I/O module (analog inputs) · BACnet points list

Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Acromag 961EN/962EN: 139 objects (133 AI, 4 AO, 2 BI), 18 polled by default (status, value and count for channels 0-5). Module settings, calibration registers, ranges and min/max/average values are unpolled.

This page lists 139 BACnet objects for the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Equipment
I/O module (analog inputs)
Equipment type
Other equipment
BACnet objects
139 (4 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax
Source document
BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a · Acromag_961_962EN_Module_a_LX.csv
Download CSV 139 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX

Integration in brief

Map channel 0 value, channel 1 value and channel 2 value first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 11CHOO ValueChannel 0 valueRead
AI 12CHOI ValueChannel 1 valueRead
AI 13CH02 ValueChannel 2 valueRead
AI 14CH03 ValueChannel 3 valueRead
AI 15CH04 ValueChannel 4 valueRead
AI 16CH05 ValueChannel 5 valueRead
AI 5CHOO StatusChannel 0 statusRead

Network setup

Watch out for

Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

139 of 139 shown
Type
Binary
Access
Show
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet Points List
DescriptionStates
BI1Wink Mode FlagModbus 300001 bit 14; not polled by defaultRead
BI2Default Mode FlagModbus 300001 bit 13; not polled by defaultRead
AI3Input Range (CH 0 1 2 )Modbus 300002; not polled by defaultRead
AI4Input Range (CH 3 4 5 )Modbus 300003; not polled by defaultRead
AImin5CHOO StatusModbus 300004Read
AI6CHOI StatusModbus 300005Read
AI7CH02 StatusModbus 300006Read
AI8CH03 StatusModbus 300007Read
AI9CH04 StatusModbus 300008Read
AI10CH05 StatusModbus 300009Read
AImin11CHOO ValueModbus 300010Read
AImin12CHOI ValueModbus 300011Read
AImin13CH02 ValueModbus 300012Read
AImin14CH03 ValueModbus 300013Read
AImin15CH04 ValueModbus 300014Read
AImin16CH05 ValueModbus 300015Read
AI17CHOO CountModbus 300016Read
AI18CHOI CountModbus 300017Read
AI19CH02 CountModbus 300018Read
AI20CH03 CountModbus 300019Read
AI21CH04 CountModbus 300020Read
AI22CH05 CountModbus 300021Read
AO23Input Range (CH 0 1 2 ) R _WModbus 400001; not polled by defaultCommand
AI24Input Range (CH 3 4 5 ) R_WModbus 400002; not polled by defaultRead
AO25Calibration AccessModbus 400014; not polled by defaultCommand
AI26CHO Cal Hi Range 0Modbus 400022; not polled by defaultRead
AI27CHO Cal Lo Range 0Modbus 400023; not polled by defaultRead
AI28CHO Cal Hi Range 1Modbus 400024; not polled by defaultRead
AI29CHO Cal Lo Range 1Modbus 400025; not polled by defaultRead
AI30CHO Cal Hi Range 2Modbus 400026; not polled by defaultRead
AI31CHO Cal Lo Range 2Modbus 400027; not polled by defaultRead
AI32CHO Cal Hi Range 3Modbus 400028; not polled by defaultRead
AI33CHO Cal Lo Range 3Modbus 400029; not polled by defaultRead
AI34CHO Cal Hi Range 4Modbus 400030; not polled by defaultmVRead
AI35CHO Cal Lo Range 4Modbus 400031; not polled by defaultmVRead
AI36CHO Cal Hi Range 5Modbus 400032; not polled by defaultmVRead
AI37CHO Cal Lo Range 5Modbus 400033; not polled by defaultmVRead
AI38CHO Cal Hi Range 6Modbus 400034; not polled by defaultmVRead
AI39CHO Cal Lo Range 6Modbus 400035; not polled by defaultmVRead
AI40CHO Cal Hi Range 7Modbus 400036; not polled by defaultmVRead
AI41CHO Cal Lo Range 7Modbus 400037; not polled by defaultmVRead
AI42CH1 Cal Hi Range 0Modbus 400038; not polled by defaultRead
AI43CH1 Cal Lo Range 0Modbus 400039; not polled by defaultRead
AI44CH1 Cal Hi Range 1Modbus 400040; not polled by defaultRead
