- Home
- BACnet points lists
- Contemporary Controls
- GE EPM 4500 multi-point submeter via BASgatewayLX
Multi-circuit power and energy meter (submeter) · BACnet points list
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the GE EPM 4500: 481 objects (472 AI, 9 AO), 364 polled by default. Per meter point it reads total kW, kvar, kVA and PF, then kWh, kvarh and instantaneous values (three-phase meters 1-8, then single/two-phase points); unpolled outputs handle the clock, interval data selection and data-ready flag.
This page lists 481 BACnet objects for the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- GE EPM 4500 multi-point submeter via BASgatewayLX
- Equipment
- Multi-circuit power and energy meter (submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 481 (9 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- EPM 4500, EPM4500, GE Multilin EPM 4500
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
Map meter 1 total kW, meter 1 kWh and meter 1 power factor first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 36 | Meter #1 Three-Phase Total kW | Meter 1 total kW | Read |
| AI 256 | Meter #1 Three-Phase kWh | Meter 1 kWh | Read |
| AI 39 | Meter #1 Three-Phase Total Power Factor | Meter 1 power factor | Read |
| AI 40 | Meter #2 Three-Phase Total kW | Meter 2 total kW | Read |
| AI 262 | Meter #2 Three-Phase kWh | Meter 2 kWh | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Meter Serial Number | Modbus 400001; not polled by default | Read | ||
| AI | 2 | Meter Serial Number Extension | Modbus 400003; not polled by default | Read | ||
| AI | 3 | Meter Version Number | Modbus 400005; not polled by default | Read | ||
| AI | 4 | Meter Version Number Extension | Modbus 400007; not polled by default | Read | ||
| AI | 5 | Meter Modbus Address | Modbus 400009; not polled by default | Read | ||
| AI | 6 | Baud Rate | Modbus 400010; not polled by default | Read | ||
| AI | 7 | Meter Status | Modbus 400013; not polled by default | Read | ||
| AI | 8 | Meter Ready | Modbus 400014; not polled by default | Read | ||
| AI | 9 | Number of Meters Configured | Modbus 400015; not polled by default | Read | ||
| AI | 10 | Number of Real-Time Points Configured | Modbus 400016; not polled by default | Read | ||
| AI | 11 | Number of Interval Points Configured | Modbus 400017; not polled by default | Read | ||
| AI | 12 | Number of Max/Min Points Configured | Modbus 400018; not polled by default | Read | ||
| AI | 13 | Maximum Number of Intervals That Can Be Recorded | Modbus 400019; not polled by default | Read | ||
| AI | 14 | Number of slots configured for Scan Transponder | Modbus 400020; not polled by default | Read | ||
| AO | 15 | Current slot being read in Scan Transponder | Modbus 400021; not polled by default | Command | ||
| AI | 16 | Store Interval Length | Modbus 400050; not polled by default | min | Read | |
| AI | 17 | Internal Time - Hours/Minutes | Modbus 400051; not polled by default | Read | ||
| AI | 18 | Internal Time - Seconds | Modbus 400052; not polled by default | s | Read | |
| AI | 19 | Internal Date - Month/Day | Modbus 400053; not polled by default | Read | ||
| AI | 20 | Interval Date - Year | Modbus 400054; not polled by default | years | Read | |
| AO | 21 | Internal Time - Hours/Minutes | Modbus 400055; not polled by default | Command | ||
| AO | 22 | Internal Time - Seconds | Modbus 400056; not polled by default | Command | ||
| AO | 23 | Internal Date - Month/Day | Modbus 400057; not polled by default | years | Command | |
| AO | 24 | Interval Date - Year | Modbus 400058; not polled by default | Command | ||
| AI | 25 | Date/Time of Oldest Interval - Hours/Minutes | Modbus 400059; not polled by default | Read | ||
| AI | 26 | Date/Time of Oldest Interval - Month/Day | Modbus 400060; not polled by default | Read | ||
| AI | 27 | Date/Time of Oldest Interval - Year | Modbus 400061; not polled by default | Read | ||
| AI | 28 | Date/Time of Newest Interval - Hours/Minutes | Modbus 400062; not polled by default | Read | ||
| AI | 29 | Date/Time of Newest Interval - Month/Day | Modbus 400063; not polled by default | Read | ||
| AI | 30 | Date/Time of Newest Interval - Year | Modbus 400064; not polled by default | Read | ||
| AO | 31 | Date/Time of Currently Selected Interval - Hours/Minutes | Modbus 400065; not polled by default | Command | ||
| AO | 32 | Date/Time of Currently Selected Interval - Month/Day | Modbus 400066; not polled by default | Command | ||
| AO | 33 | Date/Time of Currently Selected Interval - Year | Modbus 400067; not polled by default | Command | ||
| AO | 34 | Data Ready Flag | Modbus 400068; not polled by default | Command | ||
| AI | 35 | Interval Data Qualifying Register | Modbus 400100; not polled by default | Read | ||
| AImin | 36 | Meter #1 Three-Phase Total kW | Modbus 400101 | kW | Read | |
| AI | 37 | Meter #1 Three-Phase Total kvar | Modbus 400103 | kVAR | Read | |
| AI | 38 | Meter #1 Three-Phase Total kVA | Modbus 400105 | kVA | Read | |
| AImin | 39 | Meter #1 Three-Phase Total Power Factor | Modbus 400107 | % | Read | |
| AImin | 40 | Meter #2 Three-Phase Total kW | Modbus 400109 | kW | Read | |
| AI | 41 | Meter #2 Three-Phase Total kvar | Modbus 400111 | kVAR | Read | |
| AI | 42 | Meter #2 Three-Phase Total kVA | Modbus 400113 | kVA | Read | |
| AI | 43 | Meter #2 Three-Phase Total Power Factor | Modbus 400115 | % | Read | |
| AI | 44 | Meter #3 Three-Phase Total kW | Modbus 400117 | kW | Read | |
| AI | 45 | Meter #3 Three-Phase Total kvar | Modbus 400119 | kVAR | Read | |
| AI | 46 | Meter #3 Three-Phase Total kVA | Modbus 400121 | kVA | Read | |
| AI | 47 | Meter #3 Three-Phase Total Power Factor | Modbus 400123 | % | Read | |
| AI | 48 | Meter #4 Three-Phase Total kW | Modbus 400125 | kW | Read | |
| AI | 49 | Meter #4 Three-Phase Total kvar | Modbus 400127 | kVAR | Read | |
| AI | 50 | Meter #4 Three-Phase Total kVA | Modbus 400129 | kVA | Read | |
| AI | 51 | Meter #4 Three-Phase Total Power Factor | Modbus 400131 | % | Read | |
| AI | 52 | Meter #5 Three-Phase Total kW | Modbus 400133 | kW | Read | |
| AI | 53 | Meter #5 Three-Phase Total kvar | Modbus 400135 | kVAR | Read | |
| AI | 54 | Meter #5 Three-Phase Total kVA | Modbus 400137 | kVA | Read | |
| AI | 55 | Meter #5 Three-Phase Total Power Factor | Modbus 400139 | % | Read | |
| AI | 56 | Meter #6 Three-Phase Total kW | Modbus 400141 | kW | Read | |
| AI | 57 | Meter #6 Three-Phase Total kvar | Modbus 400143 | kVAR | Read | |
