Generator set monitor · BACnet points list
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Cummins CCM-G: 415 objects (255 AI, 160 BI), 83 polled by default. The map repeats one block per genset (Gen 0 to Gen 3): name, control switch, state, fault code and type, kW, frequency, PF, voltages, currents, engine values, counters and the annunciator bits. Only Gen 0 is polled by default.
This page lists 415 BACnet objects for the Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
- Equipment
- Generator set monitor
- Equipment type
- Other equipment
- BACnet objects
- 415 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Read Gen 0 state, running and supplying-load bits, kW and fault code; enable the Gen 1-3 blocks for more gensets.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 54 | Gen 0 Genset Running | Gen 0 running | Read |
| BI 53 | Gen 0 Genset Supplying Load | Gen 0 supplying load | Read |
| BI 55 | Gen 0 Not in Auto | Gen 0 not in auto | Read |
| AI 11 | Gen 0 State | Gen 0 state | Read |
| AI 21 | Gen 0 Total kW | Gen 0 total kW | Read |
| AI 18 | Gen 0 Frequency | Gen 0 frequency | Read |
| AI 23 | Gen 0 Volts ab | Gen 0 voltage A-B | Read |
| AI 12 | Gen 0 Fault Code | Gen 0 fault code | Read |
| BI 83 | Gen 0 Emergency Stop | Gen 0 emergency stop | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Gen 0 Start/Stop and Reset (AI 50, AI 51) are inputs here, so they cannot be written.
- Units in the Gen 0 block are partly off (e.g. Amps a shows volts); trust the names.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Gen 0 Name 0_1 | Modbus 400001 | Read | ||
| AI | 2 | Gen 0 Name 2_3 | Modbus 400002 | Read | ||
| AI | 3 | Gen 0 Name 4_5 | Modbus 400003 | Read | ||
| AI | 4 | Gen 0 Name 6_7 | Modbus 400004 | Read | ||
| AI | 5 | Gen 0 Name 8_9 | Modbus 400005 | Read | ||
| AI | 6 | Gen 0 Name 10_11 | Modbus 400006 | Read | ||
| AI | 7 | Gen 0 Name 12_13 | Modbus 400007 | Read | ||
| AI | 8 | Gen 0 Name 14_15 | Modbus 400008 | Read | ||
| AI | 9 | Gen 0 Device Type | Modbus 400009 | Read | ||
| AI | 10 | Gen 0 Control Switch | Modbus 400010 | Read | ||
| AImin | 11 | Gen 0 State | Modbus 400011 | Read | ||
| AImin | 12 | Gen 0 Fault Code | Modbus 400012 | Read | ||
| AI | 13 | Gen 0 Fault Type | Modbus 400013 | Read | ||
| AI | 14 | Gen 0 Percent kW | Modbus 400014 | % | Read | |
| AI | 15 | Gen 0 Total kW | Modbus 400015 | Read | ||
| AI | 16 | Gen 0 NFPA 110 | Modbus 400016 | Read | ||
| AI | 17 | Gen 0 Extended | Modbus 400017 | Read | ||
| AImin | 18 | Gen 0 Frequency | Modbus 400018 | Hz | Read | |
| AI | 19 | Gen 0 Total pf | Modbus 400019 | PF | Read | |
| AI | 20 | Gen 0 Total kva | Modbus 400020 | kVA | Read | |
| AImin | 21 | Gen 0 Total kW | Modbus 400021 | kW | Read | |
| AI | 22 | Gen 0 Total kvar | Modbus 400022 | kVAR | Read | |
| AImin | 23 | Gen 0 Volts ab | Modbus 400023 | V | Read | |
| AI | 24 | Gen 0 Volts bc | Modbus 400024 | V | Read | |
| AI | 25 | Gen 0 Volts ca | Modbus 400025 | V | Read | |
| AI | 26 | Gen 0 Volts a | Modbus 400026 | V | Read | |
| AI | 27 | Gen 0 Volts b | Modbus 400027 | V | Read | |
| AI | 28 | Gen 0 Volts c | Modbus 400028 | V | Read | |
| AI | 29 | Gen 0 Amps a | Modbus 400029 | V | Read | |
| AI | 30 | Gen 0 Amps b | Modbus 400030 | V | Read | |
| AI | 31 | Gen 0 Amps c | Modbus 400031 | V | Read | |
| AI | 32 | Gen 0 Percent Amps A | Modbus 400032 | % | Read | |
| AI | 33 | Gen 0 Percent Amps B | Modbus 400033 | % | Read | |
| AI | 34 | Gen 0 Percent Amps C | Modbus 400034 | % | Read | |
| AI | 35 | Gen 0 Battery Voltage | Modbus 400035 | V | Read | |
| AI | 36 | Gen 0 Oil Pressure | Modbus 400036 | kPa | Read | |
| AI | 37 | Gen 0 Oil Temp | Modbus 400037 | K | Read | |
| AI | 38 | Gen 0 Coolant Temp | Modbus 400038 | K | Read | |
| AI | 39 | Gen 0 Misc Temp 1 | Modbus 400039 | K | Read | |
| AI | 40 | Gen 0 Misc Temp 2 | Modbus 400040 | K | Read | |
| AI | 41 | Gen 0 Fuel Rate | Modbus 400041 | Read | ||
| AI | 42 | Gen 0 Engine RPM | Modbus 400042 | rpm | Read | |
| AI | 43 | Gen 0 Engine Starts | Modbus 400043 | Read | ||
| AI | 44 | Gen 0 Engine Run Time High | Modbus 400044 | s | Read | |
| AI | 45 | Gen 0 Engine Run Time Low | Modbus 400045 | s | Read | |
| AI | 46 | Gen 0 Total kwh High | Modbus 400046 | kWh | Read | |
| AI | 47 | Gen 0 Total kwh Low | Modbus 400047 | kWh | Read | |
| AI | 48 | Gen 0 Total Fuel High | Modbus 400048 | Read | ||
| AI | 49 | Gen 0 Total Fuel Low | Modbus 400049 | Read | ||
| AI | 50 | Gen 0 Start/Stop | Modbus 400050 | Read | ||
| AI | 51 | Gen 0 Reset | Modbus 400051 | Read | ||
| BI | 52 | Gen 0 Normal Power | Modbus 400016 bit 15 | Read | ||
| BImin | 53 | Gen 0 Genset Supplying Load | Modbus 400016 bit 14 | Read | ||
| BImin | 54 | Gen 0 Genset Running | Modbus 400016 bit 13 | Read | ||
| BImin | 55 | Gen 0 Not in Auto | Modbus 400016 bit 12 | Read | ||
| BI | 56 | Gen 0 High Battery Voltage | Modbus 400016 bit 11 | Read | ||
| BI | 57 | Gen 0 Low Battery Voltage | Modbus 400016 bit 10 | Read | ||
| BI | 58 | Gen 0 Charger AC Failure | Modbus 400016 bit 9 | Read | ||
| BI | 59 | Gen 0 Fail to Start | Modbus 400016 bit 8 | Read | ||
| BI | 60 | Gen 0 Low Coolant Temperature | Modbus 400016 bit 7 | Read | ||
| BI | 61 | Gen 0 Pre-High Engine Temperature | Modbus 400016 bit 6 | Read | ||
| BI | 62 | Gen 0 High Engine Temperature | Modbus 400016 bit 5 | Read | ||
| BI | 63 | Gen 0 Pre-Low Engine Temperature | Modbus 400016 bit 4 | Read | ||
| BI | 64 | Gen 0 Low Oil Pressure | Modbus 400016 bit 3 | Read | ||
| BI | 65 | Gen 0 Overspeed | Modbus 400016 bit 2 | Read | ||
| BI | 66 | Gen 0 Low Coolant Level | Modbus 400016 bit 1 | Read | ||
| BI | 67 | Gen 0 Low Fuel Level | Modbus 400016 bit 0 | Read | ||
| BI | 68 | Gen 0 Check Genset | Modbus 400017 bit 15 | Read | ||
| BI | 69 | Gen 0 Ground Fault | Modbus 400017 bit 14 | Read | ||
