Boiler sequencer (boiler management system) · BACnet points list
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the AERCO BMS / BMS II plant sequencer: 188 objects (173 AI, 15 BI), 34 polled by default. It reads header, outside and indoor/return temperatures, header setpoint, fire rate out, boilers fired and on line, the fault/message bits and the configuration menu values. There are no output objects.
This page lists 188 BACnet objects for the Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- AERCO BMS / BMS II Boiler Management System via BASgatewayLX
- Equipment
- Boiler sequencer (boiler management system)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 188 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- AERCO BMS, AERCO BMS II, Boiler Management System, BMSII
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
Read header temperature against the header setpoint, fire rate and boilers fired; watch the fault bits. Setpoints are changed on the BMS panel, not through this profile.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Header Temperature | Header temperature | Read |
| AI 5 | Header Set Temperature | Header setpoint | Read |
| AI 4 | Fire Rate Out | Fire rate out, % | Read |
| AI 7 | Total Boilers Fired | Boilers firing | Read |
| AI 8 | Total Boilers On Line | Boilers on line | Read |
| AI 2 | Outside Air Temperature | Outside air temperature | Read |
| BI 10 | Fault/Message Code Bit 1 = Header Sensor Error | Header sensor error | Read |
| BI 58 | Bit map BMS II Only Bit 1 = Fault Relay | Fault relay (BMS II only) | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Some bits are BMS II only or BMS only; the names say which.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Header Temperature | Modbus 300002 | °F | Read | |
| AImin | 2 | Outside Air Temperature | Modbus 300003 | °F | Read | |
| AI | 3 | Indoor Air/Return Temperature | Modbus 300004 | °F | Read | |
| AImin | 4 | Fire Rate Out | Modbus 300005 | % | Read | |
| AImin | 5 | Header Set Temperature | Modbus 300006 | °F | Read | |
| AI | 6 | Network Address | Modbus 300007; not polled by default | Read | ||
| AImin | 7 | Total Boilers Fired | Modbus 300008 | Read | ||
| AImin | 8 | Total Boilers On Line | Modbus 300009 | Read | ||
| BI | 9 | Fault/Message Code Bit 0 = Outside Air Sensor | Modbus 300011 bit 0 | Read | ||
| BImin | 10 | Fault/Message Code Bit 1 = Header Sensor Error | Modbus 300011 bit 1 | Read | ||
| BI | 11 | Fault/Message Code Bit 2 = Interlock 1 Error | Modbus 300011 bit 2 | Read | ||
| BI | 12 | Fault/Message Code Bit 3 = Interlock 2 Error | Modbus 300011 bit 3 | Read | ||
| BI | 13 | Fault/Message Code BMS Bit 4 = Indoor Air Sensor Error | Modbus 300011 bit 4 | Read | ||
| BI | 14 | Fault/Message Code BMSII Bit 4 = Return Sensor Error | Modbus 300011 bit 4 | Read | ||
| BI | 15 | Fault/Message Code Bit 5 = 4-20mA Input Error | Modbus 300011 bit 5 | Read | ||
| AI | 16 | Lead Boiler Number | Modbus 300017 | Read | ||
| AI | 17 | Boiler 1 Status (PWM Boiler 1) | Modbus 300018; not polled by default | Read | ||
| AI | 18 | Boiler 2 Status (PWM Boiler 2) | Modbus 300019; not polled by default | Read | ||
| AI | 19 | Boiler 3 Status (PWM Boiler 3) | Modbus 300020; not polled by default | Read | ||
| AI | 20 | Boiler 4 Status (PWM Boiler 4) | Modbus 300021; not polled by default | Read | ||
| AI | 21 | Boiler 5 Status (PWM Boiler 5) | Modbus 300022; not polled by default | Read | ||
