Room operating unit (thermostat / sensor) · BACnet points list
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Thermokon Thanos: 590 objects (72 AI, 456 AO, 62 BO), 192 polled by default. Most of the map is configuration: display, illumination, set point ranges and labels, fan stages, occupancy and two controller blocks (parameters, limits, fan coil interaction). Live values - internal temperature and humidity, effective set points, fan stage, occupancy, key states and controller outputs - are inputs and are unpolled by default.
This page lists 590 BACnet objects for the Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX — 518 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Thermokon Thanos room operating unit via BASgatewayLX
- Equipment
- Room operating unit (thermostat / sensor)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 590 (518 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Tick the live values (temperature, humidity, effective set point, fan stage, occupancy, controller outputs) before mapping; the polled defaults are mostly controller 1 and 2 parameters.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 446 | Temperature internal sensor | Room temperature (internal sensor) | Read |
| AI 447 | Humidity internal sensor | Room humidity (internal sensor) | Read |
| AI 435 | Set point effective 1 (Default set point + set point offset) | Effective set point 1 | Read |
| AI 448 | Current fan stage | Current fan stage | Read |
| AI 449 | Current room occupancy | Current room occupancy | Read |
| AI 450 | Control variable Heating Controller 1 | Controller 1 heating output | Read |
| AI 451 | Control variable Cooling Controller 1 | Controller 1 cooling output | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- The polled defaults are configuration outputs; writing them changes the device setup.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Device code | Modbus 400001; not polled by default | Read | ||
| AI | 2 | Firmware version | Modbus 400002; not polled by default | Read | ||
| AI | 3 | Device version | Modbus 400003; not polled by default | Read | ||
| AI | 4 | Humidity sensor existing | Modbus 400004; not polled by default | Read | ||
| AO | 5 | Rotation Display | Modbus 400005; not polled by default | Command | ||
| AO | 6 | Device location identification | Modbus 400006; not polled by default | Command | ||
| AO | 7 | Temperature offset | Modbus 400007; not polled by default | Command | ||
| AO | 8 | Humidity offset | Modbus 400008; not polled by default | Command | ||
| AO | 9 | Setting of the maximal available fan stages | Modbus 400009; not polled by default | Command | ||
| AO | 10 | Status fan stage after reset | Modbus 400010; not polled by default | Command | ||
| AO | 11 | Status room occupancy after reset | Modbus 400011; not polled by default | Command | ||
| AO | 12 | Bypass time room occupancy | Modbus 400012; not polled by default | Command | ||
| AO | 13 | Time cleaning function | Modbus 400013; not polled by default | Command | ||
| AO | 14 | Device type | Modbus 400014; not polled by default | Command | ||
| AO | 15 | Minimum response delay time [ms] | Modbus 400015; not polled by default | Command | ||
| AO | 16 | Background illumination LCD | Modbus 400016; not polled by default | Command | ||
| AI | 17 | Contrast | Modbus 400017; not polled by default | Read | ||
| AO | 18 | Intensity background illumination LCD Standard-Mode | Modbus 400018; not polled by default | Command | ||
| AO | 19 | Intensity background illumination LCD Idle-Mode | Modbus 400019; not polled by default | Command | ||
| AO | 20 | Intensity background illumination LCD Standby-Mode | Modbus 400020; not polled by default | Command | ||
| AO | 21 | Intensity background illumination keypad Standard | Modbus 400021; not polled by default | Command | ||
| AO | 22 | Intensity background illumination keypad Idle | Modbus 400022; not polled by default | Command | ||
| AO | 23 | Intensity background illumination keypad Standby | Modbus 400023; not polled by default | Command | ||
| AO | 24 | Time to switch Standard- in Idle mode | Modbus 400024; not polled by default | Command | ||
| AO | 25 | Time to switch Idle- in Standby mode | Modbus 400025; not polled by default | Command | ||
| AO | 26 | Duration of displaying a menu point | Modbus 400026; not polled by default | Command | ||
| AO | 27 | Duration of displaying an operation | Modbus 400027; not polled by default | Command | ||
| AO | 28 | Date display | Modbus 400028; not polled by default | Command | ||
| AO | 29 | Time display | Modbus 400029; not polled by default | Command | ||
| AO | 30 | Time mode | Modbus 400030; not polled by default | Command | ||
| AO | 31 | Register to configure available submenus (only S version!!) | Modbus 400031; not polled by default | Command | ||
| AO | 32 | Refresh interval of LCD in seconds | Modbus 400032; not polled by default | Command | ||
| AO | 33 | Display time of single submenus (only S version!!) | Modbus 400033; not polled by default | Command | ||
| AO | 34 | Upper range of adjustment Set point offset Set point 1 | Modbus 400034; not polled by default | Command | ||
| AO | 35 | Lower range of adjustment Set point offset Set point 1 | Modbus 400035; not polled by default | Command | ||
| AO | 36 | Step size set point adjustment Set point 1 | Modbus 400036; not polled by default | Command | ||
| AO | 37 | Default set point after reset Set point 1 | Modbus 400037; not polled by default | Command | ||
| AO | 38 | 1. ASCII symbol unit Set point 1 | Modbus 400038; not polled by default | Command | ||
| AO | 39 | 2. ASCII symbol unit Set point 1 | Modbus 400039; not polled by default | Command | ||
| AO | 40 | 3. ASCII symbol unit Set point 1 | Modbus 400040; not polled by default | Command | ||
| AO | 41 | 1. ASCII symbol set point description Set point 1 | Modbus 400041; not polled by default | Command | ||
| AO | 42 | 2. ASCII symbol set point description Set point 1 | Modbus 400042; not polled by default | Command | ||
| AO | 43 | 3. ASCII symbol set point description Set point 1 | Modbus 400043; not polled by default | Command | ||
| AO | 44 | 4. ASCII symbol set point description Set point 1 | Modbus 400044; not polled by default | Command | ||
| AO | 45 | Upper range of adjustment Set point adjustment Set point 2 | Modbus 400045; not polled by default | Command | ||
| AO | 46 | Lower range of adjustment Set point adjustment Set point 2 | Modbus 400046; not polled by default | Command | ||
| AO | 47 | Step size set point adjustment Set point 2 | Modbus 400047; not polled by default | Command | ||
| AO | 48 | Default set point after reset Set point 2 | Modbus 400048; not polled by default | Command | ||
| AO | 49 | 1. ASCII symbol unit Set point 2 | Modbus 400049; not polled by default | Command | ||
| AO | 50 | 2. ASCII symbol unit Set point 2 | Modbus 400050; not polled by default | Command | ||
| AO | 51 | 3. ASCII symbol unit Set point 2 | Modbus 400051; not polled by default | Command | ||
| AO | 52 | 1. ASCII symbol set point description) Set point 2 | Modbus 400052; not polled by default | Command | ||
| AO | 53 | 2. ASCII symbol set point description Set point 2 | Modbus 400053; not polled by default | Command | ||
| AO | 54 | 3. ASCII symbol set point description Set point 2 | Modbus 400054; not polled by default | Command | ||
| AO | 55 | 4. ASCII symbol set point description Set point 2 | Modbus 400055; not polled by default | Command | ||
| AO | 56 | Upper range of adjustment Set point offset (Set point 3 | Modbus 400056; not polled by default | Command | ||
| AO | 57 | Lower range of adjustment Set point offset Set point 3 | Modbus 400057; not polled by default | Command | ||
| AO | 58 | Step size set point adjustment Set point 3 | Modbus 400058; not polled by default | Command | ||
| AO | 59 | Default set point 3 after reset Set point 3 | Modbus 400059; not polled by default | Command | ||
| AO | 60 | 1. ASCII symbol unit Set point 3 | Modbus 400060; not polled by default | Command | ||
| AO | 61 | 2. ASCII symbol unit Set point 3 | Modbus 400061; not polled by default | Command | ||
| AO | 62 | 3. ASCII symbol unit Set point 3 | Modbus 400062; not polled by default | Command | ||
| AO | 63 | 1. ASCII symbol set point description Set point 3 | Modbus 400063; not polled by default | Command | ||
| AO | 64 | 2. ASCII symbol set point description Set point 3 | Modbus 400064; not polled by default | Command | ||
| AO | 65 | 3. ASCII symbol set point description Set point 3 | Modbus 400065; not polled by default | Command | ||
| AO | 66 | 4. ASCII symbol set point description Set point 3 | Modbus 400066; not polled by default | Command | ||
| AO | 67 | Upper range of adjustment Set point offset Set point 4 | Modbus 400067; not polled by default | Command | ||
| AO | 68 | Lower range of adjustment Set point offset Set point 4 | Modbus 400068; not polled by default | Command | ||
| AO | 69 | Step size set point adjustment Set point 4 | Modbus 400069; not polled by default | Command | ||
| AO | 70 | Default set point 4 after reset Set point 4 | Modbus 400070; not polled by default | Command | ||
| AO | 71 | 1. ASCII symbol unit Set point 4 | Modbus 400071; not polled by default | Command | ||
| AO | 72 | 2. ASCII symbol unit Set point 4 | Modbus 400072; not polled by default | Command | ||
| AO | 73 | 3. ASCII symbol unit Set point 4 | Modbus 400073; not polled by default | Command | ||
| AO | 74 | 1. ASCII symbol set point description Set point 4 | Modbus 400074; not polled by default | Command | ||
| AO | 75 | 2. ASCII symbol set point description Set point 4 | Modbus 400075; not polled by default | Command | ||
| AO | 76 | 3. ASCII symbol set point description Set point 4 | Modbus 400076; not polled by default | Command | ||
| AO | 77 | 4. ASCII symbol set point description Set point 4 | Modbus 400077; not polled by default | Command | ||
| AO | 78 | Upper range of adjustment Set point offset Set point 5 | Modbus 400078; not polled by default | Command | ||
| AO | 79 | Lower range of adjustment Set point offset Set point 5 | Modbus 400079; not polled by default | Command | ||
| AO | 80 | Step size set point adjustment Set point 5 | Modbus 400080; not polled by default | Command | ||
| AO | 81 | Default set point 5 after reset Set point 5 | Modbus 400081; not polled by default | Command | ||
| AO | 82 | 1. ASCII symbol unit Set point 5 | Modbus 400082; not polled by default | Command | ||
