- Home
- BACnet points lists
- Contemporary Controls
- Schneider Electric PowerLogic PM800 via BASgatewayLX
Power and energy meter · BACnet points list
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the PowerLogic PM800: 126 Analog Inputs, 44 polled by default. Polled values cover phase, neutral and ground currents, voltages, real/reactive/apparent power per phase and total, true PF, frequency and real, reactive, apparent and conditional energy.
This page lists 126 BACnet objects for the Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Schneider Electric PowerLogic PM800 via BASgatewayLX
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 126 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- PM800, PM810, PM820, PM850, PM870, PowerLogic PM800
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Map real power total, real energy in and voltage L-L average first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 24 | Real Power Total | Real power total | Read |
| AI 38 | Energy Real In | Real energy in | Read |
| AI 15 | Voltage L-L Average | Voltage L-L average | Read |
| AI 11 | Current 3-Phase Average | Current 3-phase average | Read |
| AI 36 | True Power Factor Total | True power factor total | Read |
| AI 37 | Frequency | Frequency | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Energy Real Total (signed/absolute) | Modbus 402600; not polled by default | Wh | Read | |
| AI | 2 | Energy Reactive Total (signed/absolute) | Modbus 402602; not polled by default | VAR | Read | |
| AI | 3 | Energy Apparent | Modbus 402604; not polled by default | VA | Read | |
| AI | 4 | True Power Factor Total | Modbus 402606; not polled by default | PF | Read | |
| AI | 5 | Display 1 Second Metering Floating Point Values | Modbus 403248; not polled by default | Read | ||
| AI | 6 | Current Phase A | Modbus 411700 | A | Read | |
| AI | 7 | Current Phase B | Modbus 411702 | A | Read | |
| AI | 8 | Current Phase C | Modbus 411704 | A | Read | |
| AI | 9 | Current Neutral | Modbus 411706 | A | Read | |
| AI | 10 | Current Ground | Modbus 411708 | A | Read | |
| AImin | 11 | Current 3-Phase Average | Modbus 411710 | A | Read | |
| AI | 12 | Voltage A-B | Modbus 411712 | V | Read | |
| AI | 13 | Voltage B-C | Modbus 411714 | V | Read | |
| AI | 14 | Voltage C-A | Modbus 411716 | V | Read | |
| AImin | 15 | Voltage L-L Average | Modbus 411718 | V | Read | |
| AI | 16 | Voltage A-N | Modbus 411720 | V | Read | |
| AI | 17 | Voltage B-N | Modbus 411722 | V | Read | |
| AI | 18 | Voltage C-N | Modbus 411724 | V | Read | |
| AI | 19 | Voltage N-G | Modbus 411726 | V | Read | |
| AI | 20 | Voltage L-N Average | Modbus 411728 | V | Read | |
| AI | 21 | Real Power Phase A | Modbus 411730 | W | Read | |
| AI | 22 | Real Power Phase B | Modbus 411732 | W | Read | |
| AI | 23 | Real Power Phase C | Modbus 411734 | W | Read | |
| AImin | 24 | Real Power Total | Modbus 411736 | W | Read | |
| AI | 25 | Reactive Power Phase A | Modbus 411738 | VAR | Read | |
| AI | 26 | Reactive Power Phase B | Modbus 411740 | VAR | Read | |
| AI | 27 | Reactive Power Phase C | Modbus 411742 | VAR | Read | |
| AI | 28 | Reactive Power Total | Modbus 411744 | VAR | Read | |
| AI | 29 | Apparent Power Phase A | Modbus 411746 | VA | Read | |
| AI | 30 | Apparent Power Phase B | Modbus 411748 | VA | Read | |
| AI | 31 | Apparent Power Phase C | Modbus 411750 | VA | Read | |
| AI | 32 | Apparent Power Total | Modbus 411752 | VA | Read | |
| AI | 33 | True Power Factor Phase A | Modbus 411754 | PF | Read | |
| AI | 34 | True Power Factor Phase B | Modbus 411756 | PF | Read | |
| AI | 35 | True Power Factor Phase C | Modbus 411758 | PF | Read | |
| AImin | 36 | True Power Factor Total | Modbus 411760 | PF | Read | |
| AImin | 37 | Frequency | Modbus 411762 | Hz | Read | |
| AImin | 38 | Energy Real In | Modbus 411800 | Wh | Read | |
| AI | 39 | Energy Reactive In | Modbus 411802 | VAR | Read | |
| AI | 40 | Energy Real Out | Modbus 411804 | Wh | Read | |
