- Home
- BACnet points lists
- Contemporary Controls
- U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
Boiler controller · BACnet points list
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Sage2 controller: 308 objects (303 AI, 5 AO), 53 polled by default. It reads supply, return, header, stack and outdoor sensors, commanded firing rate, fan speed, flame signal, active CH/DHW/lead-lag setpoints and operating points, burner control state, lockout, hold and alarm codes, demand and pump status. Five outputs are the resettable cycle and run-time counters.
This page lists 308 BACnet objects for the Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
- Equipment
- Boiler controller
- Equipment type
- Boilers & water heaters
- BACnet objects
- 308 (5 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
Read burner control state, supply temperature against the active CH setpoint, firing rate and the lockout/hold/alarm codes. The profile does not write setpoints.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 18 | Burner control state | Burner control state | Read |
| AI 29 | CH heat demand | CH heat demand | Read |
| AI 1 | Supply sensor | Supply temperature | Read |
| AI 5 | Return sensor | Return temperature | Read |
| AI 8 | Active CH setpoint | Active CH setpoint | Read |
| AI 2 | Firing rate Commanded | Commanded firing rate | Read |
| AI 4 | Flame signal | Flame signal | Read |
| AI 19 | Lockout code | Lockout code | Read |
| AI 20 | Hold code | Hold code | Read |
| AI 308 | Alarm Code | Alarm code | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- The writable outputs are only the cycle and run-time counters; don't write them by accident.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Supply sensor | Modbus 400007 | °C | Read | |
| AImin | 2 | Firing rate Commanded | Modbus 400008 | Read | ||
| AI | 3 | Fan speed Measured | Modbus 400009 | rpm | Read | |
| AImin | 4 | Flame signal | Modbus 400010 | V | Read | |
| AImin | 5 | Return sensor | Modbus 400011 | °C | Read | |
| AI | 6 | Header sensor | Modbus 400013 | °C | Read | |
| AI | 7 | Stack sensor | Modbus 400014 | °C | Read | |
| AImin | 8 | Active CH setpoint | Modbus 400016 | °C | Read | |
| AI | 9 | Active DHW setpoint | Modbus 400017 | °C | Read | |
| AI | 10 | Active LL setpoint | Modbus 400018 | °C | Read | |
| AI | 11 | Active CH operating point | Modbus 400025 | °C | Read | |
| AI | 12 | Active DHW operating point | Modbus 400026 | °C | Read | |
| AI | 13 | Active Lead Lag operating point | Modbus 400027 | °C | Read | |
| AI | 14 | Active system operating point | Modbus 400028 | °C | Read | |
| AI | 15 | Active system setpoint | Modbus 400029 | °C | Read | |
| AI | 16 | Active system on hysteresis | Modbus 400030 | °C | Read | |
| AI | 17 | Active system off hysteresis | Modbus 400031 | °C | Read | |
| AImin | 18 | Burner control state | Modbus 400033 | Read | ||
| AImin | 19 | Lockout code | Modbus 400034 | Read | ||
| AImin | 20 | Hold code | Modbus 400040 | Read | ||
| AI | 21 | Supply sensor (S3=J8-8) state | Modbus 400048 | Read | ||
| AI | 22 | Return sensor (S1=J8-4) state | Modbus 400049 | Read | ||
| AI | 23 | Stack sensor (S8=J9-4) state | Modbus 400051 | Read | ||
| AI | 24 | Header sensor state | Modbus 400052 | Read | ||
| AI | 25 | 4-20mA remote control input (S2=J8-6) state | Modbus 400053 | Read | ||
| AI | 26 | Active system sensor | Modbus 400061 | Read | ||
| AI | 27 | Active Lead Lag sensor | Modbus 400062 | Read | ||
| AI | 28 | CH setpoint source | Modbus 400065 | Read | ||
| AImin | 29 | CH heat demand | Modbus 400066 | Read | ||
| AI | 30 | CH requested rate | Modbus 400068 | Read | ||
| AI | 31 | CH frost burner demand | Modbus 400070 | Read | ||
| AI | 32 | Active CH on hysteresis | Modbus 400071 | °C | Read | |
| AI | 33 | Active CH off hysteresis | Modbus 400072 | °C | Read | |
| AI | 34 | Active CH sensor | Modbus 400076 | Read | ||
| AI | 35 | Active DHW sensor | Modbus 400079 | Read | ||
| AI | 36 | DHW setpoint source | Modbus 400081 | Read | ||
| AI | 37 | DHW priority count | Modbus 400082 | Read | ||
| AI | 38 | DHW heat demand | Modbus 400083 | Read | ||
| AI | 39 | Active DHW on hysteresis | Modbus 400088 | Read | ||
| AI | 40 | Active DHW off hysteresis | Modbus 400089 | °C | Read | |
| AI | 41 | CH pump status | Modbus 400096 | °C | Read | |
| AI | 42 | DHW pump status | Modbus 400100 | Read | ||
| AI | 43 | Boiler pump status | Modbus 400108 | Read | ||
| AO | 44 | Burner cycle count | Modbus 400128 | Command | ||
| AO | 45 | Burner run time | Modbus 400130 | h | Command | |
| AO | 46 | CH pump cycle count | Modbus 400132 | Command | ||
| AO | 47 | DHW pump cycle count | Modbus 400134 | Command | ||
| AO | 48 | Boiler pump cycle count | Modbus 400138 | Command | ||
| AI | 49 | Lead Lag master setpoint source | Modbus 400162 | Read | ||
| AI | 50 | Lead Lag slave burner demand | Modbus 400164 | Read | ||
| AI | 51 | Outdoor temperature | Modbus 400170 | °C | Read | |
