- Home
- BACnet points lists
- Contemporary Controls
- Generac G-Panel generator control via BASgatewayLX
Generator set controller · BACnet points list
Contemporary Controls Generac G-Panel generator control via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Generac G-Panel: 197 objects (45 AI, 32 BI, 120 BO), 151 polled by default. Analog inputs give engine temperatures and pressures, fuel and coolant level, battery, bus and generator voltages, currents, kW, PF, frequency and rpm. The panel's status and alarm flags (common alarm, running, in auto, ready to accept load, each shutdown and warning) are mapped as Binary Outputs because they are Modbus coils.
This page lists 197 BACnet objects for the Contemporary Controls Generac G-Panel generator control via BASgatewayLX — 120 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Generac G-Panel generator control via BASgatewayLX
- Equipment
- Generator set controller
- Equipment type
- Other equipment
- BACnet objects
- 197 (120 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- G-Panel, Generac G Panel, Generac Modbus G-Panel
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Read RUNNING, GENERATOR IN AUTO, READY TO ACCEPT LOAD and COMMON ALARM (Binary Outputs here) plus generator kW and voltage.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 128 | RUNNING | Generator running | Command |
| BO 122 | GENERATOR IN AUTO | Generator in auto | Command |
| BO 129 | READY TO ACCEPT LOAD | Ready to accept load | Command |
| AI 35 | GEN TOTAL KW | Generator total kW | Read |
| AI 34 | GEN AVERAGE VOLTAGE | Generator average voltage | Read |
| AI 39 | GEN FREQUENCY | Generator frequency | Read |
| AI 18 | BATTERY VOLTAGE | Battery voltage | Read |
| BO 76 | COMMON ALARM | Common alarm | Command |
| BO 77 | COMMON WARNING | Common warning | Command |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Status and alarm flags are Binary Outputs (coils) in this profile; treat them as read-only and never write them.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Generac G-Panel generator control via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | OIL TEMPERATURE | Modbus 400140 | Read | ||
| AI | 2 | COOLANT TEMPERATURE | Modbus 400142 | Read | ||
| AI | 3 | OIL PRESSURE | Modbus 400144 | Read | ||
| AI | 4 | GOVERNOR COMMAND | Modbus 400146 | Read | ||
| AI | 5 | USER CONFIGURABLE 05 | Modbus 400148; not polled by default | Read | ||
| AI | 6 | USER CONFIGURABLE 06 | Modbus 400150; not polled by default | Read | ||
| AI | 7 | USER CONFIGURABLE 07 | Modbus 400152; not polled by default | Read | ||
| AI | 8 | USER CONFIGURABLE 08 | Modbus 400154; not polled by default | Read | ||
| AI | 9 | USER CONFIGURABLE 09 | Modbus 400156; not polled by default | Read | ||
| AI | 10 | COOLANT LEVEL | Modbus 400158 | Read | ||