| AI | 58 | Meter #6 Three-Phase Total kVA | Modbus 400145 | kVA | Read | |
| AI | 59 | Meter #6 Three-Phase Total Power Factor | Modbus 400147 | % | Read | |
| AI | 60 | Meter #7 Three-Phase Total kW | Modbus 400149 | kW | Read | |
| AI | 61 | Meter #7 Three-Phase Total kvar | Modbus 400151 | kVAR | Read | |
| AI | 62 | Meter #7 Three-Phase Total kVA | Modbus 400153 | kVA | Read | |
| AI | 63 | Meter #7 Three-Phase Total Power Factor | Modbus 400155 | % | Read | |
| AI | 64 | Meter #8 Three-Phase Total kW | Modbus 400157 | kW | Read | |
| AI | 65 | Meter #8 Three-Phase Total kvar | Modbus 400159 | kVAR | Read | |
| AI | 66 | Meter #8 Three-Phase Total kVA | Modbus 400161 | kVA | Read | |
| AI | 67 | Meter #8 Three-Phase Total Power Factor | Modbus 400163 | % | Read | |
| AI | 68 | Meter #9 Two-Phase Total kW | Modbus 400165 | kW | Read | |
| AI | 69 | Meter #9 Two-Phase Total kvar | Modbus 400167 | kVAR | Read | |
| AI | 70 | Meter #9 Two-Phase Total kVA | Modbus 400169 | kVA | Read | |
| AI | 71 | Meter #9 Two-Phase Total Power Factor | Modbus 400171 | % | Read | |
| AI | 72 | Meter #10 Two-Phase Total kW | Modbus 400173 | kW | Read | |
| AI | 73 | Meter #10 Two-Phase Total kvar | Modbus 400175 | kVAR | Read | |
| AI | 74 | Meter #10 Two-Phase Total kVA | Modbus 400177 | kVA | Read | |
| AI | 75 | Meter #10 Two-Phase Total Power Factor | Modbus 400179 | % | Read | |
| AI | 76 | Meter #11 Two-Phase Total kW | Modbus 400181 | kW | Read | |
| AI | 77 | Meter #11 Two-Phase Total kvar | Modbus 400183 | kVAR | Read | |
| AI | 78 | Meter #11 Two-Phase Total kVA | Modbus 400185 | kVA | Read | |
| AI | 79 | Meter #11 Two-Phase Total Power Factor | Modbus 400187 | % | Read | |
| AI | 80 | Meter #12 Two-Phase Total kW | Modbus 400189 | kW | Read | |
| AI | 81 | Meter #12 Two-Phase Total kvar | Modbus 400191 | kVAR | Read | |
| AI | 82 | Meter #12 Two-Phase Total kVA | Modbus 400193 | kVA | Read | |
| AI | 83 | Meter #12 Two-Phase Total Power Factor | Modbus 400195 | % | Read | |
| AI | 84 | Meter #13 Single-Phase Total kW | Modbus 400197 | kW | Read | |
| AI | 85 | Meter #13 Single-Phase Total kvar | Modbus 400199 | kVAR | Read | |
| AI | 86 | Meter #13 Single-Phase Total kVA | Modbus 400201 | kVA | Read | |
| AI | 87 | Meter #13 Single-Phase Total Power Factor | Modbus 400203 | % | Read | |
| AI | 88 | Meter #14 Single-Phase Total kW | Modbus 400205 | kW | Read | |
| AI | 89 | Meter #14 Single-Phase Total kvar | Modbus 400207 | kVAR | Read | |
| AI | 90 | Meter #14 Single-Phase Total kVA | Modbus 400209 | kVA | Read | |
| AI | 91 | Meter #14 Single-Phase Total Power Factor | Modbus 400211 | % | Read | |
| AI | 92 | Meter #15 Single-Phase Total kW | Modbus 400213 | kW | Read | |
| AI | 93 | Meter #15 Single-Phase Total kvar | Modbus 400215 | kVAR | Read | |
| AI | 94 | Meter #15 Single-Phase Total kVA | Modbus 400217 | kVA | Read | |
| AI | 95 | Meter #15 Single-Phase Total Power Factor | Modbus 400219 | % | Read | |
| AI | 96 | Meter #16 Single-Phase Total kW | Modbus 400221 | kW | Read | |
| AI | 97 | Meter #16 Single-Phase Total kvar | Modbus 400223 | kVAR | Read | |
| AI | 98 | Meter #16 Single-Phase Total kVA | Modbus 400225 | kVA | Read | |
| AI | 99 | Meter #16 Single-Phase Total Power Factor | Modbus 400227 | % | Read | |
| AI | 100 | Meter #17 Single-Phase Total kW | Modbus 400229 | kW | Read | |
| AI | 101 | Meter #17 Single-Phase Total kvar | Modbus 400231 | kVAR | Read | |
| AI | 102 | Meter #17 Single-Phase Total kVA | Modbus 400233 | kVA | Read | |
| AI | 103 | Meter #17 Single-Phase Total Power Factor | Modbus 400235 | % | Read | |
| AI | 104 | Meter #18 Single-Phase Total kW | Modbus 400237 | kW | Read | |
| AI | 105 | Meter #18 Single-Phase Total kvar | Modbus 400239 | kVAR | Read | |
| AI | 106 | Meter #18 Single-Phase Total kVA | Modbus 400241 | kVA | Read | |
| AI | 107 | Meter #18 Single-Phase Total Power Factor | Modbus 400243 | % | Read | |
| AI | 108 | Meter #19 Single-Phase Total kW | Modbus 400245 | kW | Read | |
| AI | 109 | Meter #19 Single-Phase Total kvar | Modbus 400247 | kVAR | Read | |
| AI | 110 | Meter #19 Single-Phase Total kVA | Modbus 400249 | kVA | Read | |
| AI | 111 | Meter #19 Single-Phase Total Power Factor | Modbus 400251 | % | Read | |
| AI | 112 | Meter #20 Single-Phase Total kW | Modbus 400253 | kW | Read | |
| AI | 113 | Meter #20 Single-Phase Total kvar | Modbus 400255 | kVAR | Read | |
| AI | 114 | Meter #20 Single-Phase Total kVA | Modbus 400257 | kVA | Read | |
| AI | 115 | Meter #20 Single-Phase Total Power Factor | Modbus 400259 | % | Read | |
| AI | 116 | Meter #21 Single-Phase Total kW | Modbus 400261 | kW | Read | |
| AI | 117 | Meter #21 Single-Phase Total kvar | Modbus 400263 | kVAR | Read | |
| AI | 118 | Meter #21 Single-Phase Total kVA | Modbus 400265 | kVA | Read | |
| AI | 119 | Meter #21 Single-Phase Total Power Factor | Modbus 400267 | % | Read | |
| AI | 120 | Meter #22 Single-Phase Total kW | Modbus 400269 | kW | Read | |
| AI | 121 | Meter #22 Single-Phase Total kvar | Modbus 400271 | kVAR | Read | |
| AI | 122 | Meter #22 Single-Phase Total kVA | Modbus 400273 | kVA | Read | |
| AI | 123 | Meter #22 Single-Phase Total Power Factor | Modbus 400275 | % | Read | |
| AI | 124 | Meter #23 Single-Phase Total kW | Modbus 400277 | kW | Read | |
| AI | 125 | Meter #23 Single-Phase Total kvar | Modbus 400279 | kVAR | Read | |
| AI | 126 | Meter #23 Single-Phase Total kVA | Modbus 400281 | kVA | Read | |
| AI | 127 | Meter #23 Single-Phase Total Power Factor | Modbus 400283 | % | Read | |
| AI | 128 | Meter #24 Single-Phase Total kW | Modbus 400285 | kW | Read | |
| AI | 129 | Meter #24 Single-Phase Total kvar | Modbus 400287 | kVAR | Read | |
| AI | 130 | Meter #24 Single-Phase Total kVA | Modbus 400289 | kVA | Read | |
| AI | 131 | Meter #24 Single-Phase Total Power Factor | Modbus 400291 | % | Read | |
| AI | 132 | Frequency (Phase A) | Modbus 400355 | Hz | Read | |
| AI | 133 | Voltage (A-N) | Modbus 400363 | V | Read | |
| AI | 134 | Voltage (B-N) | Modbus 400365 | V | Read | |
| AI | 135 | Voltage (C-N) | Modbus 400367 | V | Read | |
| AI | 136 | Voltage (CT01) | Modbus 400369 | V | Read | |
| AI | 137 | Amps (CT01) | Modbus 400371 | A | Read | |
| AI | 138 | kW (CT01) | Modbus 400373 | kW | Read | |
| AI | 139 | kvar (CT01) | Modbus 400375 | kVAR | Read | |
| AI | 140 | kVA (CT01) | Modbus 400377 | kVA | Read | |
| AI | 141 | Voltage (CT02) | Modbus 400379 | V | Read | |
| AI | 142 | Amps (CT02) | Modbus 400381 | A | Read | |
| AI | 143 | kW (CT02) | Modbus 400383 | kW | Read | |