| AI | 52 | Outdoor sensor state | Modbus 400171 | Read | ||
| AI | 53 | Lockout history record 1_ a | Modbus 400864; not polled by default | Read | ||
| AI | 54 | Lockout history record 1_ b | Modbus 400865; not polled by default | Read | ||
| AI | 55 | Lockout history record 1_ c | Modbus 400866; not polled by default | Read | ||
| AI | 56 | Lockout history record 1_ d | Modbus 400867; not polled by default | Read | ||
| AI | 57 | Lockout history record 1_ e | Modbus 400868; not polled by default | Read | ||
| AI | 58 | Lockout history record 1_ f | Modbus 400869; not polled by default | Read | ||
| AI | 59 | Lockout history record 1_ g | Modbus 400870; not polled by default | Read | ||
| AI | 60 | Lockout history record 1_ h | Modbus 400871; not polled by default | Read | ||
| AI | 61 | Lockout history record 1_ i | Modbus 400872; not polled by default | Read | ||
| AI | 62 | Lockout history record 1_ j | Modbus 400873; not polled by default | Read | ||
| AI | 63 | Lockout history record 1_ k | Modbus 400874; not polled by default | Read | ||
| AI | 64 | Lockout history record 1_ l | Modbus 400875; not polled by default | Read | ||
| AI | 65 | Lockout history record 1_ m | Modbus 400876; not polled by default | Read | ||
| AI | 66 | Lockout history record 1_ n | Modbus 400877; not polled by default | Read | ||
| AI | 67 | Lockout history record 1_ o | Modbus 400878; not polled by default | Read | ||
| AI | 68 | Lockout history record 1_ p | Modbus 400879; not polled by default | Read | ||
| AI | 69 | Lockout history record 1_ q | Modbus 400880; not polled by default | Read | ||
| AI | 70 | Lockout history record 2_ a | Modbus 400881; not polled by default | Read | ||
| AI | 71 | Lockout history record 2_ b | Modbus 400882; not polled by default | Read | ||
| AI | 72 | Lockout history record 2_ c | Modbus 400883; not polled by default | Read | ||
| AI | 73 | Lockout history record 2_ d | Modbus 400884; not polled by default | Read | ||
| AI | 74 | Lockout history record 2_ e | Modbus 400885; not polled by default | Read | ||
| AI | 75 | Lockout history record 2_ f | Modbus 400886; not polled by default | Read | ||
| AI | 76 | Lockout history record 2_ g | Modbus 400887; not polled by default | Read | ||
| AI | 77 | Lockout history record 2_ h | Modbus 400888; not polled by default | Read | ||
| AI | 78 | Lockout history record 2_ i | Modbus 400889; not polled by default | Read | ||
| AI | 79 | Lockout history record 2_ j | Modbus 400890; not polled by default | Read | ||
| AI | 80 | Lockout history record 2_ k | Modbus 400891; not polled by default | Read | ||
| AI | 81 | Lockout history record 2_ l | Modbus 400892; not polled by default | Read | ||
| AI | 82 | Lockout history record 2_ m | Modbus 400893; not polled by default | Read | ||
| AI | 83 | Lockout history record 2_ n | Modbus 400894; not polled by default | Read | ||
| AI | 84 | Lockout history record 2_ o | Modbus 400895; not polled by default | Read | ||
| AI | 85 | Lockout history record 2_ p | Modbus 400896; not polled by default | Read | ||
| AI | 86 | Lockout history record 2_ q | Modbus 400897; not polled by default | Read | ||
| AI | 87 | Lockout history record 3_ a | Modbus 400898; not polled by default | Read | ||
| AI | 88 | Lockout history record 3_ b | Modbus 400899; not polled by default | Read | ||
| AI | 89 | Lockout history record 3_ c | Modbus 400900; not polled by default | Read | ||
| AI | 90 | Lockout history record 3_ d | Modbus 400901; not polled by default | Read | ||
| AI | 91 | Lockout history record 3_ e | Modbus 400902; not polled by default | Read | ||
| AI | 92 | Lockout history record 3_ f | Modbus 400903; not polled by default | Read | ||
| AI | 93 | Lockout history record 3_ g | Modbus 400904; not polled by default | Read | ||
| AI | 94 | Lockout history record 3_ h | Modbus 400905; not polled by default | Read | ||
| AI | 95 | Lockout history record 3_ i | Modbus 400906; not polled by default | Read | ||
| AI | 96 | Lockout history record 3_ j | Modbus 400907; not polled by default | Read | ||
| AI | 97 | Lockout history record 3_ k | Modbus 400908; not polled by default | Read | ||
| AI | 98 | Lockout history record 3_ l | Modbus 400909; not polled by default | Read | ||
| AI | 99 | Lockout history record 3_ m | Modbus 400910; not polled by default | Read | ||
| AI | 100 | Lockout history record 3_ n | Modbus 400911; not polled by default | Read | ||
| AI | 101 | Lockout history record 3_ o | Modbus 400912; not polled by default | Read | ||
| AI | 102 | Lockout history record 3_ p | Modbus 400913; not polled by default | Read | ||
| AI | 103 | Lockout history record 3_ q | Modbus 400914; not polled by default | Read | ||
| AI | 104 | Lockout history record 4_ a | Modbus 400915; not polled by default | Read | ||
| AI | 105 | Lockout history record 4_ b | Modbus 400916; not polled by default | Read | ||
| AI | 106 | Lockout history record 4_ c | Modbus 400917; not polled by default | Read | ||