| AI | 11 | FUEL LEVEL | Modbus 400160 | Read | ||
| AI | 12 | AI-1 AUX INPUT 1 | Modbus 400162 | Read | ||
| AI | 13 | AI-2 AUX INPUT 2 | Modbus 400164 | Read | ||
| AI | 14 | USER CONFIGURABLE 14 | Modbus 400166 | Read | ||
| AI | 15 | BAT CHARGE CURRENT | Modbus 400168 | Read | ||
| AI | 16 | USER CONFIGURABLE 16 | Modbus 400170 | Read | ||
| AI | 17 | USER CONFIGURABLE 17 | Modbus 400172 | Read | ||
| AImin | 18 | BATTERY VOLTAGE | Modbus 400174 | Read | ||
| AI | 19 | BUS CURRENT PHASE A | Modbus 400176 | Read | ||
| AI | 20 | BUS CURRENT PHASE B | Modbus 400178 | Read | ||
| AI | 21 | BUS CURRENT PHASE C | Modbus 400180 | Read | ||
| AI | 22 | BUS AVERAGE CURRENT | Modbus 400182 | Read | ||
| AI | 23 | GEN CURRENT PHASE A | Modbus 400184 | Read | ||
| AI | 24 | GEN CURRENT PHASE B | Modbus 400186 | Read | ||
| AI | 25 | GEN CURRENT PHASE C | Modbus 400188 | Read | ||
| AI | 26 | GEN AVERAGE CURRENT | Modbus 400190 | Read | ||
| AI | 27 | BUS VOLT PHASE A-B | Modbus 400192 | Read | ||
| AI | 28 | BUS VOLT PHASE B-C | Modbus 400194 | Read | ||
| AI | 29 | BUS VOLT PHASE C-A | Modbus 400196 | Read | ||
| AI | 30 | BUS AVERAGE VOLTAGE | Modbus 400198 | Read | ||
| AI | 31 | GEN VOLT PHASE A-B | Modbus 400200 | Read | ||
| AI | 32 | GEN VOLT PHASE B-C | Modbus 400202 | Read | ||
| AI | 33 | GEN VOLT PHASE C-A | Modbus 400204 | Read | ||
| AImin | 34 | GEN AVERAGE VOLTAGE | Modbus 400206 | Read | ||
| AImin | 35 | GEN TOTAL KW | Modbus 400208 | Read | ||
| AI | 36 | BUS TOTAL KW | Modbus 400210 | Read | ||
| AI | 37 | GEN TOTAL PF | Modbus 400212 | Read | ||
| AI | 38 | BUS TOTAL PF | Modbus 400214 | Read | ||
| AImin | 39 | GEN FREQUENCY | Modbus 400216 | Read | ||
| AI | 40 | BUS FREQUENCY | Modbus 400218 | Read | ||
| AI | 41 | ENGINE RPM | Modbus 400220 | Read | ||
| AI | 42 | RPM 2 | Modbus 400222 | Read | ||
| AI | 43 | RPM 3 | Modbus 400224 | Read | ||
| BI | 44 | AUTO SWITCH | Modbus 400129 bit 15 | Read | ||
| BI | 45 | MANUAL SWITCH | Modbus 400129 bit 14 | Read | ||
| BI | 46 | ALARM ACKNOWLEDGE | Modbus 400129 bit 13 | Read | ||
| BI | 47 | EMERGENCY STOP | Modbus 400129 bit 12 | Read | ||
| BI | 48 | REMOTE START | Modbus 400129 bit 11 | Read | ||
| BI | 49 | BATTERY CHARGER FAIL | Modbus 400129 bit 10 | Read | ||
| BI | 50 | RUPTURED BASIN | Modbus 400129 bit 9 | Read | ||
| BI | 51 | USER CONFIGURABLE 08 | Modbus 400129 bit 8; not polled by default | Read | ||
| BI | 52 | USER CONFIGURABLE 09 | Modbus 400129 bit 7; not polled by default | Read | ||
| BI | 53 | USER CONFIGURABLE 10 | Modbus 400129 bit 6; not polled by default | Read | ||
| BI | 54 | STOP DEADBUS CONNECT | Modbus 400129 bit 5 | Read | ||
| BI | 55 | EXERCISER | Modbus 400129 bit 4 | Read | ||
| BI | 56 | GEN SWITCH STATUS | Modbus 400129 bit 3 | Read | ||
