Boiler burner control (flame safeguard) · BACnet points list
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Honeywell 7800 SERIES flame safeguard through the S7800A1142: 283 objects (71 AI, 212 BI), 44 polled by default. It reads the burner control fault code, sequence state and its bit flags (standby, purge, ignition, run, lockout), sequence time, cycles, hours, flame signals, remote-command status bits and timing settings.
This page lists 283 BACnet objects for the Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
- Equipment
- Boiler burner control (flame safeguard)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 283 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Read sequence state, run and lockout bits, flame signal and the fault code. The profile has no writable objects; the remote-command bits are read-only here.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 3 | BC Sequence State | Burner sequence state | Read |
| BI 16 | BC State Bits_Run | Run state | Read |
| BI 12 | BC State Bits_Standby | Standby | Read |
| AI 9 | BC Flame 1 signal strength | Flame 1 signal strength | Read |
| BI 20 | BC State Bits_Alarm | Alarm | Read |
| BI 22 | BC State Bits_Lockout | Lockout | Read |
| AI 1 | Burner Control (BC) Fault Code | Burner control fault code | Read |
| AI 8 | BC Total hours | Total burner hours | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Remote command bits (BI 270-277) are mapped as inputs, so remote off/high fire/low fire/reset cannot be sent through this profile as published.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Burner Control (BC) Fault Code | Modbus 400001 | Read | ||
| AI | 2 | BC Fault String Code | Modbus 400002; not polled by default | Read | ||
| AImin | 3 | BC Sequence State | Modbus 400003 | Read | ||
| AI | 4 | BC State String Code (line 1) | Modbus 400004 | Read | ||
| AI | 5 | BC State String Code (line 2) | Modbus 400005 | Read | ||
| AI | 6 | BC Sequence time | Modbus 400006 | Read | ||
| AI | 7 | BC Total cycles | Modbus 400007 | Read | ||
| AImin | 8 | BC Total hours | Modbus 400009 | Read | ||
| AImin | 9 | BC Flame 1 signal strength | Modbus 400011 | Read | ||
| AI | 10 | BC Flame 2 signal strength | Modbus 400012 | Read | ||
| BI | 11 | BC State Bits_Initiate | Modbus 400013 bit 0 | Read | ||
| BImin | 12 | BC State Bits_Standby | Modbus 400013 bit 1 | Read | ||
| BI | 13 | BC State Bits_Purge | Modbus 400013 bit 2 | Read | ||
| BI | 14 | BC State Bits_Pilot Ignition | Modbus 400013 bit 3 | Read | ||
| BI | 15 | BC State Bits_Main Ignition | Modbus 400013 bit 4 | Read | ||
| BImin | 16 | BC State Bits_Run | Modbus 400013 bit 5 | Read | ||
| BI | 17 | BC State Bits_Postpurge | Modbus 400013 bit 6 | Read | ||
| BI | 18 | BC State Bits_Pre-Ignition | Modbus 400013 bit 7 | Read | ||
| BI | 19 | BC State Bits_Valve Proving | Modbus 400013 bit 8 | Read | ||
| BImin | 20 | BC State Bits_Alarm | Modbus 400013 bit 13 | Read | ||
| BI | 21 | BC State Bits_Hold | Modbus 400013 bit 14 | Read | ||
| BImin | 22 | BC State Bits_Lockout | Modbus 400013 bit 15 | Read | ||
| AI | 23 | S7830 First Out Code | Modbus 400014 | Read | ||
| AI | 24 | S7830 State Bits | Modbus 400015 | Read | ||
| AI | 25 | BC Fault history record 1_Fault code | Modbus 400017; not polled by default | Read | ||
| AI | 26 | BC Fault history record 1_Fault String | Modbus 400018; not polled by default | Read | ||
| AI | 27 | BC Fault history record 1_Sequence State | Modbus 400019; not polled by default | Read | ||
| AI | 28 | BC Fault history record 1_First line message | Modbus 400020; not polled by default | Read | ||
| AI | 29 | BC Fault history record 1_Second line message | Modbus 400021; not polled by default | Read | ||
| AI | 30 | BC Fault history record 1_Sequence time | Modbus 400022; not polled by default | Read | ||
| AI | 31 | BC Fault history record 1_Total cycles | Modbus 400023; not polled by default | Read | ||
| AI | 32 | BC Fault history record 1_Total hours | Modbus 400025; not polled by default | Read | ||
| AI | 33 | BC Fault history record 2_Fault code | Modbus 400027; not polled by default | Read | ||
| AI | 34 | BC Fault history record 2_Fault String | Modbus 400028; not polled by default | Read | ||
| AI | 35 | BC Fault history record 2_Sequence State | Modbus 400029; not polled by default | Read | ||
| AI | 36 | BC Fault history record 2_First line message | Modbus 400030; not polled by default | Read | ||
| AI | 37 | BC Fault history record 2_Second line message | Modbus 400031; not polled by default | Read | ||
| AI | 38 | BC Fault history record 2_Sequence time | Modbus 400032; not polled by default | Read | ||
| AI | 39 | BC Fault history record 2_Total cycles | Modbus 400033; not polled by default | Read | ||
| AI | 40 | BC Fault history record 2_Total hours | Modbus 400035; not polled by default | Read | ||
| AI | 41 | BC Fault history record 3_Fault code | Modbus 400037; not polled by default | Read | ||
| AI | 42 | BC Fault history record 3_Fault String | Modbus 400038; not polled by default | Read | ||