| AI | 22 | Boiler 6 Status (PWM Boiler 6) | Modbus 300023; not polled by default | Read | ||
| AI | 23 | Boiler 7 Status (PWM Boiler 7) | Modbus 300024; not polled by default | Read | ||
| AI | 24 | Boiler 8 Status (PWM Boiler 8) | Modbus 300025; not polled by default | Read | ||
| AI | 25 | Boiler 9 Status (BMS) (Net Boiler 1) Boiler 1 Status (BMS II) | Modbus 300026; not polled by default | Read | ||
| AI | 26 | Boiler 10 Status (BMS) (Net Boiler 2) Boiler 2 Status (BMS II) | Modbus 300027; not polled by default | Read | ||
| AI | 27 | Boiler 11 Status (BMS) (Net Boiler 3) Boiler 3 Status (BMS II) | Modbus 300028; not polled by default | Read | ||
| AI | 28 | Boiler 12 Status (BMS) (Net Boiler 4) Boiler 4 Status (BMS II) | Modbus 300029; not polled by default | Read | ||
| AI | 29 | Boiler 13 Status (BMS) (Net Boiler 5) Boiler 5 Status (BMS II) | Modbus 300030; not polled by default | Read | ||
| AI | 30 | Boiler 14 Status (BMS) (Net Boiler 6) Boiler 6 Status (BMS II) | Modbus 300031; not polled by default | Read | ||
| AI | 31 | Boiler 15 Status (BMS) (Net Boiler 7) Boiler 7 Status (BMS II) | Modbus 300032; not polled by default | Read | ||
| AI | 32 | Boiler 16 Status (BMS) (Net Boiler 8) Boiler 8 Status (BMS II) | Modbus 300033; not polled by default | Read | ||
| AI | 33 | Boiler 17 Status (BMS) (Net Boiler 9) Boiler 9 Status (BMS II) | Modbus 300034; not polled by default | Read | ||
| AI | 34 | Boiler 18 Status (BMS) (Net Boiler 10) Boiler 10 Status (BMS II) | Modbus 300035; not polled by default | Read | ||
| AI | 35 | Boiler 19 Status (BMS) (Net Boiler 11) Boiler 11 Status (BMS II) | Modbus 300036; not polled by default | Read | ||
| AI | 36 | Boiler 20 Status (BMS) (Net Boiler 12) Boiler 12 Status (BMS II) | Modbus 300037; not polled by default | Read | ||
| AI | 37 | Boiler 21 Status (BMS) (Net Boiler 13) Boiler 13 Status (BMS II) | Modbus 300038; not polled by default | Read | ||
| AI | 38 | Boiler 22 Status (BMS) (Net Boiler 14) Boiler 14 Status (BMS II) | Modbus 300039; not polled by default | Read | ||
| AI | 39 | Boiler 23 Status (BMS) (Net Boiler 15) Boiler 15 Status (BMS II) | Modbus 300040; not polled by default | Read | ||
| AI | 40 | Boiler 24 Status (BMS) (Net Boiler 16) Boiler 16 Status (BMS II) | Modbus 300041; not polled by default | Read | ||
| AI | 41 | Boiler 25 Status (BMS) (Net Boiler 17) Boiler 17 Status (BMS II) | Modbus 300042; not polled by default | Read | ||
| AI | 42 | Boiler 26 Status (BMS) (Net Boiler 18) Boiler 18 Status (BMS II) | Modbus 300043; not polled by default | Read | ||
| AI | 43 | Boiler 27 Status (BMS) (Net Boiler 19) Boiler 19 Status (BMS II) | Modbus 300044; not polled by default | Read | ||
| AI | 44 | Boiler 28 Status (BMS) (Net Boiler 20) Boiler 20 Status (BMS II) | Modbus 300045; not polled by default | Read | ||
| AI | 45 | Boiler 29 Status (BMS) (Net Boiler 21) Boiler 21 Status (BMS II) | Modbus 300046; not polled by default | Read | ||
| AI | 46 | Boiler 30 Status (BMS) (Net Boiler 22) Boiler 22 Status (BMS II) | Modbus 300047; not polled by default | Read | ||
| AI | 47 | Boiler 31 Status (BMS) (Net Boiler 23) Boiler 23 Status (BMS II) | Modbus 300048; not polled by default | Read | ||
| AI | 48 | Boiler 32 Status (BMS) (Net Boiler 24) Boiler 24 Status (BMS II) | Modbus 300049; not polled by default | Read | ||
