Boiler burner management system · BACnet points list
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Siemens LMV5: 142 objects (85 AI, 31 AO, 26 BI), 60 polled by default. Inputs cover phase, every actuator position, VSD output, fuel type, output, setpoint and actual value, flame signal, throughput, O2 and efficiency (LMV52), counters and the current error, plus the input/output states. Program stop and the load-controller operating mode are polled outputs; Modbus local/remote, remote operating mode, external setpoint W3, preselected output and fuel selection are unpolled outputs.
This page lists 142 BACnet objects for the Contemporary Controls Siemens LMV5 burner management via BASgatewayLX — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Siemens LMV5 burner management via BASgatewayLX
- Equipment
- Boiler burner management system
- Equipment type
- Boilers & water heaters
- BACnet objects
- 142 (31 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Set Modbus mode to remote and the remote operating mode, then write the external setpoint W3 (or a preselected output). Read phase, output, actual value and flame signal.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 61 | Modbus mode: Local / Remote | Modbus mode: local or remote | Command |
| AO 63 | Operating mode in Remote mode Auto Remote ON Remote OFF | Operating mode in remote (auto/on/off) | Command |
| AO 64 | External setpoint W3 Unit: See address 18 / 19 | External setpoint W3 | Command |
| AI 1 | Phase | Burner phase | Read |
| AI 11 | Current output | Current output | Read |
| AI 12 | Current setpoint / temperature / pressure | Current setpoint | Read |
| AI 13 | Actual value / temperature / pressure Unit: See address 18 / 19 | Actual temperature/pressure | Read |
| AI 14 | Flame signal | Flame signal | Read |
| BI 45 | Outputs Alarm | Alarm output | Read |
| AI 24 | Current error: Error code | Current error code | Read |
Enable & remote start
Modbus mode (AO 61) must be remote before the remote operating mode (AO 63) and external setpoint W3 (AO 64) act; all three are unpolled in the published profile.
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Modbus downtime (AO 62) sets how long the LMV5 waits before dropping back to local after communication stops.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Phase | Modbus 400001 | Read | ||
| AI | 2 | Position of currently active fuel actuator | Modbus 400002 | Read | ||
| AI | 3 | Position of gas actuator | Modbus 400003 | Read | ||
| AI | 4 | Position of oil actuator | Modbus 400004 | Read | ||
| AI | 5 | Position of air actuator | Modbus 400005 | Read | ||
| AI | 6 | Position of auxiliary actuator 1 | Modbus 400006 | Read | ||
| AI | 7 | Position of auxiliary actuator 2 | Modbus 400007 | Read | ||
| AI | 8 | Position of auxiliary actuator 3 | Modbus 400008 | Read | ||
| AI | 9 | Manipulated variable for variable speed drive | Modbus 400009 | % | Read | |
| AI | 10 | Current type of fuel | Modbus 400010 | Read | ||
| AImin | 11 | Current output | Modbus 400011 | % | Read | |
| AImin | 12 | Current setpoint / temperature / pressure | Modbus 400012 | Read | ||
| AImin | 13 | Actual value / temperature / pressure Unit: See address 18 / 19 | Modbus 400013 | Read | ||
| AImin | 14 | Flame signal | Modbus 400014 | % | Read | |
| AI | 15 | Current fuel throughput | Modbus 400015 | Read | ||
| AI | 16 | Current O2 value (LMV52...) | Modbus 400016 | % | Read | |
| AI | 17 | Volume unit of gas | Modbus 400017 | Read | ||
| AI | 18 | Volume unit of oil | Modbus 400018 | Read | ||
| AI | 19 | Unit of temperature | Modbus 400019 | Read | ||
| AI | 20 | Unit of pressure | Modbus 400020 | Read | ||
| AI | 21 | Sensor selection | Modbus 400021 | Read | ||
| AI | 22 | Startup counter total | Modbus 400022 | Read | ||
| AI | 23 | Hours run counter | Modbus 400024 | Read | ||
| AImin | 24 | Current error: Error code | Modbus 400026 | Read | ||
| AI | 25 | Current error: Diagnostic code | Modbus 400027 | Read | ||
| AI | 26 | Current error: Error class | Modbus 400028 | Read | ||
| AI | 27 | Current error: Error phase | Modbus 400029 | Read | ||
