; not polled by defaultRead
BI122Switch D Input StatusModbus 400513 bit 11; not polled by defaultRead
BI123Aux 1 Relay LED Status FlagModbus 400514 bit 0; not polled by defaultRead
BI124Aux 2 Relay LED Status FlagModbus 400514 bit 1; not polled by defaultRead
BI125Aux 3 Relay LED Status FlagModbus 400514 bit 2; not polled by defaultRead
BI126Alarm LED Status FlagModbus 400514 bit 3; not polled by defaultRead
BI127Program LED Status FlagModbus 400514 bit 4; not polled by defaultRead
BI128Simulation LED Status FlagModbus 400514 bit 5; not polled by defaultRead
BI129Alarm Relay LED Status FlagModbus 400514 bit 6; not polled by defaultRead
BI130Self Test LED Status FlagModbus 400514 bit 7; not polled by defaultRead
BI131Aux 1 Relay LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 0; not polled by defaultRead
BI132Aux 2 Relay LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 1; not polled by defaultRead
BI133Aux 3 Relay LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 2; not polled by defaultRead
BI134Alarm LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 3; not polled by defaultRead
BI135Program LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 4; not polled by defaultRead
BI136Simulation LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 5; not polled by defaultRead
BI137Alarm relay LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 6; not polled by defaultRead
BI138Self Test LED Attribute Flag Off=Flash ON=SteadyModbus 400515 bit 7; not polled by defaultRead
BImin139Alarm RelayModbus 400516 bit 0; not polled by defaultRead
BI140Auxiliary Relay 1Modbus 400516 bit 1; not polled by defaultRead
BI141Auxiliary Relay 2Modbus 400516 bit 2; not polled by defaultRead
BI142Auxiliary Relay 3Modbus 400516 bit 3; not polled by defaultRead
BI143Alarm Active Status Flags 1 - Phase Undercurrent AlarmModbus 400517 bit 0; not polled by defaultRead
BI144Alarm Active Status Flags 1 - Phase Overcurrent AlarmModbus 400517 bit 1; not polled by defaultRead
BI145Alarm Active Status Flags 1 - Neutral Overcurrent AlarmModbus 400517 bit 2; not polled by defaultRead
BI146Alarm Active Status Flags 1 - Undervoltage AlarmModbus 400517 bit 3; not polled by defaultRead
BI147Alarm Active Status Flags 1 - Overvoltage AlarmModbus 400517 bit 4; not polled by defaultRead
BI148Alarm Active Status Flags 1 - Current Unbalance AlarmModbus 400517 bit 5; not polled by defaultRead
BI149Alarm Active Status Flags 1 - Voltage Unbalance AlarmModbus 400517 bit 6; not polled by defaultRead
BI150Alarm Active Status Flags 1 - Voltage Phase ReversalModbus 400517 bit 7; not polled by defaultRead
BI151Alarm Active Status Flags 1 - PF Lead Alarm 1Modbus 400517 bit 8; not polled by defaultRead
BI152Alarm Active Status Flags 1 - PF Lead Alarm 2Modbus 400517 bit 9; not polled by defaultRead
BI153Alarm Active Status Flags 1 - Power Factor Log Alarm 1Modbus 400517 bit 10; not polled by defaultRead
BI154Alarm Active Status Flags 1 - Ppower Factor Log Alarm 2Modbus 400517 bit 11; not polled by defaultRead
BI155Alarm Active Status Flags 1 - Positive Real Power AlarmModbus 400517 bit 12; not polled by defaultRead
BI156Alarm Active Status Flags 1 - Neg Real Power AlarmModbus 400517 bit 13; not polled by defaultRead
BI157Alarm Active Status Flags 1 - Pos Reactive Power AlarmModbus 400517 bit 14; not polled by defaultRead
BI158Alarm Active Status Flags 1 - Neg Reactive Powere AlarmModbus 400517 bit 15; not polled by defaultRead
BI159Alarm Pickup Status Flags 1 - Phase Undercurrent AlarmModbus 400518 bit 0; not polled by defaultRead
BI160Alarm Pickup Status Flags 1 - Phase Overcurrent AlarmModbus 400518 bit 1; not polled by defaultRead
BI161Alarm Pickup Status Flags 1 - Neutral Overcurrent AlarmModbus 400518 bit 2; not polled by defaultRead
BI162Alarm Pickup Status Flags 1 - Undervoltage AlarmModbus 400518 bit 3; not polled by defaultRead
BI163Alarm Pickup Status Flags 1 - Overvoltage AlarmModbus 400518 bit 4; not polled by defaultRead
BI164Alarm Pickup Status Flags 1 - Current Unbalance AlarmModbus 400518 bit 5; not polled by defaultRead
BI165Alarm Pickup Status Flags 1 - Voltage Unbalance AlarmModbus 400518 bit 6; not polled by defaultRead
BI166Alarm Pickup Status Flags 1 - Voltage Phase ReversalModbus 400518 bit 7; not polled by defaultRead
BI167Alarm Pickup Status Flags 1 - PF Lead Alarm 1Modbus 400518 bit 8; not polled by defaultRead
BI168Alarm Pickup Status Flags 1 - PF Lead Alarm 2Modbus 400518 bit 9; not polled by defaultRead
BI169Alarm Pickup Status Flags 1 - Power Factor Log Alarm 1Modbus 400518 bit 10; not polled by defaultRead
BI170Alarm Pickup Status Flags 1 - Ppower Factor Log Alarm 2Modbus 400518 bit 11; not polled by defaultRead
BI171Alarm Pickup Status Flags 1 - Positive Real Power AlarmModbus 400518 bit 12; not polled by defaultRead
BI172Alarm Pickup Status Flags 1 - Neg Real Power AlarmModbus 400518 bit 13; not polled by defaultRead
BI173Alarm Pickup Status Flags 1 - Pos Reactive Power AlarmModbus 400518 bit 14; not polled by defaultRead
BI174Alarm Pickup Status Flags 1 - Neg Reactive Powere AlarmModbus 400518 bit 15; not polled by defaultRead
BI175Alarm Active Status Flags 2 - Underfrequency AlarmModbus 400519 bit 0; not polled by defaultRead
BI176Alarm Active Status Flags 2 - Overfrequency AlarmModbus 400519 bit 1; not polled by defaultRead
BI177Alarm Active Status Flags 2 - Positive Real Power Demand AlarmModbus 400519 bit 2; not polled by defaultRead