| AI | 144 | kvar (CT02) | Modbus 400385 | kVAR | Read | |
| AI | 145 | kVA (CT02) | Modbus 400387 | kVA | Read | |
| AI | 146 | Voltage (CT03) | Modbus 400389 | V | Read | |
| AI | 147 | Amps (CT03) | Modbus 400391 | A | Read | |
| AI | 148 | kW (CT03) | Modbus 400393 | kW | Read | |
| AI | 149 | kvar (CT03) | Modbus 400395 | kVAR | Read | |
| AI | 150 | kVA (CT03) | Modbus 400397 | kVA | Read | |
| AI | 151 | Voltage (CT04) | Modbus 400399 | V | Read | |
| AI | 152 | Amps (CT04) | Modbus 400401 | A | Read | |
| AI | 153 | kW (CT04) | Modbus 400403 | kW | Read | |
| AI | 154 | kvar (CT04) | Modbus 400405 | kVAR | Read | |
| AI | 155 | kVA (CT04) | Modbus 400407 | kVA | Read | |
| AI | 156 | Voltage (CT05) | Modbus 400409 | V | Read | |
| AI | 157 | Amps (CT05) | Modbus 400411 | A | Read | |
| AI | 158 | kW (CT05) | Modbus 400413 | kW | Read | |
| AI | 159 | kvar (CT05) | Modbus 400415 | kVAR | Read | |
| AI | 160 | kVA (CT05) | Modbus 400417 | kVA | Read | |
| AI | 161 | Voltage (CT06) | Modbus 400419 | V | Read | |
| AI | 162 | Amps (CT06) | Modbus 400421 | A | Read | |
| AI | 163 | kW (CT06) | Modbus 400423 | kW | Read | |
| AI | 164 | kvar (CT06) | Modbus 400425 | kVAR | Read | |
| AI | 165 | kVA (CT06) | Modbus 400427 | kVA | Read | |
| AI | 166 | Voltage (CT07) | Modbus 400429 | V | Read | |
| AI | 167 | Amps (CT07) | Modbus 400431 | A | Read | |
| AI | 168 | kW (CT07) | Modbus 400433 | kW | Read | |
| AI | 169 | kvar (CT07) | Modbus 400435 | kVAR | Read | |
| AI | 170 | kVA (CT07) | Modbus 400437 | kVA | Read | |
| AI | 171 | Voltage (CT08) | Modbus 400439 | V | Read | |
| AI | 172 | Amps (CT08) | Modbus 400441 | A | Read | |
| AI | 173 | kW (CT08) | Modbus 400443 | kW | Read | |
| AI | 174 | kvar (CT08) | Modbus 400445 | kVAR | Read | |
| AI | 175 | kVA (CT08) | Modbus 400447 | kVA | Read | |
| AI | 176 | Voltage (CT09) | Modbus 400449 | V | Read | |
| AI | 177 | Amps (CT09) | Modbus 400451 | A | Read | |
| AI | 178 | kW (CT09) | Modbus 400453 | kW | Read | |
| AI | 179 | kvar (CT09) | Modbus 400455 | kVAR | Read | |
| AI | 180 | kVA (CT09) | Modbus 400457 | kVA | Read | |
| AI | 181 | Voltage (CT10) | Modbus 400459 | V | Read | |
| AI | 182 | Amps (CT10) | Modbus 400461 | A | Read | |
| AI | 183 | kW (CT10) | Modbus 400463 | kW | Read | |
| AI | 184 | kvar (CT10) | Modbus 400465 | kVAR | Read | |
| AI | 185 | kVA (CT10) | Modbus 400467 | kVA | Read | |
| AI | 186 | Voltage (CT11) | Modbus 400469 | V | Read | |
| AI | 187 | Amps (CT11) | Modbus 400471 | A | Read | |
| AI | 188 | kW (CT11) | Modbus 400473 | kW | Read | |
| AI | 189 | kvar (CT11) | Modbus 400475 | kVAR | Read | |
| AI | 190 | kVA (CT11) | Modbus 400477 | kVA | Read | |
| AI | 191 | Voltage (CT12) | Modbus 400479 | V | Read | |
| AI | 192 | Amps (CT12) | Modbus 400481 | A | Read | |
| AI | 193 | kW (CT12) | Modbus 400483 | kW | Read | |
| AI | 194 | kvar (CT12) | Modbus 400485 | kVAR | Read | |
| AI | 195 | kVA (CT12) | Modbus 400487 | kVA | Read | |
| AI | 196 | Voltage (CT13) | Modbus 400489 | V | Read | |
| AI | 197 | Amps (CT13) | Modbus 400491 | A | Read | |
| AI | 198 | kW (CT13) | Modbus 400493 | kW | Read | |
| AI | 199 | kvar (CT13) | Modbus 400495 | kVAR | Read | |
| AI | 200 | kVA (CT13) | Modbus 400497 | kVA | Read | |
| AI | 201 | Voltage (CT14) | Modbus 400499 | V | Read | |
| AI | 202 | Amps (CT14) | Modbus 400501 | A | Read | |
| AI | 203 | kW (CT14) | Modbus 400503 | kW | Read | |
| AI | 204 | kvar (CT14) | Modbus 400505 | kVAR | Read | |
| AI | 205 | kVA (CT14) | Modbus 400507 | kVA | Read | |
| AI | 206 | Voltage (CT15) | Modbus 400509 | V | Read | |
| AI | 207 | Amps (CT15) | Modbus 400511 | A | Read | |
| AI | 208 | kW (CT15) | Modbus 400513 | kW | Read | |
| AI | 209 | kvar (CT15) | Modbus 400515 | kVAR | Read | |
| AI | 210 | kVA (CT15) | Modbus 400517 | kVA | Read | |
| AI | 211 | Voltage (CT16) | Modbus 400519 | V | Read | |
| AI | 212 | Amps (CT16) | Modbus 400521 | A | Read | |
| AI | 213 | kW (CT16) | Modbus 400523 | kW | Read | |
| AI | 214 | kvar (CT16) | Modbus 400525 | kVAR | Read | |
| AI | 215 | kVA (CT16) | Modbus 400527 | kVA | Read | |
| AI | 216 | Voltage (CT17) | Modbus 400529 | V | Read | |
| AI | 217 | Amps (CT17) | Modbus 400531 | A | Read | |
| AI | 218 | kW (CT17) | Modbus 400533 | kW | Read | |
| AI | 219 | kvar (CT17) | Modbus 400535 | kVAR | Read | |
| AI | 220 | kVA (CT17) | Modbus 400537 | kVA | Read | |
| AI | 221 | Voltage (CT18) | Modbus 400539 | V | Read | |
| AI | 222 | Amps (CT18) | Modbus 400541 | A | Read | |
| AI | 223 | kW (CT18) | Modbus 400543 | kW | Read | |
| AI | 224 | kvar (CT18) | Modbus 400545 | kVAR | Read | |
| AI | 225 | kVA (CT18) | Modbus 400547 | kVA | Read | |
| AI | 226 | Voltage (CT19) | Modbus 400549 | V | Read | |
| AI | 227 | Amps (CT19) | Modbus 400551 | A | Read | |
| AI | 228 | kW (CT19) | Modbus 400553 | kW | Read | |
| AI | 229 | kvar (CT19) | Modbus 400555 | kVAR | Read | |
| AI | 230 | kVA (CT19) | Modbus 400557 | kVA | Read | |
| AI | 231 | Voltage (CT20) | Modbus 400559 | V | Read | |
| AI | 232 | Amps (CT20) | Modbus 400561 | A | Read | |
| AI | 233 | kW (CT20) | Modbus 400563 | kW | Read | |
| AI | 234 | kvar (CT20) | Modbus 400565 | kVAR | Read | |
| AI | 235 | kVA (CT20) | Modbus 400567 | kVA | Read | |
| AI | 236 | Voltage (CT21) | Modbus 400569 | V | Read | |
| AI | 237 | Amps (CT21) | Modbus 400571 | A | Read | |
| AI | 238 | kW (CT21) | Modbus 400573 | kW | Read | |
| AI | 239 | kvar (CT21) | Modbus 400575 | kVAR | Read | |
| AI | 240 | kVA (CT21) | Modbus 400577 | kVA | Read | |
| AI | 241 | Voltage (CT22) | Modbus 400579 | V | Read | |
| AI | 242 | Amps (CT22) | Modbus 400581 | A | Read | |
| AI | 243 | kW (CT22) | Modbus 400583 | kW | Read | |
| AI | 244 | kvar (CT22) | Modbus 400585 | kVAR | Read | |
| AI | 245 | kVA (CT22) | Modbus 400587 | kVA | Read | |
| AI | 246 | Voltage (CT23) | Modbus 400589 | V | Read | |
| AI | 247 | Amps (CT23) | Modbus 400591 | A | Read | |
| AI | 248 | kW (CT23) | Modbus 400593 | kW | Read | |
| AI | 249 | kvar (CT23) | Modbus 400595 | kVAR | Read | |
| AI | 250 | kVA (CT23) | Modbus 400597 | kVA | Read | |
| AI | 251 | Voltage (CT24) | Modbus 400599 | V | Read | |
| AI | 252 | Amps (CT24) | Modbus 400601 | A | Read | |
| AI | 253 | kW (CT24) | Modbus 400603 | kW | Read | |
| AI | 254 | kvar (CT24) | Modbus 400605 | kVAR | Read | |
| AI | 255 | kVA (CT24) | Modbus 400607 | kVA | Read | |
| AImin | 256 | Meter #1 Three-Phase kWh | Modbus 400649 | kWh | Read | |
