Multi-circuit power and energy meter (submeter) · BACnet points list

Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the GE EPM 4500: 481 objects (472 AI, 9 AO), 364 polled by default. Per meter point it reads total kW, kvar, kVA and PF, then kWh, kvarh and instantaneous values (three-phase meters 1-8, then single/two-phase points); unpolled outputs handle the clock, interval data selection and data-ready flag.

This page lists 481 BACnet objects for the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
GE EPM 4500 multi-point submeter via BASgatewayLX
Equipment
Multi-circuit power and energy meter (submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
481 (9 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
EPM 4500, EPM4500, GE Multilin EPM 4500
Source document
BASgatewayLX Modbus device profile GE_EPM4500_Submeter_a · GE_EPM4500_Submeter_a_LX.csv
Download CSV 481 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX

Integration in brief

Map meter 1 total kW, meter 1 kWh and meter 1 power factor first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 36Meter #1 Three-Phase Total kWMeter 1 total kWRead
AI 256Meter #1 Three-Phase kWhMeter 1 kWhRead
AI 39Meter #1 Three-Phase Total Power FactorMeter 1 power factorRead
AI 40Meter #2 Three-Phase Total kWMeter 2 total kWRead
AI 262Meter #2 Three-Phase kWhMeter 2 kWhRead

Network setup

Watch out for

Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

481 of 481 shown
Type
Access
Show
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet Points List
DescriptionStates
AI1Meter Serial NumberModbus 400001; not polled by defaultRead
AI2Meter Serial Number ExtensionModbus 400003; not polled by defaultRead
AI3Meter Version NumberModbus 400005; not polled by defaultRead
AI4Meter Version Number ExtensionModbus 400007; not polled by defaultRead
AI5Meter Modbus AddressModbus 400009; not polled by defaultRead
AI6Baud RateModbus 400010; not polled by defaultRead
AI7Meter StatusModbus 400013; not polled by defaultRead
AI8Meter ReadyModbus 400014; not polled by defaultRead
AI9Number of Meters ConfiguredModbus 400015; not polled by defaultRead
AI10Number of Real-Time Points ConfiguredModbus 400016; not polled by defaultRead
AI11Number of Interval Points ConfiguredModbus 400017; not polled by defaultRead
AI12Number of Max/Min Points ConfiguredModbus 400018; not polled by defaultRead
AI13Maximum Number of Intervals That Can Be RecordedModbus 400019; not polled by defaultRead
AI14Number of slots configured for Scan TransponderModbus 400020; not polled by defaultRead
AO15Current slot being read in Scan TransponderModbus 400021; not polled by defaultCommand
AI16Store Interval LengthModbus 400050; not polled by defaultminRead
AI17Internal Time - Hours/MinutesModbus 400051; not polled by defaultRead
AI18Internal Time - SecondsModbus 400052; not polled by defaultsRead
AI19Internal Date - Month/DayModbus 400053; not polled by defaultRead
AI20Interval Date - YearModbus 400054; not polled by defaultyearsRead
AO21Internal Time - Hours/MinutesModbus 400055; not polled by defaultCommand
AO22Internal Time - SecondsModbus 400056; not polled by defaultCommand
AO23Internal Date - Month/DayModbus 400057; not polled by defaultyearsCommand
AO24Interval Date - YearModbus 400058; not polled by defaultCommand
AI25Date/Time of Oldest Interval - Hours/MinutesModbus 400059; not polled by defaultRead
AI26Date/Time of Oldest Interval - Month/DayModbus 400060; not polled by defaultRead
AI27Date/Time of Oldest Interval - YearModbus 400061; not polled by defaultRead