| AI | 41 | Energy Reactive Out | Modbus 411806 | VAR | Read | |
| AI | 42 | Energy Real Total (signed/absolute) | Modbus 411808 | Wh | Read | |
| AI | 43 | Energy Reactive Total (signed/absolute) | Modbus 411810 | VAR | Read | |
| AI | 44 | Energy Apparent | Modbus 411812 | Read | ||
| AI | 45 | Energy Conditional Real In | Modbus 411814 | Wh | Read | |
| AI | 46 | Energy Conditional Reactive In | Modbus 411816 | VAR | Read | |
| AI | 47 | Energy Conditional Real Out | Modbus 411818 | Wh | Read | |
| AI | 48 | Energy Conditional Reactive Out | Modbus 411820 | VAR | Read | |
| AI | 49 | Energy Conditional Apparent | Modbus 411822 | Read | ||
| AI | 50 | Energy Incremental Real In Last Complete Interval | Modbus 411824; not polled by default | Wh | Read | |
| AI | 51 | Energy. Incremental Reactive In Last Complete Interval | Modbus 411826; not polled by default | VAR | Read | |
| AI | 52 | Energy Incremental Real Out Last Complete Interval | Modbus 411828; not polled by default | Wh | Read | |
| AI | 53 | Energy Incremental Reactive Out Last Complete Interval | Modbus 411830; not polled by default | VAR | Read | |
| AI | 54 | Energy Incremental Apparent Last Complete Interval | Modbus 411832; not polled by default | Read | ||
| AI | 55 | Energy Incremental Real In Present interval | Modbus 411836; not polled by default | Wh | Read | |
| AI | 56 | Energy. Incremental Reactive In Present Interval | Modbus 411838; not polled by default | VAR | Read | |
| AI | 57 | Energy Incremental Real Out Present Interval | Modbus 411840; not polled by default | Wh | Read | |
| AI | 58 | Energy Incremental Reactive Out Present Interval | Modbus 411842; not polled by default | VAR | Read | |
| AI | 59 | Energy Incremental Apparent Present Interval | Modbus 411844; not polled by default | Read | ||
| AI | 60 | Energy Reactive Quadrant 1 | Modbus 411846; not polled by default | VAR | Read | |
| AI | 61 | Energy Reactive Quadrant 2 | Modbus 411848; not polled by default | VAR | Read | |
| AI | 62 | Energy Reactive Quadrant 3 | Modbus 411850; not polled by default | VAR | Read | |
| AI | 63 | Energy Reactive Quadrant 4 | Modbus 411852; not polled by default | VAR | Read | |
| AI | 64 | Cumulative Usage Input Channel #1 | Modbus 411854; not polled by default | Read | ||
| AI | 65 | Cumulative Usage Input Channel #2 | Modbus 411856; not polled by default | Read | ||
| AI | 66 | Cumulative Usage Input Channel #3 | Modbus 411858; not polled by default | Read | ||
| AI | 67 | Cumulative Usage Input Channel #4 | Modbus 411860; not polled by default | Read | ||
| AI | 68 | Cumulative Usage Input Channel #5 | Modbus 411862; not polled by default | Read | ||
| AI | 69 | Energy Real 3-Phase Total Usage Today | Modbus 411864; not polled by default | Wh | Read | |
| AI | 70 | Energy Real 3-Phase Total Usage Yesterday | Modbus 411866; not polled by default | Wh | Read | |
| AI | 71 | Energy Real 3-Phase Total Usage This Week | Modbus 411868; not polled by default | Wh | Read | |
| AI | 72 | Energy Real 3-Phase Total Usage Last Week | Modbus 411870; not polled by default | Wh | Read | |
| AI | 73 | Energy Real 3-Phase Total Usage This Month | Modbus 411872; not polled by default | Wh | Read | |
| AI | 74 | Energy Real 3-Phase Total Usage Last Month | Modbus 411874; not polled by default | Wh | Read | |
| AI | 75 | Energy Apparent 3-Phase Total Usage Today | Modbus 411876; not polled by default | Wh | Read | |
| AI | 76 | Energy Apparent 3-Phase Total Usage Yesterday | Modbus 411878; not polled by default | Wh | Read | |
| AI | 77 | Energy Apparent 3-Phase Total Usage This Week | Modbus 411880; not polled by default | Read | ||
| AI | 78 | Energy Apparent 3-Phase Total Usage Last Week | Modbus 411882; not polled by default | Read | ||
| AI | 79 | Energy Apparent 3-Phase Total Usage This Month | Modbus 411884; not polled by default | Read | ||
| AI | 80 | Energy Apparent 3-Phase Total Usage Last Month | Modbus 411886; not polled by default | Read | ||
