Power and energy meter · BACnet points list
Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the GE PQMII: 531 objects (118 AI, 413 BI), 38 polled by default (currents, voltages, power, PF, demand and frequency). Hundreds of switch, relay, LED and alarm status bits and energy, harmonic and setup values are unpolled.
This page lists 531 BACnet objects for the Contemporary Controls GE Multilin PQMII via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- GE Multilin PQMII via BASgatewayLX
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 531 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls GE Multilin PQMII via BASgatewayLX
Map 3-phase real power, 3-phase positive real energy and average line voltage first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 46 | 3 Phase Real Power | 3-phase real power | Read |
| AI 94 | 3 Phase Positive Real Energy Used | 3-phase positive real energy | Read |
| AI 24 | Average Line Voltage | Average line voltage | Read |
| AI 4 | Average Current | Average current | Read |
| AI 49 | 3 Phase Power Factor | 3-phase power factor | Read |
| AI 116 | Frequency | Frequency | Read |
| AI 106 | 3 Phase Real Power Demand | 3-phase real power demand | Read |
| BI 139 | Alarm Relay | Alarm relay | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Phase A Current | Modbus 400577 | A | Read | |
| AI | 2 | Phase B Current | Modbus 400578 | A | Read | |
| AI | 3 | Phase C Current | Modbus 400579 | A | Read | |
| AImin | 4 | Average Current | Modbus 400580 | A | Read | |
| AI | 5 | Neutral Current | Modbus 400581 | A | Read | |
| AI | 6 | Current Unbalance | Modbus 400582 | % | Read | |
| AI | 7 | Phase A Current - Minimum | Modbus 400583; not polled by default | A | Read | |
| AI | 8 | Phase B Current - Minimum | Modbus 400584; not polled by default | A | Read | |
| AI | 9 | Phase C Current - Minimum | Modbus 400585; not polled by default | A | Read | |
| AI | 10 | Neutral Current - Minimum | Modbus 400586; not polled by default | A | Read | |
| AI | 11 | Current Unbalance - Minimum | Modbus 400587; not polled by default | % | Read | |
| AI | 12 | Phase A Current - Maximum | Modbus 400588; not polled by default | A | Read | |
| AI | 13 | Phase B Current - Maximum | Modbus 400589; not polled by default | A | Read | |
| AI | 14 | Phase C Current - Maximum | Modbus 400590; not polled by default | A | Read | |
| AI | 15 | Neutral Current - Maximum | Modbus 400591; not polled by default | A | Read | |
| AI | 16 | Current Unbalance - Maximum | Modbus 400592; not polled by default | % | Read | |
| AI | 17 | Voltage Van | Modbus 400641 | V | Read | |
| AI | 18 | Voltage Vbn | Modbus 400643 | V | Read | |
| AI | 19 | Voltage Vcn | Modbus 400645 | V | Read | |
| AI | 20 | Average Phase Voltage | Modbus 400647 | V | Read | |
| AI | 21 | Voltage Vab | Modbus 400649 | V | Read | |
| AI | 22 | Voltage Vbc | Modbus 400651 | V | Read | |
| AI | 23 | Voltage Vca | Modbus 400653 | V | Read | |
| AImin | 24 | Average Line Voltage | Modbus 400655 | V | Read | |
| AI | 25 | Voltage Unbalance | Modbus 400657; not polled by default | % | Read | |
| AI | 26 | Voltage Van - Minimum | Modbus 400658; not polled by default | V | Read | |
| AI | 27 | Voltage Vbn - Minimum | Modbus 400660; not polled by default | V | Read | |
| AI | 28 | Voltage Vcn - Minimum | Modbus 400662; not polled by default | V | Read | |
| AI | 29 | Voltage Vab - Minimum | Modbus 400664; not polled by default | V | Read | |
| AI | 30 | Voltage Vbc - Minimum | Modbus 400666; not polled by default | V | Read | |
| AI | 31 | Voltage Vca - Minimum | Modbus 400668; not polled by default | V | Read | |
| AI | 32 | Voltage Unbalance - Minimum | Modbus 400670; not polled by default | % | Read | |
| AI | 33 | Voltage Van - Maximum | Modbus 400671; not polled by default | V | Read | |
| AI | 34 | Voltage Vbn - Maximum | Modbus 400673; not polled by default | V | Read | |
| AI | 35 | Voltage Vcn - Maximum | Modbus 400675; not polled by default | V | Read | |
| AI | 36 | Voltage Vab - Maximum | Modbus 400677; not polled by default | V | Read | |
| AI | 37 | Voltage Vbc - Maximum | Modbus 400679; not polled by default | V | Read | |
| AI | 38 | Voltage Vca - Maximum | Modbus 400681; not polled by default | V | Read | |
| AI | 39 | Voltage Unbalance - Maximum | Modbus 400683; not polled by default | % | Read | |
| AI | 40 | Va Phasor Angle | Modbus 400744; not polled by default | ° | Read | |
| AI | 41 | Vb Phasor Angle | Modbus 400745; not polled by default | ° | Read | |
| AI | 42 | Vc Phasor Angle | Modbus 400746; not polled by default | ° | Read | |
| AI | 43 | Ia Phasor Angle | Modbus 400747; not polled by default | ° | Read | |
| AI | 44 | Ib Phasor Angle | Modbus 400748; not polled by default | ° | Read | |
| AI | 45 | Ic Phasor Angle | Modbus 400749; not polled by default | ° | Read | |
| AImin | 46 | 3 Phase Real Power | Modbus 400753 | kW | Read | |
| AI | 47 | 3 Phase Reactive Power | Modbus 400755 | kVAR | Read | |
| AI | 48 | 3 Phase Apparent Power | Modbus 400757 | kVA | Read | |
| AImin | 49 | 3 Phase Power Factor | Modbus 400759 | PF | Read | |
| AI | 50 | Phase A Real Power | Modbus 400760 | kW | Read | |
| AI | 51 | Phase A Reactive Power | Modbus 400762 | kVAR | Read | |
| AI | 52 | Phase A Apparent Power | Modbus 400764 | kVA | Read | |
| AI | 53 | Phase A Power Factor | Modbus 400766 | PF | Read | |
| AI | 54 | Phase B Real Power | Modbus 400767 | kW | Read | |
| AI | 55 | Phase B Reactive Power | Modbus 400769 | kVAR | Read | |
| AI | 56 | Phase B Apparent Power | Modbus 400771 | kVA | Read | |
| AI | 57 | Phase B Power Factor | Modbus 400773 | PF | Read | |
| AI | 58 | Phase C Real Power | Modbus 400774 | kW | Read | |
| AI | 59 | Phase C Reactive Power | Modbus 400776 | kVAR | Read | |
| AI | 60 | Phase C Apparent Power | Modbus 400778 | kVA | Read | |
| AI | 61 | Phase C Power Factor | Modbus 400780 | PF | Read | |
| AI | 62 | 3 Phase Real Power - Minimum | Modbus 400781; not polled by default | kW | Read | |
| AI | 63 | 3 Phase Reactive Power - Minimum | Modbus 400783; not polled by default | kVAR | Read | |
| AI | 64 | 3 Phase Apparent Power - Minimum | Modbus 400785; not polled by default | kVA | Read | |
| AI | 65 | 3 Phase Power Factor - Minimum | Modbus 400787; not polled by default | PF | Read | |
| AI | 66 | 3 Phase Real Power - Maximum | Modbus 400788; not polled by default | kW | Read | |
| AI | 67 | 3 Phase Reactive Power - Maximum | Modbus 400790; not polled by default | kVAR | Read | |
| AI | 68 | 3 Phase Apparent Power - Maximum | Modbus 400792; not polled by default | kVA | Read | |
| AI | 69 | 3 Phase Power Factor - Maximum | Modbus 400794; not polled by default | PF | Read | |
| AI | 70 | Phase A Real Power - Minimum | Modbus 400795; not polled by default | kW | Read | |
| AI | 71 | Phase A Reactive Power - Minimum | Modbus 400797; not polled by default | kVAR | Read | |
| AI | 72 | Phase A Apparent Power - Minimum | Modbus 400799; not polled by default | kVA | Read | |
| AI | 73 | Phase A Power Factor - Minimum | Modbus 400801; not polled by default | PF | Read | |
| AI | 74 | Phase A Real Power - Maximum | Modbus 400802; not polled by default | kW | Read | |
| AI | 75 | Phase A Reactive Power - Maximum | Modbus 400804; not polled by default | kVAR | Read | |
| AI | 76 | Phase A Apparent Power - Maximum | Modbus 400806; not polled by default | kVA | Read | |
| AI | 77 | Phase A Power Factor - Maximum | Modbus 400808; not polled by default | PF | Read | |
| AI | 78 | Phase B Real Power - Minimum | Modbus 400809; not polled by default | kW | Read | |
| AI | 79 | Phase B Reactive Power - Minimum | Modbus 400811; not polled by default | kVAR | Read | |
| AI | 80 | Phase B Apparent Power - Minimum | Modbus 400813; not polled by default | kVA | Read | |
| AI | 81 | Phase B Power Factor - Minimum | Modbus 400815; not polled by default | PF | Read | |
| AI | 82 | Phase B Real Power - Maximum | Modbus 400816; not polled by default | kW | Read | |
| AI | 83 | Phase B Reactive Power - Maximum | Modbus 400818; not polled by default | kVAR | Read | |
| AI | 84 | Phase B Apparent Power - Maximum | Modbus 400820; not polled by default | kVA | Read | |
| AI | 85 | Phase B Power Factor - Maximum | Modbus 400822; not polled by default | PF | Read | |
| AI | 86 | Phase C Real Power - Minimum | Modbus 400823; not polled by default | kW | Read | |
| AI | 87 | Phase C Reactive Power - Minimum | Modbus 400825; not polled by default | kVAR | Read | |
| AI | 88 | Phase C Apparent Power - Minimum | Modbus 400827; not polled by default | kVA | Read | |
| AI | 89 | Phase C Power Factor - Minimum | Modbus 400829; not polled by default | PF | Read | |
| AI | 90 | Phase C Real Power - Maximum | Modbus 400830; not polled by default | kW | Read | |
| AI | 91 | Phase C Reactive Power - Maximum | Modbus 400832; not polled by default | kVAR | Read | |
| AI | 92 | Phase C Apparent Power - Maximum | Modbus 400834; not polled by default | kVA | Read | |
| AI | 93 | Phase C Power Factor - Maximum | Modbus 400836; not polled by default | PF | Read | |
| AImin | 94 | 3 Phase Positive Real Energy Used | Modbus 400977; not polled by default | kWh | Read | |
| AI | 95 | 3 Phase Negative Real Energy Used | Modbus 400979; not polled by default | kWh | Read | |
| AI | 96 | 3 Phase Positive React. Energy Used | Modbus 400981; not polled by default | Read | ||
| AI | 97 | 3 Phase Neg Reactive Energy Used | Modbus 400983; not polled by default | Read | ||
| AI | 98 | 3 Phase Apparent Energy Used | Modbus 400985; not polled by default | kWh | Read | |
| AI | 99 | 3 Phase Energy Used in Last 24 h | Modbus 400987; not polled by default | Read | ||
| AI | 100 | 3 Phase Energy Cost Since Reset | Modbus 400989; not polled by default | Read | ||
| AI | 101 | 3 Phase Energy Cost Per Day | Modbus 400991; not polled by default | Read | ||
| AI | 102 | Phase A Current Demand | Modbus 401025 | A | Read | |
| AI | 103 | Phase B Current Demand | Modbus 401026 | A | Read | |
| AI | 104 | Phase C Current Demand | Modbus 401027 | A | Read | |
| AI | 105 | Neutral Current Demand | Modbus 401028 | A | Read | |
| AImin | 106 | 3 Phase Real Power Demand | Modbus 401029 | kW | Read | |
| AI | 107 | 3 Phase React Power Demand | Modbus 401031 | kVAR | Read | |
| AI | 108 | 3 Phase Apparent Power Demand | Modbus 401033 | kVA | Read | |
| AI | 109 | Phase A Current Demand - Maximum | Modbus 401035; not polled by default | A | Read | |
| AI | 110 | Phase B Current Demand - Maximum | Modbus 401036; not polled by default | A | Read | |
| AI | 111 | Phase C Current Demand - Maximum | Modbus 401037; not polled by default | A | Read | |
| AI | 112 | Neutral Current Demand - Maximum | Modbus 401038; not polled by default | A | Read | |
| AI | 113 | 3 Phase Real Power Dmd - Max | Modbus 401039; not polled by default | kW | Read | |
| AI | 114 | 3 Phase React Power Dmd - Max | Modbus 401041; not polled by default | kVAR | Read | |
| AI | 115 | 3 Phase Apparent Power Dmd - Max | Modbus 401043; not polled by default | kVA | Read | |