| BI | 70 | Gen 0 High AC Vvoltage | Modbus 400017 bit 13 | Read | ||
| BI | 71 | Gen 0 Low AC Voltage | Modbus 400017 bit 12 | Read | ||
| BI | 72 | Gen 0 Under Frequency | Modbus 400017 bit 11 | Read | ||
| BI | 73 | Gen 0 Overload | Modbus 400017 bit 10 | Read | ||
| BI | 74 | Gen 0 Overcurrent | Modbus 400017 bit 9 | Read | ||
| BI | 75 | Gen 0 Short Circuit | Modbus 400017 bit 8 | Read | ||
| BI | 76 | Gen 0 Reverse KW | Modbus 400017 bit 7 | Read | ||
| BI | 77 | Gen 0 Reverse KVAR | Modbus 400017 bit 6 | Read | ||
| BI | 78 | Gen 0 Fail to Sync | Modbus 400017 bit 5 | Read | ||
| BI | 79 | Gen 0 Fail to Close | Modbus 400017 bit 4 | Read | ||
| BI | 80 | Gen 0 Load Demand | Modbus 400017 bit 3 | Read | ||
| BI | 81 | Gen 0 Genset Circuit Breaker Tripped | Modbus 400017 bit 2 | Read | ||
| BI | 82 | Gen 0 Utlity Circuit Breaker Tripped | Modbus 400017 bit 1 | Read | ||
| BImin | 83 | Gen 0 Emergency Stop | Modbus 400017 bit 0 | Read | ||
| AI | 84 | Gen 1 Name 0_1 | Modbus 400101; not polled by default | Read | ||
| AI | 85 | Gen 1 Name 2_3 | Modbus 400102; not polled by default | Read | ||
| AI | 86 | Gen 1 Name 4_5 | Modbus 400103; not polled by default | Read | ||
| AI | 87 | Gen 1 Name 6_7 | Modbus 400104; not polled by default | Read | ||
| AI | 88 | Gen 1 Name 8_9 | Modbus 400105; not polled by default | Read | ||
| AI | 89 | Gen 1 Name 10_11 | Modbus 400106; not polled by default | Read | ||
| AI | 90 | Gen 1 Name 12_13 | Modbus 400107; not polled by default | Read | ||
| AI | 91 | Gen 1 Name 14_15 | Modbus 400108; not polled by default | Read | ||
| AI | 92 | Gen 1 Device Type | Modbus 400109; not polled by default | Read | ||
| AI | 93 | Gen 1 Control Switch | Modbus 400110; not polled by default | Read | ||
| AI | 94 | Gen 1 State | Modbus 400111; not polled by default | Read | ||
| AI | 95 | Gen 1 Fault Code | Modbus 400112; not polled by default | Read | ||
| AI | 96 | Gen 1 Fault Type | Modbus 400113; not polled by default | Read | ||
| AI | 97 | Gen 1 Percent kW | Modbus 400114; not polled by default | % | Read | |
| AI | 98 | Gen 1 Total kW | Modbus 400115; not polled by default | Read | ||
| AI | 99 | Gen 1 NFPA 110 | Modbus 400116; not polled by default | Read | ||
| AI | 100 | Gen 1 Extended | Modbus 400117; not polled by default | Read | ||
| AI | 101 | Gen 1 Frequency | Modbus 400118; not polled by default | Hz | Read | |
| AI | 102 | Gen 1 Total pf | Modbus 400119; not polled by default | PF | Read | |
| AI | 103 | Gen 1 Total kva | Modbus 400120; not polled by default | kVA | Read | |
| AI | 104 | Gen 1 Total kW | Modbus 400121; not polled by default | kW | Read | |
| AI | 105 | Gen 1 Total kvar | Modbus 400122; not polled by default | kVAR | Read | |
| AI | 106 | Gen 1 Volts ab | Modbus 400123; not polled by default | V | Read | |
| AI | 107 | Gen 1 Volts bc | Modbus 400124; not polled by default | V | Read | |
| AI | 108 | Gen 1 Volts ca | Modbus 400125; not polled by default | V | Read | |
| AI | 109 | Gen 1 Volts a | Modbus 400126; not polled by default | V | Read | |
| AI | 110 | Gen 1 Volts b | Modbus 400127; not polled by default | V | Read | |
| AI | 111 | Gen 1 Volts c | Modbus 400128; not polled by default | V | Read | |
| AI | 112 | Gen 1 Amps a | Modbus 400129; not polled by default | V | Read | |
| AI | 113 | Gen 1 Amps b | Modbus 400130; not polled by default | V | Read | |
| AI | 114 | Gen 1 Amps c | Modbus 400131; not polled by default | V | Read | |
| AI | 115 | Gen 1 Percent Amps A | Modbus 400132; not polled by default | % | Read | |
| AI | 116 | Gen 1 Percent Amps B | Modbus 400133; not polled by default | % | Read | |
| AI | 117 | Gen 1 Percent Amps C | Modbus 400134; not polled by default | % | Read | |
| AI | 118 | Gen 1 Battery Voltage | Modbus 400135; not polled by default | V | Read | |
| AI | 119 | Gen 1 Oil Pressure | Modbus 400136; not polled by default | kPa | Read | |
| AI | 120 | Gen 1 Oil Temp | Modbus 400137; not polled by default | K | Read | |
| AI | 121 | Gen 1 Coolant Temp | Modbus 400138; not polled by default | K | Read | |
| AI | 122 | Gen 1 Misc Temp 1 | Modbus 400139; not polled by default | K | Read | |
| AI | 123 | Gen 1 Misc Temp 2 | Modbus 400140; not polled by default | K | Read | |
| AI | 124 | Gen 1 Fuel Rate | Modbus 400141; not polled by default | Read | ||
| AI | 125 | Gen 1 Engine RPM | Modbus 400142; not polled by default | rpm | Read | |
| AI | 126 | Gen 1 Engine Starts | Modbus 400143; not polled by default | Read | ||
| AI | 127 | Gen 1 Engine Run Time High | Modbus 400144; not polled by default | s | Read | |
| AI | 128 | Gen 1 Engine Run Time Low | Modbus 400145; not polled by default | s | Read | |
| AI | 129 | Gen 1 Total kwh High | Modbus 400146; not polled by default | kWh | Read | |
| AI | 130 | Gen 1 Total kwh Low | Modbus 400147; not polled by default | kWh | Read | |
| AI | 131 | Gen 1 Total Fuel High | Modbus 400148; not polled by default | Read | ||
| AI | 132 | Gen 1 Total Fuel Low | Modbus 400149; not polled by default | Read | ||
| AI | 133 | Gen 1 Start/Stop | Modbus 400150; not polled by default | Read | ||
| AI | 134 | Gen 1 Reset | Modbus 400151; not polled by default | Read | ||
| BI | 135 | Gen 1 Normal Power | Modbus 400116 bit 15; not polled by default | Read | ||
| BI | 136 | Gen 1 Genset Supplying Load | Modbus 400116 bit 14; not polled by default | Read | ||
| BI | 137 | Gen 1 Genset Running | Modbus 400116 bit 13; not polled by default | Read | ||
| BI | 138 | Gen 1 Not in Auto | Modbus 400116 bit 12; not polled by default | Read | ||
| BI | 139 | Gen 1 High Battery Voltage | Modbus 400116 bit 11; not polled by default | Read | ||
| BI | 140 | Gen 1 Low Battery Voltage | Modbus 400116 bit 10; not polled by default | Read | ||
| BI | 141 | Gen 1 Charger AC Failure | Modbus 400116 bit 9; not polled by default | Read | ||
