- Home
- BACnet points lists
- Contemporary Controls
- Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Automatic transfer switch controller · BACnet points list
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Kohler MPAC 1500: 135 objects (47 AI, 88 AO), 79 polled by default. Inputs give the system overview word, normal and emergency source line-neutral and line-line voltages, frequencies, load currents, transition data, mode and switch position, and the active time delay. Outputs hold the nominal ratings, time delays and pickup/dropout settings, plus unpolled programmable I/O.
This page lists 135 BACnet objects for the Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX — 88 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Kohler MPAC 1500 transfer switch controller via BASgatewayLX
- Equipment
- Automatic transfer switch controller
- Equipment type
- Other equipment
- BACnet objects
- 135 (88 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- MPAC 1500, Kohler ATS, MPAC1500
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Read the system overview word, source voltages and frequencies and the mode/switch position register. Most outputs are settings, not commands.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | System Overview Word | System overview word (bit-coded) | Read |
| AI 35 | Transition Mode_Mode of Operation_Switch Position | Transition mode, mode and switch position | Read |
| AI 8 | Source N Line Voltage LI -L2 | Normal source voltage L1-L2 | Read |
| AI 11 | Source E Line Voltage L1-L2 | Emergency source voltage L1-L2 | Read |
| AI 14 | Source N Frequency | Normal source frequency | Read |
| AI 15 | Source E Frequency | Emergency source frequency | Read |
| AI 16 | Current LI | Load current L1 | Read |
| AI 51 | Active Time Delay # | Active time delay number | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Time delay and voltage/frequency settings are writable here; changing them alters transfer behaviour.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | System Overview Word | Modbus 400001 | Read | ||
| AI | 2 | Source N Line-Neutral L1-L0 | Modbus 400002 | V | Read | |
| AI | 3 | Source N Line-Neutral L2-L0 | Modbus 400003 | V | Read | |
| AI | 4 | Source N Line-Neutral L3-L0 | Modbus 400004 | V | Read | |
| AI | 5 | Source E Line-Neutral L1-L0 | Modbus 400005 | V | Read | |
| AI | 6 | Source E Line-Neutral L2-L0 | Modbus 400006 | V | Read | |
| AI | 7 | Source E Line-Neutral L3-L0 | Modbus 400007 | V | Read | |
| AImin | 8 | Source N Line Voltage LI -L2 | Modbus 400008 | V | Read | |
| AI | 9 | Source N Line Voltage L2-L3 | Modbus 400009 | V | Read | |
| AI | 10 | Source N Line Voltage L3-L1 | Modbus 400010 | V | Read | |
| AImin | 11 | Source E Line Voltage L1-L2 | Modbus 400011 | V | Read | |
| AI | 12 | Source E Line Voltage L2-L3 | Modbus 400012 | V | Read | |
| AI | 13 | Source E Line Voltage L3-L1 | Modbus 400013 | V | Read | |
| AImin | 14 | Source N Frequency | Modbus 400014 | Hz | Read | |
| AImin | 15 | Source E Frequency | Modbus 400015 | Hz | Read | |
| AImin | 16 | Current LI | Modbus 400016 | A | Read | |
| AI | 17 | Current L2 | Modbus 400017 | A | Read | |
| AI | 18 | Current L3 | Modbus 400018 | A | Read | |
| AI | 19 | Closed Transition In Phase Degree Delta | Modbus 400019 | ° (phase) | Read | |
| AI | 20 | Closed-Programmed Transition Override Mode | Modbus 400039 | Read | ||
| AO | 21 | Password for writing register 40042 | Modbus 400040 | Command | ||
| AI | 22 | Synchronous Voltage Phase Angle | Modbus 400041 | ° (phase) | Read | |
| AO | 23 | Synchronous Voltage Differential | Modbus 400042 | % | Command | |
| AO | 24 | Synchronous Frequency Differential | Modbus 400043 | Hz | Command | |
| AO | 25 | Service Entrance Type | Modbus 400044 | Command | ||
| AI | 26 | Phase Rotation Actual | Modbus 400045 | Read | ||
| AO | 27 | Phase Rotation Expected | Modbus 400046 | Command | ||