| AImin | 116 | Frequency | Modbus 401089 | Hz | Read | |
| AI | 117 | Frequency Minimum | Modbus 401090; not polled by default | Hz | Read | |
| AI | 118 | Frequency Maximum | Modbus 401091; not polled by default | Hz | Read | |
| BI | 119 | Switch A Input Status | Modbus 400513 bit 8; not polled by default | Read | ||
| BI | 120 | Switch B Input Status | Modbus 400513 bit 9; not polled by default | Read | ||
| BI | 121 | Switch C Input Status | Modbus 400513 bit 10; not polled by default | Read | ||
| BI | 122 | Switch D Input Status | Modbus 400513 bit 11; not polled by default | Read | ||
| BI | 123 | Aux 1 Relay LED Status Flag | Modbus 400514 bit 0; not polled by default | Read | ||
| BI | 124 | Aux 2 Relay LED Status Flag | Modbus 400514 bit 1; not polled by default | Read | ||
| BI | 125 | Aux 3 Relay LED Status Flag | Modbus 400514 bit 2; not polled by default | Read | ||
| BI | 126 | Alarm LED Status Flag | Modbus 400514 bit 3; not polled by default | Read | ||
| BI | 127 | Program LED Status Flag | Modbus 400514 bit 4; not polled by default | Read | ||
| BI | 128 | Simulation LED Status Flag | Modbus 400514 bit 5; not polled by default | Read | ||
| BI | 129 | Alarm Relay LED Status Flag | Modbus 400514 bit 6; not polled by default | Read | ||
| BI | 130 | Self Test LED Status Flag | Modbus 400514 bit 7; not polled by default | Read | ||
| BI | 131 | Aux 1 Relay LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 0; not polled by default | Read | ||
| BI | 132 | Aux 2 Relay LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 1; not polled by default | Read | ||
| BI | 133 | Aux 3 Relay LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 2; not polled by default | Read | ||
| BI | 134 | Alarm LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 3; not polled by default | Read | ||
| BI | 135 | Program LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 4; not polled by default | Read | ||
| BI | 136 | Simulation LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 5; not polled by default | Read | ||
| BI | 137 | Alarm relay LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 6; not polled by default | Read | ||
| BI | 138 | Self Test LED Attribute Flag Off=Flash ON=Steady | Modbus 400515 bit 7; not polled by default | Read | ||
| BImin | 139 | Alarm Relay | Modbus 400516 bit 0; not polled by default | Read | ||
| BI | 140 | Auxiliary Relay 1 | Modbus 400516 bit 1; not polled by default | Read | ||
| BI | 141 | Auxiliary Relay 2 | Modbus 400516 bit 2; not polled by default | Read | ||
| BI | 142 | Auxiliary Relay 3 | Modbus 400516 bit 3; not polled by default | Read | ||
| BI | 143 | Alarm Active Status Flags 1 - Phase Undercurrent Alarm | Modbus 400517 bit 0; not polled by default | Read | ||
| BI | 144 | Alarm Active Status Flags 1 - Phase Overcurrent Alarm | Modbus 400517 bit 1; not polled by default | Read | ||
| BI | 145 | Alarm Active Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400517 bit 2; not polled by default | Read | ||
| BI | 146 | Alarm Active Status Flags 1 - Undervoltage Alarm | Modbus 400517 bit 3; not polled by default | Read | ||
| BI | 147 | Alarm Active Status Flags 1 - Overvoltage Alarm | Modbus 400517 bit 4; not polled by default | Read | ||
| BI | 148 | Alarm Active Status Flags 1 - Current Unbalance Alarm | Modbus 400517 bit 5; not polled by default | Read | ||
| BI | 149 | Alarm Active Status Flags 1 - Voltage Unbalance Alarm | Modbus 400517 bit 6; not polled by default | Read | ||
| BI | 150 | Alarm Active Status Flags 1 - Voltage Phase Reversal | Modbus 400517 bit 7; not polled by default | Read | ||
| BI | 151 | Alarm Active Status Flags 1 - PF Lead Alarm 1 | Modbus 400517 bit 8; not polled by default | Read | ||
| BI | 152 | Alarm Active Status Flags 1 - PF Lead Alarm 2 | Modbus 400517 bit 9; not polled by default | Read | ||
| BI | 153 | Alarm Active Status Flags 1 - Power Factor Log Alarm 1 | Modbus 400517 bit 10; not polled by default | Read | ||
| BI | 154 | Alarm Active Status Flags 1 - Ppower Factor Log Alarm 2 | Modbus 400517 bit 11; not polled by default | Read | ||
| BI | 155 | Alarm Active Status Flags 1 - Positive Real Power Alarm | Modbus 400517 bit 12; not polled by default | Read | ||
| BI | 156 | Alarm Active Status Flags 1 - Neg Real Power Alarm | Modbus 400517 bit 13; not polled by default | Read | ||
| BI | 157 | Alarm Active Status Flags 1 - Pos Reactive Power Alarm | Modbus 400517 bit 14; not polled by default | Read | ||
| BI | 158 | Alarm Active Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400517 bit 15; not polled by default | Read | ||
| BI | 159 | Alarm Pickup Status Flags 1 - Phase Undercurrent Alarm | Modbus 400518 bit 0; not polled by default | Read | ||
| BI | 160 | Alarm Pickup Status Flags 1 - Phase Overcurrent Alarm | Modbus 400518 bit 1; not polled by default | Read | ||
| BI | 161 | Alarm Pickup Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400518 bit 2; not polled by default | Read | ||
| BI | 162 | Alarm Pickup Status Flags 1 - Undervoltage Alarm | Modbus 400518 bit 3; not polled by default | Read | ||
| BI | 163 | Alarm Pickup Status Flags 1 - Overvoltage Alarm | Modbus 400518 bit 4; not polled by default | Read | ||
| BI | 164 | Alarm Pickup Status Flags 1 - Current Unbalance Alarm | Modbus 400518 bit 5; not polled by default | Read | ||
| BI | 165 | Alarm Pickup Status Flags 1 - Voltage Unbalance Alarm | Modbus 400518 bit 6; not polled by default | Read | ||
| BI | 166 | Alarm Pickup Status Flags 1 - Voltage Phase Reversal | Modbus 400518 bit 7; not polled by default | Read | ||
| BI | 167 | Alarm Pickup Status Flags 1 - PF Lead Alarm 1 | Modbus 400518 bit 8; not polled by default | Read | ||
| BI | 168 | Alarm Pickup Status Flags 1 - PF Lead Alarm 2 | Modbus 400518 bit 9; not polled by default | Read | ||
| BI | 169 | Alarm Pickup Status Flags 1 - Power Factor Log Alarm 1 | Modbus 400518 bit 10; not polled by default | Read | ||
| BI | 170 | Alarm Pickup Status Flags 1 - Ppower Factor Log Alarm 2 | Modbus 400518 bit 11; not polled by default | Read | ||
| BI | 171 | Alarm Pickup Status Flags 1 - Positive Real Power Alarm | Modbus 400518 bit 12; not polled by default | Read | ||
| BI | 172 | Alarm Pickup Status Flags 1 - Neg Real Power Alarm | Modbus 400518 bit 13; not polled by default | Read | ||
| BI | 173 | Alarm Pickup Status Flags 1 - Pos Reactive Power Alarm | Modbus 400518 bit 14; not polled by default | Read | ||
| BI | 174 | Alarm Pickup Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400518 bit 15; not polled by default | Read | ||
| BI | 175 | Alarm Active Status Flags 2 - Underfrequency Alarm | Modbus 400519 bit 0; not polled by default | Read | ||
| BI | 176 | Alarm Active Status Flags 2 - Overfrequency Alarm | Modbus 400519 bit 1; not polled by default | Read | ||
| BI | 177 | Alarm Active Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400519 bit 2; not polled by default | Read | ||
| BI | 178 | Alarm Active Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400519 bit 3; not polled by default | Read | ||
| BI | 179 | Alarm Active Status Flags 2 - Appartent Power Demand Alarm | Modbus 400519 bit 4; not polled by default | Read | ||
| BI | 180 | Alarm Active Status Flags 2 - Ph A Current Demand Alarm | Modbus 400519 bit 5; not polled by default | Read | ||
| BI | 181 | Alarm Active Status Flags 2 - Ph B Current Demand Alarm | Modbus 400519 bit 6; not polled by default | Read | ||
| BI | 182 | Alarm Active Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400519 bit 7; not polled by default | Read | ||
| BI | 183 | Alarm Active Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400519 bit 8; not polled by default | Read | ||
| BI | 184 | Alarm Active Status Flags 2 - Switch A Alarm | Modbus 400519 bit 9; not polled by default | Read | ||
| BI | 185 | Alarm Active Status Flags 2 - Switch B Alarm | Modbus 400519 bit 10; not polled by default | Read | ||
| BI | 186 | Alarm Active Status Flags 2 - Switch C Alarm | Modbus 400519 bit 11; not polled by default | Read | ||
| BI | 187 | Alarm Active Status Flags 2 - Switch D Alarm | Modbus 400519 bit 12; not polled by default | Read | ||
| BI | 188 | Alarm Active Status Flags 2 - Internal Fault Alarm | Modbus 400519 bit 13; not polled by default | Read | ||
| BI | 189 | Alarm Active Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400519 bit 14; not polled by default | Read | ||
| BI | 190 | Alarm Active Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400519 bit 15; not polled by default | Read | ||
| BI | 191 | Alarm Pickup Status Flags 2 - Underfrequency Alarm | Modbus 400520 bit 0; not polled by default | Read | ||
| BI | 192 | Alarm Pickup Status Flags 2 - Overfrequency Alarm | Modbus 400520 bit 1; not polled by default | Read | ||
| BI | 193 | Alarm Pickup Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400520 bit 2; not polled by default | Read | ||
| BI | 194 | Alarm Pickup Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400520 bit 3; not polled by default | Read | ||
| BI | 195 | Alarm Pickup Status Flags 2 - Appartent Power Demand Alarm | Modbus 400520 bit 4; not polled by default | Read | ||
| BI | 196 | Alarm Pickup Status Flags 2 - Ph A Current Demand Alarm | Modbus 400520 bit 5; not polled by default | Read | ||
| BI | 197 | Alarm Pickup Status Flags 2 - Ph B Current Demand Alarm | Modbus 400520 bit 6; not polled by default | Read | ||
| BI | 198 | Alarm Pickup Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400520 bit 7; not polled by default | Read | ||
| BI | 199 | Alarm Pickup Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400520 bit 8; not polled by default | Read | ||
| BI | 200 | Alarm Pickup Status Flags 2 - Switch A Alarm | Modbus 400520 bit 9; not polled by default | Read | ||
| BI | 201 | Alarm Pickup Status Flags 2 - Switch B Alarm | Modbus 400520 bit 10; not polled by default | Read | ||
| BI | 202 | Alarm Pickup Status Flags 2 - Switch C Alarm | Modbus 400520 bit 11; not polled by default | Read | ||
| BI | 203 | Alarm Pickup Status Flags 2 - Switch D Alarm | Modbus 400520 bit 12; not polled by default | Read | ||
| BI | 204 | Alarm Pickup Status Flags 2 - Internal Fault Alarm | Modbus 400520 bit 13; not polled by default | Read | ||
| BI | 205 | Alarm Pickup Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400520 bit 14; not polled by default | Read | ||
| BI | 206 | Alarm Pickup Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400520 bit 15; not polled by default | Read | ||
| BI | 207 | Alarm Active Status Flags 3 - Clock Not Set Alarm | Modbus 400521 bit 0; not polled by default | Read | ||
| BI | 208 | Alarm Active Status Flags 3 - Parameters Not Set Alarm | Modbus 400521 bit 1; not polled by default | Read | ||
| BI | 209 | Alarm Active Status Flags 3 - Pulse Input 1 Alarm | Modbus 400521 bit 2; not polled by default | Read | ||
| BI | 210 | Alarm Active Status Flags 3 - Current THD Alarm | Modbus 400521 bit 3; not polled by default | Read | ||
| BI | 211 | Alarm Active Status Flags 3 - Voltage THD Alarm | Modbus 400521 bit 4; not polled by default | Read | ||