| BI | 57 | UTIL SWITCH STATUS | Modbus 400129 bit 2 | Read | ||
| BI | 58 | SEL TRIP STATUS | Modbus 400129 bit 1 | Read | ||
| BI | 59 | MCB STATUS | Modbus 400129 bit 0 | Read | ||
| BI | 60 | PHASE ROTATION VALID | Modbus 400130 bit 15 | Read | ||
| BI | 61 | USER CONFIGURABLE 18 | Modbus 400130 bit 14; not polled by default | Read | ||
| BI | 62 | USER CONFIGURABLE 19 | Modbus 400130 bit 13; not polled by default | Read | ||
| BI | 63 | USER CONFIGURABLE 20 | Modbus 400130 bit 12; not polled by default | Read | ||
| BI | 64 | USER CONFIGURABLE 21 | Modbus 400130 bit 11; not polled by default | Read | ||
| BI | 65 | USER CONFIGURABLE 22 | Modbus 400130 bit 10; not polled by default | Read | ||
| BI | 66 | USER CONFIGURABLE 23 | Modbus 400130 bit 9; not polled by default | Read | ||
| BI | 67 | USER CONFIGURABLE 24 | Modbus 400130 bit 8; not polled by default | Read | ||
| BI | 68 | MODEM SELECTED | Modbus 400130 bit 7 | Read | ||
| BI | 69 | GENERATOR OVERSPEED | Modbus 400130 bit 6 | Read | ||
| BI | 70 | DI-1 | Modbus 400130 bit 5 | Read | ||
| BI | 71 | DI-2 | Modbus 400130 bit 4 | Read | ||
| BI | 72 | DI-3 / LINE POWER | Modbus 400130 bit 3 | Read | ||
| BI | 73 | DI-4 / GENERATOR PWR | Modbus 400130 bit 2 | Read | ||
| BI | 74 | USER CONFIGURABLE 31 | Modbus 400130 bit 1; not polled by default | Read | ||
| BI | 75 | USER CONFIGURABLE 32 | Modbus 400130 bit 0; not polled by default | Read | ||
| BOmin | 76 | COMMON ALARM | Modbus 400131 bit 15 | Command | ||
| BOmin | 77 | COMMON WARNING | Modbus 400131 bit 14 | Command | ||
| BO | 78 | LO OIL PRESSURE WARN | Modbus 400131 bit 13 | Command | ||
| BO | 79 | LO OIL PRESSURE ALRM | Modbus 400131 bit 12 | Command | ||
| BO | 80 | HI COOLANT TEMP WARN | Modbus 400131 bit 11 | Command | ||
| BO | 81 | HI COOLANT TEMP ALRM | Modbus 400131 bit 10 | Command | ||
| BO | 82 | LO COOLANT TEMP WARN | Modbus 400131 bit 9 | Command | ||
| BO | 83 | HI OIL TEMP WARN | Modbus 400131 bit 8 | Command | ||
| BO | 84 | HI OIL TEMP ALARM | Modbus 400131 bit 7 | Command | ||
| BO | 85 | LO BATTERY VOLT WARN | Modbus 400131 bit 6 | Command | ||
| BO | 86 | HI BATTERY VOLT WARN | Modbus 400131 bit 5 | Command | ||
| BO | 87 | OVERSPEED ALARM | Modbus 400131 bit 4 | Command | ||
| BO | 88 | UNDERSPEED ALARM | Modbus 400131 bit 3 | Command | ||
| BO | 89 | OVER VOLTAGE ALARM | Modbus 400131 bit 2 | Command | ||
| BO | 90 | UNDER VOLTAGE ALARM | Modbus 400131 bit 1 | Command | ||
| BO | 91 | OVER FREQUENCY ALARM | Modbus 400131 bit 0 | Command | ||
| BO | 92 | UNDER FREQUENCY ALRM | Modbus 400132 bit 15 | Command | ||
| BO | 93 | HI FUEL ALARM | Modbus 400132 bit 14 | Command | ||
| BO | 94 | LO FUEL WARNING | Modbus 400132 bit 13 | Command | ||
| BO | 95 | LO FUEL ALARM | Modbus 400132 bit 12 | Command | ||
