- Home
- BACnet points lists
- Contemporary Controls
- Schneider Electric PowerLogic CM4000 via BASgatewayLX
Power and energy meter · BACnet points list
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the PowerLogic CM4000: 711 objects (664 AI, 47 BI), 68 polled by default (the 1-second current, voltage, unbalance, power, PF and frequency values). 100 ms readings, min/max, demand, energy registers, THD and status bits are unpolled.
This page lists 711 BACnet objects for the Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Schneider Electric PowerLogic CM4000 via BASgatewayLX
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 711 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Map real power total (1 s), voltage L-L average (1 s) and current 3-phase average (1 s) first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 69 | 1sec Real Power Total | Real power total (1 s) | Read |
| AI 52 | 1sec Voltage L-L Average | Voltage L-L average (1 s) | Read |
| AI 43 | 1sec Current 3-Phase Average | Current 3-phase average (1 s) | Read |
| AI 81 | 1sec True Power Factor Total | True power factor total (1 s) | Read |
| AI 94 | 1sec Frequency | Frequency (1 s) | Read |
| AI 512 | Energy Real Total (signed/absolute) Reg 1 | Real energy total, register 1 | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | 100ms Current Phase A | Modbus 401000; not polled by default | A | Read | |
| AI | 2 | 100ms Current Phase B | Modbus 401001; not polled by default | A | Read | |
| AI | 3 | 100ms Current Phase C | Modbus 401002; not polled by default | A | Read | |
| AI | 4 | 100ms Current Neutral | Modbus 401003; not polled by default | A | Read | |
| AI | 5 | 100ms Current Ground | Modbus 401004; not polled by default | A | Read | |
| AI | 6 | 100ms Current 3-Phase Average | Modbus 401005; not polled by default | A | Read | |
| AI | 7 | 100ms Current Apparent RMS | Modbus 401006; not polled by default | A | Read | |
| AI | 8 | 100ms Voltage A-B | Modbus 401020; not polled by default | V | Read | |
| AI | 9 | 100ms Voltage B-C | Modbus 401021; not polled by default | V | Read | |
| AI | 10 | 100ms Voltage C-A | Modbus 401022; not polled by default | V | Read | |
| AI | 11 | 100ms Voltage L-L Average | Modbus 401023; not polled by default | V | Read | |
| AI | 12 | 100ms Voltage A-N | Modbus 401024; not polled by default | V | Read | |
| AI | 13 | 100ms Voltage B-N | Modbus 401025; not polled by default | V | Read | |
| AI | 14 | 100ms Voltage C-N | Modbus 401026; not polled by default | V | Read | |
| AI | 15 | 100ms Voltage N-G | Modbus 401027; not polled by default | V | Read | |
| AI | 16 | 100ms Voltage L-N Average | Modbus 401028; not polled by default | V | Read | |
| AI | 17 | 100ms Real Power Phase A | Modbus 401040; not polled by default | kW | Read | |
| AI | 18 | 100ms Real Power Phase B | Modbus 401041; not polled by default | kW | Read | |
| AI | 19 | 100ms Real Power Phase C | Modbus 401042; not polled by default | kW | Read | |
| AI | 20 | 100ms Real Power Total | Modbus 401043; not polled by default | kW | Read | |
| AI | 21 | 100ms Reactive Power Phase A | Modbus 401044; not polled by default | kVAR | Read | |
| AI | 22 | 100ms Reactive Power Phase B | Modbus 401045; not polled by default | kVAR | Read | |
| AI | 23 | 100ms Reactive Power Phase C | Modbus 401046; not polled by default | kVAR | Read | |
| AI | 24 | 100ms Reactive Power Total | Modbus 401047; not polled by default | kVAR | Read | |
| AI | 25 | 100ms Apparent Power Phase A | Modbus 401048; not polled by default | kVA | Read | |
| AI | 26 | 100ms Apparent Power Phase B | Modbus 401049; not polled by default | kVA | Read | |
| AI | 27 | 100ms Apparent Power Phase C | Modbus 401050; not polled by default | kVA | Read | |
| AI | 28 | 100ms Apparent Power Total | Modbus 401051; not polled by default | kVA | Read | |
| AI | 29 | 100ms True Power Factor Phase A | Modbus 401060; not polled by default | PF | Read | |
| AI | 30 | 100ms True Power Factor Phase B | Modbus 401061; not polled by default | PF | Read | |
| AI | 31 | 100ms True Power Factor Phase C | Modbus 401062; not polled by default | PF | Read | |
| AI | 32 | 100ms True Power Factor Total | Modbus 401063; not polled by default | PF | Read | |
| AI | 33 | 100ms Alternate True Power Factor Phase A | Modbus 401064; not polled by default | PF | Read | |
| AI | 34 | 100ms Alternate True Power Factor Phase B | Modbus 401065; not polled by default | PF | Read | |
| AI | 35 | 100ms Alternate True Power Factor Phase C | Modbus 401066; not polled by default | PF | Read | |
| AI | 36 | 100ms Alternate True Power Factor Total | Modbus 401067; not polled by default | PF | Read | |
| AI | 37 | 100ms Frequency | Modbus 401080; not polled by default | Hz | Read | |
| AI | 38 | 1sec Current Phase A | Modbus 401100 | A | Read | |
| AI | 39 | 1sec Current Phase B | Modbus 401101 | A | Read | |
| AI | 40 | 1sec Current Phase C | Modbus 401102 | A | Read | |
| AI | 41 | 1sec Current Neutral | Modbus 401103 | A | Read | |
| AI | 42 | 1sec Current Ground | Modbus 401104 | A | Read | |
| AImin | 43 | 1sec Current 3-Phase Average | Modbus 401105 | A | Read | |
| AI | 44 | 1sec Current Apparent RMS | Modbus 401106 | A | Read | |
| AI | 45 | 1sec Current Unbalance Phase A | Modbus 401107 | % | Read | |
| AI | 46 | 1sec Current Unbalance Phase B | Modbus 401108 | % | Read | |
| AI | 47 | 1sec Current Unbalance Phase C | Modbus 401109 | % | Read | |
| AI | 48 | 1sec Current Unbalance Max | Modbus 401110 | % | Read | |
| AI | 49 | 1sec Voltage A-B | Modbus 401120 | V | Read | |
| AI | 50 | 1sec Voltage B-C | Modbus 401121 | V | Read | |
| AI | 51 | 1sec Voltage C-A | Modbus 401122 | V | Read | |
| AImin | 52 | 1sec Voltage L-L Average | Modbus 401123 | V | Read | |
| AI | 53 | 1sec Voltage A-N | Modbus 401124 | V | Read | |
| AI | 54 | 1sec Voltage B-N | Modbus 401125 | V | Read | |
| AI | 55 | 1sec Voltage C-N | Modbus 401126 | V | Read | |
| AI | 56 | 1sec Voltage N-G | Modbus 401127 | V | Read | |
| AI | 57 | 1sec Voltage L-N Average | Modbus 401128 | V | Read | |
| AI | 58 | 1sec Voltage Unbalance A-B | Modbus 401129 | % | Read | |
| AI | 59 | 1sec Voltage Unbalance B-C | Modbus 401130 | % | Read | |
| AI | 60 | 1sec Voltage Unbalance C-A | Modbus 401131 | % | Read | |
| AI | 61 | 1sec Voltage Unbalance Max L-L | Modbus 401132 | % | Read | |
| AI | 62 | 1sec Voltage Unbalance A-N | Modbus 401133 | % | Read | |
| AI | 63 | 1sec Voltage Unbalance B-N | Modbus 401134 | % | Read | |
| AI | 64 | 1sec Voltage Unbalance C-N | Modbus 401135 | % | Read | |
| AI | 65 | 1sec Voltage Unbalance Max L-N | Modbus 401136 | % | Read | |
| AI | 66 | 1sec Real Power Phase A | Modbus 401140 | kW | Read | |
| AI | 67 | 1sec Real Power Phase B | Modbus 401141 | kW | Read | |
| AI | 68 | 1sec Real Power Phase C | Modbus 401142 | kW | Read | |
| AImin | 69 | 1sec Real Power Total | Modbus 401143 | kW | Read | |
| AI | 70 | 1sec Reactive Power Phase A | Modbus 401144 | kVAR | Read | |
| AI | 71 | 1sec Reactive Power Phase B | Modbus 401145 | kVAR | Read | |
| AI | 72 | 1sec Reactive Power Phase C | Modbus 401146 | kVAR | Read | |
| AI | 73 | 1sec Reactive Power Total | Modbus 401147 | kVAR | Read | |
| AI | 74 | 1sec Apparent Power Phase A | Modbus 401148 | kVA | Read | |
| AI | 75 | 1sec Apparent Power Phase B | Modbus 401149 | kVA | Read | |
| AI | 76 | 1sec Apparent Power Phase C | Modbus 401150 | kVA | Read | |
| AI | 77 | 1sec Apparent Power Total | Modbus 401151 | kVA | Read | |
| AI | 78 | 1sec True Power Factor Phase A | Modbus 401160 | PF | Read | |
| AI | 79 | 1sec True Power Factor Phase B | Modbus 401161 | PF | Read | |
| AI | 80 | 1sec True Power Factor Phase C | Modbus 401162 | PF | Read | |
| AImin | 81 | 1sec True Power Factor Total | Modbus 401163 | PF | Read | |
| AI | 82 | 1sec Alternate True Power Factor Phase A | Modbus 401164 | PF | Read | |
| AI | 83 | 1sec Alternate True Power Factor Phase B | Modbus 401165 | PF | Read | |
| AI | 84 | 1sec Alternate True Power Factor Phase C | Modbus 401166 | PF | Read | |
| AI | 85 | 1sec Alternate True Power Factor Total | Modbus 401167 | PF | Read | |
| AI | 86 | 1sec Displacement Power Factor Phase A | Modbus 401168 | PF | Read | |
| AI | 87 | 1sec Displacement Power Factor Phase B | Modbus 401169 | PF | Read | |
| AI | 88 | 1sec Displacement Power Factor Phase C | Modbus 401170 | PF | Read | |
| AI | 89 | 1sec Displacement Power Factor Total | Modbus 401171 | PF | Read | |
| AI | 90 | 1sec Alternate Displacement Power Factor Phase A | Modbus 401172 | PF | Read | |
| AI | 91 | 1sec Alternate Displacement Power Factor Phase B | Modbus 401173 | PF | Read | |
| AI | 92 | 1sec Alternate Displacement Power Factor Phase C | Modbus 401174 | PF | Read | |
| AI | 93 | 1sec Alternate Displacement Power Factor Total | Modbus 401175 | PF | Read | |
| AImin | 94 | 1sec Frequency | Modbus 401180 | Hz | Read | |
| AI | 95 | 1sec Temperature | Modbus 401181 | Read | ||
| AI | 96 | 1sec Auxiliary Analog Input Value User-Selected Input 1 | Modbus 401190 | Read | ||
| AI | 97 | 1sec Auxiliary Analog Input Value User-Selected Input 2 | Modbus 401191 | Read | ||
| AI | 98 | 1sec Auxiliary Analog Input Value User-Selected Input 3 | Modbus 401192 | Read | ||
| AI | 99 | 1sec Auxiliary Analog Input Value User-Selected Input 4 | Modbus 401193 | Read | ||
| AI | 100 | 1sec Auxiliary Analog Input Value User-Selected Input 5 | Modbus 401194 | Read | ||
| AI | 101 | 1sec Auxiliary Analog Input Value User-Selected Input 6 | Modbus 401195 | Read | ||
| AI | 102 | 1sec Auxiliary Analog Input Value User-Selected Input 7 | Modbus 401196 | Read | ||
| AI | 103 | 1sec Auxiliary Analog Input Value User-Selected Input 8 | Modbus 401197 | Read | ||
| AI | 104 | 1sec Auxiliary Analog Input Value User-Selected Input 9 | Modbus 401198 | Read | ||
| AI | 105 | 1sec Auxiliary Analog Input Value User-Selected Input 10 | Modbus 401199 | Read | ||
| AI | 106 | THD/thd Current Phase A | Modbus 401200; not polled by default | % | Read | |
| AI | 107 | THD/thd Current Phase B | Modbus 401201; not polled by default | % | Read | |
| AI | 108 | THD/thd Current Phase C | Modbus 401202; not polled by default | % | Read | |
| AI | 109 | THD/thd Current Phase N | Modbus 401203; not polled by default | % | Read | |
| AI | 110 | THD/thd Current Ground | Modbus 401204; not polled by default | % | Read | |
| AI | 111 | THD/thd Voltage Phase A-N | Modbus 401207; not polled by default | % | Read | |
| AI | 112 | THD/thd Voltage Phase B-N | Modbus 401208; not polled by default | % | Read | |
| AI | 113 | THD/thd Voltage Phase C-N | Modbus 401209; not polled by default | % | Read | |
| AI | 114 | THD/thd Voltage Phase N-G | Modbus 401210; not polled by default | % | Read | |
| AI | 115 | THD/thd Voltage Phase A-B | Modbus 401211; not polled by default | % | Read | |
| AI | 116 | THD/thd Voltage Phase B-C | Modbus 401212; not polled by default | % | Read | |
| AI | 117 | THD/thd Voltage Phase C-A | Modbus 401213; not polled by default | % | Read | |
| AI | 118 | THD/thd Voltage 3-Phase Average-N | Modbus 401215; not polled by default | % | Read | |
| AI | 119 | THD/thd Voltage 3-Phase Average-L | Modbus 401216; not polled by default | % | Read | |
| AI | 120 | K-Factor Current Phase A | Modbus 401218; not polled by default | Read | ||
| AI | 121 | K-Factor Current Phase B | Modbus 401219; not polled by default | Read | ||
| AI | 122 | K-Factor Current Phase C | Modbus 401220; not polled by default | Read | ||
| AI | 123 | Crest Factor Current Phase A | Modbus 401221; not polled by default | Read | ||
| AI | 124 | Crest Factor Current Phase B | Modbus 401222; not polled by default | Read | ||
| AI | 125 | Crest Factor Current Phase C | Modbus 401223; not polled by default | Read | ||
| AI | 126 | Crest Factor Current Neutral | Modbus 401224; not polled by default | Read | ||
| AI | 127 | Crest Factor Voltage A-N/A-B | Modbus 401225; not polled by default | Read | ||
| AI | 128 | Crest Factor Voltage B-N/B-C | Modbus 401226; not polled by default | Read | ||
| AI | 129 | Crest Factor Voltage C-N/C-A | Modbus 401227; not polled by default | Read | ||
| AI | 130 | Current Fundamental RMS Magnitude Phase A | Modbus 401230; not polled by default | A | Read | |
| AI | 131 | Current Fundamental Coincident Angle Phase A | Modbus 401231; not polled by default | Read | ||
| AI | 132 | Current Fundamental RMS Magnitude Phase B | Modbus 401232; not polled by default | A | Read | |
| AI | 133 | Current Fundamental Coincident Angle Phase B | Modbus 401233; not polled by default | Read | ||
| AI | 134 | Current Fundamental RMS Magnitude Phase C | Modbus 401234; not polled by default | A | Read | |
| AI | 135 | Current Fundamental Coincident Angle Phase C | Modbus 401235; not polled by default | Read | ||
| AI | 136 | Current Fundamental RMS Magnitude Neutral | Modbus 401236; not polled by default | A | Read | |
| AI | 137 | Current Fundamental Coincident Angle Neutral | Modbus 401237; not polled by default | Read | ||