| AI | 49 | Boiler 33 Status (BMS) (Net Boiler 25) Boiler 25 Status (BMS II) | Modbus 300050; not polled by default | Read | ||
| AI | 50 | Boiler 34 Status (BMS) (Net Boiler 25) Boiler 25 Status (BMS II) | Modbus 300051; not polled by default | Read | ||
| AI | 51 | Boiler 35 Status (BMS) (Net Boiler 27) Boiler 27 Status (BMS II) | Modbus 300052; not polled by default | Read | ||
| AI | 52 | Boiler 36 Status (BMS) (Net Boiler 28) Boiler 28 Status (BMS II) | Modbus 300053; not polled by default | Read | ||
| AI | 53 | Boiler 37 Status (BMS) (Net Boiler 29) Boiler 29 Status (BMS II) | Modbus 300054; not polled by default | Read | ||
| AI | 54 | Boiler 38 Status (BMS) (Net Boiler 30) Boiler 30 Status (BMS II) | Modbus 300055; not polled by default | Read | ||
| AI | 55 | Boiler 39 Status (BMS) (Net Boiler 31) Boiler 31 Status (BMS II) | Modbus 300056; not polled by default | Read | ||
| AI | 56 | Boiler 40 Status (BMS) (Net Boiler 32) Boiler 32 Status (BMS II) | Modbus 300057; not polled by default | Read | ||
| BI | 57 | Bit map BMS II Only Bit 0 = AUX Relay | Modbus 300058 bit 0 | Read | ||
| BImin | 58 | Bit map BMS II Only Bit 1 = Fault Relay | Modbus 300058 bit 1 | Read | ||
| BI | 59 | Bit map BMS II Only Bit 2 = Sys Start Relay | Modbus 300058 bit 2 | Read | ||
| BI | 60 | Bit map BMS II Only Bit 3 = Empty | Modbus 300058 bit 3 | Read | ||
| BI | 61 | Bit map BMS II Only Bit 4 = Setback | Modbus 300058 bit 4 | Read | ||
| BI | 62 | Bit map BMS II Only Bit 5 = Interlock 2 | Modbus 300058 bit 5 | Read | ||
| BI | 63 | Bit map BMS II Only Bit 6 = Interlock 1 | Modbus 300058 bit 6 | Read | ||
| BI | 64 | Bit map BMS II Only Bit 7 = Empty | Modbus 300058 bit 7 | Read | ||
| AI | 65 | Return Sensor Temp BMS II Only | Modbus 300059 | °F | Read | |
| AI | 66 | Net Header Set Temp | Modbus 400005 | °F | Read | |
| AI | 67 | System Start Temp | Modbus 400006 | °F | Read | |
| AI | 68 | System Start Option | Modbus 400007 | Read | ||
| AI | 69 | Manual Hdr Set Manual Hdr Set | Modbus 400008 | °F | Read | |
| AI | 70 | Bldg Ref Temp | Modbus 400009 | °F | Read | |
| AI | 71 | Indoor Prop Band | Modbus 400010 | °F | Read | |
| AI | 72 | Indoor Setpoint Temp | Modbus 400011 | °F | Read | |
| AI | 73 | Reset Ratio | Modbus 400012; not polled by default | Read | ||
| AI | 74 | Max Header Temp | Modbus 400013 | °F | Read | |
| AI | 75 | Min Header Temp | Modbus 400014 | °F | Read | |
| AI | 76 | Start Percent | Modbus 400015; not polled by default | % | Read | |
| AI | 77 | Stop Percent | Modbus 400016; not polled by default | % | Read | |
| AI | 78 | Integral Gain | Modbus 400017; not polled by default | Read | ||
| AI | 79 | Header Set Mode | Modbus 400018; not polled by default | Read | ||
| AI | 80 | Derivative Gain | Modbus 400019; not polled by default | Read | ||
| AI | 81 | Header Temp Bandwidth | Modbus 400020; not polled by default | °F | Read | |
| AI | 82 | Aux Relay Open | Modbus 400021; not polled by default | % | Read | |
| AI | 83 | Aux Relay Mode | Modbus 400022; not polled by default | Read | ||
| AI | 84 | Temp Sensor Fail Mode/Failsafe Mode | Modbus 400023; not polled by default | Read | ||
| AI | 85 | Fault Alarm Relay Mode | Modbus 400024; not polled by default | Read | ||
| AI | 86 | Fault Alarm Clear Method | Modbus 400025; not polled by default | Read | ||
| AI | 87 | Boiler Operation Mode | Modbus 400026; not polled by default | Read | ||
| AI | 88 | Number Of Combination Mode Boilers | Modbus 400027; not polled by default | Read | ||
