Power and energy meter · BACnet points list

Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Veris E50B1A/E50C2A/E50C3A: 57 objects (42 AI, 15 BI), 55 polled by default. Inputs give real, apparent and reactive energy, power and PF total and per phase, voltages, currents, frequency, present and max demand and per-phase energy; binary inputs flag voltage and current out of range.

This page lists 57 BACnet objects for the Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
57 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter
Source document
BASgatewayLX Modbus device profile Veris_E50C2A_E50C3A_a · Veris_E50C2A_E50C3A_a_LX.csv
Download CSV 57 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX

Integration in brief

Map total real power, real energy consumption and average voltage L-L first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3Total Instantaneous Real PowerTotal real powerRead
AI 1RealEnergy Consumption (clear via reset register)1Real energy consumptionRead
AI 7Voltage L-L Averageof3PhasesAverage voltage L-LRead
AI 9Current Average of 3 PhasesAverage currentRead
AI 6Total PowerFactor (Total KW /TotalKVA)Total power factorRead
AI 25Frequency (derivedfrom Phase A)FrequencyRead
AI 34Total RealPower Present DemandReal power present demandRead

Network setup

Watch out for

Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

57 of 57 shown
Type
AnalogBinary
Show
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX BACnet Points List
DescriptionStates
AImin1RealEnergy Consumption (clear via reset register)1Modbus 400257kWhRead
AI2RealEnergy Consumption (clear via reset register)2Modbus 400259kWhRead
AImin3Total Instantaneous Real PowerModbus 400261kVRead
AI4Total Instantaneous ReactivePowerModbus 400263kVARRead
AI5Total Instantaneous Apparent PowerModbus 400265kVARead
AImin6Total PowerFactor (Total KW /TotalKVA)Modbus 400267Read
AImin7Voltage L-L Averageof3PhasesModbus 400269VRead
AI8Voltage L-N Averageof3PhasesModbus 400271VRead
AImin9Current Average of 3 PhasesModbus 400273ARead
AI10RealPower Phase AModbus 400275kWRead
AI11RealPower Phase BModbus 400277kWRead
AI12RealPower Phase CModbus 400279kWRead
AI13Power Factor Phase AModbus 400281PFRead
AI14Power Factor Phase BModbus 400283PFRead
AI15Power Factor Phase CModbus 400285PFRead
AI16Voltage Phase A-BModbus 400287VRead
AI17Voltage Phase B-CModbus 400289VRead
AI18Voltage Phase A-CModbus 400291VRead
AI19Voltage Phase A-NModbus 400293VRead
AI20Voltage Phase B-NModbus 400295VRead
AI21Voltage Phase C-NModbus 400297VRead
AI22Current Instantaneous Phase AModbus 400299ARead
AI23Current Instantaneous Phase BModbus 400301ARead
AI24Current Instantaneous Phase CModbus 400303ARead
AImin25Frequency (derivedfrom Phase A)Modbus 400307HzRead
AI26Apparent EnergyConsumptionModbus 400309Read
AI27Reactive EnergyConsumptionModbus 400311Read
AI28Apparent Power Phase AModbus 400313kVARead
AI29Apparent Power Phase BModbus 400315kVARead
AI30Apparent Power Phase CModbus 400317kVARead
AI31Reactive Power PhaseAModbus 400319kVARRead
AI32Reactive Power PhaseBModbus 400321kVARRead
AI33Reactive Power PhaseCModbus 400323kVARRead
AImin34Total RealPower Present DemandModbus 400325kWRead
AI35Total Reactive PowerPresentDemandModbus 400327kVARRead
AI36Total Apparent PowerPresent DemandModbus 400329kVARead
AI37Total RealPower Max DemandModbus 400331kWRead
AI38Total Reactive PowerMaxDemandModbus 400333kVARRead
AI39Total Apparent PowerMax DemandModbus 400335kVARead
AI40RealEnergy Consumption PhaseAModbus 400341kWhRead
AI41RealEnergy Consumption PhaseBModbus 400343kWhRead
AI42RealEnergy Consumption PhaseCModbus 400345kWhRead
BI43Phase A Voltage out of rangeModbus 400146 bit 0Read
BI44Phase B Voltage out of rangeModbus 400146 bit 1Read
BI45Phase C Voltage out of rangeModbus 400146 bit 2Read
BI46Phase A Current out of rangeModbus 400146 bit 3Read
BI47Phase B Current out of rangeModbus 400146 bit 4Read
BI48Phase C Current out of rangeModbus 400146 bit 5Read
BI49Frequency out of rangeModbus 400146 bit 6Read
BI50Phase Loss AModbus 400146 bit 8Read
BI51Phase Loss BModbus 400146 bit 9Read
BI52Phase Loss CModbus 400146 bit 10Read
BI53Low Power Factor on AModbus 400146 bit 11Read
BI54Low Power Factor on BModbus 400146 bit 12Read
BI55Low Power Factor on CModbus 400146 bit 13Read
BI56Energy pulse output overrun errorModbus 400146 bit 14; not polled by defaultRead
BI57Energy pulse output configuration errorModbus 400146 bit 15; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX Veris E50 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Veris E50B1A / E50C2A / E50C3A via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX

How many BACnet points does the Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX have?

This list has 57 BACnet objects: 42 analog inputs, 15 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Veris_E50C2A_E50C3A_a (Veris_E50C2A_E50C3A_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Veris_E50C2A_E50C3A_a_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX?

Start with AI 3 Total Instantaneous Real Power (Total real power); AI 1 RealEnergy Consumption (clear via reset register)1 (Real energy consumption); AI 7 Voltage L-L Averageof3Phases (Average voltage L-L); AI 9 Current Average of 3 Phases (Average current); AI 6 Total PowerFactor (Total KW /TotalKVA) (Total power factor); AI 25 Frequency (derivedfrom Phase A) (Frequency); AI 34 Total RealPower Present Demand (Real power present demand).

How do I check these points on the real Veris E50B1A / E50C2A / E50C3A via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Veris_E50C2A_E50C3A_a · Veris_E50C2A_E50C3A_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.