| BI | 142 | Gen 1 Fail to Start | Modbus 400116 bit 8; not polled by default | Read | ||
| BI | 143 | Gen 1 Low Coolant Temperature | Modbus 400116 bit 7; not polled by default | Read | ||
| BI | 144 | Gen 1 Pre-High Engine Temperature | Modbus 400116 bit 6; not polled by default | Read | ||
| BI | 145 | Gen 1 High Engine Temperature | Modbus 400116 bit 5; not polled by default | Read | ||
| BI | 146 | Gen 1 Pre-Low Engine Temperature | Modbus 400116 bit 4; not polled by default | Read | ||
| BI | 147 | Gen 1 Low Oil Pressure | Modbus 400116 bit 3; not polled by default | Read | ||
| BI | 148 | Gen 1 Overspeed | Modbus 400116 bit 2; not polled by default | Read | ||
| BI | 149 | Gen 1 Low Coolant Level | Modbus 400116 bit 1; not polled by default | Read | ||
| BI | 150 | Gen 1 Low Fuel Level | Modbus 400116 bit 0; not polled by default | Read | ||
| BI | 151 | Gen 1 Check Genset | Modbus 400117 bit 15; not polled by default | Read | ||
| BI | 152 | Gen 1 Ground Fault | Modbus 400117 bit 14; not polled by default | Read | ||
| BI | 153 | Gen 1 High AC Vvoltage | Modbus 400117 bit 13; not polled by default | Read | ||
| BI | 154 | Gen 1 Low AC Voltage | Modbus 400117 bit 12; not polled by default | Read | ||
| BI | 155 | Gen 1 Under Frequency | Modbus 400117 bit 11; not polled by default | Read | ||
| BI | 156 | Gen 1 Overload | Modbus 400117 bit 10; not polled by default | Read | ||
| BI | 157 | Gen 1 Overcurrent | Modbus 400117 bit 9; not polled by default | Read | ||
| BI | 158 | Gen 1 Short Circuit | Modbus 400117 bit 8; not polled by default | Read | ||
| BI | 159 | Gen 1 Reverse KW | Modbus 400117 bit 7; not polled by default | Read | ||
| BI | 160 | Gen 1 Reverse KVAR | Modbus 400117 bit 6; not polled by default | Read | ||
| BI | 161 | Gen 1 Fail to Sync | Modbus 400117 bit 5; not polled by default | Read | ||
| BI | 162 | Gen 1 Fail to Close | Modbus 400117 bit 4; not polled by default | Read | ||
| BI | 163 | Gen 1 Load Demand | Modbus 400117 bit 3; not polled by default | Read | ||
| BI | 164 | Gen 1 Genset Circuit Breaker Tripped | Modbus 400117 bit 2; not polled by default | Read | ||
| BI | 165 | Gen 1 Utlity Circuit Breaker Tripped | Modbus 400117 bit 1; not polled by default | Read | ||
| BI | 166 | Gen 1 Emergency Stop | Modbus 400117 bit 0; not polled by default | Read | ||
| AI | 167 | Gen 2 Name 0_1 | Modbus 400201; not polled by default | Read | ||
| AI | 168 | Gen 2 Name 2_3 | Modbus 400202; not polled by default | Read | ||
| AI | 169 | Gen 2 Name 4_5 | Modbus 400203; not polled by default | Read | ||
| AI | 170 | Gen 2 Name 6_7 | Modbus 400204; not polled by default | Read | ||
| AI | 171 | Gen 2 Name 8_9 | Modbus 400205; not polled by default | Read | ||
| AI | 172 | Gen 2 Name 10_11 | Modbus 400206; not polled by default | Read | ||
| AI | 173 | Gen 2 Name 12_13 | Modbus 400207; not polled by default | Read | ||
| AI | 174 | Gen 2 Name 14_15 | Modbus 400208; not polled by default | Read | ||
| AI | 175 | Gen 2 Device Type | Modbus 400209; not polled by default | Read | ||
| AI | 176 | Gen 2 Control Switch | Modbus 400210; not polled by default | Read | ||
| AI | 177 | Gen 2 State | Modbus 400211; not polled by default | Read | ||
| AI | 178 | Gen 2 Fault Code | Modbus 400212; not polled by default | Read | ||
| AI | 179 | Gen 2 Fault Type | Modbus 400213; not polled by default | Read | ||
| AI | 180 | Gen 2 Percent kW | Modbus 400214; not polled by default | % | Read | |
| AI | 181 | Gen 2 Total kW | Modbus 400215; not polled by default | Read | ||
| AI | 182 | Gen 2 NFPA 110 | Modbus 400216; not polled by default | Read | ||
| AI | 183 | Gen 2 Extended | Modbus 400217; not polled by default | Read | ||
| AI | 184 | Gen 2 Frequency | Modbus 400218; not polled by default | Hz | Read | |
| AI | 185 | Gen 2 Total pf | Modbus 400219; not polled by default | PF | Read | |
| AI | 186 | Gen 2 Total kva | Modbus 400220; not polled by default | kVA | Read | |
| AI | 187 | Gen 2 Total kW | Modbus 400221; not polled by default | kW | Read | |
| AI | 188 | Gen 2 Total kvar | Modbus 400222; not polled by default | kVAR | Read | |
| AI | 189 | Gen 2 Volts ab | Modbus 400223; not polled by default | V | Read | |
| AI | 190 | Gen 2 Volts bc | Modbus 400224; not polled by default | V | Read | |
| AI | 191 | Gen 2 Volts ca | Modbus 400225; not polled by default | V | Read | |
| AI | 192 | Gen 2 Volts a | Modbus 400226; not polled by default | V | Read | |
| AI | 193 | Gen 2 Volts b | Modbus 400227; not polled by default | V | Read | |
| AI | 194 | Gen 2 Volts c | Modbus 400228; not polled by default | V | Read | |
| AI | 195 | Gen 2 Amps a | Modbus 400229; not polled by default | V | Read | |
| AI | 196 | Gen 2 Amps b | Modbus 400230; not polled by default | V | Read | |
| AI | 197 | Gen 2 Amps c | Modbus 400231; not polled by default | V | Read | |
| AI | 198 | Gen 2 Percent Amps A | Modbus 400232; not polled by default | % | Read | |
| AI | 199 | Gen 2 Percent Amps B | Modbus 400233; not polled by default | % | Read | |
| AI | 200 | Gen 2 Percent Amps C | Modbus 400234; not polled by default | % | Read | |
| AI | 201 | Gen 2 Battery Voltage | Modbus 400235; not polled by default | V | Read | |
| AI | 202 | Gen 2 Oil Pressure | Modbus 400236; not polled by default | kPa | Read | |
| AI | 203 | Gen 2 Oil Temp | Modbus 400237; not polled by default | K | Read | |
| AI | 204 | Gen 2 Coolant Temp | Modbus 400238; not polled by default | K | Read | |
| AI | 205 | Gen 2 Misc Temp 1 | Modbus 400239; not polled by default | K | Read | |
| AI | 206 | Gen 2 Misc Temp 2 | Modbus 400240; not polled by default | K | Read | |
| AI | 207 | Gen 2 Fuel Rate | Modbus 400241; not polled by default | Read | ||
| AI | 208 | Gen 2 Engine RPM | Modbus 400242; not polled by default | rpm | Read | |
| AI | 209 | Gen 2 Engine Starts | Modbus 400243; not polled by default | Read | ||