| BO | 96 | FAIL TO START ALARM | Modbus 400132 bit 11 | Command | ||
| BO | 97 | COOLANT LEVEL ALARM | Modbus 400132 bit 10 | Command | ||
| BO | 98 | RPM SENSOR FAIL ALRM | Modbus 400132 bit 9 | Command | ||
| BO | 99 | START INHIBIT ALARM | Modbus 400132 bit 8 | Command | ||
| BO | 100 | ESTOP ALARM | Modbus 400132 bit 7 | Command | ||
| BO | 101 | OIL PRESS SENSOR FLT | Modbus 400132 bit 6 | Command | ||
| BO | 102 | OIL TEMP SENSOR FLT | Modbus 400132 bit 5 | Command | ||
| BO | 103 | COOLANT TEMP SENSOR | Modbus 400132 bit 4 | Command | ||
| BO | 104 | KNOCK UNIT FAULT | Modbus 400132 bit 3 | Command | ||
| BO | 105 | KNOCK NOT CALIBRATED | Modbus 400132 bit 2 | Command | ||
| BO | 106 | XFER SWITCH ERROR AL | Modbus 400132 bit 1 | Command | ||
| BO | 107 | REVERSE POWER ALARM | Modbus 400132 bit 0 | Command | ||
| BO | 108 | MCB IS OPEN | Modbus 400133 bit 15 | Command | ||
| BO | 109 | OIL FILT BLOCKD ALRM | Modbus 400133 bit 14 | Command | ||
| BO | 110 | AIR FILT BLOCKD ALRM | Modbus 400133 bit 13 | Command | ||
| BO | 111 | OXYGEN SENSOR FAULT | Modbus 400133 bit 12 | Command | ||
| BO | 112 | ALTERNATOR PROBLEM | Modbus 400133 bit 11 | Command | ||
| BO | 113 | GAS PRESSURE WARN | Modbus 400133 bit 10 | Command | ||
| BO | 114 | EXHAUST TEMP WARNING | Modbus 400133 bit 9 | Command | ||
| BO | 115 | EXHAUST TEMP ALARM | Modbus 400133 bit 8 | Command | ||
| BO | 116 | FLAME DETECTION | Modbus 400133 bit 7 | Command | ||
| BO | 117 | CARBON MONOXIDE ALRM | Modbus 400133 bit 6 | Command | ||
| BO | 118 | VACUUM SENSOR FAULT | Modbus 400133 bit 5 | Command | ||
| BO | 119 | CAM MAPPED O P | Modbus 400133 bit 4 | Command | ||
| BO | 120 | CRANK MAPPED O P | Modbus 400133 bit 3 | Command | ||
| BO | 121 | GAS FLOW SENSOR FLT | Modbus 400133 bit 2 | Command | ||
| BOmin | 122 | GENERATOR IN AUTO | Modbus 400133 bit 1 | Command | ||
| BO | 123 | GENERATOR IN MANUAL | Modbus 400133 bit 0 | Command | ||
| BO | 124 | GENERATOR IN OFF | Modbus 400134 bit 15 | Command | ||
| BO | 125 | ENGINE STOPPED | Modbus 400134 bit 14 | Command | ||
| BO | 126 | ENGINE STOPPED-ALARM | Modbus 400134 bit 13 | Command | ||
| BO | 127 | STOPPED READY TO RUN | Modbus 400134 bit 12 | Command | ||
| BOmin | 128 | RUNNING | Modbus 400134 bit 11 | Command | ||
| BOmin | 129 | READY TO ACCEPT LOAD | Modbus 400134 bit 10 | Command | ||
| BO | 130 | ALARMS ENABLED | Modbus 400134 bit 9 | Command | ||
| BO | 131 | IN WARM UP | Modbus 400134 bit 8 | Command | ||
| BO | 132 | IN COOL DOWN | Modbus 400134 bit 7 | Command | ||
| BO | 133 | CRANKING | Modbus 400134 bit 6 | Command | ||
| BO | 134 | VOLTAGE DROPOUT | Modbus 400134 bit 5 | Command | ||
| BO | 135 | VOLTAGE PICKUP | Modbus 400134 bit 4 | Command | ||
| BO | 136 | IN LINE INTRRPT DLY | Modbus 400134 bit 3 | Command | ||
