Variable frequency drive (HVAC) · BACnet points list
Contemporary Controls ABB ACH 400 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the ABB ACH 400 HVAC drive: 270 objects (249 AI, 21 BI), 62 polled by default. It reads the status word bits, output frequency, current, speed, power, DC bus voltage, fault history and the drive parameter groups. Every object is an input, so the profile monitors the drive but cannot command it.
This page lists 270 BACnet objects for the Contemporary Controls ABB ACH 400 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- ABB ACH 400 via BASgatewayLX
- Equipment
- Variable frequency drive (HVAC)
- Equipment type
- VFDs & pumps
- BACnet objects
- 270 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- ABB ACH400, ACH400 drive, ACH 400 Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls ABB ACH 400 via BASgatewayLX
Poll the status bits and actual values for monitoring. The profile has no writable objects, so drive commands need another path (hard-wired I/O or an edited profile).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 20 | OPERATING | Drive running (operating) | Read |
| BI 21 | Drive control location: REMOTE | Control location is remote | Read |
| AI 28 | OUTPUT FREQ | Output frequency | Read |
| AI 27 | SPEED | Motor speed | Read |
| AI 29 | CURRENT | Motor current | Read |
| AI 31 | POWER | Drive output power | Read |
| BI 19 | Alarm is active | Any active alarm | Read |
| BI 15 | FAULT | Drive tripped on a fault | Read |
| AI 50 | LAST FAULT | Most recent fault code | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- The profile is read-only: it has no output objects, so start/stop and speed reference cannot be written through it as published.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls ABB ACH 400 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Enter READY TO OPERATE | Modbus 400001 | Read | ||
| BI | 2 | Continue operation (OFF2 inactive) | Modbus 400001 bit 0 | Read | ||
| BI | 3 | Continue operation (OFF3 inactive) | Modbus 400001 bit 1 | Read | ||
| BI | 4 | Enter OPERATION ENABLED | Modbus 400001 bit 2 | Read | ||
| BI | 5 | Normal operation | Modbus 400001 bit 3 | Read | ||
| BI | 6 | Normal operation. Enter OPERATING | Modbus 400001 bit 5 | Read | ||
| BI | 7 | Fault reset (enter SWITCH-ON INHIBITED) | Modbus 400001 bit 6 | Read | ||
| BI | 8 | Select external control location 2 (EXT2) | Modbus 400001 bit 7 | Read | ||
| BI | 9 | frequency reference REF1 | Modbus 400001 bit 11 | Read | ||
| AI | 10 | frequency reference REF2 | Modbus 400002 | Read | ||
| AI | 11 | Status Word | Modbus 400003 | Read | ||
| AI | 12 | READY TO SWITCH ON | Modbus 400004 | Read | ||
| BI | 13 | READY TO OPERATE | Modbus 400004 bit 0 | Read | ||
| BI | 14 | OPERATION ENABLED | Modbus 400004 bit 1 | Read | ||
| BImin | 15 | FAULT | Modbus 400004 bit 2 | Read | ||
| BI | 16 | OFF2 inactive | Modbus 400004 bit 3 | Read | ||
| BI | 17 | OFF3 inactive | Modbus 400004 bit 4 | Read | ||
| BI | 18 | SWITCH-ON INHIBITED | Modbus 400004 bit 5 | Read | ||
| BImin | 19 | Alarm is active | Modbus 400004 bit 6 | Read | ||
| BImin | 20 | OPERATING | Modbus 400004 bit 7 | Read | ||
| BImin | 21 | Drive control location: REMOTE | Modbus 400004 bit 8 | Read | ||
| BI | 22 | first supervised parameter => supervision limit | Modbus 400004 bit 9 | Read | ||
| BI | 23 | External control location 2 (EXT2) selected | Modbus 400004 bit 10 | Read | ||
| BI | 24 | Run Enable signal received | Modbus 400004 bit 11 | Read | ||
| BI | 25 | Actual output frequency | Modbus 400004 bit 12 | Read | ||
| AI | 26 | Actual output current | Modbus 400005 | Hz | Read | |
| AImin | 27 | SPEED | Modbus 400006 | A | Read | |