| AO | 83 | 2. ASCII symbol unit Set point 5 | Modbus 400083; not polled by default | Command | ||
| AO | 84 | 3. ASCII symbol unit Set point 5 | Modbus 400084; not polled by default | Command | ||
| AO | 85 | 1. ASCII symbol set point description Set point 5 | Modbus 400085; not polled by default | Command | ||
| AO | 86 | 2. ASCII symbol set point description Set point 5 | Modbus 400086; not polled by default | Command | ||
| AO | 87 | 3. ASCII symbol set point description Set point 5 | Modbus 400087; not polled by default | Command | ||
| AO | 88 | 4. ASCII symbol set point description Set point 5 | Modbus 400088; not polled by default | Command | ||
| AO | 89 | Upper range of adjustment Set point offset Set point 6 | Modbus 400089; not polled by default | Command | ||
| AO | 90 | Lower range of adjustment Set point offset Set point 6 | Modbus 400090; not polled by default | Command | ||
| AO | 91 | Step size set point adjustment Set point 6 | Modbus 400091; not polled by default | Command | ||
| AO | 92 | Default set point 5 after reset Set point 6 | Modbus 400092; not polled by default | Command | ||
| AO | 93 | 1. ASCII symbol unit Set point 6 | Modbus 400093; not polled by default | Command | ||
| AO | 94 | 2. ASCII symbol unit Set point 6 | Modbus 400094; not polled by default | Command | ||
| AO | 95 | 3. ASCII symbol unit Set point 6 | Modbus 400095; not polled by default | Command | ||
| AO | 96 | 1. ASCII symbol set point description Set point 6 | Modbus 400096; not polled by default | Command | ||
| AO | 97 | 2. ASCII symbol set point description Set point 6 | Modbus 400097; not polled by default | Command | ||
| AO | 98 | 3. ASCII symbol set point description Set point 6 | Modbus 400098; not polled by default | Command | ||
| AO | 99 | 4. ASCII symbol set point description Set point 6 | Modbus 400099; not polled by default | Command | ||
| AO | 100 | 1. ASCII symbol unit External value 1 | Modbus 400100; not polled by default | Command | ||
| AO | 101 | 2. ASCII symbol unit External value 1 | Modbus 400101; not polled by default | Command | ||
| AO | 102 | 3. ASCII symbol unit External value 1 | Modbus 400102; not polled by default | Command | ||
| AO | 103 | 1. ASCII symbol description External value 1 | Modbus 400103; not polled by default | Command | ||
| AO | 104 | 2. ASCII symbol description External value 1 | Modbus 400104; not polled by default | Command | ||
| AO | 105 | 3. ASCII symbol description External value 1 | Modbus 400105; not polled by default | Command | ||
| AO | 106 | 4. ASCII symbol description External value 1 | Modbus 400106; not polled by default | Command | ||
| AO | 107 | 1. ASCII symbol unit External value 2 | Modbus 400107; not polled by default | Command | ||
| AO | 108 | 2. ASCII symbol unit External value 2 | Modbus 400108; not polled by default | Command | ||
| AO | 109 | 3. ASCII symbol unit External value 2 | Modbus 400109; not polled by default | Command | ||
| AO | 110 | 1. ASCII symbol description External value 2 | Modbus 400110; not polled by default | Command | ||
| AO | 111 | 2. ASCII symbol description External value 2 | Modbus 400111; not polled by default | Command | ||
| AO | 112 | 3. ASCII symbol description External value 2 | Modbus 400112; not polled by default | Command | ||
| AO | 113 | 4. ASCII symbol description External value 2 | Modbus 400113; not polled by default | Command | ||
| AO | 114 | 1. ASCII symbol unit External value 3 | Modbus 400114; not polled by default | Command | ||
| AO | 115 | 2. ASCII symbol unit External value 3 | Modbus 400115; not polled by default | Command | ||
| AO | 116 | 3. ASCII symbol unit External value 3 | Modbus 400116; not polled by default | Command | ||
| AO | 117 | 1. ASCII symbol description External value 3 | Modbus 400117; not polled by default | Command | ||
| AO | 118 | 2. ASCII symbol description External value 3 | Modbus 400118; not polled by default | Command | ||
| AO | 119 | 3. ASCII symbol description External value 3 | Modbus 400119; not polled by default | Command | ||
| AO | 120 | 4. ASCII symbol description External value 3 | Modbus 400120; not polled by default | Command | ||
| AO | 121 | 1. ASCII symbol unit External value 4 | Modbus 400121; not polled by default | Command | ||
| AO | 122 | 2. ASCII symbol unit External value 4 | Modbus 400122; not polled by default | Command | ||
| AO | 123 | 3. ASCII symbol unit External value 4 | Modbus 400123; not polled by default | Command | ||
| AO | 124 | 1. ASCII symbol description External value 4 | Modbus 400124; not polled by default | Command | ||
| AO | 125 | 2. ASCII symbol description External value 4 | Modbus 400125; not polled by default | Command | ||
| AO | 126 | 3. ASCII symbol description External value 4 | Modbus 400126; not polled by default | Command | ||
| AO | 127 | 4. ASCII symbol description External value 4 | Modbus 400127; not polled by default | Command | ||
| AO | 128 | 1. ASCII symbol unit External value 5 | Modbus 400128; not polled by default | Command | ||
| AO | 129 | 2. ASCII symbol unit External value 5 | Modbus 400129; not polled by default | Command | ||
| AO | 130 | 3. ASCII symbol unit External value 5 | Modbus 400130; not polled by default | Command | ||
| AO | 131 | 1. ASCII symbol description External value | Modbus 400131; not polled by default | Command | ||
| AO | 132 | 2. ASCII symbol description External value 5 | Modbus 400132; not polled by default | Command | ||
| AO | 133 | 3. ASCII symbol description External value 5 | Modbus 400133; not polled by default | Command | ||
| AO | 134 | 4. ASCII symbol description External value 5 | Modbus 400134; not polled by default | Command | ||
| AO | 135 | 1. ASCII symbol unit External value 6 | Modbus 400135; not polled by default | Command | ||
| AO | 136 | 2. ASCII symbol unit External value 6 | Modbus 400136; not polled by default | Command | ||
| AO | 137 | 3. ASCII symbol unit External value 6 | Modbus 400137; not polled by default | Command | ||
| AO | 138 | 1. ASCII symbol description External value 6 | Modbus 400138; not polled by default | Command | ||
| AO | 139 | 2. ASCII symbol description External value 6 | Modbus 400139; not polled by default | Command | ||
| AO | 140 | 3. ASCII symbol description External value 6 | Modbus 400140; not polled by default | Command | ||
| AO | 141 | 4. ASCII symbol description External value 6 | Modbus 400141; not polled by default | Command | ||
| AO | 142 | Configuration functional clip | Modbus 400142; not polled by default | Command | ||
| AO | 143 | Configuration menu key 1 | Modbus 400143; not polled by default | Command | ||
| AO | 144 | Configuration menu key 4 | Modbus 400144; not polled by default | Command | ||
| AO | 145 | onfiguration menu key 5 | Modbus 400145; not polled by default | Command | ||
| AO | 146 | Configuration menu key 6 | Modbus 400146; not polled by default | Command | ||
| AO | 147 | Configuration menu key 7 | Modbus 400147; not polled by default | Command | ||
| AO | 148 | Configuration Direct key 8 | Modbus 400148; not polled by default | Command | ||
| AO | 149 | Configuration Direct key 9 | Modbus 400149; not polled by default | Command | ||
| AO | 150 | Configuration Direct key 10 | Modbus 400150; not polled by default | Command | ||
| AO | 151 | Configuration Direct key 11 | Modbus 400151; not polled by default | Command | ||
| AO | 152 | Configuration Direct key 12 | Modbus 400152; not polled by default | Command | ||
| AO | 153 | Configuration Direct key 13 | Modbus 400153; not polled by default | Command | ||
| AO | 154 | Configuration Direct key 14 | Modbus 400154; not polled by default | Command | ||
| AO | 155 | Configuration Direct key 15 | Modbus 400155; not polled by default | Command | ||
| AO | 156 | Lock external defaults | Modbus 400156; not polled by default | Command | ||
| AO | 157 | Controller 1 Default set point after reset Comfort | Modbus 400157 | Command | ||
| AO | 158 | Controller 1 Set point difference Standby | Modbus 400158 | Command | ||
| AO | 159 | Controller 1 Set point difference Unoccupied | Modbus 400159 | Command | ||
| AO | 160 | Controller 1 Controller parameter XP Heating | Modbus 400160 | Command | ||
| AO | 161 | Controller 1 Controller parameter TN Heating | Modbus 400161 | Command | ||
| AO | 162 | Controller 1 Controller parameter XP Cooling | Modbus 400162 | Command | ||
| AO | 163 | Controller 1 Controller parameter TN Cooling | Modbus 400163 | Command | ||
| AO | 164 | Controller 1 Dead zone | Modbus 400164 | Command | ||
| AO | 165 | Controller 1 Minimum control variable Heating | Modbus 400165 | Command | ||
| AO | 166 | Controller 1 Maximum control variable Heating | Modbus 400166 | Command | ||
| AO | 167 | Controller 1 Minimum control variable Cooling | Modbus 400167 | Command | ||
| AO | 168 | Controller 1 Maximum control variable Cooling | Modbus 400168 | Command | ||
| AO | 169 | Controller 1 Controller mode after reset | Modbus 400169 | Command | ||
| AO | 170 | Controller 1 Selection actual value | Modbus 400170 | Command | ||
| AO | 171 | Controller 1 Selection set value | Modbus 400171 | Command | ||
| AO | 172 | Controller 1 Selection energy hold-off | Modbus 400172 | Command | ||
| AO | 173 | Controller 1 Selection Un-/Occupied | Modbus 400173 | Command | ||
| AO | 174 | Controller 1 Frost protection-Set point | Modbus 400174 | Command | ||
| AO | 175 | Controller 1 Minimum control variable | Modbus 400175 | Command | ||
| AO | 176 | Controller 1 Controller has access to symbols Heating Cooling | Modbus 400176 | Command | ||
| AO | 177 | Controller 1 Number of fan stages | Modbus 400177 | Command | ||
| AO | 178 | Controller 1 Control variable threshold for fan stage 1 Heating | Modbus 400178 | Command | ||
| AO | 179 | Controller 1 Control variable threshold for fan stage 2 Heating | Modbus 400179 | Command | ||
| AO | 180 | Controller 1 Control variable threshold for fan stage 3 Heating | Modbus 400180 | Command | ||
| AO | 181 | Controller 1 Control variable threshold for fan stage 1 Cooling | Modbus 400181 | Command | ||
| AO | 182 | Controller 1 Control variable threshold for fan stage 2 Cooling | Modbus 400182 | Command | ||
| AO | 183 | Controller 1 Control variable threshold for fan stage 3 Cooling | Modbus 400183 | Command | ||
| AO | 184 | Controller 1 PWM cycle time | Modbus 400184 | Command | ||
| AO | 185 | Controller 1 Select fan coil X interacts with Main-Fan control | Modbus 400185 | Command | ||
| AO | 186 | Controller 1 Display dew point signal of controller | Modbus 400186 | Command | ||
