Updated 12 November 2026

Short answer

Gateway profile for the Pixel elevator controller: 160 objects (96 AI, 64 BI), 20 polled by default. It repeats one block per car (cars 1-8): car number, online and in-group bits, class and mode of operation, door states, position indicator, faulted bit and active fault, moving and direction, inspection, independent and fire service bits. Only car 1 is polled by default.

This page lists 160 BACnet objects for the Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Equipment
Elevator controller
Equipment type
Other equipment
BACnet objects
160 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus
Source document
BASgatewayLX Modbus device profile Pixel_Elevator_Controller_a · Pixel_Elevator_Controller_a_LX.csv
Download CSV 160 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX

Integration in brief

Read each car's online, mode, position, door and fault values; enable the blocks for cars 2-8 as needed. Monitoring only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 2Car 1 OnlineCar 1 onlineRead
AI 5Car 1 Mode of OperationCar 1 mode of operationRead
AI 8Car 1 Car PI LandingCar 1 position (PI landing)Read
AI 12Car 1 Car MovingCar 1 movingRead
AI 6Car 1 Front Door StateCar 1 front door stateRead
BI 16Car 1 Any Fire Service mode activeCar 1 fire service activeRead
BI 10Car 1 Car FaultedCar 1 faultedRead
AI 11Car 1 Active Fault NumberCar 1 active fault numberRead