| AImin | 28 | OUTPUT FREQ | Modbus 400102 | rpm | Read | |
| AImin | 29 | CURRENT | Modbus 400103 | Hz | Read | |
| AI | 30 | TORQUE | Modbus 400104 | A | Read | |
| AImin | 31 | POWER | Modbus 400105 | % | Read | |
| AI | 32 | DC BUS VOLTAGE | Modbus 400106 | kW | Read | |
| AI | 33 | OUTPUT VOLTAGE | Modbus 400107 | V | Read | |
| AI | 34 | ACH400 TEMP | Modbus 400108 | V | Read | |
| AI | 35 | EXTERNAL REF 1 | Modbus 400109 | °C | Read | |
| AI | 36 | EXTERNAL REF 2 | Modbus 400110 | Hz | Read | |
| AI | 37 | CTRL LOCATION | Modbus 400111 | % | Read | |
| AI | 38 | RUN TIME (R) | Modbus 400112 | Read | ||
| AI | 39 | kWh COUNTER (R) | Modbus 400113 | h | Read | |
| AI | 40 | APPL BLK OUTPUT | Modbus 400114 | kWh | Read | |
| AI | 41 | DI1-DI4 STATUS | Modbus 400115 | % | Read | |
| AI | 42 | AI1 | Modbus 400116 | Read | ||
| AI | 43 | AI2 | Modbus 400117 | % | Read | |
| AI | 44 | DI5 RELAYS | Modbus 400118 | % | Read | |
| AI | 45 | AO | Modbus 400119 | Read | ||
| AI | 46 | ACTUAL VALUE 1 | Modbus 400121 | mA | Read | |
| AI | 47 | ACTUAL VALUE 2 | Modbus 400122 | % | Read | |
| AI | 48 | CONTROL DEV | Modbus 400125 | % | Read | |
| AI | 49 | PID ACT VALUE | Modbus 400126 | % | Read | |
| AImin | 50 | LAST FAULT | Modbus 400127 | % | Read | |
| AI | 51 | PREVIOUS FAULT | Modbus 400128 | Read | ||
| AI | 52 | OLDEST FAULT | Modbus 400129 | Read | ||
| AI | 53 | SER LINK DATA 1 | Modbus 400130 | Read | ||
| AI | 54 | SER LINK DATA 2 | Modbus 400131 | Read | ||
| AI | 55 | SER LINK DATA 3 | Modbus 400132 | Read | ||
| AI | 56 | PROCESS VAR 1 (0 to 65535) | Modbus 400133 | Read | ||
| AI | 57 | PROCESS VAR 1 (-32768 to 32767) | Modbus 400134 | Read | ||
| AI | 58 | PROCESS VAR 2 (0 to 65535) | Modbus 400134 | Read | ||
| AI | 59 | PROCESS VAR 2 (-32768 to 32767) | Modbus 400135 | Read | ||
| AI | 60 | RUN TIME | Modbus 400135 | Read | ||
| AI | 61 | MWh COUNTER | Modbus 400136 | Read | ||
| AI | 62 | EXT1 COMMANDS | Modbus 400137 | MWh | Read | |
| AI | 63 | EXT2 COMMANDS | Modbus 401001; not polled by default | Read | ||
| AI | 64 | DIRECTION | Modbus 401002; not polled by default | Read | ||
| AI | 65 | KEYPAD REF SEL | Modbus 401003; not polled by default | Read | ||
| AI | 66 | EXT1/EXT2 SEL | Modbus 401101; not polled by default | Read | ||
| AI | 67 | EXT REF1 SELECT | Modbus 401102; not polled by default | Read | ||
| AI | 68 | EXT REF1 MIN | Modbus 401103; not polled by default | Read | ||
| AI | 69 | EXT REF1 MAX | Modbus 401104; not polled by default | Hz | Read | |
| AI | 70 | EXT REF2 SELECT | Modbus 401105; not polled by default | Hz | Read | |
| AI | 71 | EXT REF2 MIN | Modbus 401106; not polled by default | Read | ||
| AI | 72 | EXT REF2 MAX | Modbus 401107; not polled by default | % | Read | |
| AI | 73 | CONST SPEED SEL | Modbus 401108; not polled by default | % | Read | |
| AI | 74 | CONST SPEED 1 | Modbus 401201; not polled by default | Read | ||
| AI | 75 | CONST SPEED 2 | Modbus 401202; not polled by default | Hz | Read | |
| AI | 76 | CONST SPEED 3 | Modbus 401203; not polled by default | Hz | Read | |
| AI | 77 | CONST SPEED 4 | Modbus 401204; not polled by default | Hz | Read | |
| AI | 78 | CONST SPEED 5 | Modbus 401205; not polled by default | Hz | Read | |
| AI | 79 | CONST SPEED 6 | Modbus 401206; not polled by default | Hz | Read | |
| AI | 80 | CONST SPEED 7 | Modbus 401207; not polled by default | Hz | Read | |
| AI | 81 | MINIMUM AI1 | Modbus 401208; not polled by default | Hz | Read | |
| AI | 82 | MAXIMUM AI1 | Modbus 401301; not polled by default | % | Read | |
| AI | 83 | FILTER AI1 | Modbus 401302; not polled by default | % | Read | |
| AI | 84 | MINIMUM AI2 | Modbus 401303; not polled by default | s | Read | |
