Automatic transfer switch controller · BACnet points list

Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the ASCO 7000 Group 5 controller: 89 objects (38 AI, 51 BI), all polled. It reads switch position (main and auxiliary on normal/emergency), source availability, phase rotation, normal and emergency voltages, frequencies and unbalance, engine running, lockout, breaker trips, switch type and rating, controller state and the event log.

This page lists 89 BACnet objects for the Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
ASCO 7000 Series Group 5 controller via BASgatewayLX
Equipment
Automatic transfer switch controller
Equipment type
Other equipment
BACnet objects
89 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series
Source document
BASgatewayLX Modbus device profile Asco_Group_5_Controller_a · Asco_Group_5_Controller_a_LX.csv
Download CSV 89 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX

Integration in brief

Read the switch position and source available bits, both sources' voltages and engine running. The profile has no output objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 4Main on NormalMain contacts on normalRead
BI 5Main on EmergencyMain contacts on emergencyRead
BI 8Normal Source AvailableNormal source availableRead
BI 9Emergency Source AvailableEmergency source availableRead
BI 51Engine runningEngine runningRead
AI 17Normal Voltage Phase ABNormal voltage A-BRead
AI 21Emergency Voltage Phase ABEmergency voltage A-BRead
AI 54Control Panel StateController stateRead
BI 46Transfer Switch Locked OutTransfer switch locked outRead