| AI | 28 | Temperature limiter OFF threshold in degrees C/F | Modbus 400030 | Read | ||
| AI | 29 | Supply air temperature in degrees C / F (LMV52...) | Modbus 400031 | Read | ||
| AI | 30 | Flue gas temperature in degrees Celsius /Fahrenheit (LMV52...) | Modbus 400032 | Read | ||
| AI | 31 | Combustion efficiency (LMV52...) | Modbus 400033 | % | Read | |
| BI | 32 | Inputs Controller ON/OFF | Modbus 400036 bit 0 | Read | ||
| BI | 33 | Inputs Fan contactor contact | Modbus 400036 bit 1 | Read | ||
| BI | 34 | Inputs Fuel selection oil | Modbus 400036 bit 2 | Read | ||
| BI | 35 | Inputs Fuel selection gas | Modbus 400036 bit 3 | Read | ||
| BI | 36 | Inputs Pressure switch-max-oil | Modbus 400036 bit 5 | Read | ||
| BI | 37 | Inputs Pressure switch-min-oil | Modbus 400036 bit 6 | Read | ||
| BI | 38 | Inputs Pressure switch – valve proving | Modbus 400036 bit 7 | Read | ||
| BI | 39 | Inputs Safety loop | Modbus 400036 bit 8 | Read | ||
| BI | 40 | Inputs Pressure switch-min-gas | Modbus 400036 bit 10 | Read | ||
| BI | 41 | Inputs Pressure switch-max-gas | Modbus 400036 bit 11 | Read | ||
| BI | 42 | Inputs LP | Modbus 400036 bit 13 | Read | ||
| BI | 43 | Inputs Start release oil | Modbus 400036 bit 14 | Read | ||
| BI | 44 | Inputs Heavy oil immediate start | Modbus 400036 bit 15 | Read | ||
| BImin | 45 | Outputs Alarm | Modbus 400038 bit 0 | Read | ||
| BI | 46 | Outputs Ignition | Modbus 400038 bit 4 | Read | ||
| BI | 47 | Outputs Start signal / DW valve | Modbus 400038 bit 5 | Read | ||
| BI | 48 | Outputs Fan | Modbus 400038 bit 6 | Read | ||
| BI | 49 | Outputs Oil pump / magnetic coupling | Modbus 400038 bit 7 | Read | ||
| BI | 50 | Outputs Fuel valve SV oil | Modbus 400038 bit 8 | Read | ||
| BI | 51 | Outputs Fuel valve V1 oil | Modbus 400038 bit 9 | Read | ||
| BI | 52 | Outputs Fuel valve V2 oil | Modbus 400038 bit 10 | Read | ||
| BI | 53 | Outputs Fuel valve V3 oil | Modbus 400038 bit 11 | Read | ||
| BI | 54 | Outputs Fuel valve SV gas | Modbus 400038 bit 12 | Read | ||
| BI | 55 | Outputs Fuel valve V1 gas | Modbus 400038 bit 13 | Read | ||
| BI | 56 | Outputs Fuel valve V2 gas | Modbus 400038 bit 14 | Read | ||
| BI | 57 | Outputs Fuel valve PV gas | Modbus 400038 bit 15 | Read | ||
| AO | 58 | Program stop | Modbus 400039 | Command | ||
| AO | 59 | Operating mode with load controller | Modbus 400040 | Command | ||
| AI | 60 | Selection of manual or automatic operation | Modbus 400041 | Read | ||
| AOmin | 61 | Modbus mode: Local / Remote | Modbus 400042; not polled by default | Command | ||
| AO | 62 | Modbus downtime | Modbus 400043; not polled by default | s | Command | |
| AOmin | 63 | Operating mode in Remote mode Auto Remote ON Remote OFF | Modbus 400044; not polled by default | Command | ||
| AOmin | 64 | External setpoint W3 Unit: See address 18 / 19 | Modbus 400045; not polled by default | Command | ||
| AO | 65 | Predefined output mod. / multistage | Modbus 400046; not polled by default | Command | ||
| AO | 66 | Fuel selection AZL... | Modbus 400047; not polled by default | Command | ||
| AO | 67 | Setpoint W1 | Modbus 400048; not polled by default | Command | ||
| AO | 68 | Setpoint W2 | Modbus 400049; not polled by default | Command | ||
| AO | 69 | Weekday | Modbus 400050; not polled by default | Command | ||
| AO | 70 | Date | Modbus 400051; not polled by default | Command | ||
| AO | 71 | Time of day - 1 | Modbus 400054; not polled by default | Command | ||
| AO | 72 | Time of day - 2 | Modbus 400055; not polled by default | Command | ||
| AO | 73 | Time of day -3 | Modbus 400056; not polled by default | Command | ||
| AO | 74 | Hours run gas (adjustable) | Modbus 400057; not polled by default | h | Command | |
| AO | 75 | Hours run oil stage 1 or modulating (adjustable) | Modbus 400059; not polled by default | h | Command | |
| AO | 76 | Hours run oil stage 2 or modulating (adjustable) | Modbus 400061; not polled by default | h | Command | |
| AO | 77 | Hours run oil stage 3 or modulating (adjustable) | Modbus 400063; not polled by default | h | Command | |