| AI | 138 | Current Fundamental RMS Magnitude Ground | Modbus 401238; not polled by default | A | Read | |
| AI | 139 | Current Fundamental Coincident Angle Ground | Modbus 401239; not polled by default | Read | ||
| AI | 140 | Voltage Fundamental RMS Magnitude A-N/A-B | Modbus 401244; not polled by default | V | Read | |
| AI | 141 | Voltage Fundamental Coincident Angle A-N/A-B | Modbus 401245; not polled by default | Read | ||
| AI | 142 | Voltage Fundamental RMS Magnitude B-N/B-C | Modbus 401246; not polled by default | V | Read | |
| AI | 143 | Voltage Fundamental Coincident Angle B-N/B-C | Modbus 401247; not polled by default | Read | ||
| AI | 144 | Voltage Fundamental RMS Magnitude C-N/C-A | Modbus 401248; not polled by default | V | Read | |
| AI | 145 | Voltage Fundamental Coincident Angle C-N/C-A | Modbus 401249; not polled by default | Read | ||
| AI | 146 | Voltage Fundamental RMS Magnitude N-G | Modbus 401250; not polled by default | V | Read | |
| AI | 147 | Voltage Fundamental Coincident Angle N-G | Modbus 401251; not polled by default | Read | ||
| AI | 148 | Fundamental Real Power Phase A | Modbus 401255; not polled by default | kW | Read | |
| AI | 149 | Fundamental Real Power Phase B | Modbus 401256; not polled by default | kW | Read | |
| AI | 150 | Fundamental Real Power Phase C | Modbus 401257; not polled by default | kW | Read | |
| AI | 151 | Fundamental Real Power Total | Modbus 401258; not polled by default | kW | Read | |
| AI | 152 | Fundamental Reactive Power Phase A | Modbus 401259; not polled by default | kVAR | Read | |
| AI | 153 | Fundamental Reactive Power Phase B | Modbus 401260; not polled by default | kVAR | Read | |
| AI | 154 | Fundamental Reactive Power Phase C | Modbus 401261; not polled by default | kVAR | Read | |
| AI | 155 | Fundamental Reactive Power Total | Modbus 401262; not polled by default | kVAR | Read | |
| AI | 156 | Distortion Power Phase A | Modbus 401264; not polled by default | kW | Read | |
| AI | 157 | Distortion Power Phase B | Modbus 401265; not polled by default | kW | Read | |
| AI | 158 | Distortion Power Phase C | Modbus 401266; not polled by default | kW | Read | |
| AI | 159 | Distortion Power Total | Modbus 401267; not polled by default | kW | Read | |
| AI | 160 | Distortion Power Factor Phase A | Modbus 401268; not polled by default | % | Read | |
| AI | 161 | Distortion Power Factor Phase B | Modbus 401269; not polled by default | % | Read | |
| AI | 162 | Distortion Power Factor Phase C | Modbus 401270; not polled by default | % | Read | |
| AI | 163 | Distortion Power Factor Total | Modbus 401271; not polled by default | % | Read | |
| AI | 164 | Harmonic Current Phase A | Modbus 401274; not polled by default | A | Read | |
| AI | 165 | Harmonic Current Phase B | Modbus 401275; not polled by default | A | Read | |
| AI | 166 | Harmonic Current Phase C | Modbus 401276; not polled by default | A | Read | |
| AI | 167 | Harmonic Current Neutral | Modbus 401277; not polled by default | V | Read | |
| AI | 168 | Harmonic Voltage A-N/A-B | Modbus 401278; not polled by default | V | Read | |
| AI | 169 | Harmonic Voltage B-N/B-C | Modbus 401279; not polled by default | V | Read | |
| AI | 170 | Harmonic Voltage C-N/C-A | Modbus 401280; not polled by default | V | Read | |
| AI | 171 | Total Demand Distortion | Modbus 401281; not polled by default | % | Read | |
| BI | 172 | Harmonic Power Flow kW Phase A | Modbus 401282 bit 0; not polled by default | Read | ||
| BI | 173 | Harmonic Power Flow kW Phase B | Modbus 401282 bit 1; not polled by default | Read | ||
| BI | 174 | Harmonic Power Flow kW Phase C | Modbus 401282 bit 2; not polled by default | Read | ||
| BI | 175 | Harmonic Power Flow kW Phase Total | Modbus 401282 bit 3; not polled by default | Read | ||
| BI | 176 | Harmonic Power Flow kVAr Phase A | Modbus 401282 bit 8; not polled by default | Read | ||
| BI | 177 | Harmonic Power Flow kVAr Phase B | Modbus 401282 bit 9; not polled by default | Read | ||
| BI | 178 | Harmonic Power Flow kVAr Phase C | Modbus 401282 bit 10; not polled by default | Read | ||
| BI | 179 | Harmonic Power Flow kVAr Phase Total | Modbus 401282 bit 11; not polled by default | Read | ||
| AI | 180 | Current Positive Sequence Magnitude | Modbus 401284; not polled by default | A | Read | |
| AI | 181 | Current Positive Sequence Angle | Modbus 401285; not polled by default | Read | ||
| AI | 182 | Current Negative Sequence Magnitude | Modbus 401286; not polled by default | A | Read | |
| AI | 183 | Current Negative Sequence Angle | Modbus 401287; not polled by default | Read | ||
| AI | 184 | Current Zero Sequence Magnitude | Modbus 401288; not polled by default | A | Read | |
| AI | 185 | Current Zero Sequence Angle | Modbus 401289; not polled by default | Read | ||
| AI | 186 | Voltage Positive Sequence Magnitude | Modbus 401290; not polled by default | V | Read | |
| AI | 187 | Voltage Positive Sequence Angle | Modbus 401291; not polled by default | Read | ||
| AI | 188 | Voltage Negative Sequence Magnitude | Modbus 401292; not polled by default | V | Read | |
| AI | 189 | Voltage Negative Sequence Angle | Modbus 401293; not polled by default | Read | ||
| AI | 190 | Voltage Zero Sequence Magnitude | Modbus 401294; not polled by default | V | Read | |
| AI | 191 | Voltage Zero Sequence Angle | Modbus 401295; not polled by default | Read | ||
| AI | 192 | Current Sequence Unbalance | Modbus 401296; not polled by default | % | Read | |
| AI | 193 | Voltage Sequence Unbalance | Modbus 401297; not polled by default | % | Read | |
| AI | 194 | Current Sequence Unbalance Factor | Modbus 401298; not polled by default | % | Read | |
| AI | 195 | Voltage Sequence Unbalance Factor | Modbus 401299; not polled by default | % | Read | |
| AI | 196 | Minimum Current Phase A | Modbus 401300; not polled by default | A | Read | |
| AI | 197 | Minimum Current Phase B | Modbus 401301; not polled by default | A | Read | |
| AI | 198 | Minimum Current Phase C | Modbus 401302; not polled by default | A | Read | |
| AI | 199 | Minimum Current Neutral | Modbus 401303; not polled by default | A | Read | |
| AI | 200 | Minimum Current Ground | Modbus 401304; not polled by default | A | Read | |
| AI | 201 | Minimum Current 3-Phase Average | Modbus 401305; not polled by default | A | Read | |
| AI | 202 | Minimum Current Apparent RMS | Modbus 401306; not polled by default | A | Read | |
| AI | 203 | Minimum Current Unbalance Phase A | Modbus 401307; not polled by default | % | Read | |
| AI | 204 | Minimum Current Unbalance Phase B | Modbus 401308; not polled by default | % | Read | |
| AI | 205 | Minimum Current Unbalance Phase C | Modbus 401309; not polled by default | % | Read | |
| AI | 206 | Minimum Current Unbalance Max | Modbus 401310; not polled by default | % | Read | |
| AI | 207 | Minimum Voltage A-B | Modbus 401320; not polled by default | V | Read | |
| AI | 208 | Minimum Voltage B-C | Modbus 401321; not polled by default | V | Read | |
| AI | 209 | Minimum Voltage C-A | Modbus 401322; not polled by default | V | Read | |
| AI | 210 | Minimum Voltage L-L Average | Modbus 401323; not polled by default | V | Read | |
| AI | 211 | Minimum Voltage A-N | Modbus 401324; not polled by default | V | Read | |
| AI | 212 | Minimum Voltage B-N | Modbus 401325; not polled by default | V | Read | |
| AI | 213 | Minimum Voltage C-N | Modbus 401326; not polled by default | V | Read | |
| AI | 214 | Minimum Voltage N-G | Modbus 401327; not polled by default | V | Read | |
| AI | 215 | Minimum Voltage L-N Average | Modbus 401328; not polled by default | V | Read | |
| AI | 216 | Minimum Voltage Unbalance A-B | Modbus 401329; not polled by default | % | Read | |
| AI | 217 | Minimum Voltage Unbalance B-C | Modbus 401330; not polled by default | % | Read | |
| AI | 218 | Minimum Voltage Unbalance C-A | Modbus 401331; not polled by default | % | Read | |
| AI | 219 | Minimum Voltage Unbalance Max L-L | Modbus 401332; not polled by default | % | Read | |
| AI | 220 | Minimum Voltage Unbalance A-N | Modbus 401333; not polled by default | % | Read | |
| AI | 221 | Minimum Voltage Unbalance B-N | Modbus 401334; not polled by default | % | Read | |
| AI | 222 | Minimum Voltage Unbalance C-N | Modbus 401335; not polled by default | % | Read | |
| AI | 223 | Minimum Voltage Unbalance Max L-N | Modbus 401336; not polled by default | % | Read | |
| AI | 224 | Minimum Real Power Phase A | Modbus 401340; not polled by default | kW | Read | |
| AI | 225 | Minimum Real Power Phase B | Modbus 401341; not polled by default | kW | Read | |
| AI | 226 | Minimum Real Power Phase C | Modbus 401342; not polled by default | kW | Read | |
| AI | 227 | Minimum Real Power Total | Modbus 401343; not polled by default | kW | Read | |
| AI | 228 | Minimum Reactive Power Phase A | Modbus 401344; not polled by default | kVAR | Read | |
| AI | 229 | Minimum Reactive Power Phase B | Modbus 401345; not polled by default | kVAR | Read | |
| AI | 230 | Minimum Reactive Power Phase C | Modbus 401346; not polled by default | kVAR | Read | |
| AI | 231 | Minimum Reactive Power Total | Modbus 401347; not polled by default | kVAR | Read | |
| AI | 232 | Minimum Apparent Power Phase A | Modbus 401348; not polled by default | kVA | Read | |
| AI | 233 | Minimum Apparent Power Phase B | Modbus 401349; not polled by default | kVA | Read | |
| AI | 234 | Minimum Apparent Power Phase C | Modbus 401350; not polled by default | kVA | Read | |
| AI | 235 | Minimum Apparent Power Total | Modbus 401351; not polled by default | kVA | Read | |
| AI | 236 | Minimum True Power Factor Phase A | Modbus 401360; not polled by default | PF | Read | |
| AI | 237 | Minimum True Power Factor Phase B | Modbus 401361; not polled by default | PF | Read | |
| AI | 238 | Minimum True Power Factor Phase C | Modbus 401362; not polled by default | PF | Read | |
| AI | 239 | Minimum True Power Factor Total | Modbus 401363; not polled by default | PF | Read | |
| AI | 240 | Minimum Alternate True Power Factor Phase A | Modbus 401364; not polled by default | PF | Read | |
| AI | 241 | Minimum Alternate True Power Factor Phase B | Modbus 401365; not polled by default | PF | Read | |
| AI | 242 | Minimum Alternate True Power Factor Phase C | Modbus 401366; not polled by default | Read | ||
| AI | 243 | Minimum Alternate True Power Factor Total | Modbus 401367; not polled by default | Read | ||
| AI | 244 | Minimum Displacement Power Factor Phase A | Modbus 401368; not polled by default | Read | ||
| AI | 245 | Minimum Displacement Power Factor Phase B | Modbus 401369; not polled by default | Read | ||
| AI | 246 | Minimum Displacement Power Factor Phase C | Modbus 401370; not polled by default | Read | ||
| AI | 247 | Minimum Displacement Power Factor Total | Modbus 401371; not polled by default | Read | ||
| AI | 248 | Minimum Alternate Displacement Power Factor Phase A | Modbus 401372; not polled by default | Read | ||
| AI | 249 | Minimum Alternate Displacement Power Factor Phase B | Modbus 401373; not polled by default | Read | ||
| AI | 250 | Minimum Alternate Displacement Power Factor Phase C | Modbus 401374; not polled by default | Read | ||
| AI | 251 | Minimum Alternate Displacement Power Factor Total | Modbus 401375; not polled by default | Read | ||
| AI | 252 | Minimum Frequency | Modbus 401380; not polled by default | Read | ||
| AI | 253 | Minimum Temperature | Modbus 401381; not polled by default | Read | ||
| AI | 254 | Minimum Auxiliary Analog Input Value User-Selected Input 1 | Modbus 401390; not polled by default | Hz | Read | |
| AI | 255 | Minimum Auxiliary Analog Input Value User-Selected Input 2 | Modbus 401391; not polled by default | Read | ||
| AI | 256 | Minimum Auxiliary Analog Input Value User-Selected Input 3 | Modbus 401392; not polled by default | Read | ||
| AI | 257 | Minimum Auxiliary Analog Input Value User-Selected Input 4 | Modbus 401393; not polled by default | Read | ||
| AI | 258 | Minimum Auxiliary Analog Input Value User-Selected Input 5 | Modbus 401394; not polled by default | Read | ||
| AI | 259 | Minimum Auxiliary Analog Input Value User-Selected Input 6 | Modbus 401395; not polled by default | Read | ||
| AI | 260 | Minimum Auxiliary Analog Input Value User-Selected Input 7 | Modbus 401396; not polled by default | Read | ||
| AI | 261 | Minimum Auxiliary Analog Input Value User-Selected Input 8 | Modbus 401397; not polled by default | Read | ||
| AI | 262 | Minimum Auxiliary Analog Input Value User-Selected Input 9 | Modbus 401398; not polled by default | Read | ||
| AI | 263 | Minimum Auxiliary Analog Input Value User-Selected Input 10 | Modbus 401399; not polled by default | Read | ||
| AI | 264 | Minimum THD/thd Current Phase A | Modbus 401400; not polled by default | % | Read | |
| AI | 265 | Minimum THD/thd Current Phase B | Modbus 401401; not polled by default | % | Read | |