| AI | 210 | Gen 2 Engine Run Time High | Modbus 400244; not polled by default | s | Read | |
| AI | 211 | Gen 2 Engine Run Time Low | Modbus 400245; not polled by default | s | Read | |
| AI | 212 | Gen 2 Total kwh High | Modbus 400246; not polled by default | kWh | Read | |
| AI | 213 | Gen 2 Total kwh Low | Modbus 400247; not polled by default | kWh | Read | |
| AI | 214 | Gen 2 Total Fuel High | Modbus 400248; not polled by default | Read | ||
| AI | 215 | Gen 2 Total Fuel Low | Modbus 400249; not polled by default | Read | ||
| AI | 216 | Gen 2 Start/Stop | Modbus 400250; not polled by default | Read | ||
| AI | 217 | Gen 2 Reset | Modbus 400251; not polled by default | Read | ||
| BI | 218 | Gen 2 Normal Power | Modbus 400216 bit 15; not polled by default | Read | ||
| BI | 219 | Gen 2 Genset Supplying Load | Modbus 400216 bit 14; not polled by default | Read | ||
| BI | 220 | Gen 2 Genset Running | Modbus 400216 bit 13; not polled by default | Read | ||
| BI | 221 | Gen 2 Not in Auto | Modbus 400216 bit 12; not polled by default | Read | ||
| BI | 222 | Gen 2 High Battery Voltage | Modbus 400216 bit 11; not polled by default | Read | ||
| BI | 223 | Gen 2 Low Battery Voltage | Modbus 400216 bit 10; not polled by default | Read | ||
| BI | 224 | Gen 2 Charger AC Failure | Modbus 400216 bit 9; not polled by default | Read | ||
| BI | 225 | Gen 2 Fail to Start | Modbus 400216 bit 8; not polled by default | Read | ||
| BI | 226 | Gen 2 Low Coolant Temperature | Modbus 400216 bit 7; not polled by default | Read | ||
| BI | 227 | Gen 2 Pre-High Engine Temperature | Modbus 400216 bit 6; not polled by default | Read | ||
| BI | 228 | Gen 2 High Engine Temperature | Modbus 400216 bit 5; not polled by default | Read | ||
| BI | 229 | Gen 2 Pre-Low Engine Temperature | Modbus 400216 bit 4; not polled by default | Read | ||
| BI | 230 | Gen 2 Low Oil Pressure | Modbus 400216 bit 3; not polled by default | Read | ||
| BI | 231 | Gen 2 Overspeed | Modbus 400216 bit 2; not polled by default | Read | ||
| BI | 232 | Gen 2 Low Coolant Level | Modbus 400216 bit 1; not polled by default | Read | ||
| BI | 233 | Gen 2 Low Fuel Level | Modbus 400216 bit 0; not polled by default | Read | ||
| BI | 234 | Gen 2 Check Genset | Modbus 400217 bit 15; not polled by default | Read | ||
| BI | 235 | Gen 2 Ground Fault | Modbus 400217 bit 14; not polled by default | Read | ||
| BI | 236 | Gen 2 High AC Vvoltage | Modbus 400217 bit 13; not polled by default | Read | ||
| BI | 237 | Gen 2 Low AC Voltage | Modbus 400217 bit 12; not polled by default | Read | ||
| BI | 238 | Gen 2 Under Frequency | Modbus 400217 bit 11; not polled by default | Read | ||
| BI | 239 | Gen 2 Overload | Modbus 400217 bit 10; not polled by default | Read | ||
| BI | 240 | Gen 2 Overcurrent | Modbus 400217 bit 9; not polled by default | Read | ||
| BI | 241 | Gen 2 Short Circuit | Modbus 400217 bit 8; not polled by default | Read | ||
| BI | 242 | Gen 2 Reverse KW | Modbus 400217 bit 7; not polled by default | Read | ||
| BI | 243 | Gen 2 Reverse KVAR | Modbus 400217 bit 6; not polled by default | Read | ||
| BI | 244 | Gen 2 Fail to Sync | Modbus 400217 bit 5; not polled by default | Read | ||
| BI | 245 | Gen 2 Fail to Close | Modbus 400217 bit 4; not polled by default | Read | ||
| BI | 246 | Gen 2 Load Demand | Modbus 400217 bit 3; not polled by default | Read | ||
| BI | 247 | Gen 2 Genset Circuit Breaker Tripped | Modbus 400217 bit 2; not polled by default | Read | ||
| BI | 248 | Gen 2 Utlity Circuit Breaker Tripped | Modbus 400217 bit 1; not polled by default | Read | ||
| BI | 249 | Gen 2 Emergency Stop | Modbus 400217 bit 0; not polled by default | Read | ||
| AI | 250 | Gen 3 Name 0_1 | Modbus 400301; not polled by default | Read | ||
| AI | 251 | Gen 3 Name 2_3 | Modbus 400302; not polled by default | Read | ||
| AI | 252 | Gen 3 Name 4_5 | Modbus 400303; not polled by default | Read | ||
| AI | 253 | Gen 3 Name 6_7 | Modbus 400304; not polled by default | Read | ||
| AI | 254 | Gen 3 Name 8_9 | Modbus 400305; not polled by default | Read | ||
| AI | 255 | Gen 3 Name 10_11 | Modbus 400306; not polled by default | Read | ||
| AI | 256 | Gen 3 Name 12_13 | Modbus 400307; not polled by default | Read | ||
| AI | 257 | Gen 3 Name 14_15 | Modbus 400308; not polled by default | Read | ||
| AI | 258 | Gen 3 Device Type | Modbus 400309; not polled by default | Read | ||
| AI | 259 | Gen 3 Control Switch | Modbus 400310; not polled by default | Read | ||
| AI | 260 | Gen 3 State | Modbus 400311; not polled by default | Read | ||
| AI | 261 | Gen 3 Fault Code | Modbus 400312; not polled by default | Read | ||
| AI | 262 | Gen 3 Fault Type | Modbus 400313; not polled by default | Read | ||
| AI | 263 | Gen 3 Percent kW | Modbus 400314; not polled by default | % | Read | |
| AI | 264 | Gen 3 Total kW | Modbus 400315; not polled by default | Read | ||
| AI | 265 | Gen 3 NFPA 110 | Modbus 400316; not polled by default | Read | ||
| AI | 266 | Gen 3 Extended | Modbus 400317; not polled by default | Read | ||
| AI | 267 | Gen 3 Frequency | Modbus 400318; not polled by default | Hz | Read | |
| AI | 268 | Gen 3 Total pf | Modbus 400319; not polled by default | PF | Read | |
| AI | 269 | Gen 3 Total kva | Modbus 400320; not polled by default | kVA | Read | |
| AI | 270 | Gen 3 Total kW | Modbus 400321; not polled by default | kW | Read | |
| AI | 271 | Gen 3 Total kvar | Modbus 400322; not polled by default | kVAR | Read | |
| AI | 272 | Gen 3 Volts ab | Modbus 400323; not polled by default | V | Read | |
| AI | 273 | Gen 3 Volts bc | Modbus 400324; not polled by default | V | Read | |
| AI | 274 | Gen 3 Volts ca | Modbus 400325; not polled by default | V | Read | |
| AI | 275 | Gen 3 Volts a | Modbus 400326; not polled by default | V | Read | |
| AI | 276 | Gen 3 Volts b | Modbus 400327; not polled by default | V | Read | |