| AO | 28 | Nominal Normal Voltage | Modbus 400047 | V | Command | |
| AO | 29 | Nominal Emergency Voltage | Modbus 400048 | V | Command | |
| AO | 30 | Nominal Normal Frequency | Modbus 400049 | Hz | Command | |
| AO | 31 | Nominal Emergency Frequency | Modbus 400050 | Hz | Command | |
| AO | 32 | Normal Number of Phases | Modbus 400051 | Command | ||
| AO | 33 | Emergency Number of Phases | Modbus 400052 | Command | ||
| AO | 34 | Rated Amperage | Modbus 400053 | Command | ||
| AImin | 35 | Transition Mode_Mode of Operation_Switch Position | Modbus 400057 | Read | ||
| AI | 36 | Password for writing register 40057 | Modbus 400058 | Read | ||
| AO | 37 | Normal Engine Start Time Delay | Modbus 400059 | s | Command | |
| AO | 38 | Emergency Engine Start Time Delay | Modbus 400060 | s | Command | |
| AO | 39 | Normal Ext. Engine Start Time Delay | Modbus 400061 | s | Command | |
| AO | 40 | Emergency Ext. Engine Start Time Delay | Modbus 400062 | s | Command | |
| AO | 41 | Normal Engine Cooldown | Modbus 400063 | s | Command | |
| AO | 42 | Emergency Engine Cooldown | Modbus 400064 | s | Command | |
| AO | 43 | Standby to Preferred | Modbus 400065 | s | Command | |
| AO | 44 | Preferred to Standby | Modbus 400066 | s | Command | |
| AO | 45 | Off (Preferred to Standby - Prog. Transition) | Modbus 400067 | s | Command | |
| AO | 46 | Off (Standby to Preferred - Prog. Transition) | Modbus 400068 | s | Command | |
| AO | 47 | Fail to Acquire Preferred | Modbus 400069 | s | Command | |
| AO | 48 | Fail to Acquire Standby | Modbus 400070 | s | Command | |
| AO | 49 | Fail to Synchronize | Modbus 400071 | s | Command | |
| AO | 50 | Fail to Synch. Enable | Modbus 400072 | Command | ||
| AImin | 51 | Active Time Delay # | Modbus 400075 | Read | ||
| AI | 52 | Active Time Delay Remaining | Modbus 400076 | Read | ||
| AI | 53 | Active Time Delay Preset | Modbus 400077 | Read | ||
| AO | 54 | Normal Over Voltage Dropout | Modbus 400078 | % | Command | |
| AO | 55 | Normal Over Voltage Pickup | Modbus 400079 | % | Command | |
| AO | 56 | Normal Under Voltage Pickup | Modbus 400080 | % | Command | |
| AO | 57 | Normal Under Voltage Dropout | Modbus 400081 | % | Command | |
| AO | 58 | Normal Unbalance Enabled | Modbus 400082 | Command | ||
| AO | 59 | Normal Unbalance Voltage Dropout | Modbus 400083 | % | Command | |
| AO | 60 | Normal Unbalance Voltage Pickup | Modbus 400084 | % | Command | |
| AO | 61 | Normal Voltage Debounce Time | Modbus 400085 | s | Command | |
| AO | 62 | Emergency Over Voltage Dropout | Modbus 400086 | % | Command | |
| AO | 63 | Emergency Over Voltage Pickup | Modbus 400087 | % | Command | |
| AO | 64 | Emergency Under Voltage Pickup | Modbus 400088 | % | Command | |
| AO | 65 | Emergency Under Voltage Dropout | Modbus 400089 | % | Command | |
| AO | 66 | Emergency Unbalance Enabled | Modbus 400090 | Command | ||
| AO | 67 | Emergency Unbalance Voltage Dropout | Modbus 400091 | % | Command | |
| AO | 68 | Emergency Unbalance Voltage Pickup | Modbus 400092 | % | Command | |
| AO | 69 | Emergency Voltage Debounce Time | Modbus 400093 | s | Command | |
| AO | 70 | Normal Over Freq Dropout | Modbus 400094 | % | Command | |
| AO | 71 | Normal Over Freq Pickup | Modbus 400095 | % | Command | |
| AO | 72 | Normal Under Freq Dropout | Modbus 400096 | % | Command | |
| AO | 73 | Normal Under Freq Pickup | Modbus 400097 | % | Command | |
| AO | 74 | Normal Freq Dropout Time | Modbus 400098 | s | Command | |
| AO | 75 | Emergency Over Freq Dropout | Modbus 400099 | % | Command | |
| AO | 76 | Emergency Over Freq Pickup | Modbus 400100 | % | Command | |
| AO | 77 | Emergency Under Freq Dropout | Modbus 400101 | % | Command | |
| AO | 78 | Emergency Under Freq Pickup | Modbus 400102 | % | Command | |
| AO | 79 | Emergency Freq Dropout Time | Modbus 400103 | s | Command | |
