Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP) · BACnet points list

Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat BACnet points list

Updated 11 November 2026

Short answer

The BAST-421C-BW2 is a Wi-Fi BACnet IP thermostat for 4-pipe fan coil units with modulating or floating cooling and heating valves and a multi-speed fan. It exposes temperatures, valve outputs, setpoints, system and fan modes, occupancy and setup values as BACnet objects.

This page lists 50 BACnet objects for the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Equipment
Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Equipment type
Thermostats, sensors & meters
BACnet objects
50 (40 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
700001
Also known as
BAST-421C-BW2, BAST-421-BW2, BASstat 421C
Source document
BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat User Manual · UM-15093500-AA2
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat

Integration in brief

Turn the thermostat outputs on with On-Off Control (BV 5), set occupancy with Occupancy Command (BV 14), and write the system mode, cooling and heating setpoints and fan mode. Read the space temperature, occupancy status, output status and fan speed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 5On-Off ControlThermostat outputs on/off (1 = on)Write
BV 14Occupancy Command0 = occupied, 1 = unoccupiedWrite
MV 1System ModeCool, heat or ventilation modeWrite
AV 0Cooling Temperature SetpointOccupied cooling setpointWrite
AV 3Heating Temperature SetpointOccupied heating setpointWrite
MV 0Fan Mode1 = auto, then fan speedsWrite
AI 0Current TemperatureSpace temperature in useRead
BI 0Occupancy Status0 = occupied, 1 = unoccupiedRead
BI 2Cooling-heating StatusHeating/cooling output activeRead
MV 5Fan Speed StatusCurrent fan speed, 0 = stopRead

Enable & remote start

On-Off Control (BV 5) switches the thermostat outputs. Occupancy Command (BV 14) only takes effect when the ESI contact is disabled in Lock (AV 18 bit value 64); by default occupancy comes from the ESI dry contact.

Heartbeat & communication loss

A space temperature written to Temperature Assigned Via BACnet (AV 1) is only used while the BMS keeps toggling Heartbeat (BV 16) within the Heartbeat Rate (AV 29) period, in seconds; otherwise the thermostat reverts to its own sensor.

Sensors & values from the BMS

Set Temperature Source (MV 3) to 3 (Assigned through BACnet) and write the space temperature to AV 1, toggling BV 16 as a heartbeat.