| AO | 187 | Controller 1 Bypass time | Modbus 400187 | Command | ||
| AO | 188 | Controller 1 Minimal ON time for fan coil | Modbus 400188 | Command | ||
| AO | 189 | Controller 2 Default set point after reset Comfort | Modbus 400189 | Command | ||
| AO | 190 | Controller 2 Set point difference Standby | Modbus 400190 | Command | ||
| AO | 191 | Controller 2 Set point difference Unoccupied | Modbus 400191 | Command | ||
| AO | 192 | Controller 2 Controller parameter XP Heating | Modbus 400192 | Command | ||
| AO | 193 | Controller 2 Controller parameter TN Heating | Modbus 400193 | Command | ||
| AO | 194 | Controller 2 Controller parameter XP Cooling | Modbus 400194 | Command | ||
| AO | 195 | Controller 2 Controller parameter TN Cooling | Modbus 400195 | Command | ||
| AO | 196 | Controller 2 Dead zone | Modbus 400196 | Command | ||
| AO | 197 | Controller 2 Minimum control variable Heating | Modbus 400197 | Command | ||
| AO | 198 | Controller 2 Maximum control variable Heating | Modbus 400198 | Command | ||
| AO | 199 | Controller 2 Minimum control variable Cooling | Modbus 400199 | Command | ||
| AO | 200 | Controller 2 Maximum control variable Cooling | Modbus 400200 | Command | ||
| AO | 201 | Controller 2 Controller mode after reset | Modbus 400201 | Command | ||
| AO | 202 | Controller 2 Selection actual value | Modbus 400202 | Command | ||
| AO | 203 | Controller 2 Selection set value | Modbus 400203 | Command | ||
| AO | 204 | Controller 2 Selection energy hold-off | Modbus 400204 | Command | ||
| AO | 205 | Controller 2 Selection Un-/Occupied | Modbus 400205 | Command | ||
| AO | 206 | Controller 2 Frost protection-Set point | Modbus 400206 | Command | ||
| AO | 207 | Controller 2 Minimum control variable | Modbus 400207 | Command | ||
| AO | 208 | Controller 2 Controller has access to symbols Heating Cooling | Modbus 400208 | Command | ||
| AO | 209 | Controller 2 Number of fan stages | Modbus 400209 | Command | ||
| AO | 210 | Controller 2 Control variable threshold for fan stage 1 Heating | Modbus 400210 | Command | ||
| AO | 211 | Controller 2 Control variable threshold for fan stage 2 Heating | Modbus 400211 | Command | ||
| AO | 212 | Controller 2 Control variable threshold for fan stage 3 Heating | Modbus 400212 | Command | ||
| AO | 213 | Controller 2 Control variable threshold for fan stage 1 Cooling | Modbus 400213 | Command | ||
| AO | 214 | Controller 2 Control variable threshold for fan stage 2 Cooling | Modbus 400214 | Command | ||
| AO | 215 | Controller 2 Control variable threshold for fan stage 3 Cooling | Modbus 400215 | Command | ||
| AO | 216 | Controller 2 PWM cycle time | Modbus 400216 | Command | ||
| AO | 217 | Controller 2 Select fan coil X interacts with Main-Fan control | Modbus 400217 | Command | ||
| AO | 218 | Controller 2 Display dew point signal of controller | Modbus 400218 | Command | ||
| AO | 219 | Controller 2 Bypass time | Modbus 400219 | Command | ||
| AO | 220 | Controller 2 Minimal ON time for fan coil | Modbus 400220 | Command | ||
| AO | 221 | Controller 3 Default set point after reset Comfort | Modbus 400221 | Command | ||
| AO | 222 | Controller 3 Set point difference Standby | Modbus 400222 | Command | ||
| AO | 223 | Controller 3 Set point difference Unoccupied | Modbus 400223 | Command | ||
| AO | 224 | Controller 3 Controller parameter XP Heating | Modbus 400224 | Command | ||
| AO | 225 | Controller 3 Controller parameter TN Heating | Modbus 400225 | Command | ||
| AO | 226 | Controller 3 Controller parameter XP Cooling | Modbus 400226 | Command | ||
| AO | 227 | Controller 3 Controller parameter TN Cooling | Modbus 400227 | Command | ||
| AO | 228 | Controller 3 Dead zone | Modbus 400228 | Command | ||
| AO | 229 | Controller 3 Minimum control variable Heating | Modbus 400229 | Command | ||
| AO | 230 | Controller 3 Maximum control variable Heating | Modbus 400230 | Command | ||
| AO | 231 | Controller 3 Minimum control variable Cooling | Modbus 400231 | Command | ||
| AO | 232 | Controller 3 Maximum control variable Cooling | Modbus 400232 | Command | ||
| AO | 233 | Controller 3 Controller mode after reset | Modbus 400233 | Command | ||
| AO | 234 | Controller 3 Selection actual value | Modbus 400234 | Command | ||
| AO | 235 | Controller 3 Selection set value | Modbus 400235 | Command | ||
| AO | 236 | Controller 3 Selection energy hold-off | Modbus 400236 | Command | ||
| AO | 237 | Controller 3 Selection Un-/Occupied | Modbus 400237 | Command | ||
| AO | 238 | Controller 3 Frost protection-Set point | Modbus 400238 | Command | ||
| AO | 239 | Controller 3 Minimum control variable | Modbus 400239 | Command | ||
| AO | 240 | Controller 3 Controller has access to symbols Heating Cooling | Modbus 400240 | Command | ||
| AO | 241 | Controller 3 Number of fan stages | Modbus 400241 | Command | ||
| AO | 242 | Controller 3 Control variable threshold for fan stage 1 Heating | Modbus 400242 | Command | ||
| AO | 243 | Controller 3 Control variable threshold for fan stage 2 Heating | Modbus 400243 | Command | ||
| AO | 244 | Controller 3 Control variable threshold for fan stage 3 Heating | Modbus 400244 | Command | ||
| AO | 245 | Controller 3 Control variable threshold for fan stage 1 Cooling | Modbus 400245 | Command | ||
| AO | 246 | Controller 3 Control variable threshold for fan stage 2 Cooling | Modbus 400246 | Command | ||
| AO | 247 | Controller 3 Control variable threshold for fan stage 3 Cooling | Modbus 400247 | Command | ||
| AO | 248 | Controller 3 PWM cycle time | Modbus 400248 | Command | ||
| AO | 249 | Controller 3 Select fan coil X interacts with Main-Fan control | Modbus 400249 | Command | ||
| AO | 250 | Controller 3 Display dew point signal of controller | Modbus 400250 | Command | ||
| AO | 251 | Controller 3 Bypass time | Modbus 400251 | Command | ||
| AO | 252 | Controller 3 Minimal ON time for fan coil | Modbus 400252 | Command | ||
| AO | 253 | Controller 4 Default set point after reset Comfort | Modbus 400253 | Command | ||
| AO | 254 | Controller 4 Set point difference Standby | Modbus 400254 | Command | ||
| AO | 255 | Controller 4 Set point difference Unoccupied | Modbus 400255 | Command | ||
| AO | 256 | Controller 4 Controller parameter XP Heating | Modbus 400256 | Command | ||
| AO | 257 | Controller 4 Controller parameter TN Heating | Modbus 400257 | Command | ||
| AO | 258 | Controller 4 Controller parameter XP Cooling | Modbus 400258 | Command | ||
| AO | 259 | Controller 4 Controller parameter TN Cooling | Modbus 400259 | Command | ||
| AO | 260 | Controller 4 Dead zone | Modbus 400260 | Command | ||
| AO | 261 | Controller 4 Minimum control variable Heating | Modbus 400261 | Command | ||
| AO | 262 | Controller 4 Maximum control variable Heating | Modbus 400262 | Command | ||
| AO | 263 | Controller 4 Minimum control variable Cooling | Modbus 400263 | Command | ||
| AO | 264 | Controller 4 Maximum control variable Cooling | Modbus 400264 | Command | ||
| AO | 265 | Controller 4 Controller mode after reset | Modbus 400265 | Command | ||
| AO | 266 | Controller 4 Selection actual value | Modbus 400266 | Command | ||
| AO | 267 | Controller 4 Selection set value | Modbus 400267 | Command | ||
| AO | 268 | Controller 4 Selection energy hold-off | Modbus 400268 | Command | ||
| AO | 269 | Controller 4 Selection Un-/Occupied | Modbus 400269 | Command | ||
| AO | 270 | Controller 4 Frost protection-Set point | Modbus 400270 | Command | ||
| AO | 271 | Controller 4 Minimum control variable | Modbus 400271 | Command | ||
| AO | 272 | Controller 4 Controller has access to symbols Heating Cooling | Modbus 400272 | Command | ||
| AO | 273 | Controller 4 Number of fan stages | Modbus 400273 | Command | ||
| AO | 274 | Controller 4 Control variable threshold for fan stage 1 Heating | Modbus 400274 | Command | ||
| AO | 275 | Controller 4 Control variable threshold for fan stage 2 Heating | Modbus 400275 | Command | ||
| AO | 276 | Controller 4 Control variable threshold for fan stage 3 Heating | Modbus 400276 | Command | ||
| AO | 277 | Controller 4 Control variable threshold for fan stage 1 Cooling | Modbus 400277 | Command | ||
| AO | 278 | Controller 4 Control variable threshold for fan stage 2 Cooling | Modbus 400278 | Command | ||
| AO | 279 | Controller 4 Control variable threshold for fan stage 3 Cooling | Modbus 400279 | Command | ||
| AO | 280 | Controller 4 PWM cycle time | Modbus 400280 | Command | ||
| AO | 281 | Controller 4 Select fan coil X interacts with Main-Fan control | Modbus 400281 | Command | ||
| AO | 282 | Controller 4 Display dew point signal of controller | Modbus 400282 | Command | ||
| AO | 283 | Controller 4 Bypass time | Modbus 400283 | Command | ||
| AO | 284 | Controller 4 Minimal ON time for fan coil | Modbus 400284 | Command | ||
| AO | 285 | Controller 5 Default set point after reset Comfort | Modbus 400285 | Command | ||
| AO | 286 | Controller 5 Set point difference Standby | Modbus 400286 | Command | ||
| AO | 287 | Controller 5 Set point difference Unoccupied | Modbus 400287 | Command | ||
| AO | 288 | Controller 5 Controller parameter XP Heating | Modbus 400288 | Command | ||
| AO | 289 | Controller 5 Controller parameter TN Heating | Modbus 400289 | Command | ||
| AO | 290 | Controller 5 Controller parameter XP Cooling | Modbus 400290 | Command | ||
| AO | 291 | Controller 5 Controller parameter TN Cooling | Modbus 400291 | Command | ||
| AO | 292 | Controller 5 Dead zone | Modbus 400292 | Command | ||
| AO | 293 | Controller 5 Minimum control variable Heating | Modbus 400293 | Command | ||
| AO | 294 | Controller 5 Maximum control variable Heating | Modbus 400294 | Command | ||
| AO | 295 | Controller 5 Minimum control variable Cooling | Modbus 400295 | Command | ||
| AO | 296 | Controller 5 Maximum control variable Cooling | Modbus 400296 | Command | ||
| AO | 297 | Controller 5 Controller mode after reset | Modbus 400297 | Command | ||
| AO | 298 | Controller 5 Selection actual value | Modbus 400298 | Command | ||
| AO | 299 | Controller 5 Selection set value | Modbus 400299 | Command | ||
| AO | 300 | Controller 5 Selection energy hold-off | Modbus 400300 | Command | ||
| AO | 301 | Controller 5 Selection Un-/Occupied | Modbus 400301 | Command | ||
| AO | 302 | Controller 5 Frost protection-Set point | Modbus 400302 | Command | ||
| AO | 303 | Controller 5 Minimum control variable | Modbus 400303 | Command | ||
| AO | 304 | Controller 5 Controller has access to symbols Heating Cooling | Modbus 400304 | Command | ||