Network setup

Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

89 of 89 shown
Type
AnalogBinary
Show
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX BACnet Points List
DescriptionStates
AI1Phase Shift between Normal EmergencyModbus 400012° (phase)Read
AI2Normal FrequencyModbus 400013HzRead
AI3Emergency FrequencyModbus 400014Read
BImin4Main on NormalModbus 400015 bit 0Read
BImin5Main on EmergencyModbus 400015 bit 1Read
BI6Auxiliary on NormalModbus 400015 bit 2Read
BI7Auxiliary on EmergencyModbus 400015 bit 3Read
BImin8Normal Source AvailableModbus 400015 bit 4Read
BImin9Emergency Source AvailableModbus 400015 bit 5Read
BI10Normal Phase Rotation is ABCModbus 400016 bit 0Read
BI11Normal Phase Rotation is CBAModbus 400016 bit 1Read
BI12Emergency Phase Rotation is ABCModbus 400016 bit 2Read
BI13Emergency Phase Rotation is CBAModbus 400016 bit 3Read
BI14Engine Exerciser with Load ActiveModbus 400016 bit 4Read
BI15not usedModbus 400016 bit 5Read
BI16External F17 is ActiveModbus 400016 bit 6Read
AImin17Normal Voltage Phase ABModbus 400017VRead
AI18Normal Voltage Phase BCModbus 400018VRead
AI19Normal Voltage Phase CAModbus 400019VRead
AI20Normal Voltage UnbalanceModbus 400020VRead
AImin21Emergency Voltage Phase ABModbus 400021VRead
AI22Emergency Voltage Phase BCModbus 400022VRead
AI23Emergency Voltage Phase CAModbus 400023VRead
AI24Emergency Voltage UnbalanceModbus 400024VRead
AI25Nominal VoltageModbus 400025VRead
BI26Nominal FrequencyModbus 400026 bit 0Read
BI27Normal Source 3 Phase sensingModbus 400026 bit 1Read
BI28Emergency Source 3 Phase sensingModbus 400026 bit 2Read
BI29Transfer Switch Type (CTTS OTTS DTTS) AModbus 400026 bit 3Read
BI30Transfer Switch Type (CTTS OTTS DTTS) BModbus 400026 bit 4Read
BI31Transfer Switch Bypass or notModbus 400026 bit 5Read
BI32Transfer Switch or Dual BreakerModbus 400026 bit 6Read
AI33Transfer Switch Amp ratingModbus 400027Read
AI34Control Panel Software version Char 1 and 2Modbus 400028Read
AI35Control Panel Software version Char 3 and 4Modbus 400029Read
AI36Control Panel Software version Char 5 and 6Modbus 400030Read
AI37Control Panel Software version Char 7 and 8Modbus 400031Read
AI38Control Panel Software version Char 9 and 10Modbus 400032Read
AI39Control Panel Software version Char 11 and 12Modbus 400033Read
AI40Control Panel Software date Char 1 and 2Modbus 400034Read
AI41Control Panel Software date Char 3 and 4Modbus 400035Read
AI42Control Panel Software date Char 5 and 6Modbus 400036Read
AI43Control Panel Software date Char 7 and 8Modbus 400037Read
AI44Control Panel Software date Char 9 and 10Modbus 400038Read
AI45Control Panel Software date Char 11 and 12Modbus 400039Read
BImin46Transfer Switch Locked OutModbus 400040 bit 0Read
BI47CTTS extended parallel alarmModbus 400040 bit 1Read
BI48CTTS failure to synch alarmModbus 400040 bit 2Read
BI49DTTS Load DisconnectModbus 400040 bit 3Read
BI50External parameter lock is activeModbus 400040 bit 4Read
BImin51Engine runningModbus 400040 bit 5Read
BI52Normal Breaker TrippedModbus 400040 bit 6Read
BI53Emergency Breaker TrippedModbus 400040 bit 7Read
AImin54Control Panel StateModbus 400041Read
AI55Control Panel Status State Data (Ælookup table)Modbus 400042Read
BI56Feature 6BModbus 400043 bit 0Read
BI57Feature 6CModbus 400043 bit 1Read
BI58Feature 17Modbus 400043 bit 2Read
BI59not usedModbus 400043 bit 3Read
BI60Feature 29Modbus 400043 bit 4Read
BI61Feature 30Modbus 400043 bit 5Read
BI62Feature 34AModbus 400043 bit 6Read
BI63Feature 34BModbus 400043 bit 7Read
BI64Feature 89Modbus 400044 bit 0Read
BI65Feature CT BypassModbus 400044 bit 1Read
BI66Feature Alarm ResetModbus 400044 bit 2Read
BI67Feature 6DModbus 400044 bit 3Read
BI68Feature 5Modbus 400044 bit 4Read
BI69Feature 6ZModbus 400044 bit 5Read
BI70Feature 34TModbus 400044 bit 6Read
AI71Event numberModbus 400045Read
AI72Event yearModbus 400046Read
AI73Event monthModbus 400047Read
AI74Event day of monthModbus 400048Read
AI75Event day of weekModbus 400049Read
AI76Event hourModbus 400050Read
AI77Event minuteModbus 400051Read
AI78Event secondModbus 400052Read
AI79Event typeModbus 400053Read
AI80Event causeModbus 400054Read
AI81Number of entries in the control panel event logModbus 400055Read
BI82Soft Load Controller mode bit 0Modbus 400101 bit 0Read
BI83Soft Load Controller mode bit 1Modbus 400101 bit 1Read
BI84Soft Load Controller mode bit 2Modbus 400101 bit 2Read
BI85Soft Load Controller mode bit 3Modbus 400101 bit 3Read
BI86Soft Load Controller mode bit 4Modbus 400101 bit 4Read
BI87Soft Load Controller mode bit 5Modbus 400101 bit 5Read
BI88SLC Normal Breaker statusModbus 400101 bit 6Read
BI89SLC Emergency Breaker statusModbus 400101 bit 7Read
Object ID lookup: Contemporary Controls BASgatewayLX ASCO 7000 Group 5 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ASCO 7000 Series Group 5 controller via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX

How many BACnet points does the Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX have?

This list has 89 BACnet objects: 38 analog inputs, 51 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Asco_Group_5_Controller_a (Asco_Group_5_Controller_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Asco%207000%20Group%205%20controller.zip.

What are the minimum BACnet points to integrate the Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX?

Start with BI 4 Main on Normal (Main contacts on normal); BI 5 Main on Emergency (Main contacts on emergency); BI 8 Normal Source Available (Normal source available); BI 9 Emergency Source Available (Emergency source available); BI 51 Engine running (Engine running); AI 17 Normal Voltage Phase AB (Normal voltage A-B); AI 21 Emergency Voltage Phase AB (Emergency voltage A-B); AI 54 Control Panel State (Controller state); BI 46 Transfer Switch Locked Out (Transfer switch locked out).

How do I check these points on the real ASCO 7000 Series Group 5 controller via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.