| AI | 266 | Minimum THD/thd Current Phase C | Modbus 401402; not polled by default | % | Read | |
| AI | 267 | Minimum THD/thd Current Phase N | Modbus 401403; not polled by default | % | Read | |
| AI | 268 | Minimum THD/thd Current Ground | Modbus 401404; not polled by default | % | Read | |
| AI | 269 | Minimum THD/thd Voltage Phase A-N | Modbus 401407; not polled by default | % | Read | |
| AI | 270 | Minimum THD/thd Voltage Phase B-N | Modbus 401408; not polled by default | % | Read | |
| AI | 271 | Minimum THD/thd Voltage Phase C-N | Modbus 401409; not polled by default | % | Read | |
| AI | 272 | Minimum THD/thd Voltage Phase N-G | Modbus 401410; not polled by default | % | Read | |
| AI | 273 | Minimum THD/thd Voltage Phase A-B | Modbus 401411; not polled by default | % | Read | |
| AI | 274 | Minimum THD/thd Voltage Phase B-C | Modbus 401412; not polled by default | % | Read | |
| AI | 275 | Minimum THD/thd Voltage Phase C-A | Modbus 401413; not polled by default | % | Read | |
| AI | 276 | Minimum THD/thd Voltage 3-Phase Average L-N | Modbus 401415; not polled by default | % | Read | |
| AI | 277 | Minimum THD/thd Voltage 3-Phase Average L-L | Modbus 401416; not polled by default | % | Read | |
| AI | 278 | Minimum Current K-Factor Phase A | Modbus 401418; not polled by default | Read | ||
| AI | 279 | Minimum Current K-Factor Phase B | Modbus 401419; not polled by default | Read | ||
| AI | 280 | Minimum Current K-Factor Phase C | Modbus 401420; not polled by default | Read | ||
| AI | 281 | Minimum Crest Factor Current Phase A | Modbus 401421; not polled by default | Read | ||
| AI | 282 | Minimum Crest Factor Current Phase B | Modbus 401422; not polled by default | Read | ||
| AI | 283 | Minimum Crest Factor Current Phase C | Modbus 401423; not polled by default | Read | ||
| AI | 284 | Minimum Crest Factor Current Neutral | Modbus 401424; not polled by default | Read | ||
| AI | 285 | Minimum Crest Factor Voltage A-N/A-B | Modbus 401425; not polled by default | Read | ||
| AI | 286 | Minimum Crest Factor Voltage B-N/B-C | Modbus 401426; not polled by default | Read | ||
| AI | 287 | Minimum Crest Factor Voltage C-N/C-A | Modbus 401427; not polled by default | Read | ||
| AI | 288 | Minimum Current Fundamental RMS Magnitude Phase A | Modbus 401430; not polled by default | A | Read | |
| AI | 289 | Minimum Current Fundamental Coincident Angle Phase A | Modbus 401431; not polled by default | Read | ||
| AI | 290 | Minimum Current Fundamental RMS Magnitude Phase B | Modbus 401432; not polled by default | A | Read | |
| AI | 291 | Minimum Current Fundamental Coincident Angle Phase B | Modbus 401433; not polled by default | Read | ||
| AI | 292 | Minimum Current Fundamental RMS Magnitude Phase C | Modbus 401434; not polled by default | A | Read | |
| AI | 293 | Minimum Current Fundamental Coincident Angle Phase C | Modbus 401435; not polled by default | Read | ||
| AI | 294 | Minimum Current Fundamental RMS Magnitude Neutral | Modbus 401436; not polled by default | A | Read | |
| AI | 295 | Minimum Current Fundamental Coincident Angle Neutral | Modbus 401437; not polled by default | Read | ||
| AI | 296 | Minimum Current Fundamental RMS Magnitude Ground | Modbus 401438; not polled by default | A | Read | |
| AI | 297 | Minimum Current Fundamental Coincident Angle Ground | Modbus 401439; not polled by default | Read | ||
| AI | 298 | Minimum Voltage Fundamental RMS Magnitude A-N/A-B | Modbus 401444; not polled by default | V | Read | |
| AI | 299 | Minimum Voltage Fundamental Coincident Angle A-N/A-B | Modbus 401445; not polled by default | Read | ||
| AI | 300 | Minimum Voltage Fundamental RMS Magnitude B-N/B-C | Modbus 401446; not polled by default | V | Read | |
| AI | 301 | Minimum Voltage Fundamental Coincident Angle B-N/B-C | Modbus 401447; not polled by default | Read | ||
| AI | 302 | Minimum Voltage Fundamental RMS Magnitude C-N/C-A | Modbus 401448; not polled by default | V | Read | |
| AI | 303 | Minimum Voltage Fundamental Coincident Angle C-N/C-A | Modbus 401449; not polled by default | Read | ||
| AI | 304 | Minimum Voltage Fundamental RMS Magnitude N-G | Modbus 401450; not polled by default | V | Read | |
| AI | 305 | Minimum Voltage Fund. Coincident Angle N-G | Modbus 401451; not polled by default | Read | ||
| AI | 306 | Minimum Fundamental Real Power Phase A | Modbus 401455; not polled by default | kW | Read | |
| AI | 307 | Minimum Fundamental Real Power Phase B | Modbus 401456; not polled by default | kW | Read | |
| AI | 308 | Minimum Fundamental Real Power Phase C | Modbus 401457; not polled by default | kW | Read | |
| AI | 309 | Minimum Fundamental Real Power Total | Modbus 401458; not polled by default | kW | Read | |
| AI | 310 | Minimum Fundamental Reactive Power Phase A | Modbus 401459; not polled by default | kVAR | Read | |
| AI | 311 | Minimum Fundamental Reactive Power Phase B | Modbus 401460; not polled by default | kVAR | Read | |
| AI | 312 | Minimum Fundamental Reactive Power Phase C | Modbus 401461; not polled by default | kVAR | Read | |
| AI | 313 | Minimum Fundamental Reactive Power Total | Modbus 401462; not polled by default | kVAR | Read | |
| AI | 314 | Minimum Distortion Power Phase A | Modbus 401464; not polled by default | kW | Read | |
| AI | 315 | Minimum Distortion Power Phase B | Modbus 401465; not polled by default | kW | Read | |
| AI | 316 | Minimum Distortion Power Phase C | Modbus 401466; not polled by default | kW | Read | |
| AI | 317 | Minimum Distortion Power Total | Modbus 401467; not polled by default | kW | Read | |
| AI | 318 | Minimum Distortion Power Factor Phase A | Modbus 401468; not polled by default | % | Read | |
| AI | 319 | Minimum Distortion Power Factor Phase B | Modbus 401469; not polled by default | % | Read | |
| AI | 320 | Minimum Distortion Power Factor Phase C | Modbus 401470; not polled by default | % | Read | |
| AI | 321 | Minimum Distortion Power Factor Total | Modbus 401471; not polled by default | % | Read | |
| AI | 322 | Minimum Harmonic Current Phase A | Modbus 401474; not polled by default | A | Read | |
| AI | 323 | Minimum Harmonic Current Phase B | Modbus 401475; not polled by default | A | Read | |
| AI | 324 | Minimum Harmonic Current Phase C | Modbus 401476; not polled by default | A | Read | |
| AI | 325 | Minimum Harmonic Current Neutral | Modbus 401477; not polled by default | A | Read | |
| AI | 326 | Minimum Harmonic Voltage A-N/A-B | Modbus 401478; not polled by default | V | Read | |
| AI | 327 | Minimum Harmonic Voltage B-N/B-C | Modbus 401479; not polled by default | V | Read | |
| AI | 328 | Minimum Harmonic Voltage C-N/C-A | Modbus 401480; not polled by default | V | Read | |
| AI | 329 | Minimum Total Demand Distortion | Modbus 401481; not polled by default | % | Read | |
| AI | 330 | Minimum Current Positive Sequence Magnitude | Modbus 401484; not polled by default | A | Read | |
| AI | 331 | Minimum Current Positive Sequence Angle | Modbus 401485; not polled by default | Read | ||
| AI | 332 | Minimum Current Negative Sequence Magnitude | Modbus 401486; not polled by default | A | Read | |
| AI | 333 | Minimum Current Negative Sequence Angle | Modbus 401487; not polled by default | Read | ||
| AI | 334 | Minimum Current Zero Sequence Magnitude | Modbus 401488; not polled by default | A | Read | |
| AI | 335 | Minimum Current Zero Sequence Angle | Modbus 401489; not polled by default | Read | ||
| AI | 336 | Minimum Voltage Positive Sequence Magnitude | Modbus 401490; not polled by default | V | Read | |
| AI | 337 | Minimum Voltage Positive Sequence Angle | Modbus 401491; not polled by default | Read | ||
| AI | 338 | Minimum Voltage Negative Sequence Magnitude | Modbus 401492; not polled by default | V | Read | |
| AI | 339 | Minimum Voltage Negative Sequence Angle | Modbus 401493; not polled by default | Read | ||
| AI | 340 | Minimum Voltage Zero Sequence Magnitude | Modbus 401494; not polled by default | V | Read | |
| AI | 341 | Minimum Voltage Zero Sequence Angle | Modbus 401495; not polled by default | Read | ||
| AI | 342 | Minimum Current Sequence Unbalance | Modbus 401496; not polled by default | % | Read | |
| AI | 343 | Minimum Voltage Sequence Unbalance | Modbus 401497; not polled by default | % | Read | |
| AI | 344 | Minimum Current Sequence Unbalance Factor | Modbus 401498; not polled by default | % | Read | |
| AI | 345 | Minimum Voltage Sequence Unbalance Factor | Modbus 401499; not polled by default | Read | ||
| AI | 346 | Maximum Current Phase A | Modbus 401500; not polled by default | A | Read | |
| AI | 347 | Maximum Current Phase B | Modbus 401501; not polled by default | A | Read | |
| AI | 348 | Maximum Current Phase C | Modbus 401502; not polled by default | A | Read | |
| AI | 349 | Maximum Current Neutral | Modbus 401503; not polled by default | A | Read | |
| AI | 350 | Maximum Current Ground | Modbus 401504; not polled by default | A | Read | |
| AI | 351 | Maximum Current 3 Phase Average | Modbus 401505; not polled by default | A | Read | |
| AI | 352 | Maximum Current Apparent RMS | Modbus 401506; not polled by default | A | Read | |
| AI | 353 | Maximum Current Unbalance Phase A | Modbus 401507; not polled by default | % | Read | |
| AI | 354 | Maximum Current Unbalance Phase B | Modbus 401508; not polled by default | % | Read | |
| AI | 355 | Maximum Current Unbalance Phase C | Modbus 401509; not polled by default | % | Read | |
| AI | 356 | Maximum Current Unbalance Max | Modbus 401510; not polled by default | % | Read | |
| AI | 357 | Maximum Voltage A-B | Modbus 401520; not polled by default | V | Read | |
| AI | 358 | Maximum Voltage B-C | Modbus 401521; not polled by default | V | Read | |
| AI | 359 | Maximum Voltage C-A | Modbus 401522; not polled by default | V | Read | |
| AI | 360 | Maximum Voltage L-L Average | Modbus 401523; not polled by default | V | Read | |
| AI | 361 | Maximum Voltage A-N | Modbus 401524; not polled by default | V | Read | |
| AI | 362 | Maximum Voltage B-N | Modbus 401525; not polled by default | V | Read | |
| AI | 363 | Maximum Voltage C-N | Modbus 401526; not polled by default | V | Read | |
| AI | 364 | Maximum Voltage N-G | Modbus 401527; not polled by default | V | Read | |
| AI | 365 | Maximum Voltage L-N Average | Modbus 401528; not polled by default | V | Read | |
| AI | 366 | Maximum Voltage Unbalance A-B | Modbus 401529; not polled by default | % | Read | |
| AI | 367 | Maximum Voltage Unbalance B-C | Modbus 401530; not polled by default | % | Read | |
| AI | 368 | Maximum Voltage Unbalance C-A | Modbus 401531; not polled by default | % | Read | |
| AI | 369 | Maximum Voltage Unbalance Max L-L | Modbus 401532; not polled by default | % | Read | |
| AI | 370 | Maximum Voltage Unbalance A-N | Modbus 401533; not polled by default | % | Read | |
| AI | 371 | Maximum Voltage Unbalance B-N | Modbus 401534; not polled by default | % | Read | |
| AI | 372 | Maximum Voltage Unbalance C-N | Modbus 401535; not polled by default | % | Read | |
| AI | 373 | Maximum Voltage Unbalance Max L-N | Modbus 401536; not polled by default | % | Read | |
| AI | 374 | Maximum Real Power Phase A | Modbus 401540; not polled by default | kWh | Read | |
| AI | 375 | Maximum Real Power Phase B | Modbus 401541; not polled by default | kWh | Read | |
| AI | 376 | Maximum Real Power Phase C | Modbus 401542; not polled by default | kWh | Read | |
| AI | 377 | Maximum Real Power Total | Modbus 401543; not polled by default | kWh | Read | |
| AI | 378 | Maximum Reactive Power Phase A | Modbus 401544; not polled by default | kVAR | Read | |
| AI | 379 | Maximum Reactive Power Phase B | Modbus 401545; not polled by default | kVAR | Read | |
| AI | 380 | Maximum Reactive Power Phase C | Modbus 401546; not polled by default | kVAR | Read | |
| AI | 381 | Maximum Reactive Power Total | Modbus 401547; not polled by default | kVAR | Read | |
| AI | 382 | Maximum Apparent Power Phase A | Modbus 401548; not polled by default | kVA | Read | |
| AI | 383 | Maximum Apparent Power Phase B | Modbus 401549; not polled by default | kVA | Read | |
| AI | 384 | Maximum Apparent Power Phase C | Modbus 401550; not polled by default | kVA | Read | |
| AI | 385 | Maximum Apparent Power Total | Modbus 401551; not polled by default | kVA | Read | |
| AI | 386 | Maximum True Power Factor Phase A | Modbus 401560; not polled by default | Read | ||
| AI | 387 | Maximum True Power Factor Phase B | Modbus 401561; not polled by default | Read | ||
| AI | 388 | Maximum True Power Factor Phase C | Modbus 401562; not polled by default | Read | ||
| AI | 389 | Maximum True Power Factor Total | Modbus 401563; not polled by default | Read | ||
| AI | 390 | Maximum Alternate True Power Factor Phase A | Modbus 401564; not polled by default | Read | ||
| AI | 391 | Maximum Alternate True Power Factor Phase B | Modbus 401565; not polled by default | Read | ||
| AI | 392 | Maximum Alternate True Power Factor Phase C | Modbus 401566; not polled by default | Read | ||
