  4. Siemens LMV3 burner management via BASgatewayLX

Boiler burner management system · BACnet points list

Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Siemens LMV3: 246 objects (221 AI, 13 AO, 11 BI, 1 BO), 26 polled by default. Polled objects give burner control phase, fuel and air actuator positions, VSD output, fuel type, output, flame signal, throughput, the current error and the input/output states; BO 14 switches the controller on/off. Remote-mode, preselected output and counter registers are unpolled outputs.

This page lists 246 BACnet objects for the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Siemens LMV3 burner management via BASgatewayLX
Equipment
Boiler burner management system
Equipment type
Boilers & water heaters
BACnet objects
246 (14 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus
Source document
BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV3_a · Siemens_Combustion_Control_LMV3_a_LX.csv
Download CSV 246 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Siemens LMV3 burner management via BASgatewayLX

Integration in brief

Use Controller on/off (BO 14) for enable; for BMS modulation, enable and set Modbus mode, the remote operating mode and the preselected output. Read phase, output, flame signal and the current error.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 14Controller on / offController on/offCommand
AO 27Modbus modeModbus mode (local/remote)Command
AO 30Preselected target output modulating / multistagePreselected output in remote modeCommand
AI 1Burner control phaseBurner control phaseRead
AI 6Current outputCurrent outputRead
AI 7Flame signalFlame signalRead
BI 20Alarm (AL)Alarm outputRead
AI 10Current error: Error codeCurrent error codeRead

Enable & remote start

Controller on/off (BO 14) is polled by default. Remote output control needs Modbus mode (AO 27), the remote operating mode (AO 29) and the preselected output (AO 30), all unpolled in the published profile.

