I/O module (analog inputs) · BACnet points list
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Acromag 961EN/962EN: 139 objects (133 AI, 4 AO, 2 BI), 18 polled by default (status, value and count for channels 0-5). Module settings, calibration registers, ranges and min/max/average values are unpolled.
This page lists 139 BACnet objects for the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
- Equipment
- I/O module (analog inputs)
- Equipment type
- Other equipment
- BACnet objects
- 139 (4 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Map channel 0 value, channel 1 value and channel 2 value first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 11 | CHOO Value | Channel 0 value | Read |
| AI 12 | CHOI Value | Channel 1 value | Read |
| AI 13 | CH02 Value | Channel 2 value | Read |
| AI 14 | CH03 Value | Channel 3 value | Read |
| AI 15 | CH04 Value | Channel 4 value | Read |
| AI 16 | CH05 Value | Channel 5 value | Read |
| AI 5 | CHOO Status | Channel 0 status | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Calibration access and the span/zero calibration registers (AO 25, AO 138, AO 139) are unpolled; leave them that way.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | Wink Mode Flag | Modbus 300001 bit 14; not polled by default | Read | ||
| BI | 2 | Default Mode Flag | Modbus 300001 bit 13; not polled by default | Read | ||
| AI | 3 | Input Range (CH 0 1 2 ) | Modbus 300002; not polled by default | Read | ||
| AI | 4 | Input Range (CH 3 4 5 ) | Modbus 300003; not polled by default | Read | ||
| AImin | 5 | CHOO Status | Modbus 300004 | Read | ||
| AI | 6 | CHOI Status | Modbus 300005 | Read | ||
| AI | 7 | CH02 Status | Modbus 300006 | Read | ||
| AI | 8 | CH03 Status | Modbus 300007 | Read | ||
| AI | 9 | CH04 Status | Modbus 300008 | Read | ||
| AI | 10 | CH05 Status | Modbus 300009 | Read | ||
| AImin | 11 | CHOO Value | Modbus 300010 | Read | ||
| AImin | 12 | CHOI Value | Modbus 300011 | Read | ||
| AImin | 13 | CH02 Value | Modbus 300012 | Read | ||
| AImin | 14 | CH03 Value | Modbus 300013 | Read | ||
| AImin | 15 | CH04 Value | Modbus 300014 | Read | ||
| AImin | 16 | CH05 Value | Modbus 300015 | Read | ||
| AI | 17 | CHOO Count | Modbus 300016 | Read | ||
| AI | 18 | CHOI Count | Modbus 300017 | Read | ||
| AI | 19 | CH02 Count | Modbus 300018 | Read | ||
| AI | 20 | CH03 Count | Modbus 300019 | Read | ||
| AI | 21 | CH04 Count | Modbus 300020 | Read | ||
| AI | 22 | CH05 Count | Modbus 300021 | Read | ||
| AO | 23 | Input Range (CH 0 1 2 ) R _W | Modbus 400001; not polled by default | Command | ||
| AI | 24 | Input Range (CH 3 4 5 ) R_W | Modbus 400002; not polled by default | Read | ||
| AO | 25 | Calibration Access | Modbus 400014; not polled by default | Command | ||
| AI | 26 | CHO Cal Hi Range 0 | Modbus 400022; not polled by default | Read | ||
| AI | 27 | CHO Cal Lo Range 0 | Modbus 400023; not polled by default | Read | ||
| AI | 28 | CHO Cal Hi Range 1 | Modbus 400024; not polled by default | Read | ||
| AI | 29 | CHO Cal Lo Range 1 | Modbus 400025; not polled by default | Read | ||
| AI | 30 | CHO Cal Hi Range 2 | Modbus 400026; not polled by default | Read | ||
| AI | 31 | CHO Cal Lo Range 2 | Modbus 400027; not polled by default | Read | ||
| AI | 32 | CHO Cal Hi Range 3 | Modbus 400028; not polled by default | Read | ||
