- Home
- BACnet points lists
- Contemporary Controls
- Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Power and energy meter · BACnet points list
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the ION7550/ION7650: 227 Analog Inputs, 51 polled by default. Polled values cover currents, frequency, unbalance, phase reversal, voltages, kW, kVAR and kVA per phase and total with maxima, kWh and kVARh delivered/received, kVAh and signed PF; harmonics and other values are unpolled.
This page lists 227 BACnet objects for the Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 227 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Map total kW, kWh delivered and average line-line voltage first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 31 | kWtot | Total kW | Read |
| AI 43 | kWh del | kWh delivered | Read |
| AI 25 | VII avg | Average line-line voltage | Read |
| AI 6 | I avg | Average current | Read |
| AI 51 | PF sign tot | Total power factor (signed) | Read |
| AI 10 | Freq | Frequency | Read |
| AI 32 | kW tot mx | Maximum total kW | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | I a | Modbus 400150 | A | Read | |
| AI | 2 | I b | Modbus 400151 | A | Read | |
| AI | 3 | I c | Modbus 400152 | A | Read | |
| AI | 4 | I 4 | Modbus 400153 | A | Read | |
| AI | 5 | I 5 | Modbus 400154 | A | Read | |
| AImin | 6 | I avg | Modbus 400155 | A | Read | |
| AI | 7 | I avg mn | Modbus 400156 | A | Read | |
| AI | 8 | I avg mx | Modbus 400157 | A | Read | |
| AI | 9 | I avg mean | Modbus 400158 | A | Read | |
| AImin | 10 | Freq | Modbus 400159 | Hz | Read | |
| AI | 11 | Freq mn | Modbus 400160 | Hz | Read | |
| AI | 12 | Freq mx | Modbus 400161 | Hz | Read | |
| AI | 13 | Freq mean | Modbus 400162 | Hz | Read | |
| AI | 14 | V unbal | Modbus 400163 | Read | ||
| AI | 15 | 1 unbal | Modbus 400164 | Read | ||
| AI | 16 | Phase Rev | Modbus 400165 | Read | ||
| AI | 17 | VIn a | Modbus 400166 | V | Read | |
| AI | 18 | VIn b | Modbus 400168 | V | Read | |
| AI | 19 | VIn c | Modbus 400170 | V | Read | |
| AI | 20 | VIn avg | Modbus 400172 | V | Read | |
| AI | 21 | VIn avg mx | Modbus 400174 | V | Read | |
| AI | 22 | VII ab | Modbus 400178 | V | Read | |
| AI | 23 | VII be | Modbus 400180 | V | Read | |
| AI | 24 | VII ca | Modbus 400182 | V | Read | |
| AImin | 25 | VII avg | Modbus 400184 | V | Read | |
| AI | 26 | VII avg mx | Modbus 400186 | V | Read | |
| AI | 27 | VII avg mean | Modbus 400188 | V | Read | |
| AI | 28 | kWa | Modbus 400198 | kW | Read | |
| AI | 29 | kWb | Modbus 400200 | kW | Read | |
| AI | 30 | kWc | Modbus 400202 | kW | Read | |
| AImin | 31 | kWtot | Modbus 400204 | kW | Read | |
| AImin | 32 | kW tot mx | Modbus 400206 | kW | Read | |
| AI | 33 | kVARa | Modbus 400208 | kVAR | Read | |
| AI | 34 | kVARb | Modbus 400210 | kVAR | Read | |
| AI | 35 | kVARc | Modbus 400212 | kVAR | Read | |
| AI | 36 | kVAR tot | Modbus 400214 | kVAR | Read | |
| AI | 37 | kVAR tot mx | Modbus 400216 | kVAR | Read | |
| AI | 38 | kVAa | Modbus 400218 | kVA | Read | |
| AI | 39 | kVAb | Modbus 400220 | kVA | Read | |
| AI | 40 | kVAc | Modbus 400222 | kVA | Read | |
| AI | 41 | kVA tot | Modbus 400224 | kVA | Read | |
