Boiler burner management system · BACnet points list
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Siemens LMV3: 246 objects (221 AI, 13 AO, 11 BI, 1 BO), 26 polled by default. Polled objects give burner control phase, fuel and air actuator positions, VSD output, fuel type, output, flame signal, throughput, the current error and the input/output states; BO 14 switches the controller on/off. Remote-mode, preselected output and counter registers are unpolled outputs.
This page lists 246 BACnet objects for the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Siemens LMV3 burner management via BASgatewayLX
- Equipment
- Boiler burner management system
- Equipment type
- Boilers & water heaters
- BACnet objects
- 246 (14 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Use Controller on/off (BO 14) for enable; for BMS modulation, enable and set Modbus mode, the remote operating mode and the preselected output. Read phase, output, flame signal and the current error.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 14 | Controller on / off | Controller on/off | Command |
| AO 27 | Modbus mode | Modbus mode (local/remote) | Command |
| AO 30 | Preselected target output modulating / multistage | Preselected output in remote mode | Command |
| AI 1 | Burner control phase | Burner control phase | Read |
| AI 6 | Current output | Current output | Read |
| AI 7 | Flame signal | Flame signal | Read |
| BI 20 | Alarm (AL) | Alarm output | Read |
| AI 10 | Current error: Error code | Current error code | Read |
Enable & remote start
Controller on/off (BO 14) is polled by default. Remote output control needs Modbus mode (AO 27), the remote operating mode (AO 29) and the preselected output (AO 30), all unpolled in the published profile.
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Modbus breakdown time (AO 28) and the output preselected for a communication breakdown (AO 40) set what the LMV does if Modbus stops; check them before using remote mode.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Burner control phase | Modbus 400001 | Read | ||
| AI | 2 | Position of current fuel actuator | Modbus 400002 | ° | Read | |
| AI | 3 | Position of air actuator | Modbus 400005 | ° | Read | |
| AI | 4 | Manipulated variable VSD | Modbus 400009 | % | Read | |
| AI | 5 | Current type of fuel | Modbus 400010 | Read | ||
| AImin | 6 | Current output | Modbus 400011 | % | Read | |
| AImin | 7 | Flame signal | Modbus 400014 | % | Read | |
| AI | 8 | Current fuel throughput | Modbus 400015 | Read | ||
| AI | 9 | Startup counter total | Modbus 400022 | Read | ||
| AImin | 10 | Current error: Error code | Modbus 400026 | Read | ||
| AI | 11 | Current error: Diagnostic code | Modbus 400027 | Read | ||
| AI | 12 | Current error: Error class | Modbus 400028 | Read | ||
| AI | 13 | Current error: Error phase | Modbus 400029 | Read | ||
| BOmin | 14 | Controller on / off | Modbus 400036 bit 0 | Command | ||
| BI | 15 | Pressure switch valve proving (P LT) | Modbus 400036 bit 7 | Read | ||
| BI | 16 | Safety loop (SK) | Modbus 400036 bit 8 | Read | ||
| BI | 17 | Pressure switch-min (Pmin) (pressure switch valve proving) | Modbus 400036 bit 10 | Read | ||
| BI | 18 | Pressure switch-max (Pmax) / POC | Modbus 400036 bit 11 | Read | ||
| BI | 19 | Air pressure switch (LP) | Modbus 400036 bit 13 | Read | ||
| BImin | 20 | Alarm (AL) | Modbus 400038 bit 0 | Read | ||
| BI | 21 | Ignition (Z) | Modbus 400038 bit 4 | Read | ||
| BI | 22 | Fan (M) | Modbus 400038 bit 6 | Read | ||
| BI | 23 | Fuel valve 1 (V1) | Modbus 400038 bit 13 | Read | ||
| BI | 24 | Fuel valve 2 (V2) | Modbus 400038 bit 14 | Read | ||
| BI | 25 | Fuel valve 3 (V3) / pilot valve (PV) | Modbus 400038 bit 15 | Read | ||
| AO | 26 | Program stop | Modbus 400039; not polled by default | Command | ||
| AOmin | 27 | Modbus mode | Modbus 400042; not polled by default | Command | ||
| AO | 28 | Modbus breakdown time | Modbus 400043; not polled by default | s | Command | |
| AO | 29 | Operating mode in remote operation | Modbus 400044; not polled by default | Command | ||