| AI | 33 | CHO Cal Lo Range 3 | Modbus 400029; not polled by default | Read | ||
| AI | 34 | CHO Cal Hi Range 4 | Modbus 400030; not polled by default | mV | Read | |
| AI | 35 | CHO Cal Lo Range 4 | Modbus 400031; not polled by default | mV | Read | |
| AI | 36 | CHO Cal Hi Range 5 | Modbus 400032; not polled by default | mV | Read | |
| AI | 37 | CHO Cal Lo Range 5 | Modbus 400033; not polled by default | mV | Read | |
| AI | 38 | CHO Cal Hi Range 6 | Modbus 400034; not polled by default | mV | Read | |
| AI | 39 | CHO Cal Lo Range 6 | Modbus 400035; not polled by default | mV | Read | |
| AI | 40 | CHO Cal Hi Range 7 | Modbus 400036; not polled by default | mV | Read | |
| AI | 41 | CHO Cal Lo Range 7 | Modbus 400037; not polled by default | mV | Read | |
| AI | 42 | CH1 Cal Hi Range 0 | Modbus 400038; not polled by default | Read | ||
| AI | 43 | CH1 Cal Lo Range 0 | Modbus 400039; not polled by default | Read | ||
| AI | 44 | CH1 Cal Hi Range 1 | Modbus 400040; not polled by default | Read | ||
| AI | 45 | CH1 Cal Lo Range 1 | Modbus 400041; not polled by default | Read | ||
| AI | 46 | CH1 Cal Hi Range 2 | Modbus 400042; not polled by default | Read | ||
| AI | 47 | CH1 Cal Lo Range 2 | Modbus 400043; not polled by default | Read | ||
| AI | 48 | CH1 Cal Hi Range 3 | Modbus 400044; not polled by default | Read | ||
| AI | 49 | CH1 Cal Lo Range 3 | Modbus 400045; not polled by default | Read | ||
| AI | 50 | CH1 Cal Hi Range 4 | Modbus 400046; not polled by default | mV | Read | |
| AI | 51 | CH1 Cal Lo Range 4 | Modbus 400047; not polled by default | mV | Read | |
| AI | 52 | CH1 Cal Hi Range 5 | Modbus 400048; not polled by default | mV | Read | |
| AI | 53 | CH1 Cal Lo Range 5 | Modbus 400049; not polled by default | mV | Read | |
| AI | 54 | CH1 Cal Hi Range 6 | Modbus 400050; not polled by default | mV | Read | |
| AI | 55 | CH1 Cal Lo Range 6 | Modbus 400051; not polled by default | mV | Read | |
| AI | 56 | CH1 Cal Hi Range 7 | Modbus 400052; not polled by default | mV | Read | |
| AI | 57 | CH1 Cal Lo Range 7 | Modbus 400053; not polled by default | mV | Read | |
| AI | 58 | CH2 Cal Hi Range 0 | Modbus 400054; not polled by default | Read | ||
| AI | 59 | CH2 Cal Lo Range 0 | Modbus 400055; not polled by default | Read | ||
| AI | 60 | CH2 Cal Hi Range 1 | Modbus 400056; not polled by default | Read | ||
| AI | 61 | CH2 Cal Lo Range 1 | Modbus 400057; not polled by default | Read | ||
| AI | 62 | CH2 Cal Hi Range 2 | Modbus 400058; not polled by default | Read | ||
| AI | 63 | CH2 Cal Lo Range 2 | Modbus 400059; not polled by default | Read | ||
| AI | 64 | CH2 Cal Hi Range 3 | Modbus 400060; not polled by default | Read | ||
| AI | 65 | CH2 Cal Lo Range 3 | Modbus 400061; not polled by default | Read | ||
| AI | 66 | CH2 Cal Hi Range 4 | Modbus 400062; not polled by default | mV | Read | |
| AI | 67 | CH2 Cal Lo Range 4 | Modbus 400063; not polled by default | mV | Read | |
| AI | 68 | CH2 Cal Hi Range 5 | Modbus 400064; not polled by default | mV | Read | |
| AI | 69 | CH2 Cal Lo Range 5 | Modbus 400065; not polled by default | mV | Read | |
| AI | 70 | CH2 Cal Hi Range 6 | Modbus 400066; not polled by default | mV | Read | |
| AI | 71 | CH2 Cal Lo Range 6 | Modbus 400067; not polled by default | mV | Read | |