BI178Alarm Active Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400519 bit 3; not polled by defaultRead
BI179Alarm Active Status Flags 2 - Appartent Power Demand AlarmModbus 400519 bit 4; not polled by defaultRead
BI180Alarm Active Status Flags 2 - Ph A Current Demand AlarmModbus 400519 bit 5; not polled by defaultRead
BI181Alarm Active Status Flags 2 - Ph B Current Demand AlarmModbus 400519 bit 6; not polled by defaultRead
BI182Alarm Active Status Flags 2 - Ph C Current DemanD AlarmModbus 400519 bit 7; not polled by defaultRead
BI183Alarm Active Status Flags 2 - Nuetral Current Demand AlarmModbus 400519 bit 8; not polled by defaultRead
BI184Alarm Active Status Flags 2 - Switch A AlarmModbus 400519 bit 9; not polled by defaultRead
BI185Alarm Active Status Flags 2 - Switch B AlarmModbus 400519 bit 10; not polled by defaultRead
BI186Alarm Active Status Flags 2 - Switch C AlarmModbus 400519 bit 11; not polled by defaultRead
BI187Alarm Active Status Flags 2 - Switch D AlarmModbus 400519 bit 12; not polled by defaultRead
BI188Alarm Active Status Flags 2 - Internal Fault AlarmModbus 400519 bit 13; not polled by defaultRead
BI189Alarm Active Status Flags 2 - Serial COM1 Failure AlarmModbus 400519 bit 14; not polled by defaultRead
BI190Alarm Active Status Flags 2 - Serial COM2 Failure AlarmModbus 400519 bit 15; not polled by defaultRead
BI191Alarm Pickup Status Flags 2 - Underfrequency AlarmModbus 400520 bit 0; not polled by defaultRead
BI192Alarm Pickup Status Flags 2 - Overfrequency AlarmModbus 400520 bit 1; not polled by defaultRead
BI193Alarm Pickup Status Flags 2 - Positive Real Power Demand AlarmModbus 400520 bit 2; not polled by defaultRead
BI194Alarm Pickup Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400520 bit 3; not polled by defaultRead
BI195Alarm Pickup Status Flags 2 - Appartent Power Demand AlarmModbus 400520 bit 4; not polled by defaultRead
BI196Alarm Pickup Status Flags 2 - Ph A Current Demand AlarmModbus 400520 bit 5; not polled by defaultRead
BI197Alarm Pickup Status Flags 2 - Ph B Current Demand AlarmModbus 400520 bit 6; not polled by defaultRead
BI198Alarm Pickup Status Flags 2 - Ph C Current DemanD AlarmModbus 400520 bit 7; not polled by defaultRead
BI199Alarm Pickup Status Flags 2 - Nuetral Current Demand AlarmModbus 400520 bit 8; not polled by defaultRead
BI200Alarm Pickup Status Flags 2 - Switch A AlarmModbus 400520 bit 9; not polled by defaultRead
BI201Alarm Pickup Status Flags 2 - Switch B AlarmModbus 400520 bit 10; not polled by defaultRead
BI202Alarm Pickup Status Flags 2 - Switch C AlarmModbus 400520 bit 11; not polled by defaultRead
BI203Alarm Pickup Status Flags 2 - Switch D AlarmModbus 400520 bit 12; not polled by defaultRead
BI204Alarm Pickup Status Flags 2 - Internal Fault AlarmModbus 400520 bit 13; not polled by defaultRead
BI205Alarm Pickup Status Flags 2 - Serial COM1 Failure AlarmModbus 400520 bit 14; not polled by defaultRead
BI206Alarm Pickup Status Flags 2 - Serial COM2 Failure AlarmModbus 400520 bit 15; not polled by defaultRead
BI207Alarm Active Status Flags 3 - Clock Not Set AlarmModbus 400521 bit 0; not polled by defaultRead
BI208Alarm Active Status Flags 3 - Parameters Not Set AlarmModbus 400521 bit 1; not polled by defaultRead
BI209Alarm Active Status Flags 3 - Pulse Input 1 AlarmModbus 400521 bit 2; not polled by defaultRead
BI210Alarm Active Status Flags 3 - Current THD AlarmModbus 400521 bit 3; not polled by defaultRead
BI211Alarm Active Status Flags 3 - Voltage THD AlarmModbus 400521 bit 4; not polled by defaultRead
BI212Alarm Active Status Flags 3 - Analog Input Main AlarmModbus 400521 bit 5; not polled by defaultRead
BI213Alarm Active Status Flags 3 - Analog Input Alt AlarmModbus 400521 bit 6; not polled by defaultRead
BI214Alarm Active Status Flags 3 - Data Log 1Modbus 400521 bit 7; not polled by defaultRead
BI215Alarm Active Status Flags 3 - Data Log 2Modbus 400521 bit 8; not polled by defaultRead
BI216Alarm Active Status Flags 3 - Negative Real Power Demand AlarmModbus 400521 bit 9; not polled by defaultRead
BI217Alarm Active Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400521 bit 10; not polled by defaultRead
BI218Alarm Active Status Flags 3 - Pulse Input 2 AlarmModbus 400521 bit 11; not polled by defaultRead
BI219Alarm Active Status Flags 3 - Pulse Input 3 AlarmModbus 400521 bit 12; not polled by defaultRead
BI220Alarm Active Status Flags 3 - Pulse Input 4 AlarmModbus 400521 bit 13; not polled by defaultRead
BI221Alarm Active Status Flags 3 - Totalized Pulse In AlarmModbus 400521 bit 14; not polled by defaultRead
BI222Alarm Active Status Flags 3 - Time AlarmModbus 400521 bit 15; not polled by defaultRead
BI223Alarm Pickup Status Flags 3 - Clock Not Set AlarmModbus 400522 bit 0; not polled by defaultRead
BI224Alarm Pickup Status Flags 3 - Parameters Not Set AlarmModbus 400522 bit 1; not polled by defaultRead
BI225Alarm Pickup Status Flags 3 - Pulse Input 1 AlarmModbus 400522 bit 2; not polled by defaultRead
BI226Alarm Pickup Status Flags 3 - Current THD AlarmModbus 400522 bit 3; not polled by defaultRead
BI227Alarm Pickup Status Flags 3 - Voltage THD AlarmModbus 400522 bit 4; not polled by defaultRead
BI228Alarm Pickup Status Flags 3 - Analog Input Main AlarmModbus 400522 bit 5; not polled by defaultRead
BI229Alarm Pickup Status Flags 3 - Analog Input Alt AlarmModbus 400522 bit 6; not polled by defaultRead