| AI | 81 | Energy Real 3-Phase Total Usage – First Shift – Today | Modbus 411888; not polled by default | Read | ||
| AI | 82 | Energy Real 3-Phase Total Usage – Second Shift – Today | Modbus 411890; not polled by default | Read | ||
| AI | 83 | Energy Real 3-Phase Total Usage – Third Shift – Today | Modbus 411892; not polled by default | Read | ||
| AI | 84 | Energy Real 3-Phase Total Usage – First Shift – Yesterday | Modbus 411894; not polled by default | Read | ||
| AI | 85 | Energy Real 3-Phase Total Usage – Second Shift – Yesterday | Modbus 411896; not polled by default | Wh | Read | |
| AI | 86 | Energy Real 3-Phase Total Energy Real 3-Phase Total | Modbus 411898; not polled by default | Wh | Read | |
| AI | 87 | Energy Real 3-Phase Total Usage – First Shift – This Week | Modbus 411900; not polled by default | Wh | Read | |
| AI | 88 | Energy Real 3-Phase Total Usage – Second Shift – This Week | Modbus 411902; not polled by default | Wh | Read | |
| AI | 89 | Energy Real 3-Phase Total Usage – Third Shift – This Week | Modbus 411904; not polled by default | Wh | Read | |
| AI | 90 | Energy Real 3-Phase Total Usage – First Shift – Last Week | Modbus 411906; not polled by default | Wh | Read | |
| AI | 91 | Energy Real 3-Phase Total Usage – Second Shift – Last Week | Modbus 411908; not polled by default | Wh | Read | |
| AI | 92 | Energy Real 3-Phase Total Usage – Third Shift – Last Week | Modbus 411910; not polled by default | Wh | Read | |
| AI | 93 | Energy Real 3-Phase Total Usage – First Shift – This Month | Modbus 411912; not polled by default | Wh | Read | |
| AI | 94 | Energy Real 3-Phase Total Usage – Second Shift – This Month | Modbus 411914; not polled by default | Wh | Read | |
| AI | 95 | Energy Real 3-Phase Total Usage – Third Shift – This Month | Modbus 411916; not polled by default | Wh | Read | |
| AI | 96 | Energy Real 3-Phase Total Usage – First Shift – Last Month | Modbus 411918; not polled by default | Wh | Read | |
| AI | 97 | Energy Real 3-Phase Total Usage – Second Shift – Last Month | Modbus 411920; not polled by default | Wh | Read | |
| AI | 98 | Energy Real 3-Phase Total Usage – Third Shift – Last Month | Modbus 411922; not polled by default | Wh | Read | |
| AI | 99 | Energy Apparent 3-Phase Total Usage – First Shift – Today | Modbus 411924; not polled by default | Wh | Read | |
| AI | 100 | Energy Apparent 3-Phase Total Usage – Second Shift – Today | Modbus 411926; not polled by default | Wh | Read | |
| AI | 101 | Energy Apparent 3-Phase Total Usage – Third Shift – Today | Modbus 411928; not polled by default | Wh | Read | |
| AI | 102 | Energy Apparent 3-Phase Total Usage – First Shift – Yesterday | Modbus 411930; not polled by default | Wh | Read | |
| AI | 103 | Energy Apparent 3-Phase Total Usage – Second Shift – Yesterday | Modbus 411932; not polled by default | Read | ||
| AI | 104 | Energy Apparent 3-Phase Total Usage – Third Shift – Yesterday | Modbus 411934; not polled by default | Read | ||
| AI | 105 | Energy Apparent 3-Phase Total Usage – First Shift – This Week | Modbus 411936; not polled by default | Read | ||
| AI | 106 | Energy Apparent 3-Phase Total Usage – Second Shift – This Week | Modbus 411938; not polled by default | Read | ||
| AI | 107 | Energy Apparent 3-Phase Total Usage – Third Shift – This Week | Modbus 411940; not polled by default | Read | ||
| AI | 108 | Energy Apparent 3-Phase Total Usage – First Shift – Last Week | Modbus 411942; not polled by default | Read | ||
| AI | 109 | Energy Apparent 3-Phase Total Usage – Second Shift – Last Week | Modbus 411944; not polled by default | Read | ||
| AI | 110 | Energy Apparent 3-Phase Total Usage – Third Shift – Last Week | Modbus 411946; not polled by default | Read | ||
| AI | 111 | Energy Apparent 3-Phase Total Usage – First Shift – This Month | Modbus 411948; not polled by default | Read | ||
| AI | 112 | Energy Apparent 3-Phase Total Usage – Second Shift – This Month | Modbus 411950; not polled by default | Read | ||