Network setup

Watch out for

Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

50 of 50 shown
Type
Multi-state
Access
Show
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat BACnet Points List
DescriptionStates
AImin0Current Temperature°F/°CRead
AI1Active Temperature Setpoint°F/°CRead
AI2Built-in Temperature SensorBuilt-in Temperature Sensor Reading°F/°CRead
AI3Remote Temperature SensorRemote Temperature Sensor Reading°F/°CRead
AI8Modulating/ Floating Output 1Modulating/ Floating Output 1 (Cooling)%Read
AI9Modulating/ Floating Output 2Modulating/ Floating Output 2 (Heating)%Read
AVmin0Cooling Temperature Setpoint°F/°CWrite
AV1Temperature Assigned Via BACnetBACnet Assigned Current Temperature°F/°CWrite
AVmin3Heating Temperature Setpoint°F/°CWrite
AV4Hr-Running TimeRunning Time of Valve (Hr.)hWrite
AV5M-Running TimeRunning Time of Valve (M.)minWrite
AV6Sec-Running TimeRunning Time of Valve (Sec.)sWrite
AV7Deadband°FWrite
AV8Unoccupied Cool SetpointUnoccupied Cooling Setpoint°F/°CWrite
AV9Unoccupied Heat SetpointUnoccupied Heating Setpoint°F/°CWrite
AV10Integral-Cycle TimeIntegral Time and Output Cycle TimesWrite
AV11Analog Minimum Output for AO1Minimum Output Voltage in Digital Value When Reach Low Limit for AO1Write
AV12Span Offset for AO1Write
AV13Low Setpoint LimitLow Limit for Set-Point Temperature°F/°CWrite
AV14High Setpoint LimitHigh Limit for Set-Point Temperature°F/°CWrite
AV15Temperature OffsetOffset for Current Temperature°F/°CWrite
AV16Proportional Band- Stage WidthProportional Band or Stage Width°F/°CWrite
AV17Stage Differential°F/°CWrite
AV18LockBit-coded lock: buttons, ESI/door contacts, comms settings, DO controlWrite
AV20Device InstanceWrite
AV21UDP Port NoUDP Port NumberWrite
AV27Analog Minimum Output for AO2Minimum Output Voltage in Digital Value When Reach Low Limit for AO2Write
AV28Span Offset for AO2Write
AV29Heartbeat RateCommunication Heartbeat Minimum RatesWrite
AV39Minimum Cooling Setpoint°F/°CWrite
AV40Maximum Heating Setpoint°F/°CWrite
BImin0Occupancy StatusStatus of OccupancyRead0=Room Occupied, 1=Room Unoccupied
BImin2Cooling-heating StatusStatus of Cooling/Heating Control OutputRead0=Close & Off, 1=Open & On
BI9Relay 7 StatusStatus of Relay 7 FanRead0=Off, 1=On
BV0Occupancy Contact DefinitionOccupancy(DI1) Contact DefinitionWrite0=N.O. = Occupied, 1=N.C. = Occupied
BV1Cooling Direct- Reverse ActingModulating Cooling Direct/ Reverse Signal OutputWrite0=Direct (0 To10v), 1=Reverse (10 To 0V)
BV2Heating Direct- Reverse ActingModulating Heating Direct/ Reverse Signal OutputWrite0=Direct (0 To10v), 1=Reverse (10 To 0V)
BVmin5On-Off ControlOn/Off Status of ThermostatWrite0=Off, 1=On
BV6Temperature Scale°C/ °FWrite0=°C, 1=°F
BV13Relay 7 ControlOn/Off Control of Relay 7 (Fan)Write0=Off, 1=On
BVmin14Occupancy CommandRoom Occupancy SettingWrite0=Occupied, 1=Unoccupied
BV15Fan Output for HeatingDisable/ Enable Fan Output for HeatingWrite0=Disable, 1=Enable
BV16HeartbeatCommunication Heartbeat Flip-FlopWrite0=Off, 1=On
MVmin0Fan ModeWrite1=Auto, 2=Low, 3=Med., 4=Hi
MVmin1System ModeWorking Mode: Heat, Cool or VentilationWrite1=Cool Mode, 2=Heat Mode, 3=Ventilation @ Cool Mode, 4=Ventilation @ Heat Mode
MV3Temperature SourceCurrent Temperature SourceWrite1=Built-In Temp. Sensor, 2=Remote Temp. Sensor, 3=Assigned through BACnet
MV4Lowest Fan SpeedLowest Fan speed in Auto Fan modeWrite1=Stop, 2=Low, 3=Med., 4=Hi
MVmin5Fan Speed StatusRead0=Stop, 1=Low, 2=Med, 3=Hi
MV6Display OptionsLCD Display OptionsWrite1=T & Time (if available), 2=SP & Time (if available), 3=T & CO2 (if available), 4=CO2 & Time (if available)
MV7Control TypeControl Type SelectionWrite2=4-Pipe Cooling or Heating Manual Changeover, 3=4-Pipe Cooling and Heating Auto Changeover
Object ID lookup: Contemporary Controls BAST-421C-BW2 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat

How many BACnet points does the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat have?

This list has 50 BACnet objects: 6 analog inputs, 25 analog values, 3 binary inputs, 9 binary values, 7 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat BACnet points are writable?

40 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat BACnet documentation?

The source is BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat User Manual (UM-15093500-AA2), published free by Contemporary Controls at https://www.ccontrols.com/pdf/um/BAST-421C-BW2-UserManual.pdf.

What are the minimum BACnet points to integrate the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat?

Start with BV 5 On-Off Control (Thermostat outputs on/off (1 = on)); BV 14 Occupancy Command (0 = occupied, 1 = unoccupied); MV 1 System Mode (Cool, heat or ventilation mode); AV 0 Cooling Temperature Setpoint (Occupied cooling setpoint); AV 3 Heating Temperature Setpoint (Occupied heating setpoint); MV 0 Fan Mode (1 = auto, then fan speeds); AI 0 Current Temperature (Space temperature in use); BI 0 Occupancy Status (0 = occupied, 1 = unoccupied); BI 2 Cooling-heating Status (Heating/cooling output active); MV 5 Fan Speed Status (Current fan speed, 0 = stop).

How do I enable BMS control of the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat?

On-Off Control (BV 5) switches the thermostat outputs. Occupancy Command (BV 14) only takes effect when the ESI contact is disabled in Lock (AV 18 bit value 64); by default occupancy comes from the ESI dry contact.

Does the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat need a BACnet heartbeat or have a communication timeout?

A space temperature written to Temperature Assigned Via BACnet (AV 1) is only used while the BMS keeps toggling Heartbeat (BV 16) within the Heartbeat Rate (AV 29) period, in seconds; otherwise the thermostat reverts to its own sensor.

Can the BMS supply sensor values to the Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat?

Set Temperature Source (MV 3) to 3 (Assigned through BACnet) and write the space temperature to AV 1, toggling BV 16 as a heartbeat.

How do I check these points on the real BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat User Manual · UM-15093500-AA2. Object names, instances and units are reproduced as published; descriptions are our own.