| AO | 305 | Controller 5 Number of fan stages | Modbus 400305 | Command | ||
| AO | 306 | Controller 5 Control variable threshold for fan stage 1 Heating | Modbus 400306 | Command | ||
| AO | 307 | Controller 5 Control variable threshold for fan stage 2 Heating | Modbus 400307 | Command | ||
| AO | 308 | Controller 5 Control variable threshold for fan stage 3 Heating | Modbus 400308 | Command | ||
| AO | 309 | Controller 5 Control variable threshold for fan stage 1 Cooling | Modbus 400309 | Command | ||
| AO | 310 | Controller 5 Control variable threshold for fan stage 2 Cooling | Modbus 400310 | Command | ||
| AO | 311 | Controller 5 Control variable threshold for fan stage 3 Cooling | Modbus 400311 | Command | ||
| AO | 312 | Controller 5 PWM cycle time | Modbus 400312 | Command | ||
| AO | 313 | Controller 5 Select fan coil X interacts with Main-Fan control | Modbus 400313 | Command | ||
| AO | 314 | Controller 5 Display dew point signal of controller | Modbus 400314 | Command | ||
| AO | 315 | Controller 5 Bypass time | Modbus 400315 | Command | ||
| AO | 316 | Controller 5 Minimal ON time for fan coil | Modbus 400316 | Command | ||
| AO | 317 | Controller 6 Default set point after reset Comfort | Modbus 400317 | Command | ||
| AO | 318 | Controller 6 Set point difference Standby | Modbus 400318 | Command | ||
| AO | 319 | Controller 6 Set point difference Unoccupied | Modbus 400319 | Command | ||
| AO | 320 | Controller 6 Controller parameter XP Heating | Modbus 400320 | Command | ||
| AO | 321 | Controller 6 Controller parameter TN Heating | Modbus 400321 | Command | ||
| AO | 322 | Controller 6 Controller parameter XP Cooling | Modbus 400322 | Command | ||
| AO | 323 | Controller 6 Controller parameter TN Cooling | Modbus 400323 | Command | ||
| AO | 324 | Controller 6 Dead zone | Modbus 400324 | Command | ||
| AO | 325 | Controller 6 Minimum control variable Heating | Modbus 400325 | Command | ||
| AO | 326 | Controller 6 Maximum control variable Heating | Modbus 400326 | Command | ||
| AO | 327 | Controller 6 Minimum control variable Cooling | Modbus 400327 | Command | ||
| AO | 328 | Controller 6 Maximum control variable Cooling | Modbus 400328 | Command | ||
| AO | 329 | Controller 6 Controller mode after reset | Modbus 400329 | Command | ||
| AO | 330 | Controller 6 Selection actual value | Modbus 400330 | Command | ||
| AO | 331 | Controller 6 Selection set value | Modbus 400331 | Command | ||
| AO | 332 | Controller 6 Selection energy hold-off | Modbus 400332 | Command | ||
| AO | 333 | Controller 6 Selection Un-/Occupied | Modbus 400333 | Command | ||
| AO | 334 | Controller 6 Frost protection-Set point | Modbus 400334 | Command | ||
| AO | 335 | Controller 6 Minimum control variable | Modbus 400335 | Command | ||
| AO | 336 | Controller 6 Controller has access to symbols Heating Cooling | Modbus 400336 | Command | ||
| AO | 337 | Controller 6 Number of fan stages | Modbus 400337 | Command | ||
| AO | 338 | Controller 6 Control variable threshold for fan stage 1 Heating | Modbus 400338 | Command | ||
| AO | 339 | Controller 6 Control variable threshold for fan stage 2 Heating | Modbus 400339 | Command | ||
| AO | 340 | Controller 6 Control variable threshold for fan stage 3 Heating | Modbus 400340 | Command | ||
| AO | 341 | Controller 6 Control variable threshold for fan stage 1 Cooling | Modbus 400341 | Command | ||
| AO | 342 | Controller 6 Control variable threshold for fan stage 2 Cooling | Modbus 400342 | Command | ||
| AO | 343 | Controller 6 Control variable threshold for fan stage 3 Cooling | Modbus 400343 | Command | ||
| AO | 344 | Controller 6 PWM cycle time | Modbus 400344 | Command | ||
| AO | 345 | Controller 6 Select fan coil X interacts with Main-Fan control | Modbus 400345 | Command | ||
| AO | 346 | Controller 6 Display dew point signal of controller | Modbus 400346 | Command | ||
| AO | 347 | Controller 6 Bypass time | Modbus 400347 | Command | ||
| AO | 348 | Controller 6 Minimal ON time for fan coil | Modbus 400348 | Command | ||
| AO | 349 | Function digital Input 1 | Modbus 400349; not polled by default | Command | ||
| AO | 350 | Function digital Input 2 | Modbus 400350; not polled by default | Command | ||
| AO | 351 | Function digital Input 3 | Modbus 400351; not polled by default | Command | ||
| AO | 352 | Function digital Input 4 | Modbus 400352; not polled by default | Command | ||
| AO | 353 | Volume button sound | Modbus 400353; not polled by default | Command | ||
| AO | 354 | Direct key 16 | Modbus 400354; not polled by default | Command | ||
| AO | 355 | Direct key 17 | Modbus 400355; not polled by default | Command | ||
| AO | 356 | Direct key 18 | Modbus 400356; not polled by default | Command | ||
| AO | 357 | Direct key 19 | Modbus 400357; not polled by default | Command | ||
| AO | 358 | Direct key 20 | Modbus 400358; not polled by default | Command | ||
| AO | 359 | Direct key 21 | Modbus 400359; not polled by default | Command | ||
| AO | 360 | Direct key 22 | Modbus 400360; not polled by default | Command | ||
| AO | 361 | Direct key 23 | Modbus 400361; not polled by default | Command | ||
| AO | 362 | Direct key 24 | Modbus 400362; not polled by default | Command | ||
| AO | 363 | Direct key 25 | Modbus 400363; not polled by default | Command | ||
| AO | 364 | Direct key 26 | Modbus 400364; not polled by default | Command | ||
| AO | 365 | Direct key 27 | Modbus 400365; not polled by default | Command | ||
| AO | 366 | Direct key 28 | Modbus 400366; not polled by default | Command | ||
| AO | 367 | Direct key 29 | Modbus 400367; not polled by default | Command | ||
| AO | 368 | Direct key 30 | Modbus 400368; not polled by default | Command | ||
| AO | 369 | Direct key 31 | Modbus 400369; not polled by default | Command | ||
| AO | 370 | Standardscreen | Modbus 400370; not polled by default | Command | ||
| AI | 371 | Parameterversion (read only) | Modbus 400371; not polled by default | Read | ||
| AO | 372 | FanCoil OFF / AUTO only | Modbus 400372; not polled by default | Command | ||
| BO | 373 | Display temperature | Modbus 000001; not polled by default | Command | ||
| BO | 374 | Display humidity | Modbus 000002; not polled by default | Command | ||
| BO | 375 | Resolution temperature | Modbus 000003; not polled by default | Command | ||
| BO | 376 | Resolution humidity | Modbus 000004; not polled by default | Command | ||
| BO | 377 | Activate device first | Modbus 000005; not polled by default | Command | ||
| BO | 378 | Unit temperature | Modbus 000006; not polled by default | Command | ||
| BO | 379 | Fan stage after reset | Modbus 000007; not polled by default | Command | ||
| BO | 380 | Display room occupancy after reset | Modbus 000008; not polled by default | Command | ||
| BO | 381 | Show menu line 1 | Modbus 000009; not polled by default | Command | ||
| BO | 382 | Show menu line 2 | Modbus 000010; not polled by default | Command | ||
| BO | 383 | Show menu line 3 | Modbus 000011; not polled by default | Command | ||
| BO | 384 | Show menu line 4 | Modbus 000012; not polled by default | Command | ||
| BO | 385 | Show menu line 5 | Modbus 000013; not polled by default | Command | ||
| BO | 386 | Display stage in auto mode | Modbus 000014; not polled by default | Command | ||
| BO | 387 | External value 1: Resolution | Modbus 000015; not polled by default | Command | ||
| BO | 388 | External value 1: Show | Modbus 000016; not polled by default | Command | ||
| BO | 389 | External value 2: Resolution | Modbus 000017; not polled by default | Command | ||
| BO | 390 | External value 2: Show | Modbus 000018; not polled by default | Command | ||
| BO | 391 | External value 3: Resolution | Modbus 000019; not polled by default | Command | ||
| BO | 392 | External value 3: Show | Modbus 000020; not polled by default | Command | ||
| BO | 393 | External value 4: Resolution | Modbus 000021; not polled by default | Command | ||
| BO | 394 | External value 4: Show | Modbus 000022; not polled by default | Command | ||
| BO | 395 | External value 5: Resolution | Modbus 000023; not polled by default | Command | ||
| BO | 396 | External value 5: Show | Modbus 000024; not polled by default | Command | ||
| BO | 397 | External value 6: Resolution | Modbus 000025; not polled by default | Command | ||
| BO | 398 | External value 6 Show | Modbus 000026; not polled by default | Command | ||
| BO | 399 | Set point 1: Resolution | Modbus 000027; not polled by default | Command | ||
| BO | 400 | Set point 1: Display with adjustment | Modbus 000028; not polled by default | Command | ||
| BO | 401 | Set point 1: Display effective value | Modbus 000029; not polled by default | Command | ||
| BO | 402 | Set point 1: Display offset value | Modbus 000030; not polled by default | Command | ||
| BO | 403 | Set point 2: Resolution | Modbus 000031; not polled by default | Command | ||
| BO | 404 | Set point 2: Display with adjustment | Modbus 000032; not polled by default | Command | ||
| BO | 405 | Set point 2: Display effective value | Modbus 000033; not polled by default | Command | ||
| BO | 406 | Set point 2: Display offset value | Modbus 000034; not polled by default | Command | ||
| BO | 407 | Set point 3: Resolution | Modbus 000035; not polled by default | Command | ||
| BO | 408 | Set point 3: Display with adjustment | Modbus 000036; not polled by default | Command | ||
| BO | 409 | Set point 3: Display effective value | Modbus 000037; not polled by default | Command | ||
| BO | 410 | Set point 3: Display offset value | Modbus 000038; not polled by default | Command | ||
| BO | 411 | Set point 4: Resolution | Modbus 000039; not polled by default | Command | ||
| BO | 412 | Set point 4: Display with adjustment | Modbus 000040; not polled by default | Command | ||
| BO | 413 | Set point 4: Display effective value | Modbus 000041; not polled by default | Command | ||
| BO | 414 | Set point 4: Display offset value | Modbus 000042; not polled by default | Command | ||
| BO | 415 | Set point 5: Resolution | Modbus 000043; not polled by default | Command | ||
| BO | 416 | Set point 5: Display with adjustment | Modbus 000044; not polled by default | Command | ||
| BO | 417 | Set point 5: Display effective value | Modbus 000045; not polled by default | Command | ||
| BO | 418 | Set point 5: Display offset value | Modbus 000046; not polled by default | Command | ||
| BO | 419 | Set point 6: Resolution | Modbus 000047; not polled by default | Command | ||
| BO | 420 | Set point 6: Display with adjustment | Modbus 000048; not polled by default | Command | ||