Network setup

Watch out for

Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

246 of 246 shown
Type
Access
Show
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Burner control phaseModbus 400001Read
AI2Position of current fuel actuatorModbus 400002°Read
AI3Position of air actuatorModbus 400005°Read
AI4Manipulated variable VSDModbus 400009%Read
AI5Current type of fuelModbus 400010Read
AImin6Current outputModbus 400011%Read
AImin7Flame signalModbus 400014%Read
AI8Current fuel throughputModbus 400015Read
AI9Startup counter totalModbus 400022Read
AImin10Current error: Error codeModbus 400026Read
AI11Current error: Diagnostic codeModbus 400027Read
AI12Current error: Error classModbus 400028Read
AI13Current error: Error phaseModbus 400029Read
BOmin14Controller on / offModbus 400036 bit 0Command
BI15Pressure switch valve proving (P LT)Modbus 400036 bit 7Read
BI16Safety loop (SK)Modbus 400036 bit 8Read
BI17Pressure switch-min (Pmin) (pressure switch valve proving)Modbus 400036 bit 10Read
BI18Pressure switch-max (Pmax) / POCModbus 400036 bit 11Read
BI19Air pressure switch (LP)Modbus 400036 bit 13Read
BImin20Alarm (AL)Modbus 400038 bit 0Read
BI21Ignition (Z)Modbus 400038 bit 4Read
BI22Fan (M)Modbus 400038 bit 6Read
BI23Fuel valve 1 (V1)Modbus 400038 bit 13Read
BI24Fuel valve 2 (V2)Modbus 400038 bit 14Read
BI25Fuel valve 3 (V3) / pilot valve (PV)Modbus 400038 bit 15Read
AO26Program stopModbus 400039; not polled by defaultCommand
AOmin27Modbus modeModbus 400042; not polled by defaultCommand
AO28Modbus breakdown timeModbus 400043; not polled by defaultsCommand
AO29Operating mode in remote operationModbus 400044; not polled by defaultCommand
AOmin30Preselected target output modulating / multistageModbus 400046; not polled by default%Command
AO31Hours run fuel 0 resettableModbus 400057; not polled by defaultCommand
AO32Only with LMV26... / LMV36..Hours run fuel 1 resettableModbus 400059; not polled by defaultCommand
AI33Hours run unit liveModbus 400069; not polled by defaultRead
AO34Start counter fuel 0 resettableModbus 400071; not polled by defaultCommand
AO35Only with LMV26... / LMV36...Start counter fuel 1 resettableModbus 400073; not polled by defaultCommand
AI36Start counter totalModbus 400077; not polled by defaultRead
AO37Fuel volume fuel 0 0 = resettableModbus 400079; not polled by defaultCommand
AO38Only with LMV26... / LMV36 Fuel volume fuel 1 1 = resettableModbus 400081; not polled by defaultCommand
AI39Number of faultsModbus 400083Read
AO40Preselected output in the event breaks downModbus 400085; not polled by defaultCommand
AO41Only with LMV26... / LMV36 Preselected output event breaks downModbus 400086; not polled by defaultCommand
AI42Burner control type reference (ASN) ASCII Word 01Modbus 400099; not polled by defaultRead
AI43Burner control type reference (ASN) ASCII Word 02Modbus 400100; not polled by defaultRead
AI44Burner control type reference (ASN) ASCII Word 03Modbus 400101; not polled by defaultRead
AI45Burner control type reference (ASN) ASCII Word 04Modbus 400102; not polled by defaultRead
AI46Burner control type reference (ASN) ASCII Word 05Modbus 400103; not polled by defaultRead
AI47Burner control type reference (ASN) ASCII Word 06Modbus 400104; not polled by defaultRead
AI48Burner control type reference (ASN) ASCII Word 07Modbus 400105; not polled by defaultRead
AI49Burner control type reference (ASN) ASCII Word 08Modbus 400106; not polled by defaultRead
AI50Burner control parameter set codeModbus 400107; not polled by defaultRead
AI51Burner control parameter set versionModbus 400108; not polled by defaultRead
AI52Burner control identification date Word 01Modbus 400109; not polled by defaultRead
AI53Burner control identification date Word 02Modbus 400110; not polled by defaultRead
AI54Burner control identification date Word 03Modbus 400111; not polled by defaultRead
AI55Burner control identification numberModbus 400112; not polled by defaultRead
AI56Software version burner controlModbus 400114; not polled by defaultRead
AI57Burner identification Word 01Modbus 400116; not polled by defaultRead
AI58Burner identification Word 02Modbus 400117; not polled by defaultRead
AI59Burner identification Word 03Modbus 400118; not polled by defaultRead
AI60Burner identification Word 04Modbus 400119; not polled by defaultRead
AI61Burner identification Word 05Modbus 400120; not polled by defaultRead
AI62Burner identification Word 06Modbus 400121; not polled by defaultRead
AI63Burner identification Word 07Modbus 400122; not polled by defaultRead
AI64Burner identification Word 08Modbus 400123; not polled by defaultRead