| AO | 78 | Hours run total (can be reset) | Modbus 400065; not polled by default | h | Command | |
| AI | 79 | Hours run total (read only) | Modbus 400067; not polled by default | h | Read | |
| AI | 80 | Hours run device connected to power (read only) | Modbus 400069; not polled by default | h | Read | |
| AO | 81 | Startup counter gas (adjustable) | Modbus 400071; not polled by default | Command | ||
| AO | 82 | Startup counter oil (adjustable) | Modbus 400073; not polled by default | Command | ||
| AO | 83 | Startup counter total (can be reset) | Modbus 400075; not polled by default | Command | ||
| AI | 84 | Startup counter total (read only) | Modbus 400077; not polled by default | Read | ||
| AO | 85 | Fuel volume gas (read only) | Modbus 400079; not polled by default | Command | ||
| AO | 86 | Fuel volume oil (read only) | Modbus 400081; not polled by default | Command | ||
| AI | 87 | Number of lockouts | Modbus 400083; not polled by default | Read | ||
| AI | 88 | Extra temperature sensor | Modbus 400084; not polled by default | Read | ||
| AI | 89 | AZL5... ASN -1 | Modbus 400085; not polled by default | Read | ||
| AI | 90 | AZL5... ASN -2 | Modbus 400086; not polled by default | Read | ||
| AI | 91 | AZL5... ASN -3 | Modbus 400087; not polled by default | Read | ||
| AI | 92 | AZL5... ASN -4 | Modbus 400088; not polled by default | Read | ||
| AI | 93 | AZL5... ASN -5 | Modbus 400089; not polled by default | Read | ||
| AI | 94 | AZL5... ASN -6 | Modbus 400090; not polled by default | Read | ||
| AI | 95 | AZL5... ASN -7 | Modbus 400091; not polled by default | Read | ||
| AI | 96 | AZL5... ASN -8 | Modbus 400092; not polled by default | Read | ||
| AI | 97 | AZL5... parameter set code | Modbus 400093; not polled by default | Read | ||
| AI | 98 | AZL5... parameter set version | Modbus 400094; not polled by default | Read | ||
| AI | 99 | AZL5... identification date - 1 | Modbus 400095; not polled by default | Read | ||
| AI | 100 | AZL5... identification date - 2 | Modbus 400096; not polled by default | Read | ||
| AI | 101 | AZL5... identification date - 3 | Modbus 400097; not polled by default | Read | ||
| AI | 102 | AZL5... identification number | Modbus 400098; not polled by default | Read | ||
| AI | 103 | Burner control ASN - 1 | Modbus 400099; not polled by default | Read | ||
| AI | 104 | Burner control ASN - 2 | Modbus 400100; not polled by default | Read | ||
| AI | 105 | Burner control ASN - 3 | Modbus 400101; not polled by default | Read | ||
| AI | 106 | Burner control ASN - 4 | Modbus 400102; not polled by default | Read | ||
| AI | 107 | Burner control ASN - 5 | Modbus 400103; not polled by default | Read | ||
| AI | 108 | Burner control ASN - 6 | Modbus 400104; not polled by default | Read | ||
| AI | 109 | Burner control ASN - 7 | Modbus 400105; not polled by default | Read | ||
| AI | 110 | Burner control ASN - 8 | Modbus 400106; not polled by default | Read | ||
| AI | 111 | Burner control parameter set code | Modbus 400107; not polled by default | Read | ||
| AI | 112 | Burner control parameter set version | Modbus 400108; not polled by default | Read | ||
| AI | 113 | Burner control identification date - 1 | Modbus 400109; not polled by default | Read | ||
| AI | 114 | Burner control identification date - 2 | Modbus 400110; not polled by default | Read | ||
| AI | 115 | Burner control identification date - 3 | Modbus 400111; not polled by default | Read | ||
| AI | 116 | Burner control identification number | Modbus 400112; not polled by default | Read | ||
| AI | 117 | Software version AZL5... | Modbus 400113; not polled by default | Read | ||
| AI | 118 | Software version burner control | Modbus 400114; not polled by default | Read | ||
| AI | 119 | Software version load controller | Modbus 400115; not polled by default | Read | ||
| AI | 120 | Burner identification - 1 | Modbus 400116; not polled by default | Read | ||
| AI | 121 | Burner identification - 2 | Modbus 400117; not polled by default | Read | ||
| AI | 122 | Burner identification - 3 | Modbus 400118; not polled by default | Read | ||
| AI | 123 | Burner identification - 4 | Modbus 400119; not polled by default | Read | ||
