Power and energy meter · BACnet points list

Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for E-Mon D-Mon Class 3200/3400/5000 meters: 50 objects (40 AI, 10 AO), 38 polled by default. Energy delivered/received registers are mapped as outputs (presettable); inputs give real, reactive and apparent power, PF, peak demand, current, voltages, frequency, phase angle and per-phase values.

This page lists 50 BACnet objects for the Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
50 (10 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon
Source document
BASgatewayLX Modbus device profile E_Mon_D_Mon_3200_3400_5000 · E_Mon_D_Mon_3200_3400_5000_LX.csv
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX

Integration in brief

Map energy delivered, energy received and real power first. Outputs in this profile change stored values or settings, so write them only on purpose.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 5Energy deliveredEnergy deliveredCommand
AO 6Energy receivedEnergy receivedCommand
AI 9Real powerReal powerRead
AI 13Peak demandPeak demandRead
AI 15Voltage line-neutralVoltage line-neutralRead
AI 14Current averageAverage currentRead
AI 12Power factorPower factorRead
AI 17FrequencyFrequencyRead

Network setup

Watch out for

Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

50 of 50 shown
Type
Access
Show
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX BACnet Points List
DescriptionStates
AO1Energy delivered Wh PulseModbus 400001; not polled by defaultCommand
AO2Energy received Wh PulseModbus 400003; not polled by defaultCommand
AO3Reactive energy delivered VARh PulseModbus 400005; not polled by defaultCommand
AO4Reactive energy received VARh PulseModbus 400007; not polled by defaultCommand
AOmin5Energy deliveredModbus 401001kWhCommand
AOmin6Energy receivedModbus 401003kWhCommand
AO7Reactive energy deliveredModbus 401005kVARCommand
AO8Reactive energy receivedModbus 401007kVARCommand
AImin9Real powerModbus 401009kWRead
AI10Reactive powerModbus 401011kVARead
AI11Apparent powerModbus 401013kVARead
AImin12Power factorModbus 401015PFRead
AImin13Peak demandModbus 401017kWRead
AImin14Current averageModbus 401019ARead
AImin15Voltage line-neutralModbus 401021VRead
AI16Voltage line-lineModbus 401023VRead
AImin17FrequencyModbus 401025HzRead
AI18Phase angleModbus 401027° (phase)Read
AI19Real power phase AModbus 401029kWRead
AI20Real power phase BModbus 401031kWRead
AI21Real power phase CModbus 401033kWRead
AI22Reactive power phase AModbus 401035kVARRead
AI23Reactive power phase BModbus 401037kVARRead
AI24Reactive power phase CModbus 401039kVARRead
AI25Apparent power phase AModbus 401041kVARead
AI26Apparent power phase BModbus 401043kVARead
AI27Apparent power phase CModbus 401045kVARead
AI28Power factor phase AModbus 401047PFRead
AI29Power factor phase BModbus 401049PFRead
AI30Power factor phase CModbus 401051PFRead
AI31Current phase AModbus 401053ARead
AI32Current phase BModbus 401055ARead
AI33Current phase CModbus 401057ARead
AI34Voltage line to neutral phase A-NModbus 401059VRead
AI35Voltage line to neutral phase B-NModbus 401061VRead
AI36Voltage line to neutral phase C-NModbus 401063VRead
AI37Voltage line to line phase A-BModbus 401065VRead
AI38Voltage line to line phase B-CModbus 401067VRead
AI39Voltage line to line phase C-AModbus 401069VRead
AI40Phase angle phase AModbus 401071° (phase)Read
AI41Phase angle phase BModbus 401073° (phase)Read
AI42Phase angle phase CModbus 401075° (phase)Read
AO43External Input 1 PulseModbus 401083; not polled by defaultCommand
AO44External Input 2 PulseModbus 401085; not polled by defaultCommand
AI45Interval Day Block 1Modbus 404001; not polled by defaultRead
AI46Interval Day Block 2Modbus 404002; not polled by defaultRead
AI47Interval Day Block 3Modbus 404003; not polled by defaultRead
AI48Interval Day Block 4Modbus 404004; not polled by defaultRead
AI49Interval Day Block 5Modbus 404005; not polled by defaultRead
AI50Interval Day Block 6Modbus 404006; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX E-Mon Class 3200/3400/5000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX

How many BACnet points does the Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX have?

This list has 50 BACnet objects: 40 analog inputs, 10 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX BACnet points are writable?

10 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile E_Mon_D_Mon_3200_3400_5000 (E_Mon_D_Mon_3200_3400_5000_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/E_Mon_D_Mon_3200_3400_5000_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX?

Start with AO 5 Energy delivered (Energy delivered); AO 6 Energy received (Energy received); AI 9 Real power (Real power); AI 13 Peak demand (Peak demand); AI 15 Voltage line-neutral (Voltage line-neutral); AI 14 Current average (Average current); AI 12 Power factor (Power factor); AI 17 Frequency (Frequency).

How do I check these points on the real E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile E_Mon_D_Mon_3200_3400_5000 · E_Mon_D_Mon_3200_3400_5000_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.