| AI | 107 | Lockout history record 4_ d | Modbus 400918; not polled by default | Read | ||
| AI | 108 | Lockout history record 4_ e | Modbus 400919; not polled by default | Read | ||
| AI | 109 | Lockout history record 4_ f | Modbus 400920; not polled by default | Read | ||
| AI | 110 | Lockout history record 4_ g | Modbus 400921; not polled by default | Read | ||
| AI | 111 | Lockout history record 4_ h | Modbus 400922; not polled by default | Read | ||
| AI | 112 | Lockout history record 4_ i | Modbus 400923; not polled by default | Read | ||
| AI | 113 | Lockout history record 4_ j | Modbus 400924; not polled by default | Read | ||
| AI | 114 | Lockout history record 4_ k | Modbus 400925; not polled by default | Read | ||
| AI | 115 | Lockout history record 4_ l | Modbus 400926; not polled by default | Read | ||
| AI | 116 | Lockout history record 4_ m | Modbus 400927; not polled by default | Read | ||
| AI | 117 | Lockout history record 4_ n | Modbus 400928; not polled by default | Read | ||
| AI | 118 | Lockout history record 4_ o | Modbus 400929; not polled by default | Read | ||
| AI | 119 | Lockout history record 4_ p | Modbus 400930; not polled by default | Read | ||
| AI | 120 | Lockout history record 4_ q | Modbus 400931; not polled by default | Read | ||
| AI | 121 | Lockout history record 5_ a | Modbus 400932; not polled by default | Read | ||
| AI | 122 | Lockout history record 5_ b | Modbus 400933; not polled by default | Read | ||
| AI | 123 | Lockout history record 5_ c | Modbus 400934; not polled by default | Read | ||
| AI | 124 | Lockout history record 5_ d | Modbus 400935; not polled by default | Read | ||
| AI | 125 | Lockout history record 5_ e | Modbus 400936; not polled by default | Read | ||
| AI | 126 | Lockout history record 5_ f | Modbus 400937; not polled by default | Read | ||
| AI | 127 | Lockout history record 5_ g | Modbus 400938; not polled by default | Read | ||
| AI | 128 | Lockout history record 5_ h | Modbus 400939; not polled by default | Read | ||
| AI | 129 | Lockout history record 5_ i | Modbus 400940; not polled by default | Read | ||
| AI | 130 | Lockout history record 5_ j | Modbus 400941; not polled by default | Read | ||
| AI | 131 | Lockout history record 5_ k | Modbus 400942; not polled by default | Read | ||
| AI | 132 | Lockout history record 5_ l | Modbus 400943; not polled by default | Read | ||
| AI | 133 | Lockout history record 5_ m | Modbus 400944; not polled by default | Read | ||
| AI | 134 | Lockout history record 5_ n | Modbus 400945; not polled by default | Read | ||
| AI | 135 | Lockout history record 5_ o | Modbus 400946; not polled by default | Read | ||
| AI | 136 | Lockout history record 5_ p | Modbus 400947; not polled by default | Read | ||
| AI | 137 | Lockout history record 5_ q | Modbus 400948; not polled by default | Read | ||
| AI | 138 | Lockout history record 6_ a | Modbus 400949; not polled by default | Read | ||
| AI | 139 | Lockout history record 6_ b | Modbus 400950; not polled by default | Read | ||
| AI | 140 | Lockout history record 6_ c | Modbus 400951; not polled by default | Read | ||
| AI | 141 | Lockout history record 6_ d | Modbus 400952; not polled by default | Read | ||
| AI | 142 | Lockout history record 6_ e | Modbus 400953; not polled by default | Read | ||
| AI | 143 | Lockout history record 6_ f | Modbus 400954; not polled by default | Read | ||
| AI | 144 | Lockout history record 6_ g | Modbus 400955; not polled by default | Read | ||
| AI | 145 | Lockout history record 6_ h | Modbus 400956; not polled by default | Read | ||
| AI | 146 | Lockout history record 6_ i | Modbus 400957; not polled by default | Read | ||
| AI | 147 | Lockout history record 6_ j | Modbus 400958; not polled by default | Read | ||
| AI | 148 | Lockout history record 6_ k | Modbus 400959; not polled by default | Read | ||
| AI | 149 | Lockout history record 6_ l | Modbus 400960; not polled by default | Read | ||
| AI | 150 | Lockout history record 6_ m | Modbus 400961; not polled by default | Read | ||
| AI | 151 | Lockout history record 6_ n | Modbus 400962; not polled by default | Read | ||
| AI | 152 | Lockout history record 6_ o | Modbus 400963; not polled by default | Read | ||
| AI | 153 | Lockout history record 6_ p | Modbus 400964; not polled by default | Read | ||
| AI | 154 | Lockout history record 6_ q | Modbus 400965; not polled by default | Read | ||
| AI | 155 | Lockout history record 7_ a | Modbus 400966; not polled by default | Read | ||
| AI | 156 | Lockout history record 7_ b | Modbus 400967; not polled by default | Read | ||
| AI | 157 | Lockout history record 7_ c | Modbus 400968; not polled by default | Read | ||
| AI | 158 | Lockout history record 7_ d | Modbus 400969; not polled by default | Read | ||
| AI | 159 | Lockout history record 7_ e | Modbus 400970; not polled by default | Read | ||
| AI | 160 | Lockout history record 7_ f | Modbus 400971; not polled by default | Read | ||