| BO | 421 | Set point 6: Display effective value | Modbus 000049; not polled by default | Command | ||
| BO | 422 | Set point 6: Display offset value | Modbus 000050; not polled by default | Command | ||
| BO | 423 | Selection if indices will be shown in the LCD. | Modbus 000051; not polled by default | Command | ||
| BO | 424 | Selection if indices will be shown even if their value is 0. | Modbus 000052; not polled by default | Command | ||
| AI | 425 | Current state of key 1...16 | Modbus 300769; not polled by default | Read | ||
| AI | 426 | State of key since last call-off 1...16 | Modbus 300770; not polled by default | Read | ||
| AI | 427 | State light function | Modbus 300771; not polled by default | Read | ||
| AI | 428 | Current state of + dimming key | Modbus 300772; not polled by default | Read | ||
| AI | 429 | Current state of - dimming key | Modbus 300773; not polled by default | Read | ||
| AI | 430 | State shutter/blind function | Modbus 300774; not polled by default | Read | ||
| AI | 431 | Current state of + Shutter/blind key | Modbus 300775; not polled by default | Read | ||
| AI | 432 | Current state of - Shutter/blind key | Modbus 300776; not polled by default | Read | ||
| AI | 433 | State Universal function | Modbus 300777; not polled by default | Read | ||
| AI | 434 | Current Offset for set point 1 | Modbus 300778; not polled by default | Read | ||
| AImin | 435 | Set point effective 1 (Default set point + set point offset) | Modbus 300779; not polled by default | Read | ||
| AI | 436 | Current Offset for set point 2 | Modbus 300780; not polled by default | Read | ||
| AI | 437 | Set point effective 2 (Default set point + set point offset) | Modbus 300781; not polled by default | Read | ||
| AI | 438 | Current Offset for set point 3 | Modbus 300782; not polled by default | Read | ||
| AI | 439 | Set point effective 3 (Default set point + set point offset) | Modbus 300783; not polled by default | Read | ||
| AI | 440 | Current Offset for set point 4 | Modbus 300784; not polled by default | Read | ||
| AI | 441 | Set point effective 4 (Default set point + set point offset) | Modbus 300785; not polled by default | Read | ||
| AI | 442 | Current Offset for set point 5 | Modbus 300786; not polled by default | Read | ||
| AI | 443 | Set point effective 5 (Default set point + set point offset) | Modbus 300787; not polled by default | Read | ||
| AI | 444 | Current Offset for set point 6 | Modbus 300788; not polled by default | Read | ||
| AI | 445 | Set point effective 6 (Default set point + set point offset) | Modbus 300789; not polled by default | Read | ||
| AImin | 446 | Temperature internal sensor | Modbus 300790; not polled by default | Read | ||
| AImin | 447 | Humidity internal sensor | Modbus 300791; not polled by default | Read | ||
| AImin | 448 | Current fan stage | Modbus 300792; not polled by default | Read | ||
| AImin | 449 | Current room occupancy | Modbus 300793; not polled by default | Read | ||
| AImin | 450 | Control variable Heating Controller 1 | Modbus 300794; not polled by default | Read | ||
| AImin | 451 | Control variable Cooling Controller 1 | Modbus 300795; not polled by default | Read | ||
| AI | 452 | Output register PWM-signal Heating Controller 1 | Modbus 300796; not polled by default | Read | ||
| AI | 453 | Output register PWM-signal Cooling Controller 1 | Modbus 300797; not polled by default | Read | ||
| AI | 454 | Output controller mode Controller 1 | Modbus 300798; not polled by default | Read | ||
| AI | 455 | Output register fan stage Controller 1 | Modbus 300799; not polled by default | Read | ||
| AI | 456 | Effective controller set point Controller1 | Modbus 300800; not polled by default | Read | ||
| AI | 457 | Control variable Heating Controller 2 | Modbus 300801; not polled by default | Read | ||
| AI | 458 | Control variable Cooling Controller 2 | Modbus 300802; not polled by default | Read | ||
| AI | 459 | Output register PWM-Signal Heating Controller 2 | Modbus 300803; not polled by default | Read | ||
| AI | 460 | Output register PWM-Signal Cooling Controller 2 | Modbus 300804; not polled by default | Read | ||
| AI | 461 | Output Controller mode Controller 2 | Modbus 300805; not polled by default | Read | ||
| AI | 462 | Output register Fan Stage Controller 2 | Modbus 300806; not polled by default | Read | ||
| AI | 463 | Effective controller set point Controller2 | Modbus 300807; not polled by default | Read | ||
| AI | 464 | Control variable Heating Controller 3 | Modbus 300808; not polled by default | Read | ||
| AI | 465 | Control variable Cooling Controller 3 | Modbus 300809; not polled by default | Read | ||
| AI | 466 | Output register PWM-Signal Heating Controller 3 | Modbus 300810; not polled by default | Read | ||
| AI | 467 | Output register PWM-Signal Cooling Controller 3 | Modbus 300811; not polled by default | Read | ||
| AI | 468 | Output Controller mode Controller 3 | Modbus 300812; not polled by default | Read | ||
| AI | 469 | Output register Fan Stage Controller 3 | Modbus 300813; not polled by default | Read | ||
| AI | 470 | Effective controller set point Controller3 | Modbus 300814; not polled by default | Read | ||
| AI | 471 | Control variable Heating Controller 4 | Modbus 300815; not polled by default | Read | ||
| AI | 472 | Control variable Cooling Controller 4 | Modbus 300816; not polled by default | Read | ||
| AI | 473 | Output register PWM-Signal Heating Controller 4 | Modbus 300817; not polled by default | Read | ||
| AI | 474 | Output register PWM-Signal Cooling Controller 4 | Modbus 300818; not polled by default | Read | ||
| AI | 475 | Output Controller mode Controller 4 | Modbus 300819; not polled by default | Read | ||
| AI | 476 | Output register Fan Stage Controller 4 | Modbus 300820; not polled by default | Read | ||
| AI | 477 | Effective controller set point Controller4 | Modbus 300821; not polled by default | Read | ||
| AI | 478 | Control variable Heating Controller 5 | Modbus 300822; not polled by default | Read | ||
| AI | 479 | Control variable Cooling Controller 5 | Modbus 300823; not polled by default | Read | ||
| AI | 480 | Output register PWM-Signal Heating Controller 5 | Modbus 300824; not polled by default | Read | ||
| AI | 481 | Output register PWM-Signal Cooling Controller 5 | Modbus 300825; not polled by default | Read | ||
| AI | 482 | Output Controller mode Controller 5 | Modbus 300826; not polled by default | Read | ||
| AI | 483 | Output register Fan Stage Controller 5 | Modbus 300827; not polled by default | Read | ||
| AI | 484 | Effective controller set point Controller5 | Modbus 300828; not polled by default | Read | ||
| AI | 485 | Control variable Heating Controller 6 | Modbus 300829; not polled by default | Read | ||
| AI | 486 | Control variable Cooling Controller 6 | Modbus 300830; not polled by default | Read | ||
| AI | 487 | Output register PWM-Signal Heating Controller 6 | Modbus 300831; not polled by default | Read | ||
| AI | 488 | Output register PWM-Signal Cooling Controller 6 | Modbus 300832; not polled by default | Read | ||
| AI | 489 | Output Controller mode Controller 6 | Modbus 300833; not polled by default | Read | ||
| AI | 490 | Output register Fan Stage Controller 6 | Modbus 300834; not polled by default | Read | ||
| AO | 491 | Effective controller set point Controller6 | Modbus 400835; not polled by default | Command | ||
| AO | 492 | Digital Input1 | Modbus 400836; not polled by default | Command | ||
| AO | 493 | Digital Input2 | Modbus 400837; not polled by default | Command | ||
| AO | 494 | Digital Input3 | Modbus 400838; not polled by default | Command | ||
| AO | 495 | Digital Input4 | Modbus 400839; not polled by default | Command | ||
| AO | 496 | Current state of key 16...31 | Modbus 400840; not polled by default | Command | ||
| AO | 497 | State of key since last call-off 16...31 | Modbus 400841; not polled by default | Command | ||
| AO | 498 | Input seconds | Modbus 401025; not polled by default | Command | ||
| AO | 499 | Input minutes | Modbus 401026; not polled by default | Command | ||
| AO | 500 | Input hours | Modbus 401027; not polled by default | Command | ||
| AO | 501 | Input day of month | Modbus 401028; not polled by default | Command | ||
| AO | 502 | Input month | Modbus 401029; not polled by default | Command | ||
| AO | 503 | Input year | Modbus 401030; not polled by default | Command | ||
| AO | 504 | Default fan stage | Modbus 401031; not polled by default | Command | ||
| AO | 505 | Default occupancy | Modbus 401032; not polled by default | Command | ||
| AO | 506 | Bypass time re-trigger | Modbus 401033; not polled by default | Command | ||
| AO | 507 | Show message | Modbus 401034; not polled by default | Command | ||
| AO | 508 | External temperature default | Modbus 401035; not polled by default | Command | ||
| AO | 509 | External humidity default | Modbus 401036; not polled by default | Command | ||
| AO | 510 | Feedback status light function | Modbus 401037; not polled by default | Command | ||
| AO | 511 | Feedback shutter/blind function | Modbus 401038; not polled by default | Command | ||
| AO | 512 | Feedback universal function | Modbus 401039; not polled by default | Command | ||
| AO | 513 | External value1 | Modbus 401040; not polled by default | Command | ||
| AO | 514 | External value2 | Modbus 401041; not polled by default | Command | ||
| AO | 515 | External value3 | Modbus 401042; not polled by default | Command | ||
| AO | 516 | External value4 | Modbus 401043; not polled by default | Command | ||
| AO | 517 | External value5 | Modbus 401044; not polled by default | Command | ||
| AO | 518 | External value6 | Modbus 401045; not polled by default | Command | ||
| AO | 519 | Offset set point1 | Modbus 401046; not polled by default | Command | ||
| AO | 520 | Standard set point1 | Modbus 401047; not polled by default | Command | ||
| AO | 521 | Offset set point2 | Modbus 401048; not polled by default | Command | ||
| AO | 522 | Basis set point2 | Modbus 401049; not polled by default | Command | ||
| AO | 523 | Offset set point3 | Modbus 401050; not polled by default | Command | ||
| AO | 524 | Basis set point3 | Modbus 401051; not polled by default | Command | ||
| AO | 525 | Offset set point4 | Modbus 401052; not polled by default | Command | ||
| AO | 526 | Basis set point4 | Modbus 401053; not polled by default | Command | ||
| AO | 527 | Offset set point5 | Modbus 401054; not polled by default | Command | ||