| AI | 257 | Meter #1 Three-Phase kvarh | Modbus 400651 | kVARh | Read | |
| AI | 258 | Meter #1 Three-Phase kW | Modbus 400653 | kW | Read | |
| AI | 259 | Meter #1 Three-Phase kvar | Modbus 400655 | kVAR | Read | |
| AI | 260 | Meter #1 Three-Phase kVA | Modbus 400657 | kVA | Read | |
| AI | 261 | Meter #1 Three-Phase Power Factor | Modbus 400659 | PF | Read | |
| AImin | 262 | Meter #2 Three-Phase kWh | Modbus 400661 | kWh | Read | |
| AI | 263 | Meter #2 Three-Phase kvarh | Modbus 400663 | kVARh | Read | |
| AI | 264 | Meter #2 Three-Phase kW | Modbus 400665 | kW | Read | |
| AI | 265 | Meter #2 Three-Phase kvar | Modbus 400667 | kVAR | Read | |
| AI | 266 | Meter #2 Three-Phase kVA | Modbus 400669 | kVA | Read | |
| AI | 267 | Meter #2 Three-Phase Power Factor | Modbus 400671 | PF | Read | |
| AI | 268 | Meter #3 Three-Phase kWh | Modbus 400673 | kWh | Read | |
| AI | 269 | Meter #3 Three-Phase kvarh | Modbus 400675 | kVARh | Read | |
| AI | 270 | Meter #3 Three-Phase kW | Modbus 400677 | kW | Read | |
| AI | 271 | Meter #3 Three-Phase kvar | Modbus 400679 | kVAR | Read | |
| AI | 272 | Meter #3 Three-Phase kVA | Modbus 400681 | kVA | Read | |
| AI | 273 | Meter #3 Three-Phase Power Factor | Modbus 400683 | PF | Read | |
| AI | 274 | Meter #4 Three-Phase kWh | Modbus 400685 | kWh | Read | |
| AI | 275 | Meter #4 Three-Phase kvarh | Modbus 400687 | kVARh | Read | |
| AI | 276 | Meter #4 Three-Phase kW | Modbus 400689 | kW | Read | |
| AI | 277 | Meter #4 Three-Phase kvar | Modbus 400691 | kVAR | Read | |
| AI | 278 | Meter #4 Three-Phase kVA | Modbus 400693 | kVA | Read | |
| AI | 279 | Meter #4 Three-Phase Power Factor | Modbus 400695 | PF | Read | |
| AI | 280 | Meter #5 Three-Phase kWh | Modbus 400697 | kWh | Read | |
| AI | 281 | Meter #5 Three-Phase kvarh | Modbus 400699 | kVARh | Read | |
| AI | 282 | Meter #5 Three-Phase kW | Modbus 400701 | kW | Read | |
| AI | 283 | Meter #5 Three-Phase kvar | Modbus 400703 | kVAR | Read | |
| AI | 284 | Meter #5 Three-Phase kVA | Modbus 400705 | kVA | Read | |
| AI | 285 | Meter #5 Three-Phase Power Factor | Modbus 400707 | PF | Read | |
| AI | 286 | Meter #6 Three-Phase kWh | Modbus 400709 | kWh | Read | |
| AI | 287 | Meter #6 Three-Phase kvarh | Modbus 400711 | kVARh | Read | |
| AI | 288 | Meter #6 Three-Phase kW | Modbus 400713 | kW | Read | |
| AI | 289 | Meter #6 Three-Phase kvar | Modbus 400715 | kVAR | Read | |
| AI | 290 | Meter #6 Three-Phase kVA | Modbus 400717 | kVA | Read | |
| AI | 291 | Meter #6 Three-Phase Power Factor | Modbus 400719 | PF | Read | |
| AI | 292 | Meter #7 Three-Phase kWh | Modbus 400721 | kWh | Read | |
| AI | 293 | Meter #7 Three-Phase kvarh | Modbus 400723 | kVARh | Read | |
| AI | 294 | Meter #7 Three-Phase kW | Modbus 400725 | kW | Read | |
| AI | 295 | Meter #7 Three-Phase kvar | Modbus 400727 | kVAR | Read | |
| AI | 296 | Meter #7 Three-Phase kVA | Modbus 400729 | kVA | Read | |
| AI | 297 | Meter #7 Three-Phase Power Factor | Modbus 400731 | PF | Read | |
| AI | 298 | Meter #8 Three-Phase kWh | Modbus 400733 | kWh | Read | |
| AI | 299 | Meter #8 Three-Phase kvarh | Modbus 400735 | kVARh | Read | |
| AI | 300 | Meter #8 Three-Phase kW | Modbus 400737 | kW | Read | |
| AI | 301 | Meter #8 Three-Phase kvar | Modbus 400739 | kVAR | Read | |
| AI | 302 | Meter #8 Three-Phase kVA | Modbus 400741 | kVA | Read | |
| AI | 303 | Meter #8 Three-Phase Power Factor | Modbus 400743 | PF | Read | |
| AI | 304 | Meter #9 Phase kWh | Modbus 400745 | kWh | Read | |
| AI | 305 | Meter #9 Phase kvarh | Modbus 400747 | kVARh | Read | |
| AI | 306 | Meter #9 Phase kW | Modbus 400749 | kW | Read | |
| AI | 307 | Meter #9 Phase kvar | Modbus 400751 | kVAR | Read | |
| AI | 308 | Meter #9 Phase kVA | Modbus 400753 | kVA | Read | |
| AI | 309 | Meter #9 Phase Power Factor | Modbus 400755 | PF | Read | |
| AI | 310 | Meter #10 Phase kWh | Modbus 400757 | kWh | Read | |
| AI | 311 | Meter #10 Phase kvarh | Modbus 400759 | kVARh | Read | |
| AI | 312 | Meter #10 Phase kW | Modbus 400761 | kW | Read | |
| AI | 313 | Meter #10 Phase kvar | Modbus 400763 | kVAR | Read | |
| AI | 314 | Meter #10 Phase kVA | Modbus 400765 | kVA | Read | |
| AI | 315 | Meter #10 Phase Power Factor | Modbus 400767 | PF | Read | |
| AI | 316 | Meter #11 Phase kWh | Modbus 400769 | kWh | Read | |
| AI | 317 | Meter #11 Phase kvarh | Modbus 400771 | kVARh | Read | |
| AI | 318 | Meter #11 Phase kW | Modbus 400773 | kW | Read | |
| AI | 319 | Meter #11 Phase kvar | Modbus 400775 | kVAR | Read | |
| AI | 320 | Meter #11 Phase kVA | Modbus 400777 | kVA | Read | |
| AI | 321 | Meter #11 Phase Power Factor | Modbus 400779 | PF | Read | |
| AI | 322 | Meter #12 Phase kWh | Modbus 400781 | kWh | Read | |
| AI | 323 | Meter #12 Phase kvarh | Modbus 400783 | kVARh | Read | |
| AI | 324 | Meter #12 Phase kW | Modbus 400785 | kW | Read | |
| AI | 325 | Meter #12 Phase kvar | Modbus 400787 | kVAR | Read | |
| AI | 326 | Meter #12 Phase kVA | Modbus 400789 | kVA | Read | |
| AI | 327 | Meter #12 Phase Power Factor | Modbus 400791 | PF | Read | |
| AI | 328 | Meter #13 Phase kWh | Modbus 400793 | kWh | Read | |
| AI | 329 | Meter #13 Phase kvarh | Modbus 400795 | kVARh | Read | |
| AI | 330 | Meter #13 Phase kW | Modbus 400797 | kW | Read | |
| AI | 331 | Meter #13 Phase kvar | Modbus 400799 | kVAR | Read | |
| AI | 332 | Meter #13 Phase kVA | Modbus 400801 | kVA | Read | |
| AI | 333 | Meter #13 Phase Power Factor | Modbus 400803 | PF | Read | |
| AI | 334 | Meter #14 Phase kWh | Modbus 400805 | kWh | Read | |
| AI | 335 | Meter #14 Phase kvarh | Modbus 400807 | kVARh | Read | |
| AI | 336 | Meter #14 Phase kW | Modbus 400809 | kW | Read | |
| AI | 337 | Meter #14 Phase kvar | Modbus 400811 | kVAR | Read | |
| AI | 338 | Meter #14 Phase kVA | Modbus 400813 | kVA | Read | |
| AI | 339 | Meter #14 Phase Power Factor | Modbus 400815 | PF | Read | |
| AI | 340 | Meter #15 Phase kWh | Modbus 400817 | kWh | Read | |
| AI | 341 | Meter #15 Phase kvarh | Modbus 400819 | kVARh | Read | |
| AI | 342 | Meter #15 Phase kW | Modbus 400821 | kW | Read | |
| AI | 343 | Meter #15 Phase kvar | Modbus 400823 | kVAR | Read | |
| AI | 344 | Meter #15 Phase kVA | Modbus 400825 | kVA | Read | |
| AI | 345 | Meter #15 Phase Power Factor | Modbus 400827 | PF | Read | |
| AI | 346 | Meter #16 Phase kWh | Modbus 400829 | kWh | Read | |
| AI | 347 | Meter #16 Phase kvarh | Modbus 400831 | kVARh | Read | |
| AI | 348 | Meter #16 Phase kW | Modbus 400833 | kW | Read | |
| AI | 349 | Meter #16 Phase kvar | Modbus 400835 | kVAR | Read | |