| AI | 161 | Lockout history record 7_ g | Modbus 400972; not polled by default | Read | ||
| AI | 162 | Lockout history record 7_ h | Modbus 400973; not polled by default | Read | ||
| AI | 163 | Lockout history record 7_ i | Modbus 400974; not polled by default | Read | ||
| AI | 164 | Lockout history record 7_ j | Modbus 400975; not polled by default | Read | ||
| AI | 165 | Lockout history record 7_ k | Modbus 400976; not polled by default | Read | ||
| AI | 166 | Lockout history record 7_ l | Modbus 400977; not polled by default | Read | ||
| AI | 167 | Lockout history record 7_ m | Modbus 400978; not polled by default | Read | ||
| AI | 168 | Lockout history record 7_ n | Modbus 400979; not polled by default | Read | ||
| AI | 169 | Lockout history record 7_ o | Modbus 400980; not polled by default | Read | ||
| AI | 170 | Lockout history record 7_ p | Modbus 400981; not polled by default | Read | ||
| AI | 171 | Lockout history record 7_ q | Modbus 400982; not polled by default | Read | ||
| AI | 172 | Lockout history record 8_ a | Modbus 400983; not polled by default | Read | ||
| AI | 173 | Lockout history record 8_ b | Modbus 400984; not polled by default | Read | ||
| AI | 174 | Lockout history record 8_ c | Modbus 400985; not polled by default | Read | ||
| AI | 175 | Lockout history record 8_ d | Modbus 400986; not polled by default | Read | ||
| AI | 176 | Lockout history record 8_ e | Modbus 400987; not polled by default | Read | ||
| AI | 177 | Lockout history record 8_ f | Modbus 400988; not polled by default | Read | ||
| AI | 178 | Lockout history record 8_ g | Modbus 400989; not polled by default | Read | ||
| AI | 179 | Lockout history record 8_ h | Modbus 400990; not polled by default | Read | ||
| AI | 180 | Lockout history record 8_ i | Modbus 400991; not polled by default | Read | ||
| AI | 181 | Lockout history record 8_ j | Modbus 400992; not polled by default | Read | ||
| AI | 182 | Lockout history record 8_ k | Modbus 400993; not polled by default | Read | ||
| AI | 183 | Lockout history record 8_ l | Modbus 400994; not polled by default | Read | ||
| AI | 184 | Lockout history record 8_ m | Modbus 400995; not polled by default | Read | ||
| AI | 185 | Lockout history record 8_ n | Modbus 400996; not polled by default | Read | ||
| AI | 186 | Lockout history record 8_ o | Modbus 400997; not polled by default | Read | ||
| AI | 187 | Lockout history record 8_ p | Modbus 400998; not polled by default | Read | ||
| AI | 188 | Lockout history record 8_ q | Modbus 400999; not polled by default | Read | ||
| AI | 189 | Lockout history record 9_ a | Modbus 401000; not polled by default | Read | ||
| AI | 190 | Lockout history record 9_ b | Modbus 401001; not polled by default | Read | ||
| AI | 191 | Lockout history record 9_ c | Modbus 401002; not polled by default | Read | ||
| AI | 192 | Lockout history record 9_ d | Modbus 401003; not polled by default | Read | ||
| AI | 193 | Lockout history record 9_ e | Modbus 401004; not polled by default | Read | ||
| AI | 194 | Lockout history record 9_ f | Modbus 401005; not polled by default | Read | ||
| AI | 195 | Lockout history record 9_ g | Modbus 401006; not polled by default | Read | ||
| AI | 196 | Lockout history record 9_ h | Modbus 401007; not polled by default | Read | ||
| AI | 197 | Lockout history record 9_ i | Modbus 401008; not polled by default | Read | ||
| AI | 198 | Lockout history record 9_ j | Modbus 401009; not polled by default | Read | ||
| AI | 199 | Lockout history record 9_ k | Modbus 401010; not polled by default | Read | ||
| AI | 200 | Lockout history record 9_ l | Modbus 401011; not polled by default | Read | ||
| AI | 201 | Lockout history record 9_ m | Modbus 401012; not polled by default | Read | ||
| AI | 202 | Lockout history record 9_ n | Modbus 401013; not polled by default | Read | ||
| AI | 203 | Lockout history record 9_ o | Modbus 401014; not polled by default | Read | ||
| AI | 204 | Lockout history record 9_ p | Modbus 401015; not polled by default | Read | ||
| AI | 205 | Lockout history record 9_ q | Modbus 401016; not polled by default | Read | ||
| AI | 206 | Lockout history record 10_ a | Modbus 401017; not polled by default | Read | ||
| AI | 207 | Lockout history record 10_ b | Modbus 401018; not polled by default | Read | ||
| AI | 208 | Lockout history record 10_ c | Modbus 401019; not polled by default | Read | ||
| AI | 209 | Lockout history record 10_ d | Modbus 401020; not polled by default | Read | ||
| AI | 210 | Lockout history record 10_ e | Modbus 401021; not polled by default | Read | ||
| AI | 211 | Lockout history record 10_ f | Modbus 401022; not polled by default | Read | ||
| AI | 212 | Lockout history record 10_ g | Modbus 401023; not polled by default | Read | ||
| AI | 213 | Lockout history record 10_ h | Modbus 401024; not polled by default | Read | ||
| AI | 214 | Lockout history record 10_ i | Modbus 401025; not polled by default | Read | ||
