Precision cooling unit (computer room air handler) · BACnet points list

Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for Liebert table 27 units: 73 objects (18 AI, 16 AO, 33 BI, 6 BO), all polled. Inputs give temperature, humidity, cooling, heating, humidify, dehumidify, economizer, stages, % capacity, unit status and the alarm bits; outputs set the setpoints, tolerances, alarm limits and delays, and switch the unit on/off and reheat/humidifier lockouts.

This page lists 73 BACnet objects for the Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Equipment
Precision cooling unit (computer room air handler)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
73 (22 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan
Source document
BASgatewayLX Modbus device profile Liebert_Table_27_b · Liebert_Table_27_b_LX.csv
Download CSV 73 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX

Integration in brief

Turn the unit on with Unit ON (BO 65) and off with Unit OFF (BO 64), write the temperature and humidity setpoints, then read temperature, humidity, % capacity and the alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 65Unit ONUnit on commandCommand
BO 64Unit OFFUnit off commandCommand
AO 66Temperature SetpointTemperature setpoint (control)Command
AO 68Humidity SetpointHumidity setpoint (control)Command
AI 10Unit Status (On / Off)Unit status (on/off)Read
AI 1TemperatureUnit temperature readingRead
AI 2HumidityUnit humidity readingRead
AI 9% CapacityCooling capacity, %Read
BI 24High TemperatureHigh temperature alarmRead
BI 20Loss of AirflowLoss of airflowRead

Network setup

Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

73 of 73 shown
Type
Access
Show
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX BACnet Points List
DescriptionStates
AImin1TemperatureModbus 400001Read
AImin2HumidityModbus 400002Read
AI3CoolingModbus 400003Read
AI4HeatingModbus 400004Read
AI5HumidificationModbus 400005Read
AI6De-humidificationModbus 400006Read
AI7Econ-O-CycleModbus 400007Read
AI8StagesModbus 400008Read
AImin9% CapacityModbus 400009Read
AImin10Unit Status (On / Off)Modbus 400018Read
AI11Analog input 1Modbus 400023Read
AI12Analog input 2Modbus 400024Read
AI13Analog input 3Modbus 400025Read
AI14Analog input 4Modbus 400026Read
BI15CommunicationsModbus 400289 bit 0Read
BI16Local OffModbus 400289 bit 1Read
BI17Remote OffModbus 400289 bit 2Read
BI18High Head Pressure 1Modbus 400289 bit 3Read
BI19High Head Pressure 2Modbus 400289 bit 4Read
BImin20Loss of AirflowModbus 400289 bit 5Read
BI21Standby Glycol Unit OnModbus 400289 bit 6Read
BI22Liquid DetectedModbus 400289 bit 7Read
BI23Change FiltersModbus 400289 bit 8Read
BImin24High TemperatureModbus 400289 bit 9Read
BI25Low TemperatureModbus 400289 bit 10Read
BI26High HumidityModbus 400290 bit 0Read
BI27Low HumidityModbus 400290 bit 1Read
BI28Humidifier ProblemModbus 400290 bit 2Read
BI29No Water in Humidifier PanModbus 400290 bit 3Read
BI30Compressor 1 OverloadModbus 400290 bit 4Read
BI31Compressor 2 OverloadModbus 400290 bit 5Read
BI32Main Fan OverloadModbus 400290 bit 6Read
BI33Manual OverrideModbus 400290 bit 7Read
BI34Smoke DetectedModbus 400290 bit 8Read
BI35Loss of WaterModbus 400290 bit 9Read
BI36Standby Unit OnModbus 400290 bit 10Read
BI37Low SuctionModbus 400291 bit 0Read
BI38Short CycleModbus 400291 bit 1Read
BI39Loss of PowerModbus 400291 bit 2Read
BI40Inverter on BypassModbus 400291 bit 3Read
BI41Standby Fan OnModbus 400291 bit 4Read
BI42Loss of Emergency PowerModbus 400291 bit 5Read
BI43Local Alarm 1Modbus 400291 bit 6Read
BI44Local Alarm 2Modbus 400291 bit 7Read
BI45Off by Remote ShutdownModbus 400291 bit 8Read
BI46Local Alarm 3Modbus 400291 bit 9Read
BI47Local Alarm 4Modbus 400291 bit 10Read
AI48Compressor 1 Run HoursModbus 400019hRead
AI49Compressor 2 Run HoursModbus 400020hRead
AI50Fan Motor Run HoursModbus 400021hRead
AI51Humidifier Run HoursModbus 400022hRead
AO52Temperature SetpointModbus 400010Command
AO53Temperature ToleranceModbus 400011Command
AO54Humidity SetpointModbus 400012Command
AO55Humidity ToleranceModbus 400013Command
AO56High Temp Alarm SetpointModbus 400014Command
AO57Low Temp Alarm SetpointModbus 400015Command
AO58High Humd Alarm SetpointModbus 400016Command
AO59Low Humidity Alarm SetpointModbus 400017Command
AO60Winter Start DelayModbus 400028Command
AO61Auto Flush RateModbus 400029Command
AO62Chill Water Flush RateModbus 400030Command
AO63Auto Restart DelayModbus 400031Command
BOmin64Unit OFFModbus 400349 bit 0Command
BOmin65Unit ONModbus 400349 bit 1Command
AOmin66Temperature SetpointModbus 400350Command
AO67Temperature ToleranceModbus 400350Command
AOmin68Humidity SetpointModbus 400351Command
AO69Humidity ToleranceModbus 400351Command
BO70Reheat Lockout OffModbus 400349 bit 2Command
BO71Reheat Lockout OnModbus 400349 bit 3Command
BO72Humidifier Lockout OffModbus 400349 bit 4Command
BO73Humidifier Lockout OnModbus 400349 bit 5Command
Object ID lookup: Contemporary Controls BASgatewayLX Liebert Table 27 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX

How many BACnet points does the Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX have?

This list has 73 BACnet objects: 18 analog inputs, 16 analog outputs, 33 binary inputs, 6 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX BACnet points are writable?

22 of the 73 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Liebert_Table_27_b (Liebert_Table_27_b_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Liebert_Table_27_b_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX?

Start with BO 65 Unit ON (Unit on command); BO 64 Unit OFF (Unit off command); AO 66 Temperature Setpoint (Temperature setpoint (control)); AO 68 Humidity Setpoint (Humidity setpoint (control)); AI 10 Unit Status (On / Off) (Unit status (on/off)); AI 1 Temperature (Unit temperature reading); AI 2 Humidity (Unit humidity reading); AI 9 % Capacity (Cooling capacity, %); BI 24 High Temperature (High temperature alarm); BI 20 Loss of Airflow (Loss of airflow).

How do I check these points on the real Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Liebert_Table_27_b · Liebert_Table_27_b_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.