| AI | 350 | Meter #16 Phase kVA | Modbus 400837 | kVA | Read | |
| AI | 351 | Meter #16 Phase Power Factor | Modbus 400839 | PF | Read | |
| AI | 352 | Meter #17 Phase kWh | Modbus 400841 | kWh | Read | |
| AI | 353 | Meter #17 Phase kvarh | Modbus 400843 | kVARh | Read | |
| AI | 354 | Meter #17 Phase kW | Modbus 400845 | kW | Read | |
| AI | 355 | Meter #17 Phase kvar | Modbus 400847 | kVAR | Read | |
| AI | 356 | Meter #17 Phase kVA | Modbus 400849 | kVA | Read | |
| AI | 357 | Meter #17 Phase Power Factor | Modbus 400851 | PF | Read | |
| AI | 358 | Meter #18 Phase kWh | Modbus 400853 | kWh | Read | |
| AI | 359 | Meter #18 Phase kvarh | Modbus 400855 | kVARh | Read | |
| AI | 360 | Meter #18 Phase kW | Modbus 400857 | kW | Read | |
| AI | 361 | Meter #18 Phase kvar | Modbus 400859 | kVAR | Read | |
| AI | 362 | Meter #18 Phase kVA | Modbus 400861 | kVA | Read | |
| AI | 363 | Meter #18 Phase Power Factor | Modbus 400863 | PF | Read | |
| AI | 364 | Meter #19 Phase kWh | Modbus 400865 | kWh | Read | |
| AI | 365 | Meter #19 Phase kvarh | Modbus 400867 | kVARh | Read | |
| AI | 366 | Meter #19 Phase kW | Modbus 400869 | kW | Read | |
| AI | 367 | Meter #19 Phase kvar | Modbus 400871 | kVAR | Read | |
| AI | 368 | Meter #19 Phase kVA | Modbus 400873 | kVA | Read | |
| AI | 369 | Meter #19 Phase Power Factor | Modbus 400875 | PF | Read | |
| AI | 370 | Meter #20 Phase kWh | Modbus 400877 | kWh | Read | |
| AI | 371 | Meter #20 Phase kvarh | Modbus 400879 | kVARh | Read | |
| AI | 372 | Meter #20 Phase kW | Modbus 400881 | kW | Read | |
| AI | 373 | Meter #20 Phase kvar | Modbus 400883 | kVAR | Read | |
| AI | 374 | Meter #20 Phase kVA | Modbus 400885 | kVA | Read | |
| AI | 375 | Meter #20 Phase Power Factor | Modbus 400887 | PF | Read | |
| AI | 376 | Meter #21 Phase kWh | Modbus 400889 | kWh | Read | |
| AI | 377 | Meter #21 Phase kvarh | Modbus 400891 | kVARh | Read | |
| AI | 378 | Meter #21 Phase kW | Modbus 400893 | kW | Read | |
| AI | 379 | Meter #21 Phase kvar | Modbus 400895 | kVAR | Read | |
| AI | 380 | Meter #21 Phase kVA | Modbus 400897 | kVA | Read | |
| AI | 381 | Meter #21 Phase Power Factor | Modbus 400899 | PF | Read | |
| AI | 382 | Meter #22 Phase kWh | Modbus 400901 | kWh | Read | |
| AI | 383 | Meter #22 Phase kvarh | Modbus 400903 | kVARh | Read | |
| AI | 384 | Meter #22 Phase kW | Modbus 400905 | kW | Read | |
| AI | 385 | Meter #22 Phase kvar | Modbus 400907 | kVAR | Read | |
| AI | 386 | Meter #22 Phase kVA | Modbus 400909 | kVA | Read | |
| AI | 387 | Meter #22 Phase Power Factor | Modbus 400911 | PF | Read | |
| AI | 388 | Meter #23 Phase kWh | Modbus 400913 | kWh | Read | |
| AI | 389 | Meter #23 Phase kvarh | Modbus 400915 | kVARh | Read | |
| AI | 390 | Meter #23 Phase kW | Modbus 400917 | kW | Read | |
| AI | 391 | Meter #23 Phase kvar | Modbus 400919 | kVAR | Read | |
| AI | 392 | Meter #23 Phase kVA | Modbus 400921 | kVA | Read | |
| AI | 393 | Meter #23 Phase Power Factor | Modbus 400923 | PF | Read | |
| AI | 394 | Meter #24 Phase kWh | Modbus 400925 | kWh | Read | |
| AI | 395 | Meter #24 Phase kvarh | Modbus 400927 | kVARh | Read | |
| AI | 396 | Meter #24 Phase kW | Modbus 400929 | kW | Read | |
| AI | 397 | Meter #24 Phase kvar | Modbus 400931 | kVAR | Read | |
| AI | 398 | Meter #24 Phase kVA | Modbus 400933 | kVA | Read | |
| AI | 399 | Meter #24 Phase Power Factor | Modbus 400935 | PF | Read | |
| AI | 400 | Meter #1 THD Phase A | Modbus 401001; not polled by default | % | Read | |
| AI | 401 | Meter #1 Phase Angle A | Modbus 401003; not polled by default | ° (phase) | Read | |
| AI | 402 | Meter #1 Phase-to-Phase Voltage A | Modbus 401005; not polled by default | V | Read | |
| AI | 403 | Meter #1 THD Phase B | Modbus 401007; not polled by default | % | Read | |
| AI | 404 | Meter #1 Phase Angle B | Modbus 401009; not polled by default | ° (phase) | Read | |
| AI | 405 | Meter #1 Phase-to-Phase Voltage B | Modbus 401011; not polled by default | V | Read | |
| AI | 406 | Meter #1 THD Phase C | Modbus 401013; not polled by default | % | Read | |
| AI | 407 | Meter #1 Phase Angle C | Modbus 401015; not polled by default | ° (phase) | Read | |
| AI | 408 | Meter #1 Phase-to-Phase Voltage C | Modbus 401017; not polled by default | V | Read | |
| AI | 409 | Meter #2 THD Phase A | Modbus 401019; not polled by default | % | Read | |
| AI | 410 | Meter #2 Phase Angle A | Modbus 401021; not polled by default | ° (phase) | Read | |
| AI | 411 | Meter #2 Phase-to-Phase Voltage A | Modbus 401023; not polled by default | V | Read | |
| AI | 412 | Meter #2 THD Phase B | Modbus 401025; not polled by default | % | Read | |
| AI | 413 | Meter #2 Phase Angle B | Modbus 401027; not polled by default | ° (phase) | Read | |
| AI | 414 | Meter #2 Phase-to-Phase Voltage B | Modbus 401029; not polled by default | V | Read | |
| AI | 415 | Meter #2 THD Phase C | Modbus 401031; not polled by default | % | Read | |
| AI | 416 | Meter #2 Phase Angle C | Modbus 401033; not polled by default | ° (phase) | Read | |
| AI | 417 | Meter #2 Phase-to-Phase Voltage C | Modbus 401035; not polled by default | V | Read | |
| AI | 418 | Meter #3 THD Phase A | Modbus 401037; not polled by default | % | Read | |
| AI | 419 | Meter #3 Phase Angle A | Modbus 401039; not polled by default | ° (phase) | Read | |
| AI | 420 | Meter #3 Phase-to-Phase Voltage A | Modbus 401041; not polled by default | V | Read | |
| AI | 421 | Meter #3 THD Phase B | Modbus 401043; not polled by default | % | Read | |
| AI | 422 | Meter #3 Phase Angle B | Modbus 401045; not polled by default | ° (phase) | Read | |
| AI | 423 | Meter #3 Phase-to-Phase Voltage B | Modbus 401047; not polled by default | V | Read | |
| AI | 424 | Meter #3 THD Phase C | Modbus 401049; not polled by default | % | Read | |
| AI | 425 | Meter #3 Phase Angle C | Modbus 401051; not polled by default | ° (phase) | Read | |
| AI | 426 | Meter #3 Phase-to-Phase Voltage C | Modbus 401053; not polled by default | V | Read | |
| AI | 427 | Meter #4 THD Phase A | Modbus 401055; not polled by default | % | Read | |
| AI | 428 | Meter #4 Phase Angle A | Modbus 401057; not polled by default | ° (phase) | Read | |
| AI | 429 | Meter #4 Phase-to-Phase Voltage A | Modbus 401059; not polled by default | V | Read | |
| AI | 430 | Meter #4 THD Phase B | Modbus 401061; not polled by default | % | Read | |
| AI | 431 | Meter #4 Phase Angle B | Modbus 401063; not polled by default | ° (phase) | Read | |
| AI | 432 | Meter #4 Phase-to-Phase Voltage B | Modbus 401065; not polled by default | V | Read | |