| BO | 137 | IN RETURN toUTIL DLY | Modbus 400134 bit 2 | Command | ||
| BO | 138 | IN TDN | Modbus 400134 bit 1 | Command | ||
| BO | 139 | LOAD SHEDDING | Modbus 400134 bit 0 | Command | ||
| BO | 140 | OUT OF SERVICE | Modbus 400135 bit 15 | Command | ||
| BO | 141 | NEED SERVICE | Modbus 400135 bit 14 | Command | ||
| BO | 142 | BATTERY CHARGER FAIL | Modbus 400135 bit 13 | Command | ||
| BO | 143 | LINE POWER | Modbus 400135 bit 12 | Command | ||
| BO | 144 | GENERATOR POWER | Modbus 400135 bit 11 | Command | ||
| BO | 145 | GAS REDUCED - KNOCK | Modbus 400135 bit 10 | Command | ||
| BO | 146 | ALL ENGINES ON LINE | Modbus 400135 bit 9 | Command | ||
| BO | 147 | SHUTDOWN GENSET | Modbus 400135 bit 8 | Command | ||
| BO | 148 | CHECK VOLT PHASE ROT | Modbus 400135 bit 7 | Command | ||
| BO | 149 | CHECK CURR PHASE ROT | Modbus 400135 bit 6 | Command | ||
| BO | 150 | ILC ALARM/WARNING 1 | Modbus 400135 bit 5 | Command | ||
| BO | 151 | ILC ALARM/WARNING 2 | Modbus 400135 bit 4 | Command | ||
| BO | 152 | GAS SHUTOFF - KNOCK | Modbus 400135 bit 3 | Command | ||
| BO | 153 | HI INLET MAN TEMP AL | Modbus 400135 bit 2 | Command | ||
| BO | 154 | HI INLET MAN TEMP WN | Modbus 400135 bit 1 | Command | ||
| BO | 155 | LO TURBO PRESS - GAS | Modbus 400135 bit 0 | Command | ||
| BO | 156 | LO TURBO PRESS - DSL | Modbus 400136 bit 15 | Command | ||
| BO | 157 | LO GAS PRESS SHUTOFF | Modbus 400136 bit 14 | Command | ||
| BO | 158 | LO GAS PRESS DISABLE | Modbus 400136 bit 13 | Command | ||
| BO | 159 | HI GAS PRESS DISABLE | Modbus 400136 bit 12 | Command | ||
| BO | 160 | CAC BYPASS VALVE FLT | Modbus 400136 bit 11 | Command | ||
| BO | 161 | KNOCK SAMPLE MISSING | Modbus 400136 bit 10 | Command | ||
| BO | 162 | DISABLE CHECKSYNC BD | Modbus 400136 bit 9 | Command | ||
| BO | 163 | FAULT RELAY ACTIVE | Modbus 400136 bit 8 | Command | ||
| BO | 164 | ANNUNCIATOR LIGHT 20 | Modbus 400136 bit 7 | Command | ||
| BO | 165 | PM-SC COMMS FAILED | Modbus 400136 bit 6 | Command | ||
| BO | 166 | CHECK IF ILC RUNNING | Modbus 400136 bit 5 | Command | ||
| BO | 167 | USR CONFIGURABLE 092 | Modbus 400136 bit 4; not polled by default | Command | ||
| BO | 168 | USR CONFIGURABLE 093 | Modbus 400136 bit 3; not polled by default | Command | ||
| BO | 169 | USR CONFIGURABLE 094 | Modbus 400136 bit 2; not polled by default | Command | ||
| BO | 170 | USR CONFIGURABLE 095 | Modbus 400136 bit 1; not polled by default | Command | ||
| BO | 171 | USR CONFIGURABLE 096 | Modbus 400136 bit 0; not polled by default | Command | ||
| BO | 172 | USR CONFIGURABLE 097 | Modbus 400137 bit 15; not polled by default | Command | ||
| BO | 173 | USR CONFIGURABLE 098 | Modbus 400137 bit 14; not polled by default | Command | ||
| BO | 174 | USR CONFIGURABLE 099 | Modbus 400137 bit 13; not polled by default | Command | ||