AI28Date/Time of Newest Interval - Hours/MinutesModbus 400062; not polled by defaultRead
AI29Date/Time of Newest Interval - Month/DayModbus 400063; not polled by defaultRead
AI30Date/Time of Newest Interval - YearModbus 400064; not polled by defaultRead
AO31Date/Time of Currently Selected Interval - Hours/MinutesModbus 400065; not polled by defaultCommand
AO32Date/Time of Currently Selected Interval - Month/DayModbus 400066; not polled by defaultCommand
AO33Date/Time of Currently Selected Interval - YearModbus 400067; not polled by defaultCommand
AO34Data Ready FlagModbus 400068; not polled by defaultCommand
AI35Interval Data Qualifying RegisterModbus 400100; not polled by defaultRead
AImin36Meter #1 Three-Phase Total kWModbus 400101kWRead
AI37Meter #1 Three-Phase Total kvarModbus 400103kVARRead
AI38Meter #1 Three-Phase Total kVAModbus 400105kVARead
AImin39Meter #1 Three-Phase Total Power FactorModbus 400107%Read
AImin40Meter #2 Three-Phase Total kWModbus 400109kWRead
AI41Meter #2 Three-Phase Total kvarModbus 400111kVARRead
AI42Meter #2 Three-Phase Total kVAModbus 400113kVARead
AI43Meter #2 Three-Phase Total Power FactorModbus 400115%Read
AI44Meter #3 Three-Phase Total kWModbus 400117kWRead
AI45Meter #3 Three-Phase Total kvarModbus 400119kVARRead
AI46Meter #3 Three-Phase Total kVAModbus 400121kVARead
AI47Meter #3 Three-Phase Total Power FactorModbus 400123%Read
AI48Meter #4 Three-Phase Total kWModbus 400125kWRead
AI49Meter #4 Three-Phase Total kvarModbus 400127kVARRead
AI50Meter #4 Three-Phase Total kVAModbus 400129kVARead
AI51Meter #4 Three-Phase Total Power FactorModbus 400131%Read
AI52Meter #5 Three-Phase Total kWModbus 400133kWRead
AI53Meter #5 Three-Phase Total kvarModbus 400135kVARRead
AI54Meter #5 Three-Phase Total kVAModbus 400137kVARead
AI55Meter #5 Three-Phase Total Power FactorModbus 400139%Read
AI56Meter #6 Three-Phase Total kWModbus 400141kWRead
AI57Meter #6 Three-Phase Total kvarModbus 400143kVARRead
AI58Meter #6 Three-Phase Total kVAModbus 400145kVARead
AI59Meter #6 Three-Phase Total Power FactorModbus 400147%Read
AI60Meter #7 Three-Phase Total kWModbus 400149kWRead
AI61Meter #7 Three-Phase Total kvarModbus 400151kVARRead
AI62Meter #7 Three-Phase Total kVAModbus 400153kVARead
AI63Meter #7 Three-Phase Total Power FactorModbus 400155%Read
AI64Meter #8 Three-Phase Total kWModbus 400157kWRead
AI65Meter #8 Three-Phase Total kvarModbus 400159kVARRead
AI66Meter #8 Three-Phase Total kVAModbus 400161kVARead
AI67Meter #8 Three-Phase Total Power FactorModbus 400163%Read
AI68Meter #9 Two-Phase Total kWModbus 400165kWRead
AI69Meter #9 Two-Phase Total kvarModbus 400167kVARRead
AI70Meter #9 Two-Phase Total kVAModbus 400169kVARead
AI71Meter #9 Two-Phase Total Power FactorModbus 400171%Read
AI72Meter #10 Two-Phase Total kWModbus 400173kWRead
AI73Meter #10 Two-Phase Total kvarModbus 400175kVARRead
AI74Meter #10 Two-Phase Total kVAModbus 400177kVARead
AI75Meter #10 Two-Phase Total Power FactorModbus 400179%Read
AI76Meter #11 Two-Phase Total kWModbus 400181kWRead
AI77Meter #11 Two-Phase Total kvarModbus 400183kVARRead
AI78Meter #11 Two-Phase Total kVAModbus 400185kVARead
AI79Meter #11 Two-Phase Total Power FactorModbus 400187%Read
AI80Meter #12 Two-Phase Total kWModbus 400189kWRead
AI81Meter #12 Two-Phase Total kvarModbus 400191kVARRead
AI82Meter #12 Two-Phase Total kVAModbus 400193kVARead
AI83Meter #12 Two-Phase Total Power FactorModbus 400195%Read
AI84Meter #13 Single-Phase Total kWModbus 400197kWRead
AI85Meter #13 Single-Phase Total kvarModbus 400199kVARRead
AI86Meter #13 Single-Phase Total kVAModbus 400201kVARead