| AI | 89 | Max Power Input | Modbus 400031; not polled by default | % | Read | |
| AI | 90 | Interlock 1 Method (BMS)/Sys Intlk Config (BMSII) | Modbus 400032; not polled by default | Read | ||
| AI | 91 | Real Time Clock Minutes | Modbus 400033; not polled by default | min | Read | |
| AI | 92 | Real Time Clock Hours | Modbus 400034; not polled by default | h | Read | |
| AI | 93 | Real Time Clock Day of Week | Modbus 400035; not polled by default | days | Read | |
| AI | 94 | Real Time Clock Year | Modbus 400036; not polled by default | years | Read | |
| AI | 95 | Real Time Clock Day of Month | Modbus 400037; not polled by default | days | Read | |
| AI | 96 | Real Time Clock Month | Modbus 400038; not polled by default | months | Read | |
| AI | 97 | Offset Temp Day 1 | Modbus 400039; not polled by default | °F | Read | |
| AI | 98 | Offset Temp Day 2 | Modbus 400040; not polled by default | °F | Read | |
| AI | 99 | Offset Temp Day 3 | Modbus 400041; not polled by default | °F | Read | |
| AI | 100 | Offset Temp Day 4 | Modbus 400042; not polled by default | °F | Read | |
| AI | 101 | Offset Temp Day 5 | Modbus 400043; not polled by default | °F | Read | |
| AI | 102 | Offset Temp Day 6 | Modbus 400044; not polled by default | °F | Read | |
| AI | 103 | Offset Temp Day 7 | Modbus 400045; not polled by default | °F | Read | |
| AI | 104 | Offset On Time Day 1 – Minutes | Modbus 400046; not polled by default | min | Read | |
| AI | 105 | Offset On Time Day 2 – Minutes | Modbus 400047; not polled by default | min | Read | |
| AI | 106 | Offset On Time Day 3 – Minutes | Modbus 400048; not polled by default | min | Read | |
| AI | 107 | Offset On Time Day 4 – Minutes | Modbus 400049; not polled by default | min | Read | |
| AI | 108 | Offset On Time Day 5 – Minutes | Modbus 400050; not polled by default | min | Read | |
| AI | 109 | Offset On Time Day 6 – Minutes | Modbus 400051; not polled by default | min | Read | |
| AI | 110 | Offset On Time Day 7 – Minutes | Modbus 400052; not polled by default | min | Read | |
| AI | 111 | Offset On Time Day 1 – Hours | Modbus 400053; not polled by default | h | Read | |
| AI | 112 | Offset On Time Day 2 – Hours | Modbus 400054; not polled by default | h | Read | |
| AI | 113 | Offset On Time Day 3 – Hours | Modbus 400055; not polled by default | h | Read | |
| AI | 114 | Offset On Time Day 4 – Hours | Modbus 400056; not polled by default | h | Read | |
| AI | 115 | Offset On Time Day 5 – Hours | Modbus 400057; not polled by default | h | Read | |
| AI | 116 | Offset On Time Day 6 – Hours | Modbus 400058; not polled by default | h | Read | |
| AI | 117 | Offset On Time Day 7 – Hours | Modbus 400059; not polled by default | h | Read | |
| AI | 118 | Offset Enable | Modbus 400060; not polled by default | Read | ||
| AI | 119 | Header Offset | Modbus 400061; not polled by default | °F | Read | |
| AI | 120 | System Start Interlock | Modbus 400062; not polled by default | Read | ||
| AI | 121 | Offset Off Time Day 1 – Minutes | Modbus 400071; not polled by default | min | Read | |
| AI | 122 | Offset Off Time Day 2 – Minutes | Modbus 400072; not polled by default | min | Read | |
| AI | 123 | Offset Off Time Day 3 – Minutes | Modbus 400073; not polled by default | min | Read | |
| AI | 124 | Offset Off Time Day 4 – Minutes | Modbus 400074; not polled by default | min | Read | |
