Power and energy meter · BACnet points list

Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the ION6200: 134 objects (129 AI, 5 AO), 22 polled by default. Polled inputs give phase and average voltages and currents, current demand, frequency, PF, kW totals and phases and kVAR/kVA demand; energy, peak demand and setup values are unpolled, and five unpolled outputs reset energy and demand or drive the two digital outputs.

This page lists 134 BACnet objects for the Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Schneider Electric PowerLogic ION6200 via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
134 (5 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ION6200, PowerLogic ION6200
Source document
BASgatewayLX Modbus device profile Schneider_Electric_ION6200_a · Schneider_Electric_ION6200_a_LX.csv
Download CSV 134 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX

Integration in brief

Map total kW, kWh delivered and average line-line voltage first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 31kW totalTotal kWRead
AI 49kWh delkWh deliveredRead
AI 18Vll avgAverage line-line voltageRead
AI 22I avgAverage currentRead
AI 27PF sign totalTotal power factor (signed)Read
AI 26FrequencyFrequencyRead

Network setup

Watch out for

Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

134 of 134 shown
Type
Access
Show
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX BACnet Points List
DescriptionStates
AI1serial numberModbus 400001; not polled by defaultRead
AI2firmware revisionModbus 400003; not polled by defaultRead
AI3oem identificationModbus 400004; not polled by defaultRead
AI4meter optionsModbus 400005; not polled by defaultRead
AI5# meter power upsModbus 400007; not polled by defaultRead
AI6# peak demand resetsModbus 400008; not polled by defaultRead
AI7meter on-timeModbus 400009; not polled by defaultRead
AI8# flash erase cyclesModbus 400011; not polled by defaultRead
AI9device typeModbus 400013; not polled by defaultRead
AI10demand interval down counterModbus 400015; not polled by defaultRead
AI11Vln aModbus 400100VRead
AI12Vln bModbus 400101VRead
AI13Vln cModbus 400102VRead
AI14Vln avgModbus 400103VRead
AI15Vll abModbus 400104VRead
AI16VllbcModbus 400105VRead
AI17VllcaModbus 400106VRead
AImin18Vll avgModbus 400107VRead
AI19I aModbus 400108ARead
AI20I bModbus 400109ARead
AI21I cModbus 400110ARead
AImin22I avgModbus 400111ARead
AI23I demandModbus 400112ARead
AI24I peak demandModbus 400113ARead
AI25I 4Modbus 400114; not polled by defaultARead
AImin26FrequencyModbus 400115HzRead
AImin27PF sign totalModbus 400116PFRead
AI28PF sign aModbus 400117; not polled by defaultPFRead
AI29PF sign bModbus 400118; not polled by defaultPFRead
AI30PF sign cModbus 400119; not polled by defaultPFRead
AImin31kW totalModbus 400120kWRead
AI32kVAR totalModbus 400121; not polled by defaultkVARRead
AI33kVA TotalModbus 400122; not polled by defaultkVARead
AI34kWaModbus 400123kWRead
AI35KWbModbus 400124kWRead
AI36kWcModbus 400125kWRead
AI37kVAR aModbus 400126; not polled by defaultkVARRead
AI38kVAR bModbus 400127; not polled by defaultkVARRead
AI39kVAR cModbus 400128; not polled by defaultkVARRead
AI40kVA aModbus 400129; not polled by defaultkVARead
AI41kVA bModbus 400130; not polled by defaultkVARead
AI42kVA cModbus 400131; not polled by defaultkVARead
AI43kW demandModbus 400132; not polled by defaultkWRead
AI44kW peak demandModbus 400133; not polled by defaultkWRead
AI45kVAR demandModbus 400134kVARRead
AI46kVA demandModbus 400135kVARead
AI47kVAR peak demandModbus 400136; not polled by defaultkVARRead
AI48kVA peak demandModbus 400137; not polled by defaultkVARead
AImin49kWh delModbus 400138; not polled by defaultkWhRead
AI50kWh recModbus 400140; not polled by defaultkWhRead
AI51kVARh delModbus 400142; not polled by defaultRead
AI52kVARh recModbus 400144; not polled by defaultRead
AI53kVAh del+recModbus 400146; not polled by defaultRead
AI54V1 THDModbus 400148; not polled by defaultRead
AI55V2 THDModbus 400149; not polled by defaultRead
AI56V3 THDModbus 400150; not polled by defaultRead
AI57I1 THDModbus 400151; not polled by defaultRead
AI58I2 THDModbus 400152; not polled by defaultRead
AI59I3 THDModbus 400153; not polled by defaultRead
AI60I a demandModbus 400154; not polled by defaultARead
AI61I b demandModbus 400155; not polled by defaultARead
AI62I c demandModbus 400156; not polled by defaultARead
AI63I a peak demandModbus 400157; not polled by defaultARead
AI64I b peak demandModbus 400158; not polled by defaultARead
AI65I c peak demandModbus 400159; not polled by defaultARead
AI66kWh a delModbus 400160; not polled by defaultkWhRead
AI67kWh b delModbus 400162; not polled by defaultkWhRead
AI68kWh c delModbus 400164; not polled by defaultkWhRead
AI69kWh a recModbus 400166; not polled by defaultkWhRead
AI70kWh b recModbus 400168; not polled by defaultkWhRead
AI71kWh c recModbus 400170; not polled by defaultkWhRead