AI87Meter #13 Single-Phase Total Power FactorModbus 400203%Read
AI88Meter #14 Single-Phase Total kWModbus 400205kWRead
AI89Meter #14 Single-Phase Total kvarModbus 400207kVARRead
AI90Meter #14 Single-Phase Total kVAModbus 400209kVARead
AI91Meter #14 Single-Phase Total Power FactorModbus 400211%Read
AI92Meter #15 Single-Phase Total kWModbus 400213kWRead
AI93Meter #15 Single-Phase Total kvarModbus 400215kVARRead
AI94Meter #15 Single-Phase Total kVAModbus 400217kVARead
AI95Meter #15 Single-Phase Total Power FactorModbus 400219%Read
AI96Meter #16 Single-Phase Total kWModbus 400221kWRead
AI97Meter #16 Single-Phase Total kvarModbus 400223kVARRead
AI98Meter #16 Single-Phase Total kVAModbus 400225kVARead
AI99Meter #16 Single-Phase Total Power FactorModbus 400227%Read
AI100Meter #17 Single-Phase Total kWModbus 400229kWRead
AI101Meter #17 Single-Phase Total kvarModbus 400231kVARRead
AI102Meter #17 Single-Phase Total kVAModbus 400233kVARead
AI103Meter #17 Single-Phase Total Power FactorModbus 400235%Read
AI104Meter #18 Single-Phase Total kWModbus 400237kWRead
AI105Meter #18 Single-Phase Total kvarModbus 400239kVARRead
AI106Meter #18 Single-Phase Total kVAModbus 400241kVARead
AI107Meter #18 Single-Phase Total Power FactorModbus 400243%Read
AI108Meter #19 Single-Phase Total kWModbus 400245kWRead
AI109Meter #19 Single-Phase Total kvarModbus 400247kVARRead
AI110Meter #19 Single-Phase Total kVAModbus 400249kVARead
AI111Meter #19 Single-Phase Total Power FactorModbus 400251%Read
AI112Meter #20 Single-Phase Total kWModbus 400253kWRead
AI113Meter #20 Single-Phase Total kvarModbus 400255kVARRead
AI114Meter #20 Single-Phase Total kVAModbus 400257kVARead
AI115Meter #20 Single-Phase Total Power FactorModbus 400259%Read
AI116Meter #21 Single-Phase Total kWModbus 400261kWRead
AI117Meter #21 Single-Phase Total kvarModbus 400263kVARRead
AI118Meter #21 Single-Phase Total kVAModbus 400265kVARead
AI119Meter #21 Single-Phase Total Power FactorModbus 400267%Read
AI120Meter #22 Single-Phase Total kWModbus 400269kWRead
AI121Meter #22 Single-Phase Total kvarModbus 400271kVARRead
AI122Meter #22 Single-Phase Total kVAModbus 400273kVARead
AI123Meter #22 Single-Phase Total Power FactorModbus 400275%Read
AI124Meter #23 Single-Phase Total kWModbus 400277kWRead
AI125Meter #23 Single-Phase Total kvarModbus 400279kVARRead
AI126Meter #23 Single-Phase Total kVAModbus 400281kVARead
AI127Meter #23 Single-Phase Total Power FactorModbus 400283%Read
AI128Meter #24 Single-Phase Total kWModbus 400285kWRead
AI129Meter #24 Single-Phase Total kvarModbus 400287kVARRead
AI130Meter #24 Single-Phase Total kVAModbus 400289kVARead
AI131Meter #24 Single-Phase Total Power FactorModbus 400291%Read
AI132Frequency (Phase A)Modbus 400355HzRead
AI133Voltage (A-N)Modbus 400363VRead
AI134Voltage (B-N)Modbus 400365VRead
AI135Voltage (C-N)Modbus 400367VRead
AI136Voltage (CT01)Modbus 400369VRead
AI137Amps (CT01)Modbus 400371ARead
AI138kW (CT01)Modbus 400373kWRead
AI139kvar (CT01)Modbus 400375kVARRead
AI140kVA (CT01)Modbus 400377kVARead
AI141Voltage (CT02)Modbus 400379VRead
AI142Amps (CT02)Modbus 400381ARead
AI143kW (CT02)Modbus 400383kWRead
AI144kvar (CT02)Modbus 400385kVARRead
AI145kVA (CT02)Modbus 400387kVARead
AI146Voltage (CT03)Modbus 400389VRead
AI147Amps (CT03)Modbus 400391ARead
AI148kW (CT03)Modbus 400393kWRead
AI149kvar (CT03)Modbus 400395kVARRead
AI150kVA (CT03)Modbus 400397kVARead
AI151Voltage (CT04)Modbus 400399VRead
AI152Amps (CT04)Modbus 400401ARead
AI153kW (CT04)Modbus 400403kWRead
AI154kvar (CT04)Modbus 400405kVARRead
AI155kVA (CT04)Modbus 400407kVARead
AI156Voltage (CT05)Modbus 400409VRead