| AOmin | 30 | Preselected target output modulating / multistage | Modbus 400046; not polled by default | % | Command | |
| AO | 31 | Hours run fuel 0 resettable | Modbus 400057; not polled by default | Command | ||
| AO | 32 | Only with LMV26... / LMV36..Hours run fuel 1 resettable | Modbus 400059; not polled by default | Command | ||
| AI | 33 | Hours run unit live | Modbus 400069; not polled by default | Read | ||
| AO | 34 | Start counter fuel 0 resettable | Modbus 400071; not polled by default | Command | ||
| AO | 35 | Only with LMV26... / LMV36...Start counter fuel 1 resettable | Modbus 400073; not polled by default | Command | ||
| AI | 36 | Start counter total | Modbus 400077; not polled by default | Read | ||
| AO | 37 | Fuel volume fuel 0 0 = resettable | Modbus 400079; not polled by default | Command | ||
| AO | 38 | Only with LMV26... / LMV36 Fuel volume fuel 1 1 = resettable | Modbus 400081; not polled by default | Command | ||
| AI | 39 | Number of faults | Modbus 400083 | Read | ||
| AO | 40 | Preselected output in the event breaks down | Modbus 400085; not polled by default | Command | ||
| AO | 41 | Only with LMV26... / LMV36 Preselected output event breaks down | Modbus 400086; not polled by default | Command | ||
| AI | 42 | Burner control type reference (ASN) ASCII Word 01 | Modbus 400099; not polled by default | Read | ||
| AI | 43 | Burner control type reference (ASN) ASCII Word 02 | Modbus 400100; not polled by default | Read | ||
| AI | 44 | Burner control type reference (ASN) ASCII Word 03 | Modbus 400101; not polled by default | Read | ||
| AI | 45 | Burner control type reference (ASN) ASCII Word 04 | Modbus 400102; not polled by default | Read | ||
| AI | 46 | Burner control type reference (ASN) ASCII Word 05 | Modbus 400103; not polled by default | Read | ||
| AI | 47 | Burner control type reference (ASN) ASCII Word 06 | Modbus 400104; not polled by default | Read | ||
| AI | 48 | Burner control type reference (ASN) ASCII Word 07 | Modbus 400105; not polled by default | Read | ||
| AI | 49 | Burner control type reference (ASN) ASCII Word 08 | Modbus 400106; not polled by default | Read | ||
| AI | 50 | Burner control parameter set code | Modbus 400107; not polled by default | Read | ||
| AI | 51 | Burner control parameter set version | Modbus 400108; not polled by default | Read | ||
| AI | 52 | Burner control identification date Word 01 | Modbus 400109; not polled by default | Read | ||
| AI | 53 | Burner control identification date Word 02 | Modbus 400110; not polled by default | Read | ||
| AI | 54 | Burner control identification date Word 03 | Modbus 400111; not polled by default | Read | ||
| AI | 55 | Burner control identification number | Modbus 400112; not polled by default | Read | ||
| AI | 56 | Software version burner control | Modbus 400114; not polled by default | Read | ||
| AI | 57 | Burner identification Word 01 | Modbus 400116; not polled by default | Read | ||
| AI | 58 | Burner identification Word 02 | Modbus 400117; not polled by default | Read | ||
| AI | 59 | Burner identification Word 03 | Modbus 400118; not polled by default | Read | ||
| AI | 60 | Burner identification Word 04 | Modbus 400119; not polled by default | Read | ||
| AI | 61 | Burner identification Word 05 | Modbus 400120; not polled by default | Read | ||
| AI | 62 | Burner identification Word 06 | Modbus 400121; not polled by default | Read | ||
| AI | 63 | Burner identification Word 07 | Modbus 400122; not polled by default | Read | ||
| AI | 64 | Burner identification Word 08 | Modbus 400123; not polled by default | Read | ||
| AI | 65 | Minimum output fuel 0 | Modbus 400124; not polled by default | % | Read | |
| AI | 66 | Maximum output fuel 0 | Modbus 400125; not polled by default | Read | ||
| AI | 67 | Only with LMV26... / LMV36 Minimum output fuel 1 | Modbus 400126; not polled by default | Read | ||
| AI | 68 | Only with LMV26... / LMV36..Maximum output fuel 1 | Modbus 400127; not polled by default | Read | ||