| AI | 215 | Lockout history record 10_ j | Modbus 401026; not polled by default | Read | ||
| AI | 216 | Lockout history record 10_ k | Modbus 401027; not polled by default | Read | ||
| AI | 217 | Lockout history record 10_ l | Modbus 401028; not polled by default | Read | ||
| AI | 218 | Lockout history record 10_ m | Modbus 401029; not polled by default | Read | ||
| AI | 219 | Lockout history record 10_ n | Modbus 401030; not polled by default | Read | ||
| AI | 220 | Lockout history record 10_ o | Modbus 401031; not polled by default | Read | ||
| AI | 221 | Lockout history record 10_ p | Modbus 401032; not polled by default | Read | ||
| AI | 222 | Lockout history record 10_ q | Modbus 401033; not polled by default | Read | ||
| AI | 223 | Lockout history record 11_ a | Modbus 401034; not polled by default | Read | ||
| AI | 224 | Lockout history record 11_ b | Modbus 401035; not polled by default | Read | ||
| AI | 225 | Lockout history record 11_ c | Modbus 401036; not polled by default | Read | ||
| AI | 226 | Lockout history record 11_ d | Modbus 401037; not polled by default | Read | ||
| AI | 227 | Lockout history record 11_ e | Modbus 401038; not polled by default | Read | ||
| AI | 228 | Lockout history record 11_ f | Modbus 401039; not polled by default | Read | ||
| AI | 229 | Lockout history record 11_ g | Modbus 401040; not polled by default | Read | ||
| AI | 230 | Lockout history record 11_ h | Modbus 401041; not polled by default | Read | ||
| AI | 231 | Lockout history record 11_ i | Modbus 401042; not polled by default | Read | ||
| AI | 232 | Lockout history record 11_ j | Modbus 401043; not polled by default | Read | ||
| AI | 233 | Lockout history record 11_ k | Modbus 401044; not polled by default | Read | ||
| AI | 234 | Lockout history record 11_ l | Modbus 401045; not polled by default | Read | ||
| AI | 235 | Lockout history record 11_ m | Modbus 401046; not polled by default | Read | ||
| AI | 236 | Lockout history record 11_ n | Modbus 401047; not polled by default | Read | ||
| AI | 237 | Lockout history record 11_ o | Modbus 401048; not polled by default | Read | ||
| AI | 238 | Lockout history record 11_ p | Modbus 401049; not polled by default | Read | ||
| AI | 239 | Lockout history record 11_ q | Modbus 401050; not polled by default | Read | ||
| AI | 240 | Lockout history record 12_ a | Modbus 401051; not polled by default | Read | ||
| AI | 241 | Lockout history record 12_ b | Modbus 401052; not polled by default | Read | ||
| AI | 242 | Lockout history record 12_ c | Modbus 401053; not polled by default | Read | ||
| AI | 243 | Lockout history record 12_ d | Modbus 401054; not polled by default | Read | ||
| AI | 244 | Lockout history record 12_ e | Modbus 401055; not polled by default | Read | ||
| AI | 245 | Lockout history record 12_ f | Modbus 401056; not polled by default | Read | ||
| AI | 246 | Lockout history record 12_ g | Modbus 401057; not polled by default | Read | ||
| AI | 247 | Lockout history record 12_ h | Modbus 401058; not polled by default | Read | ||
| AI | 248 | Lockout history record 12_ i | Modbus 401059; not polled by default | Read | ||
| AI | 249 | Lockout history record 12_ j | Modbus 401060; not polled by default | Read | ||
| AI | 250 | Lockout history record 12_ k | Modbus 401061; not polled by default | Read | ||
| AI | 251 | Lockout history record 12_ l | Modbus 401062; not polled by default | Read | ||
| AI | 252 | Lockout history record 12_ m | Modbus 401063; not polled by default | Read | ||
| AI | 253 | Lockout history record 12_ n | Modbus 401064; not polled by default | Read | ||
| AI | 254 | Lockout history record 12_ o | Modbus 401065; not polled by default | Read | ||
| AI | 255 | Lockout history record 12_ p | Modbus 401066; not polled by default | Read | ||
| AI | 256 | Lockout history record 12_ q | Modbus 401067; not polled by default | Read | ||
| AI | 257 | Lockout history record 13_ a | Modbus 401068; not polled by default | Read | ||
| AI | 258 | Lockout history record 13_ b | Modbus 401069; not polled by default | Read | ||
| AI | 259 | Lockout history record 13_ c | Modbus 401070; not polled by default | Read | ||
| AI | 260 | Lockout history record 13_ d | Modbus 401071; not polled by default | Read | ||
| AI | 261 | Lockout history record 13_ e | Modbus 401072; not polled by default | Read | ||
| AI | 262 | Lockout history record 13_ f | Modbus 401073; not polled by default | Read | ||
| AI | 263 | Lockout history record 13_ g | Modbus 401074; not polled by default | Read | ||
| AI | 264 | Lockout history record 13_ h | Modbus 401075; not polled by default | Read | ||
| AI | 265 | Lockout history record 13_ i | Modbus 401076; not polled by default | Read | ||
| AI | 266 | Lockout history record 13_ j | Modbus 401077; not polled by default | Read | ||
| AI | 267 | Lockout history record 13_ k | Modbus 401078; not polled by default | Read | ||
| AI | 268 | Lockout history record 13_ l | Modbus 401079; not polled by default | Read | ||