| AI | 433 | Meter #4 THD Phase C | Modbus 401067; not polled by default | % | Read | |
| AI | 434 | Meter #4 Phase Angle C | Modbus 401069; not polled by default | ° (phase) | Read | |
| AI | 435 | Meter #4 Phase-to-Phase Voltage C | Modbus 401071; not polled by default | V | Read | |
| AI | 436 | Meter #5 THD Phase A | Modbus 401073; not polled by default | % | Read | |
| AI | 437 | Meter #5 Phase Angle A | Modbus 401075; not polled by default | ° (phase) | Read | |
| AI | 438 | Meter #5 Phase-to-Phase Voltage A | Modbus 401077; not polled by default | V | Read | |
| AI | 439 | Meter #5 THD Phase B | Modbus 401079; not polled by default | % | Read | |
| AI | 440 | Meter #5 Phase Angle B | Modbus 401081; not polled by default | ° (phase) | Read | |
| AI | 441 | Meter #5 Phase-to-Phase Voltage B | Modbus 401083; not polled by default | V | Read | |
| AI | 442 | Meter #5 THD Phase C | Modbus 401085; not polled by default | % | Read | |
| AI | 443 | Meter #5 Phase Angle C | Modbus 401087; not polled by default | ° (phase) | Read | |
| AI | 444 | Meter #5 Phase-to-Phase Voltage C | Modbus 401089; not polled by default | V | Read | |
| AI | 445 | Meter #6 THD Phase A | Modbus 401091; not polled by default | % | Read | |
| AI | 446 | Meter #6 Phase Angle A | Modbus 401093; not polled by default | ° (phase) | Read | |
| AI | 447 | Meter #6 Phase-to-Phase Voltage A | Modbus 401095; not polled by default | V | Read | |
| AI | 448 | Meter #6 THD Phase B | Modbus 401097; not polled by default | % | Read | |
| AI | 449 | Meter #6 Phase Angle B | Modbus 401099; not polled by default | ° (phase) | Read | |
| AI | 450 | Meter #6 Phase-to-Phase Voltage B | Modbus 401101; not polled by default | V | Read | |
| AI | 451 | Meter #6 THD Phase C | Modbus 401103; not polled by default | % | Read | |
| AI | 452 | Meter #6 Phase Angle C | Modbus 401105; not polled by default | ° (phase) | Read | |
| AI | 453 | Meter #6 Phase-to-Phase Voltage C | Modbus 401107; not polled by default | V | Read | |
| AI | 454 | Meter #7 THD Phase A | Modbus 401109; not polled by default | % | Read | |
| AI | 455 | Meter #7 Phase Angle A | Modbus 401111; not polled by default | ° (phase) | Read | |
| AI | 456 | Meter #7 Phase-to-Phase Voltage A | Modbus 401113; not polled by default | V | Read | |
| AI | 457 | Meter #7 THD Phase B | Modbus 401115; not polled by default | % | Read | |
| AI | 458 | Meter #7 Phase Angle B | Modbus 401117; not polled by default | ° (phase) | Read | |
| AI | 459 | Meter #7 Phase-to-Phase Voltage B | Modbus 401119; not polled by default | V | Read | |
| AI | 460 | Meter #7 THD Phase C | Modbus 401121; not polled by default | % | Read | |
| AI | 461 | Meter #7 Phase Angle C | Modbus 401123; not polled by default | ° (phase) | Read | |
| AI | 462 | Meter #7 Phase-to-Phase Voltage C | Modbus 401125; not polled by default | V | Read | |
| AI | 463 | Meter #8 THD Phase A | Modbus 401127; not polled by default | % | Read | |
| AI | 464 | Meter #8 Phase Angle A | Modbus 401129; not polled by default | ° (phase) | Read | |
| AI | 465 | Meter #8 Phase-to-Phase Voltage A | Modbus 401131; not polled by default | V | Read | |
| AI | 466 | Meter #8 THD Phase B | Modbus 401133; not polled by default | % | Read | |
| AI | 467 | Meter #8 Phase Angle B | Modbus 401135; not polled by default | ° (phase) | Read | |
| AI | 468 | Meter #8 Phase-to-Phase Voltage B | Modbus 401137; not polled by default | V | Read | |
| AI | 469 | Meter #8 THD Phase C | Modbus 401139; not polled by default | % | Read | |
| AI | 470 | Meter #8 Phase Angle C | Modbus 401141; not polled by default | ° (phase) | Read | |
| AI | 471 | Meter #8 Phase-to-Phase Voltage C | Modbus 401143; not polled by default | V | Read | |
| AI | 472 | Number of phases offset | Modbus 402001; not polled by default | Read | ||
| AI | 473 | Demand Window Offset | Modbus 402002; not polled by default | Read | ||
| AI | 474 | I Multiplier Type Offset | Modbus 402003; not polled by default | Read | ||
| AI | 475 | Number of Pulse Counters Offset | Modbus 402004; not polled by default | Read | ||
| AI | 476 | Overlap Offset | Modbus 402005; not polled by default | Read | ||
| AI | 477 | Number TOU's Offset | Modbus 402006; not polled by default | Read | ||
| AI | 478 | MDT_M_TABLE_REG_START | Modbus 402007; not polled by default | Read | ||
| AI | 479 | NUM_MDT_M_TABLE_COLUMNS | Modbus 402008; not polled by default | Read | ||
| AI | 480 | NUM_MDT_M_TABLE_REGS | Modbus 402009; not polled by default | Read | ||
| AI | 481 | MDT_M_TABLE_REG_END | Modbus 402010; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX GE EPM 4500 point IDs by name
AI1Meter Serial NumberAI2Meter Serial Number ExtensionAI3Meter Version NumberAI4Meter Version Number ExtensionAI5Meter Modbus AddressAI6Baud RateAI7Meter StatusAI8Meter ReadyAI9Number of Meters ConfiguredAI10Number of Real-Time Points ConfiguredAI11Number of Interval Points ConfiguredAI12Number of Max/Min Points ConfiguredAI13Maximum Number of Intervals That Can Be RecordedAI14Number of slots configured for Scan TransponderAO15Current slot being read in Scan TransponderAI16Store Interval LengthAI17Internal Time - Hours/MinutesAI18Internal Time - SecondsAI19Internal Date - Month/DayAI20Interval Date - YearAO21Internal Time - Hours/MinutesAO22Internal Time - SecondsAO23Internal Date - Month/DayAO24Interval Date - YearAI25Date/Time of Oldest Interval - Hours/MinutesAI26Date/Time of Oldest Interval - Month/DayAI27Date/Time of Oldest Interval - YearAI28Date/Time of Newest Interval - Hours/MinutesAI29Date/Time of Newest Interval - Month/DayAI30Date/Time of Newest Interval - YearAO31Date/Time of Currently Selected Interval - Hours/MinutesAO32Date/Time of Currently Selected Interval - Month/DayAO33Date/Time of Currently Selected Interval - YearAO34Data Ready FlagAI35Interval Data Qualifying RegisterAI36Meter #1 Three-Phase Total kWAI37Meter #1 Three-Phase Total kvarAI38Meter #1 Three-Phase Total kVAAI39Meter #1 Three-Phase Total Power FactorAI40Meter #2 Three-Phase Total kWAI41Meter #2 Three-Phase Total kvarAI42Meter #2 Three-Phase Total kVAAI43Meter #2 Three-Phase Total Power FactorAI44Meter #3 Three-Phase Total kWAI45Meter #3 Three-Phase Total kvarAI46Meter #3 Three-Phase Total kVAAI47Meter #3 Three-Phase Total Power FactorAI48Meter #4 Three-Phase Total kWAI49Meter #4 Three-Phase Total kvarAI50Meter #4 Three-Phase Total kVAAI51Meter #4 Three-Phase Total Power FactorAI52Meter #5 Three-Phase Total kWAI53Meter #5 