| AO | 528 | Basis set point5 | Modbus 401055; not polled by default | Command | ||
| AO | 529 | Offset set point6 | Modbus 401056; not polled by default | Command | ||
| AO | 530 | Basis set point6 | Modbus 401057; not polled by default | Command | ||
| AO | 531 | Actual value Controller 1 | Modbus 401058; not polled by default | Command | ||
| AO | 532 | Occupancy Controller 1 | Modbus 401059; not polled by default | Command | ||
| AO | 533 | Energy hold-off Controller 1 | Modbus 401060; not polled by default | Command | ||
| AO | 534 | Controller mode Controller 1 | Modbus 401061; not polled by default | Command | ||
| AO | 535 | Base set point Controller 1 | Modbus 401062; not polled by default | Command | ||
| AO | 536 | Dew point Controller 1 | Modbus 401063; not polled by default | Command | ||
| AO | 537 | Trigger bypass time Controller 1 | Modbus 401064; not polled by default | Command | ||
| AO | 538 | Default set point offset Controller 1 | Modbus 401065; not polled by default | Command | ||
| AO | 539 | Actual value Controller 2 | Modbus 401066; not polled by default | Command | ||
| AO | 540 | Occupancy Controller 2 | Modbus 401067; not polled by default | Command | ||
| AO | 541 | Energy hold-off Controller 2 | Modbus 401068; not polled by default | Command | ||
| AO | 542 | Controller mode Controller 2 | Modbus 401069; not polled by default | Command | ||
| AO | 543 | Base set point Controller 2 | Modbus 401070; not polled by default | Command | ||
| AO | 544 | Dew point Controller 2 | Modbus 401071; not polled by default | Command | ||
| AO | 545 | Trigger bypass time Controller 2 | Modbus 401072; not polled by default | Command | ||
| AO | 546 | Default set point offset Controller 2 | Modbus 401073; not polled by default | Command | ||
| AO | 547 | Actual value Controller 3 | Modbus 401074; not polled by default | Command | ||
| AO | 548 | Occupancy Controller 3 | Modbus 401075; not polled by default | Command | ||
| AO | 549 | Energy hold-off Controller 3 | Modbus 401076; not polled by default | Command | ||
| AO | 550 | Controller mode Controller 3 | Modbus 401077; not polled by default | Command | ||
| AO | 551 | Base set point Controller 3 | Modbus 401078; not polled by default | Command | ||
| AO | 552 | Dew point Controller 3 | Modbus 401079; not polled by default | Command | ||
| AO | 553 | Trigger bypass time Controller 3 | Modbus 401080; not polled by default | Command | ||
| AO | 554 | Default set point offset Controller 3 | Modbus 401081; not polled by default | Command | ||
| AO | 555 | Actual value Controller 4 | Modbus 401082; not polled by default | Command | ||
| AO | 556 | Occupancy Controller 4 | Modbus 401083; not polled by default | Command | ||
| AO | 557 | Energy hold-off Controller 4 | Modbus 401084; not polled by default | Command | ||
| AO | 558 | Controller mode Controller 4 | Modbus 401085; not polled by default | Command | ||
| AO | 559 | Standard set point Controller 4 | Modbus 401086; not polled by default | Command | ||
| AO | 560 | Dew point Controller 4 | Modbus 401087; not polled by default | Command | ||
| AO | 561 | Trigger bypass time Controller 4 | Modbus 401088; not polled by default | Command | ||
| AO | 562 | Default set point offset Controller 4 | Modbus 401089; not polled by default | Command | ||
| AO | 563 | Actual value Controller 5 | Modbus 401090; not polled by default | Command | ||
| AO | 564 | Occupancy Controller 5 | Modbus 401091; not polled by default | Command | ||
| AO | 565 | Energy hold-off Controller 5 | Modbus 401092; not polled by default | Command | ||
| AO | 566 | Controller mode Controller 5 | Modbus 401093; not polled by default | Command | ||
| AO | 567 | Base set point Controller 5 | Modbus 401094; not polled by default | Command | ||
| AO | 568 | Dew point Controller 5 | Modbus 401095; not polled by default | Command | ||
| AO | 569 | Trigger bypass time Controller 5 | Modbus 401096; not polled by default | Command | ||
| AO | 570 | Default set point offset Controller 5 | Modbus 401097; not polled by default | Command | ||
| AO | 571 | Actual value Controller 6 | Modbus 401098; not polled by default | Command | ||
| AO | 572 | Occupancy Controller 6 | Modbus 401099; not polled by default | Command | ||
| AO | 573 | Energy hold-off Controller 6 | Modbus 401100; not polled by default | Command | ||
| AO | 574 | Controller mode Controller 6 | Modbus 401101; not polled by default | Command | ||
| AO | 575 | Base set point Controller 6 | Modbus 401102; not polled by default | Command | ||
| AO | 576 | Dew point Controller 6 | Modbus 401103; not polled by default | Command | ||
| AO | 577 | Trigger bypass time Controller 6 | Modbus 401104; not polled by default | Command | ||
| AO | 578 | Default set point offset Controller 6 | Modbus 401105; not polled by default | Command | ||
| AO | 579 | Restart 1 | Modbus 401106; not polled by default | Command | ||
| AO | 580 | Restart 2 | Modbus 401107; not polled by default | Command | ||
| BO | 581 | Symbol failure | Modbus 000257; not polled by default | Command | ||
| BO | 582 | Symbol heating | Modbus 000258; not polled by default | Command | ||
| BO | 583 | Symbol cooling | Modbus 000259; not polled by default | Command | ||
| BO | 584 | Symbol window | Modbus 000260; not polled by default | Command | ||
| BO | 585 | Symbol dew point | Modbus 000261; not polled by default | Command | ||
| BO | 586 | Key lock | Modbus 000262; not polled by default | Command | ||
| BO | 587 | Lock room occupancy | Modbus 000263; not polled by default | Command | ||
| BO | 588 | Lock fan stages | Modbus 000264; not polled by default | Command | ||
| BO | 589 | Lock set points | Modbus 000265; not polled by default | Command | ||
| BO | 590 | Activation of TFT- and key- illumination | Modbus 000266; not polled by default | Command |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Thermokon Thanos point IDs by name
AI1Device codeAI2Firmware versionAI3Device versionAI4Humidity sensor existingAO5Rotation DisplayAO6Device location identificationAO7Temperature offsetAO8Humidity offsetAO9Setting of the maximal available fan stagesAO10Status fan stage after resetAO11Status room occupancy after resetAO12Bypass time room occupancyAO13Time cleaning functionAO14Device typeAO15Minimum response delay time [ms]AO16Background illumination LCDAI17ContrastAO18Intensity background illumination LCD Standard-ModeAO19Intensity background illumination LCD Idle-ModeAO20Intensity background illumination LCD Standby-ModeAO21Intensity background illumination keypad StandardAO22Intensity background illumination keypad IdleAO23Intensity background illumination keypad StandbyAO24Time to switch Standard- in Idle modeAO25Time to switch Idle- in Standby modeAO26Duration of displaying a menu pointAO27Duration of displaying an operationAO28Date displayAO29Time displayAO30Time modeAO31Register to configure available submenus (only S version!!)AO32Refresh interval of LCD in secondsAO33Display time of single submenus (only S version!!)AO34Upper range of adjustment Set point offset Set point 1AO35Lower range of adjustment Set point offset Set point 1AO36Step size set point adjustment Set point 1AO37Default set point after reset Set point 1AO381. ASCII symbol unit Set point 1AO392. ASCII symbol unit Set point 1AO403. ASCII symbol unit Set point 1AO411. ASCII symbol set point description Set point 1AO422. ASCII symbol set point description Set point 1AO433. ASCII symbol set point description Set point 1AO444. ASCII symbol set point description Set point 1AO45Upper range of adjustment Set point adjustment Set point 2AO46Lower range of adjustment Set point adjustment Set point 2AO47Step size set point adjustment Set point 2AO48Default set point after reset Set point 2AO491. ASCII symbol unit Set point 2AO502. ASCII symbol unit Set point 2AO513. ASCII symbol unit Set point 2AO521. ASCII symbol set point description) Set point 2AO532. ASCII symbol set point description Set point 2AO543. ASCII symbol set point description Set point 2AO554. ASCII symbol set point description Set point 2AO56Upper range of adjustment Set point offset (Set point 3AO57Lower range of adjustment Set point offset Set point 3AO58Step size set point adjustment Set point 3AO59Default set point 3 after reset Set point 3AO601. ASCII symbol unit Set point 3AO612. ASCII symbol unit Set point 3AO623. ASCII symbol unit Set point 3AO631. ASCII symbol set point description Set point 3AO642. ASCII symbol set point description Set point 3AO653. ASCII symbol set point description Set point 3AO664. ASCII symbol set point description Set point 3AO67Upper range of adjustment Set point offset Set point 4AO68Lower range of adjustment Set point offset Set point 4AO69Step size set point adjustment Set point 4AO70Default set point 4 after reset Set point 4AO711. ASCII symbol unit Set point 4AO722. ASCII symbol unit Set point 4AO733. ASCII symbol unit Set point 4AO741. ASCII symbol set point description Set point 4AO752. ASCII symbol set point description Set point 4AO763. ASCII symbol set point description Set point 4AO774. ASCII symbol set point description Set point 4AO78Upper range of adjustment Set point offset Set point 5AO79Lower range of adjustment Set point offset Set point 5AO80Step size set point adjustment Set point 5AO81Default set point 5 after reset Set point 5AO821. ASCII symbol unit Set point 5AO832. ASCII symbol unit Set point 5AO843. ASCII symbol unit Set point 5AO851. ASCII symbol set point description Set point 5AO862. ASCII symbol set point description Set point 5AO873. ASCII symbol set point description Set point 5AO884. ASCII symbol set point description Set point 5AO89Upper range of adjustment Set point offset Set point 6AO90Lower range of adjustment Set point offset Set point 6AO91Step size set point adjustment Set point 6AO92Default set point 5 after reset Set point 6AO931. ASCII symbol unit Set point 6AO942. ASCII symbol unit Set point 6AO953. ASCII symbol unit Set point 6AO961. ASCII symbol set point description Set point 6AO972. ASCII symbol set point description Set point 6AO983. ASCII symbol set point description Set point 6AO994. ASCII symbol set point description Set point 6AO1001. ASCII symbol unit External value 1AO1012. ASCII symbol unit External value 1AO1023. ASCII symbol unit External value 1AO1031. ASCII symbol description External value 1AO1042. ASCII symbol description External value 1AO1053. ASCII symbol description External value 1AO1064. ASCII symbol description External value 1AO1071. ASCII symbol unit External value 2AO1082. ASCII symbol