Easy BACnet
  1. Home
  2. BACnet points lists
  3. Contemporary Controls
  4. Schneider Electric PowerLogic PM200 via BASgatewayLX

Power and energy meter · BACnet points list

Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the PowerLogic PM200: 58 objects (39 AI, 12 AO, 7 BI), all polled. Inputs give real, apparent and reactive energy and power, PF, frequency, present and max demand, phase currents and voltages, scale factors, range flags and firmware; outputs hold the demand intervals, CT/PT ratios, system type, units and reset.

This page lists 58 BACnet objects for the Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Schneider Electric PowerLogic PM200 via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
58 (12 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
PM200, PM210, PowerLogic PM200, Square D PM200
Source document
BASgatewayLX Modbus device profile Scheider_Power_Meter_PM200_a · Scheider_Power_Meter_PM200_a_LX.csv
Download CSV 58 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX

Integration in brief

Map total real power, real energy consumption and voltage A-B first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 4Total Real PowerTotal real powerRead
AI 1Real Energy ConsumptionReal energy consumptionRead
AI 24Voltage Phase A-BVoltage A-BRead
AI 15Current Instantaneous Phase ACurrent ARead
AI 7Total Power FactorTotal power factorRead
AI 8Frequency (derived from Phase A)FrequencyRead
AI 9Total Real Power Present DemandReal power present demandRead

Network setup

Watch out for

Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

58 of 58 shown
Type
Binary
Access
Show
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Real Energy ConsumptionModbus 404000kWhRead
AI2Apparent Energy ConsumptionModbus 404002Read
AI3Reactive Energy ConsumptionModbus 404004Read
AImin4Total Real PowerModbus 404006kWRead
AI5Total Apparent PowerModbus 404007kVARead
AI6Total Reactive PowerModbus 404008kVARRead
AImin7Total Power FactorModbus 404009Read
AImin8Frequency (derived from Phase A)Modbus 404013HzRead
AImin9Total Real Power Present DemandModbus 404014kWRead
AI10Total Apparent Power Present DemandModbus 404015kVARead
AI11Total Reactive Power Present DemandModbus 404016kVARRead
AI12Total Real Power Max DemandModbus 404017kWRead
AI13Total Apparent Power Max DemandModbus 404018kVARead
AI14Total Reactive Power Max DemandModbus 404019kVARRead
AImin15Current Instantaneous Phase AModbus 404020ARead
AI16Current Instantaneous Phase BModbus 404021ARead
AI17Current Instantaneous Phase CModbus 404022ARead
AI18Current Present Demand Phase AModbus 404024ARead
AI19Current Present Demand Phase BModbus 404025ARead
AI20Current Present Demand Phase CModbus 404026ARead
AI21Current Max Demand Phase AModbus 404027ARead
AI22Current Max Demand Phase BModbus 404028ARead
AI23Current Max Demand Phase CModbus 404029ARead
AImin24Voltage Phase A-BModbus 404030VRead
AI25Voltage Phase B-CModbus 404031VRead
AI26Voltage Phase A-CModbus 404032VRead
AI27Voltage Phase A-NModbus 404033VRead
AI28Voltage Phase B-NModbus 404034VRead
AI29Voltage Phase C-NModbus 404035VRead
AI30Scale Factor I (current)Modbus 404105Read
AI31Scale Factor V (voltage)Modbus 404106Read
AI32Scale Factor W (power)Modbus 404107Read
AI33Scale Factor E (energy)Modbus 404108Read
BI34bit 0: Phase A Voltage over rangeModbus 404112 bit 0Read
BI35bit 1: Phase B Voltage over rangeModbus 404112 bit 1Read
BI36bit 2: Phase C Voltage over rangeModbus 404112 bit 2Read
BI37bit 3: Phase A Current over rangeModbus 404112 bit 3Read
BI38bit 4: Phase B Current over rangeModbus 404112 bit 4Read
BI39bit 5: Phase C Current over rangeModbus 404112 bit 5Read
BI40bit 6: Frequency out of rangeModbus 404112 bit 6Read
AO41Thermal Demand IntervalModbus 404117minCommand
AO42Power Block Demand IntervalModbus 404118minCommand
AO43Power Block Demand Sub-IntervalsModbus 404119Command
AO44CT Ratio – PrimaryModbus 404120Command
AO45CT Ratio - SecondaryModbus 404121Command
AO46PT Ratio - PrimaryModbus 404122Command
AO47PT Ratio - Scale (0 = No PT)Modbus 404123Command
AO48PT Ratio – SecondaryModbus 404124Command
AO49Service FrequencyModbus 404125HzCommand
AO50ResetModbus 404126Command
AO51System TypeModbus 404127Command
AO52Units: 0 = IEC 1 = IEEE unitsModbus 404128Command
AI53Firmware Version Reset SystemModbus 407000Read
AI54Firmware Version Operating SystemModbus 407001Read
AI55Serial Number (date/time of mfg. in UTC)Modbus 407002Read
AI56Device ID = 15201Modbus 407004Read
AI57Modbus AddressModbus 407005Read
AI58Baud rateModbus 407006Read
Object ID lookup: Contemporary Controls BASgatewayLX PowerLogic PM200 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric PowerLogic PM200 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX

How many BACnet points does the Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX have?

This list has 58 BACnet objects: 39 analog inputs, 12 analog outputs, 7 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX BACnet points are writable?

12 of the 58 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Scheider_Power_Meter_PM200_a (Scheider_Power_Meter_PM200_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Schneider%20Electric%20PM200.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX?

Start with AI 4 Total Real Power (Total real power); AI 1 Real Energy Consumption (Real energy consumption); AI 24 Voltage Phase A-B (Voltage A-B); AI 15 Current Instantaneous Phase A (Current A); AI 7 Total Power Factor (Total power factor); AI 8 Frequency (derived from Phase A) (Frequency); AI 9 Total Real Power Present Demand (Real power present demand).

How do I check these points on the real Schneider Electric PowerLogic PM200 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Scheider_Power_Meter_PM200_a · Scheider_Power_Meter_PM200_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.