| AI | 69 | Operation mode of burner | Modbus 400128; not polled by default | Read | ||
| AI | 70 | Only LMV26... / LMV36..Operation mode of burner fuel 1 | Modbus 400129; not polled by default | Read | ||
| AI | 71 | Switching cycles Revert to pilot | Modbus 400130; not polled by default | Read | ||
| AI | 72 | Error Error code | Modbus 400545; not polled by default | Read | ||
| AI | 73 | Error Diagnostic code | Modbus 400546; not polled by default | Read | ||
| AI | 74 | Error Error class | Modbus 400547; not polled by default | Read | ||
| AI | 75 | Error Error phase | Modbus 400548; not polled by default | Read | ||
| AI | 76 | Error Type of fuel | Modbus 400549; not polled by default | Read | ||
| AI | 77 | Error Output | Modbus 400550; not polled by default | Read | ||
| AI | 78 | Error Start counter total | Modbus 400551; not polled by default | Read | ||
| AI | 79 | Error Error code -1 | Modbus 400553; not polled by default | Read | ||
| AI | 80 | Error Diagnostic code -1 | Modbus 400554; not polled by default | Read | ||
| AI | 81 | Error Error class -1 | Modbus 400555; not polled by default | Read | ||
| AI | 82 | Error Error phase -1 | Modbus 400556; not polled by default | Read | ||
| AI | 83 | Error Type of fuel-1 | Modbus 400557; not polled by default | Read | ||
| AI | 84 | Error Output -1 | Modbus 400558; not polled by default | Read | ||
| AI | 85 | Error Start counter total -1 | Modbus 400559; not polled by default | Read | ||
| AI | 86 | Error Error code -2 | Modbus 400561; not polled by default | Read | ||
| AI | 87 | Error Diagnostic code -2 | Modbus 400562; not polled by default | Read | ||
| AI | 88 | Error Error class -2 | Modbus 400563; not polled by default | Read | ||
| AI | 89 | Error Error phase -2 | Modbus 400564; not polled by default | Read | ||
| AI | 90 | Error Type of fuel-2 | Modbus 400565; not polled by default | Read | ||
| AI | 91 | Error Output -2 | Modbus 400566; not polled by default | Read | ||
| AI | 92 | Error Start counter total -2 | Modbus 400567; not polled by default | Read | ||
| AI | 93 | Error Error code -3 | Modbus 400569; not polled by default | Read | ||
| AI | 94 | Error Diagnostic code -3 | Modbus 400570; not polled by default | Read | ||
| AI | 95 | Error Error class -3 | Modbus 400571; not polled by default | Read | ||
| AI | 96 | Error Error phase -3 | Modbus 400572; not polled by default | Read | ||
| AI | 97 | Error Type of fuel-3 | Modbus 400573; not polled by default | Read | ||
| AI | 98 | Error Output -3 | Modbus 400574; not polled by default | Read | ||
| AI | 99 | Error Start counter total -3 | Modbus 400575; not polled by default | Read | ||
| AI | 100 | Error Error code -4 | Modbus 400577; not polled by default | Read | ||
| AI | 101 | Error Diagnostic code -4 | Modbus 400578; not polled by default | Read | ||
| AI | 102 | Error Error class -4 | Modbus 400579; not polled by default | Read | ||
| AI | 103 | Error Error phase -4 | Modbus 400580; not polled by default | Read | ||
| AI | 104 | Error Type of fuel-4 | Modbus 400581; not polled by default | Read | ||
| AI | 105 | Error Output -4 | Modbus 400582; not polled by default | Read | ||
| AI | 106 | Error Start counter total -4 | Modbus 400583; not polled by default | Read | ||
| AI | 107 | Error Error code -5 | Modbus 400585; not polled by default | Read | ||
| AI | 108 | Error Diagnostic code -5 | Modbus 400586; not polled by default | Read | ||
| AI | 109 | Error Error class -5 | Modbus 400587; not polled by default | Read | ||
| AI | 110 | Error Error phase -5 | Modbus 400588; not polled by default | Read | ||
| AI | 111 | Error Type of fuel-5 | Modbus 400589; not polled by default | Read | ||
| AI | 112 | Error Output -5 | Modbus 400590; not polled by default | Read | ||
| AI | 113 | Error Start counter total -5 | Modbus 400591; not polled by default | Read | ||
| AI | 114 | Error Error code -6 | Modbus 400593; not polled by default | Read | ||
| AI | 115 | Error Diagnostic code -6 | Modbus 400594; not polled by default | Read | ||
| AI | 116 | Error Error class -6 | Modbus 400595; not polled by default | Read | ||