| AI | 43 | BC Fault history record 3_Sequence State | Modbus 400039; not polled by default | Read | ||
| AI | 44 | BC Fault history record 3_First line message | Modbus 400040; not polled by default | Read | ||
| AI | 45 | BC Fault history record 3_Second line message | Modbus 400041; not polled by default | Read | ||
| AI | 46 | BC Fault history record 3_Sequence time | Modbus 400042; not polled by default | Read | ||
| AI | 47 | BC Fault history record 3_Total cycles | Modbus 400043; not polled by default | Read | ||
| AI | 48 | BC Fault history record 3_Total hours | Modbus 400045; not polled by default | Read | ||
| AI | 49 | BC Fault history record 4_Fault code | Modbus 400047; not polled by default | Read | ||
| AI | 50 | BC Fault history record 4_Fault String | Modbus 400048; not polled by default | Read | ||
| AI | 51 | BC Fault history record 4_Sequence State | Modbus 400049; not polled by default | Read | ||
| AI | 52 | BC Fault history record 4_First line message | Modbus 400050; not polled by default | Read | ||
| AI | 53 | BC Fault history record 4_Second line message | Modbus 400051; not polled by default | Read | ||
| AI | 54 | BC Fault history record 4_Sequence time | Modbus 400052; not polled by default | Read | ||
| AI | 55 | BC Fault history record 4_Total cycles | Modbus 400053; not polled by default | Read | ||
| AI | 56 | BC Fault history record 4_Total hours | Modbus 400055; not polled by default | Read | ||
| AI | 57 | BC Fault history record 5_Fault code | Modbus 400057; not polled by default | Read | ||
| AI | 58 | BC Fault history record 5_Fault String | Modbus 400058; not polled by default | Read | ||
| AI | 59 | BC Fault history record 5_Sequence State | Modbus 400059; not polled by default | Read | ||
| AI | 60 | BC Fault history record 5_First line message | Modbus 400060; not polled by default | Read | ||
| AI | 61 | BC Fault history record 5_Second line message | Modbus 400061; not polled by default | Read | ||
| AI | 62 | BC Fault history record 5_Sequence time | Modbus 400062; not polled by default | Read | ||
| AI | 63 | BC Fault history record 5_Total cycles | Modbus 400063; not polled by default | Read | ||
| AI | 64 | BC Fault history record 5_Total hours | Modbus 400065; not polled by default | Read | ||
| AI | 65 | BC Fault history record 6_Fault code | Modbus 400067; not polled by default | Read | ||
| AI | 66 | BC Fault history record 6_Fault String | Modbus 400068; not polled by default | Read | ||
| AI | 67 | BC Fault history record 6_Sequence State | Modbus 400069; not polled by default | Read | ||
| AI | 68 | BC Fault history record 6_First line message | Modbus 400070; not polled by default | Read | ||
| AI | 69 | BC Fault history record 6_Second line message | Modbus 400071; not polled by default | Read | ||
| AI | 70 | BC Fault history record 6_Sequence time | Modbus 400072; not polled by default | Read | ||
| AI | 71 | BC Fault history record 6_Total cycles | Modbus 400073; not polled by default | Read | ||
| AI | 72 | BC Fault history record 6_Total hours | Modbus 400075; not polled by default | Read | ||
| AI | 73 | BC Flame Failure Response Time | Modbus 400077; not polled by default | Read | ||
| AI | 74 | BC Manufacturing code | Modbus 400078; not polled by default | Read | ||
| AI | 75 | BC Type Code | Modbus 400080; not polled by default | Read | ||
| AI | 76 | S7800M/BC Software version | Modbus 400081; not polled by default | Read | ||
| AI | 77 | EA Software version | Modbus 400083; not polled by default | Read | ||
| BI | 78 | BC Rem Com stat_Autonomous. | Modbus 400085 bit 0 | Read | ||
| BI | 79 | BC Rem Com stat_Remote commanded off. | Modbus 400085 bit 1 | Read | ||
| BI | 80 | BC Rem Com stat_Remote commanded High fire | Modbus 400085 bit 2 | Read | ||
| BI | 81 | BC Rem Com stat_Remote commanded low fire. | Modbus 400085 bit 3 | Read | ||
| BI | 82 | BC Rem Com stat_Remote reset has/will be sent to BC | Modbus 400085 bit 4 | Read | ||
| BI | 83 | BC Rem Com stat_Copied from Remote Command Bit 15 | Modbus 400085 bit 15 | Read | ||
| AI | 84 | BC Flame Amplifier type | Modbus 400086 | Read | ||
| AI | 85 | BC Purge Time | Modbus 400087 | Read | ||
| BI | 86 | BC Diagnostics_Initiate_40088 | Modbus 400088 bit 0; not polled by default | Read | ||
| BI | 87 | BC Diagnostics_Standby_40088 | Modbus 400088 bit 1; not polled by default | Read | ||
| BI | 88 | BC Diagnostics_Purge_40088 | Modbus 400088 bit 2; not polled by default | Read | ||
| BI | 89 | BC Diagnostics_Pilot Ignition_40088 | Modbus 400088 bit 3; not polled by default | Read | ||
| BI | 90 | BC Diagnostics_Main Ignition_40088 | Modbus 400088 bit 4; not polled by default | Read | ||
| BI | 91 | BC Diagnostics_Run_40088 | Modbus 400088 bit 5; not polled by default | Read | ||
| BI | 92 | BC Diagnostics_Postpurge_40088 | Modbus 400088 bit 6; not polled by default | Read | ||
| BI | 93 | BC Diagnostics_Pre-Ignition_40088 | Modbus 400088 bit 7; not polled by default | Read | ||