BI230Alarm Pickup Status Flags 3 - Data Log 1Modbus 400522 bit 7; not polled by defaultRead
BI231Alarm Pickup Status Flags 3 - Data Log 2Modbus 400522 bit 8; not polled by defaultRead
BI232Alarm Pickup Status Flags 3 - Negative Real Power Demand AlarmModbus 400522 bit 9; not polled by defaultRead
BI233Alarm Pickup Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400522 bit 10; not polled by defaultRead
BI234Alarm Pickup Status Flags 3 - Pulse Input 2 AlarmModbus 400522 bit 11; not polled by defaultRead
BI235Alarm Pickup Status Flags 3 - Pulse Input 3 AlarmModbus 400522 bit 12; not polled by defaultRead
BI236Alarm Pickup Status Flags 3 - Pulse Input 4 AlarmModbus 400522 bit 13; not polled by defaultRead
BI237Alarm Pickup Status Flags 3 - Totalized Pulse In AlarmModbus 400522 bit 14; not polled by defaultRead
BI238Alarm Pickup Status Flags 3 - Time AlarmModbus 400522 bit 15; not polled by defaultRead
BI239Aux 1 Active Status Flags 1 - Phase Undercurrent AlarmModbus 400523 bit 0; not polled by defaultRead
BI240Aux 1 Active Status Flags 1 - Phase Overcurrent AlarmModbus 400523 bit 1; not polled by defaultRead
BI241Aux 1 Active Status Flags 1 - Neutral Overcurrent AlarmModbus 400523 bit 2; not polled by defaultRead
BI242Aux 1 Active Status Flags 1 - Undervoltage AlarmModbus 400523 bit 3; not polled by defaultRead
BI243Aux 1 Active Status Flags 1 - Overvoltage AlarmModbus 400523 bit 4; not polled by defaultRead
BI244Aux 1 Active Status Flags 1 - Current Unbalance AlarmModbus 400523 bit 5; not polled by defaultRead
BI245Aux 1 Active Status Flags 1 - Voltage Unbalance AlarmModbus 400523 bit 6; not polled by defaultRead
BI246Aux 1 Active Status Flags 1 - Voltage Phase Reversal AlarmModbus 400523 bit 7; not polled by defaultRead
BI247Aux 1 Active Status Flags 1 - PF Lead Alarm 1Modbus 400523 bit 8; not polled by defaultRead
BI248Aux 1 Active Status Flags 1 - PF Lead Alarm 2Modbus 400523 bit 9; not polled by defaultRead
BI249Aux 1 Active Status Flags 1 - Power Factor Log Alarm 1Modbus 400523 bit 10; not polled by defaultRead
BI250Aux 1 Active Status Flags 1 - Power Factor Log Alarm 2Modbus 400523 bit 11; not polled by defaultRead
BI251Aux 1 Active Status Flags 1 - Positive Real Power AlarmModbus 400523 bit 12; not polled by defaultRead
BI252Aux 1 Active Status Flags 1 - Neg Real Power AlarmModbus 400523 bit 13; not polled by defaultRead
BI253Aux 1 Active Status Flags 1 - Pos Reactive Power AlarmModbus 400523 bit 14; not polled by defaultRead
BI254Aux 1 Active Status Flags 1 - Neg Reactive Powere AlarmModbus 400523 bit 15; not polled by defaultRead
BI255Aux 1 Pickup Status Flags 1 - Phase Undercurrent AlarmModbus 400524 bit 0; not polled by defaultRead
BI256Aux 1 Pickup Status Flags 1 - Phase Overcurrent AlarmModbus 400524 bit 1; not polled by defaultRead
BI257Aux 1 Pickup Status Flags 1 - Neutral Overcurrent AlarmModbus 400524 bit 2; not polled by defaultRead
BI258Aux 1 Pickup Status Flags 1 - Undervoltage AlarmModbus 400524 bit 3; not polled by defaultRead
BI259Aux 1 Pickup Status Flags 1 - Overvoltage AlarmModbus 400524 bit 4; not polled by defaultRead
BI260Aux 1 Pickup Status Flags 1 - Current Unbalance AlarmModbus 400524 bit 5; not polled by defaultRead
BI261Aux 1 Pickup Status Flags 1 - Voltage Unbalance AlarmModbus 400524 bit 6; not polled by defaultRead
BI262Aux 1 Pickup Status Flags 1 - Voltage Phase Reversal AlarmModbus 400524 bit 7; not polled by defaultRead
BI263Aux 1 Pickup Status Flags 1 - PF Lead Alarm 1Modbus 400524 bit 8; not polled by defaultRead
BI264Aux 1 Pickup Status Flags 1 - PF Lead Alarm 2Modbus 400524 bit 9; not polled by defaultRead
BI265Aux 1 Pickup Status Flags 1 - Power Factor Log Alarm 1Modbus 400524 bit 10; not polled by defaultRead
BI266Aux 1 Pickup Status Flags 1 - Ppower Factor Log Alarm 2Modbus 400524 bit 11; not polled by defaultRead
BI267Aux 1 Pickup Status Flags 1 - Positive Real Power AlarmModbus 400524 bit 12; not polled by defaultRead
BI268Aux 1 Pickup Status Flags 1 - Neg Real Power AlarmModbus 400524 bit 13; not polled by defaultRead
BI269Aux 1 Pickup Status Flags 1 - Pos Reactive Power AlarmModbus 400524 bit 14; not polled by defaultRead
BI270Aux 1 Pickup Status Flags 1 - Neg Reactive Powere AlarmModbus 400524 bit 15; not polled by defaultRead
BI271Aux 1 Active Status Flags 2 - Underfrequency AlarmModbus 400525 bit 0; not polled by defaultRead
BI272Aux 1 Active Status Flags 2 - Overfrequency AlarmModbus 400525 bit 1; not polled by defaultRead
BI273Aux 1 Active Status Flags 2 - Positive Real Power Demand AlarmModbus 400525 bit 2; not polled by defaultRead
BI274Aux 1 Active Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400525 bit 3; not polled by defaultRead
BI275Aux 1 Active Status Flags 2 - Appartent Power Demand AlarmModbus 400525 bit 4; not polled by defaultRead
BI276Aux 1 Active Status Flags 2 - Ph A Current Demand AlarmModbus 400525 bit 5; not polled by defaultRead
BI277Aux 1 Active Status Flags 2 - Ph B Current Demand AlarmModbus 400525 bit 6; not polled by defaultRead
BI278Aux 1 Active Status Flags 2 - Ph C Current Demand AlarmModbus 400525 bit 7; not polled by defaultRead
BI279Aux 1 Active Status Flags 2 - Nuetral Current Demand AlarmModbus 400525 bit 8; not polled by defaultRead
BI280Aux 1 Active Status Flags 2 - Switch A AlarmModbus 400525 bit 9; not polled by defaultRead
BI281Aux 1 Active Status Flags 2 - Switch B AlarmModbus 400525 bit 10; not polled by defaultRead