| BO | 175 | USR CONFIGURABLE 100 | Modbus 400137 bit 12; not polled by default | Command | ||
| BO | 176 | USR CONFIGURABLE 101 | Modbus 400137 bit 11; not polled by default | Command | ||
| BO | 177 | USR CONFIGURABLE 102 | Modbus 400137 bit 10; not polled by default | Command | ||
| BO | 178 | USR CONFIGURABLE 103 | Modbus 400137 bit 9; not polled by default | Command | ||
| BO | 179 | USR CONFIGURABLE 104 | Modbus 400137 bit 8; not polled by default | Command | ||
| BO | 180 | USR CONFIGURABLE 105 | Modbus 400137 bit 7; not polled by default | Command | ||
| BO | 181 | USR CONFIGURABLE 106 | Modbus 400137 bit 6; not polled by default | Command | ||
| BO | 182 | USR CONFIGURABLE 107 | Modbus 400137 bit 5; not polled by default | Command | ||
| BO | 183 | USR CONFIGURABLE 108 | Modbus 400137 bit 4; not polled by default | Command | ||
| BO | 184 | USR CONFIGURABLE 109 | Modbus 400137 bit 3; not polled by default | Command | ||
| BO | 185 | USR CONFIGURABLE 110 | Modbus 400137 bit 2; not polled by default | Command | ||
| BO | 186 | USR CONFIGURABLE 111 | Modbus 400137 bit 1; not polled by default | Command | ||
| BO | 187 | USR CONFIGURABLE 112 | Modbus 400137 bit 0; not polled by default | Command | ||
| BO | 188 | USR CONFIGURABLE 113 | Modbus 400138 bit 15; not polled by default | Command | ||
| BO | 189 | USR CONFIGURABLE 114 | Modbus 400138 bit 14; not polled by default | Command | ||
| BO | 190 | USR CONFIGURABLE 115 | Modbus 400138 bit 13; not polled by default | Command | ||
| BO | 191 | USR CONFIGURABLE 116 | Modbus 400138 bit 12; not polled by default | Command | ||
| BO | 192 | USR CONFIGURABLE 117 | Modbus 400138 bit 11; not polled by default | Command | ||
| BO | 193 | USR CONFIGURABLE 118 | Modbus 400138 bit 10; not polled by default | Command | ||
| BO | 194 | RPM MISSING IN CRANK | Modbus 400138 bit 9 | Command | ||
| BO | 195 | ON-LINE IN BKUP MODE | Modbus 400138 bit 8 | Command | ||
| AI | 196 | ENGINE HOURS NOW HI/LO | Modbus 400304; not polled by default | Read | ||
| AI | 197 | ENGINE HOURS NOW LO/HI | Modbus 400304; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Generac G-Panel point IDs by name
AI1OIL TEMPERATUREAI2COOLANT TEMPERATUREAI3OIL PRESSUREAI4GOVERNOR COMMANDAI5USER CONFIGURABLE 05AI6USER CONFIGURABLE 06AI7USER CONFIGURABLE 07AI8USER CONFIGURABLE 08AI9USER CONFIGURABLE 09AI10COOLANT LEVELAI11FUEL LEVELAI12AI-1 AUX INPUT 1AI13AI-2 AUX INPUT 2AI14USER CONFIGURABLE 14AI15BAT CHARGE CURRENTAI16USER CONFIGURABLE 16AI17USER CONFIGURABLE 17AI18BATTERY VOLTAGEAI19BUS CURRENT PHASE AAI20BUS CURRENT PHASE BAI21BUS CURRENT PHASE CAI22BUS AVERAGE CURRENTAI23GEN CURRENT PHASE AAI24GEN CURRENT PHASE BAI25GEN CURRENT PHASE CAI26GEN AVERAGE CURRENTAI27BUS VOLT PHASE A-BAI28BUS VOLT PHASE B-CAI29BUS VOLT