Three-Phase Total kvarAI54Meter #5 Three-Phase Total kVAAI55Meter #5 Three-Phase Total Power FactorAI56Meter #6 Three-Phase Total kWAI57Meter #6 Three-Phase Total kvarAI58Meter #6 Three-Phase Total kVAAI59Meter #6 Three-Phase Total Power FactorAI60Meter #7 Three-Phase Total kWAI61Meter #7 Three-Phase Total kvarAI62Meter #7 Three-Phase Total kVAAI63Meter #7 Three-Phase Total Power FactorAI64Meter #8 Three-Phase Total kWAI65Meter #8 Three-Phase Total kvarAI66Meter #8 Three-Phase Total kVAAI67Meter #8 Three-Phase Total Power FactorAI68Meter #9 Two-Phase Total kWAI69Meter #9 Two-Phase Total kvarAI70Meter #9 Two-Phase Total kVAAI71Meter #9 Two-Phase Total Power FactorAI72Meter #10 Two-Phase Total kWAI73Meter #10 Two-Phase Total kvarAI74Meter #10 Two-Phase Total kVAAI75Meter #10 Two-Phase Total Power FactorAI76Meter #11 Two-Phase Total kWAI77Meter #11 Two-Phase Total kvarAI78Meter #11 Two-Phase Total kVAAI79Meter #11 Two-Phase Total Power FactorAI80Meter #12 Two-Phase Total kWAI81Meter #12 Two-Phase Total kvarAI82Meter #12 Two-Phase Total kVAAI83Meter #12 Two-Phase Total Power FactorAI84Meter #13 Single-Phase Total kWAI85Meter #13 Single-Phase Total kvarAI86Meter #13 Single-Phase Total kVAAI87Meter #13 Single-Phase Total Power FactorAI88Meter #14 Single-Phase Total kWAI89Meter #14 Single-Phase Total kvarAI90Meter #14 Single-Phase Total kVAAI91Meter #14 Single-Phase Total Power FactorAI92Meter #15 Single-Phase Total kWAI93Meter #15 Single-Phase Total kvarAI94Meter #15 Single-Phase Total kVAAI95Meter #15 Single-Phase Total Power FactorAI96Meter #16 Single-Phase Total kWAI97Meter #16 Single-Phase Total kvarAI98Meter #16 Single-Phase Total kVAAI99Meter #16 Single-Phase Total Power FactorAI100Meter #17 Single-Phase Total kWAI101Meter #17 Single-Phase Total kvarAI102Meter #17 Single-Phase Total kVAAI103Meter #17 Single-Phase Total Power FactorAI104Meter #18 Single-Phase Total kWAI105Meter #18 Single-Phase Total kvarAI106Meter #18 Single-Phase Total kVAAI107Meter #18 Single-Phase Total Power FactorAI108Meter #19 Single-Phase Total kWAI109Meter #19 Single-Phase Total kvarAI110Meter #19 Single-Phase Total kVAAI111Meter #19 Single-Phase Total Power FactorAI112Meter #20 Single-Phase Total kWAI113Meter #20 Single-Phase Total kvarAI114Meter #20 Single-Phase Total kVAAI115Meter #20 Single-Phase Total Power FactorAI116Meter #21 Single-Phase Total kWAI117Meter #21 Single-Phase Total kvarAI118Meter #21 Single-Phase Total kVAAI119Meter #21 Single-Phase Total Power FactorAI120Meter #22 Single-Phase Total kWAI121Meter #22 Single-Phase Total kvarAI122Meter #22 Single-Phase Total kVAAI123Meter #22 Single-Phase Total Power FactorAI124Meter #23 Single-Phase Total kWAI125Meter #23 Single-Phase Total kvarAI126Meter #23 Single-Phase Total kVAAI127Meter #23 Single-Phase Total Power FactorAI128Meter #24 Single-Phase Total kWAI129Meter #24 Single-Phase Total kvarAI130Meter #24 Single-Phase Total kVAAI131Meter #24 Single-Phase Total Power FactorAI132Frequency (Phase A)AI133Voltage (A-N)AI134Voltage (B-N)AI135Voltage (C-N)AI136Voltage (CT01)AI137Amps (CT01)AI138kW (CT01)AI139kvar (CT01)AI140kVA (CT01)AI141Voltage (CT02)AI142Amps (CT02)AI143kW (CT02)AI144kvar (CT02)AI145kVA (CT02)AI146Voltage (CT03)AI147Amps (CT03)AI148kW (CT03)AI149kvar (CT03)AI150kVA (CT03)AI151Voltage (CT04)AI152Amps (CT04)AI153kW (CT04)AI154kvar (CT04)AI155kVA (CT04)AI156Voltage (CT05)AI157Amps (CT05)AI158kW (CT05)AI159kvar (CT05)AI160kVA (CT05)AI161Voltage (CT06)AI162Amps (CT06)AI163kW (CT06)AI164kvar (CT06)AI165kVA (CT06)AI166Voltage (CT07)AI167Amps (CT07)AI168kW (CT07)AI169kvar (CT07)AI170kVA (CT07)AI171Voltage (CT08)AI172Amps (CT08)AI173kW (CT08)AI174kvar (CT08)AI175kVA (CT08)AI176Voltage (CT09)AI177Amps (CT09)AI178kW (CT09)AI179kvar (CT09)AI180kVA (CT09)AI181Voltage (CT10)AI182Amps (CT10)AI183kW (CT10)AI184kvar (CT10)AI185kVA (CT10)AI186Voltage (CT11)AI187Amps (CT11)AI188kW (CT11)AI189kvar (CT11)AI190kVA (CT11)AI191Voltage (CT12)AI192Amps (CT12)AI193kW (CT12)AI194kvar (CT12)AI195kVA (CT12)AI196Voltage (CT13)AI197Amps (CT13)AI198kW (CT13)AI199kvar (CT13)AI200kVA (CT13)AI201Voltage (CT14)AI202Amps (CT14)AI203kW (CT14)AI204kvar (CT14)AI205kVA (CT14)AI206Voltage (CT15)AI207Amps (CT15)AI208kW (CT15)AI209kvar (CT15)AI210kVA (CT15)AI211Voltage (CT16)AI212Amps (CT16)AI213kW (CT16)AI214kvar (CT16)AI215kVA (CT16)AI216Voltage (CT17)AI217Amps (CT17)AI218kW (CT17)AI219kvar (CT17)AI220kVA (CT17)AI221Voltage (CT18)AI222Amps (CT18)AI223kW (CT18)AI224kvar (CT18)AI225kVA (CT18)AI226Voltage (CT19)AI227Amps (CT19)AI228kW (CT19)AI229kvar (CT19)AI230kVA (CT19)AI231Voltage (CT20)AI232Amps (CT20)AI233kW (CT20)AI234kvar (CT20)AI235kVA (CT20)AI236Voltage (CT21)AI237Amps (CT21)AI238kW (CT21)AI239kvar (CT21)AI240kVA (CT21)AI241Voltage (CT22)AI242Amps (CT22)AI243kW (CT22)AI244kvar (CT22)AI245kVA (CT22)AI246Voltage (CT23)AI247Amps (CT23)AI248kW (CT23)AI249kvar (CT23)AI250kVA (CT23)AI251Voltage (CT24)AI252Amps (CT24)AI253kW (CT24)AI254kvar (CT24)AI255kVA (CT24)AI256Meter #1 Three-Phase kWhAI257Meter #1 Three-Phase kvarhAI258Meter #1 Three-Phase kWAI259Meter #1 Three-Phase kvarAI260Meter #1 Three-Phase kVAAI261Meter #1 Three-Phase Power FactorAI262Meter #2 Three-Phase kWhAI263Meter #2 Three-Phase kvarhAI264Meter #2 Three-Phase kWAI265Meter #2 Three-Phase kvarAI266Meter #2 Three-Phase kVAAI267Meter #2 Three-Phase Power FactorAI268Meter #3 Three-Phase kWhAI269Meter #3 Three-Phase kvarhAI270Meter #3 Three-Phase kWAI271Meter #3 Three-Phase kvarAI272Meter #3 Three-Phase kVAAI273Meter #3 Three-Phase Power FactorAI274Meter #4 Three-Phase kWhAI275Meter #4 Three-Phase kvarhAI276Meter #4 Three-Phase kWAI277Meter #4 Three-Phase kvarAI278Meter #4 Three-Phase kVAAI279Meter #4 Three-Phase Power FactorAI280Meter #5 Three-Phase kWhAI281Meter #5 Three-Phase kvarhAI282Meter #5 Three-Phase kWAI283Meter #5 Three-Phase kvarAI284Meter #5 Three-Phase kVAAI285Meter #5 Three-Phase Power FactorAI286Meter #6 Three-Phase kWhAI287Meter #6 Three-Phase kvarhAI288Meter #6 Three-Phase kWAI289Meter #6 Three-Phase kvarAI290Meter #6 Three-Phase kVAAI291Meter #6 Three-Phase Power FactorAI292Meter #7 Three-Phase kWhAI293Meter #7 Three-Phase kvarhAI294Meter #7 Three-Phase kWAI295Meter #7 Three-Phase kvarAI296Meter #7 Three-Phase kVAAI297Meter #7 Three-Phase Power FactorAI298Meter #8 Three-Phase kWhAI299Meter #8 Three-Phase kvarhAI300Meter #8 Three-Phase kWAI301Meter #8 Three-Phase kvarAI302Meter #8 Three-Phase kVAAI303Meter #8 Three-Phase Power FactorAI304Meter #9 Phase kWhAI305Meter #9 Phase kvarhAI306Meter #9 Phase kWAI307Meter #9 Phase kvarAI308Meter #9 Phase kVAAI309Meter #9 Phase Power FactorAI310Meter #10 Phase kWhAI311Meter #10 Phase kvarhAI312Meter #10 Phase kWAI313Meter #10 Phase kvarAI314Meter #10 Phase kVAAI315Meter #10 Phase Power FactorAI316Meter #11 Phase kWhAI317Meter #11 Phase kvarhAI318Meter #11 Phase kWAI319Meter #11 Phase kvarAI320Meter #11 Phase kVAAI321Meter #11 Phase Power FactorAI322Meter #12 Phase kWhAI323Meter #12 Phase kvarhAI324Meter #12 Phase kWAI325Meter #12 Phase kvarAI326Meter #12 Phase kVAAI327Meter #12 Phase Power FactorAI328Meter #13 Phase kWhAI329Meter #13 Phase kvarhAI330Meter #13 Phase kWAI331Meter #13 Phase kvarAI332Meter #13 Phase kVAAI333Meter #13 Phase Power FactorAI334Meter #14 Phase kWhAI335Meter #14 Phase kvarhAI336Meter #14 Phase kWAI337Meter #14 Phase kvarAI338Meter #14 Phase kVAAI339Meter #14 Phase Power FactorAI340Meter #15 Phase kWhAI341Meter #15 Phase kvarhAI342Meter #15 Phase kWAI343Meter #15 Phase kvarAI344Meter #15 Phase kVAAI345Meter #15 Phase Power FactorAI346Meter #16 Phase kWhAI347Meter #16 Phase kvarhAI348Meter #16 Phase kWAI349Meter #16 Phase kvarAI350Meter #16 Phase kVAAI351Meter #16 Phase Power FactorAI352Meter #17 Phase kWhAI353Meter #17 Phase kvarhAI354Meter #17 Phase kWAI355Meter #17 Phase kvarAI356Meter #17 Phase kVAAI357Meter #17 Phase Power FactorAI358Meter #18 Phase kWhAI359Meter #18 Phase kvarhAI360Meter #18 Phase kWAI361Meter #18 Phase kvarAI362Meter #18 Phase kVAAI363Meter #18 Phase Power FactorAI364Meter #19 Phase kWhAI365Meter #19 Phase kvarhAI366Meter #19 Phase kWAI367Meter #19 Phase kvarAI368Meter #19 Phase kVAAI369Meter #19 Phase Power FactorAI370Meter #20 Phase kWhAI371Meter #20 Phase kvarhAI372Meter #20 Phase kWAI373Meter #20 Phase kvarAI374Meter #20 Phase kVAAI375Meter #20 Phase Power FactorAI376Meter #21 Phase kWhAI377Meter #21 Phase kvarhAI378Meter #21 Phase kWAI379Meter #21 Phase kvarAI380Meter #21 Phase kVAAI381Meter #21 Phase Power FactorAI382Meter #22 Phase kWhAI383Meter #22 Phase kvarhAI384Meter #22 Phase kWAI385Meter #22 Phase kvarAI386Meter #22 Phase kVAAI387Meter #22 Phase Power FactorAI388Meter #23 Phase kWhAI389Meter #23 Phase kvarhAI390Meter #23 Phase kWAI391Meter #23 Phase kvarAI392Meter #23 Phase kVAAI393Meter #23 Phase Power FactorAI394Meter #24 Phase kWhAI395Meter #24 Phase kvarhAI396Meter #24 Phase kWAI397Meter #24 Phase kvarAI398Meter #24 Phase kVAAI399Meter #24 Phase Power FactorAI400Meter #1 THD Phase AAI401Meter #1 Phase Angle AAI402Meter #1 Phase-to-Phase Voltage AAI403Meter #1 THD Phase BAI404Meter #1 Phase Angle BAI405Meter #1 Phase-to-Phase Voltage BAI406Meter #1 THD Phase CAI407Meter #1 Phase Angle CAI408Meter #1 Phase-to-Phase Voltage CAI409Meter #2 THD Phase AAI410Meter #2 Phase Angle AAI411Meter #2 Phase-to-Phase Voltage AAI412Meter #2 THD Phase BAI413Meter #2 Phase Angle BAI414Meter #2 Phase-to-Phase Voltage BAI415Meter #2 THD Phase CAI416Meter #2 Phase Angle CAI417Meter #2 Phase-to-Phase Voltage CAI418Meter #3 THD Phase AAI419Meter #3 Phase Angle AAI420Meter #3 Phase-to-Phase Voltage AAI421Meter #3 THD Phase BAI422Meter #3 Phase Angle BAI423Meter #3 Phase-to-Phase Voltage BAI424Meter #3 THD Phase CAI425Meter #3 Phase Angle CAI426Meter #3 Phase-to-Phase Voltage CAI427Meter #4 THD Phase AAI428Meter #4 Phase Angle AAI429Meter #4 Phase-to-Phase Voltage AAI430Meter #4 THD Phase BAI431Meter #4 Phase Angle BAI432Meter #4 Phase-to-Phase Voltage BAI433Meter #4 THD Phase CAI434Meter #4 Phase Angle CAI435Meter #4 Phase-to-Phase Voltage CAI436Meter #5 THD Phase AAI437Meter #5 Phase Angle AAI438Meter #5 Phase-to-Phase Voltage AAI439Meter #5 THD Phase BAI440Meter #5 Phase Angle BAI441Meter #5 Phase-to-Phase Voltage BAI442Meter #5 THD Phase CAI443Meter #5 Phase Angle CAI444Meter #5 Phase-to-Phase Voltage CAI445Meter #6 THD Phase AAI446Meter #6 Phase Angle AAI447Meter #6 Phase-to-Phase Voltage AAI448Meter #6 THD Phase BAI449Meter #6 Phase Angle BAI450Meter #6 Phase-to-Phase Voltage BAI451Meter #6 THD Phase CAI452Meter #6 Phase Angle CAI453Meter #6 Phase-to-Phase Voltage CAI454Meter #7 THD Phase AAI455Meter #7 Phase Angle AAI456Meter #7 Phase-to-Phase Voltage AAI457Meter #7 THD Phase BAI458Meter #7 Phase Angle BAI459Meter #7 Phase-to-Phase Voltage BAI460Meter #7 THD Phase CAI461Meter #7 Phase Angle CAI462Meter #7 Phase-to-Phase Voltage CAI463Meter #8 THD Phase AAI464Meter #8 Phase Angle AAI465Meter #8 Phase-to-Phase Voltage AAI466Meter #8 THD Phase BAI467Meter #8 Phase Angle BAI468Meter #8 Phase-to-Phase Voltage BAI469Meter #8 THD Phase CAI470Meter #8 Phase Angle CAI471Meter #8 Phase-to-Phase Voltage CAI472Number of phases offsetAI473Demand Window OffsetAI474I Multiplier Type OffsetAI475Number of Pulse Counters OffsetAI476Overlap OffsetAI477Number TOU's OffsetAI478MDT_M_TABLE_REG_STARTAI479NUM_MDT_M_TABLE_COLUMNSAI480NUM_MDT_M_TABLE_REGSAI481MDT_M_TABLE_REG_END
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile GE_EPM4500_Submeter_a_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/EPM4500.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 364 of the 481 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Internal Time - Hours/Minutes; Internal Time - Seconds; Internal Date - Month/Day...); they are kept as printed and told apart by instance.
- Each meter point repeats the same group of objects at higher instances; map the points that are wired.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GE EPM 4500 multi-point submeter via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
How many BACnet points does the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX have?
This list has 481 BACnet objects: 472 analog inputs, 9 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet points are writable?
9 of the 481 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile GE_EPM4500_Submeter_a (GE_EPM4500_Submeter_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/EPM4500_Submeter_Modbus%20Profile.zip.
What are the minimum BACnet points to integrate the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX?
Start with AI 36 Meter #1 Three-Phase Total kW (Meter 1 total kW); AI 256 Meter #1 Three-Phase kWh (Meter 1 kWh); AI 39 Meter #1 Three-Phase Total Power Factor (Meter 1 power factor); AI 40 Meter #2 Three-Phase Total kW (Meter 2 total kW); AI 262 Meter #2 Three-Phase kWh (Meter 2 kWh).
How do I check these points on the real GE EPM 4500 multi-point submeter via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile GE_EPM4500_Submeter_a · GE_EPM4500_Submeter_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.