BI282Aux 1 Active Status Flags 2 - Switch C AlarmModbus 400525 bit 11; not polled by defaultRead
BI283Aux 1 Active Status Flags 2 - Switch D AlarmModbus 400525 bit 12; not polled by defaultRead
BI284Aux 1 Active Status Flags 2 - Internal Fault AlarmModbus 400525 bit 13; not polled by defaultRead
BI285Aux 1 Active Status Flags 2 - Serial COM1 Failure AlarmModbus 400525 bit 14; not polled by defaultRead
BI286Aux 1 Active Status Flags 2 - Serial COM2 Failure AlarmModbus 400525 bit 15; not polled by defaultRead
BI287Aux 1 Pickup Status Flags 2 - Underfrequency AlarmModbus 400526 bit 0; not polled by defaultRead
BI288Aux 1 Pickup Status Flags 2 - Overfrequency AlarmModbus 400526 bit 1; not polled by defaultRead
BI289Aux 1 Pickup Status Flags 2 - Positive Real Power Demand AlarmModbus 400526 bit 2; not polled by defaultRead
BI290Aux 1 Pickup Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400526 bit 3; not polled by defaultRead
BI291Aux 1 Pickup Status Flags 2 - Appartent Power Demand AlarmModbus 400526 bit 4; not polled by defaultRead
BI292Aux 1 Pickup Status Flags 2 - Ph A Current Demand AlarmModbus 400526 bit 5; not polled by defaultRead
BI293Aux 1 Pickup Status Flags 2 - Ph B Current Demand AlarmModbus 400526 bit 6; not polled by defaultRead
BI294Aux 1 Pickup Status Flags 2 - Ph C Current DemanD AlarmModbus 400526 bit 7; not polled by defaultRead
BI295Aux 1 Pickup Status Flags 2 - Nuetral Current Demand AlarmModbus 400526 bit 8; not polled by defaultRead
BI296Aux 1 Pickup Status Flags 2 - Switch A AlarmModbus 400526 bit 9; not polled by defaultRead
BI297Aux 1 Pickup Status Flags 2 - Switch B AlarmModbus 400526 bit 10; not polled by defaultRead
BI298Aux 1 Pickup Status Flags 2 - Switch C AlarmModbus 400526 bit 11; not polled by defaultRead
BI299Aux 1 Pickup Status Flags 2 - Switch D AlarmModbus 400526 bit 12; not polled by defaultRead
BI300Aux 1 Pickup Status Flags 2 - Internal Fault AlarmModbus 400526 bit 13; not polled by defaultRead
BI301Aux 1 Pickup Status Flags 2 - Serial COM1 Failure AlarmModbus 400526 bit 14; not polled by defaultRead
BI302Aux 1 Pickup Status Flags 2 - Serial COM2 Failure AlarmModbus 400526 bit 15; not polled by defaultRead
BI303Aux 1 Active Status Flags 3 - Clock Not Set AlarmModbus 400527 bit 0; not polled by defaultRead
BI304Aux 1 Active Status Flags 3 - Parameters Not Set AlarmModbus 400527 bit 1; not polled by defaultRead
BI305Aux 1 Active Status Flags 3 - Pulse Input 1 AlarmModbus 400527 bit 2; not polled by defaultRead
BI306Aux 1 Active Status Flags 3 - Current THD AlarmModbus 400527 bit 3; not polled by defaultRead
BI307Aux 1 Active Status Flags 3 - Voltage THD AlarmModbus 400527 bit 4; not polled by defaultRead
BI308Aux 1 Active Status Flags 3 - Analog Input Main AlarmModbus 400527 bit 5; not polled by defaultRead
BI309Aux 1 Active Status Flags 3 - Analog Input Alt AlarmModbus 400527 bit 6; not polled by defaultRead
BI310Aux 1 Active Status Flags 3 - Data Log 1Modbus 400527 bit 7; not polled by defaultRead
BI311Aux 1 Active Status Flags 3 - Data Log 2Modbus 400527 bit 8; not polled by defaultRead
BI312Aux 1 Active Status Flags 3 - Negative Real Power Demand AlarmModbus 400527 bit 9; not polled by defaultRead
BI313Aux 1 Active Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400527 bit 10; not polled by defaultRead
BI314Aux 1 Active Status Flags 3 - Pulse Input 2 AlarmModbus 400527 bit 11; not polled by defaultRead
BI315Aux 1 Active Status Flags 3 - Pulse Input 3 AlarmModbus 400527 bit 12; not polled by defaultRead
BI316Aux 1 Active Status Flags 3 - Pulse Input 4 AlarmModbus 400527 bit 13; not polled by defaultRead
BI317Aux 1 Active Status Flags 3 - Totalized Pulse In AlarmModbus 400527 bit 14; not polled by defaultRead
BI318Aux 1 Active Status Flags 3 - Time AlarmModbus 400527 bit 15; not polled by defaultRead
BI319Aux 1 Pickup Status Flags 3 - Clock Not Set AlarmModbus 400528 bit 0; not polled by defaultRead
BI320Aux 1 Pickup Status Flags 3 - Parameters Not Set AlarmModbus 400528 bit 1; not polled by defaultRead
BI321Aux 1 Pickup Status Flags 3 - Pulse Input 1 AlarmModbus 400528 bit 2; not polled by defaultRead
BI322Aux 1 Pickup Status Flags 3 - Current THD AlarmModbus 400528 bit 3; not polled by defaultRead
BI323Aux 1 Pickup Status Flags 3 - Voltage THD AlarmModbus 400528 bit 4; not polled by defaultRead
BI324Aux 1 Pickup Status Flags 3 - Analog Input Main AlarmModbus 400528 bit 5; not polled by defaultRead
BI325Aux 1 Pickup Status Flags 3 - Analog Input Alt AlarmModbus 400528 bit 6; not polled by defaultRead
BI326Aux 1 Pickup Status Flags 3 - Data Log 1Modbus 400528 bit 7; not polled by defaultRead
BI327Aux 1 Pickup Status Flags 3 - Data Log 2Modbus 400528 bit 8; not polled by defaultRead
BI328Aux 1 Pickup Status Flags 3 - Negative Real Power Demand AlarmModbus 400528 bit 9; not polled by defaultRead
BI329Aux 1 Pickup Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400528 bit 10; not polled by defaultRead
BI330Aux 1 Pickup Status Flags 3 - Pulse Input 2 AlarmModbus 400528 bit 11; not polled by defaultRead
BI331Aux 1 Pickup Status Flags 3 - Pulse Input 3 AlarmModbus 400528 bit 12; not polled by defaultRead
BI332Aux 1 Pickup Status Flags 3 - Pulse Input 4 AlarmModbus 400528 bit 13; not polled by defaultRead
BI333Aux 1 Pickup Status Flags 3 - Totalized Pulse In AlarmModbus 400528 bit 14; not polled by defaultRead