| AI | 85 | MAXIMUM AI2 | Modbus 401304; not polled by default | % | Read | |
| AI | 86 | FILTER AI2 | Modbus 401305; not polled by default | % | Read | |
| AI | 87 | RELAY OUTPUT 1 | Modbus 401306; not polled by default | s | Read | |
| AI | 88 | RELAY OUTPUT 2 | Modbus 401401; not polled by default | Read | ||
| AI | 89 | RELAY 1 ON DELAY ( 1 sec) | Modbus 401402; not polled by default | Read | ||
| AI | 90 | RELAY 1 ON DELAY ( .1 sec) | Modbus 401403; not polled by default | s | Read | |
| AI | 91 | RELAY 1 OFF DELAY ( 1 sec) | Modbus 401403; not polled by default | s | Read | |
| AI | 92 | RELAY 1 OFF DELAY ( .1 sec) | Modbus 401404; not polled by default | s | Read | |
| AI | 93 | RELAY 2 ON DELAY ( 1 sec) | Modbus 401404; not polled by default | s | Read | |
| AI | 94 | RELAY 2 ON DELAY ( .1 sec) | Modbus 401405; not polled by default | s | Read | |
| AI | 95 | RELAY 2 OFF DELAY ( 1 sec) | Modbus 401405; not polled by default | s | Read | |
| AI | 96 | RELAY 2 OFF DELAY ( .1 sec) | Modbus 401406; not polled by default | s | Read | |
| AI | 97 | AO CONTENT | Modbus 401406; not polled by default | s | Read | |
| AI | 98 | AO CONTENT MIN | Modbus 401501; not polled by default | Read | ||
| AI | 99 | AO CONTENT MAX | Modbus 401502; not polled by default | Read | ||
| AI | 100 | MINIMUM AO | Modbus 401503; not polled by default | Read | ||
| AI | 101 | MAXIMUM AO | Modbus 401504; not polled by default | mA | Read | |
| AI | 102 | FILTER AO | Modbus 401505; not polled by default | mA | Read | |
| AI | 103 | RUN ENABLE | Modbus 401506; not polled by default | s | Read | |
| AI | 104 | PARAMETER LOCK | Modbus 401601; not polled by default | Read | ||
| AI | 105 | FAULT RESET SEL | Modbus 401602; not polled by default | Read | ||
| AI | 106 | LOCAL LOCK | Modbus 401604; not polled by default | Read | ||
| AI | 107 | PARAM. SAVE | Modbus 401605; not polled by default | Read | ||
| AI | 108 | MAX CURRENT | Modbus 401607; not polled by default | Read | ||
| AI | 109 | OVERVOLT CTRL | Modbus 402003; not polled by default | A | Read | |
| AI | 110 | UNDERVOLT CTRL | Modbus 402005; not polled by default | Read | ||
| AI | 111 | MINIMUM FREQ | Modbus 402006; not polled by default | Read | ||
| AI | 112 | MAXIMUM FREQ | Modbus 402007; not polled by default | Hz | Read | |
| AI | 113 | START FUNCTION | Modbus 402008; not polled by default | Hz | Read | |
| AI | 114 | STOP FUNCTION | Modbus 402101; not polled by default | Read | ||
| AI | 115 | TORQ BOOST CURR | Modbus 402102; not polled by default | Read | ||
| AI | 116 | STOP DC INJ TIME | Modbus 402103; not polled by default | Read | ||
| AI | 117 | PREMAGN SEL | Modbus 402104; not polled by default | s | Read | |
| AI | 118 | PREMAGN MAX TIME | Modbus 402105; not polled by default | Read | ||
| AI | 119 | START INHIBIT | Modbus 402106; not polled by default | Read | ||
| AI | 120 | ACC/DEC 1/2 SEL | Modbus 402107; not polled by default | Read | ||
| AI | 121 | ACCEL TIME 1 ( 1 Sec ) | Modbus 402201; not polled by default | Read | ||
| AI | 122 | ACCEL TIME 1 ( .1 Sec ) | Modbus 402202; not polled by default | s | Read | |
| AI | 123 | DECEL TIME 1 ( 1 Sec) | Modbus 402202; not polled by default | s | Read | |
| AI | 124 | DECEL TIME 1 ( .1 Sec) | Modbus 402203; not polled by default | s | Read | |
| AI | 125 | ACCEL TIME 2 ( 1 Sec ) | Modbus 402203; not polled by default | s | Read | |
| AI | 126 | ACCEL TIME 2 ( .1 Sec ) | Modbus 402204; not polled by default | s | Read | |
| AI | 127 | DECEL TIME 2 ( 1 Sec) | Modbus 402204; not polled by default | s | Read | |
| AI | 128 | DECEL TIME 2 ( .1 Sec) | Modbus 402205; not polled by default | s | Read | |
| AI | 129 | RAMP SHAPE | Modbus 402205; not polled by default | s | Read | |