| AI | 117 | Error Error phase -6 | Modbus 400596; not polled by default | Read | ||
| AI | 118 | Error Type of fuel-6 | Modbus 400597; not polled by default | Read | ||
| AI | 119 | Error Output -6 | Modbus 400598; not polled by default | Read | ||
| AI | 120 | Error Start counter total -6 | Modbus 400599; not polled by default | Read | ||
| AI | 121 | Error Error code -7 | Modbus 400601; not polled by default | Read | ||
| AI | 122 | Error Diagnostic code -7 | Modbus 400602; not polled by default | Read | ||
| AI | 123 | Error Error class -7 | Modbus 400603; not polled by default | Read | ||
| AI | 124 | Error Error phase -7 | Modbus 400604; not polled by default | Read | ||
| AI | 125 | Error Type of fuel-7 | Modbus 400605; not polled by default | Read | ||
| AI | 126 | Error Output -7 | Modbus 400606; not polled by default | Read | ||
| AI | 127 | Error Start counter total -7 | Modbus 400607; not polled by default | Read | ||
| AI | 128 | Error Error code -8 | Modbus 400609; not polled by default | Read | ||
| AI | 129 | Error Diagnostic code -8 | Modbus 400610; not polled by default | Read | ||
| AI | 130 | Error Error class -8 | Modbus 400611; not polled by default | Read | ||
| AI | 131 | Error Error phase -8 | Modbus 400612; not polled by default | Read | ||
| AI | 132 | Error Type of fuel-8 | Modbus 400613; not polled by default | Read | ||
| AI | 133 | Error Output -8 | Modbus 400614; not polled by default | Read | ||
| AI | 134 | Error Start counter total -8 | Modbus 400615; not polled by default | Read | ||
| AI | 135 | Error Error code -9 | Modbus 400617; not polled by default | Read | ||
| AI | 136 | Error Diagnostic code -9 | Modbus 400618; not polled by default | Read | ||
| AI | 137 | Error Error class -9 | Modbus 400619; not polled by default | Read | ||
| AI | 138 | Error Error phase -9 | Modbus 400620; not polled by default | Read | ||
| AI | 139 | Error Type of fuel-9 | Modbus 400621; not polled by default | Read | ||
| AI | 140 | Error Output -9 | Modbus 400622; not polled by default | Read | ||
| AI | 141 | Error Start counter total -9 | Modbus 400623; not polled by default | Read | ||
| AI | 142 | Error Error code -10 | Modbus 400625; not polled by default | Read | ||
| AI | 143 | Error Diagnostic code -10 | Modbus 400626; not polled by default | Read | ||
| AI | 144 | Error Error class -10 | Modbus 400627; not polled by default | Read | ||
| AI | 145 | Error Error phase -10 | Modbus 400628; not polled by default | Read | ||
| AI | 146 | Error Type of fuel-10 | Modbus 400629; not polled by default | Read | ||
| AI | 147 | Error Output -10 | Modbus 400630; not polled by default | Read | ||
| AI | 148 | Error Start counter total -10 | Modbus 400631; not polled by default | Read | ||
| AI | 149 | Error Error code -11 | Modbus 400633; not polled by default | Read | ||
| AI | 150 | Error Diagnostic code -11 | Modbus 400634; not polled by default | Read | ||
| AI | 151 | Error Error class -11 | Modbus 400635; not polled by default | Read | ||
| AI | 152 | Error Error phase -11 | Modbus 400636; not polled by default | Read | ||
| AI | 153 | Error Type of fuel-11 | Modbus 400637; not polled by default | Read | ||
| AI | 154 | Error Output -11 | Modbus 400638; not polled by default | Read | ||
| AI | 155 | Error Start counter total -11 | Modbus 400640; not polled by default | Read | ||
| AI | 156 | Error Error code -12 | Modbus 400641; not polled by default | Read | ||
| AI | 157 | Error Diagnostic code -12 | Modbus 400642; not polled by default | Read | ||
| AI | 158 | Error Error class -12 | Modbus 400643; not polled by default | Read | ||
| AI | 159 | Error Error phase -12 | Modbus 400644; not polled by default | Read | ||
| AI | 160 | Error Type of fuel-12 | Modbus 400645; not polled by default | Read | ||
| AI | 161 | Error Output -12 | Modbus 400646; not polled by default | Read | ||
| AI | 162 | Error Start counter total -12 | Modbus 400647; not polled by default | Read | ||
| AI | 163 | Error Error code -13 | Modbus 400649; not polled by default | Read | ||