BI334Aux 1 Pickup Status Flags 3 - Time AlarmModbus 400528 bit 15; not polled by defaultRead
BI335Aux 2 Active Status Flags 1 - Phase Undercurrent AlarmModbus 400529 bit 0; not polled by defaultRead
BI336Aux 2 Active Status Flags 1 - Phase Overcurrent AlarmModbus 400529 bit 1; not polled by defaultRead
BI337Aux 2 Active Status Flags 1 - Neutral Overcurrent AlarmModbus 400529 bit 2; not polled by defaultRead
BI338Aux 2 Active Status Flags 1 - Undervoltage AlarmModbus 400529 bit 3; not polled by defaultRead
BI339Aux 2 Active Status Flags 1 - Overvoltage AlarmModbus 400529 bit 4; not polled by defaultRead
BI340Aux 2 Active Status Flags 1 - Current Unbalance AlarmModbus 400529 bit 5; not polled by defaultRead
BI341Aux 2 Active Status Flags 1 - Voltage Unbalance AlarmModbus 400529 bit 6; not polled by defaultRead
BI342Aux 2 Active Status Flags 1 - Voltage Phase Reversal AlarmModbus 400529 bit 7; not polled by defaultRead
BI343Aux 2 Active Status Flags 1 - PF Lead Alarm 1Modbus 400529 bit 8; not polled by defaultRead
BI344Aux 2 Active Status Flags 1 - PF Lead Alarm 2Modbus 400529 bit 9; not polled by defaultRead
BI345Aux 2 Active Status Flags 1 - Power Factor Log AlarmModbus 400529 bit 10; not polled by defaultRead
BI346Aux 2 Active Status Flags 1 - Ppower Factor Log AlarmModbus 400529 bit 11; not polled by defaultRead
BI347Aux 2 Active Status Flags 1 - Positive Real Power AlarmModbus 400529 bit 12; not polled by defaultRead
BI348Aux 2 Active Status Flags 1 - Neg Real Power AlarmModbus 400529 bit 13; not polled by defaultRead
BI349Aux 2 Active Status Flags 1 - Pos Reactive Power AlarmModbus 400529 bit 14; not polled by defaultRead
BI350Aux 2 Active Status Flags 1 - Neg Reactive Powere AlarmModbus 400529 bit 15; not polled by defaultRead
BI351Aux 2 Pickup Status Flags 1 - Phase Undercurrent AlarmModbus 400530 bit 0; not polled by defaultRead
BI352Aux 2 Pickup Status Flags 1 - Phase Overcurrent AlarmModbus 400530 bit 1; not polled by defaultRead
BI353Aux 2 Pickup Status Flags 1 - Neutral Overcurrent AlarmModbus 400530 bit 2; not polled by defaultRead
BI354Aux 2 Pickup Status Flags 1 - Undervoltage AlarmModbus 400530 bit 3; not polled by defaultRead
BI355Aux 2 Pickup Status Flags 1 - Overvoltage AlarmModbus 400530 bit 4; not polled by defaultRead
BI356Aux 2 Pickup Status Flags 1 - Current Unbalance AlarmModbus 400530 bit 5; not polled by defaultRead
BI357Aux 2 Pickup Status Flags 1 - Voltage Unbalance AlarmModbus 400530 bit 6; not polled by defaultRead
BI358Aux 2 Pickup Status Flags 1 - Voltage Phase Reversal AlarmModbus 400530 bit 7; not polled by defaultRead
BI359Aux 2 Pickup Status Flags 1 - PF Lead Alarm 1Modbus 400530 bit 8; not polled by defaultRead
BI360Aux 2 Pickup Status Flags 1 - PF Lead Alarm 2Modbus 400530 bit 9; not polled by defaultRead
BI361Aux 2 Pickup Status Flags 1 - Power Factor Log AlarmModbus 400530 bit 10; not polled by defaultRead
BI362Aux 2 Pickup Status Flags 1 - Power Factor Log Alarm 2Modbus 400530 bit 11; not polled by defaultRead
BI363Aux 2 Pickup Status Flags 1 - Positive Real Power AlarmModbus 400530 bit 12; not polled by defaultRead
BI364Aux 2 Pickup Status Flags 1 - Neg Real Power AlarmModbus 400530 bit 13; not polled by defaultRead
BI365Aux 2 Pickup Status Flags 1 - Pos Reactive Power AlarmModbus 400530 bit 14; not polled by defaultRead
BI366Aux 2 Pickup Status Flags 1 - Neg Reactive Powere AlarmModbus 400530 bit 15; not polled by defaultRead
BI367Aux 2 Active Status Flags 2 - Underfrequency AlarmModbus 400531 bit 0; not polled by defaultRead
BI368Aux 2 Active Status Flags 2 - Overfrequency AlarmModbus 400531 bit 1; not polled by defaultRead
BI369Aux 2 Active Status Flags 2 - Positive Real Power Demand AlarmModbus 400531 bit 2; not polled by defaultRead
BI370Aux 2 Active Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400531 bit 3; not polled by defaultRead
BI371Aux 2 Active Status Flags 2 - Appartent Power Demand AlarmModbus 400531 bit 4; not polled by defaultRead
BI372Aux 2 Active Status Flags 2 - Ph A Current Demand AlarmModbus 400531 bit 5; not polled by defaultRead
BI373Aux 2 Active Status Flags 2 - Ph B Current Demand AlarmModbus 400531 bit 6; not polled by defaultRead
BI374Aux 2 Active Status Flags 2 - Ph C Current DemanD AlarmModbus 400531 bit 7; not polled by defaultRead
BI375Aux 2 Active Status Flags 2 - Nuetral Current Demand AlarmModbus 400531 bit 8; not polled by defaultRead
BI376Aux 2 Active Status Flags 2 - Switch A AlarmModbus 400531 bit 9; not polled by defaultRead
BI377Aux 2 Active Status Flags 2 - Switch B AlarmModbus 400531 bit 10; not polled by defaultRead
BI378Aux 2 Active Status Flags 2 - Switch C AlarmModbus 400531 bit 11; not polled by defaultRead
BI379Aux 2 Active Status Flags 2 - Switch D AlarmModbus 400531 bit 12; not polled by defaultRead
BI380Aux 2 Active Status Flags 2 - Internal Fault AlarmModbus 400531 bit 13; not polled by defaultRead
BI381Aux 2 Active Status Flags 2 - Serial COM1 Failure AlarmModbus 400531 bit 14; not polled by defaultRead
BI382Aux 2 Active Status Flags 2 - Serial COM2 Failure AlarmModbus 400531 bit 15; not polled by defaultRead
BI383Aux 2 Pickup Status Flags 2 - Underfrequency AlarmModbus 400532 bit 0; not polled by defaultRead
BI384Aux 2 Pickup Status Flags 2 - Overfrequency AlarmModbus 400532 bit 1; not polled by defaultRead
BI385Aux 2 Pickup Status Flags 2 - Positive Real Power Demand AlarmModbus 400532 bit 2; not polled by defaultRead