| AI | 130 | CRIT FREQ SEL | Modbus 402206; not polled by default | Read | ||
| AI | 131 | CRIT FREQ 1 LO | Modbus 402501; not polled by default | Read | ||
| AI | 132 | CRIT FREQ 1 HI | Modbus 402502; not polled by default | Hz | Read | |
| AI | 133 | CRIT FREQ 2 LO | Modbus 402503; not polled by default | Hz | Read | |
| AI | 134 | CRIT FREQ 2 HI | Modbus 402504; not polled by default | Hz | Read | |
| AI | 135 | IR COMPENSATION | Modbus 402505; not polled by default | Hz | Read | |
| AI | 136 | IR COMP RANGE | Modbus 402603; not polled by default | V | Read | |
| AI | 137 | LOW NOISE | Modbus 402604; not polled by default | Hz | Read | |
| AI | 138 | U/f RATIO | Modbus 402605; not polled by default | Read | ||
| AI | 139 | SLIP COMP RATIO | Modbus 402606; not polled by default | Read | ||
| AI | 140 | AI<MIN FUNCTION | Modbus 402607; not polled by default | % | Read | |
| AI | 141 | PANEL LOSS | Modbus 403001; not polled by default | Read | ||
| AI | 142 | EXTERNAL FAULT | Modbus 403002; not polled by default | Read | ||
| AI | 143 | MOT THERM PROT | Modbus 403003; not polled by default | Read | ||
| AI | 144 | MOT THERM TIME | Modbus 403004; not polled by default | Read | ||
| AI | 145 | MOT LOAD CURVE | Modbus 403005; not polled by default | s | Read | |
| AI | 146 | ZERO SPEED LOAD | Modbus 403006; not polled by default | % | Read | |
| AI | 147 | BREAK POINT | Modbus 403007; not polled by default | % | Read | |
| AI | 148 | STALL FUNCTION | Modbus 403008; not polled by default | Hz | Read | |
| AI | 149 | STALL CURRENT | Modbus 403009; not polled by default | Read | ||
| AI | 150 | STALL FREQ HI | Modbus 403010; not polled by default | A | Read | |
| AI | 151 | STALL TIME | Modbus 403011; not polled by default | Hz | Read | |
| AI | 152 | UNDERLOAD FUNC | Modbus 403012; not polled by default | s | Read | |
| AI | 153 | UNDERLOAD TIME | Modbus 403013; not polled by default | Read | ||
| AI | 154 | UNDERLOAD CURVE | Modbus 403014; not polled by default | s | Read | |
| AI | 155 | MOTOR PHASE LOSS | Modbus 403015; not polled by default | Read | ||
| AI | 156 | GROUND FAULT | Modbus 403016; not polled by default | Read | ||
| AI | 157 | NR OF TRIALS | Modbus 403017; not polled by default | Read | ||
| AI | 158 | TRIAL TIME | Modbus 403101; not polled by default | Read | ||
| AI | 159 | DELAY TIME | Modbus 403102; not polled by default | s | Read | |
| AI | 160 | AR OVERCURRENT | Modbus 403103; not polled by default | s | Read | |
| AI | 161 | AR OVERVOLTAGE | Modbus 403104; not polled by default | Read | ||
| AI | 162 | AR UNDERVOLTAGE | Modbus 403105; not polled by default | Read | ||
| AI | 163 | AR AI<MIN | Modbus 403106; not polled by default | Read | ||
| AI | 164 | SUPERV 1 PARAM | Modbus 403107; not polled by default | Read | ||
| AI | 165 | SUPERV 1 LIM LO | Modbus 403201; not polled by default | Read | ||
| AI | 166 | SUPERV 1 LIM HI | Modbus 403202; not polled by default | Read | ||
| AI | 167 | SUPERV 2 PARAM | Modbus 403203; not polled by default | Read | ||
| AI | 168 | SUPERV 2 LIM LO | Modbus 403204; not polled by default | Read | ||
| AI | 169 | SUPERV 2 LIM HI | Modbus 403205; not polled by default | Read | ||
| AI | 170 | SW VERSION | Modbus 403206; not polled by default | Read | ||
| AI | 171 | TEST DATE | Modbus 403301; not polled by default | Read | ||
| AI | 172 | DISPLAY SEL | Modbus 403302; not polled by default | Read | ||
| AI | 173 | P VAR 1 SEL | Modbus 403401; not polled by default | Read | ||
| AI | 174 | P VAR 1 MULTIP | Modbus 403402; not polled by default | Read | ||
| AI | 175 | P VAR 1 DIVISOR | Modbus 403403; not polled by default | Read | ||
| AI | 176 | P VAR 1 SCALING | Modbus 403404; not polled by default | Read | ||