PHASE C-AAI30BUS AVERAGE VOLTAGEAI31GEN VOLT PHASE A-BAI32GEN VOLT PHASE B-CAI33GEN VOLT PHASE C-AAI34GEN AVERAGE VOLTAGEAI35GEN TOTAL KWAI36BUS TOTAL KWAI37GEN TOTAL PFAI38BUS TOTAL PFAI39GEN FREQUENCYAI40BUS FREQUENCYAI41ENGINE RPMAI42RPM 2AI43RPM 3BI44AUTO SWITCHBI45MANUAL SWITCHBI46ALARM ACKNOWLEDGEBI47EMERGENCY STOPBI48REMOTE STARTBI49BATTERY CHARGER FAILBI50RUPTURED BASINBI51USER CONFIGURABLE 08BI52USER CONFIGURABLE 09BI53USER CONFIGURABLE 10BI54STOP DEADBUS CONNECTBI55EXERCISERBI56GEN SWITCH STATUSBI57UTIL SWITCH STATUSBI58SEL TRIP STATUSBI59MCB STATUSBI60PHASE ROTATION VALIDBI61USER CONFIGURABLE 18BI62USER CONFIGURABLE 19BI63USER CONFIGURABLE 20BI64USER CONFIGURABLE 21BI65USER CONFIGURABLE 22BI66USER CONFIGURABLE 23BI67USER CONFIGURABLE 24BI68MODEM SELECTEDBI69GENERATOR OVERSPEEDBI70DI-1BI71DI-2BI72DI-3 / LINE POWERBI73DI-4 / GENERATOR PWRBI74USER CONFIGURABLE 31BI75USER CONFIGURABLE 32BO76COMMON ALARMBO77COMMON WARNINGBO78LO OIL PRESSURE WARNBO79LO OIL PRESSURE ALRMBO80HI COOLANT TEMP WARNBO81HI COOLANT TEMP ALRMBO82LO COOLANT TEMP WARNBO83HI OIL TEMP WARNBO84HI OIL TEMP ALARMBO85LO BATTERY VOLT WARNBO86HI BATTERY VOLT WARNBO87OVERSPEED ALARMBO88UNDERSPEED ALARMBO89OVER VOLTAGE ALARMBO90UNDER VOLTAGE ALARMBO91OVER FREQUENCY ALARMBO92UNDER FREQUENCY ALRMBO93HI FUEL ALARMBO94LO FUEL WARNINGBO95LO FUEL ALARMBO96FAIL TO START ALARMBO97COOLANT LEVEL ALARMBO98RPM SENSOR FAIL ALRMBO99START INHIBIT ALARMBO100ESTOP ALARMBO101OIL PRESS SENSOR FLTBO102OIL TEMP SENSOR FLTBO103COOLANT TEMP SENSORBO104KNOCK UNIT FAULTBO105KNOCK NOT CALIBRATEDBO106XFER SWITCH ERROR ALBO107REVERSE POWER ALARMBO108MCB IS OPENBO109OIL FILT BLOCKD ALRMBO110AIR FILT BLOCKD ALRMBO111OXYGEN SENSOR FAULTBO112ALTERNATOR PROBLEMBO113GAS PRESSURE WARNBO114EXHAUST TEMP WARNINGBO115EXHAUST TEMP ALARMBO116FLAME DETECTIONBO117CARBON MONOXIDE ALRMBO118VACUUM SENSOR FAULTBO119CAM MAPPED O PBO120CRANK MAPPED O PBO121GAS FLOW SENSOR FLTBO122GENERATOR IN AUTOBO123GENERATOR IN MANUALBO124GENERATOR IN OFFBO125ENGINE STOPPEDBO126ENGINE STOPPED-ALARMBO127STOPPED READY TO RUNBO128RUNNINGBO129READY TO ACCEPT LOADBO130ALARMS ENABLEDBO131IN WARM UPBO132IN COOL DOWNBO133CRANKINGBO134VOLTAGE DROPOUTBO135VOLTAGE PICKUPBO136IN LINE INTRRPT DLYBO137IN RETURN toUTIL DLYBO138IN TDNBO139LOAD SHEDDINGBO140OUT OF SERVICEBO141NEED SERVICEBO142BATTERY CHARGER FAILBO143LINE POWERBO144GENERATOR POWERBO145GAS REDUCED - KNOCKBO146ALL ENGINES ON LINEBO147SHUTDOWN GENSETBO148CHECK VOLT PHASE ROTBO149CHECK CURR PHASE ROTBO150ILC ALARM/WARNING 1BO151ILC ALARM/WARNING 2BO152GAS SHUTOFF - KNOCKBO153HI INLET MAN TEMP ALBO154HI INLET MAN TEMP WNBO155LO TURBO PRESS - GASBO156LO TURBO PRESS - DSLBO157LO GAS PRESS SHUTOFFBO158LO GAS PRESS DISABLEBO159HI GAS PRESS DISABLEBO160CAC BYPASS VALVE FLTBO161KNOCK SAMPLE MISSINGBO162DISABLE