BI386Aux 2 Pickup Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400532 bit 3; not polled by defaultRead
BI387Aux 2 Pickup Status Flags 2 - Appartent Power Demand AlarmModbus 400532 bit 4; not polled by defaultRead
BI388Aux 2 Pickup Status Flags 2 - Ph A Current Demand AlarmModbus 400532 bit 5; not polled by defaultRead
BI389Aux 2 Pickup Status Flags 2 - Ph B Current Demand AlarmModbus 400532 bit 6; not polled by defaultRead
BI390Aux 2 Pickup Status Flags 2 - Ph C Current DemanD AlarmModbus 400532 bit 7; not polled by defaultRead
BI391Aux 2 Pickup Status Flags 2 - Nuetral Current Demand AlarmModbus 400532 bit 8; not polled by defaultRead
BI392Aux 2 Pickup Status Flags 2 - Switch A AlarmModbus 400532 bit 9; not polled by defaultRead
BI393Aux 2 Pickup Status Flags 2 - Switch B AlarmModbus 400532 bit 10; not polled by defaultRead
BI394Aux 2 Pickup Status Flags 2 - Switch C AlarmModbus 400532 bit 11; not polled by defaultRead
BI395Aux 2 Pickup Status Flags 2 - Switch D AlarmModbus 400532 bit 12; not polled by defaultRead
BI396Aux 2 Pickup Status Flags 2 - Internal Fault AlarmModbus 400532 bit 13; not polled by defaultRead
BI397Aux 2 Pickup Status Flags 2 - Serial COM1 Failure AlarmModbus 400532 bit 14; not polled by defaultRead
BI398Aux 2 Pickup Status Flags 2 - Serial COM2 Failure AlarmModbus 400532 bit 15; not polled by defaultRead
BI399Aux 2 Active Status Flags 3 - Clock Not Set AlarmModbus 400533 bit 0; not polled by defaultRead
BI400Aux 2 Active Status Flags 3 - Parameters Not Set AlarmModbus 400533 bit 1; not polled by defaultRead
BI401Aux 2 Active Status Flags 3 - Pulse Input 1 AlarmModbus 400533 bit 2; not polled by defaultRead
BI402Aux 2 Active Status Flags 3 - Current THD AlarmModbus 400533 bit 3; not polled by defaultRead
BI403Aux 2 Active Status Flags 3 - Voltage THD AlarmModbus 400533 bit 4; not polled by defaultRead
BI404Aux 2 Active Status Flags 3 - Analog Input Main AlarmModbus 400533 bit 5; not polled by defaultRead
BI405Aux 2 Active Status Flags 3 - Analog Input Alt AlarmModbus 400533 bit 6; not polled by defaultRead
BI406Aux 2 Active Status Flags 3 - Data Log 1Modbus 400533 bit 7; not polled by defaultRead
BI407Aux 2 Active Status Flags 3 - Data Log 2Modbus 400533 bit 8; not polled by defaultRead
BI408Aux 2 Active Status Flags 3 - Negative Real Power Demand AlarmModbus 400533 bit 9; not polled by defaultRead
BI409Aux 2 Active Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400533 bit 10; not polled by defaultRead
BI410Aux 2 Active Status Flags 3 - Pulse Input 2 AlarmModbus 400533 bit 11; not polled by defaultRead
BI411Aux 2 Active Status Flags 3 - Pulse Input 3 AlarmModbus 400533 bit 12; not polled by defaultRead
BI412Aux 2 Active Status Flags 3 - Pulse Input 4 AlarmModbus 400533 bit 13; not polled by defaultRead
BI413Aux 2 Active Status Flags 3 - Totalized Pulse In AlarmModbus 400533 bit 14; not polled by defaultRead
BI414Aux 2 Active Status Flags 3 - Time AlarmModbus 400533 bit 15; not polled by defaultRead
BI415Aux 2 Pickup Status Flags 3 - Clock Not Set AlarmModbus 400534 bit 0; not polled by defaultRead
BI416Aux 2 Pickup Status Flags 3 - Parameters Not Set AlarmModbus 400534 bit 1; not polled by defaultRead
BI417Aux 2 Pickup Status Flags 3 - Pulse Input 1 AlarmModbus 400534 bit 2; not polled by defaultRead
BI418Aux 2 Pickup Status Flags 3 - Current THD AlarmModbus 400534 bit 3; not polled by defaultRead
BI419Aux 2 Pickup Status Flags 3 - Voltage THD AlarmModbus 400534 bit 4; not polled by defaultRead
BI420Aux 2 Pickup Status Flags 3 - Analog Input Main AlarmModbus 400534 bit 5; not polled by defaultRead
BI421Aux 2 Pickup Status Flags 3 - Analog Input Alt AlarmModbus 400534 bit 6; not polled by defaultRead
BI422Aux 2 Pickup Status Flags 3 - Data Log 1Modbus 400534 bit 7; not polled by defaultRead
BI423Aux 2 Pickup Status Flags 3 - Data Log 2Modbus 400534 bit 8; not polled by defaultRead
BI424Aux 2 Pickup Status Flags 3 - Negative Real Power Demand AlarmModbus 400534 bit 9; not polled by defaultRead
BI425Aux 2 Pickup Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400534 bit 10; not polled by defaultRead
BI426Aux 2 Pickup Status Flags 3 - Pulse Input 2 Aux 2Modbus 400534 bit 11; not polled by defaultRead
BI427Aux 2 Pickup Status Flags 3 - Pulse Input 3 AlarmModbus 400534 bit 12; not polled by defaultRead
BI428Aux 2 Pickup Status Flags 3 - Pulse Input 4 AlarmModbus 400534 bit 13; not polled by defaultRead
BI429Aux 2 Pickup Status Flags 3 - Totalized Pulse In AlarmModbus 400534 bit 14; not polled by defaultRead
BI430Aux 2 Pickup Status Flags 3 - Time AlarmModbus 400534 bit 15; not polled by defaultRead
BI431Aux 3 Active Status Flags 1 - Phase Undercurrent AlarmModbus 400535 bit 0; not polled by defaultRead
BI432Aux 3 Active Status Flags 1 - Phase Overcurrent AlarmModbus 400535 bit 1; not polled by defaultRead
BI433Aux 3 Active Status Flags 1 - Neutral Overcurrent AlarmModbus 400535 bit 2; not polled by defaultRead
BI434Aux 3 Active Status Flags 1 - Undervoltage AlarmModbus 400535 bit 3; not polled by defaultRead
BI435Aux 3 Active Status Flags 1 - Overvoltage AlarmModbus 400535 bit 4; not polled by defaultRead
BI436Aux 3 Active Status Flags 1 - Current Unbalance AlarmModbus 400535 bit 5; not polled by defaultRead
BI437Aux 3 Active Status Flags 1 - Voltage Unbalance AlarmModbus 400535 bit 6; not polled by defaultRead