| AI | 277 | Gen 3 Volts c | Modbus 400328; not polled by default | V | Read | |
| AI | 278 | Gen 3 Amps a | Modbus 400329; not polled by default | V | Read | |
| AI | 279 | Gen 3 Amps b | Modbus 400330; not polled by default | V | Read | |
| AI | 280 | Gen 3 Amps c | Modbus 400331; not polled by default | V | Read | |
| AI | 281 | Gen 3 Percent Amps A | Modbus 400332; not polled by default | % | Read | |
| AI | 282 | Gen 3 Percent Amps B | Modbus 400333; not polled by default | % | Read | |
| AI | 283 | Gen 3 Percent Amps C | Modbus 400334; not polled by default | % | Read | |
| AI | 284 | Gen 3 Battery Voltage | Modbus 400335; not polled by default | V | Read | |
| AI | 285 | Gen 3 Oil Pressure | Modbus 400336; not polled by default | kPa | Read | |
| AI | 286 | Gen 3 Oil Temp | Modbus 400337; not polled by default | K | Read | |
| AI | 287 | Gen 3 Coolant Temp | Modbus 400338; not polled by default | K | Read | |
| AI | 288 | Gen 3 Misc Temp 1 | Modbus 400339; not polled by default | K | Read | |
| AI | 289 | Gen 3 Misc Temp 2 | Modbus 400340; not polled by default | K | Read | |
| AI | 290 | Gen 3 Fuel Rate | Modbus 400341; not polled by default | Read | ||
| AI | 291 | Gen 3 Engine RPM | Modbus 400342; not polled by default | rpm | Read | |
| AI | 292 | Gen 3 Engine Starts | Modbus 400343; not polled by default | Read | ||
| AI | 293 | Gen 3 Engine Run Time High | Modbus 400344; not polled by default | s | Read | |
| AI | 294 | Gen 3 Engine Run Time Low | Modbus 400345; not polled by default | s | Read | |
| AI | 295 | Gen 3 Total kwh High | Modbus 400346; not polled by default | kWh | Read | |
| AI | 296 | Gen 3 Total kwh Low | Modbus 400347; not polled by default | kWh | Read | |
| AI | 297 | Gen 3 Total Fuel High | Modbus 400348; not polled by default | Read | ||
| AI | 298 | Gen 3 Total Fuel Low | Modbus 400349; not polled by default | Read | ||
| AI | 299 | Gen 3 Start/Stop | Modbus 400350; not polled by default | Read | ||
| AI | 300 | Gen 3 Reset | Modbus 400351; not polled by default | Read | ||
| BI | 301 | Gen 3 Normal Power | Modbus 400316 bit 15; not polled by default | Read | ||
| BI | 302 | Gen 3 Genset Supplying Load | Modbus 400316 bit 14; not polled by default | Read | ||
| BI | 303 | Gen 3 Genset Running | Modbus 400316 bit 13; not polled by default | Read | ||
| BI | 304 | Gen 3 Not in Auto | Modbus 400316 bit 12; not polled by default | Read | ||
| BI | 305 | Gen 3 High Battery Voltage | Modbus 400316 bit 11; not polled by default | Read | ||
| BI | 306 | Gen 3 Low Battery Voltage | Modbus 400316 bit 10; not polled by default | Read | ||
| BI | 307 | Gen 3 Charger AC Failure | Modbus 400316 bit 9; not polled by default | Read | ||
| BI | 308 | Gen 3 Fail to Start | Modbus 400316 bit 8; not polled by default | Read | ||
| BI | 309 | Gen 3 Low Coolant Temperature | Modbus 400316 bit 7; not polled by default | Read | ||
| BI | 310 | Gen 3 Pre-High Engine Temperature | Modbus 400316 bit 6; not polled by default | Read | ||
| BI | 311 | Gen 3 High Engine Temperature | Modbus 400316 bit 5; not polled by default | Read | ||
| BI | 312 | Gen 3 Pre-Low Engine Temperature | Modbus 400316 bit 4; not polled by default | Read | ||
| BI | 313 | Gen 3 Low Oil Pressure | Modbus 400316 bit 3; not polled by default | Read | ||
| BI | 314 | Gen 3 Overspeed | Modbus 400316 bit 2; not polled by default | Read | ||
| BI | 315 | Gen 3 Low Coolant Level | Modbus 400316 bit 1; not polled by default | Read | ||
| BI | 316 | Gen 3 Low Fuel Level | Modbus 400316 bit 0; not polled by default | Read | ||
| BI | 317 | Gen 3 Check Genset | Modbus 400317 bit 15; not polled by default | Read | ||
| BI | 318 | Gen 3 Ground Fault | Modbus 400317 bit 14; not polled by default | Read | ||
| BI | 319 | Gen 3 High AC Vvoltage | Modbus 400317 bit 13; not polled by default | Read | ||
| BI | 320 | Gen 3 Low AC Voltage | Modbus 400317 bit 12; not polled by default | Read | ||
| BI | 321 | Gen 3 Under Frequency | Modbus 400317 bit 11; not polled by default | Read | ||
| BI | 322 | Gen 3 Overload | Modbus 400317 bit 10; not polled by default | Read | ||
| BI | 323 | Gen 3 Overcurrent | Modbus 400317 bit 9; not polled by default | Read | ||
| BI | 324 | Gen 3 Short Circuit | Modbus 400317 bit 8; not polled by default | Read | ||
| BI | 325 | Gen 3 Reverse KW | Modbus 400317 bit 7; not polled by default | Read | ||
| BI | 326 | Gen 3 Reverse KVAR | Modbus 400317 bit 6; not polled by default | Read | ||
| BI | 327 | Gen 3 Fail to Sync | Modbus 400317 bit 5; not polled by default | Read | ||
| BI | 328 | Gen 3 Fail to Close | Modbus 400317 bit 4; not polled by default | Read | ||
| BI | 329 | Gen 3 Load Demand | Modbus 400317 bit 3; not polled by default | Read | ||
| BI | 330 | Gen 3 Genset Circuit Breaker Tripped | Modbus 400317 bit 2; not polled by default | Read | ||
| BI | 331 | Gen 3 Utlity Circuit Breaker Tripped | Modbus 400317 bit 1; not polled by default | Read | ||
| BI | 332 | Gen 3 Emergency Stop | Modbus 400317 bit 0; not polled by default | Read | ||
| AI | 333 | Gen 4 Name 0_1 | Modbus 400401; not polled by default | Read | ||
| AI | 334 | Gen 4 Name 2_3 | Modbus 400402; not polled by default | Read | ||
| AI | 335 | Gen 4 Name 4_5 | Modbus 400403; not polled by default | Read | ||
| AI | 336 | Gen 4 Name 6_7 | Modbus 400404; not polled by default | Read | ||
| AI | 337 | Gen 4 Name 8_9 | Modbus 400405; not polled by default | Read | ||
| AI | 338 | Gen 4 Name 10_11 | Modbus 400406; not polled by default | Read | ||
| AI | 339 | Gen 4 Name 12_13 | Modbus 400407; not polled by default | Read | ||
| AI | 340 | Gen 4 Name 14_15 | Modbus 400408; not polled by default | Read | ||
| AI | 341 | Gen 4 Device Type | Modbus 400409; not polled by default | Read | ||
| AI | 342 | Gen 4 Control Switch | Modbus 400410; not polled by default | Read | ||