CHECKSYNC BDBO163FAULT RELAY ACTIVEBO164ANNUNCIATOR LIGHT 20BO165PM-SC COMMS FAILEDBO166CHECK IF ILC RUNNINGBO167USR CONFIGURABLE 092BO168USR CONFIGURABLE 093BO169USR CONFIGURABLE 094BO170USR CONFIGURABLE 095BO171USR CONFIGURABLE 096BO172USR CONFIGURABLE 097BO173USR CONFIGURABLE 098BO174USR CONFIGURABLE 099BO175USR CONFIGURABLE 100BO176USR CONFIGURABLE 101BO177USR CONFIGURABLE 102BO178USR CONFIGURABLE 103BO179USR CONFIGURABLE 104BO180USR CONFIGURABLE 105BO181USR CONFIGURABLE 106BO182USR CONFIGURABLE 107BO183USR CONFIGURABLE 108BO184USR CONFIGURABLE 109BO185USR CONFIGURABLE 110BO186USR CONFIGURABLE 111BO187USR CONFIGURABLE 112BO188USR CONFIGURABLE 113BO189USR CONFIGURABLE 114BO190USR CONFIGURABLE 115BO191USR CONFIGURABLE 116BO192USR CONFIGURABLE 117BO193USR CONFIGURABLE 118BO194RPM MISSING IN CRANKBO195ON-LINE IN BKUP MODEAI196ENGINE HOURS NOW HI/LOAI197ENGINE HOURS NOW LO/HI
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Generac_G_Panel__a_LX.csv; the profile maps the registers in the Generac G-Panel Modbus register list (https://www.ccontrols.com/support/dp/SupportFileGeneracGPanel.zip).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 151 of the 197 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (USER CONFIGURABLE 08; USER CONFIGURABLE 09; BATTERY CHARGER FAIL); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Generac G-Panel generator control via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Generac G-Panel generator control via BASgatewayLX
How many BACnet points does the Contemporary Controls Generac G-Panel generator control via BASgatewayLX have?
This list has 197 BACnet objects: 45 analog inputs, 32 binary inputs, 120 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Generac G-Panel generator control via BASgatewayLX BACnet points are writable?
120 of the 197 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Generac G-Panel generator control via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Generac_G_Panel__a (Generac_G_Panel__a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/GeneracGPanel.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Generac G-Panel generator control via BASgatewayLX?
Start with BO 128 RUNNING (Generator running); BO 122 GENERATOR IN AUTO (Generator in auto); BO 129 READY TO ACCEPT LOAD (Ready to accept load); AI 35 GEN TOTAL KW (Generator total kW); AI 34 GEN AVERAGE VOLTAGE (Generator average voltage); AI 39 GEN FREQUENCY (Generator frequency); AI 18 BATTERY VOLTAGE (Battery voltage); BO 76 COMMON ALARM (Common alarm); BO 77 COMMON WARNING (Common warning).
How do I check these points on the real Generac G-Panel generator control via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Generac_G_Panel__a · Generac_G_Panel__a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.