AI72kVARh a delModbus 400172; not polled by defaultRead
AI73kVARh b delModbus 400174; not polled by defaultRead
AI74kVARh c delModbus 400176; not polled by defaultRead
AI75kVARh a recModbus 400178; not polled by defaultRead
AI76kVARh b recModbus 400180; not polled by defaultRead
AI77kVARh c recModbus 400182; not polled by defaultRead
AI78kVAh aModbus 400184; not polled by defaultRead
AI79kVAh bModbus 400186; not polled by defaultRead
AI80kVAh cModbus 400188; not polled by defaultRead
AI81kWh delModbus 401138; not polled by defaultRead
AI82kWh recModbus 401140; not polled by defaultRead
AI83kVARh delModbus 401142; not polled by defaultRead
AI84kVARh recModbus 401144; not polled by defaultRead
AI85kVAh del+recModbus 401146; not polled by defaultRead
AI86kWh a delModbus 401160; not polled by defaultRead
AI87kWh b delModbus 401162; not polled by defaultRead
AI88kWh c delModbus 401164; not polled by defaultRead
AI89kWh a recModbus 401166; not polled by defaultRead
AI90kWh b recModbus 401168; not polled by defaultRead
AI91kWh c recModbus 401170; not polled by defaultRead
AI92kVARh a delModbus 401172; not polled by defaultRead
AI93kVARh b delModbus 401174; not polled by defaultRead
AI94kVARh c delModbus 401176; not polled by defaultRead
AI95kVARh a recModbus 401178; not polled by defaultRead
AI96kVARh b recModbus 401180; not polled by defaultRead
AI97kVARh c recModbus 401182; not polled by defaultRead
AI98kVAh aModbus 401184; not polled by defaultRead
AI99kVAh bModbus 401186; not polled by defaultRead
AI100kVAh cModbus 401188; not polled by defaultRead
AI101Configuration via display passwordModbus 404000; not polled by defaultRead
AI102Volts ModeModbus 404001; not polled by defaultRead
AI103PT PrimaryModbus 404002; not polled by defaultRead
AI104PT SecondaryModbus 404003; not polled by defaultRead
AI105CT PrimaryModbus 404004; not polled by defaultRead
AI106CT SecondaryModbus 404005; not polled by defaultRead
AI107V1 PolarityModbus 404006; not polled by defaultRead
AI108V2 PolarityModbus 404007; not polled by defaultRead
AI109V3 PolarityModbus 404008; not polled by defaultRead
AI110I1 PolarityModbus 404009; not polled by defaultRead
AI111I2 PolarityModbus 404010; not polled by defaultRead
AI112I3 PolarityModbus 404011; not polled by defaultRead
AI113Programmable Voltage Scale (PVS)Modbus 404012; not polled by defaultRead
AI114Programmable Current Scale (PIS)Modbus 404013; not polled by defaultRead
AI115Programmable Neutral Current Scale (PnS)Modbus 404014; not polled by defaultRead
AI116Programmable Power Scale (PPS)Modbus 404015; not polled by defaultRead
AI117Demand Sub IntervalModbus 404016; not polled by defaultRead
AI118Demand #Sub IntervalsModbus 404017; not polled by defaultRead
AI119Kt Digital Output #1Modbus 404018; not polled by defaultRead
AI120Kt Digital Output #2Modbus 404019; not polled by defaultRead
AI121Output Mode Digital Output #1Modbus 404021; not polled by defaultRead
AI122Output Mode Digital Output #2Modbus 404022; not polled by defaultRead
AI123Baud RateModbus 404024; not polled by defaultRead
AI124ProtocolModbus 404025; not polled by defaultRead
AI125Unit IDModbus 404026; not polled by defaultRead
AI126RTS DelayModbus 404027; not polled by defaultRead
AI127Display Scroll TimeModbus 404028; not polled by defaultRead
AI128Display Refresh PeriodModbus 404029; not polled by defaultRead
AI129PT ScaleModbus 404030; not polled by defaultRead
AO130Energy ResetModbus 402001; not polled by defaultCommand
AO131Peak Power Demand ResetModbus 402002; not polled by defaultCommand
AO132Peak Current Demand ResetModbus 402003; not polled by defaultCommand
AO133Digital Output #1Modbus 402004; not polled by defaultCommand
AO134Digital Output #2Modbus 402005; not polled by defaultCommand
Object ID lookup: Contemporary Controls BASgatewayLX ION6200 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric PowerLogic ION6200 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX

How many BACnet points does the Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX have?

This list has 134 BACnet objects: 129 analog inputs, 5 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX BACnet points are writable?

5 of the 134 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Schneider_Electric_ION6200_a (Schneider_Electric_ION6200_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Schneider_Electric_ION6200.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX?

Start with AI 31 kW total (Total kW); AI 49 kWh del (kWh delivered); AI 18 Vll avg (Average line-line voltage); AI 22 I avg (Average current); AI 27 PF sign total (Total power factor (signed)); AI 26 Frequency (Frequency).

How do I check these points on the real Schneider Electric PowerLogic ION6200 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Schneider_Electric_ION6200_a · Schneider_Electric_ION6200_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.