| AI | 125 | Offset Off Time Day 5 – Minutes | Modbus 400075; not polled by default | min | Read | |
| AI | 126 | Offset Off Time Day 6 – Minutes | Modbus 400076; not polled by default | min | Read | |
| AI | 127 | Offset Off Time Day 7 – Minutes | Modbus 400077; not polled by default | min | Read | |
| AI | 128 | Offset Off Time Day 1 – Hours | Modbus 400078; not polled by default | h | Read | |
| AI | 129 | Offset Off Time Day 2 – Hours | Modbus 400079; not polled by default | h | Read | |
| AI | 130 | Offset Off Time Day 3 – Hours | Modbus 400080; not polled by default | h | Read | |
| AI | 131 | Offset Off Time Day 4 – Hours | Modbus 400081; not polled by default | h | Read | |
| AI | 132 | Offset Off Time Day 5 – Hours | Modbus 400082; not polled by default | h | Read | |
| AI | 133 | Offset Off Time Day 6 – Hours | Modbus 400083; not polled by default | h | Read | |
| AI | 134 | Offset Off Time Day 7 – Hours | Modbus 400084; not polled by default | h | Read | |
| AI | 135 | Indoor Air Input | Modbus 400086 | Read | ||
| AI | 136 | Remote Signal | Modbus 400087; not polled by default | Read | ||
| AI | 137 | RS232 Mode | Modbus 400088; not polled by default | Read | ||
| AI | 138 | RS232 Baud Rate | Modbus 400089; not polled by default | Read | ||
| AI | 139 | Number Of Network Boilers | Modbus 400090; not polled by default | Read | ||
| AI | 140 | Min Slave Address | Modbus 400091; not polled by default | Read | ||
| AI | 141 | Max Slave Address | Modbus 400092; not polled by default | Read | ||
| AI | 142 | Net Boiler 1 Address | Modbus 400093; not polled by default | Read | ||
| AI | 143 | Net Boiler 2 Address | Modbus 400094; not polled by default | Read | ||
| AI | 144 | Net Boiler 3 Address | Modbus 400095; not polled by default | Read | ||
| AI | 145 | Net Boiler 4 Address | Modbus 400096; not polled by default | Read | ||
| AI | 146 | Net Boiler 5 Address | Modbus 400097; not polled by default | Read | ||
| AI | 147 | Net Boiler 6 Address | Modbus 400098; not polled by default | Read | ||
| AI | 148 | Net Boiler 7 Address | Modbus 400099; not polled by default | Read | ||
| AI | 149 | Net Boiler 8 Address | Modbus 400100; not polled by default | Read | ||
| AI | 150 | Net Boiler 9 Address | Modbus 400101; not polled by default | Read | ||
| AI | 151 | Net Boiler 10 Address | Modbus 400102; not polled by default | Read | ||
| AI | 152 | Net Boiler 11 Address | Modbus 400103; not polled by default | Read | ||
| AI | 153 | Net Boiler 12 Address | Modbus 400104; not polled by default | Read | ||
| AI | 154 | Net Boiler 13 Address | Modbus 400105; not polled by default | Read | ||
| AI | 155 | Net Boiler 14 Address | Modbus 400106; not polled by default | Read | ||
| AI | 156 | Net Boiler 15 Address | Modbus 400107; not polled by default | Read | ||
| AI | 157 | Net Boiler 16 Address | Modbus 400108; not polled by default | Read | ||
| AI | 158 | Net Boiler 17 Address | Modbus 400109; not polled by default | Read | ||
| AI | 159 | Net Boiler 18 Address | Modbus 400110; not polled by default | Read | ||
| AI | 160 | Net Boiler 19 Address | Modbus 400111; not polled by default | Read | ||
| AI | 161 | Net Boiler 20 Address | Modbus 400112; not polled by default | Read | ||
| AI | 162 | Net Boiler 21 Address | Modbus 400113; not polled by default | Read | ||
| AI | 163 | Net Boiler 22 Address | Modbus 400114; not polled by default | Read | ||