Network setup

Watch out for

Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

160 of 160 shown
Type
AnalogBinary
Show
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX BACnet Points List
DescriptionStates
AI1Car 1 Car NumberModbus 400001Read
BImin2Car 1 OnlineModbus 000001Read
BI3Car 1 In GroupModbus 000002Read
AI4Car 1 Class of OperationModbus 400002Read
AImin5Car 1 Mode of OperationModbus 400003Read
AImin6Car 1 Front Door StateModbus 400004Read
AI7Car 1 Rear Door StateModbus 400005Read
AImin8Car 1 Car PI LandingModbus 400006Read
AI9Car 1 Car Landing PI LabelModbus 400007Read
BImin10Car 1 Car FaultedModbus 000003Read
AImin11Car 1 Active Fault NumberModbus 400008Read
AImin12Car 1 Car MovingModbus 400009Read
AI13Car 1 Car Direction ArrowsModbus 400010Read
BI14Car 1 Any Inspection Input activeModbus 000004Read
BI15Car 1 Independent Input ActiveModbus 000005Read
BImin16Car 1 Any Fire Service mode activeModbus 000006Read
BI17Car 1 SpareModbus 000007Read
BI18Car 1 SpareModbus 000008Read
AI19Car 1 SpareModbus 400011Read
AI20Car 1 SpareModbus 400012Read
AI21Car 2 Car NumberModbus 400021; not polled by defaultRead
BI22Car 2 OnlineModbus 000021; not polled by defaultRead
BI23Car 2 In GroupModbus 000022; not polled by defaultRead
AI24Car 2 Class of OperationModbus 400022; not polled by defaultRead
AI25Car 2 Mode of OperationModbus 400023; not polled by defaultRead
AI26Car 2 Front Door StateModbus 400024; not polled by defaultRead
AI27Car 2 Rear Door StateModbus 400025; not polled by defaultRead
AI28Car 2 Car PI LandingModbus 400026; not polled by defaultRead
AI29Car 2 Car Landing PI LabelModbus 400027; not polled by defaultRead
BI30Car 2 Car FaultedModbus 000023; not polled by defaultRead
AI31Car 2 Active Fault NumberModbus 400028; not polled by defaultRead
AI32Car 2 Car MovingModbus 400029; not polled by defaultRead
AI33Car 2 Car Direction ArrowsModbus 400030; not polled by defaultRead
BI34Car 2 Any Inspection Input activeModbus 000024; not polled by defaultRead
BI35Car 2 Independent Input ActiveModbus 000025; not polled by defaultRead
BI36Car 2 Any Fire Service mode activeModbus 000026; not polled by defaultRead
BI37Car 2 SpareModbus 000027; not polled by defaultRead
BI38Car 2 SpareModbus 000028; not polled by defaultRead
AI39Car 2 SpareModbus 400031; not polled by defaultRead
AI40Car 2 SpareModbus 400032; not polled by defaultRead
AI41Car 3 Car NumberModbus 400041; not polled by defaultRead
BI42Car 3 OnlineModbus 000041; not polled by defaultRead
BI43Car 3 In GroupModbus 000042; not polled by defaultRead
AI44Car 3 Class of OperationModbus 400042; not polled by defaultRead
AI45Car 3 Mode of OperationModbus 400043; not polled by defaultRead
AI46Car 3 Front Door StateModbus 400044; not polled by defaultRead
AI47Car 3 Rear Door StateModbus 400045; not polled by defaultRead
AI48Car 3 Car PI LandingModbus 400046; not polled by defaultRead
AI49Car 3 Car Landing PI LabelModbus 400047; not polled by defaultRead
BI50Car 3 Car FaultedModbus 000043; not polled by defaultRead
AI51Car 3 Active Fault NumberModbus 400048; not polled by defaultRead
AI52Car 3 Car MovingModbus 400049; not polled by defaultRead
AI53Car 3 Car Direction ArrowsModbus 400050; not polled by defaultRead
BI54Car 3 Any Inspection Input activeModbus 000044; not polled by defaultRead
BI55Car 3 Independent Input ActiveModbus 000045; not polled by defaultRead
BI56Car 3 Any Fire Service mode activeModbus 000046; not polled by defaultRead
BI57Car 3 SpareModbus 000047; not polled by defaultRead
BI58Car 3 SpareModbus 000048; not polled by defaultRead
AI59Car 3 SpareModbus 400051; not polled by defaultRead
AI60Car 3 SpareModbus 400052; not polled by defaultRead
AI61Car 4 Car NumberModbus 400061; not polled by defaultRead
BI62Car 4 OnlineModbus 000061; not polled by defaultRead
BI63Car 4 In GroupModbus 000062; not polled by defaultRead
AI64Car 4 Class of OperationModbus 400062; not polled by defaultRead
AI65Car 4 Mode of OperationModbus 400063; not polled by defaultRead
AI66Car 4 Front Door StateModbus 400064; not polled by defaultRead
AI67Car 4 Rear Door StateModbus 400065; not polled by defaultRead
AI68Car 4 Car PI LandingModbus 400066; not polled by defaultRead
AI69Car 4 Car Landing PI LabelModbus 400067; not polled by defaultRead
BI70Car 4 Car FaultedModbus 000063; not polled by defaultRead
AI71Car 4 Active Fault NumberModbus 400068; not polled by defaultRead
AI72Car 4 Car MovingModbus 400069; not polled by defaultRead
AI73Car 4 Car Direction ArrowsModbus 400070; not polled by defaultRead
BI74Car 4 Any Inspection Input activeModbus 000064; not polled by defaultRead
BI75Car 4 Independent Input ActiveModbus 000065; not polled by defaultRead
BI76Car 4 Any Fire Service mode activeModbus 000066; not polled by defaultRead
BI77Car 4 SpareModbus 000067; not polled by defaultRead
BI78Car 4 SpareModbus 000068; not polled by defaultRead
AI79Car 4 SpareModbus 400071; not polled by defaultRead
AI80Car 4 SpareModbus 400072; not polled by defaultRead
AI81Car 5 Car NumberModbus 400081; not polled by defaultRead
BI82Car 5 OnlineModbus 000081; not polled by defaultRead
BI83Car 5 In GroupModbus 000082; not polled by defaultRead
AI84Car 5 Class of OperationModbus 400082; not polled by defaultRead
AI85Car 5 Mode of OperationModbus 400083; not polled by defaultRead
AI86Car 5 Front Door StateModbus 400084; not polled by defaultRead
AI87Car 5 Rear Door StateModbus 400085; not polled by defaultRead
AI88Car 5 Car PI LandingModbus 400086; not polled by defaultRead
AI89Car 5 Car Landing PI LabelModbus 400087; not polled by defaultRead
BI90Car 5 Car FaultedModbus 000083; not polled by defaultRead
AI91Car 5 Active Fault NumberModbus 400088; not polled by defaultRead
AI92Car 5 Car MovingModbus 400089; not polled by defaultRead