unit External value 2AO1093. ASCII symbol unit External value 2AO1101. ASCII symbol description External value 2AO1112. ASCII symbol description External value 2AO1123. ASCII symbol description External value 2AO1134. ASCII symbol description External value 2AO1141. ASCII symbol unit External value 3AO1152. ASCII symbol unit External value 3AO1163. ASCII symbol unit External value 3AO1171. ASCII symbol description External value 3AO1182. ASCII symbol description External value 3AO1193. ASCII symbol description External value 3AO1204. ASCII symbol description External value 3AO1211. ASCII symbol unit External value 4AO1222. ASCII symbol unit External value 4AO1233. ASCII symbol unit External value 4AO1241. ASCII symbol description External value 4AO1252. ASCII symbol description External value 4AO1263. ASCII symbol description External value 4AO1274. ASCII symbol description External value 4AO1281. ASCII symbol unit External value 5AO1292. ASCII symbol unit External value 5AO1303. ASCII symbol unit External value 5AO1311. ASCII symbol description External valueAO1322. ASCII symbol description External value 5AO1333. ASCII symbol description External value 5AO1344. ASCII symbol description External value 5AO1351. ASCII symbol unit External value 6AO1362. ASCII symbol unit External value 6AO1373. ASCII symbol unit External value 6AO1381. ASCII symbol description External value 6AO1392. ASCII symbol description External value 6AO1403. ASCII symbol description External value 6AO1414. ASCII symbol description External value 6AO142Configuration functional clipAO143Configuration menu key 1AO144Configuration menu key 4AO145onfiguration menu key 5AO146Configuration menu key 6AO147Configuration menu key 7AO148Configuration Direct key 8AO149Configuration Direct key 9AO150Configuration Direct key 10AO151Configuration Direct key 11AO152Configuration Direct key 12AO153Configuration Direct key 13AO154Configuration Direct key 14AO155Configuration Direct key 15AO156Lock external defaultsAO157Controller 1 Default set point after reset ComfortAO158Controller 1 Set point difference StandbyAO159Controller 1 Set point difference UnoccupiedAO160Controller 1 Controller parameter XP HeatingAO161Controller 1 Controller parameter TN HeatingAO162Controller 1 Controller parameter XP CoolingAO163Controller 1 Controller parameter TN CoolingAO164Controller 1 Dead zoneAO165Controller 1 Minimum control variable HeatingAO166Controller 1 Maximum control variable HeatingAO167Controller 1 Minimum control variable CoolingAO168Controller 1 Maximum control variable CoolingAO169Controller 1 Controller mode after resetAO170Controller 1 Selection actual valueAO171Controller 1 Selection set valueAO172Controller 1 Selection energy hold-offAO173Controller 1 Selection Un-/OccupiedAO174Controller 1 Frost protection-Set pointAO175Controller 1 Minimum control variableAO176Controller 1 Controller has access to symbols Heating CoolingAO177Controller 1 Number of fan stagesAO178Controller 1 Control variable threshold for fan stage 1 HeatingAO179Controller 1 Control variable threshold for fan stage 2 HeatingAO180Controller 1 Control variable threshold for fan stage 3 HeatingAO181Controller 1 Control variable threshold for fan stage 1 CoolingAO182Controller 1 Control variable threshold for fan stage 2 CoolingAO183Controller 1 Control variable threshold for fan stage 3 CoolingAO184Controller 1 PWM cycle timeAO185Controller 1 Select fan coil X interacts with Main-Fan controlAO186Controller 1 Display dew point signal of controllerAO187Controller 1 Bypass timeAO188Controller 1 Minimal ON time for fan coilAO189Controller 2 Default set point after reset ComfortAO190Controller 2 Set point difference StandbyAO191Controller 2 Set point difference UnoccupiedAO192Controller 2 Controller parameter XP HeatingAO193Controller 2 Controller parameter TN HeatingAO194Controller 2 Controller parameter XP CoolingAO195Controller 2 Controller parameter TN CoolingAO196Controller 2 Dead zoneAO197Controller 2 Minimum control variable HeatingAO198Controller 2 Maximum control variable HeatingAO199Controller 2 Minimum control variable CoolingAO200Controller 2 Maximum control variable CoolingAO201Controller 2 Controller mode after resetAO202Controller 2 Selection actual valueAO203Controller 2 Selection set valueAO204Controller 2 Selection energy hold-offAO205Controller 2 Selection Un-/OccupiedAO206Controller 2 Frost protection-Set pointAO207Controller 2 Minimum control variableAO208Controller 2 Controller has access to symbols Heating CoolingAO209Controller 2 Number of fan stagesAO210Controller 2 Control variable threshold for fan stage 1 HeatingAO211Controller 2 Control variable threshold for fan stage 2 HeatingAO212Controller 2 Control variable threshold for fan stage 3 HeatingAO213Controller 2 Control variable threshold for fan stage 1 CoolingAO214Controller 2 Control variable threshold for fan stage 2 CoolingAO215Controller 2 Control variable threshold for fan stage 3 CoolingAO216Controller 2 PWM cycle timeAO217Controller 2 Select fan coil X interacts with Main-Fan controlAO218Controller 2 Display dew point signal of controllerAO219Controller 2 Bypass timeAO220Controller 2 Minimal ON time for fan coilAO221Controller 3 Default set point after reset ComfortAO222Controller 3 Set point difference StandbyAO223Controller 3 Set point difference UnoccupiedAO224Controller 3 Controller parameter XP HeatingAO225Controller 3 Controller parameter TN HeatingAO226Controller 3 Controller parameter XP CoolingAO227Controller 3 Controller parameter TN CoolingAO228Controller 3 Dead zoneAO229Controller 3 Minimum control variable HeatingAO230Controller 3 Maximum control variable HeatingAO231Controller 3 Minimum control variable CoolingAO232Controller 3 Maximum control variable CoolingAO233Controller 3 Controller mode after resetAO234Controller 3 Selection actual valueAO235Controller 3 Selection set valueAO236Controller 3 Selection energy hold-offAO237Controller 3 Selection Un-/OccupiedAO238Controller 3 Frost protection-Set pointAO239Controller 3 Minimum control variableAO240Controller 3 Controller has access to symbols Heating CoolingAO241Controller 3 Number of fan stagesAO242Controller 3 Control variable threshold for fan stage 1 HeatingAO243Controller 3 Control variable threshold for fan stage 2 HeatingAO244Controller 3 Control variable threshold for fan stage 3 HeatingAO245Controller 3 Control variable threshold for fan stage 1 CoolingAO246Controller 3 Control variable threshold for fan stage 2 CoolingAO247Controller 3 Control variable threshold for fan stage 3 CoolingAO248Controller 3 PWM cycle timeAO249Controller 3 Select fan coil X interacts with Main-Fan controlAO250Controller 3 Display dew point signal of controllerAO251Controller 3 Bypass timeAO252Controller 3 Minimal ON time for fan coilAO253Controller 4 Default set point after reset ComfortAO254Controller 4 Set point difference StandbyAO255Controller 4 Set point difference UnoccupiedAO256Controller 4 Controller parameter XP HeatingAO257Controller 4 Controller parameter TN HeatingAO258Controller 4 Controller parameter XP CoolingAO259Controller 4 Controller parameter TN CoolingAO260Controller 4 Dead zoneAO261Controller 4 Minimum control variable HeatingAO262Controller 4 Maximum control variable HeatingAO263Controller 4 Minimum control variable CoolingAO264Controller 4 Maximum control variable CoolingAO265Controller 4 Controller mode after resetAO266Controller 4 Selection actual valueAO267Controller 4 Selection set valueAO268Controller 4 Selection energy hold-offAO269Controller 4 Selection Un-/OccupiedAO270Controller 4 Frost protection-Set pointAO271Controller 4 Minimum control variableAO272Controller 4 Controller has access to symbols Heating CoolingAO273Controller 4 Number of fan stagesAO274Controller 4 Control variable threshold for fan stage 1 HeatingAO275Controller 4 Control variable threshold for fan stage 2 HeatingAO276Controller 4 Control variable threshold for fan stage 3 HeatingAO277Controller 4 Control variable threshold for fan stage 1 CoolingAO278Controller 4 Control variable threshold for fan stage 2 CoolingAO279Controller 4 Control variable threshold for fan stage 3 CoolingAO280Controller 4 PWM cycle timeAO281Controller 4 Select fan coil X interacts with Main-Fan controlAO282Controller 4 Display dew point signal of controllerAO283Controller 4 Bypass timeAO284Controller 4 Minimal ON time for fan coilAO285Controller 5 Default set point after reset ComfortAO286Controller 5 Set point difference StandbyAO287Controller 5 Set point difference UnoccupiedAO288Controller 5 Controller parameter XP HeatingAO289Controller 5 Controller parameter TN HeatingAO290Controller 5 Controller parameter XP CoolingAO291Controller 5 Controller parameter TN CoolingAO292Controller 5 Dead zoneAO293Controller 5 Minimum control variable HeatingAO294Controller 5 Maximum control variable HeatingAO295Controller 5 Minimum control variable CoolingAO296Controller 5 Maximum control variable CoolingAO297Controller 5 Controller mode after resetAO298Controller 5 Selection actual valueAO299Controller 5 Selection set valueAO300Controller 5 Selection energy hold-offAO301Controller 5 Selection Un-/OccupiedAO302Controller 5 Frost protection-Set pointAO303Controller 5 Minimum control variableAO304Controller 5 Controller has access to symbols Heating CoolingAO305Controller 5 Number of fan stagesAO306Controller 5 Control variable threshold for fan stage 1 HeatingAO307Controller 5 Control variable threshold for fan stage 2 HeatingAO308Controller 5 Control variable threshold for fan stage 3 HeatingAO309Controller 5 Control variable threshold for fan stage 1 CoolingAO310Controller 5 Control variable threshold for fan stage 2 CoolingAO311Controller 5 Control variable threshold for fan stage 3 CoolingAO312Controller 5 PWM cycle timeAO313Controller 5 Select fan coil X interacts with Main-Fan controlAO314Controller 5 Display dew point signal of controllerAO315Controller 5 Bypass timeAO316Controller 5 Minimal ON time for fan coilAO317Controller 6 Default set point after reset ComfortAO318Controller 6 Set point difference StandbyAO319Controller 6 Set point difference UnoccupiedAO320Controller 6 Controller parameter XP HeatingAO321Controller 6 Controller parameter TN HeatingAO322Controller 6 Controller parameter XP CoolingAO323Controller 6 Controller parameter TN CoolingAO324Controller 6 Dead zoneAO325Controller 6 Minimum control variable HeatingAO326Controller 6 Maximum control variable HeatingAO327Controller 6 Minimum control variable CoolingAO328Controller 