| AI | 393 | Maximum Alternate True Power Factor Total | Modbus 401567; not polled by default | Read | ||
| AI | 394 | Maximum Displacement Power Factor Phase A | Modbus 401568; not polled by default | Read | ||
| AI | 395 | Maximum Displacement Power Factor Phase B | Modbus 401569; not polled by default | Read | ||
| AI | 396 | Maximum Displacement Power Factor Phase C | Modbus 401570; not polled by default | Read | ||
| AI | 397 | Maximum Displacement Power Factor Total | Modbus 401571; not polled by default | Read | ||
| AI | 398 | Maximum Alternate Displacement Power Factor Phase A | Modbus 401572; not polled by default | Read | ||
| AI | 399 | Maximum Alternate Displacement Power Factor Phase B | Modbus 401573; not polled by default | Read | ||
| AI | 400 | Maximum Alternate Displacement Power Factor Phase C | Modbus 401574; not polled by default | Read | ||
| AI | 401 | Maximum Alternate Displacement Power Factor Total | Modbus 401575; not polled by default | Read | ||
| AI | 402 | Maximum Frequency | Modbus 401580; not polled by default | Hz | Read | |
| AI | 403 | Maximum Temperature | Modbus 401581; not polled by default | Read | ||
| AI | 404 | Maximum Auxiliary Analog Input Value User-Selected Input 1 | Modbus 401590; not polled by default | Read | ||
| AI | 405 | Maximum Auxiliary Analog Input Value User-Selected Input 2 | Modbus 401591; not polled by default | Read | ||
| AI | 406 | Maximum Auxiliary Analog Input Value User-Selected Input 3 | Modbus 401592; not polled by default | Read | ||
| AI | 407 | Maximum Auxiliary Analog Input Value User-Selected Input 4 | Modbus 401593; not polled by default | Read | ||
| AI | 408 | Maximum Auxiliary Analog Input Value User-Selected Input 5 | Modbus 401594; not polled by default | Read | ||
| AI | 409 | Maximum Auxiliary Analog Input Value User-Selected Input 6 | Modbus 401595; not polled by default | Read | ||
| AI | 410 | Maximum Auxiliary Analog Input Value User-Selected Input 7 | Modbus 401596; not polled by default | Read | ||
| AI | 411 | Maximum Auxiliary Analog Input Value User-Selected Input 8 | Modbus 401597; not polled by default | Read | ||
| AI | 412 | Maximum Auxiliary Analog Input Value User-Selected Input 9 | Modbus 401598; not polled by default | Read | ||
| AI | 413 | Maximum Auxiliary Analog Input Value User-Selected Input 10 | Modbus 401599; not polled by default | Read | ||
| AI | 414 | Maximum THD/thd Current Phase A | Modbus 401600; not polled by default | % | Read | |
| AI | 415 | Maximum THD/thd Current Phase B | Modbus 401601; not polled by default | % | Read | |
| AI | 416 | Maximum THD/thd Current Phase C | Modbus 401602; not polled by default | % | Read | |
| AI | 417 | Maximum THD/thd Current Phase N | Modbus 401603; not polled by default | % | Read | |
| AI | 418 | Maximum THD/thd Current Ground | Modbus 401604; not polled by default | % | Read | |
| AI | 419 | Maximum THD/thd Voltage Phase A-N | Modbus 401607; not polled by default | % | Read | |
| AI | 420 | Maximum THD/thd Voltage Phase B-N | Modbus 401608; not polled by default | % | Read | |
| AI | 421 | Maximum THD/thd Voltage Phase C-N | Modbus 401609; not polled by default | % | Read | |
| AI | 422 | Maximum THD/thd Voltage Phase N-G | Modbus 401610; not polled by default | % | Read | |
| AI | 423 | Maximum THD/thd Voltage Phase A-B | Modbus 401611; not polled by default | % | Read | |
| AI | 424 | Maximum THD/thd Voltage Phase B-C | Modbus 401612; not polled by default | % | Read | |
| AI | 425 | Maximum THD/thd Voltage Phase C-A | Modbus 401613; not polled by default | % | Read | |
| AI | 426 | Maximum THD/thd Voltage 3-Phase Average L-N | Modbus 401615; not polled by default | % | Read | |
| AI | 427 | Maximum THD/thd Voltage 3-Phase Average L-L | Modbus 401616; not polled by default | % | Read | |
| AI | 428 | Maximum Current K-Factor Phase A | Modbus 401618; not polled by default | Read | ||
| AI | 429 | Maximum Current K-Factor Phase B | Modbus 401619; not polled by default | Read | ||
| AI | 430 | Maximum Current K-Factor Phase C | Modbus 401620; not polled by default | Read | ||
| AI | 431 | Maximum Crest Factor Current Phase A | Modbus 401621; not polled by default | Read | ||
| AI | 432 | Maximum Crest Factor Current Phase B | Modbus 401622; not polled by default | Read | ||
| AI | 433 | Maximum Crest Factor Current Phase C | Modbus 401623; not polled by default | Read | ||
| AI | 434 | Maximum Crest Factor Current Neutral | Modbus 401624; not polled by default | Read | ||
| AI | 435 | Maximum Crest Factor Voltage A-N/A-B | Modbus 401625; not polled by default | Read | ||
| AI | 436 | Maximum Crest Factor Voltage B-N/B-C | Modbus 401626; not polled by default | Read | ||
| AI | 437 | Maximum Crest Factor Voltage C-N/C-A | Modbus 401627; not polled by default | Read | ||
| AI | 438 | Maximum Current Fundamental RMS Magnitude Phase A | Modbus 401630; not polled by default | A | Read | |
| AI | 439 | Maximum Current Fundamental Coincident Angle Phase A | Modbus 401631; not polled by default | Read | ||
| AI | 440 | Maximum Current Fundamental RMS Magnitude Phase B | Modbus 401632; not polled by default | A | Read | |
| AI | 441 | Maximum Current Fundamental Coincident Angle Phase B | Modbus 401633; not polled by default | Read | ||
| AI | 442 | Maximum Current Fundamental RMS Magnitude Phase C | Modbus 401634; not polled by default | A | Read | |
| AI | 443 | Maximum Current Fundamental Coincident Angle Phase C | Modbus 401635; not polled by default | Read | ||
| AI | 444 | Maximum Current Fundamental RMS Magnitude Neutral | Modbus 401636; not polled by default | A | Read | |
| AI | 445 | Maximum Current Fundamental Coincident Angle Neutral | Modbus 401637; not polled by default | Read | ||
| AI | 446 | Maximum Current Fundamental RMS Magnitude Ground | Modbus 401638; not polled by default | A | Read | |
| AI | 447 | Maximum Current Fundamental Coincident Angle Ground | Modbus 401639; not polled by default | Read | ||
| AI | 448 | Maximum Voltage Fundamental RMS Magnitude A-N/A-B | Modbus 401644; not polled by default | V | Read | |
| AI | 449 | Maximum Voltage Fundamental Coincident Angle A-N/A-B | Modbus 401645; not polled by default | Read | ||
| AI | 450 | Maximum Voltage Fundamental RMS Magnitude B-N/B-C | Modbus 401646; not polled by default | V | Read | |
| AI | 451 | Maximum Voltage Fundamental Coincident Angle B-N/B-C | Modbus 401647; not polled by default | Read | ||
| AI | 452 | Maximum Voltage Fundamental RMS Magnitude C-N/C-A | Modbus 401648; not polled by default | V | Read | |
| AI | 453 | Maximum Voltage Fundamental Coincident Angle C-N/C-A | Modbus 401649; not polled by default | Read | ||
| AI | 454 | Maximum Voltage Fundamental RMS Magnitude N-G | Modbus 401650; not polled by default | V | Read | |
| AI | 455 | Maximum Voltage Fund. Coincident Angle N-G | Modbus 401651; not polled by default | Read | ||
| AI | 456 | Maximum Fundamental Real Power Phase A | Modbus 401655; not polled by default | kW | Read | |
| AI | 457 | Maximum Fundamental Real Power Phase B | Modbus 401656; not polled by default | kW | Read | |
| AI | 458 | Maximum Fundamental Real Power Phase C | Modbus 401657; not polled by default | kW | Read | |
| AI | 459 | Maximum Fundamental Real Power Total | Modbus 401658; not polled by default | kW | Read | |
| AI | 460 | Maximum Fundamental Reactive Power Phase A | Modbus 401659; not polled by default | kVAR | Read | |
| AI | 461 | Maximum Fundamental Reactive Power Phase B | Modbus 401660; not polled by default | kVAR | Read | |
| AI | 462 | Maximum Fundamental Reactive Power Phase C | Modbus 401661; not polled by default | kVAR | Read | |
| AI | 463 | Maximum Fundamental Reactive Power Total | Modbus 401662; not polled by default | kVAR | Read | |
| AI | 464 | Maximum Distortion Power Phase A | Modbus 401664; not polled by default | kW | Read | |
| AI | 465 | Maximum Distortion Power Phase B | Modbus 401665; not polled by default | kW | Read | |
| AI | 466 | Maximum Distortion Power Phase C | Modbus 401666; not polled by default | kW | Read | |
| AI | 467 | Maximum Distortion Power Total | Modbus 401667; not polled by default | kW | Read | |
| AI | 468 | Maximum Distortion Factor Phase A | Modbus 401668; not polled by default | Read | ||
| AI | 469 | Maximum Distortion Factor Phase B | Modbus 401669; not polled by default | Read | ||
| AI | 470 | Maximum Distortion Factor Phase C | Modbus 401670; not polled by default | Read | ||
| AI | 471 | Maximum Distortion Factor Total | Modbus 401671; not polled by default | Read | ||
| AI | 472 | Maximum Harmonic Current Phase A | Modbus 401674; not polled by default | A | Read | |
| AI | 473 | Maximum Harmonic Current Phase B | Modbus 401675; not polled by default | A | Read | |
| AI | 474 | Maximum Harmonic Current Phase C | Modbus 401676; not polled by default | A | Read | |
| AI | 475 | Maximum Harmonic Current Neutral | Modbus 401677; not polled by default | A | Read | |
| AI | 476 | Maximum Harmonic Voltage A | Modbus 401678; not polled by default | V | Read | |
| AI | 477 | Maximum Harmonic Voltage B | Modbus 401679; not polled by default | V | Read | |
| AI | 478 | Maximum Harmonic Voltage C | Modbus 401680; not polled by default | V | Read | |
| AI | 479 | Maximum Total Demand Distortion | Modbus 401681; not polled by default | % | Read | |
| AI | 480 | Maximum Current Positive Sequence Magnitude | Modbus 401684; not polled by default | A | Read | |
| AI | 481 | Maximum Current Positive Sequence Angle | Modbus 401685; not polled by default | Read | ||
| AI | 482 | Maximum Current Negative Sequence Magnitude | Modbus 401686; not polled by default | A | Read | |
| AI | 483 | Maximum Current Negative Sequence Angle | Modbus 401687; not polled by default | Read | ||
| AI | 484 | Maximum Current Zero Sequence Magnitude | Modbus 401688; not polled by default | A | Read | |
| AI | 485 | Maximum Current Zero Sequence Angle | Modbus 401689; not polled by default | Read | ||
| AI | 486 | Maximum Voltage Positive Sequence Magnitude | Modbus 401690; not polled by default | V | Read | |
| AI | 487 | Maximum Voltage Positive Sequence Angle | Modbus 401691; not polled by default | Read | ||
| AI | 488 | Maximum Voltage Negative Sequence Magnitude | Modbus 401692; not polled by default | V | Read | |
| AI | 489 | Maximum Voltage Negative Sequence Angle | Modbus 401693; not polled by default | Read | ||
| AI | 490 | Maximum Voltage Zero Sequence Magnitude | Modbus 401694; not polled by default | V | Read | |
| AI | 491 | Maximum Voltage Zero Sequence Angle | Modbus 401695; not polled by default | Read | ||
| AI | 492 | Maximum Current Sequence Unbalance | Modbus 401696; not polled by default | % | Read | |
| AI | 493 | Maximum Voltage Sequence Unbalance | Modbus 401697; not polled by default | % | Read | |
| AI | 494 | Maximum Current Sequence Unbalance Factor | Modbus 401698; not polled by default | % | Read | |
| AI | 495 | Maximum Voltage Sequence Unbalance Factor | Modbus 401699; not polled by default | % | Read | |
| AI | 496 | Energy Real In Reg 1 | Modbus 401700; not polled by default | Wh | Read | |
| AI | 497 | Energy Real In Reg 2 | Modbus 401701; not polled by default | Wh | Read | |
| AI | 498 | Energy Real In Reg 3 | Modbus 401702; not polled by default | Wh | Read | |
| AI | 499 | Energy Real In Reg 4 | Modbus 401703; not polled by default | Wh | Read | |
| AI | 500 | Energy Reactive In Reg 1 | Modbus 401704; not polled by default | VAR | Read | |
| AI | 501 | Energy Reactive In Reg 2 | Modbus 401705; not polled by default | VAR | Read | |
| AI | 502 | Energy Reactive In Reg 3 | Modbus 401706; not polled by default | VAR | Read | |
| AI | 503 | Energy Reactive In Reg 4 | Modbus 401707; not polled by default | VAR | Read | |
| AI | 504 | Energy Real Out Reg 1 | Modbus 401708; not polled by default | Wh | Read | |
| AI | 505 | Energy Real Out Reg 2 | Modbus 401709; not polled by default | Wh | Read | |
| AI | 506 | Energy Real Out Reg 3 | Modbus 401710; not polled by default | Wh | Read | |
| AI | 507 | Energy Real Out Reg 4 | Modbus 401711; not polled by default | Wh | Read | |
| AI | 508 | Energy Reactive Out Reg 1 | Modbus 401712; not polled by default | VAR | Read | |
| AI | 509 | Energy Reactive Out Reg 2 | Modbus 401713; not polled by default | VAR | Read | |
| AI | 510 | Energy Reactive Out Reg 3 | Modbus 401714; not polled by default | VAR | Read | |
| AI | 511 | Energy Reactive Out Reg 4 | Modbus 401715; not polled by default | VAR | Read | |
| AImin | 512 | Energy Real Total (signed/absolute) Reg 1 | Modbus 401716; not polled by default | Wh | Read | |
| AI | 513 | Energy Real Total (signed/absolute) Reg 2 | Modbus 401717; not polled by default | Wh | Read | |
| AI | 514 | Energy Real Total (signed/absolute) Reg 3 | Modbus 401718; not polled by default | Wh | Read | |
| AI | 515 | Energy Real Total (signed/absolute) Reg 4 | Modbus 401719; not polled by default | Wh | Read | |