| AI | 343 | Gen 4 State | Modbus 400411; not polled by default | Read | ||
| AI | 344 | Gen 4 Fault Code | Modbus 400412; not polled by default | Read | ||
| AI | 345 | Gen 4 Fault Type | Modbus 400413; not polled by default | Read | ||
| AI | 346 | Gen 4 Percent kW | Modbus 400414; not polled by default | % | Read | |
| AI | 347 | Gen 4 Total kW | Modbus 400415; not polled by default | Read | ||
| AI | 348 | Gen 4 NFPA 110 | Modbus 400416; not polled by default | Read | ||
| AI | 349 | Gen 4 Extended | Modbus 400417; not polled by default | Read | ||
| AI | 350 | Gen 4 Frequency | Modbus 400418; not polled by default | Hz | Read | |
| AI | 351 | Gen 4 Total pf | Modbus 400419; not polled by default | PF | Read | |
| AI | 352 | Gen 4 Total kva | Modbus 400420; not polled by default | kVA | Read | |
| AI | 353 | Gen 4 Total kW | Modbus 400421; not polled by default | kW | Read | |
| AI | 354 | Gen 4 Total kvar | Modbus 400422; not polled by default | kVAR | Read | |
| AI | 355 | Gen 4 Volts ab | Modbus 400423; not polled by default | V | Read | |
| AI | 356 | Gen 4 Volts bc | Modbus 400424; not polled by default | V | Read | |
| AI | 357 | Gen 4 Volts ca | Modbus 400425; not polled by default | V | Read | |
| AI | 358 | Gen 4 Volts a | Modbus 400426; not polled by default | V | Read | |
| AI | 359 | Gen 4 Volts b | Modbus 400427; not polled by default | V | Read | |
| AI | 360 | Gen 4 Volts c | Modbus 400428; not polled by default | V | Read | |
| AI | 361 | Gen 4 Amps a | Modbus 400429; not polled by default | V | Read | |
| AI | 362 | Gen 4 Amps b | Modbus 400430; not polled by default | V | Read | |
| AI | 363 | Gen 4 Amps c | Modbus 400431; not polled by default | V | Read | |
| AI | 364 | Gen 4 Percent Amps A | Modbus 400432; not polled by default | % | Read | |
| AI | 365 | Gen 4 Percent Amps B | Modbus 400433; not polled by default | % | Read | |
| AI | 366 | Gen 4 Percent Amps C | Modbus 400434; not polled by default | % | Read | |
| AI | 367 | Gen 4 Battery Voltage | Modbus 400435; not polled by default | V | Read | |
| AI | 368 | Gen 4 Oil Pressure | Modbus 400436; not polled by default | kPa | Read | |
| AI | 369 | Gen 4 Oil Temp | Modbus 400437; not polled by default | K | Read | |
| AI | 370 | Gen 4 Coolant Temp | Modbus 400438; not polled by default | K | Read | |
| AI | 371 | Gen 4 Misc Temp 1 | Modbus 400439; not polled by default | K | Read | |
| AI | 372 | Gen 4 Misc Temp 2 | Modbus 400440; not polled by default | K | Read | |
| AI | 373 | Gen 4 Fuel Rate | Modbus 400441; not polled by default | Read | ||
| AI | 374 | Gen 4 Engine RPM | Modbus 400442; not polled by default | rpm | Read | |
| AI | 375 | Gen 4 Engine Starts | Modbus 400443; not polled by default | Read | ||
| AI | 376 | Gen 4 Engine Run Time High | Modbus 400444; not polled by default | s | Read | |
| AI | 377 | Gen 4 Engine Run Time Low | Modbus 400445; not polled by default | s | Read | |
| AI | 378 | Gen 4 Total kwh High | Modbus 400446; not polled by default | kWh | Read | |
| AI | 379 | Gen 4 Total kwh Low | Modbus 400447; not polled by default | kWh | Read | |
| AI | 380 | Gen 4 Total Fuel High | Modbus 400448; not polled by default | Read | ||
| AI | 381 | Gen 4 Total Fuel Low | Modbus 400449; not polled by default | Read | ||
| AI | 382 | Gen 4 Start/Stop | Modbus 400450; not polled by default | Read | ||
| AI | 383 | Gen 4 Reset | Modbus 400451; not polled by default | Read | ||
| BI | 384 | Gen 4 Normal Power | Modbus 400416 bit 15; not polled by default | Read | ||
| BI | 385 | Gen 4 Genset Supplying Load | Modbus 400416 bit 14; not polled by default | Read | ||
| BI | 386 | Gen 4 Genset Running | Modbus 400416 bit 13; not polled by default | Read | ||
| BI | 387 | Gen 4 Not in Auto | Modbus 400416 bit 12; not polled by default | Read | ||
| BI | 388 | Gen 4 High Battery Voltage | Modbus 400416 bit 11; not polled by default | Read | ||
| BI | 389 | Gen 4 Low Battery Voltage | Modbus 400416 bit 10; not polled by default | Read | ||
| BI | 390 | Gen 4 Charger AC Failure | Modbus 400416 bit 9; not polled by default | Read | ||
| BI | 391 | Gen 4 Fail to Start | Modbus 400416 bit 8; not polled by default | Read | ||
| BI | 392 | Gen 4 Low Coolant Temperature | Modbus 400416 bit 7; not polled by default | Read | ||
| BI | 393 | Gen 4 Pre-High Engine Temperature | Modbus 400416 bit 6; not polled by default | Read | ||
| BI | 394 | Gen 4 High Engine Temperature | Modbus 400416 bit 5; not polled by default | Read | ||
| BI | 395 | Gen 4 Pre-Low Engine Temperature | Modbus 400416 bit 4; not polled by default | Read | ||
| BI | 396 | Gen 4 Low Oil Pressure | Modbus 400416 bit 3; not polled by default | Read | ||
| BI | 397 | Gen 4 Overspeed | Modbus 400416 bit 2; not polled by default | Read | ||
| BI | 398 | Gen 4 Low Coolant Level | Modbus 400416 bit 1; not polled by default | Read | ||
| BI | 399 | Gen 4 Low Fuel Level | Modbus 400416 bit 0; not polled by default | Read | ||
| BI | 400 | Gen 4 Check Genset | Modbus 400417 bit 15; not polled by default | Read | ||
| BI | 401 | Gen 4 Ground Fault | Modbus 400417 bit 14; not polled by default | Read | ||
| BI | 402 | Gen 4 High AC Vvoltage | Modbus 400417 bit 13; not polled by default | Read | ||
| BI | 403 | Gen 4 Low AC Voltage | Modbus 400417 bit 12; not polled by default | Read | ||
| BI | 404 | Gen 4 Under Frequency | Modbus 400417 bit 11; not polled by default | Read | ||
| BI | 405 | Gen 4 Overload | Modbus 400417 bit 10; not polled by default | Read | ||
| BI | 406 | Gen 4 Overcurrent | Modbus 400417 bit 9; not polled by default | Read | ||
| BI | 407 | Gen 4 Short Circuit | Modbus 400417 bit 8; not polled by default | Read | ||
| BI | 408 | Gen 4 Reverse KW | Modbus 400417 bit 7; not polled by default | Read | ||
| BI | 409 | Gen 4 Reverse KVAR | Modbus 400417 bit 6; not polled by default | Read | ||