AI157Amps (CT05)Modbus 400411ARead
AI158kW (CT05)Modbus 400413kWRead
AI159kvar (CT05)Modbus 400415kVARRead
AI160kVA (CT05)Modbus 400417kVARead
AI161Voltage (CT06)Modbus 400419VRead
AI162Amps (CT06)Modbus 400421ARead
AI163kW (CT06)Modbus 400423kWRead
AI164kvar (CT06)Modbus 400425kVARRead
AI165kVA (CT06)Modbus 400427kVARead
AI166Voltage (CT07)Modbus 400429VRead
AI167Amps (CT07)Modbus 400431ARead
AI168kW (CT07)Modbus 400433kWRead
AI169kvar (CT07)Modbus 400435kVARRead
AI170kVA (CT07)Modbus 400437kVARead
AI171Voltage (CT08)Modbus 400439VRead
AI172Amps (CT08)Modbus 400441ARead
AI173kW (CT08)Modbus 400443kWRead
AI174kvar (CT08)Modbus 400445kVARRead
AI175kVA (CT08)Modbus 400447kVARead
AI176Voltage (CT09)Modbus 400449VRead
AI177Amps (CT09)Modbus 400451ARead
AI178kW (CT09)Modbus 400453kWRead
AI179kvar (CT09)Modbus 400455kVARRead
AI180kVA (CT09)Modbus 400457kVARead
AI181Voltage (CT10)Modbus 400459VRead
AI182Amps (CT10)Modbus 400461ARead
AI183kW (CT10)Modbus 400463kWRead
AI184kvar (CT10)Modbus 400465kVARRead
AI185kVA (CT10)Modbus 400467kVARead
AI186Voltage (CT11)Modbus 400469VRead
AI187Amps (CT11)Modbus 400471ARead
AI188kW (CT11)Modbus 400473kWRead
AI189kvar (CT11)Modbus 400475kVARRead
AI190kVA (CT11)Modbus 400477kVARead
AI191Voltage (CT12)Modbus 400479VRead
AI192Amps (CT12)Modbus 400481ARead
AI193kW (CT12)Modbus 400483kWRead
AI194kvar (CT12)Modbus 400485kVARRead
AI195kVA (CT12)Modbus 400487kVARead
AI196Voltage (CT13)Modbus 400489VRead
AI197Amps (CT13)Modbus 400491ARead
AI198kW (CT13)Modbus 400493kWRead
AI199kvar (CT13)Modbus 400495kVARRead
AI200kVA (CT13)Modbus 400497kVARead
AI201Voltage (CT14)Modbus 400499VRead
AI202Amps (CT14)Modbus 400501ARead
AI203kW (CT14)Modbus 400503kWRead
AI204kvar (CT14)Modbus 400505kVARRead
AI205kVA (CT14)Modbus 400507kVARead
AI206Voltage (CT15)Modbus 400509VRead
AI207Amps (CT15)Modbus 400511ARead
AI208kW (CT15)Modbus 400513kWRead
AI209kvar (CT15)Modbus 400515kVARRead
AI210kVA (CT15)Modbus 400517kVARead
AI211Voltage (CT16)Modbus 400519VRead
AI212Amps (CT16)Modbus 400521ARead
AI213kW (CT16)Modbus 400523kWRead
AI214kvar (CT16)Modbus 400525kVARRead
AI215kVA (CT16)Modbus 400527kVARead
AI216Voltage (CT17)Modbus 400529VRead
AI217Amps (CT17)Modbus 400531ARead
AI218kW (CT17)Modbus 400533kWRead
AI219kvar (CT17)Modbus 400535kVARRead
AI220kVA (CT17)Modbus 400537kVARead
AI221Voltage (CT18)Modbus 400539VRead
AI222Amps (CT18)Modbus 400541ARead
AI223kW (CT18)Modbus 400543kWRead
AI224kvar (CT18)Modbus 400545kVARRead
AI225kVA (CT18)Modbus 400547kVARead
AI226Voltage (CT19)Modbus 400549VRead
AI227Amps (CT19)Modbus 400551ARead
AI228kW (CT19)Modbus 400553kWRead
AI229kvar (CT19)Modbus 400555kVARRead
AI230kVA (CT19)Modbus 400557kVARead
AI231Voltage (CT20)Modbus 400559VRead
AI232Amps (CT20)Modbus 400561ARead
AI233kW (CT20)Modbus 400563kWRead
AI234kvar (CT20)Modbus 400565kVARRead
AI235kVA (CT20)Modbus 400567kVARead
AI236Voltage (CT21)Modbus 400569VRead
AI237Amps (CT21)Modbus 400571ARead
AI238kW (CT21)Modbus 400573kWRead
AI239kvar (CT21)Modbus 400575kVARRead
AI240kVA (CT21)Modbus 400577kVARead
AI241Voltage (CT22)Modbus 400579VRead
AI242Amps (CT22)Modbus 400581ARead
AI243kW (CT22)Modbus 400583kWRead
AI244kvar (CT22)Modbus 400585kVARRead
AI245kVA (CT22)Modbus 400587kVARead
AI246Voltage (CT23)Modbus 400589VRead
AI247Amps (CT23)Modbus 400591ARead
AI248kW (CT23)Modbus 400593kWRead
AI249kvar (CT23)Modbus 400595kVARRead
AI250kVA (CT23)Modbus 400597kVARead
AI251Voltage (CT24)Modbus 400599VRead
AI252Amps (CT24)Modbus 400601ARead
AI253kW (CT24)Modbus 400603kWRead
AI254kvar (CT24)Modbus 400605kVARRead
AI255kVA (CT24)Modbus 400607kVARead