| AI | 164 | Error Diagnostic code -13 | Modbus 400650; not polled by default | Read | ||
| AI | 165 | Error Error class -13 | Modbus 400651; not polled by default | Read | ||
| AI | 166 | Error Error phase -13 | Modbus 400652; not polled by default | Read | ||
| AI | 167 | Error Type of fuel-13 | Modbus 400653; not polled by default | Read | ||
| AI | 168 | Error Output -13 | Modbus 400654; not polled by default | Read | ||
| AI | 169 | Error Start counter total -13 | Modbus 400655; not polled by default | Read | ||
| AI | 170 | Error Error code -14 | Modbus 400657; not polled by default | Read | ||
| AI | 171 | Error Diagnostic code -14 | Modbus 400658; not polled by default | Read | ||
| AI | 172 | Error Error class -14 | Modbus 400659; not polled by default | Read | ||
| AI | 173 | Error Error phase -14 | Modbus 400660; not polled by default | Read | ||
| AI | 174 | Error Type of fuel-14 | Modbus 400661; not polled by default | Read | ||
| AI | 175 | Error Output -14 | Modbus 400662; not polled by default | Read | ||
| AI | 176 | Error Start counter total -14 | Modbus 400663; not polled by default | Read | ||
| AI | 177 | Error Error code -15 | Modbus 400665; not polled by default | Read | ||
| AI | 178 | Error Diagnostic code -15 | Modbus 400666; not polled by default | Read | ||
| AI | 179 | Error Error class -15 | Modbus 400667; not polled by default | Read | ||
| AI | 180 | Error Error phase -15 | Modbus 400668; not polled by default | Read | ||
| AI | 181 | Error Type of fuel-15 | Modbus 400669; not polled by default | Read | ||
| AI | 182 | Error Output -15 | Modbus 400670; not polled by default | Read | ||
| AI | 183 | Error Start counter total -15 | Modbus 400671; not polled by default | Read | ||
| AI | 184 | Error Error code -16 | Modbus 400673; not polled by default | Read | ||
| AI | 185 | Error Diagnostic code -16 | Modbus 400674; not polled by default | Read | ||
| AI | 186 | Error Error class -16 | Modbus 400675; not polled by default | Read | ||
| AI | 187 | Error Error phase -16 | Modbus 400676; not polled by default | Read | ||
| AI | 188 | Error Type of fuel-16 | Modbus 400677; not polled by default | Read | ||
| AI | 189 | Error Output -16 | Modbus 400678; not polled by default | Read | ||
| AI | 190 | Error Start counter total -16 | Modbus 400679; not polled by default | Read | ||
| AI | 191 | Error Error code -17 | Modbus 400681; not polled by default | Read | ||
| AI | 192 | Error Diagnostic code -17 | Modbus 400682; not polled by default | Read | ||
| AI | 193 | Error Error class -17 | Modbus 400683; not polled by default | Read | ||
| AI | 194 | Error Error phase -17 | Modbus 400684; not polled by default | Read | ||
| AI | 195 | Error Type of fuel-17 | Modbus 400685; not polled by default | Read | ||
| AI | 196 | Error Output -17 | Modbus 400686; not polled by default | Read | ||
| AI | 197 | Error Start counter total -17 | Modbus 400687; not polled by default | Read | ||
| AI | 198 | Error Error code -18 | Modbus 400689; not polled by default | Read | ||
| AI | 199 | Error Diagnostic code -18 | Modbus 400690; not polled by default | Read | ||
| AI | 200 | Error Error class -18 | Modbus 400691; not polled by default | Read | ||
| AI | 201 | Error Error phase -18 | Modbus 400692; not polled by default | Read | ||
| AI | 202 | Error Type of fuel-18 | Modbus 400693; not polled by default | Read | ||
| AI | 203 | Error Output -18 | Modbus 400694; not polled by default | Read | ||
| AI | 204 | Error Start counter total -18 | Modbus 400695; not polled by default | Read | ||
| AI | 205 | Error Error code -19 | Modbus 400697; not polled by default | Read | ||
| AI | 206 | Error Diagnostic code -19 | Modbus 400698; not polled by default | Read | ||
| AI | 207 | Error Error class -19 | Modbus 400699; not polled by default | Read | ||
| AI | 208 | Error Error phase -19 | Modbus 400700; not polled by default | Read | ||
| AI | 209 | Error Type of fuel-19 | Modbus 400701; not polled by default | Read | ||
| AI | 210 | Error Output -19 | Modbus 400702; not polled by default | Read | ||