| AI | 164 | Net Boiler 23 Address | Modbus 400115; not polled by default | Read | ||
| AI | 165 | Net Boiler 24 Address | Modbus 400116; not polled by default | Read | ||
| AI | 166 | Net Boiler 25 Address | Modbus 400117; not polled by default | Read | ||
| AI | 167 | Net Boiler 26 Address | Modbus 400118; not polled by default | Read | ||
| AI | 168 | Net Boiler 27 Address | Modbus 400119; not polled by default | Read | ||
| AI | 169 | Net Boiler 28 Address | Modbus 400120; not polled by default | Read | ||
| AI | 170 | Net Boiler 29 Address | Modbus 400121; not polled by default | Read | ||
| AI | 171 | Net Boiler 30 Address | Modbus 400122; not polled by default | Read | ||
| AI | 172 | Net Boiler 31 Address | Modbus 400123; not polled by default | Read | ||
| AI | 173 | Net Boiler 32 Address | Modbus 400124; not polled by default | Read | ||
| AI | 174 | Network Baud | Modbus 400125; not polled by default | Read | ||
| AI | 175 | Network Timeout | Modbus 400126; not polled by default | Read | ||
| AI | 176 | Password Lo | Modbus 400127; not polled by default | Read | ||
| AI | 177 | Password Hi | Modbus 400128; not polled by default | Read | ||
| AI | 178 | Modbus Control Type | Modbus 400129; not polled by default | Read | ||
| AI | 179 | Modbus Pass-Thru | Modbus 400130; not polled by default | Read | ||
| AI | 180 | Header Dead Band | Modbus 400131; not polled by default | °F | Read | |
| AI | 181 | Outside Temp Sensor Offset | Modbus 400132; not polled by default | °F | Read | |
| AI | 182 | Ramp Up %/MIN | Modbus 400133; not polled by default | Read | ||
| AI | 183 | Ramp Down %/MIN | Modbus 400134; not polled by default | Read | ||
| AI | 184 | Fault Alarm Boilers | Modbus 400135; not polled by default | Read | ||
| AI | 185 | 4 to 20 mA Current Offset | Modbus 400136; not polled by default | Read | ||
| AI | 186 | Return Sensor Offset | Modbus 400137; not polled by default | Read | ||
| AI | 187 | Load Start Pct | Modbus 400138; not polled by default | Read | ||
| AI | 188 | Load Stop Pct | Modbus 400139; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX AERCO BMS/BMSII point IDs by name
AI1Header TemperatureAI2Outside Air TemperatureAI3Indoor Air/Return TemperatureAI4Fire Rate OutAI5Header Set TemperatureAI6Network AddressAI7Total Boilers FiredAI8Total Boilers On LineBI9Fault/Message Code Bit 0 = Outside Air SensorBI10Fault/Message Code Bit 1 = Header Sensor ErrorBI11Fault/Message Code Bit 2 = Interlock 1 ErrorBI12Fault/Message Code Bit 3 = Interlock 2 ErrorBI13Fault/Message Code BMS Bit 4 = Indoor Air Sensor ErrorBI14Fault/Message Code BMSII Bit 4 = Return Sensor ErrorBI15Fault/Message Code Bit 5 = 4-20mA Input ErrorAI16Lead Boiler NumberAI17Boiler 1 Status (PWM Boiler 1)AI18Boiler 2 Status (PWM Boiler 2)AI19Boiler 3 Status (PWM Boiler 3)AI20Boiler 4 Status (PWM Boiler 4)AI21Boiler 5 Status (PWM Boiler 5)AI22Boiler 6 Status (PWM Boiler 6)AI23Boiler 7 Status (PWM Boiler 7)AI24Boiler 8 Status (PWM Boiler 8)AI25Boiler 9 Status (BMS) (Net Boiler 1) Boiler 1 Status (BMS II)AI26Boiler 10 Status (BMS) (Net Boiler 2) Boiler 2 Status (BMS II)AI27Boiler 11 Status (BMS) (Net Boiler 3) Boiler 3 Status (BMS II)AI28Boiler 12 Status (BMS) (Net Boiler 4) Boiler 4 Status (BMS II)AI29Boiler 13 Status (BMS) (Net Boiler 5) Boiler 5 Status (BMS II)AI30Boiler 14 Status (BMS) (Net Boiler 6) Boiler 6 Status (BMS II)AI31Boiler 15 Status (BMS) (Net Boiler 7) Boiler 7 Status (BMS