| AI | 516 | Energy Reactive Total (signed/absolute) Reg 1 | Modbus 401720; not polled by default | VAR | Read | |
| AI | 517 | Energy Reactive Total (signed/absolute) Reg 2 | Modbus 401721; not polled by default | VAR | Read | |
| AI | 518 | Energy Reactive Total (signed/absolute) Reg 3 | Modbus 401722; not polled by default | VAR | Read | |
| AI | 519 | Energy Reactive Total (signed/absolute) Reg 4 | Modbus 401723; not polled by default | VAR | Read | |
| AI | 520 | Energy Apparent Reg 1 | Modbus 401724; not polled by default | Read | ||
| AI | 521 | Energy Apparent Reg 2 | Modbus 401725; not polled by default | Read | ||
| AI | 522 | Energy Apparent Reg 3 | Modbus 401726; not polled by default | Read | ||
| AI | 523 | Energy Apparent Reg 4 | Modbus 401727; not polled by default | Read | ||
| AI | 524 | Energy Conditional Real In Reg 1 | Modbus 401728; not polled by default | Wh | Read | |
| AI | 525 | Energy Conditional Real In Reg 2 | Modbus 401729; not polled by default | Wh | Read | |
| AI | 526 | Energy Conditional Real In Reg 3 | Modbus 401730; not polled by default | Wh | Read | |
| AI | 527 | Energy Conditional Real In Reg 4 | Modbus 401731; not polled by default | Wh | Read | |
| AI | 528 | Energy Conditional Reactive In Reg 1 | Modbus 401732; not polled by default | VAR | Read | |
| AI | 529 | Energy Conditional Reactive In Reg 2 | Modbus 401733; not polled by default | VAR | Read | |
| AI | 530 | Energy Conditional Reactive In Reg 3 | Modbus 401734; not polled by default | VAR | Read | |
| AI | 531 | Energy Conditional Reactive In Reg 4 | Modbus 401735; not polled by default | VAR | Read | |
| AI | 532 | Energy Conditional Real Out Reg 1 | Modbus 401736; not polled by default | Wh | Read | |
| AI | 533 | Energy Conditional Real Out Reg 2 | Modbus 401737; not polled by default | Wh | Read | |
| AI | 534 | Energy Conditional Real Out Reg 3 | Modbus 401738; not polled by default | Wh | Read | |
| AI | 535 | Energy Conditional Real Out Reg 4 | Modbus 401739; not polled by default | Wh | Read | |
| AI | 536 | Energy Conditional Reactive Out Reg 1 | Modbus 401740; not polled by default | Read | ||
| AI | 537 | Energy Conditional Reactive Out Reg 2 | Modbus 401741; not polled by default | Read | ||
| AI | 538 | Energy Conditional Reactive Out Reg 3 | Modbus 401742; not polled by default | Read | ||
| AI | 539 | Energy Conditional Reactive Out Reg 4 | Modbus 401743; not polled by default | Read | ||
| AI | 540 | Energy Conditional Apparent Reg 1 | Modbus 401744; not polled by default | Read | ||
| AI | 541 | Energy Conditional Apparent Reg 2 | Modbus 401745; not polled by default | Read | ||
| AI | 542 | Energy Conditional Apparent Reg 3 | Modbus 401746; not polled by default | Read | ||
| AI | 543 | Energy Conditional Apparent Reg 4 | Modbus 401747; not polled by default | Read | ||
| AI | 544 | Energy Incremental Real In Last Complete Interval Reg 1 | Modbus 401748; not polled by default | Read | ||
| AI | 545 | Energy Incremental Real In Last Complete Interval Reg 2 | Modbus 401749; not polled by default | Read | ||
| AI | 546 | Energy Incremental Real In Last Complete Interval Reg 3 | Modbus 401750; not polled by default | Read | ||
| AI | 547 | Energy Incremental Reactive In Last Complete Interval Reg 1 | Modbus 401751; not polled by default | Read | ||
| AI | 548 | Energy Incremental Reactive In Last Complete Interval Reg 2 | Modbus 401752; not polled by default | Read | ||
| AI | 549 | Energy Incremental Reactive In Last Complete Interval Reg 3 | Modbus 401753; not polled by default | Read | ||
| AI | 550 | Energy Incremental Real Out Last Complete Interval Reg 1 | Modbus 401754; not polled by default | Read | ||
| AI | 551 | Energy Incremental Real Out Last Complete Interval Reg 2 | Modbus 401755; not polled by default | Read | ||
| AI | 552 | Energy Incremental Real Out Last Complete Interval Reg 3 | Modbus 401756; not polled by default | Read | ||
| AI | 553 | Energy Incremental Reactive Out Last Complete Interval Reg 1 | Modbus 401757; not polled by default | Read | ||
| AI | 554 | Energy Incremental Reactive Out Last Complete Interval Reg 2 | Modbus 401758; not polled by default | Read | ||
| AI | 555 | Energy Incremental Reactive Out Last Complete Interval Reg 3 | Modbus 401759; not polled by default | Read | ||
| AI | 556 | Energy Incremental Apparent Last Complete Interval Reg 1 | Modbus 401760; not polled by default | Read | ||
| AI | 557 | Energy Incremental Apparent Last Complete Interval Reg 2 | Modbus 401761; not polled by default | Read | ||
| AI | 558 | Energy Incremental Apparent Last Complete Interval Reg 3 | Modbus 401762; not polled by default | Read | ||
| AI | 559 | DateTime Last Complete Incremental Energy Interval Reg 1 | Modbus 401763; not polled by default | Read | ||
| AI | 560 | DateTime Last Complete Incremental Energy Interval Reg 2 | Modbus 401764; not polled by default | Read | ||
| AI | 561 | DateTime Last Complete Incremental Energy Interval Reg 3 | Modbus 401765; not polled by default | Read | ||
| AI | 562 | DateTime Last Complete Incremental Energy Interval Reg 4 | Modbus 401766; not polled by default | Read | ||
| AI | 563 | Energy Incremental Real In Present Interval Reg 1 | Modbus 401767; not polled by default | Read | ||
| AI | 564 | Energy Incremental Real In Present Interval Reg 2 | Modbus 401768; not polled by default | Read | ||
| AI | 565 | Energy Incremental Real In Present Interval Reg 3 | Modbus 401769; not polled by default | Read | ||
| AI | 566 | Energy. Incremental Reactive In Present Interval Reg 1 | Modbus 401770; not polled by default | Read | ||
| AI | 567 | Energy. Incremental Reactive In Present Interval Reg 2 | Modbus 401771; not polled by default | Read | ||
| AI | 568 | Energy. Incremental Reactive In Present Interval Reg 3 | Modbus 401772; not polled by default | Read | ||
| AI | 569 | Energy Incremental Real Out Present Interval Reg 1 | Modbus 401773; not polled by default | Read | ||
| AI | 570 | Energy Incremental Real Out Present Interval Reg 2 | Modbus 401774; not polled by default | Read | ||
| AI | 571 | Energy Incremental Real Out Present Interval Reg 3 | Modbus 401775; not polled by default | Read | ||
| AI | 572 | Energy Incremental Reactive Out Present Interval Reg 1 | Modbus 401776; not polled by default | Read | ||
| AI | 573 | Energy Incremental Reactive Out Present Interval Reg 2 | Modbus 401777; not polled by default | Read | ||
| AI | 574 | Energy Incremental Reactive Out Present Interval Reg 3 | Modbus 401778; not polled by default | Read | ||
| AI | 575 | Energy Incremental Apparent Present Interval Reg 1 | Modbus 401779; not polled by default | Read | ||
| AI | 576 | Energy Incremental Apparent Present Interval Reg 2 | Modbus 401780; not polled by default | Read | ||
| AI | 577 | Energy Incremental Apparent Present Interval Reg 3 | Modbus 401781; not polled by default | Read | ||
| AI | 578 | Energy Reactive Quadrant 1 Reg 1 | Modbus 401782; not polled by default | Read | ||
| AI | 579 | Energy Reactive Quadrant 1 Reg 2 | Modbus 401783; not polled by default | Read | ||
| AI | 580 | Energy Reactive Quadrant 1 Reg 3 | Modbus 401784; not polled by default | Read | ||
| AI | 581 | Energy Reactive Quadrant 2 Reg 1 | Modbus 401785; not polled by default | Read | ||
| AI | 582 | Energy Reactive Quadrant 2 Reg 2 | Modbus 401786; not polled by default | Read | ||
| AI | 583 | Energy Reactive Quadrant 2 Reg 3 | Modbus 401787; not polled by default | Read | ||
| AI | 584 | Energy Reactive Quadrant 3 Reg 1 | Modbus 401788; not polled by default | Read | ||
| AI | 585 | Energy Reactive Quadrant 3 Reg 2 | Modbus 401789; not polled by default | Read | ||
| AI | 586 | Energy Reactive Quadrant 3 Reg 3 | Modbus 401790; not polled by default | Read | ||
| AI | 587 | Energy Reactive Quadrant 4 Reg 1 | Modbus 401791; not polled by default | Read | ||
| AI | 588 | Energy Reactive Quadrant 4 Reg 2 | Modbus 401792; not polled by default | Read | ||
| AI | 589 | Energy Reactive Quadrant 4 Reg 3 | Modbus 401793; not polled by default | Read | ||
| AI | 590 | Conditional Energy Control Status | Modbus 401794; not polled by default | Read | ||
| AI | 591 | Last Demand Real Power 3- Phase Total | Modbus 402150; not polled by default | kW | Read | |
| AI | 592 | Present Demand Real Power 3- Phase Total | Modbus 402151; not polled by default | kW | Read | |
| AI | 593 | Running Average Demand Real Power 3- Phase Total | Modbus 402152; not polled by default | kW | Read | |
| AI | 594 | Predicted Demand Real Power 3- Phase Total | Modbus 402153; not polled by default | kW | Read | |
| AI | 595 | Peak Demand Real Power 3- Phase Total | Modbus 402154; not polled by default | kW | Read | |
| AI | 596 | Peak Demand DateTime Real Power 3- Phase Total Reg 1 | Modbus 402155; not polled by default | Read | ||
| AI | 597 | Peak Demand DateTime Real Power 3- Phase Total Reg 2 | Modbus 402156; not polled by default | Read | ||
| AI | 598 | Peak Demand DateTime Real Power 3- Phase Total Reg 3 | Modbus 402157; not polled by default | Read | ||
| AI | 599 | Peak Demand DateTime Real Power 3- Phase Total Reg 4 | Modbus 402158; not polled by default | Read | ||
| AI | 600 | Cumulative Demand Real Power 3- Phase Total | Modbus 402159; not polled by default | Read | ||
| AI | 601 | Power Factor Average @ Peak Demand Real Power | Modbus 402161; not polled by default | PF | Read | |
| AI | 602 | Power Demand Reactive @ Peak Demand Real Power | Modbus 402162; not polled by default | kVAR | Read | |
| AI | 603 | Power Demand Apparent @ Peak Demand Real Power | Modbus 402163; not polled by default | kVA | Read | |
| AI | 604 | Last Demand Reactive Power 3-Phase Total | Modbus 402164; not polled by default | kVAR | Read | |
| AI | 605 | Present Demand Reactive Power 3-Phase Total | Modbus 402165; not polled by default | kVAR | Read | |
| AI | 606 | Running Average Demand | Modbus 402166; not polled by default | kVAR | Read | |
| AI | 607 | Reactive Power 3-Phase Total | Modbus 402167; not polled by default | kVAR | Read | |
| AI | 608 | Predicted Demand Reactive Power 3-Phase Total | Modbus 402168; not polled by default | kVAR | Read | |
| AI | 609 | Peak Demand Reactive Power 3-Phase Total | Modbus 402169; not polled by default | kVAR | Read | |
| AI | 610 | Peak Demand DateTime Reactive Power 3-Phase Total Reg 1 | Modbus 402170; not polled by default | Read | ||
| AI | 611 | Peak Demand DateTime Reactive Power 3-Phase Total Reg 2 | Modbus 402171; not polled by default | Read | ||
| AI | 612 | Peak Demand DateTime Reactive Power 3-Phase Total Reg 3 | Modbus 402172; not polled by default | Read | ||
| AI | 613 | Peak Demand DateTime Reactive Power 3-Phase Total Reg 4 | Modbus 402173; not polled by default | Read | ||
| AI | 614 | Cumulative Demand Reactive Power 3-Phase Total | Modbus 402174; not polled by default | Read | ||
| AI | 615 | Power Factor Average @ Peak Demand Reactive Power | Modbus 402176; not polled by default | Read | ||
| AI | 616 | Power Demand Real @ Peak Demand Reactive Power | Modbus 402177; not polled by default | kW | Read | |
| AI | 617 | Power Demand Apparent @ Peak Demand Reactive Power | Modbus 402178; not polled by default | kVA | Read | |
| AI | 618 | Last Demand Apparent Power 3-Phase Total | Modbus 402180; not polled by default | kVA | Read | |
| AI | 619 | Present Demand Apparent Power 3-Phase Total | Modbus 402181; not polled by default | kVA | Read | |
| AI | 620 | Running Average Demand Apparent Power 3-Phase Total | Modbus 402182; not polled by default | kVA | Read | |
| AI | 621 | Predicted Demand Apparent Power 3-Phase Total | Modbus 402183; not polled by default | kVA | Read | |
| AI | 622 | Peak Demand Apparent Power 3-Phase Total | Modbus 402184; not polled by default | kVA | Read | |
| AI | 623 | Peak Demand DateTime Apparent Power 3-Phase Total Reg 1 | Modbus 402185; not polled by default | Read | ||
| AI | 624 | Peak Demand DateTime Apparent Power 3-Phase Total Reg 2 | Modbus 402186; not polled by default | Read | ||
| AI | 625 | Peak Demand DateTime Apparent Power 3-Phase Total Reg 3 | Modbus 402187; not polled by default | Read | ||
| AI | 626 | Peak Demand DateTime Apparent Power 3-Phase Total Reg 4 | Modbus 402188; not polled by default | Read | ||
| AI | 627 | Cumulative Demand Apparent Power 3-Phase Total | Modbus 402189; not polled by default | kVA | Read | |
| AI | 628 | Power Factor Average @ Peak Demand Apparent Power | Modbus 402191; not polled by default | Read | ||
| AI | 629 | Power Demand Real @ Peak Demand Apparent Power | Modbus 402192; not polled by default | Read | ||
| AI | 630 | Power Demand Reactive @ Peak Demand Apparent Power | Modbus 402193; not polled by default | Read | ||
| AI | 631 | Circuit Monitor Label Reg 1 | Modbus 403000; not polled by default | Read | ||
| AI | 632 | Circuit Monitor Label Reg 2 | Modbus 403001; not polled by default | Read | ||
| AI | 633 | Circuit Monitor Nameplate Reg 1 | Modbus 403002; not polled by default | Read | ||