| AI | 113 | Energy Apparent 3-Phase Total Energy Apparent 3-Phase Total | Modbus 411952; not polled by default | Read | ||
| AI | 114 | Energy Apparent 3-Phase Total Usage – First Shift – Last Month | Modbus 411954; not polled by default | Read | ||
| AI | 115 | Energy Apparent 3-Phase Total Usage – Second Shift – Last Month | Modbus 411956; not polled by default | Read | ||
| AI | 116 | Energy Apparent 3-Phase Total Usage – Third Shift – Last Month | Modbus 411958; not polled by default | Read | ||
| AI | 117 | THD/thd Current Phase A | Modbus 411960; not polled by default | Read | ||
| AI | 118 | THD/thd Current Phase B | Modbus 411962; not polled by default | Read | ||
| AI | 119 | THD/thd Current Phase C | Modbus 411964; not polled by default | Read | ||
| AI | 120 | THD/thd Current Phase N | Modbus 411966; not polled by default | Read | ||
| AI | 121 | THD/thd Voltage Phase A-N | Modbus 411968; not polled by default | Read | ||
| AI | 122 | THD/thd Voltage Phase B-N | Modbus 411970; not polled by default | Read | ||
| AI | 123 | THD/thd Voltage Phase C-N | Modbus 411972; not polled by default | Read | ||
| AI | 124 | THD/thd Voltage Phase A-B | Modbus 411974; not polled by default | Read | ||
| AI | 125 | THD/thd Voltage Phase B-C | Modbus 411976; not polled by default | Read | ||
| AI | 126 | THD/thd Voltage Phase C-A | Modbus 411978; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX PowerLogic PM800 point IDs by name
AI1Energy Real Total (signed/absolute)AI2Energy Reactive Total (signed/absolute)AI3Energy ApparentAI4True Power Factor TotalAI5Display 1 Second Metering Floating Point ValuesAI6Current Phase AAI7Current Phase BAI8Current Phase CAI9Current NeutralAI10Current GroundAI11Current 3-Phase AverageAI12Voltage A-BAI13Voltage B-CAI14Voltage C-AAI15Voltage L-L AverageAI16Voltage A-NAI17Voltage B-NAI18Voltage C-NAI19Voltage N-GAI20Voltage L-N AverageAI21Real Power Phase AAI22Real Power Phase BAI23Real Power Phase CAI24Real Power TotalAI25Reactive Power Phase AAI26Reactive Power Phase BAI27Reactive Power Phase CAI28Reactive Power TotalAI29Apparent Power Phase AAI30Apparent Power Phase BAI31Apparent Power Phase CAI32Apparent Power TotalAI33True Power Factor Phase AAI34True Power Factor Phase BAI35True Power Factor Phase CAI36True Power Factor TotalAI37FrequencyAI38Energy Real InAI39Energy Reactive InAI40Energy Real OutAI41Energy Reactive OutAI42Energy Real Total (signed/absolute)AI43Energy Reactive Total (signed/absolute)AI44Energy ApparentAI45Energy Conditional Real InAI46Energy Conditional Reactive InAI47Energy Conditional Real OutAI48Energy Conditional Reactive OutAI49Energy Conditional ApparentAI50Energy Incremental Real In Last Complete IntervalAI51Energy. Incremental Reactive In Last Complete IntervalAI52Energy Incremental Real Out Last Complete IntervalAI53Energy Incremental Reactive Out Last Complete IntervalAI54Energy Incremental Apparent Last Complete IntervalAI55Energy Incremental Real In Present intervalAI56Energy. Incremental Reactive In Present IntervalAI57Energy Incremental Real Out Present IntervalAI58Energy Incremental Reactive Out Present IntervalAI59Energy Incremental Apparent Present IntervalAI60Energy Reactive Quadrant 1AI61Energy Reactive Quadrant 2AI62Energy Reactive Quadrant 3AI63Energy Reactive Quadrant 4AI64Cumulative Usage Input Channel #1AI65Cumulative Usage Input Channel #2AI66Cumulative Usage Input Channel #3AI67Cumulative Usage Input Channel #4AI68Cumulative Usage Input Channel #5AI69Energy Real 3-Phase Total Usage TodayAI70Energy Real 3-Phase Total Usage YesterdayAI71Energy Real 3-Phase Total Usage This WeekAI72Energy Real 3-Phase Total Usage Last WeekAI73Energy Real 3-Phase Total Usage This MonthAI74Energy Real 3-Phase Total Usage Last MonthAI75Energy Apparent 3-Phase Total Usage TodayAI76Energy Apparent 3-Phase Total Usage YesterdayAI77Energy Apparent 3-Phase Total Usage This WeekAI78Energy Apparent 3-Phase Total Usage Last WeekAI79Energy Apparent 3-Phase Total Usage This MonthAI80Energy Apparent 3-Phase Total Usage Last MonthAI81Energy Real 