| AI | 177 | P VAR 1 UNIT | Modbus 403405; not polled by default | Read | ||
| AI | 178 | P VAR 2 SEL | Modbus 403406; not polled by default | A | Read | |
| AI | 179 | P VAR 2 MULTIP | Modbus 403407; not polled by default | Read | ||
| AI | 180 | P VAR 2 DIVISOR | Modbus 403408; not polled by default | Read | ||
| AI | 181 | P VAR 2 SCALING | Modbus 403409; not polled by default | Read | ||
| AI | 182 | P VAR 2 UNIT | Modbus 403410; not polled by default | Read | ||
| AI | 183 | PID GAIN | Modbus 403411; not polled by default | Hz | Read | |
| AI | 184 | PID INTEG TIME | Modbus 404001; not polled by default | Read | ||
| AI | 185 | PID DERIV TIME | Modbus 404002; not polled by default | s | Read | |
| AI | 186 | PID DERIV FILTER | Modbus 404003; not polled by default | s | Read | |
| AI | 187 | ERROR VALUE INV | Modbus 404004; not polled by default | s | Read | |
| AI | 188 | ACTUAL VAL SEL | Modbus 404005; not polled by default | Read | ||
| AI | 189 | ACT1 INPUT SEL | Modbus 404006; not polled by default | Read | ||
| AI | 190 | ACT2 INPUT SEL | Modbus 404007; not polled by default | Read | ||
| AI | 191 | ACT1 MINIMUM | Modbus 404008; not polled by default | Read | ||
| AI | 192 | ACT1 MAXIMUM | Modbus 404009; not polled by default | % | Read | |
| AI | 193 | ACT2 MINIMUM | Modbus 404010; not polled by default | % | Read | |
| AI | 194 | ACT2 MAXIMUM | Modbus 404011; not polled by default | % | Read | |
| AI | 195 | PID SLEEP DELAY (1 Sec) | Modbus 404012; not polled by default | % | Read | |
| AI | 196 | PID SLEEP DELAY (.1 Sec ) | Modbus 404013; not polled by default | s | Read | |
| AI | 197 | PID SLEEP LEVEL | Modbus 404013; not polled by default | Read | ||
| AI | 198 | WAKE-UP LEVEL | Modbus 404014; not polled by default | Hz | Read | |
| AI | 199 | PID PARAM SET | Modbus 404015; not polled by default | % | Read | |
| AI | 200 | WAKE-UP DELAY | Modbus 404016; not polled by default | Read | ||
| AI | 201 | SLEEP SELECTION | Modbus 404017; not polled by default | s | Read | |
| AI | 202 | SET POINT SEL | Modbus 404018; not polled by default | Read | ||
| AI | 203 | INTERNAL SETPNT | Modbus 404019; not polled by default | Read | ||
| AI | 204 | PID GAIN | Modbus 404020; not polled by default | % | Read | |
| AI | 205 | PID INTEG TIME | Modbus 404101; not polled by default | Read | ||
| AI | 206 | PID DERIV TIME | Modbus 404102; not polled by default | s | Read | |
| AI | 207 | PID DERIV FILTER | Modbus 404103; not polled by default | s | Read | |
| AI | 208 | ERROR VALUE INV | Modbus 404104; not polled by default | s | Read | |
| AI | 209 | ACTUAL VAL SEL | Modbus 404105; not polled by default | Read | ||
| AI | 210 | ACT1 INPUT SEL | Modbus 404106; not polled by default | Read | ||
| AI | 211 | ACT2 INPUT SEL | Modbus 404107; not polled by default | Read | ||
| AI | 212 | ACT1 MINIMUM | Modbus 404108; not polled by default | Read | ||
| AI | 213 | ACT1 MAXIMUM | Modbus 404109; not polled by default | % | Read | |
| AI | 214 | ACT2 MINIMUM | Modbus 404110; not polled by default | % | Read | |
| AI | 215 | ACT2 MAXIMUM | Modbus 404111; not polled by default | % | Read | |
| AI | 216 | SET POINT SEL | Modbus 404112; not polled by default | % | Read | |
| AI | 217 | INTERNAL SETPNT | Modbus 404119; not polled by default | Read | ||
| AI | 218 | DDCS BIT RATE | Modbus 404120; not polled by default | % | Read | |
| AI | 219 | DDCS NODE NR | Modbus 405001; not polled by default | Read | ||
| AI | 220 | COMM FAULT TIME | Modbus 405002; not polled by default | Read | ||
| AI | 221 | COMM FAULT FUNC | Modbus 405003; not polled by default | s | Read | |
| AI | 222 | PROTOCOL SEL | Modbus 405004; not polled by default | Read | ||