AImin256Meter #1 Three-Phase kWhModbus 400649kWhRead
AI257Meter #1 Three-Phase kvarhModbus 400651kVARhRead
AI258Meter #1 Three-Phase kWModbus 400653kWRead
AI259Meter #1 Three-Phase kvarModbus 400655kVARRead
AI260Meter #1 Three-Phase kVAModbus 400657kVARead
AI261Meter #1 Three-Phase Power FactorModbus 400659PFRead
AImin262Meter #2 Three-Phase kWhModbus 400661kWhRead
AI263Meter #2 Three-Phase kvarhModbus 400663kVARhRead
AI264Meter #2 Three-Phase kWModbus 400665kWRead
AI265Meter #2 Three-Phase kvarModbus 400667kVARRead
AI266Meter #2 Three-Phase kVAModbus 400669kVARead
AI267Meter #2 Three-Phase Power FactorModbus 400671PFRead
AI268Meter #3 Three-Phase kWhModbus 400673kWhRead
AI269Meter #3 Three-Phase kvarhModbus 400675kVARhRead
AI270Meter #3 Three-Phase kWModbus 400677kWRead
AI271Meter #3 Three-Phase kvarModbus 400679kVARRead
AI272Meter #3 Three-Phase kVAModbus 400681kVARead
AI273Meter #3 Three-Phase Power FactorModbus 400683PFRead
AI274Meter #4 Three-Phase kWhModbus 400685kWhRead
AI275Meter #4 Three-Phase kvarhModbus 400687kVARhRead
AI276Meter #4 Three-Phase kWModbus 400689kWRead
AI277Meter #4 Three-Phase kvarModbus 400691kVARRead
AI278Meter #4 Three-Phase kVAModbus 400693kVARead
AI279Meter #4 Three-Phase Power FactorModbus 400695PFRead
AI280Meter #5 Three-Phase kWhModbus 400697kWhRead
AI281Meter #5 Three-Phase kvarhModbus 400699kVARhRead
AI282Meter #5 Three-Phase kWModbus 400701kWRead
AI283Meter #5 Three-Phase kvarModbus 400703kVARRead
AI284Meter #5 Three-Phase kVAModbus 400705kVARead
AI285Meter #5 Three-Phase Power FactorModbus 400707PFRead
AI286Meter #6 Three-Phase kWhModbus 400709kWhRead
AI287Meter #6 Three-Phase kvarhModbus 400711kVARhRead
AI288Meter #6 Three-Phase kWModbus 400713kWRead
AI289Meter #6 Three-Phase kvarModbus 400715kVARRead
AI290Meter #6 Three-Phase kVAModbus 400717kVARead
AI291Meter #6 Three-Phase Power FactorModbus 400719PFRead
AI292Meter #7 Three-Phase kWhModbus 400721kWhRead
AI293Meter #7 Three-Phase kvarhModbus 400723kVARhRead
AI294Meter #7 Three-Phase kWModbus 400725kWRead
AI295Meter #7 Three-Phase kvarModbus 400727kVARRead
AI296Meter #7 Three-Phase kVAModbus 400729kVARead
AI297Meter #7 Three-Phase Power FactorModbus 400731PFRead
AI298Meter #8 Three-Phase kWhModbus 400733kWhRead
AI299Meter #8 Three-Phase kvarhModbus 400735kVARhRead
AI300Meter #8 Three-Phase kWModbus 400737kWRead
AI301Meter #8 Three-Phase kvarModbus 400739kVARRead
AI302Meter #8 Three-Phase kVAModbus 400741kVARead
AI303Meter #8 Three-Phase Power FactorModbus 400743PFRead
AI304Meter #9 Phase kWhModbus 400745kWhRead
AI305Meter #9 Phase kvarhModbus 400747kVARhRead
AI306Meter #9 Phase kWModbus 400749kWRead
AI307Meter #9 Phase kvarModbus 400751kVARRead
AI308Meter #9 Phase kVAModbus 400753kVARead
AI309Meter #9 Phase Power FactorModbus 400755PFRead
AI310Meter #10 Phase kWhModbus 400757kWhRead
AI311Meter #10 Phase kvarhModbus 400759kVARhRead
AI312Meter #10 Phase kWModbus 400761kWRead
AI313Meter #10 Phase kvarModbus 400763kVARRead
AI314Meter #10 Phase kVAModbus 400765kVARead
AI315Meter #10 Phase Power FactorModbus 400767PFRead
AI316Meter #11 Phase kWhModbus 400769kWhRead
AI317Meter #11 Phase kvarhModbus 400771kVARhRead
AI318Meter #11 Phase kWModbus 400773kWRead
AI319Meter #11 Phase kvarModbus 400775kVARRead
AI320Meter #11 Phase kVAModbus 400777kVARead
AI321Meter #11 Phase Power FactorModbus 400779PFRead
AI322Meter #12 Phase kWhModbus 400781kWhRead
AI323Meter #12 Phase kvarhModbus 400783kVARhRead
AI324Meter #12 Phase kWModbus 400785kWRead
AI325Meter #12 Phase kvarModbus 400787kVARRead
AI326Meter #12 Phase kVAModbus 400789kVARead