6 Maximum control variable CoolingAO329Controller 6 Controller mode after resetAO330Controller 6 Selection actual valueAO331Controller 6 Selection set valueAO332Controller 6 Selection energy hold-offAO333Controller 6 Selection Un-/OccupiedAO334Controller 6 Frost protection-Set pointAO335Controller 6 Minimum control variableAO336Controller 6 Controller has access to symbols Heating CoolingAO337Controller 6 Number of fan stagesAO338Controller 6 Control variable threshold for fan stage 1 HeatingAO339Controller 6 Control variable threshold for fan stage 2 HeatingAO340Controller 6 Control variable threshold for fan stage 3 HeatingAO341Controller 6 Control variable threshold for fan stage 1 CoolingAO342Controller 6 Control variable threshold for fan stage 2 CoolingAO343Controller 6 Control variable threshold for fan stage 3 CoolingAO344Controller 6 PWM cycle timeAO345Controller 6 Select fan coil X interacts with Main-Fan controlAO346Controller 6 Display dew point signal of controllerAO347Controller 6 Bypass timeAO348Controller 6 Minimal ON time for fan coilAO349Function digital Input 1AO350Function digital Input 2AO351Function digital Input 3AO352Function digital Input 4AO353Volume button soundAO354Direct key 16AO355Direct key 17AO356Direct key 18AO357Direct key 19AO358Direct key 20AO359Direct key 21AO360Direct key 22AO361Direct key 23AO362Direct key 24AO363Direct key 25AO364Direct key 26AO365Direct key 27AO366Direct key 28AO367Direct key 29AO368Direct key 30AO369Direct key 31AO370StandardscreenAI371Parameterversion (read only)AO372FanCoil OFF / AUTO onlyBO373Display temperatureBO374Display humidityBO375Resolution temperatureBO376Resolution humidityBO377Activate device firstBO378Unit temperatureBO379Fan stage after resetBO380Display room occupancy after resetBO381Show menu line 1BO382Show menu line 2BO383Show menu line 3BO384Show menu line 4BO385Show menu line 5BO386Display stage in auto modeBO387External value 1: ResolutionBO388External value 1: ShowBO389External value 2: ResolutionBO390External value 2: ShowBO391External value 3: ResolutionBO392External value 3: ShowBO393External value 4: ResolutionBO394External value 4: ShowBO395External value 5: ResolutionBO396External value 5: ShowBO397External value 6: ResolutionBO398External value 6 ShowBO399Set point 1: ResolutionBO400Set point 1: Display with adjustmentBO401Set point 1: Display effective valueBO402Set point 1: Display offset valueBO403Set point 2: ResolutionBO404Set point 2: Display with adjustmentBO405Set point 2: Display effective valueBO406Set point 2: Display offset valueBO407Set point 3: ResolutionBO408Set point 3: Display with adjustmentBO409Set point 3: Display effective valueBO410Set point 3: Display offset valueBO411Set point 4: ResolutionBO412Set point 4: Display with adjustmentBO413Set point 4: Display effective valueBO414Set point 4: Display offset valueBO415Set point 5: ResolutionBO416Set point 5: Display with adjustmentBO417Set point 5: Display effective valueBO418Set point 5: Display offset valueBO419Set point 6: ResolutionBO420Set point 6: Display with adjustmentBO421Set point 6: Display effective valueBO422Set point 6: Display offset valueBO423Selection if indices will be shown in the LCD.BO424Selection if indices will be shown even if their value is 0.AI425Current state of key 1...16AI426State of key since last call-off 1...16AI427State light functionAI428Current state of + dimming keyAI429Current state of - dimming keyAI430State shutter/blind functionAI431Current state of + Shutter/blind keyAI432Current state of - Shutter/blind keyAI433State Universal functionAI434Current Offset for set point 1AI435Set point effective 1 (Default set point + set point offset)AI436Current Offset for set point 2AI437Set point effective 2 (Default set point + set point offset)AI438Current Offset for set point 3AI439Set point effective 3 (Default set point + set point offset)AI440Current Offset for set point 4AI441Set point effective 4 (Default set point + set point offset)AI442Current Offset for set point 5AI443Set point effective 5 (Default set point + set point offset)AI444Current Offset for set point 6AI445Set point effective 6 (Default set point + set point offset)AI446Temperature internal sensorAI447Humidity internal sensorAI448Current fan stageAI449Current room occupancyAI450Control variable Heating Controller 1AI451Control variable Cooling Controller 1AI452Output register PWM-signal Heating Controller 1AI453Output register PWM-signal Cooling Controller 1AI454Output controller mode Controller 1AI455Output register fan stage Controller 1AI456Effective controller set point Controller1AI457Control variable Heating Controller 2AI458Control variable Cooling Controller 2AI459Output register PWM-Signal Heating Controller 2AI460Output register PWM-Signal Cooling Controller 2AI461Output Controller mode Controller 2AI462Output register Fan Stage Controller 2AI463Effective controller set point Controller2AI464Control variable Heating Controller 3AI465Control variable Cooling Controller 3AI466Output register PWM-Signal Heating Controller 3AI467Output register PWM-Signal Cooling Controller 3AI468Output Controller mode Controller 3AI469Output register Fan Stage Controller 3AI470Effective controller set point Controller3AI471Control variable Heating Controller 4AI472Control variable Cooling Controller 4AI473Output register PWM-Signal Heating Controller 4AI474Output register PWM-Signal Cooling Controller 4AI475Output Controller mode Controller 4AI476Output register Fan Stage Controller 4AI477Effective controller set point Controller4AI478Control variable Heating Controller 5AI479Control variable Cooling Controller 5AI480Output register PWM-Signal Heating Controller 5AI481Output register PWM-Signal Cooling Controller 5AI482Output Controller mode Controller 5AI483Output register Fan Stage Controller 5AI484Effective controller set point Controller5AI485Control variable Heating Controller 6AI486Control variable Cooling Controller 6AI487Output register PWM-Signal Heating Controller 6AI488Output register PWM-Signal Cooling Controller 6AI489Output Controller mode Controller 6AI490Output register Fan Stage Controller 6AO491Effective controller set point Controller6AO492Digital Input1AO493Digital Input2AO494Digital Input3AO495Digital Input4AO496Current state of key 16...31AO497State of key since last call-off 16...31AO498Input secondsAO499Input minutesAO500Input hoursAO501Input day of monthAO502Input monthAO503Input yearAO504Default fan stageAO505Default occupancyAO506Bypass time re-triggerAO507Show messageAO508External temperature defaultAO509External humidity defaultAO510Feedback status light functionAO511Feedback shutter/blind functionAO512Feedback universal functionAO513External value1AO514External value2AO515External value3AO516External value4AO517External value5AO518External value6AO519Offset set point1AO520Standard set point1AO521Offset set point2AO522Basis set point2AO523Offset set point3AO524Basis set point3AO525Offset set point4AO526Basis set point4AO527Offset set point5AO528Basis set point5AO529Offset set point6AO530Basis set point6AO531Actual value Controller 1AO532Occupancy Controller 1AO533Energy hold-off Controller 1AO534Controller mode Controller 1AO535Base set point Controller 1AO536Dew point Controller 1AO537Trigger bypass time Controller 1AO538Default set point offset Controller 1AO539Actual value Controller 2AO540Occupancy Controller 2AO541Energy hold-off Controller 2AO542Controller mode Controller 2AO543Base set point Controller 2AO544Dew point Controller 2AO545Trigger bypass time Controller 2AO546Default set point offset Controller 2AO547Actual value Controller 3AO548Occupancy Controller 3AO549Energy hold-off Controller 3AO550Controller mode Controller 3AO551Base set point Controller 3AO552Dew point Controller 3AO553Trigger bypass time Controller 3AO554Default set point offset Controller 3AO555Actual value Controller 4AO556Occupancy Controller 4AO557Energy hold-off Controller 4AO558Controller mode Controller 4AO559Standard set point Controller 4AO560Dew point Controller 4AO561Trigger bypass time Controller 4AO562Default set point offset Controller 4AO563Actual value Controller 5AO564Occupancy Controller 5AO565Energy hold-off Controller 5AO566Controller mode Controller 5AO567Base set point Controller 5AO568Dew point Controller 5AO569Trigger bypass time Controller 5AO570Default set point offset Controller 5AO571Actual value Controller 6AO572Occupancy Controller 6AO573Energy hold-off Controller 6AO574Controller mode Controller 6AO575Base set point Controller 6AO576Dew point Controller 6AO577Trigger bypass time Controller 6AO578Default set point offset Controller 6AO579Restart 1AO580Restart 2BO581Symbol failureBO582Symbol heatingBO583Symbol coolingBO584Symbol windowBO585Symbol dew pointBO586Key lockBO587Lock room occupancyBO588Lock fan stagesBO589Lock set pointsBO590Activation of TFT- and key- illumination
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Thermokon_Thanos_a_LX.csv; the profile maps the registers in the Thanos Modbus register list (https://www.ccontrols.com/support/dp/Thermokon_Thanos_a_LX.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 192 of the 590 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Thermokon Thanos room operating unit via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
How many BACnet points does the Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX have?
This list has 590 BACnet objects: 72 analog inputs, 456 analog outputs, 62 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX BACnet points are writable?
518 of the 590 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Thermokon_Thanos_a (Thermokon_Thanos_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Thermokon_Thanos_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX?
Start with AI 446 Temperature internal sensor (Room temperature (internal sensor)); AI 447 Humidity internal sensor (Room humidity (internal sensor)); AI 435 Set point effective 1 (Default set point + set point offset) (Effective set point 1); AI 448 Current fan stage (Current fan stage); AI 449 Current room occupancy (Current room occupancy); AI 450 Control variable Heating Controller 1 (Controller 1 heating output); AI 451 Control variable Cooling Controller 1 (Controller 1 cooling output).
How do I check these points on the real Thermokon Thanos room operating unit via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Thermokon_Thanos_a · Thermokon_Thanos_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.