3-Phase Total Usage – First Shift – TodayAI82Energy Real 3-Phase Total Usage – Second Shift – TodayAI83Energy Real 3-Phase Total Usage – Third Shift – TodayAI84Energy Real 3-Phase Total Usage – First Shift – YesterdayAI85Energy Real 3-Phase Total Usage – Second Shift – YesterdayAI86Energy Real 3-Phase Total Energy Real 3-Phase TotalAI87Energy Real 3-Phase Total Usage – First Shift – This WeekAI88Energy Real 3-Phase Total Usage – Second Shift – This WeekAI89Energy Real 3-Phase Total Usage – Third Shift – This WeekAI90Energy Real 3-Phase Total Usage – First Shift – Last WeekAI91Energy Real 3-Phase Total Usage – Second Shift – Last WeekAI92Energy Real 3-Phase Total Usage – Third Shift – Last WeekAI93Energy Real 3-Phase Total Usage – First Shift – This MonthAI94Energy Real 3-Phase Total Usage – Second Shift – This MonthAI95Energy Real 3-Phase Total Usage – Third Shift – This MonthAI96Energy Real 3-Phase Total Usage – First Shift – Last MonthAI97Energy Real 3-Phase Total Usage – Second Shift – Last MonthAI98Energy Real 3-Phase Total Usage – Third Shift – Last MonthAI99Energy Apparent 3-Phase Total Usage – First Shift – TodayAI100Energy Apparent 3-Phase Total Usage – Second Shift – TodayAI101Energy Apparent 3-Phase Total Usage – Third Shift – TodayAI102Energy Apparent 3-Phase Total Usage – First Shift – YesterdayAI103Energy Apparent 3-Phase Total Usage – Second Shift – YesterdayAI104Energy Apparent 3-Phase Total Usage – Third Shift – YesterdayAI105Energy Apparent 3-Phase Total Usage – First Shift – This WeekAI106Energy Apparent 3-Phase Total Usage – Second Shift – This WeekAI107Energy Apparent 3-Phase Total Usage – Third Shift – This WeekAI108Energy Apparent 3-Phase Total Usage – First Shift – Last WeekAI109Energy Apparent 3-Phase Total Usage – Second Shift – Last WeekAI110Energy Apparent 3-Phase Total Usage – Third Shift – Last WeekAI111Energy Apparent 3-Phase Total Usage – First Shift – This MonthAI112Energy Apparent 3-Phase Total Usage – Second Shift – This MonthAI113Energy Apparent 3-Phase Total Energy Apparent 3-Phase TotalAI114Energy Apparent 3-Phase Total Usage – First Shift – Last MonthAI115Energy Apparent 3-Phase Total Usage – Second Shift – Last MonthAI116Energy Apparent 3-Phase Total Usage – Third Shift – Last MonthAI117THD/thd Current Phase AAI118THD/thd Current Phase BAI119THD/thd Current Phase CAI120THD/thd Current Phase NAI121THD/thd Voltage Phase A-NAI122THD/thd Voltage Phase B-NAI123THD/thd Voltage Phase C-NAI124THD/thd Voltage Phase A-BAI125THD/thd Voltage Phase B-CAI126THD/thd Voltage Phase C-A
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Schneider_Electric__PM800_Meter_aLX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/PM800.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 44 of the 126 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Energy Real Total (signed/absolute); Energy Reactive Total (signed/absolute); Energy Apparent...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric PowerLogic PM800 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
How many BACnet points does the Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX have?
This list has 126 BACnet objects: 126 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Schneider_Electric__PM800_Meter (Schneider_Electric__PM800_Meter_aLX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Schneider_Electric__PM800_Meter.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX?
Start with AI 24 Real Power Total (Real power total); AI 38 Energy Real In (Real energy in); AI 15 Voltage L-L Average (Voltage L-L average); AI 11 Current 3-Phase Average (Current 3-phase average); AI 36 True Power Factor Total (True power factor total); AI 37 Frequency (Frequency).
How do I check these points on the real Schneider Electric PowerLogic PM800 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Schneider_Electric__PM800_Meter · Schneider_Electric__PM800_Meter_aLX.csv. Object names, instances and units are reproduced as published; descriptions are our own.