| BI | 410 | Gen 4 Fail to Sync | Modbus 400417 bit 5; not polled by default | Read | ||
| BI | 411 | Gen 4 Fail to Close | Modbus 400417 bit 4; not polled by default | Read | ||
| BI | 412 | Gen 4 Load Demand | Modbus 400417 bit 3; not polled by default | Read | ||
| BI | 413 | Gen 4 Genset Circuit Breaker Tripped | Modbus 400417 bit 2; not polled by default | Read | ||
| BI | 414 | Gen 4 Utlity Circuit Breaker Tripped | Modbus 400417 bit 1; not polled by default | Read | ||
| BI | 415 | Gen 4 Emergency Stop | Modbus 400417 bit 0; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Cummins CCM-G point IDs by name
AI1Gen 0 Name 0_1AI2Gen 0 Name 2_3AI3Gen 0 Name 4_5AI4Gen 0 Name 6_7AI5Gen 0 Name 8_9AI6Gen 0 Name 10_11AI7Gen 0 Name 12_13AI8Gen 0 Name 14_15AI9Gen 0 Device TypeAI10Gen 0 Control SwitchAI11Gen 0 StateAI12Gen 0 Fault CodeAI13Gen 0 Fault TypeAI14Gen 0 Percent kWAI15Gen 0 Total kWAI16Gen 0 NFPA 110AI17Gen 0 ExtendedAI18Gen 0 FrequencyAI19Gen 0 Total pfAI20Gen 0 Total kvaAI21Gen 0 Total kWAI22Gen 0 Total kvarAI23Gen 0 Volts abAI24Gen 0 Volts bcAI25Gen 0 Volts caAI26Gen 0 Volts aAI27Gen 0 Volts bAI28Gen 0 Volts cAI29Gen 0 Amps aAI30Gen 0 Amps bAI31Gen 0 Amps cAI32Gen 0 Percent Amps AAI33Gen 0 Percent Amps BAI34Gen 0 Percent Amps CAI35Gen 0 Battery VoltageAI36Gen 0 Oil PressureAI37Gen 0 Oil TempAI38Gen 0 Coolant TempAI39Gen 0 Misc Temp 1AI40Gen 0 Misc Temp 2AI41Gen 0 Fuel RateAI42Gen 0 Engine RPMAI43Gen 0 Engine StartsAI44Gen 0 Engine Run Time HighAI45Gen 0 Engine Run Time LowAI46Gen 0 Total kwh HighAI47Gen 0 Total kwh LowAI48Gen 0 Total Fuel HighAI49Gen 0 Total Fuel LowAI50Gen 0 Start/StopAI51Gen 0 ResetBI52Gen 0 Normal PowerBI53Gen 0 Genset Supplying LoadBI54Gen 0 Genset RunningBI55Gen 0 Not in AutoBI56Gen 0 High Battery VoltageBI57Gen 0 Low Battery VoltageBI58Gen 0 Charger AC FailureBI59Gen 0 Fail to StartBI60Gen 0 Low Coolant TemperatureBI61Gen 0 Pre-High Engine TemperatureBI62Gen 0 High Engine TemperatureBI63Gen 0 Pre-Low Engine TemperatureBI64Gen 0 Low Oil PressureBI65Gen 0 OverspeedBI66Gen 0 Low Coolant LevelBI67Gen 0 Low Fuel LevelBI68Gen 0 Check GensetBI69Gen 0 Ground FaultBI70Gen 0 High AC VvoltageBI71Gen 0 Low AC VoltageBI72Gen 0 Under FrequencyBI73Gen 0 OverloadBI74Gen 0 OvercurrentBI75Gen 0 Short CircuitBI76Gen 0 Reverse KWBI77Gen 0 Reverse KVARBI78Gen 0 Fail to SyncBI79Gen 0 Fail to CloseBI80Gen 0 Load DemandBI81Gen 0 Genset Circuit Breaker TrippedBI82Gen 0 Utlity Circuit Breaker TrippedBI83Gen 0 Emergency StopAI84Gen 1 Name 0_1AI85Gen 1 Name 2_3AI86Gen 1 Name 4_5AI87Gen 1 Name 6_7AI88Gen 1 Name 8_9AI89Gen 1 Name 10_11AI90Gen 1 Name 12_13AI91Gen 1 Name 14_15AI92Gen 1 Device TypeAI93Gen 1 Control SwitchAI94Gen 1 StateAI95Gen 1 Fault CodeAI96Gen 1 Fault TypeAI97Gen 1 Percent kWAI98Gen 1 Total kWAI99Gen 1 NFPA 110AI100Gen 1 ExtendedAI101Gen 1 FrequencyAI102Gen 1 Total pfAI103Gen 1 Total kvaAI104Gen 1 Total kWAI105Gen 1 Total kvarAI106Gen 1 Volts abAI107Gen 1 Volts bcAI108Gen 1 Volts caAI109Gen 1 Volts aAI110Gen 1 Volts bAI111Gen 1 Volts cAI112Gen 1 Amps aAI113Gen 1 Amps bAI114Gen 1 Amps cAI115Gen 1 Percent Amps AAI116Gen 1 Percent Amps BAI117Gen 1 Percent Amps CAI118Gen 1 Battery VoltageAI119Gen 1 Oil PressureAI120Gen 1 Oil TempAI121Gen 1 Coolant TempAI122Gen 1 Misc Temp 1AI123Gen 1 Misc Temp 2AI124Gen 1 Fuel RateAI125Gen 1 Engine RPMAI126Gen 1 Engine StartsAI127Gen 1 Engine Run Time HighAI128Gen 1 Engine Run Time LowAI129Gen 1 Total kwh HighAI130Gen 1 Total kwh LowAI131Gen 1 Total Fuel HighAI132Gen 1 Total Fuel LowAI133Gen 1 Start/StopAI134Gen 1 ResetBI135Gen 1 Normal PowerBI136Gen 1 Genset Supplying LoadBI137Gen 1 Genset RunningBI138Gen 1 Not in AutoBI139Gen 1 High Battery VoltageBI140Gen 1 Low Battery VoltageBI141Gen 1 Charger AC FailureBI142Gen 1 Fail to StartBI143Gen 1 Low Coolant TemperatureBI144Gen 1 Pre-High Engine TemperatureBI145Gen 1 High Engine TemperatureBI146Gen 1 Pre-Low Engine TemperatureBI147Gen 1 Low Oil PressureBI148Gen 1 OverspeedBI149Gen 1 Low Coolant LevelBI150Gen 1 Low Fuel LevelBI151Gen 1 Check GensetBI152Gen 1 Ground FaultBI153Gen 1 High AC VvoltageBI154Gen 1 Low AC VoltageBI155Gen 1 Under FrequencyBI156Gen 1 OverloadBI157Gen 1 OvercurrentBI158Gen 1 Short CircuitBI159Gen 1 Reverse KWBI160Gen 1 Reverse KVARBI161Gen 1 Fail to SyncBI162Gen 1 Fail to CloseBI163Gen 1 Load DemandBI164Gen 1 Genset Circuit Breaker TrippedBI165Gen 1 Utlity Circuit Breaker TrippedBI166Gen 1 Emergency StopAI167Gen 2 Name 0_1AI168Gen 2 Name 2_3AI169Gen 2 Name 4_5AI170Gen 2 Name 6_7AI171Gen 2 Name 8_9AI172Gen 2 Name 10_11AI173Gen 2 Name 12_13AI174Gen 2 Name 14_15AI175Gen 2 Device TypeAI176Gen 2 Control SwitchAI177Gen 2 StateAI178Gen 2 Fault CodeAI179Gen 2 Fault TypeAI180Gen 2 Percent kWAI181Gen 2 Total kWAI182Gen 2 NFPA 110AI183Gen 2 ExtendedAI184Gen 2 FrequencyAI185Gen 2 Total pfAI186Gen 2 Total kvaAI187Gen 2 Total kWAI188Gen 2 Total kvarAI189Gen 2 Volts abAI190Gen 2 Volts bcAI191Gen 2 Volts caAI192Gen 2 Volts aAI193Gen 2 Volts bAI194Gen 2 Volts cAI195Gen 2 Amps aAI196Gen 2 Amps bAI197Gen 2 Amps cAI198Gen 2 Percent Amps AAI199Gen 2 Percent Amps BAI200Gen 2 Percent Amps CAI201Gen 2 Battery VoltageAI202Gen 2 Oil PressureAI203Gen 2 Oil TempAI204Gen 2 Coolant TempAI205Gen 2 Misc Temp 1AI206Gen 2 Misc Temp 2AI207Gen 2 Fuel RateAI208Gen 2 Engine RPMAI209Gen 2 Engine StartsAI210Gen 2 Engine Run Time HighAI211Gen 2 Engine Run Time LowAI212Gen 2 Total kwh HighAI213Gen 2 Total kwh LowAI214Gen 2 Total Fuel HighAI215Gen 2 Total Fuel LowAI216Gen 2 Start/StopAI217Gen 2 ResetBI218Gen 2 Normal PowerBI219Gen 2 Genset Supplying LoadBI220Gen 2 Genset RunningBI221Gen 2 Not in AutoBI222Gen 2 High Battery VoltageBI223Gen 2 Low Battery VoltageBI224Gen 2 Charger AC FailureBI225Gen 2 Fail to StartBI226Gen 2 Low Coolant TemperatureBI227Gen 2 Pre-High Engine TemperatureBI228Gen 2 High Engine TemperatureBI229Gen 2 Pre-Low Engine TemperatureBI230Gen 2 Low Oil