AI45CH1 Cal Lo Range 1Modbus 400041; not polled by defaultRead
AI46CH1 Cal Hi Range 2Modbus 400042; not polled by defaultRead
AI47CH1 Cal Lo Range 2Modbus 400043; not polled by defaultRead
AI48CH1 Cal Hi Range 3Modbus 400044; not polled by defaultRead
AI49CH1 Cal Lo Range 3Modbus 400045; not polled by defaultRead
AI50CH1 Cal Hi Range 4Modbus 400046; not polled by defaultmVRead
AI51CH1 Cal Lo Range 4Modbus 400047; not polled by defaultmVRead
AI52CH1 Cal Hi Range 5Modbus 400048; not polled by defaultmVRead
AI53CH1 Cal Lo Range 5Modbus 400049; not polled by defaultmVRead
AI54CH1 Cal Hi Range 6Modbus 400050; not polled by defaultmVRead
AI55CH1 Cal Lo Range 6Modbus 400051; not polled by defaultmVRead
AI56CH1 Cal Hi Range 7Modbus 400052; not polled by defaultmVRead
AI57CH1 Cal Lo Range 7Modbus 400053; not polled by defaultmVRead
AI58CH2 Cal Hi Range 0Modbus 400054; not polled by defaultRead
AI59CH2 Cal Lo Range 0Modbus 400055; not polled by defaultRead
AI60CH2 Cal Hi Range 1Modbus 400056; not polled by defaultRead
AI61CH2 Cal Lo Range 1Modbus 400057; not polled by defaultRead
AI62CH2 Cal Hi Range 2Modbus 400058; not polled by defaultRead
AI63CH2 Cal Lo Range 2Modbus 400059; not polled by defaultRead
AI64CH2 Cal Hi Range 3Modbus 400060; not polled by defaultRead
AI65CH2 Cal Lo Range 3Modbus 400061; not polled by defaultRead
AI66CH2 Cal Hi Range 4Modbus 400062; not polled by defaultmVRead
AI67CH2 Cal Lo Range 4Modbus 400063; not polled by defaultmVRead
AI68CH2 Cal Hi Range 5Modbus 400064; not polled by defaultmVRead
AI69CH2 Cal Lo Range 5Modbus 400065; not polled by defaultmVRead
AI70CH2 Cal Hi Range 6Modbus 400066; not polled by defaultmVRead
AI71CH2 Cal Lo Range 6Modbus 400067; not polled by defaultmVRead
AI72CH2 Cal Hi Range 7Modbus 400068; not polled by defaultmVRead
AI73CH2 Cal Lo Range 7Modbus 400069; not polled by defaultmVRead
AI74CH3 Cal Hi Range 0Modbus 400070; not polled by defaultRead
AI75CH3 Cal Lo Range 0Modbus 400071; not polled by defaultRead
AI76CH3 Cal Hi Range 1Modbus 400072; not polled by defaultRead
AI77CH3 Cal Lo Range 1Modbus 400073; not polled by defaultRead
AI78CH3 Cal Hi Range 2Modbus 400074; not polled by defaultRead
AI79CH3 Cal Lo Range 2Modbus 400075; not polled by defaultRead
AI80CH3 Cal Hi Range 3Modbus 400076; not polled by defaultRead
AI81CH3 Cal Lo Range 3Modbus 400077; not polled by defaultRead
AI82CH3 Cal Hi Range 4Modbus 400078; not polled by defaultmVRead
AI83CH3 Cal Lo Range 4Modbus 400079; not polled by defaultmVRead
AI84CH3 Cal Hi Range 5Modbus 400080; not polled by defaultmVRead
AI85CH3 Cal Lo Range 5Modbus 400081; not polled by defaultmVRead
AI86CH3 Cal Hi Range 6Modbus 400082; not polled by defaultmVRead
AI87CH3 Cal Lo Range 6Modbus 400083; not polled by defaultmVRead
AI88CH3 Cal Hi Range 7Modbus 400084; not polled by defaultmVRead
AI89CH3 Cal Lo Range 7Modbus 400085; not polled by defaultmVRead
AI90CH4 Cal Hi Range 0Modbus 400086; not polled by defaultmVRead
AI91CH4 Cal Lo Range 0Modbus 400087; not polled by defaultRead
AI92CH4 Cal Hi Range 1Modbus 400088; not polled by defaultRead
AI93CH4 Cal Lo Range 1Modbus 400089; not polled by defaultRead
AI94CH4 Cal Hi Range 2Modbus 400090; not polled by defaultRead
AI95CH4 Cal Lo Range 2Modbus 400091; not polled by defaultRead
AI96CH4 Cal Hi Range 3Modbus 400092; not polled by defaultRead
AI97CH4 Cal Lo Range 3Modbus 400093; not polled by defaultRead
AI98CH4 Cal Hi Range 4Modbus 400094; not polled by defaultmVRead
AI99CH4 Cal Lo Range 4Modbus 400095; not polled by defaultmVRead
AI100CH4 Cal Hi Range 5Modbus 400096; not polled by defaultmVRead