AI327Meter #12 Phase Power FactorModbus 400791PFRead
AI328Meter #13 Phase kWhModbus 400793kWhRead
AI329Meter #13 Phase kvarhModbus 400795kVARhRead
AI330Meter #13 Phase kWModbus 400797kWRead
AI331Meter #13 Phase kvarModbus 400799kVARRead
AI332Meter #13 Phase kVAModbus 400801kVARead
AI333Meter #13 Phase Power FactorModbus 400803PFRead
AI334Meter #14 Phase kWhModbus 400805kWhRead
AI335Meter #14 Phase kvarhModbus 400807kVARhRead
AI336Meter #14 Phase kWModbus 400809kWRead
AI337Meter #14 Phase kvarModbus 400811kVARRead
AI338Meter #14 Phase kVAModbus 400813kVARead
AI339Meter #14 Phase Power FactorModbus 400815PFRead
AI340Meter #15 Phase kWhModbus 400817kWhRead
AI341Meter #15 Phase kvarhModbus 400819kVARhRead
AI342Meter #15 Phase kWModbus 400821kWRead
AI343Meter #15 Phase kvarModbus 400823kVARRead
AI344Meter #15 Phase kVAModbus 400825kVARead
AI345Meter #15 Phase Power FactorModbus 400827PFRead
AI346Meter #16 Phase kWhModbus 400829kWhRead
AI347Meter #16 Phase kvarhModbus 400831kVARhRead
AI348Meter #16 Phase kWModbus 400833kWRead
AI349Meter #16 Phase kvarModbus 400835kVARRead
AI350Meter #16 Phase kVAModbus 400837kVARead
AI351Meter #16 Phase Power FactorModbus 400839PFRead
AI352Meter #17 Phase kWhModbus 400841kWhRead
AI353Meter #17 Phase kvarhModbus 400843kVARhRead
AI354Meter #17 Phase kWModbus 400845kWRead
AI355Meter #17 Phase kvarModbus 400847kVARRead
AI356Meter #17 Phase kVAModbus 400849kVARead
AI357Meter #17 Phase Power FactorModbus 400851PFRead
AI358Meter #18 Phase kWhModbus 400853kWhRead
AI359Meter #18 Phase kvarhModbus 400855kVARhRead
AI360Meter #18 Phase kWModbus 400857kWRead
AI361Meter #18 Phase kvarModbus 400859kVARRead
AI362Meter #18 Phase kVAModbus 400861kVARead
AI363Meter #18 Phase Power FactorModbus 400863PFRead
AI364Meter #19 Phase kWhModbus 400865kWhRead
AI365Meter #19 Phase kvarhModbus 400867kVARhRead
AI366Meter #19 Phase kWModbus 400869kWRead
AI367Meter #19 Phase kvarModbus 400871kVARRead
AI368Meter #19 Phase kVAModbus 400873kVARead
AI369Meter #19 Phase Power FactorModbus 400875PFRead
AI370Meter #20 Phase kWhModbus 400877kWhRead
AI371Meter #20 Phase kvarhModbus 400879kVARhRead
AI372Meter #20 Phase kWModbus 400881kWRead
AI373Meter #20 Phase kvarModbus 400883kVARRead
AI374Meter #20 Phase kVAModbus 400885kVARead
AI375Meter #20 Phase Power FactorModbus 400887PFRead
AI376Meter #21 Phase kWhModbus 400889kWhRead
AI377Meter #21 Phase kvarhModbus 400891kVARhRead
AI378Meter #21 Phase kWModbus 400893kWRead
AI379Meter #21 Phase kvarModbus 400895kVARRead
AI380Meter #21 Phase kVAModbus 400897kVARead
AI381Meter #21 Phase Power FactorModbus 400899PFRead
AI382Meter #22 Phase kWhModbus 400901kWhRead
AI383Meter #22 Phase kvarhModbus 400903kVARhRead
AI384Meter #22 Phase kWModbus 400905kWRead
AI385Meter #22 Phase kvarModbus 400907kVARRead
AI386Meter #22 Phase kVAModbus 400909kVARead
AI387Meter #22 Phase Power FactorModbus 400911PFRead
AI388Meter #23 Phase kWhModbus 400913kWhRead
AI389Meter #23 Phase kvarhModbus 400915kVARhRead
AI390Meter #23 Phase kWModbus 400917kWRead
AI391Meter #23 Phase kvarModbus 400919kVARRead
AI392Meter #23 Phase kVAModbus 400921kVARead
AI393Meter #23 Phase Power FactorModbus 400923PFRead
AI394Meter #24 Phase kWhModbus 400925kWhRead
AI395Meter #24 Phase kvarhModbus 400927kVARhRead
AI396Meter #24 Phase kWModbus 400929kWRead
AI397Meter #24 Phase kvarModbus 400931kVARRead
AI398Meter #24 Phase kVAModbus 400933kVARead
AI399Meter #24 Phase Power FactorModbus 400935PFRead
AI400Meter #1 THD Phase AModbus 401001; not polled by default%Read
AI401Meter #1 Phase Angle AModbus 401003; not polled by default° (phase)Read