II)AI32Boiler 16 Status (BMS) (Net Boiler 8) Boiler 8 Status (BMS II)AI33Boiler 17 Status (BMS) (Net Boiler 9) Boiler 9 Status (BMS II)AI34Boiler 18 Status (BMS) (Net Boiler 10) Boiler 10 Status (BMS II)AI35Boiler 19 Status (BMS) (Net Boiler 11) Boiler 11 Status (BMS II)AI36Boiler 20 Status (BMS) (Net Boiler 12) Boiler 12 Status (BMS II)AI37Boiler 21 Status (BMS) (Net Boiler 13) Boiler 13 Status (BMS II)AI38Boiler 22 Status (BMS) (Net Boiler 14) Boiler 14 Status (BMS II)AI39Boiler 23 Status (BMS) (Net Boiler 15) Boiler 15 Status (BMS II)AI40Boiler 24 Status (BMS) (Net Boiler 16) Boiler 16 Status (BMS II)AI41Boiler 25 Status (BMS) (Net Boiler 17) Boiler 17 Status (BMS II)AI42Boiler 26 Status (BMS) (Net Boiler 18) Boiler 18 Status (BMS II)AI43Boiler 27 Status (BMS) (Net Boiler 19) Boiler 19 Status (BMS II)AI44Boiler 28 Status (BMS) (Net Boiler 20) Boiler 20 Status (BMS II)AI45Boiler 29 Status (BMS) (Net Boiler 21) Boiler 21 Status (BMS II)AI46Boiler 30 Status (BMS) (Net Boiler 22) Boiler 22 Status (BMS II)AI47Boiler 31 Status (BMS) (Net Boiler 23) Boiler 23 Status (BMS II)AI48Boiler 32 Status (BMS) (Net Boiler 24) Boiler 24 Status (BMS II)AI49Boiler 33 Status (BMS) (Net Boiler 25) Boiler 25 Status (BMS II)AI50Boiler 34 Status (BMS) (Net Boiler 25) Boiler 25 Status (BMS II)AI51Boiler 35 Status (BMS) (Net Boiler 27) Boiler 27 Status (BMS II)AI52Boiler 36 Status (BMS) (Net Boiler 28) Boiler 28 Status (BMS II)AI53Boiler 37 Status (BMS) (Net Boiler 29) Boiler 29 Status (BMS II)AI54Boiler 38 Status (BMS) (Net Boiler 30) Boiler 30 Status (BMS II)AI55Boiler 39 Status (BMS) (Net Boiler 31) Boiler 31 Status (BMS II)AI56Boiler 40 Status (BMS) (Net Boiler 32) Boiler 32 Status (BMS II)BI57Bit map BMS II Only Bit 0 = AUX RelayBI58Bit map BMS II Only Bit 1 = Fault RelayBI59Bit map BMS II Only Bit 2 = Sys Start RelayBI60Bit map BMS II Only Bit 3 = EmptyBI61Bit map BMS II Only Bit 4 = SetbackBI62Bit map BMS II Only Bit 5 = Interlock 2BI63Bit map BMS II Only Bit 6 = Interlock 1BI64Bit map BMS II Only Bit 7 = EmptyAI65Return Sensor Temp BMS II OnlyAI66Net Header Set TempAI67System Start TempAI68System Start OptionAI69Manual Hdr Set Manual Hdr SetAI70Bldg Ref TempAI71Indoor Prop BandAI72Indoor Setpoint TempAI73Reset RatioAI74Max Header TempAI75Min Header TempAI76Start PercentAI77Stop PercentAI78Integral GainAI79Header Set ModeAI80Derivative GainAI81Header Temp BandwidthAI82Aux Relay OpenAI83Aux Relay ModeAI84Temp Sensor Fail Mode/Failsafe ModeAI85Fault Alarm Relay ModeAI86Fault Alarm Clear MethodAI87Boiler Operation ModeAI88Number Of Combination Mode BoilersAI89Max Power InputAI90Interlock 1 Method (BMS)/Sys Intlk Config (BMSII)AI91Real Time Clock MinutesAI92Real Time Clock HoursAI93Real Time Clock Day of WeekAI94Real Time Clock YearAI95Real Time Clock Day of MonthAI96Real Time Clock MonthAI97Offset Temp Day 1AI98Offset Temp Day 2AI99Offset Temp Day 3AI100Offset Temp Day 4AI101Offset Temp Day 5AI102Offset Temp Day 6AI103Offset Temp Day 7AI104Offset On Time Day 1 – MinutesAI105Offset On Time Day 2 – MinutesAI106Offset On Time Day 3 – MinutesAI107Offset On Time Day 4 – MinutesAI108Offset On Time Day 5 – MinutesAI109Offset On Time Day 6 – MinutesAI110Offset On Time Day 7 – MinutesAI111Offset On Time Day 1 – HoursAI112Offset On Time Day 2 – HoursAI113Offset On Time Day 3 – HoursAI114Offset On Time Day 4 – HoursAI115Offset On Time Day 5 – HoursAI116Offset On Time Day 6 – HoursAI117Offset On