AI65Minimum output fuel 0Modbus 400124; not polled by default%Read
AI66Maximum output fuel 0Modbus 400125; not polled by defaultRead
AI67Only with LMV26... / LMV36 Minimum output fuel 1Modbus 400126; not polled by defaultRead
AI68Only with LMV26... / LMV36..Maximum output fuel 1Modbus 400127; not polled by defaultRead
AI69Operation mode of burnerModbus 400128; not polled by defaultRead
AI70Only LMV26... / LMV36..Operation mode of burner fuel 1Modbus 400129; not polled by defaultRead
AI71Switching cycles Revert to pilotModbus 400130; not polled by defaultRead
AI72Error Error codeModbus 400545; not polled by defaultRead
AI73Error Diagnostic codeModbus 400546; not polled by defaultRead
AI74Error Error classModbus 400547; not polled by defaultRead
AI75Error Error phaseModbus 400548; not polled by defaultRead
AI76Error Type of fuelModbus 400549; not polled by defaultRead
AI77Error OutputModbus 400550; not polled by defaultRead
AI78Error Start counter totalModbus 400551; not polled by defaultRead
AI79Error Error code -1Modbus 400553; not polled by defaultRead
AI80Error Diagnostic code -1Modbus 400554; not polled by defaultRead
AI81Error Error class -1Modbus 400555; not polled by defaultRead
AI82Error Error phase -1Modbus 400556; not polled by defaultRead
AI83Error Type of fuel-1Modbus 400557; not polled by defaultRead
AI84Error Output -1Modbus 400558; not polled by defaultRead
AI85Error Start counter total -1Modbus 400559; not polled by defaultRead
AI86Error Error code -2Modbus 400561; not polled by defaultRead
AI87Error Diagnostic code -2Modbus 400562; not polled by defaultRead
AI88Error Error class -2Modbus 400563; not polled by defaultRead
AI89Error Error phase -2Modbus 400564; not polled by defaultRead
AI90Error Type of fuel-2Modbus 400565; not polled by defaultRead
AI91Error Output -2Modbus 400566; not polled by defaultRead
AI92Error Start counter total -2Modbus 400567; not polled by defaultRead
AI93Error Error code -3Modbus 400569; not polled by defaultRead
AI94Error Diagnostic code -3Modbus 400570; not polled by defaultRead
AI95Error Error class -3Modbus 400571; not polled by defaultRead
AI96Error Error phase -3Modbus 400572; not polled by defaultRead
AI97Error Type of fuel-3Modbus 400573; not polled by defaultRead
AI98Error Output -3Modbus 400574; not polled by defaultRead
AI99Error Start counter total -3Modbus 400575; not polled by defaultRead
AI100Error Error code -4Modbus 400577; not polled by defaultRead
AI101Error Diagnostic code -4Modbus 400578; not polled by defaultRead
AI102Error Error class -4Modbus 400579; not polled by defaultRead
AI103Error Error phase -4Modbus 400580; not polled by defaultRead
AI104Error Type of fuel-4Modbus 400581; not polled by defaultRead
AI105Error Output -4Modbus 400582; not polled by defaultRead
AI106Error Start counter total -4Modbus 400583; not polled by defaultRead
AI107Error Error code -5Modbus 400585; not polled by defaultRead
AI108Error Diagnostic code -5Modbus 400586; not polled by defaultRead
AI109Error Error class -5Modbus 400587; not polled by defaultRead
AI110Error Error phase -5Modbus 400588; not polled by defaultRead
AI111Error Type of fuel-5Modbus 400589; not polled by defaultRead
AI112Error Output -5Modbus 400590; not polled by defaultRead
AI113Error Start counter total -5Modbus 400591; not polled by defaultRead
AI114Error Error code -6Modbus 400593; not polled by defaultRead
AI115Error Diagnostic code -6Modbus 400594; not polled by defaultRead
AI116Error Error class -6Modbus 400595; not polled by defaultRead
AI117Error Error phase -6Modbus 400596; not polled by defaultRead
AI118Error Type of fuel-6Modbus 400597; not polled by defaultRead
AI119Error Output -6Modbus 400598; not polled by defaultRead
AI120Error Start counter total -6Modbus 400599; not polled by defaultRead
AI121Error Error code -7Modbus 400601; not polled by defaultRead
AI122Error Diagnostic code -7Modbus 400602; not polled by defaultRead
AI123Error Error class -7Modbus 400603; not polled by defaultRead
AI124Error Error phase -7Modbus 400604; not polled by defaultRead
AI125Error Type of fuel-7Modbus 400605; not polled by defaultRead
AI126Error Output -7Modbus 400606; not polled by defaultRead
AI127Error Start counter total -7Modbus 400607; not polled by defaultRead
AI128Error Error code -8Modbus 400609; not polled by defaultRead
AI129Error Diagnostic code -8Modbus 400610; not polled by defaultRead
AI130Error Error class -8Modbus 400611; not polled by defaultRead
AI131Error Error phase -8Modbus 400612; not polled by defaultRead
AI132Error Type of fuel-8Modbus 400613; not polled by defaultRead
AI133Error Output -8Modbus 400614; not polled by defaultRead