BI438Aux 3 Active Status Flags 1 - Voltage Phase Reversal AlarmModbus 400535 bit 7; not polled by defaultRead
BI439Aux 3 Active Status Flags 1 - PF Lead Alarm 1Modbus 400535 bit 8; not polled by defaultRead
BI440Aux 3 Active Status Flags 1 - PF Lead Alarm 2Modbus 400535 bit 9; not polled by defaultRead
BI441Aux 3 Active Status Flags 1 - Power Factor Log AlarmModbus 400535 bit 10; not polled by defaultRead
BI442Aux 3 Active Status Flags 1 - Ppower Factor Log AlarmModbus 400535 bit 11; not polled by defaultRead
BI443Aux 3 Active Status Flags 1 - Positive Real Power AlarmModbus 400535 bit 12; not polled by defaultRead
BI444Aux 3 Active Status Flags 1 - Neg Real Power AlarmModbus 400535 bit 13; not polled by defaultRead
BI445Aux 3 Active Status Flags 1 - Pos Reactive Power AlarmModbus 400535 bit 14; not polled by defaultRead
BI446Aux 3 Active Status Flags 1 - Neg Reactive Powere AlarmModbus 400535 bit 15; not polled by defaultRead
BI447Aux 3 Pickup Status Flags 1 - Phase Undercurrent AlarmModbus 400536 bit 0; not polled by defaultRead
BI448Aux 3 Pickup Status Flags 1 - Phase Overcurrent AlarmModbus 400536 bit 1; not polled by defaultRead
BI449Aux 3 Pickup Status Flags 1 - Neutral Overcurrent AlarmModbus 400536 bit 2; not polled by defaultRead
BI450Aux 3 Pickup Status Flags 1 - Undervoltage AlarmModbus 400536 bit 3; not polled by defaultRead
BI451Aux 3 Pickup Status Flags 1 - Overvoltage AlarmModbus 400536 bit 4; not polled by defaultRead
BI452Aux 3 Pickup Status Flags 1 - Current Unbalance AlarmModbus 400536 bit 5; not polled by defaultRead
BI453Aux 3 Pickup Status Flags 1 - Voltage Unbalance AlarmModbus 400536 bit 6; not polled by defaultRead
BI454Aux 3 Pickup Status Flags 1 - Voltage Phase Reversal AlarmModbus 400536 bit 7; not polled by defaultRead
BI455Aux 3 Pickup Status Flags 1 - PF Lead Alarm 1Modbus 400536 bit 8; not polled by defaultRead
BI456Aux 3 Pickup Status Flags 1 - PF Lead Alarm 2Modbus 400536 bit 9; not polled by defaultRead
BI457Aux 3 Pickup Status Flags 1 - Power Factor Log AlarmModbus 400536 bit 10; not polled by defaultRead
BI458Aux 3 Pickup Status Flags 1 - Power Factor Log Alarm 2Modbus 400536 bit 11; not polled by defaultRead
BI459Aux 3 Pickup Status Flags 1 - Positive Real Power AlarmModbus 400536 bit 12; not polled by defaultRead
BI460Aux 3 Pickup Status Flags 1 - Neg Real Power AlarmModbus 400536 bit 13; not polled by defaultRead
BI461Aux 3 Pickup Status Flags 1 - Pos Reactive Power AlarmModbus 400536 bit 14; not polled by defaultRead
BI462Aux 3 Pickup Status Flags 1 - Neg Reactive Powere AlarmModbus 400536 bit 15; not polled by defaultRead
BI463Aux 3 Active Status Flags 2 - Underfrequency AlarmModbus 400537 bit 0; not polled by defaultRead
BI464Aux 3 Active Status Flags 2 - Overfrequency AlarmModbus 400537 bit 1; not polled by defaultRead
BI465Aux 3 Active Status Flags 2 - Positive Real Power Demand AlarmModbus 400537 bit 2; not polled by defaultRead
BI466Aux 3 Active Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400537 bit 3; not polled by defaultRead
BI467Aux 3 Active Status Flags 2 - Appartent Power Demand AlarmModbus 400537 bit 4; not polled by defaultRead
BI468Aux 3 Active Status Flags 2 - Ph A Current Demand AlarmModbus 400537 bit 5; not polled by defaultRead
BI469Aux 3 Active Status Flags 2 - Ph B Current Demand AlarmModbus 400537 bit 6; not polled by defaultRead
BI470Aux 3 Active Status Flags 2 - Ph C Current DemanD AlarmModbus 400537 bit 7; not polled by defaultRead
BI471Aux 3 Active Status Flags 2 - Nuetral Current Demand AlarmModbus 400537 bit 8; not polled by defaultRead
BI472Aux 3 Active Status Flags 2 - Switch A AlarmModbus 400537 bit 9; not polled by defaultRead
BI473Aux 3 Active Status Flags 2 - Switch B AlarmModbus 400537 bit 10; not polled by defaultRead
BI474Aux 3 Active Status Flags 2 - Switch C AlarmModbus 400537 bit 11; not polled by defaultRead
BI475Aux 3 Active Status Flags 2 - Switch D AlarmModbus 400537 bit 12; not polled by defaultRead
BI476Aux 3 Active Status Flags 2 - Internal Fault AlarmModbus 400537 bit 13; not polled by defaultRead
BI477Aux 3 Active Status Flags 2 - Serial COM1 Failure AlarmModbus 400537 bit 14; not polled by defaultRead
BI478Aux 3 Active Status Flags 2 - Serial COM2 Failure AlarmModbus 400537 bit 15; not polled by defaultRead
BI479Aux 3 Pickup Status Flags 2 - Underfrequency AlarmModbus 400538 bit 0; not polled by defaultRead
BI480Aux 3 Pickup Status Flags 2 - Overfrequency AlarmModbus 400538 bit 1; not polled by defaultRead
BI481Aux 3 Pickup Status Flags 2 - Positive Real Power Demand AlarmModbus 400538 bit 2; not polled by defaultRead
BI482Aux 3 Pickup Status Flags 2 - Positive Reactive Power Demand AlarmModbus 400538 bit 3; not polled by defaultRead
BI483Aux 3 Pickup Status Flags 2 - Appartent Power Demand AlarmModbus 400538 bit 4; not polled by defaultRead
BI484Aux 3 Pickup Status Flags 2 - Ph A Current Demand AlarmModbus 400538 bit 5; not polled by defaultRead
BI485Aux 3 Pickup Status Flags 2 - Ph B Current Demand AlarmModbus 400538 bit 6; not polled by defaultRead
BI486Aux 3 Pickup Status Flags 2 - Ph C Current DemanD AlarmModbus 400538 bit 7; not polled by defaultRead
BI487Aux 3 Pickup Status Flags 2 - Nuetral Current Demand AlarmModbus 400538 bit 8; not polled by defaultRead
BI488Aux 3 Pickup Status Flags 2 - Switch A AlarmModbus 400538 bit 9; not polled by defaultRead
BI489Aux 3 Pickup Status Flags 2 - Switch B AlarmModbus 400538 bit 10; not polled by defaultRead