| AI | 223 | COMM COMMANDS | Modbus 405005; not polled by default | Read | ||
| AI | 224 | FIELDBUSPAR 01 | Modbus 405006; not polled by default | Read | ||
| AI | 225 | FIELDBUSPAR 02 | Modbus 405101; not polled by default | Read | ||
| AI | 226 | FIELDBUSPAR 03 | Modbus 405102; not polled by default | Read | ||
| AI | 227 | FIELDBUSPAR 04 | Modbus 405103; not polled by default | Read | ||
| AI | 228 | FIELDBUSPAR 05 | Modbus 405104; not polled by default | Read | ||
| AI | 229 | FIELDBUSPAR 06 | Modbus 405105; not polled by default | Read | ||
| AI | 230 | FIELDBUSPAR 07 | Modbus 405106; not polled by default | Read | ||
| AI | 231 | FIELDBUSPAR 08 | Modbus 405107; not polled by default | Read | ||
| AI | 232 | FIELDBUSPAR 09 | Modbus 405108; not polled by default | Read | ||
| AI | 233 | FIELDBUSPAR 10 | Modbus 405109; not polled by default | Read | ||
| AI | 234 | FIELDBUSPAR 11 | Modbus 405110; not polled by default | Read | ||
| AI | 235 | FIELDBUSPAR 12 | Modbus 405111; not polled by default | Read | ||
| AI | 236 | FIELDBUSPAR 13 | Modbus 405112; not polled by default | Read | ||
| AI | 237 | FIELDBUSPAR 14 | Modbus 405113; not polled by default | Read | ||
| AI | 238 | FIELDBUSPAR 15 | Modbus 405114; not polled by default | Read | ||
| AI | 239 | STATION NUMBER | Modbus 405115; not polled by default | Read | ||
| AI | 240 | COMM SPEED | Modbus 405201; not polled by default | Read | ||
| AI | 241 | PARITY | Modbus 405202; not polled by default | Read | ||
| AI | 242 | REFERENCE STEP 1 | Modbus 405203; not polled by default | Read | ||
| AI | 243 | REFERENCE STEP 2 | Modbus 408103; not polled by default | % | Read | |
| AI | 244 | REFERENCE STEP 3 | Modbus 408104; not polled by default | % | Read | |
| AI | 245 | START FREQ 1 | Modbus 408105; not polled by default | % | Read | |
| AI | 246 | START FREQ 2 | Modbus 408109; not polled by default | Hz | Read | |
| AI | 247 | START FREQ 3 | Modbus 408110; not polled by default | Hz | Read | |
| AI | 248 | LOW FREQ 1 | Modbus 408111; not polled by default | Hz | Read | |
| AI | 249 | LOW FREQ 2 | Modbus 408112; not polled by default | Hz | Read | |
| AI | 250 | LOW FREQ 3 | Modbus 408113; not polled by default | Hz | Read | |
| AI | 251 | AUX MOT START D ( 1 Sec ) | Modbus 408114; not polled by default | Hz | Read | |
| AI | 252 | AUX MOT START D ( .1 Sec ) | Modbus 408115; not polled by default | s | Read | |
| AI | 253 | AUX MOT STOP D. ( 1 Sec) | Modbus 408115; not polled by default | s | Read | |
| AI | 254 | AUX MOT STOP D. ( .1 Sec) | Modbus 408116; not polled by default | s | Read | |
| AI | 255 | NR OF AUX MOT | Modbus 408116; not polled by default | s | Read | |
| AI | 256 | AUTOCHNG INTERV | Modbus 408117; not polled by default | Read | ||
| AI | 257 | AUTOCHNG LEVEL | Modbus 408118; not polled by default | h | Read | |
| AI | 258 | INTERLOCKS | Modbus 408119; not polled by default | % | Read | |
| AI | 259 | REG BYPASS CTRL | Modbus 408120; not polled by default | Read | ||
| AI | 260 | PFC START DELAY | Modbus 408121; not polled by default | Read | ||
| AI | 261 | LANGUAGE | Modbus 408122; not polled by default | s | Read | |
| AI | 262 | APPLIC MACRO | Modbus 409901; not polled by default | Read | ||
| AI | 263 | MOTOR CONTROL MODE | Modbus 409902; not polled by default | Read | ||
| AI | 264 | MOTOR NOM VOLT | Modbus 409904; not polled by default | Read | ||
| AI | 265 | MOTOR NOM CURR | Modbus 409905; not polled by default | V | Read | |
| AI | 266 | MOTOR NOM FREQ | Modbus 409906; not polled by default | A | Read | |
| AI | 267 | MOTOR NOM SPEED | Modbus 409907; not polled by default | Hz | Read | |
| AI | 268 | MOTOR NOM POWER | Modbus 409908; not polled by default | rpm | Read | |
| AI | 269 | MOTOR COS PHI | Modbus 409909; not polled by default | kW | Read | |
