Generator set controller · BACnet points list

Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for Cummins PowerCommand 2.x/3.x: 81 objects (49 AI, 32 BI), all polled. It reads control switch position, latest fault code and type, the NFPA-style annunciator bits (common alarm, running, supplying load, not in auto, battery, coolant, oil, fuel, overspeed...), and genset voltage, current, kW, kVAR, PF, kVA and energy.

This page lists 81 BACnet objects for the Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Equipment
Generator set controller
Equipment type
Other equipment
BACnet objects
81 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus
Source document
BASgatewayLX Modbus device profile Cummins_PowerCommand_a · Cummins_PowerCommand_a_LX.csv
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX

Integration in brief

Read Genset Running, Supplying Load, Not in Auto and Common Alarm, plus total kW. This profile is read-only; start/stop and mode stay on the genset panel or hard-wired remote start.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 7Genset RunningGenset runningRead
BI 6Genset Supplying LoadGenset supplying loadRead
BI 8Not in AutoControl not in autoRead
AI 1Control Switch PositionControl switch positionRead
AI 52Genset Total kWGenset total kWRead
AI 43Genset LL Average VoltageAverage line-line voltageRead
AI 47Genset Average CurrentAverage currentRead
BI 5Common AlarmCommon alarmRead
AI 2Most Recent Fault or WarningLatest fault/warning codeRead

Network setup

Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

81 of 81 shown
Type
AnalogBinary
Show
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Control Switch PositionModbus 400010Read
AImin2Most Recent Fault or WarningModbus 400011Read
AI3Fault Type of the Fault CodeModbus 400012Read
AI4Genset % Standby Total KwModbus 400013%Read
BImin5Common AlarmModbus 400016 bit 0Read
BImin6Genset Supplying LoadModbus 400016 bit 1Read
BImin7Genset RunningModbus 400016 bit 2Read
BImin8Not in AutoModbus 400016 bit 3Read
BI9High Battery VoltageModbus 400016 bit 4Read
BI10Low Battery VoltageModbus 400016 bit 5Read
BI11Charger AC FailureModbus 400016 bit 6Read
BI12Fail to StartModbus 400016 bit 7Read
BI13Low Coolant TemperatureModbus 400016 bit 8Read
BI14Pre-high Engine TemperatureModbus 400016 bit 9Read
BI15High Engine TemperatureModbus 400016 bit 10Read
BI16Pre-low Oil PressureModbus 400016 bit 11Read
BI17Low Oil PressureModbus 400016 bit 12Read
BI18OverspeedModbus 400016 bit 13Read
BI19Low Coolant LevelModbus 400016 bit 14Read
BI20Low Fuel LevelModbus 400016 bit 15Read
BI21Check GensetModbus 400017 bit 0Read
BI22Ground FaultModbus 400017 bit 1Read
BI23High AC VoltageModbus 400017 bit 2Read
BI24Low AC VoltageModbus 400017 bit 3Read
BI25Under FrequencyModbus 400017 bit 4Read
BI26OverloadModbus 400017 bit 5Read
BI27OvercurrentModbus 400017 bit 6Read
BI28Short CircuitModbus 400017 bit 7Read
BI29Reverse KWModbus 400017 bit 8Read
BI30Reverse KVARModbus 400017 bit 9Read
BI31Fail to SyncModbus 400017 bit 10Read
BI32Fail to CloseModbus 400017 bit 11Read
BI33Load DemandModbus 400017 bit 12Read
BI34Genset Circuit Breaker TrippedModbus 400017 bit 13Read
BI35Utility Circuit Breaker TrippedModbus 400017 bit 14Read
BI36Emergency StopModbus 400017 bit 15Read
AI37Genset L1N VoltageModbus 400018VRead
AI38Genset L2N VoltageModbus 400019VRead
AI39Genset L3N VoltageModbus 400020VRead
AI40Genset L1L2 VoltageModbus 400022VRead
AI41Genset L2L3 VoltageModbus 400023VRead
AI42Genset L3L1 VoltageModbus 400024VRead
AImin43Genset LL Average VoltageModbus 400025VRead
AI44Genset L1 CurrentModbus 400026ARead
AI45Genset L2 CurrentModbus 400027ARead
AI46Genset L3 CurrentModbus 400028ARead
AImin47Genset Average CurrentModbus 400029ARead
AI48Genset Neutral CurrentModbus 400030ARead
AI49Genset L1 kWModbus 400031kWRead
AI50Genset L2 kWModbus 400032kWRead
AI51Genset L3 kWModbus 400033kWRead
AImin52Genset Total kWModbus 400034kWRead
AI53Genset L1 kVARModbus 400035kVARRead
AI54Genset L2 kVARModbus 400036kVARRead
AI55Genset L3 kVARModbus 400037kVARRead
AI56Genset Total kVARModbus 400038kVARRead
AI57Genset Total Power FactorModbus 400039PFRead
AI58Genset L1 kVAModbus 400040kVARead
AI59Genset L2 kVAModbus 400041kVARead
AI60Genset L3 kVAModbus 400042kVARead
AI61Genset Total kVAModbus 400043kVARead
AI62Genset Total Negative kWhModbus 400046kWhRead
AI63Genset Total Positive kWhModbus 400048kWhRead
AI64Genset Total Net kWhModbus 400050kWhRead
AI65Genset Total Negative kVARhModbus 400052kVARRead
AI66Genset Total Positive kVARhModbus 400054kVARRead
AI67Genset Total Net kVARhModbus 400056kVARRead
AI68Genset % Standby L1Modbus 400058%Read
AI69Genset % Standby L2Modbus 400059%Read
AI70Genset % Standby L3Modbus 400060%Read
AI71Battery VoltageModbus 400061VRead
AI72Oil PressureModbus 400062kPaRead
AI73Oil TemperatureModbus 400063°FRead
AI74Coolant TemperatureModbus 400064°CRead
AI75Intake Manifold TemperatureModbus 400065°FRead
AI76Fuel TemperatureModbus 400066°FRead
AI77Fuel RateModbus 400067gphRead
AI78Average Engine SpeedModbus 400068rpmRead
AI79Engine Running TimeModbus 400070sRead
AI80Total Fuel ConsumptionModbus 400072galRead
AI81Total Number of RunsModbus 400074Read
Object ID lookup: Contemporary Controls BASgatewayLX Cummins PowerCommand point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX

How many BACnet points does the Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX have?

This list has 81 BACnet objects: 49 analog inputs, 32 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Cummins_PowerCommand_a (Cummins_PowerCommand_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/CumminsPowerCommand.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX?

Start with BI 7 Genset Running (Genset running); BI 6 Genset Supplying Load (Genset supplying load); BI 8 Not in Auto (Control not in auto); AI 1 Control Switch Position (Control switch position); AI 52 Genset Total kW (Genset total kW); AI 43 Genset LL Average Voltage (Average line-line voltage); AI 47 Genset Average Current (Average current); BI 5 Common Alarm (Common alarm); AI 2 Most Recent Fault or Warning (Latest fault/warning code).

How do I check these points on the real Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Cummins_PowerCommand_a · Cummins_PowerCommand_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.