PressureBI231Gen 2 OverspeedBI232Gen 2 Low Coolant LevelBI233Gen 2 Low Fuel LevelBI234Gen 2 Check GensetBI235Gen 2 Ground FaultBI236Gen 2 High AC VvoltageBI237Gen 2 Low AC VoltageBI238Gen 2 Under FrequencyBI239Gen 2 OverloadBI240Gen 2 OvercurrentBI241Gen 2 Short CircuitBI242Gen 2 Reverse KWBI243Gen 2 Reverse KVARBI244Gen 2 Fail to SyncBI245Gen 2 Fail to CloseBI246Gen 2 Load DemandBI247Gen 2 Genset Circuit Breaker TrippedBI248Gen 2 Utlity Circuit Breaker TrippedBI249Gen 2 Emergency StopAI250Gen 3 Name 0_1AI251Gen 3 Name 2_3AI252Gen 3 Name 4_5AI253Gen 3 Name 6_7AI254Gen 3 Name 8_9AI255Gen 3 Name 10_11AI256Gen 3 Name 12_13AI257Gen 3 Name 14_15AI258Gen 3 Device TypeAI259Gen 3 Control SwitchAI260Gen 3 StateAI261Gen 3 Fault CodeAI262Gen 3 Fault TypeAI263Gen 3 Percent kWAI264Gen 3 Total kWAI265Gen 3 NFPA 110AI266Gen 3 ExtendedAI267Gen 3 FrequencyAI268Gen 3 Total pfAI269Gen 3 Total kvaAI270Gen 3 Total kWAI271Gen 3 Total kvarAI272Gen 3 Volts abAI273Gen 3 Volts bcAI274Gen 3 Volts caAI275Gen 3 Volts aAI276Gen 3 Volts bAI277Gen 3 Volts cAI278Gen 3 Amps aAI279Gen 3 Amps bAI280Gen 3 Amps cAI281Gen 3 Percent Amps AAI282Gen 3 Percent Amps BAI283Gen 3 Percent Amps CAI284Gen 3 Battery VoltageAI285Gen 3 Oil PressureAI286Gen 3 Oil TempAI287Gen 3 Coolant TempAI288Gen 3 Misc Temp 1AI289Gen 3 Misc Temp 2AI290Gen 3 Fuel RateAI291Gen 3 Engine RPMAI292Gen 3 Engine StartsAI293Gen 3 Engine Run Time HighAI294Gen 3 Engine Run Time LowAI295Gen 3 Total kwh HighAI296Gen 3 Total kwh LowAI297Gen 3 Total Fuel HighAI298Gen 3 Total Fuel LowAI299Gen 3 Start/StopAI300Gen 3 ResetBI301Gen 3 Normal PowerBI302Gen 3 Genset Supplying LoadBI303Gen 3 Genset RunningBI304Gen 3 Not in AutoBI305Gen 3 High Battery VoltageBI306Gen 3 Low Battery VoltageBI307Gen 3 Charger AC FailureBI308Gen 3 Fail to StartBI309Gen 3 Low Coolant TemperatureBI310Gen 3 Pre-High Engine TemperatureBI311Gen 3 High Engine TemperatureBI312Gen 3 Pre-Low Engine TemperatureBI313Gen 3 Low Oil PressureBI314Gen 3 OverspeedBI315Gen 3 Low Coolant LevelBI316Gen 3 Low Fuel LevelBI317Gen 3 Check GensetBI318Gen 3 Ground FaultBI319Gen 3 High AC VvoltageBI320Gen 3 Low AC VoltageBI321Gen 3 Under FrequencyBI322Gen 3 OverloadBI323Gen 3 OvercurrentBI324Gen 3 Short CircuitBI325Gen 3 Reverse KWBI326Gen 3 Reverse KVARBI327Gen 3 Fail to SyncBI328Gen 3 Fail to CloseBI329Gen 3 Load DemandBI330Gen 3 Genset Circuit Breaker TrippedBI331Gen 3 Utlity Circuit Breaker TrippedBI332Gen 3 Emergency StopAI333Gen 4 Name 0_1AI334Gen 4 Name 2_3AI335Gen 4 Name 4_5AI336Gen 4 Name 6_7AI337Gen 4 Name 8_9AI338Gen 4 Name 10_11AI339Gen 4 Name 12_13AI340Gen 4 Name 14_15AI341Gen 4 Device TypeAI342Gen 4 Control SwitchAI343Gen 4 StateAI344Gen 4 Fault CodeAI345Gen 4 Fault TypeAI346Gen 4 Percent kWAI347Gen 4 Total kWAI348Gen 4 NFPA 110AI349Gen 4 ExtendedAI350Gen 4 FrequencyAI351Gen 4 Total pfAI352Gen 4 Total kvaAI353Gen 4 Total kWAI354Gen 4 Total kvarAI355Gen 4 Volts abAI356Gen 4 Volts bcAI357Gen 4 Volts caAI358Gen 4 Volts aAI359Gen 4 Volts bAI360Gen 4 Volts cAI361Gen 4 Amps aAI362Gen 4 Amps bAI363Gen 4 Amps cAI364Gen 4 Percent Amps AAI365Gen 4 Percent Amps BAI366Gen 4 Percent Amps CAI367Gen 4 Battery VoltageAI368Gen 4 Oil PressureAI369Gen 4 Oil TempAI370Gen 4 Coolant TempAI371Gen 4 Misc Temp 1AI372Gen 4 Misc Temp 2AI373Gen 4 Fuel RateAI374Gen 4 Engine RPMAI375Gen 4 Engine StartsAI376Gen 4 Engine Run Time HighAI377Gen 4 Engine Run Time LowAI378Gen 4 Total kwh HighAI379Gen 4 Total kwh LowAI380Gen 4 Total Fuel HighAI381Gen 4 Total Fuel LowAI382Gen 4 Start/StopAI383Gen 4 ResetBI384Gen 4 Normal PowerBI385Gen 4 Genset Supplying LoadBI386Gen 4 Genset RunningBI387Gen 4 Not in AutoBI388Gen 4 High Battery VoltageBI389Gen 4 Low Battery VoltageBI390Gen 4 Charger AC FailureBI391Gen 4 Fail to StartBI392Gen 4 Low Coolant TemperatureBI393Gen 4 Pre-High Engine TemperatureBI394Gen 4 High Engine TemperatureBI395Gen 4 Pre-Low Engine TemperatureBI396Gen 4 Low Oil PressureBI397Gen 4 OverspeedBI398Gen 4 Low Coolant LevelBI399Gen 4 Low Fuel LevelBI400Gen 4 Check GensetBI401Gen 4 Ground FaultBI402Gen 4 High AC VvoltageBI403Gen 4 Low AC VoltageBI404Gen 4 Under FrequencyBI405Gen 4 OverloadBI406Gen 4 OvercurrentBI407Gen 4 Short CircuitBI408Gen 4 Reverse KWBI409Gen 4 Reverse KVARBI410Gen 4 Fail to SyncBI411Gen 4 Fail to CloseBI412Gen 4 Load DemandBI413Gen 4 Genset Circuit Breaker TrippedBI414Gen 4 Utlity Circuit Breaker TrippedBI415Gen 4 Emergency Stop
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Cummins_Single_PowCmd_CCM_G_Genset_LX.csv; the profile maps the registers in the Cummins ModLon gateway Modbus map (https://www.ccontrols.com/support/dp/MODLON_Gateway.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 83 of the 415 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Gen 0 Total kW; Gen 1 Total kW; Gen 2 Total kW...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
How many BACnet points does the Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX have?
This list has 415 BACnet objects: 255 analog inputs, 160 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Cummins_Single_PowCmd_CCM_G_Genset (Cummins_Single_PowCmd_CCM_G_Genset_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Cummins_Single_PowCmd_CCM_G_Genset.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX?
Start with BI 54 Gen 0 Genset Running (Gen 0 running); BI 53 Gen 0 Genset Supplying Load (Gen 0 supplying load); BI 55 Gen 0 Not in Auto (Gen 0 not in auto); AI 11 Gen 0 State (Gen 0 state); AI 21 Gen 0 Total kW (Gen 0 total kW); AI 18 Gen 0 Frequency (Gen 0 frequency); AI 23 Gen 0 Volts ab (Gen 0 voltage A-B); AI 12 Gen 0 Fault Code (Gen 0 fault code); BI 83 Gen 0 Emergency Stop (Gen 0 emergency stop).
How do I check these points on the real Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Cummins_Single_PowCmd_CCM_G_Genset · Cummins_Single_PowCmd_CCM_G_Genset_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.