| AI | 124 | Burner identification - 5 | Modbus 400120; not polled by default | Read | ||
| AI | 125 | Burner identification - 6 | Modbus 400121; not polled by default | Read | ||
| AI | 126 | Burner identification - 7 | Modbus 400122; not polled by default | Read | ||
| AI | 127 | Burner identification - 8 | Modbus 400123; not polled by default | Read | ||
| AI | 128 | Min-output gas | Modbus 400124; not polled by default | % | Read | |
| AI | 129 | Max-output gas | Modbus 400125; not polled by default | % | Read | |
| AI | 130 | Min-output oil | Modbus 400126; not polled by default | % | Read | |
| AI | 131 | Max-output oil | Modbus 400127; not polled by default | % | Read | |
| AO | 132 | Load limitation enduser (modulating) | Modbus 400128; not polled by default | % | Command | |
| AO | 133 | Load limitation enduser (multistage) | Modbus 400129; not polled by default | Command | ||
| AI | 134 | Temperature limiter switching differential ON | Modbus 400130; not polled by default | Read | ||
| AI | 135 | Measuring range temperature sensor | Modbus 400131; not polled by default | Read | ||
| AI | 136 | Adaption active / inactive | Modbus 400132; not polled by default | Read | ||
| AI | 137 | Adaption state | Modbus 400133; not polled by default | Read | ||
| AO | 138 | Start adaption | Modbus 400134; not polled by default | Command | ||
| AO | 139 | Adaption output | Modbus 400135; not polled by default | % | Command | |
| AO | 140 | P-value | Modbus 400136; not polled by default | % | Command | |
| AO | 141 | I-value | Modbus 400137; not polled by default | s | Command | |
| AI | 142 | D-value | Modbus 400138; not polled by default | s | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Siemens LMV5 point IDs by name
AI1PhaseAI2Position of currently active fuel actuatorAI3Position of gas actuatorAI4Position of oil actuatorAI5Position of air actuatorAI6Position of auxiliary actuator 1AI7Position of auxiliary actuator 2AI8Position of auxiliary actuator 3AI9Manipulated variable for variable speed driveAI10Current type of fuelAI11Current outputAI12Current setpoint / temperature / pressureAI13Actual value / temperature / pressure Unit: See address 18 / 19AI14Flame signalAI15Current fuel throughputAI16Current O2 value (LMV52...)AI17Volume unit of gasAI18Volume unit of oilAI19Unit of temperatureAI20Unit of pressureAI21Sensor selectionAI22Startup counter totalAI23Hours run counterAI24Current error: Error codeAI25Current error: Diagnostic codeAI26Current error: Error classAI27Current error: Error phaseAI28Temperature limiter OFF threshold in degrees C/FAI29Supply air temperature in degrees C / F (LMV52...)AI30Flue gas temperature in degrees Celsius /Fahrenheit (LMV52...)AI31Combustion efficiency (LMV52...)BI32Inputs Controller ON/OFFBI33Inputs Fan contactor contactBI34Inputs Fuel selection oilBI35Inputs Fuel selection gasBI36Inputs Pressure switch-max-oilBI37Inputs Pressure switch-min-oilBI38Inputs Pressure switch – valve provingBI39Inputs Safety loopBI40Inputs Pressure switch-min-gasBI41Inputs Pressure switch-max-gasBI42Inputs LPBI43Inputs Start release oilBI44Inputs Heavy oil immediate startBI45Outputs AlarmBI46Outputs IgnitionBI47Outputs Start signal / DW valveBI48Outputs FanBI49Outputs Oil pump / magnetic couplingBI50Outputs Fuel valve SV oilBI51Outputs Fuel valve V1 oilBI52Outputs Fuel valve V2 oilBI53Outputs Fuel valve V3 oilBI54Outputs Fuel valve SV gasBI55Outputs Fuel valve V1 gasBI56Outputs Fuel valve V2 gasBI57Outputs Fuel valve PV gasAO58Program stopAO59Operating mode with load controllerAI60Selection of manual or automatic operationAO61Modbus mode: Local / RemoteAO62Modbus downtimeAO63Operating mode in Remote mode Auto Remote ON Remote OFFAO64External setpoint W3 Unit: See address 18 / 19AO65Predefined output mod. / multistageAO66Fuel selection AZL...AO67Setpoint W1AO68Setpoint W2AO69WeekdayAO70DateAO71Time of day - 1AO72Time of day - 2AO73Time of day -3AO74Hours run gas (adjustable)AO75Hours run oil stage 1 or modulating (adjustable)AO76Hours run oil stage 2 or modulating (adjustable)AO77Hours run oil