AI402Meter #1 Phase-to-Phase Voltage AModbus 401005; not polled by defaultVRead
AI403Meter #1 THD Phase BModbus 401007; not polled by default%Read
AI404Meter #1 Phase Angle BModbus 401009; not polled by default° (phase)Read
AI405Meter #1 Phase-to-Phase Voltage BModbus 401011; not polled by defaultVRead
AI406Meter #1 THD Phase CModbus 401013; not polled by default%Read
AI407Meter #1 Phase Angle CModbus 401015; not polled by default° (phase)Read
AI408Meter #1 Phase-to-Phase Voltage CModbus 401017; not polled by defaultVRead
AI409Meter #2 THD Phase AModbus 401019; not polled by default%Read
AI410Meter #2 Phase Angle AModbus 401021; not polled by default° (phase)Read
AI411Meter #2 Phase-to-Phase Voltage AModbus 401023; not polled by defaultVRead
AI412Meter #2 THD Phase BModbus 401025; not polled by default%Read
AI413Meter #2 Phase Angle BModbus 401027; not polled by default° (phase)Read
AI414Meter #2 Phase-to-Phase Voltage BModbus 401029; not polled by defaultVRead
AI415Meter #2 THD Phase CModbus 401031; not polled by default%Read
AI416Meter #2 Phase Angle CModbus 401033; not polled by default° (phase)Read
AI417Meter #2 Phase-to-Phase Voltage CModbus 401035; not polled by defaultVRead
AI418Meter #3 THD Phase AModbus 401037; not polled by default%Read
AI419Meter #3 Phase Angle AModbus 401039; not polled by default° (phase)Read
AI420Meter #3 Phase-to-Phase Voltage AModbus 401041; not polled by defaultVRead
AI421Meter #3 THD Phase BModbus 401043; not polled by default%Read
AI422Meter #3 Phase Angle BModbus 401045; not polled by default° (phase)Read
AI423Meter #3 Phase-to-Phase Voltage BModbus 401047; not polled by defaultVRead
AI424Meter #3 THD Phase CModbus 401049; not polled by default%Read
AI425Meter #3 Phase Angle CModbus 401051; not polled by default° (phase)Read
AI426Meter #3 Phase-to-Phase Voltage CModbus 401053; not polled by defaultVRead
AI427Meter #4 THD Phase AModbus 401055; not polled by default%Read
AI428Meter #4 Phase Angle AModbus 401057; not polled by default° (phase)Read
AI429Meter #4 Phase-to-Phase Voltage AModbus 401059; not polled by defaultVRead
AI430Meter #4 THD Phase BModbus 401061; not polled by default%Read
AI431Meter #4 Phase Angle BModbus 401063; not polled by default° (phase)Read
AI432Meter #4 Phase-to-Phase Voltage BModbus 401065; not polled by defaultVRead
AI433Meter #4 THD Phase CModbus 401067; not polled by default%Read
AI434Meter #4 Phase Angle CModbus 401069; not polled by default° (phase)Read
AI435Meter #4 Phase-to-Phase Voltage CModbus 401071; not polled by defaultVRead
AI436Meter #5 THD Phase AModbus 401073; not polled by default%Read
AI437Meter #5 Phase Angle AModbus 401075; not polled by default° (phase)Read
AI438Meter #5 Phase-to-Phase Voltage AModbus 401077; not polled by defaultVRead
AI439Meter #5 THD Phase BModbus 401079; not polled by default%Read
AI440Meter #5 Phase Angle BModbus 401081; not polled by default° (phase)Read
AI441Meter #5 Phase-to-Phase Voltage BModbus 401083; not polled by defaultVRead
AI442Meter #5 THD Phase CModbus 401085; not polled by default%Read
AI443Meter #5 Phase Angle CModbus 401087; not polled by default° (phase)Read
AI444Meter #5 Phase-to-Phase Voltage CModbus 401089; not polled by defaultVRead
AI445Meter #6 THD Phase AModbus 401091; not polled by default%Read
AI446Meter #6 Phase Angle AModbus 401093; not polled by default° (phase)Read
AI447Meter #6 Phase-to-Phase Voltage AModbus 401095; not polled by defaultVRead
AI448Meter #6 THD Phase BModbus 401097; not polled by default%Read
AI449Meter #6 Phase Angle BModbus 401099; not polled by default° (phase)Read