| AI | 42 | kVA tot mx | Modbus 400226 | kVA | Read | |
| AImin | 43 | kWh del | Modbus 400230 | kWh | Read | |
| AI | 44 | kWh rec | Modbus 400232 | kWh | Read | |
| AI | 45 | kVARh del | Modbus 400234 | Read | ||
| AI | 46 | kVARh rec | Modbus 400236 | Read | ||
| AI | 47 | kVAh del+rec | Modbus 400238 | Read | ||
| AI | 48 | PF sign a | Modbus 400262 | PF | Read | |
| AI | 49 | PF sign b | Modbus 400263 | PF | Read | |
| AI | 50 | PF sign c | Modbus 400264 | PF | Read | |
| AImin | 51 | PF sign tot | Modbus 400265 | PF | Read | |
| AI | 52 | V1THD mx | Modbus 400266; not polled by default | Read | ||
| AI | 53 | V2THD mx | Modbus 400267; not polled by default | Read | ||
| AI | 54 | V3THD mx | Modbus 400268; not polled by default | Read | ||
| AI | 55 | I1 THD mx | Modbus 400269; not polled by default | Read | ||
| AI | 56 | I2 THD mx | Modbus 400270; not polled by default | Read | ||
| AI | 57 | I3 THD mx | Modbus 400271; not polled by default | Read | ||
| AI | 58 | I1 K Factor | Modbus 400272; not polled by default | Read | ||
| AI | 59 | I2 K Factor | Modbus 400273; not polled by default | Read | ||
| AI | 60 | I3 K Factor | Modbus 400274; not polled by default | Read | ||
| AI | 61 | I1 Crest Factor | Modbus 400275; not polled by default | Read | ||
| AI | 62 | I2 Crest Factor | Modbus 400276; not polled by default | Read | ||
| AI | 63 | I3 Crest Factor | Modbus 400277; not polled by default | Read | ||
| AI | 64 | PO VI-FlckN | Modbus 401000; not polled by default | Read | ||
| AI | 65 | PO VI-FlckNI | Modbus 401001; not polled by default | Read | ||
| AI | 66 | PO V2-Flck N | Modbus 401002; not polled by default | Read | ||
| AI | 67 | PO V2-Flck N1 | Modbus 401003; not polled by default | Read | ||
| AI | 68 | PO V3-Flck N | Modbus 401004; not polled by default | Read | ||
| AI | 69 | PO V3-Flck N1 | Modbus 401005; not polled by default | Read | ||
| AI | 70 | PO Freq N | Modbus 401006; not polled by default | Read | ||
| AI | 71 | PO Freq N1 | Modbus 401007; not polled by default | Read | ||
| AI | 72 | PO Freq N2 | Modbus 401008; not polled by default | Read | ||
| AI | 73 | PO VI-MAG N | Modbus 401009; not polled by default | Read | ||
| AI | 74 | PO V1-MAGN1 | Modbus 401010; not polled by default | Read | ||
| AI | 75 | PO V2-MAG N | Modbus 401011; not polled by default | Read | ||
| AI | 76 | P0V2-MAGN1 | Modbus 401012; not polled by default | Read | ||
| AI | 77 | PO V3-MAG N | Modbus 401013; not polled by default | Read | ||
| AI | 78 | PO V3-MAGN1 | Modbus 401014; not polled by default | Read | ||
| AI | 79 | PO Vunbal N | Modbus 401015; not polled by default | Read | ||
| AI | 80 | PO Vunbal N1 | Modbus 401016; not polled by default | Read | ||
| AI | 81 | PO VI-MSignal N | Modbus 401017; not polled by default | Read | ||
| AI | 82 | PO VI-MSignal N1 | Modbus 401018; not polled by default | Read | ||
| AI | 83 | PO V2-MSignal N | Modbus 401019; not polled by default | Read | ||
| AI | 84 | PO V2-MSignal N1 | Modbus 401020; not polled by default | Read | ||
| AI | 85 | PO V3-MSignal N | Modbus 401021; not polled by default | Read | ||
| AI | 86 | PO V3-MSignal N1 | Modbus 401022; not polled by default | Read | ||
| AI | 87 | PO V1-Hrm N | Modbus 401023; not polled by default | Read | ||
| AI | 88 | PO V1-Hrm N1 | Modbus 401024; not polled by default | Read | ||
| AI | 89 | PO V1-Hrm N2 | Modbus 401025; not polled by default | Read | ||
| AI | 90 | PO V2-Hrm N | Modbus 401026; not polled by default | Read | ||
| AI | 91 | PO V2-Hrm N1 | Modbus 401027; not polled by default | Read | ||
| AI | 92 | PO V2-Hrm N2 | Modbus 401028; not polled by default | Read | ||
| AI | 93 | PO V3-Hrm N | Modbus 401029; not polled by default | Read | ||
| AI | 94 | PO V3-Hrm N1 | Modbus 401030; not polled by default | Read | ||
| AI | 95 | PO V3-Hrm N2 | Modbus 401031; not polled by default | Read | ||
| AI | 96 | PO V1-lnthrm N | Modbus 401032; not polled by default | Read | ||
| AI | 97 | PO V1-lnthrm N1 | Modbus 401033; not polled by default | Read | ||
| AI | 98 | PO V2-lnthrm N | Modbus 401034; not polled by default | Read | ||
| AI | 99 | PO V2-lnthrm N1 | Modbus 401035; not polled by default | Read | ||
| AI | 100 | PO V3-lnthrm N | Modbus 401036; not polled by default | Read | ||
| AI | 101 | PO V3-lnthrm N1 | Modbus 401037; not polled by default | Read | ||
| AI | 102 | PO V1-DipN11 | Modbus 401038; not polled by default | Read | ||
| AI | 103 | PO V1-DipN12 | Modbus 401039; not polled by default | Read | ||
| AI | 104 | PO V1-DipN13 | Modbus 401040; not polled by default | Read | ||
| AI | 105 | PO V1-DipN14 | Modbus 401041; not polled by default | Read | ||
| AI | 106 | PO V1-DipN21 | Modbus 401042; not polled by default | Read | ||
| AI | 107 | PO V1-DipN22 | Modbus 401043; not polled by default | Read | ||
| AI | 108 | PO V1-DipN23 | Modbus 401044; not polled by default | Read | ||
| AI | 109 | PO V1-DipN24 | Modbus 401045; not polled by default | Read | ||
| AI | 110 | PO V1-DipN31 | Modbus 401046; not polled by default | Read | ||
| AI | 111 | PO V1-DipN32 | Modbus 401047; not polled by default | Read | ||
| AI | 112 | PO V1-DipN33 | Modbus 401048; not polled by default | Read | ||
| AI | 113 | PO V1-DipN34 | Modbus 401049; not polled by default | Read | ||
| AI | 114 | PO V1-DipN41 | Modbus 401050; not polled by default | Read | ||
| AI | 115 | PO V1-DipN42 | Modbus 401051; not polled by default | Read | ||
| AI | 116 | PO V1-DipN43 | Modbus 401052; not polled by default | Read | ||
| AI | 117 | PO V1-DipN44 | Modbus 401053; not polled by default | Read | ||
| AI | 118 | PO V1-DipN51 | Modbus 401054; not polled by default | Read | ||
| AI | 119 | PO V1-DipN52 | Modbus 401055; not polled by default | Read | ||
| AI | 120 | PO V1-DipN53 | Modbus 401056; not polled by default | Read | ||
| AI | 121 | PO V1-DipN54 | Modbus 401057; not polled by default | Read | ||
| AI | 122 | PO V1-DipN61 | Modbus 401058; not polled by default | Read | ||
| AI | 123 | PO V1-DipN62 | Modbus 401059; not polled by default | Read | ||
| AI | 124 | PO V1-DipN63 | Modbus 401060; not polled by default | Read | ||
| AI | 125 | PO V1-DipN64 | Modbus 401061; not polled by default | Read | ||
| AI | 126 | P0V2-DipN11 | Modbus 401062; not polled by default | Read | ||
| AI | 127 | POV2-DipN12 | Modbus 401063; not polled by default | Read | ||
| AI | 128 | POV2-DipN13 | Modbus 401064; not polled by default | Read | ||
| AI | 129 | POV2-DipN14 | Modbus 401065; not polled by default | Read | ||
| AI | 130 | PO V2-Dip N21 | Modbus 401066; not polled by default | Read | ||
| AI | 131 | PO V2-Dip N22 | Modbus 401067; not polled by default | Read | ||
| AI | 132 | PO V2-Dip N23 | Modbus 401068; not polled by default | Read | ||
| AI | 133 | PO V2-Dip N24 | Modbus 401069; not polled by default | Read | ||
| AI | 134 | PO V2-Dip N31 | Modbus 401070; not polled by default | Read | ||
| AI | 135 | PO V2-Dip N32 | Modbus 401071; not polled by default | Read | ||
| AI | 136 | PO V2-Dip N33 | Modbus 401072; not polled by default | Read | ||
| AI | 137 | PO V2-Dip N34 | Modbus 401073; not polled by default | Read | ||
| AI | 138 | PO V2-Dip N41 | Modbus 401074; not polled by default | Read | ||
| AI | 139 | PO V2-Dip N42 | Modbus 401075; not polled by default | Read | ||
| AI | 140 | PO V2-Dip N43 | Modbus 401076; not polled by default | Read | ||
| AI | 141 | PO V2-Dip N44 | Modbus 401077; not polled by default | Read | ||
| AI | 142 | PO V2-Dip N51 | Modbus 401078; not polled by default | Read | ||
| AI | 143 | PO V2-Dip N52 | Modbus 401079; not polled by default | Read | ||
| AI | 144 | PO V2-Dip N53 | Modbus 401080; not polled by default | Read | ||
| AI | 145 | PO V2-Dip N54 | Modbus 401081; not polled by default | Read | ||
| AI | 146 | PO V2-Dip N61 | Modbus 401082; not polled by default | Read | ||
| AI | 147 | PO V2-Dip N62 | Modbus 401083; not polled by default | Read | ||
| AI | 148 | PO V2-Dip N63 | Modbus 401084; not polled by default | Read | ||
| AI | 149 | PO V2-Dip N64 | Modbus 401085; not polled by default | Read | ||
| AI | 150 | PO V3-DipN11 | Modbus 401086; not polled by default | Read | ||
| AI | 151 | PO V3-DipN12 | Modbus 401087; not polled by default | Read | ||
| AI | 152 | PO V3-DipN13 | Modbus 401088; not polled by default | Read | ||
| AI | 153 | PO V3-DipN14 | Modbus 401089; not polled by default | Read | ||
| AI | 154 | PO V3-Dip N21 | Modbus 401090; not polled by default | Read | ||
| AI | 155 | PO V3-Dip N22 | Modbus 401091; not polled by default | Read | ||
| AI | 156 | PO V3-Dip N23 | Modbus 401092; not polled by default | Read | ||
| AI | 157 | PO V3-Dip N24 | Modbus 401093; not polled by default | Read | ||
| AI | 158 | PO V3-Dip N31 | Modbus 401094; not polled by default | Read | ||
| AI | 159 | PO V3-Dip N32 | Modbus 401095; not polled by default | Read | ||
| AI | 160 | PO V3-Dip N33 | Modbus 401096; not polled by default | Read | ||
| AI | 161 | PO V3-Dip N34 | Modbus 401097; not polled by default | Read | ||
| AI | 162 | PO V3-Dip N41 | Modbus 401098; not polled by default | Read | ||
| AI | 163 | PO V3-Dip N42 | Modbus 401099; not polled by default | Read | ||
| AI | 164 | PO V3-Dip N43 | Modbus 401100; not polled by default | Read | ||
| AI | 165 | PO V3-Dip N44 | Modbus 401101; not polled by default | Read | ||
| AI | 166 | PO V3-Dip N51 | Modbus 401102; not polled by default | Read | ||
| AI | 167 | PO V3-Dip N52 | Modbus 401103; not polled by default | Read | ||