| AI | 211 | Error Start counter total -19 | Modbus 400703; not polled by default | Read | ||
| AI | 212 | Error Error code -20 | Modbus 400705; not polled by default | Read | ||
| AI | 213 | Error Diagnostic code -20 | Modbus 400706; not polled by default | Read | ||
| AI | 214 | Error Error class -20 | Modbus 400707; not polled by default | Read | ||
| AI | 215 | Error Error phase -20 | Modbus 400708; not polled by default | Read | ||
| AI | 216 | Error Type of fuel-20 | Modbus 400709; not polled by default | Read | ||
| AI | 217 | Error Output -20 | Modbus 400710; not polled by default | Read | ||
| AI | 218 | Error Start counter total -20 | Modbus 400711; not polled by default | Read | ||
| AI | 219 | Error Error code -21 | Modbus 400713; not polled by default | Read | ||
| AI | 220 | Error Diagnostic code -21 | Modbus 400714; not polled by default | Read | ||
| AI | 221 | Error Error class -21 | Modbus 400715; not polled by default | Read | ||
| AI | 222 | Error Error phase -21 | Modbus 400716; not polled by default | Read | ||
| AI | 223 | Error Type of fuel-21 | Modbus 400717; not polled by default | Read | ||
| AI | 224 | Error Output -21 | Modbus 400718; not polled by default | Read | ||
| AI | 225 | Error Start counter total -21 | Modbus 400719; not polled by default | Read | ||
| AI | 226 | Error Error code -22 | Modbus 400721; not polled by default | Read | ||
| AI | 227 | Error Diagnostic code -22 | Modbus 400722; not polled by default | Read | ||
| AI | 228 | Error Error class -22 | Modbus 400723; not polled by default | Read | ||
| AI | 229 | Error Error phase -22 | Modbus 400724; not polled by default | Read | ||
| AI | 230 | Error Type of fuel-22 | Modbus 400725; not polled by default | Read | ||
| AI | 231 | Error Output -22 | Modbus 400726; not polled by default | Read | ||
| AI | 232 | Error Start counter total -22 | Modbus 400727; not polled by default | Read | ||
| AI | 233 | Error Error code -23 | Modbus 400729; not polled by default | Read | ||
| AI | 234 | Error Diagnostic code -23 | Modbus 400730; not polled by default | Read | ||
| AI | 235 | Error Error class -23 | Modbus 400731; not polled by default | Read | ||
| AI | 236 | Error Error phase -23 | Modbus 400732; not polled by default | Read | ||
| AI | 237 | Error Type of fuel-23 | Modbus 400733; not polled by default | Read | ||
| AI | 238 | Error Output -23 | Modbus 400734; not polled by default | Read | ||
| AI | 239 | Error Start counter total -23 | Modbus 400735; not polled by default | Read | ||
| AI | 240 | Error Error code -24 | Modbus 400737; not polled by default | Read | ||
| AI | 241 | Error Diagnostic code -24 | Modbus 400738; not polled by default | Read | ||
| AI | 242 | Error Error class -24 | Modbus 400739; not polled by default | Read | ||
| AI | 243 | Error Error phase -24 | Modbus 400740; not polled by default | Read | ||
| AI | 244 | Error Type of fuel-24 | Modbus 400741; not polled by default | Read | ||
| AI | 245 | Error Output -24 | Modbus 400742; not polled by default | Read | ||
| AI | 246 | Error Start counter total -24 | Modbus 400743; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Siemens LMV3 point IDs by name
AI1Burner control phaseAI2Position of current fuel actuatorAI3Position of air actuatorAI4Manipulated variable VSDAI5Current type of fuelAI6Current outputAI7Flame signalAI8Current fuel throughputAI9Startup counter totalAI10Current error: Error codeAI11Current error: Diagnostic codeAI12Current error: Error classAI13Current error: Error phaseBO14Controller on / offBI15Pressure switch valve proving (P LT)BI16Safety loop (SK)BI17Pressure switch-min (Pmin) (pressure switch valve proving)BI18Pressure switch-max (Pmax) / POCBI19Air pressure switch (LP)BI20Alarm (AL)BI21Ignition (Z)BI22Fan (M)BI23Fuel valve 1 (V1)BI24Fuel valve 2 (V2)BI25Fuel valve 3 (V3) / pilot valve (PV)AO26Program stopAO27Modbus modeAO28Modbus breakdown timeAO29Operating mode in remote operationAO30Preselected target output modulating / multistageAO31Hours run fuel 0 resettableAO32Only with LMV26... / LMV36..Hours run fuel 1 