| AI | 269 | Lockout history record 13_ m | Modbus 401080; not polled by default | Read | ||
| AI | 270 | Lockout history record 13_ n | Modbus 401081; not polled by default | Read | ||
| AI | 271 | Lockout history record 13_ o | Modbus 401082; not polled by default | Read | ||
| AI | 272 | Lockout history record 13_ p | Modbus 401083; not polled by default | Read | ||
| AI | 273 | Lockout history record 13_ q | Modbus 401084; not polled by default | Read | ||
| AI | 274 | Lockout history record 14_ a | Modbus 401085; not polled by default | Read | ||
| AI | 275 | Lockout history record 14_ b | Modbus 401086; not polled by default | Read | ||
| AI | 276 | Lockout history record 14_ c | Modbus 401087; not polled by default | Read | ||
| AI | 277 | Lockout history record 14_ d | Modbus 401088; not polled by default | Read | ||
| AI | 278 | Lockout history record 14_ e | Modbus 401089; not polled by default | Read | ||
| AI | 279 | Lockout history record 14_ f | Modbus 401090; not polled by default | Read | ||
| AI | 280 | Lockout history record 14_ g | Modbus 401091; not polled by default | Read | ||
| AI | 281 | Lockout history record 14_ h | Modbus 401092; not polled by default | Read | ||
| AI | 282 | Lockout history record 14_ i | Modbus 401093; not polled by default | Read | ||
| AI | 283 | Lockout history record 14_ j | Modbus 401094; not polled by default | Read | ||
| AI | 284 | Lockout history record 14_ k | Modbus 401095; not polled by default | Read | ||
| AI | 285 | Lockout history record 14_ l | Modbus 401096; not polled by default | Read | ||
| AI | 286 | Lockout history record 14_ m | Modbus 401097; not polled by default | Read | ||
| AI | 287 | Lockout history record 14_ n | Modbus 401098; not polled by default | Read | ||
| AI | 288 | Lockout history record 14_ o | Modbus 401099; not polled by default | Read | ||
| AI | 289 | Lockout history record 14_ p | Modbus 401100; not polled by default | Read | ||
| AI | 290 | Lockout history record 14_ q | Modbus 401101; not polled by default | Read | ||
| AI | 291 | Lockout history record 15_ a | Modbus 401102; not polled by default | Read | ||
| AI | 292 | Lockout history record 15_ b | Modbus 401103; not polled by default | Read | ||
| AI | 293 | Lockout history record 15_ c | Modbus 401104; not polled by default | Read | ||
| AI | 294 | Lockout history record 15_ d | Modbus 401105; not polled by default | Read | ||
| AI | 295 | Lockout history record 15_ e | Modbus 401106; not polled by default | Read | ||
| AI | 296 | Lockout history record 15_ f | Modbus 401107; not polled by default | Read | ||
| AI | 297 | Lockout history record 15_ g | Modbus 401108; not polled by default | Read | ||
| AI | 298 | Lockout history record 15_ h | Modbus 401109; not polled by default | Read | ||
| AI | 299 | Lockout history record 15_ i | Modbus 401110; not polled by default | Read | ||
| AI | 300 | Lockout history record 15_ j | Modbus 401111; not polled by default | Read | ||
| AI | 301 | Lockout history record 15_ k | Modbus 401112; not polled by default | Read | ||
| AI | 302 | Lockout history record 15_ l | Modbus 401113; not polled by default | Read | ||
| AI | 303 | Lockout history record 15_ m | Modbus 401114; not polled by default | Read | ||
| AI | 304 | Lockout history record 15_ n | Modbus 401115; not polled by default | Read | ||
| AI | 305 | Lockout history record 15_ o | Modbus 401116; not polled by default | Read | ||
| AI | 306 | Lockout history record 15_ p | Modbus 401117; not polled by default | Read | ||
| AI | 307 | Lockout history record 15_ q | Modbus 401118; not polled by default | Read | ||
| AImin | 308 | Alarm Code | Modbus 401119 | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX U.S. Boiler Sage2 point IDs by name
AI1Supply sensorAI2Firing rate CommandedAI3Fan speed MeasuredAI4Flame signalAI5Return sensorAI6Header sensorAI7Stack sensorAI8Active CH setpointAI9Active DHW setpointAI10Active LL setpointAI11Active CH operating pointAI12Active DHW operating pointAI13Active Lead Lag operating pointAI14Active system operating pointAI15Active system setpointAI16Active system on hysteresisAI17Active system off hysteresisAI18Burner control stateAI19Lockout codeAI20Hold codeAI21Supply sensor (S3=J8-8) stateAI22Return sensor (S1=J8-4) stateAI23Stack sensor (S8=J9-4) stateAI24Header sensor stateAI254-20mA remote control input (S2=J8-6) stateAI26Active system sensorAI27Active Lead Lag sensorAI28CH setpoint sourceAI29CH heat demandAI30CH requested rateAI31CH frost burner demandAI32Active CH on hysteresisAI33Active CH off hysteresisAI34Active CH sensorAI35Active DHW sensorAI36DHW setpoint sourceAI37DHW priority countAI38DHW heat demandAI39Active DHW on hysteresisAI40Active DHW off hysteresisAI41CH pump statusAI42DHW pump statusAI43Boiler pump statusAO44Burner cycle countAO45Burner run timeAO46CH pump cycle countAO47DHW pump cycle countAO48Boiler pump cycle countAI49Lead Lag master setpoint sourceAI50Lead Lag slave burner