stage 3 or modulating (adjustable)AO78Hours run total (can be reset)AI79Hours run total (read only)AI80Hours run device connected to power (read only)AO81Startup counter gas (adjustable)AO82Startup counter oil (adjustable)AO83Startup counter total (can be reset)AI84Startup counter total (read only)AO85Fuel volume gas (read only)AO86Fuel volume oil (read only)AI87Number of lockoutsAI88Extra temperature sensorAI89AZL5... ASN -1AI90AZL5... ASN -2AI91AZL5... ASN -3AI92AZL5... ASN -4AI93AZL5... ASN -5AI94AZL5... ASN -6AI95AZL5... ASN -7AI96AZL5... ASN -8AI97AZL5... parameter set codeAI98AZL5... parameter set versionAI99AZL5... identification date - 1AI100AZL5... identification date - 2AI101AZL5... identification date - 3AI102AZL5... identification numberAI103Burner control ASN - 1AI104Burner control ASN - 2AI105Burner control ASN - 3AI106Burner control ASN - 4AI107Burner control ASN - 5AI108Burner control ASN - 6AI109Burner control ASN - 7AI110Burner control ASN - 8AI111Burner control parameter set codeAI112Burner control parameter set versionAI113Burner control identification date - 1AI114Burner control identification date - 2AI115Burner control identification date - 3AI116Burner control identification numberAI117Software version AZL5...AI118Software version burner controlAI119Software version load controllerAI120Burner identification - 1AI121Burner identification - 2AI122Burner identification - 3AI123Burner identification - 4AI124Burner identification - 5AI125Burner identification - 6AI126Burner identification - 7AI127Burner identification - 8AI128Min-output gasAI129Max-output gasAI130Min-output oilAI131Max-output oilAO132Load limitation enduser (modulating)AO133Load limitation enduser (multistage)AI134Temperature limiter switching differential ONAI135Measuring range temperature sensorAI136Adaption active / inactiveAI137Adaption stateAO138Start adaptionAO139Adaption outputAO140P-valueAO141I-valueAI142D-value
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV5_a_LX.csv; the profile maps the registers in the LMV5 Modbus documentation (https://www.ccontrols.com/support/dp/QSGSection_08_2011modbus.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 60 of the 142 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV5 burner management via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
How many BACnet points does the Contemporary Controls Siemens LMV5 burner management via BASgatewayLX have?
This list has 142 BACnet objects: 85 analog inputs, 31 analog outputs, 26 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Siemens LMV5 burner management via BASgatewayLX BACnet points are writable?
31 of the 142 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Siemens LMV5 burner management via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV5_a (Siemens_Combustion_Control_LMV5_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/SiemensCombustionControlLMV5.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Siemens LMV5 burner management via BASgatewayLX?
Start with AO 61 Modbus mode: Local / Remote (Modbus mode: local or remote); AO 63 Operating mode in Remote mode Auto Remote ON Remote OFF (Operating mode in remote (auto/on/off)); AO 64 External setpoint W3 Unit: See address 18 / 19 (External setpoint W3); AI 1 Phase (Burner phase); AI 11 Current output (Current output); AI 12 Current setpoint / temperature / pressure (Current setpoint); AI 13 Actual value / temperature / pressure Unit: See address 18 / 19 (Actual temperature/pressure); AI 14 Flame signal (Flame signal); BI 45 Outputs Alarm (Alarm output); AI 24 Current error: Error code (Current error code).
How do I enable BMS control of the Contemporary Controls Siemens LMV5 burner management via BASgatewayLX?
Modbus mode (AO 61) must be remote before the remote operating mode (AO 63) and external setpoint W3 (AO 64) act; all three are unpolled in the published profile.
How do I check these points on the real Siemens LMV5 burner management via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV5_a · Siemens_Combustion_Control_LMV5_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.