| BI | 94 | BC Diagnostics_Valve Proving_40088 | Modbus 400088 bit 8; not polled by default | Read | ||
| BI | 95 | BC Diagnostics_Alarm_40088 | Modbus 400088 bit 13; not polled by default | Read | ||
| BI | 96 | BC Diagnostics_Hold_40088 | Modbus 400088 bit 14; not polled by default | Read | ||
| BI | 97 | BC Diagnostics_Lockout_40088 | Modbus 400088 bit 15; not polled by default | Read | ||
| BI | 98 | BC Diagnostics_Initiate_40089 | Modbus 400089 bit 0; not polled by default | Read | ||
| BI | 99 | BC Diagnostics_Standby_40089 | Modbus 400089 bit 1; not polled by default | Read | ||
| BI | 100 | BC Diagnostics_Purge_40089 | Modbus 400089 bit 2; not polled by default | Read | ||
| BI | 101 | BC Diagnostics_Pilot Ignition_40089 | Modbus 400089 bit 3; not polled by default | Read | ||
| BI | 102 | BC Diagnostics_Main Ignition_40089 | Modbus 400089 bit 4; not polled by default | Read | ||
| BI | 103 | BC Diagnostics_Run_40089 | Modbus 400089 bit 5; not polled by default | Read | ||
| BI | 104 | BC Diagnostics_Postpurge_40089 | Modbus 400089 bit 6; not polled by default | Read | ||
| BI | 105 | BC Diagnostics_Pre-Ignition_40089 | Modbus 400089 bit 7; not polled by default | Read | ||
| BI | 106 | BC Diagnostics_Valve Proving_40089 | Modbus 400089 bit 8; not polled by default | Read | ||
| BI | 107 | BC Diagnostics_Alarm_40089 | Modbus 400089 bit 13; not polled by default | Read | ||
| BI | 108 | BC Diagnostics_Hold_40089 | Modbus 400089 bit 14; not polled by default | Read | ||
| BI | 109 | BC Diagnostics_Lockout_40089 | Modbus 400089 bit 15; not polled by default | Read | ||
| BI | 110 | BC Diagnostics_Initiate_40090 | Modbus 400090 bit 0; not polled by default | Read | ||
| BI | 111 | BC Diagnostics_Standby_40090 | Modbus 400090 bit 1; not polled by default | Read | ||
| BI | 112 | BC Diagnostics_Purge_40090 | Modbus 400090 bit 2; not polled by default | Read | ||
| BI | 113 | BC Diagnostics_Pilot Ignition_40090 | Modbus 400090 bit 3; not polled by default | Read | ||
| BI | 114 | BC Diagnostics_Main Ignition_40090 | Modbus 400090 bit 4; not polled by default | Read | ||
| BI | 115 | BC Diagnostics_Run_40090 | Modbus 400090 bit 5; not polled by default | Read | ||
| BI | 116 | BC Diagnostics_Postpurge_40090 | Modbus 400090 bit 6; not polled by default | Read | ||
| BI | 117 | BC Diagnostics_Pre-Ignition_40090 | Modbus 400090 bit 7; not polled by default | Read | ||
| BI | 118 | BC Diagnostics_Valve Proving_40090 | Modbus 400090 bit 8; not polled by default | Read | ||
| BI | 119 | BC Diagnostics_Alarm_40090 | Modbus 400090 bit 13; not polled by default | Read | ||
| BI | 120 | BC Diagnostics_Hold_40090 | Modbus 400090 bit 14; not polled by default | Read | ||
| BI | 121 | BC Diagnostics_Lockout_40090 | Modbus 400090 bit 15; not polled by default | Read | ||
| BI | 122 | BC Diagnostics_Initiate_40091 | Modbus 400091 bit 0; not polled by default | Read | ||
| BI | 123 | BC Diagnostics_Standby_40091 | Modbus 400091 bit 1; not polled by default | Read | ||
| BI | 124 | BC Diagnostics_Purge_40091 | Modbus 400091 bit 2; not polled by default | Read | ||
| BI | 125 | BC Diagnostics_Pilot Ignition_40091 | Modbus 400091 bit 3; not polled by default | Read | ||
| BI | 126 | BC Diagnostics_Main Ignition_40091 | Modbus 400091 bit 4; not polled by default | Read | ||
| BI | 127 | BC Diagnostics_Run_40091 | Modbus 400091 bit 5; not polled by default | Read | ||
| BI | 128 | BC Diagnostics_Postpurge_40091 | Modbus 400091 bit 6; not polled by default | Read | ||
| BI | 129 | BC Diagnostics_Pre-Ignition_40091 | Modbus 400091 bit 7; not polled by default | Read | ||
| BI | 130 | BC Diagnostics_Valve Proving_40091 | Modbus 400091 bit 8; not polled by default | Read | ||
| BI | 131 | BC Diagnostics_Alarm_40091 | Modbus 400091 bit 13; not polled by default | Read | ||
| BI | 132 | BC Diagnostics_Hold_40091 | Modbus 400091 bit 14; not polled by default | Read | ||
| BI | 133 | BC Diagnostics_Lockout_40091 | Modbus 400091 bit 15; not polled by default | Read | ||
| BI | 134 | BC Diagnostics_Initiate_40092 | Modbus 400092 bit 0; not polled by default | Read | ||
| BI | 135 | BC Diagnostics_Standby_40092 | Modbus 400092 bit 1; not polled by default | Read | ||
| BI | 136 | BC Diagnostics_Purge_40092 | Modbus 400092 bit 2; not polled by default | Read | ||
| BI | 137 | BC Diagnostics_Pilot Ignition_40092 | Modbus 400092 bit 3; not polled by default | Read | ||
| BI | 138 | BC Diagnostics_Main Ignition_40092 | Modbus 400092 bit 4; not polled by default | Read | ||
| BI | 139 | BC Diagnostics_Run_40092 | Modbus 400092 bit 5; not polled by default | Read | ||
| BI | 140 | BC Diagnostics_Postpurge_40092 | Modbus 400092 bit 6; not polled by default | Read | ||
| BI | 141 | BC Diagnostics_Pre-Ignition_40092 | Modbus 400092 bit 7; not polled by default | Read | ||
| BI | 142 | BC Diagnostics_Valve Proving_40092 | Modbus 400092 bit 8; not polled by default | Read | ||
| BI | 143 | BC Diagnostics_Alarm_40092 | Modbus 400092 bit 13; not polled by default | Read | ||