| AI | 72 | CH2 Cal Hi Range 7 | Modbus 400068; not polled by default | mV | Read | |
| AI | 73 | CH2 Cal Lo Range 7 | Modbus 400069; not polled by default | mV | Read | |
| AI | 74 | CH3 Cal Hi Range 0 | Modbus 400070; not polled by default | Read | ||
| AI | 75 | CH3 Cal Lo Range 0 | Modbus 400071; not polled by default | Read | ||
| AI | 76 | CH3 Cal Hi Range 1 | Modbus 400072; not polled by default | Read | ||
| AI | 77 | CH3 Cal Lo Range 1 | Modbus 400073; not polled by default | Read | ||
| AI | 78 | CH3 Cal Hi Range 2 | Modbus 400074; not polled by default | Read | ||
| AI | 79 | CH3 Cal Lo Range 2 | Modbus 400075; not polled by default | Read | ||
| AI | 80 | CH3 Cal Hi Range 3 | Modbus 400076; not polled by default | Read | ||
| AI | 81 | CH3 Cal Lo Range 3 | Modbus 400077; not polled by default | Read | ||
| AI | 82 | CH3 Cal Hi Range 4 | Modbus 400078; not polled by default | mV | Read | |
| AI | 83 | CH3 Cal Lo Range 4 | Modbus 400079; not polled by default | mV | Read | |
| AI | 84 | CH3 Cal Hi Range 5 | Modbus 400080; not polled by default | mV | Read | |
| AI | 85 | CH3 Cal Lo Range 5 | Modbus 400081; not polled by default | mV | Read | |
| AI | 86 | CH3 Cal Hi Range 6 | Modbus 400082; not polled by default | mV | Read | |
| AI | 87 | CH3 Cal Lo Range 6 | Modbus 400083; not polled by default | mV | Read | |
| AI | 88 | CH3 Cal Hi Range 7 | Modbus 400084; not polled by default | mV | Read | |
| AI | 89 | CH3 Cal Lo Range 7 | Modbus 400085; not polled by default | mV | Read | |
| AI | 90 | CH4 Cal Hi Range 0 | Modbus 400086; not polled by default | mV | Read | |
| AI | 91 | CH4 Cal Lo Range 0 | Modbus 400087; not polled by default | Read | ||
| AI | 92 | CH4 Cal Hi Range 1 | Modbus 400088; not polled by default | Read | ||
| AI | 93 | CH4 Cal Lo Range 1 | Modbus 400089; not polled by default | Read | ||
| AI | 94 | CH4 Cal Hi Range 2 | Modbus 400090; not polled by default | Read | ||
| AI | 95 | CH4 Cal Lo Range 2 | Modbus 400091; not polled by default | Read | ||
| AI | 96 | CH4 Cal Hi Range 3 | Modbus 400092; not polled by default | Read | ||
| AI | 97 | CH4 Cal Lo Range 3 | Modbus 400093; not polled by default | Read | ||
| AI | 98 | CH4 Cal Hi Range 4 | Modbus 400094; not polled by default | mV | Read | |
| AI | 99 | CH4 Cal Lo Range 4 | Modbus 400095; not polled by default | mV | Read | |
| AI | 100 | CH4 Cal Hi Range 5 | Modbus 400096; not polled by default | mV | Read | |
| AI | 101 | CH4 Cal Lo Range 5 | Modbus 400097; not polled by default | mV | Read | |
| AI | 102 | CH4 Cal Hi Range 6 | Modbus 400098; not polled by default | mV | Read | |
| AI | 103 | CH4 Cal Lo Range 6 | Modbus 400099; not polled by default | mV | Read | |
| AI | 104 | CH4 Cal Hi Range 7 | Modbus 400100; not polled by default | mV | Read | |
| AI | 105 | CH4 Cal Lo Range 7 | Modbus 400101; not polled by default | mV | Read | |
| AI | 106 | CH5 Cal Hi Range 0 | Modbus 400102; not polled by default | Read | ||
| AI | 107 | CH5 Cal Lo Range 0 | Modbus 400103; not polled by default | Read | ||
| AI | 108 | CH5 Cal Hi Range 1 | Modbus 400104; not polled by default | Read | ||
| AI | 109 | CH5 Cal Lo Range 1 | Modbus 400105; not polled by default | Read | ||
| AI | 110 | CH5 Cal Hi Range 2 | Modbus 400106; not polled by default | Read | ||
| AI | 111 | CH5 Cal Lo Range 2 | Modbus 400107; not polled by default | Read | ||