| BI | 212 | Alarm Active Status Flags 3 - Analog Input Main Alarm | Modbus 400521 bit 5; not polled by default | Read | ||
| BI | 213 | Alarm Active Status Flags 3 - Analog Input Alt Alarm | Modbus 400521 bit 6; not polled by default | Read | ||
| BI | 214 | Alarm Active Status Flags 3 - Data Log 1 | Modbus 400521 bit 7; not polled by default | Read | ||
| BI | 215 | Alarm Active Status Flags 3 - Data Log 2 | Modbus 400521 bit 8; not polled by default | Read | ||
| BI | 216 | Alarm Active Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400521 bit 9; not polled by default | Read | ||
| BI | 217 | Alarm Active Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400521 bit 10; not polled by default | Read | ||
| BI | 218 | Alarm Active Status Flags 3 - Pulse Input 2 Alarm | Modbus 400521 bit 11; not polled by default | Read | ||
| BI | 219 | Alarm Active Status Flags 3 - Pulse Input 3 Alarm | Modbus 400521 bit 12; not polled by default | Read | ||
| BI | 220 | Alarm Active Status Flags 3 - Pulse Input 4 Alarm | Modbus 400521 bit 13; not polled by default | Read | ||
| BI | 221 | Alarm Active Status Flags 3 - Totalized Pulse In Alarm | Modbus 400521 bit 14; not polled by default | Read | ||
| BI | 222 | Alarm Active Status Flags 3 - Time Alarm | Modbus 400521 bit 15; not polled by default | Read | ||
| BI | 223 | Alarm Pickup Status Flags 3 - Clock Not Set Alarm | Modbus 400522 bit 0; not polled by default | Read | ||
| BI | 224 | Alarm Pickup Status Flags 3 - Parameters Not Set Alarm | Modbus 400522 bit 1; not polled by default | Read | ||
| BI | 225 | Alarm Pickup Status Flags 3 - Pulse Input 1 Alarm | Modbus 400522 bit 2; not polled by default | Read | ||
| BI | 226 | Alarm Pickup Status Flags 3 - Current THD Alarm | Modbus 400522 bit 3; not polled by default | Read | ||
| BI | 227 | Alarm Pickup Status Flags 3 - Voltage THD Alarm | Modbus 400522 bit 4; not polled by default | Read | ||
| BI | 228 | Alarm Pickup Status Flags 3 - Analog Input Main Alarm | Modbus 400522 bit 5; not polled by default | Read | ||
| BI | 229 | Alarm Pickup Status Flags 3 - Analog Input Alt Alarm | Modbus 400522 bit 6; not polled by default | Read | ||
| BI | 230 | Alarm Pickup Status Flags 3 - Data Log 1 | Modbus 400522 bit 7; not polled by default | Read | ||
| BI | 231 | Alarm Pickup Status Flags 3 - Data Log 2 | Modbus 400522 bit 8; not polled by default | Read | ||
| BI | 232 | Alarm Pickup Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400522 bit 9; not polled by default | Read | ||
| BI | 233 | Alarm Pickup Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400522 bit 10; not polled by default | Read | ||
| BI | 234 | Alarm Pickup Status Flags 3 - Pulse Input 2 Alarm | Modbus 400522 bit 11; not polled by default | Read | ||
| BI | 235 | Alarm Pickup Status Flags 3 - Pulse Input 3 Alarm | Modbus 400522 bit 12; not polled by default | Read | ||
| BI | 236 | Alarm Pickup Status Flags 3 - Pulse Input 4 Alarm | Modbus 400522 bit 13; not polled by default | Read | ||
| BI | 237 | Alarm Pickup Status Flags 3 - Totalized Pulse In Alarm | Modbus 400522 bit 14; not polled by default | Read | ||
| BI | 238 | Alarm Pickup Status Flags 3 - Time Alarm | Modbus 400522 bit 15; not polled by default | Read | ||
| BI | 239 | Aux 1 Active Status Flags 1 - Phase Undercurrent Alarm | Modbus 400523 bit 0; not polled by default | Read | ||
| BI | 240 | Aux 1 Active Status Flags 1 - Phase Overcurrent Alarm | Modbus 400523 bit 1; not polled by default | Read | ||
| BI | 241 | Aux 1 Active Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400523 bit 2; not polled by default | Read | ||
| BI | 242 | Aux 1 Active Status Flags 1 - Undervoltage Alarm | Modbus 400523 bit 3; not polled by default | Read | ||
| BI | 243 | Aux 1 Active Status Flags 1 - Overvoltage Alarm | Modbus 400523 bit 4; not polled by default | Read | ||
| BI | 244 | Aux 1 Active Status Flags 1 - Current Unbalance Alarm | Modbus 400523 bit 5; not polled by default | Read | ||
| BI | 245 | Aux 1 Active Status Flags 1 - Voltage Unbalance Alarm | Modbus 400523 bit 6; not polled by default | Read | ||
| BI | 246 | Aux 1 Active Status Flags 1 - Voltage Phase Reversal Alarm | Modbus 400523 bit 7; not polled by default | Read | ||
| BI | 247 | Aux 1 Active Status Flags 1 - PF Lead Alarm 1 | Modbus 400523 bit 8; not polled by default | Read | ||
| BI | 248 | Aux 1 Active Status Flags 1 - PF Lead Alarm 2 | Modbus 400523 bit 9; not polled by default | Read | ||
| BI | 249 | Aux 1 Active Status Flags 1 - Power Factor Log Alarm 1 | Modbus 400523 bit 10; not polled by default | Read | ||
| BI | 250 | Aux 1 Active Status Flags 1 - Power Factor Log Alarm 2 | Modbus 400523 bit 11; not polled by default | Read | ||
| BI | 251 | Aux 1 Active Status Flags 1 - Positive Real Power Alarm | Modbus 400523 bit 12; not polled by default | Read | ||
| BI | 252 | Aux 1 Active Status Flags 1 - Neg Real Power Alarm | Modbus 400523 bit 13; not polled by default | Read | ||
| BI | 253 | Aux 1 Active Status Flags 1 - Pos Reactive Power Alarm | Modbus 400523 bit 14; not polled by default | Read | ||
| BI | 254 | Aux 1 Active Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400523 bit 15; not polled by default | Read | ||
| BI | 255 | Aux 1 Pickup Status Flags 1 - Phase Undercurrent Alarm | Modbus 400524 bit 0; not polled by default | Read | ||
| BI | 256 | Aux 1 Pickup Status Flags 1 - Phase Overcurrent Alarm | Modbus 400524 bit 1; not polled by default | Read | ||
| BI | 257 | Aux 1 Pickup Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400524 bit 2; not polled by default | Read | ||
| BI | 258 | Aux 1 Pickup Status Flags 1 - Undervoltage Alarm | Modbus 400524 bit 3; not polled by default | Read | ||
| BI | 259 | Aux 1 Pickup Status Flags 1 - Overvoltage Alarm | Modbus 400524 bit 4; not polled by default | Read | ||
| BI | 260 | Aux 1 Pickup Status Flags 1 - Current Unbalance Alarm | Modbus 400524 bit 5; not polled by default | Read | ||
| BI | 261 | Aux 1 Pickup Status Flags 1 - Voltage Unbalance Alarm | Modbus 400524 bit 6; not polled by default | Read | ||
| BI | 262 | Aux 1 Pickup Status Flags 1 - Voltage Phase Reversal Alarm | Modbus 400524 bit 7; not polled by default | Read | ||
| BI | 263 | Aux 1 Pickup Status Flags 1 - PF Lead Alarm 1 | Modbus 400524 bit 8; not polled by default | Read | ||
| BI | 264 | Aux 1 Pickup Status Flags 1 - PF Lead Alarm 2 | Modbus 400524 bit 9; not polled by default | Read | ||
| BI | 265 | Aux 1 Pickup Status Flags 1 - Power Factor Log Alarm 1 | Modbus 400524 bit 10; not polled by default | Read | ||
| BI | 266 | Aux 1 Pickup Status Flags 1 - Ppower Factor Log Alarm 2 | Modbus 400524 bit 11; not polled by default | Read | ||
| BI | 267 | Aux 1 Pickup Status Flags 1 - Positive Real Power Alarm | Modbus 400524 bit 12; not polled by default | Read | ||
| BI | 268 | Aux 1 Pickup Status Flags 1 - Neg Real Power Alarm | Modbus 400524 bit 13; not polled by default | Read | ||
| BI | 269 | Aux 1 Pickup Status Flags 1 - Pos Reactive Power Alarm | Modbus 400524 bit 14; not polled by default | Read | ||
| BI | 270 | Aux 1 Pickup Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400524 bit 15; not polled by default | Read | ||
| BI | 271 | Aux 1 Active Status Flags 2 - Underfrequency Alarm | Modbus 400525 bit 0; not polled by default | Read | ||
| BI | 272 | Aux 1 Active Status Flags 2 - Overfrequency Alarm | Modbus 400525 bit 1; not polled by default | Read | ||
| BI | 273 | Aux 1 Active Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400525 bit 2; not polled by default | Read | ||
| BI | 274 | Aux 1 Active Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400525 bit 3; not polled by default | Read | ||
| BI | 275 | Aux 1 Active Status Flags 2 - Appartent Power Demand Alarm | Modbus 400525 bit 4; not polled by default | Read | ||
| BI | 276 | Aux 1 Active Status Flags 2 - Ph A Current Demand Alarm | Modbus 400525 bit 5; not polled by default | Read | ||
| BI | 277 | Aux 1 Active Status Flags 2 - Ph B Current Demand Alarm | Modbus 400525 bit 6; not polled by default | Read | ||
| BI | 278 | Aux 1 Active Status Flags 2 - Ph C Current Demand Alarm | Modbus 400525 bit 7; not polled by default | Read | ||
| BI | 279 | Aux 1 Active Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400525 bit 8; not polled by default | Read | ||
| BI | 280 | Aux 1 Active Status Flags 2 - Switch A Alarm | Modbus 400525 bit 9; not polled by default | Read | ||
| BI | 281 | Aux 1 Active Status Flags 2 - Switch B Alarm | Modbus 400525 bit 10; not polled by default | Read | ||
| BI | 282 | Aux 1 Active Status Flags 2 - Switch C Alarm | Modbus 400525 bit 11; not polled by default | Read | ||
| BI | 283 | Aux 1 Active Status Flags 2 - Switch D Alarm | Modbus 400525 bit 12; not polled by default | Read | ||
| BI | 284 | Aux 1 Active Status Flags 2 - Internal Fault Alarm | Modbus 400525 bit 13; not polled by default | Read | ||
| BI | 285 | Aux 1 Active Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400525 bit 14; not polled by default | Read | ||
| BI | 286 | Aux 1 Active Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400525 bit 15; not polled by default | Read | ||
| BI | 287 | Aux 1 Pickup Status Flags 2 - Underfrequency Alarm | Modbus 400526 bit 0; not polled by default | Read | ||
| BI | 288 | Aux 1 Pickup Status Flags 2 - Overfrequency Alarm | Modbus 400526 bit 1; not polled by default | Read | ||
| BI | 289 | Aux 1 Pickup Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400526 bit 2; not polled by default | Read | ||
| BI | 290 | Aux 1 Pickup Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400526 bit 3; not polled by default | Read | ||
| BI | 291 | Aux 1 Pickup Status Flags 2 - Appartent Power Demand Alarm | Modbus 400526 bit 4; not polled by default | Read | ||
| BI | 292 | Aux 1 Pickup Status Flags 2 - Ph A Current Demand Alarm | Modbus 400526 bit 5; not polled by default | Read | ||
| BI | 293 | Aux 1 Pickup Status Flags 2 - Ph B Current Demand Alarm | Modbus 400526 bit 6; not polled by default | Read | ||
| BI | 294 | Aux 1 Pickup Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400526 bit 7; not polled by default | Read | ||
| BI | 295 | Aux 1 Pickup Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400526 bit 8; not polled by default | Read | ||
| BI | 296 | Aux 1 Pickup Status Flags 2 - Switch A Alarm | Modbus 400526 bit 9; not polled by default | Read | ||
| BI | 297 | Aux 1 Pickup Status Flags 2 - Switch B Alarm | Modbus 400526 bit 10; not polled by default | Read | ||
| BI | 298 | Aux 1 Pickup Status Flags 2 - Switch C Alarm | Modbus 400526 bit 11; not polled by default | Read | ||
| BI | 299 | Aux 1 Pickup Status Flags 2 - Switch D Alarm | Modbus 400526 bit 12; not polled by default | Read | ||
| BI | 300 | Aux 1 Pickup Status Flags 2 - Internal Fault Alarm | Modbus 400526 bit 13; not polled by default | Read | ||
| BI | 301 | Aux 1 Pickup Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400526 bit 14; not polled by default | Read | ||