| AI | 634 | Circuit Monitor Nameplate Reg 2 | Modbus 403003; not polled by default | Read | ||
| AI | 635 | Circuit Monitor Nameplate Reg 3 | Modbus 403004; not polled by default | Read | ||
| AI | 636 | Circuit Monitor Nameplate Reg 4 | Modbus 403005; not polled by default | Read | ||
| AI | 637 | Circuit Monitor Nameplate Reg 5 | Modbus 403006; not polled by default | Read | ||
| AI | 638 | Circuit Monitor Nameplate Reg 6 | Modbus 403007; not polled by default | Read | ||
| AI | 639 | Circuit Monitor Nameplate Reg 7 | Modbus 403008; not polled by default | Read | ||
| AI | 640 | Circuit Monitor Nameplate Reg 8 | Modbus 403009; not polled by default | Read | ||
| AI | 641 | Circuit Monitor Present Operating System Firmware Revision Level | Modbus 403014; not polled by default | Read | ||
| AI | 642 | Present Date/Time Reg 1 | Modbus 403034; not polled by default | Read | ||
| AI | 643 | Present Date/Time Reg 2 | Modbus 403035; not polled by default | Read | ||
| AI | 644 | Present Date/Time Reg 3 | Modbus 403036; not polled by default | Read | ||
| AI | 645 | Present Date/Time Reg 4 | Modbus 403037; not polled by default | Read | ||
| AI | 646 | Last Unit Restart Date Time Reg 1 | Modbus 403039; not polled by default | Read | ||
| AI | 647 | Last Unit Restart Date Time Reg 2 | Modbus 403040; not polled by default | Read | ||
| AI | 648 | Last Unit Restart Date Time Reg 3 | Modbus 403041; not polled by default | Read | ||
| AI | 649 | Last Unit Restart Date Time Reg 4 | Modbus 403042; not polled by default | Read | ||
| AI | 650 | Number of Metering System Restarts | Modbus 403043; not polled by default | Read | ||
| AI | 651 | Number of Control Power Failures | Modbus 403044; not polled by default | Read | ||
| AI | 652 | Date/Time of Last Control Power Failure Reg 1 | Modbus 403045; not polled by default | Read | ||
| AI | 653 | Date/Time of Last Control Power Failure Reg 2 | Modbus 403046; not polled by default | Read | ||
| AI | 654 | Date/Time of Last Control Power Failure Reg 3 | Modbus 403047; not polled by default | Read | ||
| AI | 655 | Date/Time of Last Control Power Failure Reg 4 | Modbus 403048; not polled by default | Read | ||
| BI | 656 | Self-Test Results Bit 00 = Is set to 1 if any failure occurs | Modbus 403050 bit 0; not polled by default | Read | ||
| BI | 657 | Self-Test Results Bit 01 = RTC failure | Modbus 403050 bit 1; not polled by default | Read | ||
| BI | 658 | Self-Test Results Bit 02 = MCF UART #1 failure | Modbus 403050 bit 2; not polled by default | Read | ||
| BI | 659 | Self-Test Results Bit 03 = MCF UART #2 failure | Modbus 403050 bit 3; not polled by default | Read | ||
| BI | 660 | Self-Test Results Bit 04 = PLD UART failure | Modbus 403050 bit 4; not polled by default | Read | ||
| BI | 661 | Self-Test Results Bit 05 = Metering Collection overrun failure | Modbus 403050 bit 5; not polled by default | Read | ||
| BI | 662 | Self-Test Results Bit 06 = Metering Process 0.1 overrun failure | Modbus 403050 bit 6; not polled by default | Read | ||
| BI | 663 | Self-Test Results Bit 07 = Metering Process 1.0 overrun failure | Modbus 403050 bit 7; not polled by default | Read | ||
| BI | 664 | Self-Test Results Bit 08 = Disk-on-Chip failure | Modbus 403050 bit 8; not polled by default | Read | ||
| BI | 665 | Self-Test Results Bit 09 = Display failure | Modbus 403050 bit 9; not polled by default | Read | ||
| BI | 666 | Self-Test Results Bit 10 = CV Module failure | Modbus 403050 bit 10; not polled by default | Read | ||
| BI | 667 | Self-Test Results Bit 11 = Aux Plug EEPROM failure | Modbus 403050 bit 11; not polled by default | Read | ||
| BI | 668 | Self-Test Results Bit 12 = Flash Memory failure | Modbus 403050 bit 12; not polled by default | Read | ||
| BI | 669 | Self-Test Results Bit 13 = Dram Memory failure | Modbus 403050 bit 13; not polled by default | Read | ||
| BI | 670 | Self-Test Results Bit 14 = Simtek Memory failure | Modbus 403050 bit 14; not polled by default | Read | ||
| BI | 671 | Self-Test Results Bit 15 = RTC Memory failure | Modbus 403050 bit 15; not polled by default | Read | ||
| BI | 672 | Self-Test Results Bit 00 = Aux IO failure | Modbus 403051 bit 0; not polled by default | Read | ||
| BI | 673 | Self-Test Results Bit 01 = Option Slot A module failure | Modbus 403051 bit 1; not polled by default | Read | ||
| BI | 674 | Self-Test Results Bit 02 = Option Slot B module failure | Modbus 403051 bit 2; not polled by default | Read | ||
| BI | 675 | Self-Test Results Bit 03 = IOX module failure | Modbus 403051 bit 3; not polled by default | Read | ||
| BI | 676 | Self-Test Results Bit 04 = Not used | Modbus 403051 bit 4; not polled by default | Read | ||
| BI | 677 | Self-Test Results Bit 05 = Not used | Modbus 403051 bit 5; not polled by default | Read | ||
| BI | 678 | Self-Test Results Bit 06 = Not used | Modbus 403051 bit 6; not polled by default | Read | ||
| BI | 679 | Self-Test Results Bit 07 = Not used | Modbus 403051 bit 7; not polled by default | Read | ||
| BI | 680 | Self-Test Results Bit 08 = OS Create failure | Modbus 403051 bit 8; not polled by default | Read | ||
| BI | 681 | Self-Test Results Bit 09 = OS Queue overrun failure | Modbus 403051 bit 9; not polled by default | Read | ||
| BI | 682 | Self-Test Results Bit 10 = Not used | Modbus 403051 bit 10; not polled by default | Read | ||
| BI | 683 | Self-Test Results Bit 11 = Not used | Modbus 403051 bit 11; not polled by default | Read | ||
| BI | 684 | Self-Test Results Bit 12 = Not used | Modbus 403051 bit 12; not polled by default | Read | ||
| BI | 685 | Self-Test Bit 13 = Systems shut down due to continuous reset | Modbus 403051 bit 13; not polled by default | Read | ||
| BI | 686 | Self-Test Results Bit 14 = Unit in Download Condition A | Modbus 403051 bit 14; not polled by default | Read | ||
| BI | 687 | Self-Test Results Bit 15 = Unit in Download Condition B | Modbus 403051 bit 15; not polled by default | Read | ||
| BI | 688 | Configuration Modified Bit 00 = Summary bit | Modbus 403052 bit 0; not polled by default | Read | ||
| BI | 689 | Configuration Modified Bit 01 = Metering System | Modbus 403052 bit 1; not polled by default | Read | ||
| BI | 690 | Configuration Modified Bit 02 = Communications System | Modbus 403052 bit 2; not polled by default | Read | ||
| BI | 691 | Configuration Modified Bit 03 = Alarm System | Modbus 403052 bit 3; not polled by default | Read | ||
| BI | 692 | Configuration Modified Bit 04 = File System | Modbus 403052 bit 4; not polled by default | Read | ||
| BI | 693 | Configuration Modified Bit 05 = Auxiliary IO System | Modbus 403052 bit 5; not polled by default | Read | ||
| BI | 694 | Configuration Modified Bit 06 = Display System | Modbus 403052 bit 6; not polled by default | Read | ||
| AI | 695 | Installed Log Memory | Modbus 403053; not polled by default | Read | ||
| AI | 696 | Free Log Memory | Modbus 403054; not polled by default | Read | ||
| AI | 697 | Log Memory Cluster Size | Modbus 403055; not polled by default | Read | ||
| AI | 698 | Programmed Disk On Chip Version Number | Modbus 403056; not polled by default | Read | ||
| AI | 699 | Real Time Clock Factory Calibration | Modbus 403058; not polled by default | Read | ||
| AI | 700 | Real Time Clock Field Calibration | Modbus 403059; not polled by default | Read | ||
| AI | 701 | Installed Log Memory | Modbus 403061; not polled by default | Read | ||
| AI | 702 | Installed Option – Slot A | Modbus 403073; not polled by default | Read | ||
| AI | 703 | Installed Option – Slot B | Modbus 403074; not polled by default | Read | ||
| AI | 704 | Installed Option – IO Extender | Modbus 403075; not polled by default | Read | ||
| AI | 705 | Present Month | Modbus 403093; not polled by default | Read | ||
| AI | 706 | Present Day | Modbus 403094; not polled by default | Read | ||
| AI | 707 | Present Year | Modbus 403095; not polled by default | Read | ||
| AI | 708 | Present Hour | Modbus 403096; not polled by default | Read | ||
| AI | 709 | Present Minute | Modbus 403097; not polled by default | Read | ||
| AI | 710 | Present Second | Modbus 403098; not polled by default | Read | ||
| AI | 711 | Day of Week | Modbus 403099; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX PowerLogic CM4000 point IDs by name
AI1100ms Current Phase AAI2100ms Current Phase BAI3100ms Current Phase CAI4100ms Current NeutralAI5100ms Current GroundAI6100ms Current 3-Phase AverageAI7100ms Current Apparent RMSAI8100ms Voltage A-BAI9100ms Voltage B-CAI10100ms Voltage C-AAI11100ms Voltage L-L AverageAI12100ms Voltage A-NAI13100ms Voltage B-NAI14100ms Voltage C-NAI15100ms Voltage N-GAI16100ms Voltage L-N AverageAI17100ms Real Power Phase AAI18100ms Real Power Phase BAI19100ms Real Power Phase CAI20100ms Real Power TotalAI21100ms Reactive Power Phase AAI22100ms Reactive Power Phase BAI23100ms Reactive Power Phase CAI24100ms Reactive Power TotalAI25100ms Apparent Power Phase AAI26100ms Apparent Power Phase BAI27100ms Apparent Power Phase CAI28100ms Apparent Power TotalAI29100ms True Power Factor Phase AAI30100ms True Power Factor Phase BAI31100ms True Power Factor Phase CAI32100ms True Power Factor TotalAI33100ms Alternate True Power Factor Phase AAI34100ms Alternate True Power Factor Phase BAI35100ms Alternate True Power Factor Phase CAI36100ms Alternate True Power Factor TotalAI37100ms FrequencyAI381sec Current Phase AAI391sec Current Phase BAI401sec Current Phase CAI411sec Current NeutralAI421sec Current GroundAI431sec Current 3-Phase AverageAI441sec Current Apparent RMSAI451sec Current Unbalance Phase AAI461sec Current Unbalance Phase BAI471sec Current Unbalance Phase CAI481sec Current Unbalance MaxAI491sec Voltage A-BAI501sec Voltage B-CAI511sec Voltage C-AAI521sec Voltage L-L AverageAI531sec Voltage A-NAI541sec Voltage B-NAI551sec Voltage C-NAI561sec Voltage N-GAI571sec Voltage L-N AverageAI581sec Voltage Unbalance A-BAI591sec Voltage Unbalance B-CAI601sec Voltage Unbalance C-AAI611sec Voltage Unbalance Max L-LAI621sec Voltage Unbalance A-NAI631sec Voltage Unbalance B-NAI641sec Voltage Unbalance C-NAI651sec Voltage Unbalance Max L-NAI661sec Real Power Phase AAI671sec Real Power Phase BAI681sec Real Power Phase CAI691sec Real Power TotalAI701sec Reactive Power Phase AAI711sec Reactive Power Phase BAI721sec Reactive Power Phase CAI731sec Reactive Power TotalAI741sec Apparent Power Phase AAI751sec Apparent Power Phase BAI761sec Apparent Power Phase CAI771sec Apparent Power TotalAI781sec True Power Factor Phase AAI791sec True Power Factor Phase BAI801sec True Power Factor Phase CAI811sec True Power Factor TotalAI821sec Alternate True Power Factor Phase AAI831sec Alternate True Power Factor Phase BAI841sec Alternate True Power Factor Phase CAI851sec Alternate True Power Factor TotalAI861sec Displacement Power Factor Phase AAI871sec Displacement Power Factor Phase BAI881sec Displacement Power Factor Phase CAI891sec Displacement Power Factor TotalAI901sec Alternate Displacement Power Factor Phase AAI911sec Alternate Displacement Power Factor Phase BAI921sec Alternate Displacement Power Factor Phase CAI931sec Alternate Displacement Power Factor TotalAI941sec FrequencyAI951sec TemperatureAI961sec Auxiliary Analog Input Value User-Selected Input 1AI971sec Auxiliary Analog Input Value User-Selected Input 2AI981sec Auxiliary Analog Input Value User-Selected Input 3AI991sec Auxiliary Analog Input Value User-Selected Input 4AI1001sec Auxiliary Analog Input Value User-Selected Input 5AI1011sec Auxiliary Analog Input Value User-Selected Input 6AI1021sec Auxiliary Analog Input Value User-Selected Input 7AI1031sec Auxiliary Analog Input Value User-Selected Input 8AI1041sec Auxiliary Analog Input Value User-Selected Input 9AI1051sec Auxiliary Analog Input Value User-Selected Input 10AI106THD/thd Current Phase AAI107THD/thd Current Phase BAI108THD/thd Current Phase CAI109THD/thd Current Phase NAI110THD/thd Current GroundAI111THD/thd Voltage Phase A-NAI112THD/thd Voltage Phase B-NAI113THD/thd Voltage Phase C-NAI114THD/thd Voltage Phase N-GAI115THD/thd Voltage Phase A-BAI116THD/thd Voltage Phase B-CAI117THD/thd Voltage Phase C-AAI118THD/thd Voltage 3-Phase Average-NAI119THD/thd Voltage 3-Phase Average-LAI120K-Factor Current Phase AAI121K-Factor Current Phase BAI122K-Factor Current Phase CAI123Crest Factor Current Phase AAI124Crest Factor Current Phase BAI125Crest Factor Current Phase CAI126Crest Factor Current NeutralAI127Crest Factor Voltage A-N/A-BAI128Crest Factor Voltage B-N/B-CAI129Crest Factor Voltage C-N/C-AAI130Current Fundamental RMS Magnitude Phase AAI131Current Fundamental Coincident Angle Phase AAI132Current Fundamental RMS Magnitude Phase BAI133Current Fundamental Coincident Angle Phase BAI134Current Fundamental RMS Magnitude Phase CAI135Current Fundamental Coincident Angle Phase CAI136Current Fundamental RMS Magnitude NeutralAI137Current Fundamental Coincident Angle NeutralAI138Current