Time Day 7 – HoursAI118Offset EnableAI119Header OffsetAI120System Start InterlockAI121Offset Off Time Day 1 – MinutesAI122Offset Off Time Day 2 – MinutesAI123Offset Off Time Day 3 – MinutesAI124Offset Off Time Day 4 – MinutesAI125Offset Off Time Day 5 – MinutesAI126Offset Off Time Day 6 – MinutesAI127Offset Off Time Day 7 – MinutesAI128Offset Off Time Day 1 – HoursAI129Offset Off Time Day 2 – HoursAI130Offset Off Time Day 3 – HoursAI131Offset Off Time Day 4 – HoursAI132Offset Off Time Day 5 – HoursAI133Offset Off Time Day 6 – HoursAI134Offset Off Time Day 7 – HoursAI135Indoor Air InputAI136Remote SignalAI137RS232 ModeAI138RS232 Baud RateAI139Number Of Network BoilersAI140Min Slave AddressAI141Max Slave AddressAI142Net Boiler 1 AddressAI143Net Boiler 2 AddressAI144Net Boiler 3 AddressAI145Net Boiler 4 AddressAI146Net Boiler 5 AddressAI147Net Boiler 6 AddressAI148Net Boiler 7 AddressAI149Net Boiler 8 AddressAI150Net Boiler 9 AddressAI151Net Boiler 10 AddressAI152Net Boiler 11 AddressAI153Net Boiler 12 AddressAI154Net Boiler 13 AddressAI155Net Boiler 14 AddressAI156Net Boiler 15 AddressAI157Net Boiler 16 AddressAI158Net Boiler 17 AddressAI159Net Boiler 18 AddressAI160Net Boiler 19 AddressAI161Net Boiler 20 AddressAI162Net Boiler 21 AddressAI163Net Boiler 22 AddressAI164Net Boiler 23 AddressAI165Net Boiler 24 AddressAI166Net Boiler 25 AddressAI167Net Boiler 26 AddressAI168Net Boiler 27 AddressAI169Net Boiler 28 AddressAI170Net Boiler 29 AddressAI171Net Boiler 30 AddressAI172Net Boiler 31 AddressAI173Net Boiler 32 AddressAI174Network BaudAI175Network TimeoutAI176Password LoAI177Password HiAI178Modbus Control TypeAI179Modbus Pass-ThruAI180Header Dead BandAI181Outside Temp Sensor OffsetAI182Ramp Up %/MINAI183Ramp Down %/MINAI184Fault Alarm BoilersAI1854 to 20 mA Current OffsetAI186Return Sensor OffsetAI187Load Start PctAI188Load Stop Pct
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Aerco_Boiler_Mgmt_System_BMS_BMSII_LX.csv; the profile maps the registers in the AERCO BMS Modbus register list (https://www.ccontrols.com/support/dp/AercoBoilerMgmt.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 34 of the 188 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AERCO BMS / BMS II Boiler Management System via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
How many BACnet points does the Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX have?
This list has 188 BACnet objects: 173 analog inputs, 15 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Aerco_Boiler_Mgmt_System_BMS_BMSII (Aerco_Boiler_Mgmt_System_BMS_BMSII_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Aerco_Boiler_Mgmt_System_BMS_BMSII_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX?
Start with AI 1 Header Temperature (Header temperature); AI 5 Header Set Temperature (Header setpoint); AI 4 Fire Rate Out (Fire rate out, %); AI 7 Total Boilers Fired (Boilers firing); AI 8 Total Boilers On Line (Boilers on line); AI 2 Outside Air Temperature (Outside air temperature); BI 10 Fault/Message Code Bit 1 = Header Sensor Error (Header sensor error); BI 58 Bit map BMS II Only Bit 1 = Fault Relay (Fault relay (BMS II only)).
How do I check these points on the real AERCO BMS / BMS II Boiler Management System via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Aerco_Boiler_Mgmt_System_BMS_BMSII · Aerco_Boiler_Mgmt_System_BMS_BMSII_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.