| BI | 302 | Aux 1 Pickup Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400526 bit 15; not polled by default | Read | ||
| BI | 303 | Aux 1 Active Status Flags 3 - Clock Not Set Alarm | Modbus 400527 bit 0; not polled by default | Read | ||
| BI | 304 | Aux 1 Active Status Flags 3 - Parameters Not Set Alarm | Modbus 400527 bit 1; not polled by default | Read | ||
| BI | 305 | Aux 1 Active Status Flags 3 - Pulse Input 1 Alarm | Modbus 400527 bit 2; not polled by default | Read | ||
| BI | 306 | Aux 1 Active Status Flags 3 - Current THD Alarm | Modbus 400527 bit 3; not polled by default | Read | ||
| BI | 307 | Aux 1 Active Status Flags 3 - Voltage THD Alarm | Modbus 400527 bit 4; not polled by default | Read | ||
| BI | 308 | Aux 1 Active Status Flags 3 - Analog Input Main Alarm | Modbus 400527 bit 5; not polled by default | Read | ||
| BI | 309 | Aux 1 Active Status Flags 3 - Analog Input Alt Alarm | Modbus 400527 bit 6; not polled by default | Read | ||
| BI | 310 | Aux 1 Active Status Flags 3 - Data Log 1 | Modbus 400527 bit 7; not polled by default | Read | ||
| BI | 311 | Aux 1 Active Status Flags 3 - Data Log 2 | Modbus 400527 bit 8; not polled by default | Read | ||
| BI | 312 | Aux 1 Active Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400527 bit 9; not polled by default | Read | ||
| BI | 313 | Aux 1 Active Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400527 bit 10; not polled by default | Read | ||
| BI | 314 | Aux 1 Active Status Flags 3 - Pulse Input 2 Alarm | Modbus 400527 bit 11; not polled by default | Read | ||
| BI | 315 | Aux 1 Active Status Flags 3 - Pulse Input 3 Alarm | Modbus 400527 bit 12; not polled by default | Read | ||
| BI | 316 | Aux 1 Active Status Flags 3 - Pulse Input 4 Alarm | Modbus 400527 bit 13; not polled by default | Read | ||
| BI | 317 | Aux 1 Active Status Flags 3 - Totalized Pulse In Alarm | Modbus 400527 bit 14; not polled by default | Read | ||
| BI | 318 | Aux 1 Active Status Flags 3 - Time Alarm | Modbus 400527 bit 15; not polled by default | Read | ||
| BI | 319 | Aux 1 Pickup Status Flags 3 - Clock Not Set Alarm | Modbus 400528 bit 0; not polled by default | Read | ||
| BI | 320 | Aux 1 Pickup Status Flags 3 - Parameters Not Set Alarm | Modbus 400528 bit 1; not polled by default | Read | ||
| BI | 321 | Aux 1 Pickup Status Flags 3 - Pulse Input 1 Alarm | Modbus 400528 bit 2; not polled by default | Read | ||
| BI | 322 | Aux 1 Pickup Status Flags 3 - Current THD Alarm | Modbus 400528 bit 3; not polled by default | Read | ||
| BI | 323 | Aux 1 Pickup Status Flags 3 - Voltage THD Alarm | Modbus 400528 bit 4; not polled by default | Read | ||
| BI | 324 | Aux 1 Pickup Status Flags 3 - Analog Input Main Alarm | Modbus 400528 bit 5; not polled by default | Read | ||
| BI | 325 | Aux 1 Pickup Status Flags 3 - Analog Input Alt Alarm | Modbus 400528 bit 6; not polled by default | Read | ||
| BI | 326 | Aux 1 Pickup Status Flags 3 - Data Log 1 | Modbus 400528 bit 7; not polled by default | Read | ||
| BI | 327 | Aux 1 Pickup Status Flags 3 - Data Log 2 | Modbus 400528 bit 8; not polled by default | Read | ||
| BI | 328 | Aux 1 Pickup Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400528 bit 9; not polled by default | Read | ||
| BI | 329 | Aux 1 Pickup Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400528 bit 10; not polled by default | Read | ||
| BI | 330 | Aux 1 Pickup Status Flags 3 - Pulse Input 2 Alarm | Modbus 400528 bit 11; not polled by default | Read | ||
| BI | 331 | Aux 1 Pickup Status Flags 3 - Pulse Input 3 Alarm | Modbus 400528 bit 12; not polled by default | Read | ||
| BI | 332 | Aux 1 Pickup Status Flags 3 - Pulse Input 4 Alarm | Modbus 400528 bit 13; not polled by default | Read | ||
| BI | 333 | Aux 1 Pickup Status Flags 3 - Totalized Pulse In Alarm | Modbus 400528 bit 14; not polled by default | Read | ||
| BI | 334 | Aux 1 Pickup Status Flags 3 - Time Alarm | Modbus 400528 bit 15; not polled by default | Read | ||
| BI | 335 | Aux 2 Active Status Flags 1 - Phase Undercurrent Alarm | Modbus 400529 bit 0; not polled by default | Read | ||
| BI | 336 | Aux 2 Active Status Flags 1 - Phase Overcurrent Alarm | Modbus 400529 bit 1; not polled by default | Read | ||
| BI | 337 | Aux 2 Active Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400529 bit 2; not polled by default | Read | ||
| BI | 338 | Aux 2 Active Status Flags 1 - Undervoltage Alarm | Modbus 400529 bit 3; not polled by default | Read | ||
| BI | 339 | Aux 2 Active Status Flags 1 - Overvoltage Alarm | Modbus 400529 bit 4; not polled by default | Read | ||
| BI | 340 | Aux 2 Active Status Flags 1 - Current Unbalance Alarm | Modbus 400529 bit 5; not polled by default | Read | ||
| BI | 341 | Aux 2 Active Status Flags 1 - Voltage Unbalance Alarm | Modbus 400529 bit 6; not polled by default | Read | ||
| BI | 342 | Aux 2 Active Status Flags 1 - Voltage Phase Reversal Alarm | Modbus 400529 bit 7; not polled by default | Read | ||
| BI | 343 | Aux 2 Active Status Flags 1 - PF Lead Alarm 1 | Modbus 400529 bit 8; not polled by default | Read | ||
| BI | 344 | Aux 2 Active Status Flags 1 - PF Lead Alarm 2 | Modbus 400529 bit 9; not polled by default | Read | ||
| BI | 345 | Aux 2 Active Status Flags 1 - Power Factor Log Alarm | Modbus 400529 bit 10; not polled by default | Read | ||
| BI | 346 | Aux 2 Active Status Flags 1 - Ppower Factor Log Alarm | Modbus 400529 bit 11; not polled by default | Read | ||
| BI | 347 | Aux 2 Active Status Flags 1 - Positive Real Power Alarm | Modbus 400529 bit 12; not polled by default | Read | ||
| BI | 348 | Aux 2 Active Status Flags 1 - Neg Real Power Alarm | Modbus 400529 bit 13; not polled by default | Read | ||
| BI | 349 | Aux 2 Active Status Flags 1 - Pos Reactive Power Alarm | Modbus 400529 bit 14; not polled by default | Read | ||
| BI | 350 | Aux 2 Active Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400529 bit 15; not polled by default | Read | ||
| BI | 351 | Aux 2 Pickup Status Flags 1 - Phase Undercurrent Alarm | Modbus 400530 bit 0; not polled by default | Read | ||
| BI | 352 | Aux 2 Pickup Status Flags 1 - Phase Overcurrent Alarm | Modbus 400530 bit 1; not polled by default | Read | ||
| BI | 353 | Aux 2 Pickup Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400530 bit 2; not polled by default | Read | ||
| BI | 354 | Aux 2 Pickup Status Flags 1 - Undervoltage Alarm | Modbus 400530 bit 3; not polled by default | Read | ||
| BI | 355 | Aux 2 Pickup Status Flags 1 - Overvoltage Alarm | Modbus 400530 bit 4; not polled by default | Read | ||
| BI | 356 | Aux 2 Pickup Status Flags 1 - Current Unbalance Alarm | Modbus 400530 bit 5; not polled by default | Read | ||
| BI | 357 | Aux 2 Pickup Status Flags 1 - Voltage Unbalance Alarm | Modbus 400530 bit 6; not polled by default | Read | ||
| BI | 358 | Aux 2 Pickup Status Flags 1 - Voltage Phase Reversal Alarm | Modbus 400530 bit 7; not polled by default | Read | ||
| BI | 359 | Aux 2 Pickup Status Flags 1 - PF Lead Alarm 1 | Modbus 400530 bit 8; not polled by default | Read | ||
| BI | 360 | Aux 2 Pickup Status Flags 1 - PF Lead Alarm 2 | Modbus 400530 bit 9; not polled by default | Read | ||
| BI | 361 | Aux 2 Pickup Status Flags 1 - Power Factor Log Alarm | Modbus 400530 bit 10; not polled by default | Read | ||
| BI | 362 | Aux 2 Pickup Status Flags 1 - Power Factor Log Alarm 2 | Modbus 400530 bit 11; not polled by default | Read | ||
| BI | 363 | Aux 2 Pickup Status Flags 1 - Positive Real Power Alarm | Modbus 400530 bit 12; not polled by default | Read | ||
| BI | 364 | Aux 2 Pickup Status Flags 1 - Neg Real Power Alarm | Modbus 400530 bit 13; not polled by default | Read | ||
| BI | 365 | Aux 2 Pickup Status Flags 1 - Pos Reactive Power Alarm | Modbus 400530 bit 14; not polled by default | Read | ||
| BI | 366 | Aux 2 Pickup Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400530 bit 15; not polled by default | Read | ||
| BI | 367 | Aux 2 Active Status Flags 2 - Underfrequency Alarm | Modbus 400531 bit 0; not polled by default | Read | ||
| BI | 368 | Aux 2 Active Status Flags 2 - Overfrequency Alarm | Modbus 400531 bit 1; not polled by default | Read | ||
| BI | 369 | Aux 2 Active Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400531 bit 2; not polled by default | Read | ||
| BI | 370 | Aux 2 Active Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400531 bit 3; not polled by default | Read | ||
| BI | 371 | Aux 2 Active Status Flags 2 - Appartent Power Demand Alarm | Modbus 400531 bit 4; not polled by default | Read | ||
| BI | 372 | Aux 2 Active Status Flags 2 - Ph A Current Demand Alarm | Modbus 400531 bit 5; not polled by default | Read | ||
| BI | 373 | Aux 2 Active Status Flags 2 - Ph B Current Demand Alarm | Modbus 400531 bit 6; not polled by default | Read | ||
| BI | 374 | Aux 2 Active Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400531 bit 7; not polled by default | Read | ||
| BI | 375 | Aux 2 Active Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400531 bit 8; not polled by default | Read | ||
| BI | 376 | Aux 2 Active Status Flags 2 - Switch A Alarm | Modbus 400531 bit 9; not polled by default | Read | ||
| BI | 377 | Aux 2 Active Status Flags 2 - Switch B Alarm | Modbus 400531 bit 10; not polled by default | Read | ||
| BI | 378 | Aux 2 Active Status Flags 2 - Switch C Alarm | Modbus 400531 bit 11; not polled by default | Read | ||
| BI | 379 | Aux 2 Active Status Flags 2 - Switch D Alarm | Modbus 400531 bit 12; not polled by default | Read | ||
| BI | 380 | Aux 2 Active Status Flags 2 - Internal Fault Alarm | Modbus 400531 bit 13; not polled by default | Read | ||
| BI | 381 | Aux 2 Active Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400531 bit 14; not polled by default | Read | ||
| BI | 382 | Aux 2 Active Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400531 bit 15; not polled by default | Read | ||
| BI | 383 | Aux 2 Pickup Status Flags 2 - Underfrequency Alarm | Modbus 400532 bit 0; not polled by default | Read | ||
| BI | 384 | Aux 2 Pickup Status Flags 2 - Overfrequency Alarm | Modbus 400532 bit 1; not polled by default | Read | ||
| BI | 385 | Aux 2 Pickup Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400532 bit 2; not polled by default | Read | ||
| BI | 386 | Aux 2 Pickup Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400532 bit 3; not polled by default | Read | ||
| BI | 387 | Aux 2 Pickup Status Flags 2 - Appartent Power Demand Alarm | Modbus 400532 bit 4; not polled by default | Read | ||
| BI | 388 | Aux 2 Pickup Status Flags 2 - Ph A Current Demand Alarm | Modbus 400532 bit 5; not polled by default | Read | ||
| BI | 389 | Aux 2 Pickup Status Flags 2 - Ph B Current Demand Alarm | Modbus 400532 bit 6; not polled by default | Read | ||
| BI | 390 | Aux 2 Pickup Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400532 bit 7; not polled by default | Read | ||
| BI | 391 | Aux 2 Pickup Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400532 bit 8; not polled by default | Read | ||
| BI | 392 | Aux 2 Pickup Status Flags 2 - Switch A Alarm | Modbus 400532 bit 9; not polled by default | Read | ||