| AO | 80 | MLB Programmable Output #1 | Modbus 400108; not polled by default | Command | ||
| AO | 81 | MLB Programmable Output #2 | Modbus 400109; not polled by default | Command | ||
| AO | 82 | MLB Programmable Input #1 | Modbus 400111; not polled by default | Command | ||
| AO | 83 | MLB Programmable Input #2 | Modbus 400112; not polled by default | Command | ||
| AO | 84 | Expansion Board Address 1 Output #1 | Modbus 400114; not polled by default | Command | ||
| AO | 85 | Expansion Board Address 1 Output #2 | Modbus 400115; not polled by default | Command | ||
| AO | 86 | Expansion Board Address 1 Output #3 | Modbus 400116; not polled by default | Command | ||
| AO | 87 | Expansion Board Address 1 Output #4 | Modbus 400117; not polled by default | Command | ||
| AO | 88 | Expansion Board Address 1 Output #5 | Modbus 400118; not polled by default | Command | ||
| AO | 89 | Expansion Board Address 1 Output #6 | Modbus 400119; not polled by default | Command | ||
| AO | 90 | Expansion Board Address 2 Output #1 | Modbus 400120; not polled by default | Command | ||
| AO | 91 | Expansion Board Address 2 Output #2 | Modbus 400121; not polled by default | Command | ||
| AO | 92 | Expansion Board Address 2 Output #3 | Modbus 400122; not polled by default | Command | ||
| AO | 93 | Expansion Board Address 2 Output #4 | Modbus 400123; not polled by default | Command | ||
| AO | 94 | Expansion Board Address 2 Output #5 | Modbus 400124; not polled by default | Command | ||
| AO | 95 | Expansion Board Address 2 Output #6 | Modbus 400125; not polled by default | Command | ||
| AO | 96 | Expansion Board Address 3 Output #1 | Modbus 400126; not polled by default | Command | ||
| AO | 97 | Expansion Board Address 3 Output #2 | Modbus 400127; not polled by default | Command | ||
| AO | 98 | Expansion Board Address 3 Output #3 | Modbus 400128; not polled by default | Command | ||
| AO | 99 | Expansion Board Address 3 Output #4 | Modbus 400129; not polled by default | Command | ||
| AO | 100 | Expansion Board Address 3 Output #5 | Modbus 400130; not polled by default | Command | ||
| AO | 101 | Expansion Board Address 3 Output #6 | Modbus 400131; not polled by default | Command | ||
| AO | 102 | Expansion Board Address 4 Output #1 | Modbus 400132; not polled by default | Command | ||
| AO | 103 | Expansion Board Address 4 Output #2 | Modbus 400133; not polled by default | Command | ||
| AO | 104 | Expansion Board Address 4 Output #3 | Modbus 400134; not polled by default | Command | ||
| AO | 105 | Expansion Board Address 4 Output #4 | Modbus 400135; not polled by default | Command | ||
| AO | 106 | Expansion Board Address 4 Output #5 | Modbus 400136; not polled by default | Command | ||
| AO | 107 | Expansion Board Address 4 Output #6 | Modbus 400137; not polled by default | Command | ||
| AO | 108 | Expansion Board Address 1 Input #1 | Modbus 400144; not polled by default | Command | ||
| AO | 109 | Expansion Board Address 1 Input #2 | Modbus 400145; not polled by default | Command | ||
| AO | 110 | Expansion Board Address 2 Input #1 | Modbus 400146; not polled by default | Command | ||
| AO | 111 | Expansion Board Address 2 Input #2 | Modbus 400147; not polled by default | Command | ||
| AO | 112 | Expansion Board Address 3 Input #1 | Modbus 400148; not polled by default | Command | ||
| AO | 113 | Expansion Board Address 3 Input #2 | Modbus 400149; not polled by default | Command | ||
| AO | 114 | Expansion Board Address 4 Input #1 | Modbus 400150; not polled by default | Command | ||
| AO | 115 | Expansion Board Address 4 Input #2 | Modbus 400151; not polled by default | Command | ||
| AI | 116 | Expansion Board Address 1 Board Type | Modbus 400154; not polled by default | Read | ||
| AI | 117 | Expansion Board Address 2 Board Type | Modbus 400155; not polled by default | Read | ||
| AI | 118 | Expansion Board Address 3 Board Type | Modbus 400156; not polled by default | Read | ||