| AI | 270 | MOTOR COS PHI | Modbus 409910; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX ABB ACH 400 point IDs by name
AI1Enter READY TO OPERATEBI2Continue operation (OFF2 inactive)BI3Continue operation (OFF3 inactive)BI4Enter OPERATION ENABLEDBI5Normal operationBI6Normal operation. Enter OPERATINGBI7Fault reset (enter SWITCH-ON INHIBITED)BI8Select external control location 2 (EXT2)BI9frequency reference REF1AI10frequency reference REF2AI11Status WordAI12READY TO SWITCH ONBI13READY TO OPERATEBI14OPERATION ENABLEDBI15FAULTBI16OFF2 inactiveBI17OFF3 inactiveBI18SWITCH-ON INHIBITEDBI19Alarm is activeBI20OPERATINGBI21Drive control location: REMOTEBI22first supervised parameter => supervision limitBI23External control location 2 (EXT2) selectedBI24Run Enable signal receivedBI25Actual output frequencyAI26Actual output currentAI27SPEEDAI28OUTPUT FREQAI29CURRENTAI30TORQUEAI31POWERAI32DC BUS VOLTAGEAI33OUTPUT VOLTAGEAI34ACH400 TEMPAI35EXTERNAL REF 1AI36EXTERNAL REF 2AI37CTRL LOCATIONAI38RUN TIME (R)AI39kWh COUNTER (R)AI40APPL BLK OUTPUTAI41DI1-DI4 STATUSAI42AI1AI43AI2AI44DI5 RELAYSAI45AOAI46ACTUAL VALUE 1AI47ACTUAL VALUE 2AI48CONTROL DEVAI49PID ACT VALUEAI50LAST FAULTAI51PREVIOUS FAULTAI52OLDEST FAULTAI53SER LINK DATA 1AI54SER LINK DATA 2AI55SER LINK DATA 3AI56PROCESS VAR 1 (0 to 65535)AI57PROCESS VAR 1 (-32768 to 32767)AI58PROCESS VAR 2 (0 to 65535)AI59PROCESS VAR 2 (-32768 to 32767)AI60RUN TIMEAI61MWh COUNTERAI62EXT1 COMMANDSAI63EXT2 COMMANDSAI64DIRECTIONAI65KEYPAD REF SELAI66EXT1/EXT2 SELAI67EXT REF1 SELECTAI68EXT REF1 MINAI69EXT REF1 MAXAI70EXT REF2 SELECTAI71EXT REF2 MINAI72EXT REF2 MAXAI73CONST SPEED SELAI74CONST SPEED 1AI75CONST SPEED 2AI76CONST SPEED 3AI77CONST SPEED 4AI78CONST SPEED 5AI79CONST SPEED 6AI80CONST SPEED 7AI81MINIMUM AI1AI82MAXIMUM AI1AI83FILTER AI1AI84MINIMUM AI2AI85MAXIMUM AI2AI86FILTER AI2AI87RELAY OUTPUT 1AI88RELAY OUTPUT 2AI89RELAY 1 ON DELAY ( 1 sec)AI90RELAY 1 ON DELAY ( .1 sec)AI91RELAY 1 OFF DELAY ( 1 sec)AI92RELAY 1 OFF DELAY ( .1 sec)AI93RELAY 2 ON DELAY ( 1 sec)AI94RELAY 2 ON DELAY ( .1 sec)AI95RELAY 2 OFF DELAY ( 1 sec)AI96RELAY 2 OFF DELAY ( .1 sec)AI97AO CONTENTAI98AO CONTENT MINAI99AO CONTENT MAXAI100MINIMUM AOAI101MAXIMUM AOAI102FILTER AOAI103RUN ENABLEAI104PARAMETER LOCKAI105FAULT RESET SELAI106LOCAL LOCKAI107PARAM. SAVEAI108MAX CURRENTAI109OVERVOLT CTRLAI110UNDERVOLT CTRLAI111MINIMUM FREQAI112MAXIMUM FREQAI113START FUNCTIONAI114STOP FUNCTIONAI115TORQ BOOST CURRAI116STOP DC INJ TIMEAI117PREMAGN SELAI118PREMAGN MAX TIMEAI119START INHIBITAI120ACC/DEC 1/2 SELAI121ACCEL TIME 1 ( 1 Sec )AI122ACCEL TIME 1 ( .1 Sec )AI123DECEL TIME 1 ( 1 Sec)AI124DECEL TIME 1 ( .1 Sec)AI125ACCEL TIME 2 ( 1 Sec )AI126ACCEL TIME 2 ( .1 Sec )AI127DECEL TIME 2 ( 1 Sec)AI128DECEL TIME 2 ( .1 Sec)AI129RAMP SHAPEAI130CRIT FREQ SELAI131CRIT FREQ 1 LOAI132CRIT FREQ 1 HIAI133CRIT FREQ 2 LOAI134CRIT FREQ 2 HIAI135IR COMPENSATIONAI136IR COMP RANGEAI137LOW NOISEAI138U/f RATIOAI139SLIP COMP RATIOAI140AI<MIN FUNCTIONAI141PANEL LOSSAI142EXTERNAL FAULTAI143MOT THERM PROTAI144MOT THERM TIMEAI145MOT LOAD CURVEAI146ZERO SPEED LOADAI147BREAK POINTAI148STALL FUNCTIONAI149STALL CURRENTAI150STALL FREQ HIAI151STALL TIMEAI152UNDERLOAD FUNCAI153UNDERLOAD TIMEAI154UNDERLOAD CURVEAI155MOTOR PHASE LOSSAI156GROUND FAULTAI157NR OF TRIALSAI158TRIAL TIMEAI159DELAY TIMEAI160AR OVERCURRENTAI161AR OVERVOLTAGEAI162AR UNDERVOLTAGEAI163AR AI<MINAI164SUPERV 1 PARAMAI165SUPERV 1 LIM LOAI166SUPERV 1 LIM HIAI167SUPERV 2 PARAMAI168SUPERV 2 LIM LOAI169SUPERV 2 LIM HIAI170SW VERSIONAI171TEST DATEAI172DISPLAY SELAI173P VAR 1 SELAI174P VAR 1 MULTIPAI175P VAR 1 DIVISORAI176P VAR 1 SCALINGAI177P VAR 1 UNITAI178P VAR 2 SELAI179P VAR 2 MULTIPAI180P VAR 2 