| AI | 112 | CH5 Cal Hi Range 3 | Modbus 400108; not polled by default | Read | ||
| AI | 113 | CH5 Cal Lo Range 3 | Modbus 400109; not polled by default | Read | ||
| AI | 114 | CH5 Cal Hi Range 4 | Modbus 400110; not polled by default | mV | Read | |
| AI | 115 | CH5 Cal Lo Range 4 | Modbus 400111; not polled by default | mV | Read | |
| AI | 116 | CH5 Cal Hi Range 5 | Modbus 400112; not polled by default | mV | Read | |
| AI | 117 | CH5 Cal Lo Range 5 | Modbus 400113; not polled by default | mV | Read | |
| AI | 118 | CH5 Cal Hi Range 6 | Modbus 400114; not polled by default | mV | Read | |
| AI | 119 | CH5 Cal Lo Range 6 | Modbus 400115; not polled by default | mV | Read | |
| AI | 120 | CH5 Cal Hi Range 7 | Modbus 400116; not polled by default | mV | Read | |
| AI | 121 | CH5 Cal Lo Range 7 | Modbus 400117; not polled by default | mV | Read | |
| AI | 122 | Ideal Range 0 Hi | Modbus 400118; not polled by default | Read | ||
| AI | 123 | Ideal Range 0 Lo | Modbus 400119; not polled by default | Read | ||
| AI | 124 | Ideal Range 1 Hi | Modbus 400120; not polled by default | Read | ||
| AI | 125 | Ideal Range 1 Lo | Modbus 400121; not polled by default | Read | ||
| AI | 126 | Ideal Range 2 Hi | Modbus 400122; not polled by default | Read | ||
| AI | 127 | Ideal Range 2 Lo | Modbus 400123; not polled by default | Read | ||
| AI | 128 | Ideal Range 3 Hi | Modbus 400124; not polled by default | Read | ||
| AI | 129 | Ideal Range 3 Lo | Modbus 400125; not polled by default | Read | ||
| AI | 130 | Ideal Range 4 Hi | Modbus 400126; not polled by default | mV | Read | |
| AI | 131 | Ideal Range 4 Lo | Modbus 400127; not polled by default | mV | Read | |
| AI | 132 | Ideal Range 5 Hi | Modbus 400128; not polled by default | mV | Read | |
| AI | 133 | Ideal Range 5 Lo | Modbus 400129; not polled by default | mV | Read | |
| AI | 134 | Ideal Range 6 Hi | Modbus 400130; not polled by default | mV | Read | |
| AI | 135 | Ideal Range 6 Lo | Modbus 400131; not polled by default | mV | Read | |
| AI | 136 | Ideal Range 7 Hi | Modbus 400132; not polled by default | mV | Read | |
| AI | 137 | Ideal Range 7 Lo | Modbus 400133; not polled by default | mV | Read | |
| AO | 138 | Span Cal Register | Modbus 400136; not polled by default | Command | ||
| AO | 139 | Zero Cal Register | Modbus 400137; not polled by default | Command |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Acromag 961EN/962EN point IDs by name
BI1Wink Mode FlagBI2Default Mode FlagAI3Input Range (CH 0 1 2 )AI4Input Range (CH 3 4 5 )AI5CHOO StatusAI6CHOI StatusAI7CH02 StatusAI8CH03 StatusAI9CH04 StatusAI10CH05 StatusAI11CHOO ValueAI12CHOI ValueAI13CH02 ValueAI14CH03 ValueAI15CH04 ValueAI16CH05 ValueAI17CHOO CountAI18CHOI CountAI19CH02 CountAI20CH03 CountAI21CH04 CountAI22CH05 CountAO23Input Range (CH 0 1 2 ) R _WAI24Input Range (CH 3 4 5 ) R_WAO25Calibration AccessAI26CHO Cal Hi Range 0AI27CHO Cal Lo Range 0AI28CHO Cal Hi Range 1AI29CHO Cal Lo Range 1AI30CHO Cal Hi Range 2AI31CHO Cal Lo Range 2AI32CHO Cal Hi Range 3AI33CHO Cal Lo Range 3AI34CHO Cal Hi Range 4AI35CHO Cal Lo Range 4AI36CHO Cal Hi Range 5AI37CHO Cal Lo Range 5AI38CHO Cal Hi Range 6AI39CHO Cal Lo Range 6AI40CHO Cal Hi Range 7AI41CHO Cal Lo Range 7AI42CH1 Cal Hi Range 0AI43CH1 Cal Lo Range 0AI44CH1 Cal Hi Range 