| BI | 393 | Aux 2 Pickup Status Flags 2 - Switch B Alarm | Modbus 400532 bit 10; not polled by default | Read | ||
| BI | 394 | Aux 2 Pickup Status Flags 2 - Switch C Alarm | Modbus 400532 bit 11; not polled by default | Read | ||
| BI | 395 | Aux 2 Pickup Status Flags 2 - Switch D Alarm | Modbus 400532 bit 12; not polled by default | Read | ||
| BI | 396 | Aux 2 Pickup Status Flags 2 - Internal Fault Alarm | Modbus 400532 bit 13; not polled by default | Read | ||
| BI | 397 | Aux 2 Pickup Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400532 bit 14; not polled by default | Read | ||
| BI | 398 | Aux 2 Pickup Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400532 bit 15; not polled by default | Read | ||
| BI | 399 | Aux 2 Active Status Flags 3 - Clock Not Set Alarm | Modbus 400533 bit 0; not polled by default | Read | ||
| BI | 400 | Aux 2 Active Status Flags 3 - Parameters Not Set Alarm | Modbus 400533 bit 1; not polled by default | Read | ||
| BI | 401 | Aux 2 Active Status Flags 3 - Pulse Input 1 Alarm | Modbus 400533 bit 2; not polled by default | Read | ||
| BI | 402 | Aux 2 Active Status Flags 3 - Current THD Alarm | Modbus 400533 bit 3; not polled by default | Read | ||
| BI | 403 | Aux 2 Active Status Flags 3 - Voltage THD Alarm | Modbus 400533 bit 4; not polled by default | Read | ||
| BI | 404 | Aux 2 Active Status Flags 3 - Analog Input Main Alarm | Modbus 400533 bit 5; not polled by default | Read | ||
| BI | 405 | Aux 2 Active Status Flags 3 - Analog Input Alt Alarm | Modbus 400533 bit 6; not polled by default | Read | ||
| BI | 406 | Aux 2 Active Status Flags 3 - Data Log 1 | Modbus 400533 bit 7; not polled by default | Read | ||
| BI | 407 | Aux 2 Active Status Flags 3 - Data Log 2 | Modbus 400533 bit 8; not polled by default | Read | ||
| BI | 408 | Aux 2 Active Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400533 bit 9; not polled by default | Read | ||
| BI | 409 | Aux 2 Active Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400533 bit 10; not polled by default | Read | ||
| BI | 410 | Aux 2 Active Status Flags 3 - Pulse Input 2 Alarm | Modbus 400533 bit 11; not polled by default | Read | ||
| BI | 411 | Aux 2 Active Status Flags 3 - Pulse Input 3 Alarm | Modbus 400533 bit 12; not polled by default | Read | ||
| BI | 412 | Aux 2 Active Status Flags 3 - Pulse Input 4 Alarm | Modbus 400533 bit 13; not polled by default | Read | ||
| BI | 413 | Aux 2 Active Status Flags 3 - Totalized Pulse In Alarm | Modbus 400533 bit 14; not polled by default | Read | ||
| BI | 414 | Aux 2 Active Status Flags 3 - Time Alarm | Modbus 400533 bit 15; not polled by default | Read | ||
| BI | 415 | Aux 2 Pickup Status Flags 3 - Clock Not Set Alarm | Modbus 400534 bit 0; not polled by default | Read | ||
| BI | 416 | Aux 2 Pickup Status Flags 3 - Parameters Not Set Alarm | Modbus 400534 bit 1; not polled by default | Read | ||
| BI | 417 | Aux 2 Pickup Status Flags 3 - Pulse Input 1 Alarm | Modbus 400534 bit 2; not polled by default | Read | ||
| BI | 418 | Aux 2 Pickup Status Flags 3 - Current THD Alarm | Modbus 400534 bit 3; not polled by default | Read | ||
| BI | 419 | Aux 2 Pickup Status Flags 3 - Voltage THD Alarm | Modbus 400534 bit 4; not polled by default | Read | ||
| BI | 420 | Aux 2 Pickup Status Flags 3 - Analog Input Main Alarm | Modbus 400534 bit 5; not polled by default | Read | ||
| BI | 421 | Aux 2 Pickup Status Flags 3 - Analog Input Alt Alarm | Modbus 400534 bit 6; not polled by default | Read | ||
| BI | 422 | Aux 2 Pickup Status Flags 3 - Data Log 1 | Modbus 400534 bit 7; not polled by default | Read | ||
| BI | 423 | Aux 2 Pickup Status Flags 3 - Data Log 2 | Modbus 400534 bit 8; not polled by default | Read | ||
| BI | 424 | Aux 2 Pickup Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400534 bit 9; not polled by default | Read | ||
| BI | 425 | Aux 2 Pickup Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400534 bit 10; not polled by default | Read | ||
| BI | 426 | Aux 2 Pickup Status Flags 3 - Pulse Input 2 Aux 2 | Modbus 400534 bit 11; not polled by default | Read | ||
| BI | 427 | Aux 2 Pickup Status Flags 3 - Pulse Input 3 Alarm | Modbus 400534 bit 12; not polled by default | Read | ||
| BI | 428 | Aux 2 Pickup Status Flags 3 - Pulse Input 4 Alarm | Modbus 400534 bit 13; not polled by default | Read | ||
| BI | 429 | Aux 2 Pickup Status Flags 3 - Totalized Pulse In Alarm | Modbus 400534 bit 14; not polled by default | Read | ||
| BI | 430 | Aux 2 Pickup Status Flags 3 - Time Alarm | Modbus 400534 bit 15; not polled by default | Read | ||
| BI | 431 | Aux 3 Active Status Flags 1 - Phase Undercurrent Alarm | Modbus 400535 bit 0; not polled by default | Read | ||
| BI | 432 | Aux 3 Active Status Flags 1 - Phase Overcurrent Alarm | Modbus 400535 bit 1; not polled by default | Read | ||
| BI | 433 | Aux 3 Active Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400535 bit 2; not polled by default | Read | ||
| BI | 434 | Aux 3 Active Status Flags 1 - Undervoltage Alarm | Modbus 400535 bit 3; not polled by default | Read | ||
| BI | 435 | Aux 3 Active Status Flags 1 - Overvoltage Alarm | Modbus 400535 bit 4; not polled by default | Read | ||
| BI | 436 | Aux 3 Active Status Flags 1 - Current Unbalance Alarm | Modbus 400535 bit 5; not polled by default | Read | ||
| BI | 437 | Aux 3 Active Status Flags 1 - Voltage Unbalance Alarm | Modbus 400535 bit 6; not polled by default | Read | ||
| BI | 438 | Aux 3 Active Status Flags 1 - Voltage Phase Reversal Alarm | Modbus 400535 bit 7; not polled by default | Read | ||
| BI | 439 | Aux 3 Active Status Flags 1 - PF Lead Alarm 1 | Modbus 400535 bit 8; not polled by default | Read | ||
| BI | 440 | Aux 3 Active Status Flags 1 - PF Lead Alarm 2 | Modbus 400535 bit 9; not polled by default | Read | ||
| BI | 441 | Aux 3 Active Status Flags 1 - Power Factor Log Alarm | Modbus 400535 bit 10; not polled by default | Read | ||
| BI | 442 | Aux 3 Active Status Flags 1 - Ppower Factor Log Alarm | Modbus 400535 bit 11; not polled by default | Read | ||
| BI | 443 | Aux 3 Active Status Flags 1 - Positive Real Power Alarm | Modbus 400535 bit 12; not polled by default | Read | ||
| BI | 444 | Aux 3 Active Status Flags 1 - Neg Real Power Alarm | Modbus 400535 bit 13; not polled by default | Read | ||
| BI | 445 | Aux 3 Active Status Flags 1 - Pos Reactive Power Alarm | Modbus 400535 bit 14; not polled by default | Read | ||
| BI | 446 | Aux 3 Active Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400535 bit 15; not polled by default | Read | ||
| BI | 447 | Aux 3 Pickup Status Flags 1 - Phase Undercurrent Alarm | Modbus 400536 bit 0; not polled by default | Read | ||
| BI | 448 | Aux 3 Pickup Status Flags 1 - Phase Overcurrent Alarm | Modbus 400536 bit 1; not polled by default | Read | ||
| BI | 449 | Aux 3 Pickup Status Flags 1 - Neutral Overcurrent Alarm | Modbus 400536 bit 2; not polled by default | Read | ||
| BI | 450 | Aux 3 Pickup Status Flags 1 - Undervoltage Alarm | Modbus 400536 bit 3; not polled by default | Read | ||
| BI | 451 | Aux 3 Pickup Status Flags 1 - Overvoltage Alarm | Modbus 400536 bit 4; not polled by default | Read | ||
| BI | 452 | Aux 3 Pickup Status Flags 1 - Current Unbalance Alarm | Modbus 400536 bit 5; not polled by default | Read | ||
| BI | 453 | Aux 3 Pickup Status Flags 1 - Voltage Unbalance Alarm | Modbus 400536 bit 6; not polled by default | Read | ||
| BI | 454 | Aux 3 Pickup Status Flags 1 - Voltage Phase Reversal Alarm | Modbus 400536 bit 7; not polled by default | Read | ||
| BI | 455 | Aux 3 Pickup Status Flags 1 - PF Lead Alarm 1 | Modbus 400536 bit 8; not polled by default | Read | ||
| BI | 456 | Aux 3 Pickup Status Flags 1 - PF Lead Alarm 2 | Modbus 400536 bit 9; not polled by default | Read | ||
| BI | 457 | Aux 3 Pickup Status Flags 1 - Power Factor Log Alarm | Modbus 400536 bit 10; not polled by default | Read | ||
| BI | 458 | Aux 3 Pickup Status Flags 1 - Power Factor Log Alarm 2 | Modbus 400536 bit 11; not polled by default | Read | ||
| BI | 459 | Aux 3 Pickup Status Flags 1 - Positive Real Power Alarm | Modbus 400536 bit 12; not polled by default | Read | ||
| BI | 460 | Aux 3 Pickup Status Flags 1 - Neg Real Power Alarm | Modbus 400536 bit 13; not polled by default | Read | ||
| BI | 461 | Aux 3 Pickup Status Flags 1 - Pos Reactive Power Alarm | Modbus 400536 bit 14; not polled by default | Read | ||
| BI | 462 | Aux 3 Pickup Status Flags 1 - Neg Reactive Powere Alarm | Modbus 400536 bit 15; not polled by default | Read | ||
| BI | 463 | Aux 3 Active Status Flags 2 - Underfrequency Alarm | Modbus 400537 bit 0; not polled by default | Read | ||
| BI | 464 | Aux 3 Active Status Flags 2 - Overfrequency Alarm | Modbus 400537 bit 1; not polled by default | Read | ||
| BI | 465 | Aux 3 Active Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400537 bit 2; not polled by default | Read | ||
| BI | 466 | Aux 3 Active Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400537 bit 3; not polled by default | Read | ||
| BI | 467 | Aux 3 Active Status Flags 2 - Appartent Power Demand Alarm | Modbus 400537 bit 4; not polled by default | Read | ||
| BI | 468 | Aux 3 Active Status Flags 2 - Ph A Current Demand Alarm | Modbus 400537 bit 5; not polled by default | Read | ||
| BI | 469 | Aux 3 Active Status Flags 2 - Ph B Current Demand Alarm | Modbus 400537 bit 6; not polled by default | Read | ||
| BI | 470 | Aux 3 Active Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400537 bit 7; not polled by default | Read | ||
| BI | 471 | Aux 3 Active Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400537 bit 8; not polled by default | Read | ||
| BI | 472 | Aux 3 Active Status Flags 2 - Switch A Alarm | Modbus 400537 bit 9; not polled by default | Read | ||
| BI | 473 | Aux 3 Active Status Flags 2 - Switch B Alarm | Modbus 400537 bit 10; not polled by default | Read | ||
| BI | 474 | Aux 3 Active Status Flags 2 - Switch C Alarm | Modbus 400537 bit 11; not polled by default | Read | ||
| BI | 475 | Aux 3 Active Status Flags 2 - Switch D Alarm | Modbus 400537 bit 12; not polled by default | Read | ||
| BI | 476 | Aux 3 Active Status Flags 2 - Internal Fault Alarm | Modbus 400537 bit 13; not polled by default | Read | ||
| BI | 477 | Aux 3 Active Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400537 bit 14; not polled by default | Read | ||
| BI | 478 | Aux 3 Active Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400537 bit 15; not polled by default | Read | ||
| BI | 479 | Aux 3 Pickup Status Flags 2 - Underfrequency Alarm | Modbus 400538 bit 0; not polled by default | Read | ||
| BI | 480 | Aux 3 Pickup Status Flags 2 - Overfrequency Alarm | Modbus 400538 bit 1; not polled by default | Read | ||
| BI | 481 | Aux 3 Pickup Status Flags 2 - Positive Real Power Demand Alarm | Modbus 400538 bit 2; not polled by default | Read | ||
| BI | 482 | Aux 3 Pickup Status Flags 2 - Positive Reactive Power Demand Alarm | Modbus 400538 bit 3; not polled by default | Read | ||
| BI | 483 | Aux 3 Pickup Status Flags 2 - Appartent Power Demand Alarm | Modbus 400538 bit 4; not polled by default | Read | ||