Fundamental RMS Magnitude GroundAI139Current Fundamental Coincident Angle GroundAI140Voltage Fundamental RMS Magnitude A-N/A-BAI141Voltage Fundamental Coincident Angle A-N/A-BAI142Voltage Fundamental RMS Magnitude B-N/B-CAI143Voltage Fundamental Coincident Angle B-N/B-CAI144Voltage Fundamental RMS Magnitude C-N/C-AAI145Voltage Fundamental Coincident Angle C-N/C-AAI146Voltage Fundamental RMS Magnitude N-GAI147Voltage Fundamental Coincident Angle N-GAI148Fundamental Real Power Phase AAI149Fundamental Real Power Phase BAI150Fundamental Real Power Phase CAI151Fundamental Real Power TotalAI152Fundamental Reactive Power Phase AAI153Fundamental Reactive Power Phase BAI154Fundamental Reactive Power Phase CAI155Fundamental Reactive Power TotalAI156Distortion Power Phase AAI157Distortion Power Phase BAI158Distortion Power Phase CAI159Distortion Power TotalAI160Distortion Power Factor Phase AAI161Distortion Power Factor Phase BAI162Distortion Power Factor Phase CAI163Distortion Power Factor TotalAI164Harmonic Current Phase AAI165Harmonic Current Phase BAI166Harmonic Current Phase CAI167Harmonic Current NeutralAI168Harmonic Voltage A-N/A-BAI169Harmonic Voltage B-N/B-CAI170Harmonic Voltage C-N/C-AAI171Total Demand DistortionBI172Harmonic Power Flow kW Phase ABI173Harmonic Power Flow kW Phase BBI174Harmonic Power Flow kW Phase CBI175Harmonic Power Flow kW Phase TotalBI176Harmonic Power Flow kVAr Phase ABI177Harmonic Power Flow kVAr Phase BBI178Harmonic Power Flow kVAr Phase CBI179Harmonic Power Flow kVAr Phase TotalAI180Current Positive Sequence MagnitudeAI181Current Positive Sequence AngleAI182Current Negative Sequence MagnitudeAI183Current Negative Sequence AngleAI184Current Zero Sequence MagnitudeAI185Current Zero Sequence AngleAI186Voltage Positive Sequence MagnitudeAI187Voltage Positive Sequence AngleAI188Voltage Negative Sequence MagnitudeAI189Voltage Negative Sequence AngleAI190Voltage Zero Sequence MagnitudeAI191Voltage Zero Sequence AngleAI192Current Sequence UnbalanceAI193Voltage Sequence UnbalanceAI194Current Sequence Unbalance FactorAI195Voltage Sequence Unbalance FactorAI196Minimum Current Phase AAI197Minimum Current Phase BAI198Minimum Current Phase CAI199Minimum Current NeutralAI200Minimum Current GroundAI201Minimum Current 3-Phase AverageAI202Minimum Current Apparent RMSAI203Minimum Current Unbalance Phase AAI204Minimum Current Unbalance Phase BAI205Minimum Current Unbalance Phase CAI206Minimum Current Unbalance MaxAI207Minimum Voltage A-BAI208Minimum Voltage B-CAI209Minimum Voltage C-AAI210Minimum Voltage L-L AverageAI211Minimum Voltage A-NAI212Minimum Voltage B-NAI213Minimum Voltage C-NAI214Minimum Voltage N-GAI215Minimum Voltage L-N AverageAI216Minimum Voltage Unbalance A-BAI217Minimum Voltage Unbalance B-CAI218Minimum Voltage Unbalance C-AAI219Minimum Voltage Unbalance Max L-LAI220Minimum Voltage Unbalance A-NAI221Minimum Voltage Unbalance B-NAI222Minimum Voltage Unbalance C-NAI223Minimum Voltage Unbalance Max L-NAI224Minimum Real Power Phase AAI225Minimum Real Power Phase BAI226Minimum Real Power Phase CAI227Minimum Real Power TotalAI228Minimum Reactive Power Phase AAI229Minimum Reactive Power Phase BAI230Minimum Reactive Power Phase CAI231Minimum Reactive Power TotalAI232Minimum Apparent Power Phase AAI233Minimum Apparent Power Phase BAI234Minimum Apparent Power Phase CAI235Minimum Apparent Power TotalAI236Minimum True Power Factor Phase AAI237Minimum True Power Factor Phase BAI238Minimum True Power Factor Phase CAI239Minimum True Power Factor TotalAI240Minimum Alternate True Power Factor Phase AAI241Minimum Alternate True Power Factor Phase BAI242Minimum Alternate True Power Factor Phase CAI243Minimum Alternate True Power Factor TotalAI244Minimum Displacement Power Factor Phase AAI245Minimum Displacement Power Factor Phase BAI246Minimum Displacement Power Factor Phase CAI247Minimum Displacement Power Factor TotalAI248Minimum Alternate Displacement Power Factor Phase AAI249Minimum Alternate Displacement Power Factor Phase BAI250Minimum Alternate Displacement Power Factor Phase CAI251Minimum Alternate Displacement Power Factor TotalAI252Minimum FrequencyAI253Minimum TemperatureAI254Minimum Auxiliary Analog Input Value User-Selected Input 1AI255Minimum Auxiliary Analog Input Value User-Selected Input 2AI256Minimum Auxiliary Analog Input Value User-Selected Input 3AI257Minimum Auxiliary Analog Input Value User-Selected Input 4AI258Minimum Auxiliary Analog Input Value User-Selected Input 5AI259Minimum Auxiliary Analog Input Value User-Selected Input 6AI260Minimum Auxiliary Analog Input Value User-Selected Input 7AI261Minimum Auxiliary Analog Input Value User-Selected Input 8AI262Minimum Auxiliary Analog Input Value User-Selected Input 9AI263Minimum Auxiliary Analog Input Value User-Selected Input 10AI264Minimum THD/thd Current Phase AAI265Minimum THD/thd Current Phase BAI266Minimum THD/thd Current Phase CAI267Minimum THD/thd Current Phase NAI268Minimum THD/thd Current GroundAI269Minimum THD/thd Voltage Phase A-NAI270Minimum THD/thd Voltage Phase B-NAI271Minimum THD/thd Voltage Phase C-NAI272Minimum THD/thd Voltage Phase N-GAI273Minimum THD/thd Voltage Phase A-BAI274Minimum THD/thd Voltage Phase B-CAI275Minimum THD/thd Voltage Phase C-AAI276Minimum THD/thd Voltage 3-Phase Average L-NAI277Minimum THD/thd Voltage 3-Phase Average L-LAI278Minimum Current K-Factor Phase AAI279Minimum Current K-Factor Phase BAI280Minimum Current K-Factor Phase CAI281Minimum Crest Factor Current Phase AAI282Minimum Crest Factor Current Phase BAI283Minimum Crest Factor Current Phase CAI284Minimum Crest Factor Current NeutralAI285Minimum Crest Factor Voltage A-N/A-BAI286Minimum Crest Factor Voltage B-N/B-CAI287Minimum Crest Factor Voltage C-N/C-AAI288Minimum Current Fundamental RMS Magnitude Phase AAI289Minimum Current Fundamental Coincident Angle Phase AAI290Minimum Current Fundamental RMS Magnitude Phase BAI291Minimum Current Fundamental Coincident Angle Phase BAI292Minimum Current Fundamental RMS Magnitude Phase CAI293Minimum Current Fundamental Coincident Angle Phase CAI294Minimum Current Fundamental RMS Magnitude NeutralAI295Minimum Current Fundamental Coincident Angle NeutralAI296Minimum Current Fundamental RMS Magnitude GroundAI297Minimum Current Fundamental Coincident Angle GroundAI298Minimum Voltage Fundamental RMS Magnitude A-N/A-BAI299Minimum Voltage Fundamental Coincident Angle A-N/A-BAI300Minimum Voltage Fundamental RMS Magnitude B-N/B-CAI301Minimum Voltage Fundamental Coincident Angle B-N/B-CAI302Minimum Voltage Fundamental RMS Magnitude C-N/C-AAI303Minimum Voltage Fundamental Coincident Angle C-N/C-AAI304Minimum Voltage Fundamental RMS Magnitude N-GAI305Minimum Voltage Fund. Coincident Angle N-GAI306Minimum Fundamental Real Power Phase AAI307Minimum Fundamental Real Power Phase BAI308Minimum Fundamental Real Power Phase CAI309Minimum Fundamental Real Power TotalAI310Minimum Fundamental Reactive Power Phase AAI311Minimum Fundamental Reactive Power Phase BAI312Minimum Fundamental Reactive Power Phase CAI313Minimum Fundamental Reactive Power TotalAI314Minimum Distortion Power Phase AAI315Minimum Distortion Power Phase BAI316Minimum Distortion Power Phase CAI317Minimum Distortion Power TotalAI318Minimum Distortion Power Factor Phase AAI319Minimum Distortion Power Factor Phase BAI320Minimum Distortion Power Factor Phase CAI321Minimum Distortion Power Factor TotalAI322Minimum Harmonic Current Phase AAI323Minimum Harmonic Current Phase BAI324Minimum Harmonic Current Phase CAI325Minimum Harmonic Current NeutralAI326Minimum Harmonic Voltage A-N/A-BAI327Minimum Harmonic Voltage B-N/B-CAI328Minimum Harmonic Voltage C-N/C-AAI329Minimum Total Demand DistortionAI330Minimum Current Positive Sequence MagnitudeAI331Minimum Current Positive Sequence AngleAI332Minimum Current Negative Sequence MagnitudeAI333Minimum Current Negative Sequence AngleAI334Minimum Current Zero Sequence MagnitudeAI335Minimum Current Zero Sequence AngleAI336Minimum Voltage Positive Sequence MagnitudeAI337Minimum Voltage Positive Sequence AngleAI338Minimum Voltage Negative Sequence MagnitudeAI339Minimum Voltage Negative Sequence AngleAI340Minimum Voltage Zero Sequence MagnitudeAI341Minimum Voltage Zero Sequence AngleAI342Minimum Current Sequence UnbalanceAI343Minimum Voltage Sequence UnbalanceAI344Minimum Current Sequence Unbalance FactorAI345Minimum Voltage Sequence Unbalance FactorAI346Maximum Current Phase AAI347Maximum Current Phase BAI348Maximum Current Phase CAI349Maximum Current NeutralAI350Maximum Current GroundAI351Maximum Current 3 Phase AverageAI352Maximum Current Apparent RMSAI353Maximum Current Unbalance Phase AAI354Maximum Current Unbalance Phase BAI355Maximum Current Unbalance Phase CAI356Maximum Current Unbalance MaxAI357Maximum Voltage A-BAI358Maximum Voltage B-CAI359Maximum Voltage C-AAI360Maximum Voltage L-L AverageAI361Maximum Voltage A-NAI362Maximum Voltage B-NAI363Maximum Voltage C-NAI364Maximum Voltage N-GAI365Maximum Voltage L-N AverageAI366Maximum Voltage Unbalance A-BAI367Maximum Voltage Unbalance B-CAI368Maximum Voltage Unbalance C-AAI369Maximum Voltage Unbalance Max L-LAI370Maximum Voltage Unbalance A-NAI371Maximum Voltage Unbalance B-NAI372Maximum Voltage Unbalance C-NAI373Maximum Voltage Unbalance Max L-NAI374Maximum Real Power Phase AAI375Maximum Real Power Phase BAI376Maximum Real Power Phase CAI377Maximum Real Power TotalAI378Maximum Reactive Power Phase AAI379Maximum Reactive Power Phase BAI380Maximum Reactive Power Phase CAI381Maximum Reactive Power TotalAI382Maximum Apparent Power Phase AAI383Maximum Apparent Power Phase BAI384Maximum Apparent Power Phase CAI385Maximum Apparent Power TotalAI386Maximum True Power Factor Phase AAI387Maximum True Power Factor Phase BAI388Maximum True Power Factor Phase CAI389Maximum True Power Factor TotalAI390Maximum Alternate True Power Factor Phase AAI391Maximum Alternate True Power Factor Phase BAI392Maximum Alternate True Power Factor Phase CAI393Maximum Alternate True Power Factor TotalAI394Maximum Displacement Power Factor Phase AAI395Maximum Displacement Power Factor Phase BAI396Maximum Displacement Power Factor Phase CAI397Maximum Displacement Power Factor TotalAI398Maximum Alternate Displacement Power Factor Phase AAI399Maximum Alternate Displacement Power Factor Phase BAI400Maximum Alternate Displacement Power Factor Phase CAI401Maximum Alternate Displacement Power Factor TotalAI402Maximum FrequencyAI403Maximum TemperatureAI404Maximum Auxiliary Analog Input Value User-Selected Input 1AI405Maximum Auxiliary Analog Input Value User-Selected Input 2AI406Maximum Auxiliary Analog Input Value User-Selected Input 3AI407Maximum Auxiliary Analog Input Value User-Selected Input 4AI408Maximum Auxiliary Analog Input Value User-Selected Input 5AI409Maximum Auxiliary Analog Input Value User-Selected Input 6AI410Maximum Auxiliary Analog Input Value User-Selected Input 7AI411Maximum Auxiliary Analog Input Value User-Selected Input 8AI412Maximum Auxiliary Analog Input Value User-Selected Input 9AI413Maximum Auxiliary Analog Input Value User-Selected Input 10AI414Maximum THD/thd Current Phase AAI415Maximum THD/thd Current Phase BAI416Maximum THD/thd Current Phase CAI417Maximum THD/thd Current Phase NAI418Maximum THD/thd Current GroundAI419Maximum THD/thd Voltage Phase A-NAI420Maximum THD/thd Voltage Phase B-NAI421Maximum THD/thd Voltage Phase C-NAI422Maximum THD/thd Voltage Phase N-GAI423Maximum THD/thd Voltage Phase A-BAI424Maximum THD/thd Voltage Phase B-CAI425Maximum THD/thd Voltage Phase C-AAI426Maximum THD/thd Voltage 3-Phase Average L-NAI427Maximum THD/thd Voltage 3-Phase Average L-LAI428Maximum Current K-Factor Phase AAI429Maximum Current K-Factor Phase BAI430Maximum Current K-Factor Phase CAI431Maximum Crest Factor Current Phase AAI432Maximum Crest Factor Current Phase BAI433Maximum Crest Factor Current Phase CAI434Maximum Crest Factor Current NeutralAI435Maximum Crest Factor Voltage A-N/A-BAI436Maximum Crest Factor Voltage B-N/B-CAI437Maximum Crest Factor Voltage C-N/C-AAI438Maximum Current Fundamental RMS Magnitude Phase AAI439Maximum Current Fundamental Coincident Angle Phase AAI440Maximum Current Fundamental RMS Magnitude Phase BAI441Maximum Current Fundamental Coincident Angle Phase BAI442Maximum Current Fundamental RMS Magnitude Phase CAI443Maximum Current Fundamental Coincident Angle Phase CAI444Maximum Current Fundamental RMS Magnitude NeutralAI445Maximum Current Fundamental Coincident Angle NeutralAI446Maximum Current Fundamental RMS Magnitude GroundAI447Maximum Current Fundamental Coincident Angle GroundAI448Maximum Voltage Fundamental RMS Magnitude A-N/A-BAI449Maximum Voltage Fundamental Coincident Angle A-N/A-BAI450Maximum Voltage Fundamental RMS Magnitude B-N/B-CAI451Maximum Voltage Fundamental Coincident Angle B-N/B-CAI452Maximum Voltage Fundamental RMS Magnitude C-N/C-AAI453Maximum Voltage Fundamental Coincident Angle C-N/C-AAI454Maximum Voltage Fundamental RMS Magnitude N-GAI455Maximum Voltage Fund. Coincident