| BI | 144 | BC Diagnostics_Hold_40092 | Modbus 400092 bit 14; not polled by default | Read | ||
| BI | 145 | BC Diagnostics_Lockout_40092 | Modbus 400092 bit 15; not polled by default | Read | ||
| BI | 146 | BC Diagnostics_Initiate_40093 | Modbus 400093 bit 0; not polled by default | Read | ||
| BI | 147 | BC Diagnostics_Standby_40093 | Modbus 400093 bit 1; not polled by default | Read | ||
| BI | 148 | BC Diagnostics_Purge_40093 | Modbus 400093 bit 2; not polled by default | Read | ||
| BI | 149 | BC Diagnostics_Pilot Ignition_40093 | Modbus 400093 bit 3; not polled by default | Read | ||
| BI | 150 | BC Diagnostics_Main Ignition_40093 | Modbus 400093 bit 4; not polled by default | Read | ||
| BI | 151 | BC Diagnostics_Run_40093 | Modbus 400093 bit 5; not polled by default | Read | ||
| BI | 152 | BC Diagnostics_Postpurge_40093 | Modbus 400093 bit 6; not polled by default | Read | ||
| BI | 153 | BC Diagnostics_Pre-Ignition_40093 | Modbus 400093 bit 7; not polled by default | Read | ||
| BI | 154 | BC Diagnostics_Valve Proving_40093 | Modbus 400093 bit 8; not polled by default | Read | ||
| BI | 155 | BC Diagnostics_Alarm_40093 | Modbus 400093 bit 13; not polled by default | Read | ||
| BI | 156 | BC Diagnostics_Hold_40093 | Modbus 400093 bit 14; not polled by default | Read | ||
| BI | 157 | BC Diagnostics_Lockout_40093 | Modbus 400093 bit 15; not polled by default | Read | ||
| BI | 158 | BC Diagnostics_Initiate_40094 | Modbus 400094 bit 0; not polled by default | Read | ||
| BI | 159 | BC Diagnostics_Standby_40094 | Modbus 400094 bit 1; not polled by default | Read | ||
| BI | 160 | BC Diagnostics_Purge_40094 | Modbus 400094 bit 2; not polled by default | Read | ||
| BI | 161 | BC Diagnostics_Pilot Ignition_40094 | Modbus 400094 bit 3; not polled by default | Read | ||
| BI | 162 | BC Diagnostics_Main Ignition_40094 | Modbus 400094 bit 4; not polled by default | Read | ||
| BI | 163 | BC Diagnostics_Run_40094 | Modbus 400094 bit 5; not polled by default | Read | ||
| BI | 164 | BC Diagnostics_Postpurge_40094 | Modbus 400094 bit 6; not polled by default | Read | ||
| BI | 165 | BC Diagnostics_Pre-Ignition_40094 | Modbus 400094 bit 7; not polled by default | Read | ||
| BI | 166 | BC Diagnostics_Valve Proving_40094 | Modbus 400094 bit 8; not polled by default | Read | ||
| BI | 167 | BC Diagnostics_Alarm_40094 | Modbus 400094 bit 13; not polled by default | Read | ||
| BI | 168 | BC Diagnostics_Hold_40094 | Modbus 400094 bit 14; not polled by default | Read | ||
| BI | 169 | BC Diagnostics_Lockout_40094 | Modbus 400094 bit 15; not polled by default | Read | ||
| BI | 170 | BC Diagnostics_Initiate_40095 | Modbus 400095 bit 0; not polled by default | Read | ||
| BI | 171 | BC Diagnostics_Standby_40095 | Modbus 400095 bit 1; not polled by default | Read | ||
| BI | 172 | BC Diagnostics_Purge_40095 | Modbus 400095 bit 2; not polled by default | Read | ||
| BI | 173 | BC Diagnostics_Pilot Ignition_40095 | Modbus 400095 bit 3; not polled by default | Read | ||
| BI | 174 | BC Diagnostics_Main Ignition_40095 | Modbus 400095 bit 4; not polled by default | Read | ||
| BI | 175 | BC Diagnostics_Run_40095 | Modbus 400095 bit 5; not polled by default | Read | ||
| BI | 176 | BC Diagnostics_Postpurge_40095 | Modbus 400095 bit 6; not polled by default | Read | ||
| BI | 177 | BC Diagnostics_Pre-Ignition_40095 | Modbus 400095 bit 7; not polled by default | Read | ||
| BI | 178 | BC Diagnostics_Valve Proving_40095 | Modbus 400095 bit 8; not polled by default | Read | ||
| BI | 179 | BC Diagnostics_Alarm_40095 | Modbus 400095 bit 13; not polled by default | Read | ||
| BI | 180 | BC Diagnostics_Hold_40095 | Modbus 400095 bit 14; not polled by default | Read | ||
| BI | 181 | BC Diagnostics_Lockout_40095 | Modbus 400095 bit 15; not polled by default | Read | ||
| BI | 182 | BC Diagnostics_Initiate_40096 | Modbus 400096 bit 0; not polled by default | Read | ||
| BI | 183 | BC Diagnostics_Standby_40096 | Modbus 400096 bit 1; not polled by default | Read | ||
| BI | 184 | BC Diagnostics_Purge_40096 | Modbus 400096 bit 2; not polled by default | Read | ||
| BI | 185 | BC Diagnostics_Pilot Ignition_40096 | Modbus 400096 bit 3; not polled by default | Read | ||
| BI | 186 | BC Diagnostics_Main Ignition_40096 | Modbus 400096 bit 4; not polled by default | Read | ||
| BI | 187 | BC Diagnostics_Run_40096 | Modbus 400096 bit 5; not polled by default | Read | ||
| BI | 188 | BC Diagnostics_Postpurge_40096 | Modbus 400096 bit 6; not polled by default | Read | ||
| BI | 189 | BC Diagnostics_Pre-Ignition_40096 | Modbus 400096 bit 7; not polled by default | Read | ||
| BI | 190 | BC Diagnostics_Valve Proving_40096 | Modbus 400096 bit 8; not polled by default | Read | ||
| BI | 191 | BC Diagnostics_Alarm_40096 | Modbus 400096 bit 13; not polled by default | Read | ||
| BI | 192 | BC Diagnostics_Hold_40096 | Modbus 400096 bit 14; not polled by default | Read | ||
| BI | 193 | BC Diagnostics_Lockout_40096 | Modbus 400096 bit 15; not polled by default | Read | ||