AI101CH4 Cal Lo Range 5Modbus 400097; not polled by defaultmVRead
AI102CH4 Cal Hi Range 6Modbus 400098; not polled by defaultmVRead
AI103CH4 Cal Lo Range 6Modbus 400099; not polled by defaultmVRead
AI104CH4 Cal Hi Range 7Modbus 400100; not polled by defaultmVRead
AI105CH4 Cal Lo Range 7Modbus 400101; not polled by defaultmVRead
AI106CH5 Cal Hi Range 0Modbus 400102; not polled by defaultRead
AI107CH5 Cal Lo Range 0Modbus 400103; not polled by defaultRead
AI108CH5 Cal Hi Range 1Modbus 400104; not polled by defaultRead
AI109CH5 Cal Lo Range 1Modbus 400105; not polled by defaultRead
AI110CH5 Cal Hi Range 2Modbus 400106; not polled by defaultRead
AI111CH5 Cal Lo Range 2Modbus 400107; not polled by defaultRead
AI112CH5 Cal Hi Range 3Modbus 400108; not polled by defaultRead
AI113CH5 Cal Lo Range 3Modbus 400109; not polled by defaultRead
AI114CH5 Cal Hi Range 4Modbus 400110; not polled by defaultmVRead
AI115CH5 Cal Lo Range 4Modbus 400111; not polled by defaultmVRead
AI116CH5 Cal Hi Range 5Modbus 400112; not polled by defaultmVRead
AI117CH5 Cal Lo Range 5Modbus 400113; not polled by defaultmVRead
AI118CH5 Cal Hi Range 6Modbus 400114; not polled by defaultmVRead
AI119CH5 Cal Lo Range 6Modbus 400115; not polled by defaultmVRead
AI120CH5 Cal Hi Range 7Modbus 400116; not polled by defaultmVRead
AI121CH5 Cal Lo Range 7Modbus 400117; not polled by defaultmVRead
AI122Ideal Range 0 HiModbus 400118; not polled by defaultRead
AI123Ideal Range 0 LoModbus 400119; not polled by defaultRead
AI124Ideal Range 1 HiModbus 400120; not polled by defaultRead
AI125Ideal Range 1 LoModbus 400121; not polled by defaultRead
AI126Ideal Range 2 HiModbus 400122; not polled by defaultRead
AI127Ideal Range 2 LoModbus 400123; not polled by defaultRead
AI128Ideal Range 3 HiModbus 400124; not polled by defaultRead
AI129Ideal Range 3 LoModbus 400125; not polled by defaultRead
AI130Ideal Range 4 HiModbus 400126; not polled by defaultmVRead
AI131Ideal Range 4 LoModbus 400127; not polled by defaultmVRead
AI132Ideal Range 5 HiModbus 400128; not polled by defaultmVRead
AI133Ideal Range 5 LoModbus 400129; not polled by defaultmVRead
AI134Ideal Range 6 HiModbus 400130; not polled by defaultmVRead
AI135Ideal Range 6 LoModbus 400131; not polled by defaultmVRead
AI136Ideal Range 7 HiModbus 400132; not polled by defaultmVRead
AI137Ideal Range 7 LoModbus 400133; not polled by defaultmVRead
AO138Span Cal RegisterModbus 400136; not polled by defaultCommand
AO139Zero Cal RegisterModbus 400137; not polled by defaultCommand
Object ID lookup: Contemporary Controls BASgatewayLX Acromag 961EN/962EN point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX

How many BACnet points does the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX have?

This list has 139 BACnet objects: 133 analog inputs, 4 analog outputs, 2 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet points are writable?

4 of the 139 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a (Acromag_961_962EN_Module_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Acromag_961_962EN_Module.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX?

Start with AI 11 CHOO Value (Channel 0 value); AI 12 CHOI Value (Channel 1 value); AI 13 CH02 Value (Channel 2 value); AI 14 CH03 Value (Channel 3 value); AI 15 CH04 Value (Channel 4 value); AI 16 CH05 Value (Channel 5 value); AI 5 CHOO Status (Channel 0 status).

How do I check these points on the real Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Acromag_961_962EN_Module_a · Acromag_961_962EN_Module_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.