| AI | 119 | Expansion Board Address 4 Board Type | Modbus 400157; not polled by default | Read | ||
| AI | 120 | Alarm Option Board | Modbus 400160; not polled by default | Read | ||
| AI | 121 | Battery Option Board Installed | Modbus 400161; not polled by default | Read | ||
| AI | 122 | MLB Output State | Modbus 400194; not polled by default | Read | ||
| AI | 123 | MLB Input State | Modbus 400195; not polled by default | Read | ||
| AI | 124 | Expansion Board #1 Outputs State | Modbus 400196; not polled by default | Read | ||
| AI | 125 | Expansion Board #2 Outputs State | Modbus 400197; not polled by default | Read | ||
| AI | 126 | Expansion Board #3 Outputs State | Modbus 400198; not polled by default | Read | ||
| AI | 127 | Expansion Board #4 Outputs State | Modbus 400199; not polled by default | Read | ||
| AI | 128 | Expansion Board #1 Inputs State | Modbus 400200; not polled by default | Read | ||
| AI | 129 | Expansion Board #2 Inputs State | Modbus 400201; not polled by default | Read | ||
| AI | 130 | Expansion Board #3 Inputs State | Modbus 400202; not polled by default | Read | ||
| AI | 131 | Expansion Board #4 Inputs State | Modbus 400203; not polled by default | Read | ||
| AI | 132 | Software Controlled Outputs State | Modbus 400250; not polled by default | Read | ||
| AI | 133 | Software Controlled Outputs Assigned | Modbus 400251; not polled by default | Read | ||
| AI | 134 | Remote Monitoring Input State | Modbus 400252; not polled by default | Read | ||
| AI | 135 | Remote Monitoring Input Assigned | Modbus 400253; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Kohler MPAC 1500 point IDs by name
AI1System Overview WordAI2Source N Line-Neutral L1-L0AI3Source N Line-Neutral L2-L0AI4Source N Line-Neutral L3-L0AI5Source E Line-Neutral L1-L0AI6Source E Line-Neutral L2-L0AI7Source E Line-Neutral L3-L0AI8Source N Line Voltage LI -L2AI9Source N Line Voltage L2-L3AI10Source N Line Voltage L3-L1AI11Source E Line Voltage L1-L2AI12Source E Line Voltage L2-L3AI13Source E Line Voltage L3-L1AI14Source N FrequencyAI15Source E FrequencyAI16Current LIAI17Current L2AI18Current L3AI19Closed Transition In Phase Degree DeltaAI20Closed-Programmed Transition Override ModeAO21Password for writing register 40042AI22Synchronous Voltage Phase AngleAO23Synchronous Voltage DifferentialAO24Synchronous Frequency DifferentialAO25Service Entrance TypeAI26Phase Rotation ActualAO27Phase Rotation ExpectedAO28Nominal Normal VoltageAO29Nominal Emergency VoltageAO30Nominal Normal FrequencyAO31Nominal Emergency FrequencyAO32Normal Number of PhasesAO33Emergency Number of PhasesAO34Rated AmperageAI35Transition Mode_Mode of Operation_Switch PositionAI36Password for writing register 40057AO37Normal Engine Start Time DelayAO38Emergency Engine Start Time DelayAO39Normal Ext. Engine Start Time DelayAO40Emergency Ext. Engine Start Time DelayAO41Normal Engine CooldownAO42Emergency Engine CooldownAO43Standby to PreferredAO44Preferred to StandbyAO45Off (Preferred to Standby - Prog. Transition)AO46Off (Standby to Preferred - Prog. Transition)AO47Fail to Acquire PreferredAO48Fail to Acquire StandbyAO49Fail to SynchronizeAO50Fail to Synch. EnableAI51Active Time Delay #AI52Active Time Delay RemainingAI53Active Time Delay PresetAO54Normal Over Voltage DropoutAO55Normal Over Voltage PickupAO56Normal Under Voltage PickupAO57Normal Under Voltage DropoutAO58Normal Unbalance EnabledAO59Normal Unbalance Voltage DropoutAO60Normal Unbalance Voltage PickupAO61Normal Voltage Debounce TimeAO62Emergency Over Voltage DropoutAO63Emergency Over Voltage PickupAO64Emergency Under Voltage PickupAO65Emergency Under Voltage DropoutAO66Emergency Unbalance EnabledAO67Emergency Unbalance Voltage DropoutAO68Emergency Unbalance Voltage PickupAO69Emergency Voltage Debounce TimeAO70Normal Over Freq DropoutAO71Normal Over Freq PickupAO72Normal Under Freq DropoutAO73Normal Under Freq