Power and energy meter · BACnet points list

Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Carlo Gavazzi EM24: 105 objects (96 AI, 6 AO, 3 BI), 51 polled by default. Inputs give voltages, currents, W, VA and VAR per phase and total, demand and peak demand, PF, frequency, total, partial, per-phase and tariff kWh/kvarh and exported energy; unpolled outputs reset the counters and peak demand.

This page lists 105 BACnet objects for the Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Carlo Gavazzi EM24 via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
105 (6 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus
Source document
BASgatewayLX Modbus device profile Carlo_Gavazzi_EM24_Meter · Carlo_Gavazzi_EM24_Meter_LX.csv
Download CSV 105 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX

Integration in brief

Map total active power, imported active energy (kWh+) and exported active energy (kWh-) first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 21W TotalTotal active powerRead
AI 35KWh(+) TOTImported active energy (kWh+)Read
AI 50KWh(-) TOTExported active energy (kWh-)Read
AI 24DMD W TotalActive power demandRead
AI 19V L-N TotalSystem line-neutral voltageRead
AI 7A L1Current L1Read
AI 29PF TotalTotal power factorRead
AI 31HzFrequencyRead

Network setup

Watch out for

Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

105 of 105 shown
Type
Binary
Access
Show
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX BACnet Points List
DescriptionStates
AI1V L1-NModbus 400001VRead
AI2V L2-NModbus 400003VRead
AI3V L3-NModbus 400005VRead
AI4V L1-L2Modbus 400007VRead
AI5V L2-L3Modbus 400009VRead
AI6V L3-L1Modbus 400011VRead
AImin7A L1Modbus 400013ARead
AI8A L2Modbus 400015ARead
AI9A L3Modbus 400017ARead
AI10W L1Modbus 400019WRead
AI11W L2Modbus 400021WRead
AI12W L3Modbus 400023WRead
AI13VA L1Modbus 400025VARead
AI14VA L2Modbus 400027VARead
AI15VA L3Modbus 400029VARead
AI16VAR L1Modbus 400031VARRead
AI17VAR L2Modbus 400033VARRead
AI18VAR L3Modbus 400035VARRead
AImin19V L-N TotalModbus 400037VRead
AI20V L-L TotalModbus 400039VRead
AImin21W TotalModbus 400041WRead
AI22VA TotalModbus 400043VARead
AI23VAR TotalModbus 400045VARRead
AImin24DMD W TotalModbus 400047Read
AI25DMD VA TotalModbus 400049Read
AI26PF L1Modbus 400051Read
AI27PF L2Modbus 400052Read
AI28PF L3Modbus 400053Read
AImin29PF TotalModbus 400054Read
AI30Phase sequenceModbus 400055Read
AImin31HzModbus 400056Read
AI32DMD W total maxModbus 400057Read
AI33DMD VA total maxModbus 400059Read
AI34DMD A maxModbus 400061Read
AImin35KWh(+) TOTModbus 400063Read
AI36Kvarh(+) TOTModbus 400065Read
AI37KWh(+) PARModbus 400067Read
AI38Kvarh(+) PARModbus 400069Read
AI39KWh(+) L1Modbus 400071Read
AI40KWh(+) L2Modbus 400073Read
AI41KWh(+) L3Modbus 400075Read
AI42KWh(+) T1Modbus 400077Read
AI43KWh(+) T2Modbus 400079Read
AI44KWh(+) T3Modbus 400081Read
AI45KWh(+) T4Modbus 400083Read
AI46Kvarh(+) T1Modbus 400085Read
AI47Kvarh(+) T2Modbus 400087Read
AI48Kvarh(+) T3Modbus 400089Read
AI49Kvarh(+) T4Modbus 400091Read
AImin50KWh(-) TOTModbus 400093Read
AI51Kvarh(-) TOTModbus 400095Read
AI52HourModbus 400097; not polled by defaultRead
AI53Counter 1Modbus 400099; not polled by defaultRead
AI54Counter 2Modbus 400101; not polled by defaultRead
AI55Counter 3Modbus 400103; not polled by defaultRead
BI56CH1 input status openModbus 400769 bit 0; not polled by defaultRead
BI57CH2 input status openModbus 400769 bit 1; not polled by defaultRead
BI58CH3 input status openModbus 400769 bit 2; not polled by defaultRead
AI59Current tariffModbus 400770; not polled by defaultRead
AI60Version codeModbus 400771; not polled by defaultRead
AI61Revision codeModbus 400772; not polled by defaultRead
AI62Front selector statusModbus 400773; not polled by defaultRead
AI63Carlo Gavazzi Controls identification codeModbus 400012; not polled by defaultRead
AI64PASSWORDModbus 404353; not polled by defaultRead