demandAI51Outdoor temperatureAI52Outdoor sensor stateAI53Lockout history record 1_ aAI54Lockout history record 1_ bAI55Lockout history record 1_ cAI56Lockout history record 1_ dAI57Lockout history record 1_ eAI58Lockout history record 1_ fAI59Lockout history record 1_ gAI60Lockout history record 1_ hAI61Lockout history record 1_ iAI62Lockout history record 1_ jAI63Lockout history record 1_ kAI64Lockout history record 1_ lAI65Lockout history record 1_ mAI66Lockout history record 1_ nAI67Lockout history record 1_ oAI68Lockout history record 1_ pAI69Lockout history record 1_ qAI70Lockout history record 2_ aAI71Lockout history record 2_ bAI72Lockout history record 2_ cAI73Lockout history record 2_ dAI74Lockout history record 2_ eAI75Lockout history record 2_ fAI76Lockout history record 2_ gAI77Lockout history record 2_ hAI78Lockout history record 2_ iAI79Lockout history record 2_ jAI80Lockout history record 2_ kAI81Lockout history record 2_ lAI82Lockout history record 2_ mAI83Lockout history record 2_ nAI84Lockout history record 2_ oAI85Lockout history record 2_ pAI86Lockout history record 2_ qAI87Lockout history record 3_ aAI88Lockout history record 3_ bAI89Lockout history record 3_ cAI90Lockout history record 3_ dAI91Lockout history record 3_ eAI92Lockout history record 3_ fAI93Lockout history record 3_ gAI94Lockout history record 3_ hAI95Lockout history record 3_ iAI96Lockout history record 3_ jAI97Lockout history record 3_ kAI98Lockout history record 3_ lAI99Lockout history record 3_ mAI100Lockout history record 3_ nAI101Lockout history record 3_ oAI102Lockout history record 3_ pAI103Lockout history record 3_ qAI104Lockout history record 4_ aAI105Lockout history record 4_ bAI106Lockout history record 4_ cAI107Lockout history record 4_ dAI108Lockout history record 4_ eAI109Lockout history record 4_ fAI110Lockout history record 4_ gAI111Lockout history record 4_ hAI112Lockout history record 4_ iAI113Lockout history record 4_ jAI114Lockout history record 4_ kAI115Lockout history record 4_ lAI116Lockout history record 4_ mAI117Lockout history record 4_ nAI118Lockout history record 4_ oAI119Lockout history record 4_ pAI120Lockout history record 4_ qAI121Lockout history record 5_ aAI122Lockout history record 5_ bAI123Lockout history record 5_ cAI124Lockout history record 5_ dAI125Lockout history record 5_ eAI126Lockout history record 5_ fAI127Lockout history record 5_ gAI128Lockout history record 5_ hAI129Lockout history record 5_ iAI130Lockout history record 5_ jAI131Lockout history record 5_ kAI132Lockout history record 5_ lAI133Lockout history record 5_ mAI134Lockout history record 5_ nAI135Lockout history record 5_ oAI136Lockout history record 5_ pAI137Lockout history record 5_ qAI138Lockout history record 6_ aAI139Lockout history record 6_ bAI140Lockout history record 6_ cAI141Lockout history record 6_ dAI142Lockout history record 6_ eAI143Lockout history record 6_ fAI144Lockout history record 6_ gAI145Lockout history record 6_ hAI146Lockout history record 6_ iAI147Lockout history record 6_ jAI148Lockout history record 6_ kAI149Lockout history record 6_ lAI150Lockout history record 6_ mAI151Lockout history record 6_ nAI152Lockout history record 6_ oAI153Lockout history record 6_ pAI154Lockout history record 6_ qAI155Lockout history record 7_ aAI156Lockout history record 7_ bAI157Lockout history record 7_ cAI158Lockout history record 7_ dAI159Lockout history record 7_ eAI160Lockout history record 7_ fAI161Lockout history record 7_ gAI162Lockout history record 7_ hAI163Lockout history record 7_ iAI164Lockout history record 7_ jAI165Lockout history record 7_ kAI166Lockout history record 7_ lAI167Lockout history record 7_ mAI168Lockout history record 7_ nAI169Lockout history record 7_ oAI170Lockout history record 7_ pAI171Lockout history record 7_ qAI172Lockout history record 8_ aAI173Lockout history record 8_ bAI174Lockout history record 8_ cAI175Lockout history record 8_ dAI176Lockout history record 8_ eAI177Lockout history record 8_ fAI178Lockout history record 8_ gAI179Lockout history record 8_ hAI180Lockout history record 8_ iAI181Lockout history record 8_ jAI182Lockout history record 8_ kAI183Lockout history record 8_ lAI184Lockout history record 8_ mAI185Lockout history record 8_ nAI186Lockout history record 8_ oAI187Lockout history record 8_ pAI188Lockout history record 8_ qAI189Lockout history record 9_ aAI190Lockout history record 9_ bAI191Lockout history record 9_ cAI192Lockout history record 9_ dAI193Lockout history record 9_ eAI194Lockout history record 9_ fAI195Lockout history record 9_ gAI196Lockout history record 9_ hAI197Lockout history record 9_ iAI198Lockout history record 9_ jAI199Lockout history record 9_ kAI200Lockout history record 9_ lAI201Lockout history record 9_ mAI202Lockout history record 9_ nAI203Lockout history record 9_ oAI204Lockout history record 9_ pAI205Lockout history record 9_ qAI206Lockout history record 10_ aAI207Lockout history record 10_ bAI208Lockout history