Angle N-GAI456Maximum Fundamental Real Power Phase AAI457Maximum Fundamental Real Power Phase BAI458Maximum Fundamental Real Power Phase CAI459Maximum Fundamental Real Power TotalAI460Maximum Fundamental Reactive Power Phase AAI461Maximum Fundamental Reactive Power Phase BAI462Maximum Fundamental Reactive Power Phase CAI463Maximum Fundamental Reactive Power TotalAI464Maximum Distortion Power Phase AAI465Maximum Distortion Power Phase BAI466Maximum Distortion Power Phase CAI467Maximum Distortion Power TotalAI468Maximum Distortion Factor Phase AAI469Maximum Distortion Factor Phase BAI470Maximum Distortion Factor Phase CAI471Maximum Distortion Factor TotalAI472Maximum Harmonic Current Phase AAI473Maximum Harmonic Current Phase BAI474Maximum Harmonic Current Phase CAI475Maximum Harmonic Current NeutralAI476Maximum Harmonic Voltage AAI477Maximum Harmonic Voltage BAI478Maximum Harmonic Voltage CAI479Maximum Total Demand DistortionAI480Maximum Current Positive Sequence MagnitudeAI481Maximum Current Positive Sequence AngleAI482Maximum Current Negative Sequence MagnitudeAI483Maximum Current Negative Sequence AngleAI484Maximum Current Zero Sequence MagnitudeAI485Maximum Current Zero Sequence AngleAI486Maximum Voltage Positive Sequence MagnitudeAI487Maximum Voltage Positive Sequence AngleAI488Maximum Voltage Negative Sequence MagnitudeAI489Maximum Voltage Negative Sequence AngleAI490Maximum Voltage Zero Sequence MagnitudeAI491Maximum Voltage Zero Sequence AngleAI492Maximum Current Sequence UnbalanceAI493Maximum Voltage Sequence UnbalanceAI494Maximum Current Sequence Unbalance FactorAI495Maximum Voltage Sequence Unbalance FactorAI496Energy Real In Reg 1AI497Energy Real In Reg 2AI498Energy Real In Reg 3AI499Energy Real In Reg 4AI500Energy Reactive In Reg 1AI501Energy Reactive In Reg 2AI502Energy Reactive In Reg 3AI503Energy Reactive In Reg 4AI504Energy Real Out Reg 1AI505Energy Real Out Reg 2AI506Energy Real Out Reg 3AI507Energy Real Out Reg 4AI508Energy Reactive Out Reg 1AI509Energy Reactive Out Reg 2AI510Energy Reactive Out Reg 3AI511Energy Reactive Out Reg 4AI512Energy Real Total (signed/absolute) Reg 1AI513Energy Real Total (signed/absolute) Reg 2AI514Energy Real Total (signed/absolute) Reg 3AI515Energy Real Total (signed/absolute) Reg 4AI516Energy Reactive Total (signed/absolute) Reg 1AI517Energy Reactive Total (signed/absolute) Reg 2AI518Energy Reactive Total (signed/absolute) Reg 3AI519Energy Reactive Total (signed/absolute) Reg 4AI520Energy Apparent Reg 1AI521Energy Apparent Reg 2AI522Energy Apparent Reg 3AI523Energy Apparent Reg 4AI524Energy Conditional Real In Reg 1AI525Energy Conditional Real In Reg 2AI526Energy Conditional Real In Reg 3AI527Energy Conditional Real In Reg 4AI528Energy Conditional Reactive In Reg 1AI529Energy Conditional Reactive In Reg 2AI530Energy Conditional Reactive In Reg 3AI531Energy Conditional Reactive In Reg 4AI532Energy Conditional Real Out Reg 1AI533Energy Conditional Real Out Reg 2AI534Energy Conditional Real Out Reg 3AI535Energy Conditional Real Out Reg 4AI536Energy Conditional Reactive Out Reg 1AI537Energy Conditional Reactive Out Reg 2AI538Energy Conditional Reactive Out Reg 3AI539Energy Conditional Reactive Out Reg 4AI540Energy Conditional Apparent Reg 1AI541Energy Conditional Apparent Reg 2AI542Energy Conditional Apparent Reg 3AI543Energy Conditional Apparent Reg 4AI544Energy Incremental Real In Last Complete Interval Reg 1AI545Energy Incremental Real In Last Complete Interval Reg 2AI546Energy Incremental Real In Last Complete Interval Reg 3AI547Energy Incremental Reactive In Last Complete Interval Reg 1AI548Energy Incremental Reactive In Last Complete Interval Reg 2AI549Energy Incremental Reactive In Last Complete Interval Reg 3AI550Energy Incremental Real Out Last Complete Interval Reg 1AI551Energy Incremental Real Out Last Complete Interval Reg 2AI552Energy Incremental Real Out Last Complete Interval Reg 3AI553Energy Incremental Reactive Out Last Complete Interval Reg 1AI554Energy Incremental Reactive Out Last Complete Interval Reg 2AI555Energy Incremental Reactive Out Last Complete Interval Reg 3AI556Energy Incremental Apparent Last Complete Interval Reg 1AI557Energy Incremental Apparent Last Complete Interval Reg 2AI558Energy Incremental Apparent Last Complete Interval Reg 3AI559DateTime Last Complete Incremental Energy Interval Reg 1AI560DateTime Last Complete Incremental Energy Interval Reg 2AI561DateTime Last Complete Incremental Energy Interval Reg 3AI562DateTime Last Complete Incremental Energy Interval Reg 4AI563Energy Incremental Real In Present Interval Reg 1AI564Energy Incremental Real In Present Interval Reg 2AI565Energy Incremental Real In Present Interval Reg 3AI566Energy. Incremental Reactive In Present Interval Reg 1AI567Energy. Incremental Reactive In Present Interval Reg 2AI568Energy. Incremental Reactive In Present Interval Reg 3AI569Energy Incremental Real Out Present Interval Reg 1AI570Energy Incremental Real Out Present Interval Reg 2AI571Energy Incremental Real Out Present Interval Reg 3AI572Energy Incremental Reactive Out Present Interval Reg 1AI573Energy Incremental Reactive Out Present Interval Reg 2AI574Energy Incremental Reactive Out Present Interval Reg 3AI575Energy Incremental Apparent Present Interval Reg 1AI576Energy Incremental Apparent Present Interval Reg 2AI577Energy Incremental Apparent Present Interval Reg 3AI578Energy Reactive Quadrant 1 Reg 1AI579Energy Reactive Quadrant 1 Reg 2AI580Energy Reactive Quadrant 1 Reg 3AI581Energy Reactive Quadrant 2 Reg 1AI582Energy Reactive Quadrant 2 Reg 2AI583Energy Reactive Quadrant 2 Reg 3AI584Energy Reactive Quadrant 3 Reg 1AI585Energy Reactive Quadrant 3 Reg 2AI586Energy Reactive Quadrant 3 Reg 3AI587Energy Reactive Quadrant 4 Reg 1AI588Energy Reactive Quadrant 4 Reg 2AI589Energy Reactive Quadrant 4 Reg 3AI590Conditional Energy Control StatusAI591Last Demand Real Power 3- Phase TotalAI592Present Demand Real Power 3- Phase TotalAI593Running Average Demand Real Power 3- Phase TotalAI594Predicted Demand Real Power 3- Phase TotalAI595Peak Demand Real Power 3- Phase TotalAI596Peak Demand DateTime Real Power 3- Phase Total Reg 1AI597Peak Demand DateTime Real Power 3- Phase Total Reg 2AI598Peak Demand DateTime Real Power 3- Phase Total Reg 3AI599Peak Demand DateTime Real Power 3- Phase Total Reg 4AI600Cumulative Demand Real Power 3- Phase TotalAI601Power Factor Average @ Peak Demand Real PowerAI602Power Demand Reactive @ Peak Demand Real PowerAI603Power Demand Apparent @ Peak Demand Real PowerAI604Last Demand Reactive Power 3-Phase TotalAI605Present Demand Reactive Power 3-Phase TotalAI606Running Average DemandAI607Reactive Power 3-Phase TotalAI608Predicted Demand Reactive Power 3-Phase TotalAI609Peak Demand Reactive Power 3-Phase TotalAI610Peak Demand DateTime Reactive Power 3-Phase Total Reg 1AI611Peak Demand DateTime Reactive Power 3-Phase Total Reg 2AI612Peak Demand DateTime Reactive Power 3-Phase Total Reg 3AI613Peak Demand DateTime Reactive Power 3-Phase Total Reg 4AI614Cumulative Demand Reactive Power 3-Phase TotalAI615Power Factor Average @ Peak Demand Reactive PowerAI616Power Demand Real @ Peak Demand Reactive PowerAI617Power Demand Apparent @ Peak Demand Reactive PowerAI618Last Demand Apparent Power 3-Phase TotalAI619Present Demand Apparent Power 3-Phase TotalAI620Running Average Demand Apparent Power 3-Phase TotalAI621Predicted Demand Apparent Power 3-Phase TotalAI622Peak Demand Apparent Power 3-Phase TotalAI623Peak Demand DateTime Apparent Power 3-Phase Total Reg 1AI624Peak Demand DateTime Apparent Power 3-Phase Total Reg 2AI625Peak Demand DateTime Apparent Power 3-Phase Total Reg 3AI626Peak Demand DateTime Apparent Power 3-Phase Total Reg 4AI627Cumulative Demand Apparent Power 3-Phase TotalAI628Power Factor Average @ Peak Demand Apparent PowerAI629Power Demand Real @ Peak Demand Apparent PowerAI630Power Demand Reactive @ Peak Demand Apparent PowerAI631Circuit Monitor Label Reg 1AI632Circuit Monitor Label Reg 2AI633Circuit Monitor Nameplate Reg 1AI634Circuit Monitor Nameplate Reg 2AI635Circuit Monitor Nameplate Reg 3AI636Circuit Monitor Nameplate Reg 4AI637Circuit Monitor Nameplate Reg 5AI638Circuit Monitor Nameplate Reg 6AI639Circuit Monitor Nameplate Reg 7AI640Circuit Monitor Nameplate Reg 8AI641Circuit Monitor Present Operating System Firmware Revision LevelAI642Present Date/Time Reg 1AI643Present Date/Time Reg 2AI644Present Date/Time Reg 3AI645Present Date/Time Reg 4AI646Last Unit Restart Date Time Reg 1AI647Last Unit Restart Date Time Reg 2AI648Last Unit Restart Date Time Reg 3AI649Last Unit Restart Date Time Reg 4AI650Number of Metering System RestartsAI651Number of Control Power FailuresAI652Date/Time of Last Control Power Failure Reg 1AI653Date/Time of Last Control Power Failure Reg 2AI654Date/Time of Last Control Power Failure Reg 3AI655Date/Time of Last Control Power Failure Reg 4BI656Self-Test Results Bit 00 = Is set to 1 if any failure occursBI657Self-Test Results Bit 01 = RTC failureBI658Self-Test Results Bit 02 = MCF UART #1 failureBI659Self-Test Results Bit 03 = MCF UART #2 failureBI660Self-Test Results Bit 04 = PLD UART failureBI661Self-Test Results Bit 05 = Metering Collection overrun failureBI662Self-Test Results Bit 06 = Metering Process 0.1 overrun failureBI663Self-Test Results Bit 07 = Metering Process 1.0 overrun failureBI664Self-Test Results Bit 08 = Disk-on-Chip failureBI665Self-Test Results Bit 09 = Display failureBI666Self-Test Results Bit 10 = CV Module failureBI667Self-Test Results Bit 11 = Aux Plug EEPROM failureBI668Self-Test Results Bit 12 = Flash Memory failureBI669Self-Test Results Bit 13 = Dram Memory failureBI670Self-Test Results Bit 14 = Simtek Memory failureBI671Self-Test Results Bit 15 = RTC Memory failureBI672Self-Test Results Bit 00 = Aux IO failureBI673Self-Test Results Bit 01 = Option Slot A module failureBI674Self-Test Results Bit 02 = Option Slot B module failureBI675Self-Test Results Bit 03 = IOX module failureBI676Self-Test Results Bit 04 = Not usedBI677Self-Test Results Bit 05 = Not usedBI678Self-Test Results Bit 06 = Not usedBI679Self-Test Results Bit 07 = Not usedBI680Self-Test Results Bit 08 = OS Create failureBI681Self-Test Results Bit 09 = OS Queue overrun failureBI682Self-Test Results Bit 10 = Not usedBI683Self-Test Results Bit 11 = Not usedBI684Self-Test Results Bit 12 = Not usedBI685Self-Test Bit 13 = Systems shut down due to continuous resetBI686Self-Test Results Bit 14 = Unit in Download Condition ABI687Self-Test Results Bit 15 = Unit in Download Condition BBI688Configuration Modified Bit 00 = Summary bitBI689Configuration Modified Bit 01 = Metering SystemBI690Configuration Modified Bit 02 = Communications SystemBI691Configuration Modified Bit 03 = Alarm SystemBI692Configuration Modified Bit 04 = File SystemBI693Configuration Modified Bit 05 = Auxiliary IO SystemBI694Configuration Modified Bit 06 = Display SystemAI695Installed Log MemoryAI696Free Log MemoryAI697Log Memory Cluster SizeAI698Programmed Disk On Chip Version NumberAI699Real Time Clock Factory CalibrationAI700Real Time Clock Field CalibrationAI701Installed Log MemoryAI702Installed Option – Slot AAI703Installed Option – Slot BAI704Installed Option – IO ExtenderAI705Present MonthAI706Present DayAI707Present YearAI708Present HourAI709Present MinuteAI710Present SecondAI711Day of Week
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Power_Logic_CM4000_Power_Meter_b_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/PowerLogicCM4000.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 68 of the 711 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Installed Log Memory); they are kept as printed and told apart by instance.
- Energy values are split over four registers each (Reg 1-4) as in the CM4000 map; combine them per the register document.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric PowerLogic CM4000 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
How many BACnet points does the Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX have?
This list has 711 BACnet objects: 664 analog inputs, 47 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Power_Logic_CM4000_Power_Meter_a (Power_Logic_CM4000_Power_Meter_b_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Power_Logic_CM4000_Power_Meter_b_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX?
Start with AI 69 1sec Real Power Total (Real power total (1 s)); AI 52 1sec Voltage L-L Average (Voltage L-L average (1 s)); AI 43 1sec Current 3-Phase Average (Current 3-phase average (1 s)); AI 81 1sec True Power Factor Total (True power factor total (1 s)); AI 94 1sec Frequency (Frequency (1 s)); AI 512 Energy Real Total (signed/absolute) Reg 1 (Real energy total, register 1).
How do I check these points on the real Schneider Electric PowerLogic CM4000 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Power_Logic_CM4000_Power_Meter_a · Power_Logic_CM4000_Power_Meter_b_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.