resettableAI33Hours run unit liveAO34Start counter fuel 0 resettableAO35Only with LMV26... / LMV36...Start counter fuel 1 resettableAI36Start counter totalAO37Fuel volume fuel 0 0 = resettableAO38Only with LMV26... / LMV36 Fuel volume fuel 1 1 = resettableAI39Number of faultsAO40Preselected output in the event breaks downAO41Only with LMV26... / LMV36 Preselected output event breaks downAI42Burner control type reference (ASN) ASCII Word 01AI43Burner control type reference (ASN) ASCII Word 02AI44Burner control type reference (ASN) ASCII Word 03AI45Burner control type reference (ASN) ASCII Word 04AI46Burner control type reference (ASN) ASCII Word 05AI47Burner control type reference (ASN) ASCII Word 06AI48Burner control type reference (ASN) ASCII Word 07AI49Burner control type reference (ASN) ASCII Word 08AI50Burner control parameter set codeAI51Burner control parameter set versionAI52Burner control identification date Word 01AI53Burner control identification date Word 02AI54Burner control identification date Word 03AI55Burner control identification numberAI56Software version burner controlAI57Burner identification Word 01AI58Burner identification Word 02AI59Burner identification Word 03AI60Burner identification Word 04AI61Burner identification Word 05AI62Burner identification Word 06AI63Burner identification Word 07AI64Burner identification Word 08AI65Minimum output fuel 0AI66Maximum output fuel 0AI67Only with LMV26... / LMV36 Minimum output fuel 1AI68Only with LMV26... / LMV36..Maximum output fuel 1AI69Operation mode of burnerAI70Only LMV26... / LMV36..Operation mode of burner fuel 1AI71Switching cycles Revert to pilotAI72Error Error codeAI73Error Diagnostic codeAI74Error Error classAI75Error Error phaseAI76Error Type of fuelAI77Error OutputAI78Error Start counter totalAI79Error Error code -1AI80Error Diagnostic code -1AI81Error Error class -1AI82Error Error phase -1AI83Error Type of fuel-1AI84Error Output -1AI85Error Start counter total -1AI86Error Error code -2AI87Error Diagnostic code -2AI88Error Error class -2AI89Error Error phase -2AI90Error Type of fuel-2AI91Error Output -2AI92Error Start counter total -2AI93Error Error code -3AI94Error Diagnostic code -3AI95Error Error class -3AI96Error Error phase -3AI97Error Type of fuel-3AI98Error Output -3AI99Error Start counter total -3AI100Error Error code -4AI101Error Diagnostic code -4AI102Error Error class -4AI103Error Error phase -4AI104Error Type of fuel-4AI105Error Output -4AI106Error Start counter total -4AI107Error Error code -5AI108Error Diagnostic code -5AI109Error Error class -5AI110Error Error phase -5AI111Error Type of fuel-5AI112Error Output -5AI113Error Start counter total -5AI114Error Error code -6AI115Error Diagnostic code -6AI116Error Error class -6AI117Error Error phase -6AI118Error Type of fuel-6AI119Error Output -6AI120Error Start counter total -6AI121Error Error code -7AI122Error Diagnostic code -7AI123Error Error class -7AI124Error Error phase -7AI125Error Type of fuel-7AI126Error Output -7AI127Error Start counter total -7AI128Error Error code -8AI129Error Diagnostic code -8AI130Error Error class -8AI131Error Error phase -8AI132Error Type of fuel-8AI133Error Output -8AI134Error Start counter total -8AI135Error Error code -9AI136Error Diagnostic code -9AI137Error Error class -9AI138Error Error phase -9AI139Error Type of fuel-9AI140Error Output -9AI141Error Start counter total -9AI142Error Error code -10AI143Error Diagnostic code -10AI144Error Error class -10AI145Error Error phase -10AI146Error Type of fuel-10AI147Error Output -10AI148Error Start counter total -10AI149Error Error code -11AI150Error Diagnostic code -11AI151Error Error class -11AI152Error Error phase -11AI153Error Type of fuel-11AI154Error Output -11AI155Error Start counter total -11AI156Error Error code -12AI157Error Diagnostic code -12AI158Error Error class -12AI159Error Error phase -12AI160Error Type of fuel-12AI161Error Output -12AI162Error Start counter total -12AI163Error Error code -13AI164Error Diagnostic code -13AI165Error Error class -13AI166Error Error phase -13AI167Error Type of fuel-13AI168Error Output -13AI169Error Start counter total -13AI170Error Error code -14AI171Error Diagnostic code -14AI172Error Error class -14AI173Error Error phase -14AI174Error Type of fuel-14AI175Error Output -14AI176Error Start counter total -14AI177Error Error code -15AI178Error Diagnostic code -15AI179Error Error class -15AI180Error Error phase -15AI181Error Type of fuel-15AI182Error Output -15AI183Error Start counter total -15AI184Error Error code -16AI185Error Diagnostic code -16AI186Error Error class -16AI187Error Error phase -16AI188Error Type of fuel-16AI189Error Output -16AI190Error Start counter total -16AI191Error Error code -17AI192Error Diagnostic code -17AI193Error Error class -17AI194Error Error phase -17AI195Error Type of fuel-17AI196Error Output -17AI197Error Start counter total -17AI198Error Error code -18AI199Error Diagnostic code -18AI200Error Error class -18AI201Error Error phase -18AI202Error Type of fuel-18AI203Error Output -18AI204Error Start counter total -18AI205Error Error code -19AI206Error Diagnostic code -19AI207Error Error class -19AI208Error Error phase -19AI209Error Type of fuel-19AI210Error Output -19AI211Error Start counter total -19AI212Error Error code -20AI213Error Diagnostic code -20AI214Error Error class -20AI215Error Error phase -20AI216Error Type of fuel-20AI217Error Output -20AI218Error Start counter total -20AI219Error Error code -21AI220Error Diagnostic code -21AI221Error Error class -21AI222Error Error phase -21AI223Error Type of fuel-21AI224Error Output -21AI225Error Start counter total -21AI226Error Error code -22AI227Error Diagnostic code -22AI228Error Error class -22AI229Error Error phase -22AI230Error Type of fuel-22AI231Error Output -22AI232Error Start counter total -22AI233Error Error code -23AI234Error Diagnostic code -23AI235Error Error class -23AI236Error Error phase -23AI237Error Type of fuel-23AI238Error Output -23AI239Error Start counter total -23AI240Error Error code -24AI241Error Diagnostic code -24AI242Error Error class -24AI243Error Error phase -24AI244Error Type of fuel-24AI245Error Output -24AI246Error Start counter total -24
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV3_a_LX.csv; the profile maps the registers in the LMV3 Modbus documentation (https://www.ccontrols.com/support/dp/LMV3.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 26 of the 246 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV3 burner management via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
How many BACnet points does the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX have?
This list has 246 BACnet objects: 221 analog inputs, 13 analog outputs, 11 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet points are writable?
14 of the 246 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Siemens LMV3 burner management via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV3_a (Siemens_Combustion_Control_LMV3_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Siemens_Combustion_Control_LMV3_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX?
Start with BO 14 Controller on / off (Controller on/off); AO 27 Modbus mode (Modbus mode (local/remote)); AO 30 Preselected target output modulating / multistage (Preselected output in remote mode); AI 1 Burner control phase (Burner control phase); AI 6 Current output (Current output); AI 7 Flame signal (Flame signal); BI 20 Alarm (AL) (Alarm output); AI 10 Current error: Error code (Current error code).
How do I enable BMS control of the Contemporary Controls Siemens LMV3 burner management via BASgatewayLX?
Controller on/off (BO 14) is polled by default. Remote output control needs Modbus mode (AO 27), the remote operating mode (AO 29) and the preselected output (AO 30), all unpolled in the published profile.
How do I check these points on the real Siemens LMV3 burner management via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Siemens_Combustion_Control_LMV3_a · Siemens_Combustion_Control_LMV3_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.