| BI | 194 | BC Diagnostics_Initiate_40097 | Modbus 400097 bit 0; not polled by default | Read | ||
| BI | 195 | BC Diagnostics_Standby_40097 | Modbus 400097 bit 1; not polled by default | Read | ||
| BI | 196 | BC Diagnostics_Purge_40097 | Modbus 400097 bit 2; not polled by default | Read | ||
| BI | 197 | BC Diagnostics_Pilot Ignition_40097 | Modbus 400097 bit 3; not polled by default | Read | ||
| BI | 198 | BC Diagnostics_Main Ignition_40097 | Modbus 400097 bit 4; not polled by default | Read | ||
| BI | 199 | BC Diagnostics_Run_40097 | Modbus 400097 bit 5; not polled by default | Read | ||
| BI | 200 | BC Diagnostics_Postpurge_40097 | Modbus 400097 bit 6; not polled by default | Read | ||
| BI | 201 | BC Diagnostics_Pre-Ignition_40097 | Modbus 400097 bit 7; not polled by default | Read | ||
| BI | 202 | BC Diagnostics_Valve Proving_40097 | Modbus 400097 bit 8; not polled by default | Read | ||
| BI | 203 | BC Diagnostics_Alarm_40097 | Modbus 400097 bit 13; not polled by default | Read | ||
| BI | 204 | BC Diagnostics_Hold_40097 | Modbus 400097 bit 14; not polled by default | Read | ||
| BI | 205 | BC Diagnostics_Lockout_40097 | Modbus 400097 bit 15; not polled by default | Read | ||
| BI | 206 | BC Diagnostics_Initiate_40098 | Modbus 400098 bit 0; not polled by default | Read | ||
| BI | 207 | BC Diagnostics_Standby_40098 | Modbus 400098 bit 1; not polled by default | Read | ||
| BI | 208 | BC Diagnostics_Purge_40098 | Modbus 400098 bit 2; not polled by default | Read | ||
| BI | 209 | BC Diagnostics_Pilot Ignition_40098 | Modbus 400098 bit 3; not polled by default | Read | ||
| BI | 210 | BC Diagnostics_Main Ignition_40098 | Modbus 400098 bit 4; not polled by default | Read | ||
| BI | 211 | BC Diagnostics_Run_40098 | Modbus 400098 bit 5; not polled by default | Read | ||
| BI | 212 | BC Diagnostics_Postpurge_40098 | Modbus 400098 bit 6; not polled by default | Read | ||
| BI | 213 | BC Diagnostics_Pre-Ignition_40098 | Modbus 400098 bit 7; not polled by default | Read | ||
| BI | 214 | BC Diagnostics_Valve Proving_40098 | Modbus 400098 bit 8; not polled by default | Read | ||
| BI | 215 | BC Diagnostics_Alarm_40098 | Modbus 400098 bit 13; not polled by default | Read | ||
| BI | 216 | BC Diagnostics_Hold_40098 | Modbus 400098 bit 14; not polled by default | Read | ||
| BI | 217 | BC Diagnostics_Lockout_40098 | Modbus 400098 bit 15; not polled by default | Read | ||
| BI | 218 | BC Diagnostics_Initiate_40099 | Modbus 400099 bit 0; not polled by default | Read | ||
| BI | 219 | BC Diagnostics_Standby_40099 | Modbus 400099 bit 1; not polled by default | Read | ||
| BI | 220 | BC Diagnostics_Purge_40099 | Modbus 400099 bit 2; not polled by default | Read | ||
| BI | 221 | BC Diagnostics_Pilot Ignition_40099 | Modbus 400099 bit 3; not polled by default | Read | ||
| BI | 222 | BC Diagnostics_Main Ignition_40099 | Modbus 400099 bit 4; not polled by default | Read | ||
| BI | 223 | BC Diagnostics_Run_40099 | Modbus 400099 bit 5; not polled by default | Read | ||
| BI | 224 | BC Diagnostics_Postpurge_40099 | Modbus 400099 bit 6; not polled by default | Read | ||
| BI | 225 | BC Diagnostics_Pre-Ignition_40099 | Modbus 400099 bit 7; not polled by default | Read | ||
| BI | 226 | BC Diagnostics_Valve Proving_40099 | Modbus 400099 bit 8; not polled by default | Read | ||
| BI | 227 | BC Diagnostics_Alarm_40099 | Modbus 400099 bit 13; not polled by default | Read | ||
| BI | 228 | BC Diagnostics_Hold_40099 | Modbus 400099 bit 14; not polled by default | Read | ||
| BI | 229 | BC Diagnostics_Lockout_40099 | Modbus 400099 bit 15; not polled by default | Read | ||
| BI | 230 | BC Diagnostics_Initiate_40100 | Modbus 400100 bit 0; not polled by default | Read | ||
| BI | 231 | BC Diagnostics_Standby_40100 | Modbus 400100 bit 1; not polled by default | Read | ||
| BI | 232 | BC Diagnostics_Purge_40100 | Modbus 400100 bit 2; not polled by default | Read | ||
| BI | 233 | BC Diagnostics_Pilot Ignition_40100 | Modbus 400100 bit 3; not polled by default | Read | ||
| BI | 234 | BC Diagnostics_Main Ignition_40100 | Modbus 400100 bit 4; not polled by default | Read | ||
| BI | 235 | BC Diagnostics_Run_40100 | Modbus 400100 bit 5; not polled by default | Read | ||
| BI | 236 | BC Diagnostics_Postpurge_40100 | Modbus 400100 bit 6; not polled by default | Read | ||
| BI | 237 | BC Diagnostics_Pre-Ignition_40100 | Modbus 400100 bit 7; not polled by default | Read | ||
| BI | 238 | BC Diagnostics_Valve Proving_40100 | Modbus 400100 bit 8; not polled by default | Read | ||
| BI | 239 | BC Diagnostics_Alarm_40100 | Modbus 400100 bit 13; not polled by default | Read | ||
| BI | 240 | BC Diagnostics_Hold_40100 | Modbus 400100 bit 14; not polled by default | Read | ||
| BI | 241 | BC Diagnostics_Lockout_40100 | Modbus 400100 bit 15; not polled by default | Read | ||
| BI | 242 | BC Diagnostics_Initiate_40101 | Modbus 400101 bit 0; not polled by default | Read | ||
| BI | 243 | BC Diagnostics_Standby_40101 | Modbus 400101 bit 1; not polled by default | Read | ||