AI134Error Start counter total -8Modbus 400615; not polled by defaultRead
AI135Error Error code -9Modbus 400617; not polled by defaultRead
AI136Error Diagnostic code -9Modbus 400618; not polled by defaultRead
AI137Error Error class -9Modbus 400619; not polled by defaultRead
AI138Error Error phase -9Modbus 400620; not polled by defaultRead
AI139Error Type of fuel-9Modbus 400621; not polled by defaultRead
AI140Error Output -9Modbus 400622; not polled by defaultRead
AI141Error Start counter total -9Modbus 400623; not polled by defaultRead
AI142Error Error code -10Modbus 400625; not polled by defaultRead
AI143Error Diagnostic code -10Modbus 400626; not polled by defaultRead
AI144Error Error class -10Modbus 400627; not polled by defaultRead
AI145Error Error phase -10Modbus 400628; not polled by defaultRead
AI146Error Type of fuel-10Modbus 400629; not polled by defaultRead
AI147Error Output -10Modbus 400630; not polled by defaultRead
AI148Error Start counter total -10Modbus 400631; not polled by defaultRead
AI149Error Error code -11Modbus 400633; not polled by defaultRead
AI150Error Diagnostic code -11Modbus 400634; not polled by defaultRead
AI151Error Error class -11Modbus 400635; not polled by defaultRead
AI152Error Error phase -11Modbus 400636; not polled by defaultRead
AI153Error Type of fuel-11Modbus 400637; not polled by defaultRead
AI154Error Output -11Modbus 400638; not polled by defaultRead
AI155Error Start counter total -11Modbus 400640; not polled by defaultRead
AI156Error Error code -12Modbus 400641; not polled by defaultRead
AI157Error Diagnostic code -12Modbus 400642; not polled by defaultRead
AI158Error Error class -12Modbus 400643; not polled by defaultRead
AI159Error Error phase -12Modbus 400644; not polled by defaultRead
AI160Error Type of fuel-12Modbus 400645; not polled by defaultRead
AI161Error Output -12Modbus 400646; not polled by defaultRead
AI162Error Start counter total -12Modbus 400647; not polled by defaultRead
AI163Error Error code -13Modbus 400649; not polled by defaultRead
AI164Error Diagnostic code -13Modbus 400650; not polled by defaultRead
AI165Error Error class -13Modbus 400651; not polled by defaultRead
AI166Error Error phase -13Modbus 400652; not polled by defaultRead
AI167Error Type of fuel-13Modbus 400653; not polled by defaultRead
AI168Error Output -13Modbus 400654; not polled by defaultRead
AI169Error Start counter total -13Modbus 400655; not polled by defaultRead
AI170Error Error code -14Modbus 400657; not polled by defaultRead
AI171Error Diagnostic code -14Modbus 400658; not polled by defaultRead
AI172Error Error class -14Modbus 400659; not polled by defaultRead
AI173Error Error phase -14Modbus 400660; not polled by defaultRead
AI174Error Type of fuel-14Modbus 400661; not polled by defaultRead
AI175Error Output -14Modbus 400662; not polled by defaultRead
AI176Error Start counter total -14Modbus 400663; not polled by defaultRead
AI177Error Error code -15Modbus 400665; not polled by defaultRead
AI178Error Diagnostic code -15Modbus 400666; not polled by defaultRead
AI179Error Error class -15Modbus 400667; not polled by defaultRead
AI180Error Error phase -15Modbus 400668; not polled by defaultRead
AI181Error Type of fuel-15Modbus 400669; not polled by defaultRead
AI182Error Output -15Modbus 400670; not polled by defaultRead
AI183Error Start counter total -15Modbus 400671; not polled by defaultRead
AI184Error Error code -16Modbus 400673; not polled by defaultRead
AI185Error Diagnostic code -16Modbus 400674; not polled by defaultRead
AI186Error Error class -16Modbus 400675; not polled by defaultRead
AI187Error Error phase -16Modbus 400676; not polled by defaultRead
AI188Error Type of fuel-16Modbus 400677; not polled by defaultRead
AI189Error Output -16Modbus 400678; not polled by defaultRead
AI190Error Start counter total -16Modbus 400679; not polled by defaultRead
AI191Error Error code -17Modbus 400681; not polled by defaultRead
AI192Error Diagnostic code -17Modbus 400682; not polled by defaultRead
AI193Error Error class -17Modbus 400683; not polled by defaultRead
AI194Error Error phase -17Modbus 400684; not polled by defaultRead
AI195Error Type of fuel-17Modbus 400685; not polled by defaultRead
AI196Error Output -17Modbus 400686; not polled by defaultRead
AI197Error Start counter total -17Modbus 400687; not polled by defaultRead
AI198Error Error code -18Modbus 400689; not polled by defaultRead
AI199Error Diagnostic code -18Modbus 400690; not polled by defaultRead
AI200Error Error class -18Modbus 400691; not polled by defaultRead
AI201Error Error phase -18Modbus 400692; not polled by defaultRead