1AI45CH1 Cal Lo Range 1AI46CH1 Cal Hi Range 2AI47CH1 Cal Lo Range 2AI48CH1 Cal Hi Range 3AI49CH1 Cal Lo Range 3AI50CH1 Cal Hi Range 4AI51CH1 Cal Lo Range 4AI52CH1 Cal Hi Range 5AI53CH1 Cal Lo Range 5AI54CH1 Cal Hi Range 6AI55CH1 Cal Lo Range 6AI56CH1 Cal Hi Range 7AI57CH1 Cal Lo Range 7AI58CH2 Cal Hi Range 0AI59CH2 Cal Lo Range 0AI60CH2 Cal Hi Range 1AI61CH2 Cal Lo Range 1AI62CH2 Cal Hi Range 2AI63CH2 Cal Lo Range 2AI64CH2 Cal Hi Range 3AI65CH2 Cal Lo Range 3AI66CH2 Cal Hi Range 4AI67CH2 Cal Lo Range 4AI68CH2 Cal Hi Range 5AI69CH2 Cal Lo Range 5AI70CH2 Cal Hi Range 6AI71CH2 Cal Lo Range 6AI72CH2 Cal Hi Range 7AI73CH2 Cal Lo Range 7AI74CH3 Cal Hi Range 0AI75CH3 Cal Lo Range 0AI76CH3 Cal Hi Range 1AI77CH3 Cal Lo Range 1AI78CH3 Cal Hi Range 2AI79CH3 Cal Lo Range 2AI80CH3 Cal Hi Range 3AI81CH3 Cal Lo Range 3AI82CH3 Cal Hi Range 4AI83CH3 Cal Lo Range 4AI84CH3 Cal Hi Range 5AI85CH3 Cal Lo Range 5AI86CH3 Cal Hi Range 6AI87CH3 Cal Lo Range 6AI88CH3 Cal Hi Range 7AI89CH3 Cal Lo Range 7AI90CH4 Cal Hi Range 0AI91CH4 Cal Lo Range 0AI92CH4 Cal Hi Range 1AI93CH4 Cal Lo Range 1AI94CH4 Cal Hi Range 2AI95CH4 Cal Lo Range 2AI96CH4 Cal Hi Range 3AI97CH4 Cal Lo Range 3AI98CH4 Cal Hi Range 4AI99CH4 Cal Lo Range 4AI100CH4 Cal Hi Range 5AI101CH4 Cal Lo Range 5AI102CH4 Cal Hi Range 6AI103CH4 Cal Lo Range 6AI104CH4 Cal Hi Range 7AI105CH4 Cal Lo Range 7AI106CH5 Cal Hi Range 0AI107CH5 Cal Lo Range 0AI108CH5 Cal Hi Range 1AI109CH5 Cal Lo Range 1AI110CH5 Cal Hi Range 2AI111CH5 Cal Lo Range 2AI112CH5 Cal Hi Range 3AI113CH5 Cal Lo Range 3AI114CH5 Cal Hi Range 4AI115CH5 Cal Lo Range 4AI116CH5 Cal Hi Range 5AI117CH5 Cal Lo Range 5AI118CH5 Cal Hi Range 6AI119CH5 Cal Lo Range 6AI120CH5 Cal Hi Range 7AI121CH5 Cal Lo Range 7AI122Ideal Range 0 HiAI123Ideal Range 0 LoAI124Ideal Range 1 HiAI125Ideal Range 1 LoAI126Ideal Range 2 HiAI127Ideal Range 2 LoAI128Ideal Range 3 HiAI129Ideal Range 3 LoAI130Ideal Range 4 HiAI131Ideal Range 4 LoAI132Ideal Range 5 HiAI133Ideal Range 5 LoAI134Ideal Range 6 HiAI135Ideal Range 6 LoAI136Ideal Range 7 HiAI137Ideal Range 7 LoAO138Span Cal RegisterAO139Zero Cal Register
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/961_962EN_MODBUS_EXTRACT.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 18 of the 139 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Names use the letter O for zero in channel 00/01 (CHOO, CHOI) as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
How many BACnet points does the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX have?
This list has 139 BACnet objects: 133 analog inputs, 4 analog outputs, 2 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet points are writable?
4 of the 139 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a (Acromag_961_962EN_Module_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Acromag_961_962EN_Module.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX?
Start with AI 11 CHOO Value (Channel 0 value); AI 12 CHOI Value (Channel 1 value); AI 13 CH02 Value (Channel 2 value); AI 14 CH03 Value (Channel 3 value); AI 15 CH04 Value (Channel 4 value); AI 16 CH05 Value (Channel 5 value); AI 5 CHOO Status (Channel 0 status).
How do I check these points on the real Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a · Acromag_961_962EN_Module_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.