AI65Type of applicationModbus 404354; not polled by defaultRead
AI66Measuring systemModbus 404355; not polled by defaultRead
AI67Interval timeModbus 404356; not polled by defaultRead
AI68Position selector: 3Modbus 404357; not polled by defaultRead
AI69Position selector: 2Modbus 404358; not polled by defaultRead
AI70Position selector: 1Modbus 404359; not polled by defaultRead
AI71Position selector: 0Modbus 404360; not polled by defaultRead
AI72Filter span parameterModbus 404361; not polled by defaultRead
AI73Filter coefficientModbus 404362; not polled by defaultRead
AI74RS485 instrument addressModbus 404363; not polled by defaultRead
AI75RS485 baud rateModbus 404364; not polled by defaultRead
AI76ID code of user 1Modbus 404365; not polled by defaultRead
AI77ID code of user 2Modbus 404366; not polled by defaultRead
AI78ID code of user 3Modbus 404367; not polled by defaultRead
AI79Out1 typeModbus 404368; not polled by defaultRead
AI80Out1 pulseModbus 404369; not polled by defaultRead
AI81Alarm1 set point onModbus 404371; not polled by defaultRead
AI82Alarm1 set point offModbus 404373; not polled by defaultRead
AI83Alarm1 delayModbus 404375; not polled by defaultRead
AI84Alarm1 statusModbus 404376; not polled by defaultRead
AI85Out2 typeModbus 404377; not polled by defaultRead
AI86Out2 pulseModbus 404378; not polled by defaultRead
AI87Alarm2 set point onModbus 404380; not polled by defaultRead
AI88Alarm2 set point offModbus 404382; not polled by defaultRead
AI89Alarm2 delayModbus 404384; not polled by defaultRead
AI90Alarm2 statusModbus 404385; not polled by defaultRead
AI91Digital input 1 typeModbus 404386; not polled by defaultRead
AI92Digital input 2 typeModbus 404387; not polled by defaultRead
AI93Digital input 3 typeModbus 404388; not polled by defaultRead
AI94Digital input 1 prescalerModbus 404389; not polled by defaultRead
AI95Digital input 2 prescalerModbus 404390; not polled by defaultRead
AI96Digital input 3 prescalerModbus 404391; not polled by defaultRead
AI97Tariff managed via serial communicationModbus 404392; not polled by defaultRead
AI98Current transformer ratioModbus 404397; not polled by defaultRead
AI99Voltage transformer ratioModbus 404399; not polled by defaultRead
AO100Reset of all meters (hour counter excluded)Modbus 412289; not polled by defaultCommand
AO101Reset of total metersModbus 412290; not polled by defaultCommand
AO102Reset of partial metersModbus 412291; not polled by defaultCommand
AO103Reset of hour counterModbus 412292; not polled by defaultCommand
AO104Reset counter 1 2 and 3Modbus 412293; not polled by defaultCommand
AO105Reset dmd maxModbus 412294; not polled by defaultCommand
Object ID lookup: Contemporary Controls BASgatewayLX Carlo Gavazzi EM24 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Carlo Gavazzi EM24 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX

How many BACnet points does the Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX have?

This list has 105 BACnet objects: 96 analog inputs, 6 analog outputs, 3 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX BACnet points are writable?

6 of the 105 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Carlo_Gavazzi_EM24_Meter (Carlo_Gavazzi_EM24_Meter_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Carlo_Gavazzi_EM24_Meter_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX?

Start with AI 21 W Total (Total active power); AI 35 KWh(+) TOT (Imported active energy (kWh+)); AI 50 KWh(-) TOT (Exported active energy (kWh-)); AI 24 DMD W Total (Active power demand); AI 19 V L-N Total (System line-neutral voltage); AI 7 A L1 (Current L1); AI 29 PF Total (Total power factor); AI 31 Hz (Frequency).

How do I check these points on the real Carlo Gavazzi EM24 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Carlo_Gavazzi_EM24_Meter · Carlo_Gavazzi_EM24_Meter_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.