AI202Error Type of fuel-18Modbus 400693; not polled by defaultRead
AI203Error Output -18Modbus 400694; not polled by defaultRead
AI204Error Start counter total -18Modbus 400695; not polled by defaultRead
AI205Error Error code -19Modbus 400697; not polled by defaultRead
AI206Error Diagnostic code -19Modbus 400698; not polled by defaultRead
AI207Error Error class -19Modbus 400699; not polled by defaultRead
AI208Error Error phase -19Modbus 400700; not polled by defaultRead
AI209Error Type of fuel-19Modbus 400701; not polled by defaultRead
AI210Error Output -19Modbus 400702; not polled by defaultRead
AI211Error Start counter total -19Modbus 400703; not polled by defaultRead
AI212Error Error code -20Modbus 400705; not polled by defaultRead
AI213Error Diagnostic code -20Modbus 400706; not polled by defaultRead
AI214Error Error class -20Modbus 400707; not polled by defaultRead
AI215Error Error phase -20Modbus 400708; not polled by defaultRead
AI216Error Type of fuel-20Modbus 400709; not polled by defaultRead
AI217Error Output -20Modbus 400710; not polled by defaultRead
AI218Error Start counter total -20Modbus 400711; not polled by defaultRead
AI219Error Error code -21Modbus 400713; not polled by defaultRead
AI220Error Diagnostic code -21Modbus 400714; not polled by defaultRead
AI221Error Error class -21Modbus 400715; not polled by defaultRead
AI222Error Error phase -21Modbus 400716; not polled by defaultRead
AI223Error Type of fuel-21Modbus 400717; not polled by defaultRead
AI224Error Output -21Modbus 400718; not polled by defaultRead
AI225Error Start counter total -21Modbus 400719; not polled by defaultRead
AI226Error Error code -22Modbus 400721; not polled by defaultRead
AI227Error Diagnostic code -22Modbus 400722; not polled by defaultRead
AI228Error Error class -22Modbus 400723; not polled by defaultRead
AI229Error Error phase -22Modbus 400724; not polled by defaultRead
AI230Error Type of fuel-22Modbus 400725; not polled by defaultRead
AI231Error Output -22Modbus 400726; not polled by defaultRead
AI232Error Start counter total -22Modbus 400727; not polled by defaultRead
AI233Error Error code -23Modbus 400729; not polled by defaultRead
AI234Error Diagnostic code -23Modbus 400730; not polled by defaultRead
AI235Error Error class -23Modbus 400731; not polled by defaultRead
AI236Error Error phase -23Modbus 400732; not polled by defaultRead
AI237Error Type of fuel-23Modbus 400733; not polled by defaultRead
AI238Error Output -23Modbus 400734; not polled by defaultRead
AI239Error Start counter total -23Modbus 400735; not polled by defaultRead
AI240Error Error code -24Modbus 400737; not polled by defaultRead
AI241Error Diagnostic code -24Modbus 400738; not polled by defaultRead
AI242Error Error class -24Modbus 400739; not polled by defaultRead
AI243Error Error phase -24Modbus 400740; not polled by defaultRead
AI244Error Type of fuel-24Modbus 400741; not polled by defaultRead
AI245Error Output -24Modbus 400742; not polled by defaultRead
AI246Error Start counter total -24Modbus 400743; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX Siemens LMV3 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV3 burner management via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX

How many BACnet points does the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX have?

This list has 246 BACnet objects: 221 analog inputs, 13 analog outputs, 11 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet points are writable?

14 of the 246 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV3_a (Siemens_Combustion_Control_LMV3_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Siemens_Combustion_Control_LMV3_a_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX?

Start with BO 14 Controller on / off (Controller on/off); AO 27 Modbus mode (Modbus mode (local/remote)); AO 30 Preselected target output modulating / multistage (Preselected output in remote mode); AI 1 Burner control phase (Burner control phase); AI 6 Current output (Current output); AI 7 Flame signal (Flame signal); BI 20 Alarm (AL) (Alarm output); AI 10 Current error: Error code (Current error code).

How do I enable BMS control of the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX?

Controller on/off (BO 14) is polled by default. Remote output control needs Modbus mode (AO 27), the remote operating mode (AO 29) and the preselected output (AO 30), all unpolled in the published profile.

How do I check these points on the real Siemens LMV3 burner management via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV3_a · Siemens_Combustion_Control_LMV3_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.