record 10_ cAI209Lockout history record 10_ dAI210Lockout history record 10_ eAI211Lockout history record 10_ fAI212Lockout history record 10_ gAI213Lockout history record 10_ hAI214Lockout history record 10_ iAI215Lockout history record 10_ jAI216Lockout history record 10_ kAI217Lockout history record 10_ lAI218Lockout history record 10_ mAI219Lockout history record 10_ nAI220Lockout history record 10_ oAI221Lockout history record 10_ pAI222Lockout history record 10_ qAI223Lockout history record 11_ aAI224Lockout history record 11_ bAI225Lockout history record 11_ cAI226Lockout history record 11_ dAI227Lockout history record 11_ eAI228Lockout history record 11_ fAI229Lockout history record 11_ gAI230Lockout history record 11_ hAI231Lockout history record 11_ iAI232Lockout history record 11_ jAI233Lockout history record 11_ kAI234Lockout history record 11_ lAI235Lockout history record 11_ mAI236Lockout history record 11_ nAI237Lockout history record 11_ oAI238Lockout history record 11_ pAI239Lockout history record 11_ qAI240Lockout history record 12_ aAI241Lockout history record 12_ bAI242Lockout history record 12_ cAI243Lockout history record 12_ dAI244Lockout history record 12_ eAI245Lockout history record 12_ fAI246Lockout history record 12_ gAI247Lockout history record 12_ hAI248Lockout history record 12_ iAI249Lockout history record 12_ jAI250Lockout history record 12_ kAI251Lockout history record 12_ lAI252Lockout history record 12_ mAI253Lockout history record 12_ nAI254Lockout history record 12_ oAI255Lockout history record 12_ pAI256Lockout history record 12_ qAI257Lockout history record 13_ aAI258Lockout history record 13_ bAI259Lockout history record 13_ cAI260Lockout history record 13_ dAI261Lockout history record 13_ eAI262Lockout history record 13_ fAI263Lockout history record 13_ gAI264Lockout history record 13_ hAI265Lockout history record 13_ iAI266Lockout history record 13_ jAI267Lockout history record 13_ kAI268Lockout history record 13_ lAI269Lockout history record 13_ mAI270Lockout history record 13_ nAI271Lockout history record 13_ oAI272Lockout history record 13_ pAI273Lockout history record 13_ qAI274Lockout history record 14_ aAI275Lockout history record 14_ bAI276Lockout history record 14_ cAI277Lockout history record 14_ dAI278Lockout history record 14_ eAI279Lockout history record 14_ fAI280Lockout history record 14_ gAI281Lockout history record 14_ hAI282Lockout history record 14_ iAI283Lockout history record 14_ jAI284Lockout history record 14_ kAI285Lockout history record 14_ lAI286Lockout history record 14_ mAI287Lockout history record 14_ nAI288Lockout history record 14_ oAI289Lockout history record 14_ pAI290Lockout history record 14_ qAI291Lockout history record 15_ aAI292Lockout history record 15_ bAI293Lockout history record 15_ cAI294Lockout history record 15_ dAI295Lockout history record 15_ eAI296Lockout history record 15_ fAI297Lockout history record 15_ gAI298Lockout history record 15_ hAI299Lockout history record 15_ iAI300Lockout history record 15_ jAI301Lockout history record 15_ kAI302Lockout history record 15_ lAI303Lockout history record 15_ mAI304Lockout history record 15_ nAI305Lockout history record 15_ oAI306Lockout history record 15_ pAI307Lockout history record 15_ qAI308Alarm Code
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile US_Boiler_SAGE2_COMB_Controller_a_LX.csv; the profile maps the registers in the Sage2 Modbus register list (https://www.ccontrols.com/support/dp/Sage2.doc).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 53 of the 308 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the U.S. Boiler Company Sage2 combustion controller via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
How many BACnet points does the Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX have?
This list has 308 BACnet objects: 303 analog inputs, 5 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX BACnet points are writable?
5 of the 308 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile US_Boiler_SAGE2_COMB_Controller_a (US_Boiler_SAGE2_COMB_Controller_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/US_Boiler_SAGE2_COMB_Controller.zip.
What are the minimum BACnet points to integrate the Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX?
Start with AI 18 Burner control state (Burner control state); AI 29 CH heat demand (CH heat demand); AI 1 Supply sensor (Supply temperature); AI 5 Return sensor (Return temperature); AI 8 Active CH setpoint (Active CH setpoint); AI 2 Firing rate Commanded (Commanded firing rate); AI 4 Flame signal (Flame signal); AI 19 Lockout code (Lockout code); AI 20 Hold code (Hold code); AI 308 Alarm Code (Alarm code).
How do I check these points on the real U.S. Boiler Company Sage2 combustion controller via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile US_Boiler_SAGE2_COMB_Controller_a · US_Boiler_SAGE2_COMB_Controller_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.