| BI | 244 | BC Diagnostics_Purge_40101 | Modbus 400101 bit 2; not polled by default | Read | ||
| BI | 245 | BC Diagnostics_Pilot Ignition_40101 | Modbus 400101 bit 3; not polled by default | Read | ||
| BI | 246 | BC Diagnostics_Main Ignition_40101 | Modbus 400101 bit 4; not polled by default | Read | ||
| BI | 247 | BC Diagnostics_Run_40101 | Modbus 400101 bit 5; not polled by default | Read | ||
| BI | 248 | BC Diagnostics_Postpurge_40101 | Modbus 400101 bit 6; not polled by default | Read | ||
| BI | 249 | BC Diagnostics_Pre-Ignition_40101 | Modbus 400101 bit 7; not polled by default | Read | ||
| BI | 250 | BC Diagnostics_Valve Proving_40101 | Modbus 400101 bit 8; not polled by default | Read | ||
| BI | 251 | BC Diagnostics_Alarm_40101 | Modbus 400101 bit 13; not polled by default | Read | ||
| BI | 252 | BC Diagnostics_Hold_40101 | Modbus 400101 bit 14; not polled by default | Read | ||
| BI | 253 | BC Diagnostics_Lockout_40101 | Modbus 400101 bit 15; not polled by default | Read | ||
| BI | 254 | BC Diagnostics_Initiate_40102 | Modbus 400102 bit 0; not polled by default | Read | ||
| BI | 255 | BC Diagnostics_Standby_40102 | Modbus 400102 bit 1; not polled by default | Read | ||
| BI | 256 | BC Diagnostics_Purge_40102 | Modbus 400102 bit 2; not polled by default | Read | ||
| BI | 257 | BC Diagnostics_Pilot Ignition_40102 | Modbus 400102 bit 3; not polled by default | Read | ||
| BI | 258 | BC Diagnostics_Main Ignition_40102 | Modbus 400102 bit 4; not polled by default | Read | ||
| BI | 259 | BC Diagnostics_Run_40102 | Modbus 400102 bit 5; not polled by default | Read | ||
| BI | 260 | BC Diagnostics_Postpurge_40102 | Modbus 400102 bit 6; not polled by default | Read | ||
| BI | 261 | BC Diagnostics_Pre-Ignition_40102 | Modbus 400102 bit 7; not polled by default | Read | ||
| BI | 262 | BC Diagnostics_Valve Proving_40102 | Modbus 400102 bit 8; not polled by default | Read | ||
| BI | 263 | BC Diagnostics_Alarm_40102 | Modbus 400102 bit 13; not polled by default | Read | ||
| BI | 264 | BC Diagnostics_Hold_40102 | Modbus 400102 bit 14; not polled by default | Read | ||
| BI | 265 | BC Diagnostics_Lockout_40102 | Modbus 400102 bit 15; not polled by default | Read | ||
| AI | 266 | Post-Purge time | Modbus 400103 | Read | ||
| AI | 267 | Valve Proving Mode | Modbus 400104 | Read | ||
| AI | 268 | Valve Proving option | Modbus 400105 | Read | ||
| AI | 269 | Valve Proving time | Modbus 400106 | Read | ||
| BI | 270 | BC Rem Com_Revert to auto operation | Modbus 400128 bit 0 | Read | ||
| BI | 271 | BC Rem Com_Do n0t fire-remain off | Modbus 400128 bit 1 | Read | ||
| BI | 272 | BC Rem Com_Go to Hi Fire during Run | Modbus 400128 bit 2 | Read | ||
| BI | 273 | BC Rem Com_Go to Lo Fire during Run | Modbus 400128 bit 3 | Read | ||
| BI | 274 | BC Rem Com_Remote reset | Modbus 400128 bit 4 | Read | ||
| BI | 275 | BC Rem Com_must be 0_a | Modbus 400128 bit 5 | Read | ||
| BI | 276 | BC Rem Com_must be 0_b | Modbus 400128 bit 6 | Read | ||
| BI | 277 | BC Rem Com_must be 0_c | Modbus 400128 bit 7 | Read | ||
| BI | 278 | BC Rem Com_Copied to the control status register | Modbus 400128 bit 15 | Read | ||
| BI | 279 | Device Data Ready_RM78XX | Modbus 400443 bit 0; not polled by default | Read | ||
| BI | 280 | Device Data Ready_EC78XX | Modbus 400443 bit 3; not polled by default | Read | ||
| BI | 281 | S7800 Dev Compat with Current Soft Rev_RM78XX | Modbus 400444 bit 0; not polled by default | Read | ||
| BI | 282 | S7800 Dev Compat with Current Soft Rev_EC78XX | Modbus 400444 bit 3; not polled by default | Read | ||
| BI | 283 | S7800 Dev Compat with Legacy Soft Rev_Series 2 | Modbus 400444 bit 8; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Honeywell 7800 SERIES point IDs by name
AI1Burner Control (BC) Fault CodeAI2BC Fault String CodeAI3BC Sequence StateAI4BC State String Code (line 1)AI5BC State String Code (line 2)AI6BC Sequence timeAI7BC Total cyclesAI8BC Total hoursAI9BC Flame 1 signal strengthAI10BC Flame 2 signal strengthBI11BC State Bits_InitiateBI12BC State Bits_StandbyBI13BC State Bits_PurgeBI14BC State Bits_Pilot IgnitionBI15BC State Bits_Main IgnitionBI16BC State Bits_RunBI17BC State Bits_PostpurgeBI18BC State Bits_Pre-IgnitionBI19BC State Bits_Valve ProvingBI20BC State Bits_AlarmBI21BC State Bits_HoldBI22BC State Bits_LockoutAI23S7830 First Out CodeAI24S7830 State BitsAI25BC Fault history record 1_Fault codeAI26BC Fault history record 1_Fault StringAI27BC Fault history record 1_Sequence StateAI28BC Fault history record 1_First line messageAI29BC Fault history record 1_Second line messageAI30BC Fault history record 1_Sequence timeAI31BC Fault history record 1_Total cyclesAI32BC Fault history record 1_Total hoursAI33BC Fault history record 2_Fault codeAI34BC Fault history record 2_Fault StringAI35BC Fault history record 2_Sequence StateAI36BC Fault history record 2_First line messageAI37BC Fault history record 2_Second line messageAI38BC Fault history record 2_Sequence