UPS (uninterruptible power supply) · BACnet points list

Contemporary Controls Liebert Series 600 UPS via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Liebert Series 600 UPS: 80 objects (42 AI, 38 BI), all polled. Binary inputs give load on inverter/bypass/battery, transfers, switch states and the alarm and customer alarm bits; analog inputs give nominal ratings, load in VA, W and % of capacity, frequencies, battery voltage, current, time and charge, and input, bypass and output voltages and currents per line.

This page lists 80 BACnet objects for the Contemporary Controls Liebert Series 600 UPS via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Liebert Series 600 UPS via BASgatewayLX
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
80 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Series 600, Liebert 600T, Liebert UPS Modbus
Source document
BASgatewayLX Modbus device profile LIEBERT_SERIES_600_UPS_a · LIEBERT_SERIES_600_UPS_a_LX.csv
Download CSV 80 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Liebert Series 600 UPS via BASgatewayLX

Integration in brief

Read the load-on-inverter/bypass/battery bits, load %, battery time and charge, and the shutdown/overload alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 2Load On InverterLoad on inverterRead
BI 3Load On BypassLoad on bypassRead
BI 6Load On BatteryLoad on batteryRead
AI 51Load / CapacityLoad, % of capacityRead
AI 57Battery Time RemainingBattery time remaining, minRead
AI 58Battery Charge PercentageBattery charge, %Read
AI 63Output Voltage L1Output voltage L1Read
AI 52Output FrequencyOutput frequencyRead
BI 14Low Battery - Shutdown ImminentLow battery, shutdown imminentRead
BI 16Output OverloadOutput overloadRead

Network setup

Watch out for

Contemporary Controls Liebert Series 600 UPS via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

80 of 80 shown
Type
AnalogBinary
Show
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX BACnet Points List
DescriptionStates
BI1Auto Retransfer PrimedModbus 100049Read
BImin2Load On InverterModbus 100073Read
BImin3Load On BypassModbus 100074Read
BI4Battery data Buffer FullModbus 100084Read
BI5Shutdown Reason - HardwareModbus 100096Read
BImin6Load On BatteryModbus 100128Read
BI7Load On BypassModbus 100129Read
BI8Manual Reset TransferModbus 100130Read
BI9Emergency TransferModbus 100134Read
BI10Battery Switch OpenModbus 100136Read
BI11Input Switch OpenModbus 100137Read
BI12Output Switch openModbus 100138Read
BI13SBS UnableModbus 100148Read
BImin14Low Battery - Shutdown ImminentModbus 100152Read
BI15Output Frequency OffModbus 100153Read
BImin16Output OverloadModbus 100154Read
BI17System Emergency OffModbus 100157Read
BI18Reverse PowerModbus 100159Read
BI19Fan FailModbus 100169Read
BI20Over Temperature WarningModbus 100171Read
BI21Ambient Over TemperatureModbus 100173Read
BI22Input Power Supply FailModbus 100186Read
BI23Input Phase Rotation ErrorModbus 100191Read
BI24Bypass Input Voltage FailModbus 100202Read
BI25Output Under VoltageModbus 100218Read
BI26Output Over VoltageModbus 100219Read
BI27DC Ground FaultModbus 100233Read
BI28DC Cap Fuse BlownModbus 100252Read
BI29Rectifier Fuse BlownModbus 100257Read
BI30Inverter Fuse BlownModbus 100261Read
BI31Customer Alarm 1Modbus 100313Read
BI32Customer Alarm 2Modbus 100314Read
BI33Customer Alarm 3Modbus 100315Read
BI34Customer Alarm 4Modbus 100316Read
BI35Customer Alarm 5Modbus 100317Read
BI36Customer Alarm 6Modbus 100318Read
BI37Customer Alarm 7Modbus 100319Read
BI38Customer Alarm 8Modbus 100320Read
AI39Number of _input_Bypass and Output LinesModbus 400004Read
AI40Nominal Power RatingModbus 400021VARead
AI41Nominal Input VoltageModbus 400027VRead
AI42Nominal Output VoltageModbus 400028VRead
AI43Nominal Static Bypass Switch VoltageModbus 400029VRead
AI44Nominal Input CurrentModbus 400030ARead
AI45Nominal Output FrequencyModbus 400032HzRead
AI46Nominal Power FactorModbus 400033Read
AI47Nominal Battery VoltageModbus 400034VRead
AI48Silence AlarmModbus 400101Read
AI49Load (Apparent Power)Modbus 300102VARead
AI50Load (Real Power)Modbus 300104WRead
AImin51Load / CapacityModbus 300106%Read
AImin52Output FrequencyModbus 300108HzRead
AI53Bypass FrequencyModbus 300109HzRead
AI54Battery Charge StatusModbus 300112Read
AI55Battery VoltageModbus 300113VRead
AI56Battery CurrentModbus 300114ARead
AImin57Battery Time RemainingModbus 300115minRead
AImin58Battery Charge PercentageModbus 300116%Read
AI59Input Voltage L1Modbus 300153VRead
AI60Input Current L1Modbus 300154ARead
AI61Bypass Voltage L1Modbus 300159VRead
AI62Bypass Current L1Modbus 300160ARead
AImin63Output Voltage L1Modbus 300163VRead
AI64Output Current L1Modbus 300164ARead
AI65Input Voltage L2Modbus 300203VRead
AI66Input Current L2Modbus 300204ARead
AI67Bypass Voltage L2Modbus 300209VRead
AI68Bypass Current L2Modbus 300210ARead
AI69Output Voltage L2Modbus 300213VRead
AI70Output Current L2Modbus 300214ARead
AI71Input Voltage L3Modbus 300253VRead
AI72Input Current L3Modbus 300254ARead
AI73Bypass Voltage L3Modbus 300259VRead
AI74Bypass Current L3Modbus 300260ARead
AI75Output Voltage L3Modbus 300263VRead
AI76Output Current L3Modbus 300264ARead
AI77Battery Discharge CountModbus 300308Read
AI78Battery Discharge durationModbus 300309sRead
AI79Battery Amp-HourModbus 300310Read
AI80Battery Watt-HourModbus 300311WhRead
Object ID lookup: Contemporary Controls BASgatewayLX Liebert 600 UPS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Series 600 UPS via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Liebert Series 600 UPS via BASgatewayLX

How many BACnet points does the Contemporary Controls Liebert Series 600 UPS via BASgatewayLX have?

This list has 80 BACnet objects: 42 analog inputs, 38 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Liebert Series 600 UPS via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Liebert Series 600 UPS via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile LIEBERT_SERIES_600_UPS_a (LIEBERT_SERIES_600_UPS_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Liebert600UPS.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Liebert Series 600 UPS via BASgatewayLX?

Start with BI 2 Load On Inverter (Load on inverter); BI 3 Load On Bypass (Load on bypass); BI 6 Load On Battery (Load on battery); AI 51 Load / Capacity (Load, % of capacity); AI 57 Battery Time Remaining (Battery time remaining, min); AI 58 Battery Charge Percentage (Battery charge, %); AI 63 Output Voltage L1 (Output voltage L1); AI 52 Output Frequency (Output frequency); BI 14 Low Battery - Shutdown Imminent (Low battery, shutdown imminent); BI 16 Output Overload (Output overload).

How do I check these points on the real Liebert Series 600 UPS via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists