UPS (uninterruptible power supply) · BACnet points list

Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for Mitsubishi UPS through the MUCM interface: 74 objects (32 AI, 12 AO, 30 BI), 52 polled by default. It follows the UPS-MIB style layout: battery status, charge, seconds on battery, input and output values, output source (normal, battery, bypass, boost, reduce), bypass values and alarm bits; outputs hold nominal ratings, battery install date, audible alarm and test.

This page lists 74 BACnet objects for the Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
74 (12 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS
Source document
BASgatewayLX Modbus device profile Mitsubishi_MUCM_1100_2033_7011_9800_9900 · Mitsubishi_MUCM_1100_2033_7011_9800_9900_LX.csv
Download CSV 74 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX

Integration in brief

Read output source normal/on battery/on bypass, % battery charge, seconds on battery, output power and the general fault and overload alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 10Output Source NormalOutput source normalRead
BI 11Output Source On BatteryOn batteryRead
BI 12Output Source On BypassOn bypassRead
AI 5% Battery Charge LeftBattery charge left, %Read
AI 4Seconds on BatterySeconds on batteryRead
AI 22Output PowerOutput powerRead
AI 16Output Voltage Phase ABOutput voltage A-BRead
AI 26Output FrequencyOutput frequencyRead
BI 38Overload AlarmOverload alarmRead
BI 46General Fault AlarmGeneral fault alarmRead

Network setup

Watch out for

Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

74 of 74 shown
Type
Binary
Access
Show
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX BACnet Points List
DescriptionStates
AI1UPS Device TypeModbus 400001Read
AI2Battery StatusModbus 400003Read
AI3Battery ChargeModbus 400004Read
AImin4Seconds on BatteryModbus 400005sRead
AImin5% Battery Charge LeftModbus 400006%Read
AI6Battery VoltageModbus 400007VRead
AI7Input Line BadsModbus 400014Read
AI8Input Frequency (Average)Modbus 400016HzRead
AI9Input Voltage (Average)Modbus 400022VRead
BImin10Output Source NormalModbus 400032 bit 0Read
BImin11Output Source On BatteryModbus 400032 bit 1Read
BImin12Output Source On BypassModbus 400032 bit 2Read
BI13Output Source ReducingModbus 400032 bit 3Read
BI14Output Source BoostingModbus 400032 bit 4Read
BI15Output Source OtherModbus 400032 bit 5Read
AImin16Output Voltage Phase ABModbus 400036VRead
AI17Output Voltage Phase BCModbus 400037VRead
AI18Output Voltage Phase CAModbus 400038VRead
AI19Output Current Phase AModbus 400039ARead
AI20Output Current Phase BModbus 400040ARead
AI21Output Current Phase CModbus 400041ARead
AImin22Output PowerModbus 400045WRead
AI23Output % Load Phase AModbus 400048%Read
AI24Output % Load Phase BModbus 400049%Read
AI25Output % Load Phase CModbus 400050%Read
AImin26Output FrequencyModbus 400051HzRead
AI27Bypass Voltage Phase ABModbus 400057VRead
AI28Bypass Voltage Phase BCModbus 400058VRead
AI29Bypass Voltage Phase BCModbus 400059VRead
AI30Bypass Current Phase AModbus 400060ARead
AI31Bypass Current Phase BModbus 400061ARead
AI32Bypass Current Phase CModbus 400062ARead
AI33Bypass PowerModbus 400063WRead
AI34Bypass FrequencyModbus 400066HzRead
BI35Temperature AlarmModbus 400067 bit 0Read
BI36Input Bad AlarmModbus 400067 bit 1Read
BI37Output Bad AlarmModbus 400067 bit 2Read
BImin38Overload AlarmModbus 400067 bit 3Read
BI39Bypass Bad AlarmModbus 400067 bit 4Read
BI40Output Off AlarmModbus 400067 bit 5Read
BI41UPS Shutdown AlarmModbus 400067 bit 6Read
BI42Charger Failure AlarmModbus 400067 bit 7Read
BI43System Off AlarmModbus 400067 bit 8Read
BI44Fan Failure AlarmModbus 400067 bit 9Read
BI45Fuse Failure AlarmModbus 400067 bit 10Read
BImin46General Fault AlarmModbus 400067 bit 11Read
BI47Awaiting Power AlarmModbus 400067 bit 12Read
BI48Shutdown Pending AlarmModbus 400067 bit 13Read
BI49Shutdown Imminent AlarmModbus 400067 bit 14Read
BI50Auto Reboot [503]Modbus 400499 bit 0; not polled by defaultRead
BI51Nominal Setting [504517]Modbus 400499 bit 1; not polled by defaultRead
BI52Shutdown After Delay [518]Modbus 400499 bit 2; not polled by defaultRead
BI53Reboot with Duration [519]Modbus 400499 bit 3; not polled by defaultRead
BI54Action taken at Shutdown [520]Modbus 400499 bit 4; not polled by defaultRead
BI55Startup After Delay [521]Modbus 400499 bit 5; not polled by defaultRead
BI56Test [522]Modbus 400499 bit 6; not polled by defaultRead
BI57UPS Baud Rate [523]Modbus 400499 bit 7; not polled by defaultRead
BI58UPS Identification [524555]Modbus 400499 bit 8; not polled by defaultRead
AI59Number of Input LinesModbus 400500; not polled by defaultRead
AI60Number of Output LinesModbus 400501; not polled by defaultRead
AI61Number of Bypass LinesModbus 400502; not polled by defaultRead
AO62Nominal Input VoltageModbus 400504; not polled by defaultVCommand
AO63Nominal Input FrequencyModbus 400505; not polled by defaultHzCommand
AO64Nominal Output VoltageModbus 400506; not polled by defaultVCommand
AO65Nominal Output FrequencyModbus 400507; not polled by defaultHzCommand
AO66Nominal VA RatingModbus 400508; not polled by defaultCommand
AO67Nominal Output PowerModbus 400509; not polled by defaultWCommand
AO68Audible AlarmModbus 400511; not polled by defaultCommand
AO69Battery Installed MonthModbus 400514monthsCommand
AO70Battery Installed DayModbus 400515daysCommand
AO71Battery Installed YearModbus 400516yearsCommand
AO72Action Taken at ShutdownModbus 400520; not polled by defaultCommand
AO73TestModbus 400522; not polled by defaultCommand
AI74UPS Baud RateModbus 400523; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX Mitsubishi UPS MUCM point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX

How many BACnet points does the Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX have?

This list has 74 BACnet objects: 32 analog inputs, 12 analog outputs, 30 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX BACnet points are writable?

12 of the 74 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Mitsubishi_MUCM_1100_2033_7011_9800_9900 (Mitsubishi_MUCM_1100_2033_7011_9800_9900_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/MitsubishiProconMUCM.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX?

Start with BI 10 Output Source Normal (Output source normal); BI 11 Output Source On Battery (On battery); BI 12 Output Source On Bypass (On bypass); AI 5 % Battery Charge Left (Battery charge left, %); AI 4 Seconds on Battery (Seconds on battery); AI 22 Output Power (Output power); AI 16 Output Voltage Phase AB (Output voltage A-B); AI 26 Output Frequency (Output frequency); BI 38 Overload Alarm (Overload alarm); BI 46 General Fault Alarm (General fault alarm).

How do I check these points on the real Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Mitsubishi_MUCM_1100_2033_7011_9800_9900 · Mitsubishi_MUCM_1100_2033_7011_9800_9900_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.