AI450Meter #6 Phase-to-Phase Voltage BModbus 401101; not polled by defaultVRead
AI451Meter #6 THD Phase CModbus 401103; not polled by default%Read
AI452Meter #6 Phase Angle CModbus 401105; not polled by default° (phase)Read
AI453Meter #6 Phase-to-Phase Voltage CModbus 401107; not polled by defaultVRead
AI454Meter #7 THD Phase AModbus 401109; not polled by default%Read
AI455Meter #7 Phase Angle AModbus 401111; not polled by default° (phase)Read
AI456Meter #7 Phase-to-Phase Voltage AModbus 401113; not polled by defaultVRead
AI457Meter #7 THD Phase BModbus 401115; not polled by default%Read
AI458Meter #7 Phase Angle BModbus 401117; not polled by default° (phase)Read
AI459Meter #7 Phase-to-Phase Voltage BModbus 401119; not polled by defaultVRead
AI460Meter #7 THD Phase CModbus 401121; not polled by default%Read
AI461Meter #7 Phase Angle CModbus 401123; not polled by default° (phase)Read
AI462Meter #7 Phase-to-Phase Voltage CModbus 401125; not polled by defaultVRead
AI463Meter #8 THD Phase AModbus 401127; not polled by default%Read
AI464Meter #8 Phase Angle AModbus 401129; not polled by default° (phase)Read
AI465Meter #8 Phase-to-Phase Voltage AModbus 401131; not polled by defaultVRead
AI466Meter #8 THD Phase BModbus 401133; not polled by default%Read
AI467Meter #8 Phase Angle BModbus 401135; not polled by default° (phase)Read
AI468Meter #8 Phase-to-Phase Voltage BModbus 401137; not polled by defaultVRead
AI469Meter #8 THD Phase CModbus 401139; not polled by default%Read
AI470Meter #8 Phase Angle CModbus 401141; not polled by default° (phase)Read
AI471Meter #8 Phase-to-Phase Voltage CModbus 401143; not polled by defaultVRead
AI472Number of phases offsetModbus 402001; not polled by defaultRead
AI473Demand Window OffsetModbus 402002; not polled by defaultRead
AI474I Multiplier Type OffsetModbus 402003; not polled by defaultRead
AI475Number of Pulse Counters OffsetModbus 402004; not polled by defaultRead
AI476Overlap OffsetModbus 402005; not polled by defaultRead
AI477Number TOU's OffsetModbus 402006; not polled by defaultRead
AI478MDT_M_TABLE_REG_STARTModbus 402007; not polled by defaultRead
AI479NUM_MDT_M_TABLE_COLUMNSModbus 402008; not polled by defaultRead
AI480NUM_MDT_M_TABLE_REGSModbus 402009; not polled by defaultRead
AI481MDT_M_TABLE_REG_ENDModbus 402010; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX GE EPM 4500 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GE EPM 4500 multi-point submeter via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX

How many BACnet points does the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX have?

This list has 481 BACnet objects: 472 analog inputs, 9 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet points are writable?

9 of the 481 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile GE_EPM4500_Submeter_a (GE_EPM4500_Submeter_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/EPM4500_Submeter_Modbus%20Profile.zip.

What are the minimum BACnet points to integrate the Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX?

Start with AI 36 Meter #1 Three-Phase Total kW (Meter 1 total kW); AI 256 Meter #1 Three-Phase kWh (Meter 1 kWh); AI 39 Meter #1 Three-Phase Total Power Factor (Meter 1 power factor); AI 40 Meter #2 Three-Phase Total kW (Meter 2 total kW); AI 262 Meter #2 Three-Phase kWh (Meter 2 kWh).

How do I check these points on the real GE EPM 4500 multi-point submeter via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile GE_EPM4500_Submeter_a · GE_EPM4500_Submeter_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.