DIVISORAI181P VAR 2 SCALINGAI182P VAR 2 UNITAI183PID GAINAI184PID INTEG TIMEAI185PID DERIV TIMEAI186PID DERIV FILTERAI187ERROR VALUE INVAI188ACTUAL VAL SELAI189ACT1 INPUT SELAI190ACT2 INPUT SELAI191ACT1 MINIMUMAI192ACT1 MAXIMUMAI193ACT2 MINIMUMAI194ACT2 MAXIMUMAI195PID SLEEP DELAY (1 Sec)AI196PID SLEEP DELAY (.1 Sec )AI197PID SLEEP LEVELAI198WAKE-UP LEVELAI199PID PARAM SETAI200WAKE-UP DELAYAI201SLEEP SELECTIONAI202SET POINT SELAI203INTERNAL SETPNTAI204PID GAINAI205PID INTEG TIMEAI206PID DERIV TIMEAI207PID DERIV FILTERAI208ERROR VALUE INVAI209ACTUAL VAL SELAI210ACT1 INPUT SELAI211ACT2 INPUT SELAI212ACT1 MINIMUMAI213ACT1 MAXIMUMAI214ACT2 MINIMUMAI215ACT2 MAXIMUMAI216SET POINT SELAI217INTERNAL SETPNTAI218DDCS BIT RATEAI219DDCS NODE NRAI220COMM FAULT TIMEAI221COMM FAULT FUNCAI222PROTOCOL SELAI223COMM COMMANDSAI224FIELDBUSPAR 01AI225FIELDBUSPAR 02AI226FIELDBUSPAR 03AI227FIELDBUSPAR 04AI228FIELDBUSPAR 05AI229FIELDBUSPAR 06AI230FIELDBUSPAR 07AI231FIELDBUSPAR 08AI232FIELDBUSPAR 09AI233FIELDBUSPAR 10AI234FIELDBUSPAR 11AI235FIELDBUSPAR 12AI236FIELDBUSPAR 13AI237FIELDBUSPAR 14AI238FIELDBUSPAR 15AI239STATION NUMBERAI240COMM SPEEDAI241PARITYAI242REFERENCE STEP 1AI243REFERENCE STEP 2AI244REFERENCE STEP 3AI245START FREQ 1AI246START FREQ 2AI247START FREQ 3AI248LOW FREQ 1AI249LOW FREQ 2AI250LOW FREQ 3AI251AUX MOT START D ( 1 Sec )AI252AUX MOT START D ( .1 Sec )AI253AUX MOT STOP D. ( 1 Sec)AI254AUX MOT STOP D. ( .1 Sec)AI255NR OF AUX MOTAI256AUTOCHNG INTERVAI257AUTOCHNG LEVELAI258INTERLOCKSAI259REG BYPASS CTRLAI260PFC START DELAYAI261LANGUAGEAI262APPLIC MACROAI263MOTOR CONTROL MODEAI264MOTOR NOM VOLTAI265MOTOR NOM CURRAI266MOTOR NOM FREQAI267MOTOR NOM SPEEDAI268MOTOR NOM POWERAI269MOTOR COS PHIAI270MOTOR COS PHI
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile ABB_ACH_400_Drive_a_LX.CSV; the profile maps the registers in the ACH 400 user's manual Modbus section (https://www.ccontrols.com/support/dp/ACH402_US_04_Web.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 62 of the 270 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (PID GAIN; PID INTEG TIME; PID DERIV TIME...); they are kept as printed and told apart by instance.
- The engineering units in this profile look shifted by one row from about AI 26 on (e.g. SPEED shows amperes, OUTPUT FREQ shows rpm); they are kept as printed, so check units against the ACH 400 manual before trending.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ABB ACH 400 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls ABB ACH 400 via BASgatewayLX
How many BACnet points does the Contemporary Controls ABB ACH 400 via BASgatewayLX have?
This list has 270 BACnet objects: 249 analog inputs, 21 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls ABB ACH 400 via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls ABB ACH 400 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile ABB_ACH_400_Drive_a (ABB_ACH_400_Drive_a_LX.CSV), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/ABB_ACH_400_Drive_a_LX.CSV.
What are the minimum BACnet points to integrate the Contemporary Controls ABB ACH 400 via BASgatewayLX?
Start with BI 20 OPERATING (Drive running (operating)); BI 21 Drive control location: REMOTE (Control location is remote); AI 28 OUTPUT FREQ (Output frequency); AI 27 SPEED (Motor speed); AI 29 CURRENT (Motor current); AI 31 POWER (Drive output power); BI 19 Alarm is active (Any active alarm); BI 15 FAULT (Drive tripped on a fault); AI 50 LAST FAULT (Most recent fault code).
How do I check these points on the real ABB ACH 400 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile ABB_ACH_400_Drive_a · ABB_ACH_400_Drive_a_LX.CSV. Object names, instances and units are reproduced as published; descriptions are our own.