PickupAO74Normal Freq Dropout TimeAO75Emergency Over Freq DropoutAO76Emergency Over Freq PickupAO77Emergency Under Freq DropoutAO78Emergency Under Freq PickupAO79Emergency Freq Dropout TimeAO80MLB Programmable Output #1AO81MLB Programmable Output #2AO82MLB Programmable Input #1AO83MLB Programmable Input #2AO84Expansion Board Address 1 Output #1AO85Expansion Board Address 1 Output #2AO86Expansion Board Address 1 Output #3AO87Expansion Board Address 1 Output #4AO88Expansion Board Address 1 Output #5AO89Expansion Board Address 1 Output #6AO90Expansion Board Address 2 Output #1AO91Expansion Board Address 2 Output #2AO92Expansion Board Address 2 Output #3AO93Expansion Board Address 2 Output #4AO94Expansion Board Address 2 Output #5AO95Expansion Board Address 2 Output #6AO96Expansion Board Address 3 Output #1AO97Expansion Board Address 3 Output #2AO98Expansion Board Address 3 Output #3AO99Expansion Board Address 3 Output #4AO100Expansion Board Address 3 Output #5AO101Expansion Board Address 3 Output #6AO102Expansion Board Address 4 Output #1AO103Expansion Board Address 4 Output #2AO104Expansion Board Address 4 Output #3AO105Expansion Board Address 4 Output #4AO106Expansion Board Address 4 Output #5AO107Expansion Board Address 4 Output #6AO108Expansion Board Address 1 Input #1AO109Expansion Board Address 1 Input #2AO110Expansion Board Address 2 Input #1AO111Expansion Board Address 2 Input #2AO112Expansion Board Address 3 Input #1AO113Expansion Board Address 3 Input #2AO114Expansion Board Address 4 Input #1AO115Expansion Board Address 4 Input #2AI116Expansion Board Address 1 Board TypeAI117Expansion Board Address 2 Board TypeAI118Expansion Board Address 3 Board TypeAI119Expansion Board Address 4 Board TypeAI120Alarm Option BoardAI121Battery Option Board InstalledAI122MLB Output StateAI123MLB Input StateAI124Expansion Board #1 Outputs StateAI125Expansion Board #2 Outputs StateAI126Expansion Board #3 Outputs StateAI127Expansion Board #4 Outputs StateAI128Expansion Board #1 Inputs StateAI129Expansion Board #2 Inputs StateAI130Expansion Board #3 Inputs StateAI131Expansion Board #4 Inputs StateAI132Software Controlled Outputs StateAI133Software Controlled Outputs AssignedAI134Remote Monitoring Input StateAI135Remote Monitoring Input Assigned
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Kohler_MPAC_1500_ATS_a_LX.csv; the profile maps the registers in the MPAC 1500 Modbus register list (https://www.ccontrols.com/support/dp/tp6113.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 79 of the 135 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Kohler MPAC 1500 transfer switch controller via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
How many BACnet points does the Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX have?
This list has 135 BACnet objects: 47 analog inputs, 88 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX BACnet points are writable?
88 of the 135 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Kohler_MPAC_1500_ATS_a (Kohler_MPAC_1500_ATS_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Kohler_MPAC_1500_ATS_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX?
Start with AI 1 System Overview Word (System overview word (bit-coded)); AI 35 Transition Mode_Mode of Operation_Switch Position (Transition mode, mode and switch position); AI 8 Source N Line Voltage LI -L2 (Normal source voltage L1-L2); AI 11 Source E Line Voltage L1-L2 (Emergency source voltage L1-L2); AI 14 Source N Frequency (Normal source frequency); AI 15 Source E Frequency (Emergency source frequency); AI 16 Current LI (Load current L1); AI 51 Active Time Delay # (Active time delay number).
How do I check these points on the real Kohler MPAC 1500 transfer switch controller via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Kohler_MPAC_1500_ATS_a · Kohler_MPAC_1500_ATS_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.