| BI | 484 | Aux 3 Pickup Status Flags 2 - Ph A Current Demand Alarm | Modbus 400538 bit 5; not polled by default | Read | ||
| BI | 485 | Aux 3 Pickup Status Flags 2 - Ph B Current Demand Alarm | Modbus 400538 bit 6; not polled by default | Read | ||
| BI | 486 | Aux 3 Pickup Status Flags 2 - Ph C Current DemanD Alarm | Modbus 400538 bit 7; not polled by default | Read | ||
| BI | 487 | Aux 3 Pickup Status Flags 2 - Nuetral Current Demand Alarm | Modbus 400538 bit 8; not polled by default | Read | ||
| BI | 488 | Aux 3 Pickup Status Flags 2 - Switch A Alarm | Modbus 400538 bit 9; not polled by default | Read | ||
| BI | 489 | Aux 3 Pickup Status Flags 2 - Switch B Alarm | Modbus 400538 bit 10; not polled by default | Read | ||
| BI | 490 | Aux 3 Pickup Status Flags 2 - Switch C Alarm | Modbus 400538 bit 11; not polled by default | Read | ||
| BI | 491 | Aux 3 Pickup Status Flags 2 - Switch D Alarm | Modbus 400538 bit 12; not polled by default | Read | ||
| BI | 492 | Aux 3 Pickup Status Flags 2 - Internal Fault Alarm | Modbus 400538 bit 13; not polled by default | Read | ||
| BI | 493 | Aux 3 Pickup Status Flags 2 - Serial COM1 Failure Alarm | Modbus 400538 bit 14; not polled by default | Read | ||
| BI | 494 | Aux 3 Pickup Status Flags 2 - Serial COM2 Failure Alarm | Modbus 400538 bit 15; not polled by default | Read | ||
| BI | 495 | Aux 3 Active Status Flags 3 - Clock Not Set Alarm | Modbus 400539 bit 0; not polled by default | Read | ||
| BI | 496 | Aux 3 Active Status Flags 3 - Parameters Not Set Alarm | Modbus 400539 bit 1; not polled by default | Read | ||
| BI | 497 | Aux 3 Active Status Flags 3 - Pulse Input 1 Alarm | Modbus 400539 bit 2; not polled by default | Read | ||
| BI | 498 | Aux 3 Active Status Flags 3 - Current THD Alarm | Modbus 400539 bit 3; not polled by default | Read | ||
| BI | 499 | Aux 3 Active Status Flags 3 - Voltage THD Alarm | Modbus 400539 bit 4; not polled by default | Read | ||
| BI | 500 | Aux 3 Active Status Flags 3 - Analog Input Main Alarm | Modbus 400539 bit 5; not polled by default | Read | ||
| BI | 501 | Aux 3 Active Status Flags 3 - Analog Input Alt Alarm | Modbus 400539 bit 6; not polled by default | Read | ||
| BI | 502 | Aux 3 Active Status Flags 3 - Data Log 1 | Modbus 400539 bit 7; not polled by default | Read | ||
| BI | 503 | Aux 3 Active Status Flags 3 - Data Log 2 | Modbus 400539 bit 8; not polled by default | Read | ||
| BI | 504 | Aux 3 Active Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400539 bit 9; not polled by default | Read | ||
| BI | 505 | Aux 3 Active Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400539 bit 10; not polled by default | Read | ||
| BI | 506 | Aux 3 Active Status Flags 3 - Pulse Input 2 Alarm | Modbus 400539 bit 11; not polled by default | Read | ||
| BI | 507 | Aux 3 Active Status Flags 3 - Pulse Input 3 Alarm | Modbus 400539 bit 12; not polled by default | Read | ||
| BI | 508 | Aux 3 Active Status Flags 3 - Pulse Input 4 Alarm | Modbus 400539 bit 13; not polled by default | Read | ||
| BI | 509 | Aux 3 Active Status Flags 3 - Totalized Pulse In Alarm | Modbus 400539 bit 14; not polled by default | Read | ||
| BI | 510 | Aux 3 Active Status Flags 3 - Time Alarm | Modbus 400539 bit 15; not polled by default | Read | ||
| BI | 511 | Aux 3 Pickup Status Flags 3 - Clock Not Set Alarm | Modbus 400540 bit 0; not polled by default | Read | ||
| BI | 512 | Aux 3 Pickup Status Flags 3 - Parameters Not Set Alarm | Modbus 400540 bit 1; not polled by default | Read | ||
| BI | 513 | Aux 3 Pickup Status Flags 3 - Pulse Input 1 Alarm | Modbus 400540 bit 2; not polled by default | Read | ||
| BI | 514 | Aux 3 Pickup Status Flags 3 - Current THD Alarm | Modbus 400540 bit 3; not polled by default | Read | ||
| BI | 515 | Aux 3 Pickup Status Flags 3 - Voltage THD Alarm | Modbus 400540 bit 4; not polled by default | Read | ||
| BI | 516 | Aux 3 Pickup Status Flags 3 - Analog Input Main Alarm | Modbus 400540 bit 5; not polled by default | Read | ||
| BI | 517 | Aux 3 Pickup Status Flags 3 - Analog Input Alt Alarm | Modbus 400540 bit 6; not polled by default | Read | ||
| BI | 518 | Aux 3 Pickup Status Flags 3 - Data Log 1 | Modbus 400540 bit 7; not polled by default | Read | ||
| BI | 519 | Aux 3 Pickup Status Flags 3 - Data Log 2 | Modbus 400540 bit 8; not polled by default | Read | ||
| BI | 520 | Aux 3 Pickup Status Flags 3 - Negative Real Power Demand Alarm | Modbus 400540 bit 9; not polled by default | Read | ||
| BI | 521 | Aux 3 Pickup Status Flags 3 - Negative Reactive Power Demand Alarm | Modbus 400540 bit 10; not polled by default | Read | ||
| BI | 522 | Aux 3 Pickup Status Flags 3 - Pulse Input 2 Aux 3 | Modbus 400540 bit 11; not polled by default | Read | ||
| BI | 523 | Aux 3 Pickup Status Flags 3 - Pulse Input 3 Alarm | Modbus 400540 bit 12; not polled by default | Read | ||
| BI | 524 | Aux 3 Pickup Status Flags 3 - Pulse Input 4 Alarm | Modbus 400540 bit 13; not polled by default | Read | ||
| BI | 525 | Aux 3 Pickup Status Flags 3 - Totalized Pulse In Alarm | Modbus 400540 bit 14; not polled by default | Read | ||
| BI | 526 | Aux 3 Pickup Status Flags 3 - Time Alarm | Modbus 400540 bit 15; not polled by default | Read | ||
| BI | 527 | Alarm Present | Modbus 400541 bit 0; not polled by default | Read | ||
| BI | 528 | Clock Not Set | Modbus 400541 bit 1; not polled by default | Read | ||
| BI | 529 | Clock Drifting | Modbus 400541 bit 2; not polled by default | Read | ||
| BI | 530 | Data Log 1 Running | Modbus 400541 bit 3; not polled by default | Read | ||
| BI | 531 | Data Log 2 Running | Modbus 400541 bit 4; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX GE PQMII point IDs by name
AI1Phase A CurrentAI2Phase B CurrentAI3Phase C CurrentAI4Average CurrentAI5Neutral CurrentAI6Current UnbalanceAI7Phase A Current - MinimumAI8Phase B Current - MinimumAI9Phase C Current - MinimumAI10Neutral Current - MinimumAI11Current Unbalance - MinimumAI12Phase A Current - MaximumAI13Phase B Current - MaximumAI14Phase C Current - MaximumAI15Neutral Current - MaximumAI16Current Unbalance - MaximumAI17Voltage VanAI18Voltage VbnAI19Voltage VcnAI20Average Phase VoltageAI21Voltage VabAI22Voltage VbcAI23Voltage VcaAI24Average Line VoltageAI25Voltage UnbalanceAI26Voltage Van - MinimumAI27Voltage Vbn - MinimumAI28Voltage Vcn - MinimumAI29Voltage Vab - MinimumAI30Voltage Vbc - MinimumAI31Voltage Vca - MinimumAI32Voltage Unbalance - MinimumAI33Voltage Van - MaximumAI34Voltage Vbn - MaximumAI35Voltage Vcn - MaximumAI36Voltage Vab - MaximumAI37Voltage Vbc - MaximumAI38Voltage Vca - MaximumAI39Voltage Unbalance - MaximumAI40Va Phasor AngleAI41Vb Phasor AngleAI42Vc Phasor AngleAI43Ia Phasor AngleAI44Ib Phasor AngleAI45Ic Phasor AngleAI463 Phase Real PowerAI473 Phase Reactive PowerAI483 Phase Apparent PowerAI493 Phase Power FactorAI50Phase A Real PowerAI51Phase A Reactive PowerAI52Phase A Apparent PowerAI53Phase A Power FactorAI54Phase B Real PowerAI55Phase B Reactive PowerAI56Phase B Apparent PowerAI57Phase B Power FactorAI58Phase C Real PowerAI59Phase C Reactive PowerAI60Phase C Apparent PowerAI61Phase C Power FactorAI623 Phase Real Power - MinimumAI633 Phase Reactive Power - MinimumAI643 Phase Apparent Power - MinimumAI653 Phase Power Factor - MinimumAI663 Phase Real Power - MaximumAI673 Phase Reactive Power - MaximumAI683 Phase Apparent Power - MaximumAI693 Phase Power Factor - MaximumAI70Phase A Real Power - MinimumAI71Phase A Reactive Power - MinimumAI72Phase A Apparent Power - MinimumAI73Phase A Power Factor - MinimumAI74Phase A Real Power - MaximumAI75Phase A Reactive Power - MaximumAI76Phase A Apparent Power - MaximumAI77Phase A Power Factor - MaximumAI78Phase B Real Power - MinimumAI79Phase B Reactive Power - MinimumAI80Phase B Apparent Power - MinimumAI81Phase B Power Factor - MinimumAI82Phase B Real Power - MaximumAI83Phase B Reactive Power - MaximumAI84Phase B Apparent Power - MaximumAI85Phase B Power Factor - MaximumAI86Phase C Real Power - MinimumAI87Phase C Reactive Power - MinimumAI88Phase C Apparent Power - MinimumAI89Phase C Power Factor - MinimumAI90Phase C Real Power - MaximumAI91Phase C Reactive Power - MaximumAI92Phase C Apparent Power - MaximumAI93Phase C Power Factor - MaximumAI943 Phase Positive Real Energy UsedAI953 Phase Negative Real Energy UsedAI963 Phase Positive React. Energy UsedAI973 Phase Neg Reactive Energy UsedAI983 Phase Apparent Energy UsedAI993 Phase Energy Used in Last 24 hAI1003 Phase Energy Cost Since ResetAI1013 Phase Energy Cost Per DayAI102Phase A Current DemandAI103Phase B Current DemandAI104Phase C Current DemandAI105Neutral Current DemandAI1063 Phase Real Power DemandAI1073 Phase React Power DemandAI1083 Phase Apparent Power DemandAI109Phase A Current Demand - MaximumAI110Phase B Current Demand - MaximumAI111Phase C Current Demand - MaximumAI112Neutral Current Demand - MaximumAI1133 Phase Real Power Dmd - MaxAI1143 Phase React Power Dmd - MaxAI1153 Phase Apparent Power Dmd - MaxAI116FrequencyAI117Frequency MinimumAI118Frequency MaximumBI119Switch A Input StatusBI120Switch B Input StatusBI121Switch C Input StatusBI122Switch D Input StatusBI123Aux 1 Relay LED Status FlagBI124Aux 2 Relay LED Status FlagBI125Aux 3 Relay LED Status FlagBI126Alarm LED Status FlagBI127Program LED Status FlagBI128Simulation LED Status FlagBI129Alarm Relay LED Status FlagBI130Self Test LED Status FlagBI131Aux 1 Relay LED Attribute Flag Off=Flash ON=SteadyBI132Aux 2 Relay LED Attribute Flag Off=Flash ON=SteadyBI133Aux 3 Relay LED Attribute Flag Off=Flash ON=SteadyBI134Alarm LED Attribute Flag Off=Flash ON=SteadyBI135Program LED Attribute Flag Off=Flash ON=SteadyBI136Simulation LED Attribute Flag Off=Flash ON=SteadyBI137Alarm relay LED Attribute Flag Off=Flash ON=SteadyBI138Self Test LED Attribute Flag Off=Flash ON=SteadyBI139Alarm RelayBI140Auxiliary Relay 1BI141Auxiliary Relay 2BI142Auxiliary Relay 3BI143Alarm Active Status Flags 1 - Phase Undercurrent AlarmBI144Alarm Active Status Flags 1 - Phase Overcurrent AlarmBI145Alarm Active Status Flags 1 - Neutral Overcurrent AlarmBI146Alarm Active Status Flags 1 - Undervoltage AlarmBI147Alarm Active Status Flags 1 - Overvoltage AlarmBI148Alarm Active Status Flags 1 - Current Unbalance AlarmBI149Alarm Active Status Flags 1 - Voltage Unbalance AlarmBI150Alarm Active Status Flags 1 - Voltage Phase ReversalBI151Alarm Active Status Flags 1 - PF Lead Alarm 1BI152Alarm Active Status Flags 1 - PF Lead Alarm 2BI153Alarm Active Status Flags 1 - Power Factor Log Alarm 1BI154Alarm Active Status Flags 1 - Ppower Factor Log Alarm 2BI155Alarm Active Status Flags 1 - Positive Real Power AlarmBI156Alarm Active Status Flags 1 - Neg Real Power AlarmBI157Alarm Active Status Flags 1 - Pos Reactive Power AlarmBI158Alarm Active Status Flags 1 - Neg Reactive Powere AlarmBI159Alarm Pickup Status Flags 1 - Phase Undercurrent AlarmBI160Alarm Pickup Status Flags 1 - Phase Overcurrent AlarmBI161Alarm Pickup Status Flags 1 - Neutral Overcurrent AlarmBI162Alarm Pickup Status Flags 1 - Undervoltage AlarmBI163Alarm Pickup Status Flags 1 - Overvoltage AlarmBI164Alarm Pickup Status Flags 1 - Current Unbalance AlarmBI165Alarm Pickup Status Flags 1 - Voltage Unbalance AlarmBI166Alarm Pickup Status Flags 1 - Voltage Phase ReversalBI167Alarm Pickup Status Flags 1 - PF Lead Alarm 1BI168Alarm Pickup Status Flags 1 - PF Lead Alarm 2BI169Alarm Pickup Status Flags 1 - Power Factor Log Alarm 1BI170Alarm Pickup Status Flags 1 - Ppower Factor Log Alarm 2BI171Alarm Pickup Status Flags 1 - Positive Real Power AlarmBI172Alarm Pickup Status Flags 1 - Neg Real Power AlarmBI173Alarm Pickup Status Flags 1 - Pos Reactive Power AlarmBI174Alarm Pickup Status Flags 1 - Neg Reactive Powere AlarmBI175Alarm Active Status Flags 2 - Underfrequency AlarmBI176Alarm Active Status Flags 2 - Overfrequency AlarmBI177Alarm Active Status Flags 2 - Positive Real Power Demand AlarmBI178Alarm Active Status Flags 2 - Positive Reactive Power Demand AlarmBI179Alarm Active Status Flags 2 - Appartent Power Demand AlarmBI180Alarm Active Status Flags 2 - Ph A Current Demand AlarmBI181Alarm Active Status Flags 2 - Ph B Current Demand AlarmBI182Alarm Active Status Flags 2 - Ph C Current DemanD AlarmBI183Alarm Active Status Flags 2 - Nuetral Current Demand AlarmBI184Alarm Active Status Flags 2 - Switch A AlarmBI185Alarm Active Status Flags 2 - Switch B AlarmBI186Alarm Active Status Flags 2 - Switch C AlarmBI187Alarm Active Status Flags 2 - Switch D AlarmBI188Alarm Active Status Flags 2 - Internal Fault AlarmBI189Alarm Active Status Flags 2 - Serial COM1 Failure AlarmBI190Alarm Active Status Flags 2 - Serial COM2 Failure AlarmBI191Alarm Pickup Status Flags 2 - Underfrequency AlarmBI192Alarm Pickup Status Flags 2 - Overfrequency AlarmBI193Alarm Pickup Status Flags 2 - Positive Real Power Demand AlarmBI194Alarm Pickup Status Flags 2 - Positive Reactive Power Demand AlarmBI195Alarm Pickup Status Flags 2 - Appartent Power Demand AlarmBI196Alarm Pickup Status Flags 2 - Ph A Current Demand AlarmBI197Alarm Pickup Status Flags 2 - Ph B Current Demand AlarmBI198Alarm Pickup Status Flags 2 - Ph C Current DemanD AlarmBI199Alarm Pickup Status Flags 2 - Nuetral Current Demand AlarmBI200Alarm Pickup Status Flags 2 - Switch A AlarmBI201Alarm Pickup Status Flags 2 - Switch B AlarmBI202Alarm Pickup Status Flags 2 - Switch C AlarmBI203Alarm Pickup Status Flags 2 - Switch D AlarmBI204Alarm Pickup Status Flags 2 - Internal Fault AlarmBI205Alarm Pickup Status Flags 2 - Serial COM1 Failure AlarmBI206Alarm Pickup Status Flags 2 - Serial COM2 Failure AlarmBI207Alarm Active Status Flags 3 - Clock Not Set AlarmBI208Alarm Active Status Flags 3 - Parameters Not Set AlarmBI209Alarm Active Status Flags 3 - Pulse Input 1 AlarmBI210Alarm Active Status Flags 3 - Current THD AlarmBI211Alarm Active Status Flags 3 - Voltage THD AlarmBI212Alarm Active Status Flags 3 - Analog Input Main AlarmBI213Alarm Active Status Flags 3 - Analog Input Alt AlarmBI214Alarm Active Status Flags 3 - Data Log 1BI215Alarm Active Status Flags 3 - Data Log 2BI216Alarm Active Status Flags 3 - Negative Real Power Demand AlarmBI217Alarm Active Status Flags 3 - Negative Reactive Power Demand AlarmBI218Alarm Active Status Flags 3 - Pulse Input 2 AlarmBI219Alarm Active Status Flags 3 - Pulse Input 3 AlarmBI220Alarm Active Status Flags 3 - Pulse Input 4 AlarmBI221Alarm Active Status Flags 3 - Totalized Pulse In AlarmBI222Alarm Active Status Flags 3 - Time AlarmBI223Alarm Pickup Status Flags 3 - Clock Not Set AlarmBI224Alarm Pickup Status Flags 3 - Parameters Not Set AlarmBI225Alarm Pickup Status Flags 3 - Pulse Input 1 AlarmBI226Alarm Pickup Status Flags 3 - Current THD AlarmBI227Alarm Pickup Status Flags 3 - Voltage THD AlarmBI228Alarm Pickup Status Flags 3 - Analog Input Main AlarmBI229Alarm Pickup Status Flags 3 - Analog Input Alt AlarmBI230Alarm Pickup Status Flags 3 - Data Log 1BI231Alarm Pickup Status Flags 3 - Data Log 2BI232Alarm Pickup Status Flags 3 - Negative Real Power Demand AlarmBI233Alarm Pickup Status Flags 3 - Negative Reactive Power Demand AlarmBI234Alarm Pickup Status Flags 3 - Pulse Input 2 AlarmBI235Alarm Pickup Status Flags 3 - Pulse Input 3 AlarmBI236Alarm Pickup Status Flags 3 - Pulse Input 4 AlarmBI237Alarm Pickup Status Flags 3 - Totalized Pulse In AlarmBI238Alarm Pickup Status Flags 3 - Time AlarmBI239Aux 1 Active Status Flags 1 - Phase Undercurrent AlarmBI240Aux 1 Active Status Flags 1 - Phase Overcurrent AlarmBI241Aux 1 Active Status Flags 1 - Neutral Overcurrent AlarmBI242Aux 1 Active Status Flags 1 - Undervoltage AlarmBI243Aux 1 Active Status Flags 1 - Overvoltage AlarmBI244Aux 1 Active Status Flags 1 - Current Unbalance AlarmBI245Aux 1 Active Status Flags 1 - Voltage Unbalance AlarmBI246Aux 1 Active Status Flags 1 - Voltage Phase Reversal AlarmBI247Aux 1 Active Status Flags 1 - PF Lead Alarm 1BI248Aux 1 Active Status Flags 1 - PF Lead Alarm 2BI249Aux 1 Active Status Flags 1 - Power Factor Log Alarm 1BI250Aux 1 Active Status Flags 1 - Power Factor Log Alarm 2BI251Aux 1 Active Status Flags 1 - Positive Real Power AlarmBI252Aux 1 Active Status Flags 1 - Neg Real Power AlarmBI253Aux 1 Active Status Flags 1 - Pos Reactive Power AlarmBI254Aux 1 Active Status Flags 1 - Neg Reactive Powere AlarmBI255Aux 1 Pickup Status Flags 1 - Phase Undercurrent AlarmBI256Aux 1 Pickup Status Flags 1 - Phase Overcurrent AlarmBI257Aux 1 Pickup Status Flags 1 - Neutral Overcurrent AlarmBI258Aux 1 Pickup Status Flags 1 - Undervoltage AlarmBI259Aux 1 Pickup Status Flags 1 - Overvoltage AlarmBI260Aux 1 Pickup Status Flags 1 - Current Unbalance AlarmBI261Aux 1 Pickup Status Flags 1 - Voltage Unbalance AlarmBI262Aux 1 Pickup Status Flags 1 - Voltage Phase Reversal AlarmBI263Aux 1 Pickup Status Flags 1 - PF Lead Alarm 1BI264Aux 1 Pickup Status Flags 1 - PF Lead Alarm 2BI265Aux 1 Pickup Status Flags 1 - Power Factor Log Alarm 1BI266Aux 1 Pickup Status Flags 1 - Ppower Factor Log Alarm 2BI267Aux 1 Pickup Status Flags 1 - Positive Real Power AlarmBI268Aux 1 Pickup Status Flags 1 - Neg Real Power AlarmBI269Aux 1 Pickup Status Flags 1 - Pos Reactive Power AlarmBI270Aux 1 Pickup Status Flags 1 - Neg Reactive Powere AlarmBI271Aux 1 Active Status Flags 2 - Underfrequency AlarmBI272Aux 1 Active Status Flags 2 - Overfrequency AlarmBI273Aux 1 Active Status Flags 2 - Positive Real Power Demand AlarmBI274Aux 1 Active Status Flags 2 - Positive Reactive Power Demand AlarmBI275Aux 1 Active Status Flags 2 - Appartent Power Demand AlarmBI276Aux 1 Active Status Flags 2 - Ph A Current Demand AlarmBI277Aux 1 Active Status Flags 2 - Ph B Current Demand AlarmBI278Aux 1 Active Status Flags 2 - Ph C Current Demand AlarmBI279Aux 1 Active Status Flags 2 - Nuetral Current Demand AlarmBI280Aux 1 Active Status Flags 2 - Switch A AlarmBI281Aux 1 Active Status Flags 2 - Switch B AlarmBI282Aux 1 Active Status Flags 2 - Switch C AlarmBI283Aux 1 Active Status Flags 2 - Switch D AlarmBI284Aux 1 Active Status Flags 2 - Internal Fault AlarmBI285Aux 1 Active Status Flags 2 - Serial COM1 Failure AlarmBI286Aux 1 Active Status Flags 2 - Serial COM2 Failure AlarmBI287Aux 1 Pickup Status Flags 2 - Underfrequency AlarmBI288Aux 1 Pickup Status Flags 2 - Overfrequency AlarmBI289Aux 1 Pickup Status Flags 2 - Positive Real Power Demand AlarmBI290Aux 1 Pickup Status Flags 2 - Positive Reactive Power Demand AlarmBI291Aux 1 Pickup Status Flags 2 - Appartent Power Demand AlarmBI292Aux 1 Pickup Status Flags 2 - Ph A Current Demand AlarmBI293Aux 1 Pickup Status Flags 2 - Ph B Current Demand AlarmBI294Aux 1 Pickup Status Flags 2 - Ph C Current DemanD AlarmBI295Aux 1 Pickup Status Flags 2 - Nuetral Current Demand AlarmBI296Aux 1 Pickup Status Flags 2 - Switch A AlarmBI297Aux 1 Pickup Status Flags 2 - Switch B AlarmBI298Aux 1 Pickup Status Flags 2 - Switch C AlarmBI299Aux 1 Pickup Status Flags 2 - Switch D AlarmBI300Aux 1 Pickup Status Flags 2 - Internal Fault AlarmBI301Aux 1 Pickup Status Flags 2 - Serial COM1 Failure AlarmBI302Aux 1 Pickup Status Flags 2 - Serial COM2 Failure AlarmBI303Aux 1 Active Status Flags 3 - Clock Not Set AlarmBI304Aux 1 Active Status Flags 3 - Parameters Not Set AlarmBI305Aux 1 Active Status Flags 3 - Pulse Input 1 AlarmBI306Aux 1 Active Status Flags 3 - Current THD AlarmBI307Aux 1 Active Status Flags 3 - Voltage THD AlarmBI308Aux 1 Active Status Flags 3 - Analog Input Main AlarmBI309Aux 1 Active Status Flags 3 - Analog Input Alt AlarmBI310Aux 1 Active Status Flags 3 - Data Log 1BI311Aux 1 Active Status Flags 3 - Data Log 2BI312Aux 1 Active Status Flags 3 - Negative Real Power Demand AlarmBI313Aux 1 Active Status Flags 3 - Negative Reactive Power Demand AlarmBI314Aux 1 Active Status Flags 3 - Pulse Input 2 AlarmBI315Aux 1 Active Status Flags 3 - Pulse Input 3 AlarmBI316Aux 1 Active Status Flags 3 - Pulse Input 4 AlarmBI317Aux 1 Active Status Flags 3 - Totalized Pulse In AlarmBI318Aux 1 Active Status Flags 3 - Time AlarmBI319Aux 1 Pickup Status Flags 3 - Clock Not Set AlarmBI320Aux 1 Pickup Status Flags 3 - Parameters Not Set AlarmBI321Aux 1 Pickup Status Flags 3 - Pulse Input 1 AlarmBI322Aux 1 Pickup Status Flags 3 - Current THD AlarmBI323Aux 1 Pickup Status Flags 3 - Voltage THD AlarmBI324Aux 1 Pickup Status Flags 3 - Analog Input Main AlarmBI325Aux 1 Pickup Status Flags 3 - Analog Input Alt AlarmBI326Aux 1 Pickup Status Flags 3 - Data Log 1BI327Aux 1 Pickup Status Flags 3 - Data Log 2BI328Aux 1 Pickup Status Flags 3 - Negative Real Power Demand AlarmBI329Aux 1 Pickup Status Flags 3 - Negative Reactive Power Demand AlarmBI330Aux 1 Pickup Status Flags 3 - Pulse Input 2 AlarmBI331Aux 1 Pickup Status Flags 3 - Pulse Input 3 AlarmBI332Aux 1 Pickup Status Flags 3 - Pulse Input 4 AlarmBI333Aux 1 Pickup Status Flags 3 - Totalized Pulse In AlarmBI334Aux 1 Pickup Status Flags 3 - Time AlarmBI335Aux 2 Active Status Flags 1 - Phase Undercurrent AlarmBI336Aux 2 Active Status Flags 1 - Phase Overcurrent AlarmBI337Aux 2 Active Status Flags 1 - Neutral Overcurrent AlarmBI338Aux 2 Active Status Flags 1 - Undervoltage AlarmBI339Aux 2 Active Status Flags 1 - Overvoltage AlarmBI340Aux 2 Active Status Flags 1 - Current Unbalance AlarmBI341Aux 2 Active Status Flags 1 - Voltage Unbalance AlarmBI342Aux 2 Active Status Flags 1 - Voltage Phase Reversal AlarmBI343Aux 2 Active Status Flags 1 - PF Lead Alarm 1BI344Aux 2 Active Status Flags 1 - PF Lead Alarm 2BI345Aux 2 Active Status Flags 1 - Power Factor Log AlarmBI346Aux 2 Active Status Flags 1 - Ppower Factor Log AlarmBI347Aux 2 Active Status Flags 1 - Positive Real Power AlarmBI348Aux 2 Active Status Flags 1 - Neg Real Power AlarmBI349Aux 2 Active Status Flags 1 - Pos Reactive Power AlarmBI350Aux 2 Active Status Flags 1 - Neg Reactive Powere AlarmBI351Aux 2 Pickup Status Flags 1 - Phase Undercurrent AlarmBI352Aux 2 Pickup Status Flags 1 - Phase Overcurrent AlarmBI353Aux 2 Pickup Status Flags 1 - Neutral Overcurrent AlarmBI354Aux 2 Pickup Status Flags 1 - Undervoltage AlarmBI355Aux 2 Pickup Status Flags 1 - Overvoltage AlarmBI356Aux 2 Pickup Status Flags 1 - Current Unbalance AlarmBI357Aux 2 Pickup Status Flags 1 - Voltage Unbalance AlarmBI358Aux 2 Pickup Status Flags 1 - Voltage Phase Reversal AlarmBI359Aux 2 Pickup Status