| AI | 168 | PO V3-Dip N53 | Modbus 401104; not polled by default | Read | ||
| AI | 169 | PO V3-Dip N54 | Modbus 401105; not polled by default | Read | ||
| AI | 170 | PO V3-Dip N61 | Modbus 401106; not polled by default | Read | ||
| AI | 171 | PO V3-Dip N62 | Modbus 401107; not polled by default | Read | ||
| AI | 172 | PO V3-Dip N63 | Modbus 401108; not polled by default | Read | ||
| AI | 173 | PO V3-Dip N64 | Modbus 401109; not polled by default | Read | ||
| AI | 174 | PO V1-lntrptN1 | Modbus 401110; not polled by default | Read | ||
| AI | 175 | PO V1-lntrpt N2 | Modbus 401111; not polled by default | Read | ||
| AI | 176 | PO V1-lntrptN3 | Modbus 401112; not polled by default | Read | ||
| AI | 177 | PO V2-lntrptN1 | Modbus 401113; not polled by default | Read | ||
| AI | 178 | PO V2-lntrpt N2 | Modbus 401114; not polled by default | Read | ||
| AI | 179 | PO V2-lntrpt N3 | Modbus 401115; not polled by default | Read | ||
| AI | 180 | PO V3-lntrptN1 | Modbus 401116; not polled by default | Read | ||
| AI | 181 | PO V3-lntrpt N2 | Modbus 401117; not polled by default | Read | ||
| AI | 182 | PO V3-lntrpt N3 | Modbus 401118; not polled by default | Read | ||
| AI | 183 | PO V1-0vltN11 | Modbus 401119; not polled by default | Read | ||
| AI | 184 | PO V1-0vltN12 | Modbus 401120; not polled by default | Read | ||
| AI | 185 | PO V1-0vltN13 | Modbus 401121; not polled by default | Read | ||
| AI | 186 | PO V1-0vltN14 | Modbus 401122; not polled by default | Read | ||
| AI | 187 | PO V1-0vltN15 | Modbus 401123; not polled by default | Read | ||
| AI | 188 | PO V1-0vlt N21 | Modbus 401124; not polled by default | Read | ||
| AI | 189 | PO V1-0vlt N22 | Modbus 401125; not polled by default | Read | ||
| AI | 190 | PO V1-0vlt N23 | Modbus 401126; not polled by default | Read | ||
| AI | 191 | PO V1-0vlt N24 | Modbus 401127; not polled by default | Read | ||
| AI | 192 | PO V1-0vlt N25 | Modbus 401128; not polled by default | Read | ||
| AI | 193 | PO V1-0vlt N31 | Modbus 401129; not polled by default | Read | ||
| AI | 194 | PO V1-0vlt N32 | Modbus 401130; not polled by default | Read | ||
| AI | 195 | PO V1-0vlt N33 | Modbus 401131; not polled by default | Read | ||
| AI | 196 | PO V1-0vlt N34 | Modbus 401132; not polled by default | Read | ||
| AI | 197 | PO V1-0vlt N35 | Modbus 401133; not polled by default | Read | ||
| AI | 198 | PO V2-0vltN11 | Modbus 401134; not polled by default | Read | ||
| AI | 199 | PO V2-OvltN12 | Modbus 401135; not polled by default | Read | ||
| AI | 200 | PO V2-OvltN13 | Modbus 401136; not polled by default | Read | ||
| AI | 201 | PO V2-OvltN14 | Modbus 401137; not polled by default | Read | ||
| AI | 202 | PO V2-OvltN15 | Modbus 401138; not polled by default | Read | ||
| AI | 203 | PO V2-0vlt N21 | Modbus 401139; not polled by default | Read | ||
| AI | 204 | PO V2-0vlt N22 | Modbus 401140; not polled by default | Read | ||
| AI | 205 | PO V2-0vlt N23 | Modbus 401141; not polled by default | Read | ||
| AI | 206 | PO V2-0vlt N24 | Modbus 401142; not polled by default | Read | ||
| AI | 207 | PO V2-0vlt N25 | Modbus 401143; not polled by default | Read | ||
| AI | 208 | PO V2-0vlt N31 | Modbus 401144; not polled by default | Read | ||