timeAI39BC Fault history record 2_Total cyclesAI40BC Fault history record 2_Total hoursAI41BC Fault history record 3_Fault codeAI42BC Fault history record 3_Fault StringAI43BC Fault history record 3_Sequence StateAI44BC Fault history record 3_First line messageAI45BC Fault history record 3_Second line messageAI46BC Fault history record 3_Sequence timeAI47BC Fault history record 3_Total cyclesAI48BC Fault history record 3_Total hoursAI49BC Fault history record 4_Fault codeAI50BC Fault history record 4_Fault StringAI51BC Fault history record 4_Sequence StateAI52BC Fault history record 4_First line messageAI53BC Fault history record 4_Second line messageAI54BC Fault history record 4_Sequence timeAI55BC Fault history record 4_Total cyclesAI56BC Fault history record 4_Total hoursAI57BC Fault history record 5_Fault codeAI58BC Fault history record 5_Fault StringAI59BC Fault history record 5_Sequence StateAI60BC Fault history record 5_First line messageAI61BC Fault history record 5_Second line messageAI62BC Fault history record 5_Sequence timeAI63BC Fault history record 5_Total cyclesAI64BC Fault history record 5_Total hoursAI65BC Fault history record 6_Fault codeAI66BC Fault history record 6_Fault StringAI67BC Fault history record 6_Sequence StateAI68BC Fault history record 6_First line messageAI69BC Fault history record 6_Second line messageAI70BC Fault history record 6_Sequence timeAI71BC Fault history record 6_Total cyclesAI72BC Fault history record 6_Total hoursAI73BC Flame Failure Response TimeAI74BC Manufacturing codeAI75BC Type CodeAI76S7800M/BC Software versionAI77EA Software versionBI78BC Rem Com stat_Autonomous.BI79BC Rem Com stat_Remote commanded off.BI80BC Rem Com stat_Remote commanded High fireBI81BC Rem Com stat_Remote commanded low fire.BI82BC Rem Com stat_Remote reset has/will be sent to BCBI83BC Rem Com stat_Copied from Remote Command Bit 15AI84BC Flame Amplifier typeAI85BC Purge TimeBI86BC Diagnostics_Initiate_40088BI87BC Diagnostics_Standby_40088BI88BC Diagnostics_Purge_40088BI89BC Diagnostics_Pilot Ignition_40088BI90BC Diagnostics_Main Ignition_40088BI91BC Diagnostics_Run_40088BI92BC Diagnostics_Postpurge_40088BI93BC Diagnostics_Pre-Ignition_40088BI94BC Diagnostics_Valve Proving_40088BI95BC Diagnostics_Alarm_40088BI96BC Diagnostics_Hold_40088BI97BC Diagnostics_Lockout_40088BI98BC Diagnostics_Initiate_40089BI99BC Diagnostics_Standby_40089BI100BC Diagnostics_Purge_40089BI101BC Diagnostics_Pilot Ignition_40089BI102BC Diagnostics_Main Ignition_40089BI103BC Diagnostics_Run_40089BI104BC Diagnostics_Postpurge_40089BI105BC Diagnostics_Pre-Ignition_40089BI106BC Diagnostics_Valve Proving_40089BI107BC Diagnostics_Alarm_40089BI108BC Diagnostics_Hold_40089BI109BC Diagnostics_Lockout_40089BI110BC Diagnostics_Initiate_40090BI111BC Diagnostics_Standby_40090BI112BC Diagnostics_Purge_40090BI113BC Diagnostics_Pilot Ignition_40090BI114BC Diagnostics_Main Ignition_40090BI115BC Diagnostics_Run_40090BI116BC Diagnostics_Postpurge_40090BI117BC Diagnostics_Pre-Ignition_40090BI118BC Diagnostics_Valve Proving_40090BI119BC Diagnostics_Alarm_40090BI120BC Diagnostics_Hold_40090BI121BC Diagnostics_Lockout_40090BI122BC Diagnostics_Initiate_40091BI123BC Diagnostics_Standby_40091BI124BC Diagnostics_Purge_40091BI125BC Diagnostics_Pilot Ignition_40091BI126BC Diagnostics_Main Ignition_40091BI127BC Diagnostics_Run_40091BI128BC Diagnostics_Postpurge_40091BI129BC Diagnostics_Pre-Ignition_40091BI130BC Diagnostics_Valve Proving_40091BI131BC Diagnostics_Alarm_40091BI132BC Diagnostics_Hold_40091BI133BC Diagnostics_Lockout_40091BI134BC Diagnostics_Initiate_40092BI135BC Diagnostics_Standby_40092BI136BC Diagnostics_Purge_40092BI137BC Diagnostics_Pilot Ignition_40092BI138BC Diagnostics_Main Ignition_40092BI139BC Diagnostics_Run_40092BI140BC Diagnostics_Postpurge_40092BI141BC Diagnostics_Pre-Ignition_40092BI142BC Diagnostics_Valve Proving_40092BI143BC Diagnostics_Alarm_40092BI144BC Diagnostics_Hold_40092BI145BC Diagnostics_Lockout_40092BI146BC Diagnostics_Initiate_40093BI147BC Diagnostics_Standby_40093BI148BC Diagnostics_Purge_40093BI149BC Diagnostics_Pilot Ignition_40093BI150BC Diagnostics_Main Ignition_40093BI151BC Diagnostics_Run_40093BI152BC Diagnostics_Postpurge_40093BI153BC Diagnostics_Pre-Ignition_40093BI154BC Diagnostics_Valve Proving_40093BI155BC Diagnostics_Alarm_40093BI156BC Diagnostics_Hold_40093BI157BC Diagnostics_Lockout_40093BI158BC Diagnostics_Initiate_40094BI159BC Diagnostics_Standby_40094BI160BC Diagnostics_Purge_40094BI161BC Diagnostics_Pilot Ignition_40094BI162BC Diagnostics_Main Ignition_40094BI163BC Diagnostics_Run_40094BI164BC Diagnostics_Postpurge_40094BI165BC Diagnostics_Pre-Ignition_40094BI166BC Diagnostics_Valve Proving_40094BI167BC Diagnostics_Alarm_40094BI168BC Diagnostics_Hold_40094BI169BC Diagnostics_Lockout_40094BI170BC Diagnostics_Initiate_40095BI171BC Diagnostics_Standby_40095BI172BC Diagnostics_Purge_40095BI173BC Diagnostics_Pilot Ignition_40095BI174BC Diagnostics_Main Ignition_40095BI175BC Diagnostics_Run_40095BI176BC