Flags 1 - PF Lead Alarm 1BI360Aux 2 Pickup Status Flags 1 - PF Lead Alarm 2BI361Aux 2 Pickup Status Flags 1 - Power Factor Log AlarmBI362Aux 2 Pickup Status Flags 1 - Power Factor Log Alarm 2BI363Aux 2 Pickup Status Flags 1 - Positive Real Power AlarmBI364Aux 2 Pickup Status Flags 1 - Neg Real Power AlarmBI365Aux 2 Pickup Status Flags 1 - Pos Reactive Power AlarmBI366Aux 2 Pickup Status Flags 1 - Neg Reactive Powere AlarmBI367Aux 2 Active Status Flags 2 - Underfrequency AlarmBI368Aux 2 Active Status Flags 2 - Overfrequency AlarmBI369Aux 2 Active Status Flags 2 - Positive Real Power Demand AlarmBI370Aux 2 Active Status Flags 2 - Positive Reactive Power Demand AlarmBI371Aux 2 Active Status Flags 2 - Appartent Power Demand AlarmBI372Aux 2 Active Status Flags 2 - Ph A Current Demand AlarmBI373Aux 2 Active Status Flags 2 - Ph B Current Demand AlarmBI374Aux 2 Active Status Flags 2 - Ph C Current DemanD AlarmBI375Aux 2 Active Status Flags 2 - Nuetral Current Demand AlarmBI376Aux 2 Active Status Flags 2 - Switch A AlarmBI377Aux 2 Active Status Flags 2 - Switch B AlarmBI378Aux 2 Active Status Flags 2 - Switch C AlarmBI379Aux 2 Active Status Flags 2 - Switch D AlarmBI380Aux 2 Active Status Flags 2 - Internal Fault AlarmBI381Aux 2 Active Status Flags 2 - Serial COM1 Failure AlarmBI382Aux 2 Active Status Flags 2 - Serial COM2 Failure AlarmBI383Aux 2 Pickup Status Flags 2 - Underfrequency AlarmBI384Aux 2 Pickup Status Flags 2 - Overfrequency AlarmBI385Aux 2 Pickup Status Flags 2 - Positive Real Power Demand AlarmBI386Aux 2 Pickup Status Flags 2 - Positive Reactive Power Demand AlarmBI387Aux 2 Pickup Status Flags 2 - Appartent Power Demand AlarmBI388Aux 2 Pickup Status Flags 2 - Ph A Current Demand AlarmBI389Aux 2 Pickup Status Flags 2 - Ph B Current Demand AlarmBI390Aux 2 Pickup Status Flags 2 - Ph C Current DemanD AlarmBI391Aux 2 Pickup Status Flags 2 - Nuetral Current Demand AlarmBI392Aux 2 Pickup Status Flags 2 - Switch A AlarmBI393Aux 2 Pickup Status Flags 2 - Switch B AlarmBI394Aux 2 Pickup Status Flags 2 - Switch C AlarmBI395Aux 2 Pickup Status Flags 2 - Switch D AlarmBI396Aux 2 Pickup Status Flags 2 - Internal Fault AlarmBI397Aux 2 Pickup Status Flags 2 - Serial COM1 Failure AlarmBI398Aux 2 Pickup Status Flags 2 - Serial COM2 Failure AlarmBI399Aux 2 Active Status Flags 3 - Clock Not Set AlarmBI400Aux 2 Active Status Flags 3 - Parameters Not Set AlarmBI401Aux 2 Active Status Flags 3 - Pulse Input 1 AlarmBI402Aux 2 Active Status Flags 3 - Current THD AlarmBI403Aux 2 Active Status Flags 3 - Voltage THD AlarmBI404Aux 2 Active Status Flags 3 - Analog Input Main AlarmBI405Aux 2 Active Status Flags 3 - Analog Input Alt AlarmBI406Aux 2 Active Status Flags 3 - Data Log 1BI407Aux 2 Active Status Flags 3 - Data Log 2BI408Aux 2 Active Status Flags 3 - Negative Real Power Demand AlarmBI409Aux 2 Active Status Flags 3 - Negative Reactive Power Demand AlarmBI410Aux 2 Active Status Flags 3 - Pulse Input 2 AlarmBI411Aux 2 Active Status Flags 3 - Pulse Input 3 AlarmBI412Aux 2 Active Status Flags 3 - Pulse Input 4 AlarmBI413Aux 2 Active Status Flags 3 - Totalized Pulse In AlarmBI414Aux 2 Active Status Flags 3 - Time AlarmBI415Aux 2 Pickup Status Flags 3 - Clock Not Set AlarmBI416Aux 2 Pickup Status Flags 3 - Parameters Not Set AlarmBI417Aux 2 Pickup Status Flags 3 - Pulse Input 1 AlarmBI418Aux 2 Pickup Status Flags 3 - Current THD AlarmBI419Aux 2 Pickup Status Flags 3 - Voltage THD AlarmBI420Aux 2 Pickup Status Flags 3 - Analog Input Main AlarmBI421Aux 2 Pickup Status Flags 3 - Analog Input Alt AlarmBI422Aux 2 Pickup Status Flags 3 - Data Log 1BI423Aux 2 Pickup Status Flags 3 - Data Log 2BI424Aux 2 Pickup Status Flags 3 - Negative Real Power Demand AlarmBI425Aux 2 Pickup Status Flags 3 - Negative Reactive Power Demand AlarmBI426Aux 2 Pickup Status Flags 3 - Pulse Input 2 Aux 2BI427Aux 2 Pickup Status Flags 3 - Pulse Input 3 AlarmBI428Aux 2 Pickup Status Flags 3 - Pulse Input 4 AlarmBI429Aux 2 Pickup Status Flags 3 - Totalized Pulse In AlarmBI430Aux 2 Pickup Status Flags 3 - Time AlarmBI431Aux 3 Active Status Flags 1 - Phase Undercurrent AlarmBI432Aux 3 Active Status Flags 1 - Phase Overcurrent AlarmBI433Aux 3 Active Status Flags 1 - Neutral Overcurrent AlarmBI434Aux 3 Active Status Flags 1 - Undervoltage AlarmBI435Aux 3 Active Status Flags 1 - Overvoltage AlarmBI436Aux 3 Active Status Flags 1 - Current Unbalance AlarmBI437Aux 3 Active Status Flags 1 - Voltage Unbalance AlarmBI438Aux 3 Active Status Flags 1 - Voltage Phase Reversal AlarmBI439Aux 3 Active Status Flags 1 - PF Lead Alarm 1BI440Aux 3 Active Status Flags 1 - PF Lead Alarm 2BI441Aux 3 Active Status Flags 1 - Power Factor Log AlarmBI442Aux 3 Active Status Flags 1 - Ppower Factor Log AlarmBI443Aux 3 Active Status Flags 1 - Positive Real Power AlarmBI444Aux 3 Active Status Flags 1 - Neg Real Power AlarmBI445Aux 3 Active Status Flags 1 - Pos Reactive Power AlarmBI446Aux 3 Active Status Flags 1 - Neg Reactive Powere AlarmBI447Aux 3 Pickup Status Flags 1 - Phase Undercurrent AlarmBI448Aux 3 Pickup Status Flags 1 - Phase Overcurrent AlarmBI449Aux 3 Pickup Status Flags 1 - Neutral Overcurrent AlarmBI450Aux 3 Pickup Status Flags 1 - Undervoltage AlarmBI451Aux 3 Pickup Status Flags 1 - Overvoltage AlarmBI452Aux 3 Pickup Status Flags 1 - Current Unbalance AlarmBI453Aux 3 Pickup Status Flags 1 - Voltage Unbalance AlarmBI454Aux 3 Pickup Status Flags 1 - Voltage Phase Reversal AlarmBI455Aux 3 Pickup Status Flags 1 - PF Lead Alarm 1BI456Aux 3 Pickup Status Flags 1 - PF Lead Alarm 2BI457Aux 3 Pickup Status Flags 1 - Power Factor Log AlarmBI458Aux 3 Pickup Status Flags 1 - Power Factor Log Alarm 2BI459Aux 3 Pickup Status Flags 1 - Positive Real Power AlarmBI460Aux 3 Pickup Status Flags 1 - Neg Real Power AlarmBI461Aux 3 Pickup Status Flags 1 - Pos Reactive Power AlarmBI462Aux 3 Pickup Status Flags 1 - Neg Reactive Powere AlarmBI463Aux 3 Active Status Flags 2 - Underfrequency AlarmBI464Aux 3 Active Status Flags 2 - Overfrequency AlarmBI465Aux 3 Active Status Flags 2 - Positive Real Power Demand AlarmBI466Aux 3 Active Status Flags 2 - Positive Reactive Power Demand AlarmBI467Aux 3 Active Status Flags 2 - Appartent Power Demand AlarmBI468Aux 3 Active Status Flags 2 - Ph A Current Demand AlarmBI469Aux 3 Active Status Flags 2 - Ph B Current Demand AlarmBI470Aux 3 Active Status Flags 2 - Ph C Current DemanD AlarmBI471Aux 3 Active Status Flags 2 - Nuetral Current Demand AlarmBI472Aux 3 Active Status Flags 2 - Switch A AlarmBI473Aux 3 Active Status Flags 2 - Switch B AlarmBI474Aux 3 Active Status Flags 2 - Switch C AlarmBI475Aux 3 Active Status Flags 2 - Switch D AlarmBI476Aux 3 Active Status Flags 2 - Internal Fault AlarmBI477Aux 3 Active Status Flags 2 - Serial COM1 Failure AlarmBI478Aux 3 Active Status Flags 2 - Serial COM2 Failure AlarmBI479Aux 3 Pickup Status Flags 2 - Underfrequency AlarmBI480Aux 3 Pickup Status Flags 2 - Overfrequency AlarmBI481Aux 3 Pickup Status Flags 2 - Positive Real Power Demand AlarmBI482Aux 3 Pickup Status Flags 2 - Positive Reactive Power Demand AlarmBI483Aux 3 Pickup Status Flags 2 - Appartent Power Demand AlarmBI484Aux 3 Pickup Status Flags 2 - Ph A Current Demand AlarmBI485Aux 3 Pickup Status Flags 2 - Ph B Current Demand AlarmBI486Aux 3 Pickup Status Flags 2 - Ph C Current DemanD AlarmBI487Aux 3 Pickup Status Flags 2 - Nuetral Current Demand AlarmBI488Aux 3 Pickup Status Flags 2 - Switch A AlarmBI489Aux 3 Pickup Status Flags 2 - Switch B AlarmBI490Aux 3 Pickup Status Flags 2 - Switch C AlarmBI491Aux 3 Pickup Status Flags 2 - Switch D AlarmBI492Aux 3 Pickup Status Flags 2 - Internal Fault AlarmBI493Aux 3 Pickup Status Flags 2 - Serial COM1 Failure AlarmBI494Aux 3 Pickup Status Flags 2 - Serial COM2 Failure AlarmBI495Aux 3 Active Status Flags 3 - Clock Not Set AlarmBI496Aux 3 Active Status Flags 3 - Parameters Not Set AlarmBI497Aux 3 Active Status Flags 3 - Pulse Input 1 AlarmBI498Aux 3 Active Status Flags 3 - Current THD AlarmBI499Aux 3 Active Status Flags 3 - Voltage THD AlarmBI500Aux 3 Active Status Flags 3 - Analog Input Main AlarmBI501Aux 3 Active Status Flags 3 - Analog Input Alt AlarmBI502Aux 3 Active Status Flags 3 - Data Log 1BI503Aux 3 Active Status Flags 3 - Data Log 2BI504Aux 3 Active Status Flags 3 - Negative Real Power Demand AlarmBI505Aux 3 Active Status Flags 3 - Negative Reactive Power Demand AlarmBI506Aux 3 Active Status Flags 3 - Pulse Input 2 AlarmBI507Aux 3 Active Status Flags 3 - Pulse Input 3 AlarmBI508Aux 3 Active Status Flags 3 - Pulse Input 4 AlarmBI509Aux 3 Active Status Flags 3 - Totalized Pulse In AlarmBI510Aux 3 Active Status Flags 3 - Time AlarmBI511Aux 3 Pickup Status Flags 3 - Clock Not Set AlarmBI512Aux 3 Pickup Status Flags 3 - Parameters Not Set AlarmBI513Aux 3 Pickup Status Flags 3 - Pulse Input 1 AlarmBI514Aux 3 Pickup Status Flags 3 - Current THD AlarmBI515Aux 3 Pickup Status Flags 3 - Voltage THD AlarmBI516Aux 3 Pickup Status Flags 3 - Analog Input Main AlarmBI517Aux 3 Pickup Status Flags 3 - Analog Input Alt AlarmBI518Aux 3 Pickup Status Flags 3 - Data Log 1BI519Aux 3 Pickup Status Flags 3 - Data Log 2BI520Aux 3 Pickup Status Flags 3 - Negative Real Power Demand AlarmBI521Aux 3 Pickup Status Flags 3 - Negative Reactive Power Demand AlarmBI522Aux 3 Pickup Status Flags 3 - Pulse Input 2 Aux 3BI523Aux 3 Pickup Status Flags 3 - Pulse Input 3 AlarmBI524Aux 3 Pickup Status Flags 3 - Pulse Input 4 AlarmBI525Aux 3 Pickup Status Flags 3 - Totalized Pulse In AlarmBI526Aux 3 Pickup Status Flags 3 - Time AlarmBI527Alarm PresentBI528Clock Not SetBI529Clock DriftingBI530Data Log 1 RunningBI531Data Log 2 Running
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile GE_PQMII_Power_Meter_Lite_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/GEK-113532.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 38 of the 531 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GE Multilin PQMII via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls GE Multilin PQMII via BASgatewayLX
How many BACnet points does the Contemporary Controls GE Multilin PQMII via BASgatewayLX have?
This list has 531 BACnet objects: 118 analog inputs, 413 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls GE Multilin PQMII via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile GE_PQMII_Power_Meter_Lite (GE_PQMII_Power_Meter_Lite_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/GE_PQMII_Power_Meter_Lite_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls GE Multilin PQMII via BASgatewayLX?
Start with AI 46 3 Phase Real Power (3-phase real power); AI 94 3 Phase Positive Real Energy Used (3-phase positive real energy); AI 24 Average Line Voltage (Average line voltage); AI 4 Average Current (Average current); AI 49 3 Phase Power Factor (3-phase power factor); AI 116 Frequency (Frequency); AI 106 3 Phase Real Power Demand (3-phase real power demand); BI 139 Alarm Relay (Alarm relay).
How do I check these points on the real GE Multilin PQMII via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile GE_PQMII_Power_Meter_Lite · GE_PQMII_Power_Meter_Lite_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.