| AI | 209 | PO V2-0vlt N32 | Modbus 401145; not polled by default | Read | ||
| AI | 210 | PO V2-0vlt N33 | Modbus 401146; not polled by default | Read | ||
| AI | 211 | PO V2-0vlt N34 | Modbus 401147; not polled by default | Read | ||
| AI | 212 | PO V2-0vlt N35 | Modbus 401148; not polled by default | Read | ||
| AI | 213 | PO V3-0vltN11 | Modbus 401149; not polled by default | Read | ||
| AI | 214 | PO V3-OvltN12 | Modbus 401150; not polled by default | Read | ||
| AI | 215 | PO V3-OvltN13 | Modbus 401151; not polled by default | Read | ||
| AI | 216 | PO V3-OvltN14 | Modbus 401152; not polled by default | Read | ||
| AI | 217 | PO V3-OvltN15 | Modbus 401153; not polled by default | Read | ||
| AI | 218 | PO V3-0vlt N21 | Modbus 401154; not polled by default | Read | ||
| AI | 219 | PO V3-0vlt N22 | Modbus 401155; not polled by default | Read | ||
| AI | 220 | PO V3-0vlt N23 | Modbus 401156; not polled by default | Read | ||
| AI | 221 | PO V3-0vlt N24 | Modbus 401157; not polled by default | Read | ||
| AI | 222 | PO V3-0vlt N25 | Modbus 401158; not polled by default | Read | ||
| AI | 223 | PO V3-0vlt N31 | Modbus 401159; not polled by default | Read | ||
| AI | 224 | PO V3-0vlt N32 | Modbus 401160; not polled by default | Read | ||
| AI | 225 | PO V3-0vlt N33 | Modbus 401161; not polled by default | Read | ||
| AI | 226 | PO V3-0vlt N34 | Modbus 401162; not polled by default | Read | ||
| AI | 227 | PO V3-0vlt N35 | Modbus 401163; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX ION7550/ION7650 point IDs by name
AI1I aAI2I bAI3I cAI4I 4AI5I 5AI6I avgAI7I avg mnAI8I avg mxAI9I avg meanAI10FreqAI11Freq mnAI12Freq mxAI13Freq meanAI14V unbalAI151 unbalAI16Phase RevAI17VIn aAI18VIn bAI19VIn cAI20VIn avgAI21VIn avg mxAI22VII abAI23VII beAI24VII caAI25VII avgAI26VII avg mxAI27VII avg meanAI28kWaAI29kWbAI30kWcAI31kWtotAI32kW tot mxAI33kVARaAI34kVARbAI35kVARcAI36kVAR totAI37kVAR tot mxAI38kVAaAI39kVAbAI40kVAcAI41kVA totAI42kVA tot mxAI43kWh delAI44kWh recAI45kVARh delAI46kVARh recAI47kVAh del+recAI48PF sign aAI49PF sign bAI50PF sign cAI51PF sign totAI52V1THD mxAI53V2THD mxAI54V3THD mxAI55I1 THD mxAI56I2 THD mxAI57I3 THD mxAI58I1 K FactorAI59I2 K FactorAI60I3 K FactorAI61I1 Crest FactorAI62I2 Crest FactorAI63I3 Crest FactorAI64PO VI-FlckNAI65PO VI-FlckNIAI66PO V2-Flck NAI67PO V2-Flck N1AI68PO V3-Flck NAI69PO V3-Flck N1AI70PO Freq NAI71PO Freq N1AI72PO Freq N2AI73PO VI-MAG NAI74PO V1-MAGN1AI75PO V2-MAG NAI76P0V2-MAGN1AI77PO V3-MAG NAI78PO V3-MAGN1AI79PO Vunbal NAI80PO Vunbal N1AI81PO VI-MSignal NAI82PO VI-MSignal N1AI83PO V2-MSignal NAI84PO V2-MSignal N1AI85PO V3-MSignal NAI86PO V3-MSignal N1AI87PO V1-Hrm NAI88PO V1-Hrm N1AI89PO V1-Hrm N2AI90PO V2-Hrm NAI91PO V2-Hrm N1AI92PO V2-Hrm N2AI93PO V3-Hrm NAI94PO V3-Hrm N1AI95PO V3-Hrm N2AI96PO V1-lnthrm NAI97PO V1-lnthrm N1AI98PO V2-lnthrm NAI99PO V2-lnthrm N1AI100PO V3-lnthrm NAI101PO V3-lnthrm N1AI102PO V1-DipN11AI103PO V1-DipN12AI104PO V1-DipN13AI105PO V1-DipN14AI106PO V1-DipN21AI107PO V1-DipN22AI108PO V1-DipN23AI109PO V1-DipN24AI110PO V1-DipN31AI111PO V1-DipN32AI112PO V1-DipN33AI113PO V1-DipN34AI114PO V1-DipN41AI115PO V1-DipN42AI116PO