Diagnostics_Postpurge_40095BI177BC Diagnostics_Pre-Ignition_40095BI178BC Diagnostics_Valve Proving_40095BI179BC Diagnostics_Alarm_40095BI180BC Diagnostics_Hold_40095BI181BC Diagnostics_Lockout_40095BI182BC Diagnostics_Initiate_40096BI183BC Diagnostics_Standby_40096BI184BC Diagnostics_Purge_40096BI185BC Diagnostics_Pilot Ignition_40096BI186BC Diagnostics_Main Ignition_40096BI187BC Diagnostics_Run_40096BI188BC Diagnostics_Postpurge_40096BI189BC Diagnostics_Pre-Ignition_40096BI190BC Diagnostics_Valve Proving_40096BI191BC Diagnostics_Alarm_40096BI192BC Diagnostics_Hold_40096BI193BC Diagnostics_Lockout_40096BI194BC Diagnostics_Initiate_40097BI195BC Diagnostics_Standby_40097BI196BC Diagnostics_Purge_40097BI197BC Diagnostics_Pilot Ignition_40097BI198BC Diagnostics_Main Ignition_40097BI199BC Diagnostics_Run_40097BI200BC Diagnostics_Postpurge_40097BI201BC Diagnostics_Pre-Ignition_40097BI202BC Diagnostics_Valve Proving_40097BI203BC Diagnostics_Alarm_40097BI204BC Diagnostics_Hold_40097BI205BC Diagnostics_Lockout_40097BI206BC Diagnostics_Initiate_40098BI207BC Diagnostics_Standby_40098BI208BC Diagnostics_Purge_40098BI209BC Diagnostics_Pilot Ignition_40098BI210BC Diagnostics_Main Ignition_40098BI211BC Diagnostics_Run_40098BI212BC Diagnostics_Postpurge_40098BI213BC Diagnostics_Pre-Ignition_40098BI214BC Diagnostics_Valve Proving_40098BI215BC Diagnostics_Alarm_40098BI216BC Diagnostics_Hold_40098BI217BC Diagnostics_Lockout_40098BI218BC Diagnostics_Initiate_40099BI219BC Diagnostics_Standby_40099BI220BC Diagnostics_Purge_40099BI221BC Diagnostics_Pilot Ignition_40099BI222BC Diagnostics_Main Ignition_40099BI223BC Diagnostics_Run_40099BI224BC Diagnostics_Postpurge_40099BI225BC Diagnostics_Pre-Ignition_40099BI226BC Diagnostics_Valve Proving_40099BI227BC Diagnostics_Alarm_40099BI228BC Diagnostics_Hold_40099BI229BC Diagnostics_Lockout_40099BI230BC Diagnostics_Initiate_40100BI231BC Diagnostics_Standby_40100BI232BC Diagnostics_Purge_40100BI233BC Diagnostics_Pilot Ignition_40100BI234BC Diagnostics_Main Ignition_40100BI235BC Diagnostics_Run_40100BI236BC Diagnostics_Postpurge_40100BI237BC Diagnostics_Pre-Ignition_40100BI238BC Diagnostics_Valve Proving_40100BI239BC Diagnostics_Alarm_40100BI240BC Diagnostics_Hold_40100BI241BC Diagnostics_Lockout_40100BI242BC Diagnostics_Initiate_40101BI243BC Diagnostics_Standby_40101BI244BC Diagnostics_Purge_40101BI245BC Diagnostics_Pilot Ignition_40101BI246BC Diagnostics_Main Ignition_40101BI247BC Diagnostics_Run_40101BI248BC Diagnostics_Postpurge_40101BI249BC Diagnostics_Pre-Ignition_40101BI250BC Diagnostics_Valve Proving_40101BI251BC Diagnostics_Alarm_40101BI252BC Diagnostics_Hold_40101BI253BC Diagnostics_Lockout_40101BI254BC Diagnostics_Initiate_40102BI255BC Diagnostics_Standby_40102BI256BC Diagnostics_Purge_40102BI257BC Diagnostics_Pilot Ignition_40102BI258BC Diagnostics_Main Ignition_40102BI259BC Diagnostics_Run_40102BI260BC Diagnostics_Postpurge_40102BI261BC Diagnostics_Pre-Ignition_40102BI262BC Diagnostics_Valve Proving_40102BI263BC Diagnostics_Alarm_40102BI264BC Diagnostics_Hold_40102BI265BC Diagnostics_Lockout_40102AI266Post-Purge timeAI267Valve Proving ModeAI268Valve Proving optionAI269Valve Proving timeBI270BC Rem Com_Revert to auto operationBI271BC Rem Com_Do n0t fire-remain offBI272BC Rem Com_Go to Hi Fire during RunBI273BC Rem Com_Go to Lo Fire during RunBI274BC Rem Com_Remote resetBI275BC Rem Com_must be 0_aBI276BC Rem Com_must be 0_bBI277BC Rem Com_must be 0_cBI278BC Rem Com_Copied to the control status registerBI279Device Data Ready_RM78XXBI280Device Data Ready_EC78XXBI281S7800 Dev Compat with Current Soft Rev_RM78XXBI282S7800 Dev Compat with Current Soft Rev_EC78XXBI283S7800 Dev Compat with Legacy Soft Rev_Series 2
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Honeywell_7800SERIES_Burner_a_LX.csv; the profile maps the registers in the S7800A1142 Modbus register list (https://www.ccontrols.com/support/dp/65-0288-1-S7800A1142.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 44 of the 283 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
How many BACnet points does the Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX have?
This list has 283 BACnet objects: 71 analog inputs, 212 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Honeywell_7800SERIES_Burner_a (Honeywell_7800SERIES_Burner_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Honeywell_7800SERIES_Burner.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX?
Start with AI 3 BC Sequence State (Burner sequence state); BI 16 BC State Bits_Run (Run state); BI 12 BC State Bits_Standby (Standby); AI 9 BC Flame 1 signal strength (Flame 1 signal strength); BI 20 BC State Bits_Alarm (Alarm); BI 22 BC State Bits_Lockout (Lockout); AI 1 Burner Control (BC) Fault Code (Burner control fault code); AI 8 BC Total hours (Total burner hours).
How do I check these points on the real Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Honeywell_7800SERIES_Burner_a · Honeywell_7800SERIES_Burner_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.