AI93Car 5 Car Direction ArrowsModbus 400090; not polled by defaultRead
BI94Car 5 Any Inspection Input activeModbus 000084; not polled by defaultRead
BI95Car 5 Independent Input ActiveModbus 000085; not polled by defaultRead
BI96Car 5 Any Fire Service mode activeModbus 000086; not polled by defaultRead
BI97Car 5 SpareModbus 000087; not polled by defaultRead
BI98Car 5 SpareModbus 000088; not polled by defaultRead
AI99Car 5 SpareModbus 400091; not polled by defaultRead
AI100Car 5 SpareModbus 400092; not polled by defaultRead
AI101Car 6 Car NumberModbus 400101; not polled by defaultRead
BI102Car 6 OnlineModbus 000101; not polled by defaultRead
BI103Car 6 In GroupModbus 000102; not polled by defaultRead
AI104Car 6 Class of OperationModbus 400102; not polled by defaultRead
AI105Car 6 Mode of OperationModbus 400103; not polled by defaultRead
AI106Car 6 Front Door StateModbus 400104; not polled by defaultRead
AI107Car 6 Rear Door StateModbus 400105; not polled by defaultRead
AI108Car 6 Car PI LandingModbus 400106; not polled by defaultRead
AI109Car 6 Car Landing PI LabelModbus 400107; not polled by defaultRead
BI110Car 6 Car FaultedModbus 000103; not polled by defaultRead
AI111Car 6 Active Fault NumberModbus 400108; not polled by defaultRead
AI112Car 6 Car MovingModbus 400109; not polled by defaultRead
AI113Car 6 Car Direction ArrowsModbus 400110; not polled by defaultRead
BI114Car 6 Any Inspection Input activeModbus 000104; not polled by defaultRead
BI115Car 6 Independent Input ActiveModbus 000105; not polled by defaultRead
BI116Car 6 Any Fire Service mode activeModbus 000106; not polled by defaultRead
BI117Car 6 SpareModbus 000107; not polled by defaultRead
BI118Car 6 SpareModbus 000108; not polled by defaultRead
AI119Car 6 SpareModbus 400111; not polled by defaultRead
AI120Car 6 SpareModbus 400112; not polled by defaultRead
AI121Car 7 Car NumberModbus 400121; not polled by defaultRead
BI122Car 7 OnlineModbus 000121; not polled by defaultRead
BI123Car 7 In GroupModbus 000122; not polled by defaultRead
AI124Car 7 Class of OperationModbus 400122; not polled by defaultRead
AI125Car 7 Mode of OperationModbus 400123; not polled by defaultRead
AI126Car 7 Front Door StateModbus 400124; not polled by defaultRead
AI127Car 7 Rear Door StateModbus 400125; not polled by defaultRead
AI128Car 7 Car PI LandingModbus 400126; not polled by defaultRead
AI129Car 7 Car Landing PI LabelModbus 400127; not polled by defaultRead
BI130Car 7 Car FaultedModbus 000123; not polled by defaultRead
AI131Car 7 Active Fault NumberModbus 400128; not polled by defaultRead
AI132Car 7 Car MovingModbus 400129; not polled by defaultRead
AI133Car 7 Car Direction ArrowsModbus 400130; not polled by defaultRead
BI134Car 7 Any Inspection Input activeModbus 000124; not polled by defaultRead
BI135Car 7 Independent Input ActiveModbus 000125; not polled by defaultRead
BI136Car 7 Any Fire Service mode activeModbus 000126; not polled by defaultRead
BI137Car 7 SpareModbus 000127; not polled by defaultRead
BI138Car 7 SpareModbus 000128; not polled by defaultRead
AI139Car 7 SpareModbus 400131; not polled by defaultRead
AI140Car 7 SpareModbus 400132; not polled by defaultRead
AI141Car 8 Car NumberModbus 400141; not polled by defaultRead
BI142Car 8 OnlineModbus 000141; not polled by defaultRead
BI143Car 8 In GroupModbus 000142; not polled by defaultRead
AI144Car 8 Class of OperationModbus 400142; not polled by defaultRead
AI145Car 8 Mode of OperationModbus 400143; not polled by defaultRead
AI146Car 8 Front Door StateModbus 400144; not polled by defaultRead
AI147Car 8 Rear Door StateModbus 400145; not polled by defaultRead
AI148Car 8 Car PI LandingModbus 400146; not polled by defaultRead
AI149Car 8 Car Landing PI LabelModbus 400147; not polled by defaultRead
BI150Car 8 Car FaultedModbus 000143; not polled by defaultRead
AI151Car 8 Active Fault NumberModbus 400148; not polled by defaultRead
AI152Car 8 Car MovingModbus 400149; not polled by defaultRead
AI153Car 8 Car Direction ArrowsModbus 400150; not polled by defaultRead
BI154Car 8 Any Inspection Input activeModbus 000144; not polled by defaultRead
BI155Car 8 Independent Input ActiveModbus 000145; not polled by defaultRead
BI156Car 8 Any Fire Service mode activeModbus 000146; not polled by defaultRead
BI157Car 8 SpareModbus 000147; not polled by defaultRead
BI158Car 8 SpareModbus 000148; not polled by defaultRead
AI159Car 8 SpareModbus 400151; not polled by defaultRead
AI160Car 8 SpareModbus 400152; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX ECC Pixel point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Elevator Controls Corporation Pixel elevator controller via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX

How many BACnet points does the Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX have?

This list has 160 BACnet objects: 96 analog inputs, 64 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Pixel_Elevator_Controller_a (Pixel_Elevator_Controller_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Pixel%20Elevator%20Controller.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX?

Start with BI 2 Car 1 Online (Car 1 online); AI 5 Car 1 Mode of Operation (Car 1 mode of operation); AI 8 Car 1 Car PI Landing (Car 1 position (PI landing)); AI 12 Car 1 Car Moving (Car 1 moving); AI 6 Car 1 Front Door State (Car 1 front door state); BI 16 Car 1 Any Fire Service mode active (Car 1 fire service active); BI 10 Car 1 Car Faulted (Car 1 faulted); AI 11 Car 1 Active Fault Number (Car 1 active fault number).

How do I check these points on the real Elevator Controls Corporation Pixel elevator controller via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Pixel_Elevator_Controller_a · Pixel_Elevator_Controller_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.