V1-DipN43AI117PO V1-DipN44AI118PO V1-DipN51AI119PO V1-DipN52AI120PO V1-DipN53AI121PO V1-DipN54AI122PO V1-DipN61AI123PO V1-DipN62AI124PO V1-DipN63AI125PO V1-DipN64AI126P0V2-DipN11AI127POV2-DipN12AI128POV2-DipN13AI129POV2-DipN14AI130PO V2-Dip N21AI131PO V2-Dip N22AI132PO V2-Dip N23AI133PO V2-Dip N24AI134PO V2-Dip N31AI135PO V2-Dip N32AI136PO V2-Dip N33AI137PO V2-Dip N34AI138PO V2-Dip N41AI139PO V2-Dip N42AI140PO V2-Dip N43AI141PO V2-Dip N44AI142PO V2-Dip N51AI143PO V2-Dip N52AI144PO V2-Dip N53AI145PO V2-Dip N54AI146PO V2-Dip N61AI147PO V2-Dip N62AI148PO V2-Dip N63AI149PO V2-Dip N64AI150PO V3-DipN11AI151PO V3-DipN12AI152PO V3-DipN13AI153PO V3-DipN14AI154PO V3-Dip N21AI155PO V3-Dip N22AI156PO V3-Dip N23AI157PO V3-Dip N24AI158PO V3-Dip N31AI159PO V3-Dip N32AI160PO V3-Dip N33AI161PO V3-Dip N34AI162PO V3-Dip N41AI163PO V3-Dip N42AI164PO V3-Dip N43AI165PO V3-Dip N44AI166PO V3-Dip N51AI167PO V3-Dip N52AI168PO V3-Dip N53AI169PO V3-Dip N54AI170PO V3-Dip N61AI171PO V3-Dip N62AI172PO V3-Dip N63AI173PO V3-Dip N64AI174PO V1-lntrptN1AI175PO V1-lntrpt N2AI176PO V1-lntrptN3AI177PO V2-lntrptN1AI178PO V2-lntrpt N2AI179PO V2-lntrpt N3AI180PO V3-lntrptN1AI181PO V3-lntrpt N2AI182PO V3-lntrpt N3AI183PO V1-0vltN11AI184PO V1-0vltN12AI185PO V1-0vltN13AI186PO V1-0vltN14AI187PO V1-0vltN15AI188PO V1-0vlt N21AI189PO V1-0vlt N22AI190PO V1-0vlt N23AI191PO V1-0vlt N24AI192PO V1-0vlt N25AI193PO V1-0vlt N31AI194PO V1-0vlt N32AI195PO V1-0vlt N33AI196PO V1-0vlt N34AI197PO V1-0vlt N35AI198PO V2-0vltN11AI199PO V2-OvltN12AI200PO V2-OvltN13AI201PO V2-OvltN14AI202PO V2-OvltN15AI203PO V2-0vlt N21AI204PO V2-0vlt N22AI205PO V2-0vlt N23AI206PO V2-0vlt N24AI207PO V2-0vlt N25AI208PO V2-0vlt N31AI209PO V2-0vlt N32AI210PO V2-0vlt N33AI211PO V2-0vlt N34AI212PO V2-0vlt N35AI213PO V3-0vltN11AI214PO V3-OvltN12AI215PO V3-OvltN13AI216PO V3-OvltN14AI217PO V3-OvltN15AI218PO V3-0vlt N21AI219PO V3-0vlt N22AI220PO V3-0vlt N23AI221PO V3-0vlt N24AI222PO V3-0vlt N25AI223PO V3-0vlt N31AI224PO V3-0vlt N32AI225PO V3-0vlt N33AI226PO V3-0vlt N34AI227PO V3-0vlt N35
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Schneider_Electric_ION7550_7650_a_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/ION_Meter_Modbus.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 51 of the 227 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
How many BACnet points does the Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX have?
This list has 227 BACnet objects: 227 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Schneider_Electric_ION7550_7650_a (Schneider_Electric_ION7550_7650_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Schneider_Electric_ION7550_7650.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX?
Start with AI 31 kWtot (Total kW); AI 43 kWh del (kWh delivered); AI 25 VII avg (Average line-line voltage); AI 6 I avg (Average current); AI 51 PF sign tot (Total power factor (signed)); AI 10 Freq (Frequency); AI 32 kW tot mx (Maximum total kW).
How do I check these points on the real Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Schneider_Electric_ION7550_7650_a · Schneider_Electric_ION7550_7650_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.