BI490Aux 3 Pickup Status Flags 2 - Switch C AlarmModbus 400538 bit 11; not polled by defaultRead
BI491Aux 3 Pickup Status Flags 2 - Switch D AlarmModbus 400538 bit 12; not polled by defaultRead
BI492Aux 3 Pickup Status Flags 2 - Internal Fault AlarmModbus 400538 bit 13; not polled by defaultRead
BI493Aux 3 Pickup Status Flags 2 - Serial COM1 Failure AlarmModbus 400538 bit 14; not polled by defaultRead
BI494Aux 3 Pickup Status Flags 2 - Serial COM2 Failure AlarmModbus 400538 bit 15; not polled by defaultRead
BI495Aux 3 Active Status Flags 3 - Clock Not Set AlarmModbus 400539 bit 0; not polled by defaultRead
BI496Aux 3 Active Status Flags 3 - Parameters Not Set AlarmModbus 400539 bit 1; not polled by defaultRead
BI497Aux 3 Active Status Flags 3 - Pulse Input 1 AlarmModbus 400539 bit 2; not polled by defaultRead
BI498Aux 3 Active Status Flags 3 - Current THD AlarmModbus 400539 bit 3; not polled by defaultRead
BI499Aux 3 Active Status Flags 3 - Voltage THD AlarmModbus 400539 bit 4; not polled by defaultRead
BI500Aux 3 Active Status Flags 3 - Analog Input Main AlarmModbus 400539 bit 5; not polled by defaultRead
BI501Aux 3 Active Status Flags 3 - Analog Input Alt AlarmModbus 400539 bit 6; not polled by defaultRead
BI502Aux 3 Active Status Flags 3 - Data Log 1Modbus 400539 bit 7; not polled by defaultRead
BI503Aux 3 Active Status Flags 3 - Data Log 2Modbus 400539 bit 8; not polled by defaultRead
BI504Aux 3 Active Status Flags 3 - Negative Real Power Demand AlarmModbus 400539 bit 9; not polled by defaultRead
BI505Aux 3 Active Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400539 bit 10; not polled by defaultRead
BI506Aux 3 Active Status Flags 3 - Pulse Input 2 AlarmModbus 400539 bit 11; not polled by defaultRead
BI507Aux 3 Active Status Flags 3 - Pulse Input 3 AlarmModbus 400539 bit 12; not polled by defaultRead
BI508Aux 3 Active Status Flags 3 - Pulse Input 4 AlarmModbus 400539 bit 13; not polled by defaultRead
BI509Aux 3 Active Status Flags 3 - Totalized Pulse In AlarmModbus 400539 bit 14; not polled by defaultRead
BI510Aux 3 Active Status Flags 3 - Time AlarmModbus 400539 bit 15; not polled by defaultRead
BI511Aux 3 Pickup Status Flags 3 - Clock Not Set AlarmModbus 400540 bit 0; not polled by defaultRead
BI512Aux 3 Pickup Status Flags 3 - Parameters Not Set AlarmModbus 400540 bit 1; not polled by defaultRead
BI513Aux 3 Pickup Status Flags 3 - Pulse Input 1 AlarmModbus 400540 bit 2; not polled by defaultRead
BI514Aux 3 Pickup Status Flags 3 - Current THD AlarmModbus 400540 bit 3; not polled by defaultRead
BI515Aux 3 Pickup Status Flags 3 - Voltage THD AlarmModbus 400540 bit 4; not polled by defaultRead
BI516Aux 3 Pickup Status Flags 3 - Analog Input Main AlarmModbus 400540 bit 5; not polled by defaultRead
BI517Aux 3 Pickup Status Flags 3 - Analog Input Alt AlarmModbus 400540 bit 6; not polled by defaultRead
BI518Aux 3 Pickup Status Flags 3 - Data Log 1Modbus 400540 bit 7; not polled by defaultRead
BI519Aux 3 Pickup Status Flags 3 - Data Log 2Modbus 400540 bit 8; not polled by defaultRead
BI520Aux 3 Pickup Status Flags 3 - Negative Real Power Demand AlarmModbus 400540 bit 9; not polled by defaultRead
BI521Aux 3 Pickup Status Flags 3 - Negative Reactive Power Demand AlarmModbus 400540 bit 10; not polled by defaultRead
BI522Aux 3 Pickup Status Flags 3 - Pulse Input 2 Aux 3Modbus 400540 bit 11; not polled by defaultRead
BI523Aux 3 Pickup Status Flags 3 - Pulse Input 3 AlarmModbus 400540 bit 12; not polled by defaultRead
BI524Aux 3 Pickup Status Flags 3 - Pulse Input 4 AlarmModbus 400540 bit 13; not polled by defaultRead
BI525Aux 3 Pickup Status Flags 3 - Totalized Pulse In AlarmModbus 400540 bit 14; not polled by defaultRead
BI526Aux 3 Pickup Status Flags 3 - Time AlarmModbus 400540 bit 15; not polled by defaultRead
BI527Alarm PresentModbus 400541 bit 0; not polled by defaultRead
BI528Clock Not SetModbus 400541 bit 1; not polled by defaultRead
BI529Clock DriftingModbus 400541 bit 2; not polled by defaultRead
BI530Data Log 1 RunningModbus 400541 bit 3; not polled by defaultRead
BI531Data Log 2 RunningModbus 400541 bit 4; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX GE PQMII point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GE Multilin PQMII via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls GE Multilin PQMII via BASgatewayLX

How many BACnet points does the Contemporary Controls GE Multilin PQMII via BASgatewayLX have?

This list has 531 BACnet objects: 118 analog inputs, 413 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile GE_PQMII_Power_Meter_Lite (GE_PQMII_Power_Meter_Lite_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/GE_PQMII_Power_Meter_Lite_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls GE Multilin PQMII via BASgatewayLX?

Start with AI 46 3 Phase Real Power (3-phase real power); AI 94 3 Phase Positive Real Energy Used (3-phase positive real energy); AI 24 Average Line Voltage (Average line voltage); AI 4 Average Current (Average current); AI 49 3 Phase Power Factor (3-phase power factor); AI 116 Frequency (Frequency); AI 106 3 Phase Real Power Demand (3-phase real power demand); BI 139 Alarm Relay (Alarm relay).

How do I check these points on the real GE Multilin PQMII via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile GE_PQMII_Power_Meter_Lite · GE_PQMII_Power_Meter_Lite_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.