Power and energy meter · BACnet points list

Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Enercept meter: 39 objects (36 AI, 3 BO), 31 polled by default. Inputs give kWh, kW, kVAR, kVA, PF, average and phase voltages and currents, demand sub-interval, min/max/present demand and reset counts; binary outputs start a demand sub-interval, clear kWh and reset peak demand.

This page lists 39 BACnet objects for the Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Schneider Electric (Veris) Enercept meter via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
39 (3 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept
Source document
BASgatewayLX Modbus device profile Square_D_Enercept_Meter · Square_D_Enercept_Meter_LX_HI_LO.csv
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX

Integration in brief

Map real power (kW), energy consumption (kWh) and average line-line voltage first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2Real Power kWReal power, kWRead
AI 1Energy Consumption kWhEnergy consumption, kWhRead
AI 6Avg Voltage L-L average of 3Average voltage L-LRead
AI 8Avg Current average 3Average currentRead
AI 5Total Power FactorTotal power factorRead
AI 27Present DemandPresent demandRead
AI 26Maximum DemandMaximum demandRead

Network setup

Watch out for

Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

39 of 39 shown
Type
AnalogBinary
Access
Show
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Energy Consumption kWhModbus 400257kWhRead
AImin2Real Power kWModbus 400261kWRead
AI3Reactive Power kVarModbus 400263kVARRead
AI4Apparent Power kVaModbus 400265kVARead
AImin5Total Power FactorModbus 400267PFRead
AImin6Avg Voltage L-L average of 3Modbus 400269VRead
AI7Avg Voltage L-N average of 3Modbus 400271VRead
AImin8Avg Current average 3Modbus 400273VRead
AI9Real Power phase AModbus 400275ARead
AI10Real Power phase BModbus 400277ARead
AI11Real Power phase CModbus 400279ARead
AI12Power Factor phase AModbus 400281PFRead
AI13Power Factor phase BModbus 400283PFRead
AI14Power Factor phase CModbus 400285PFRead
AI15Voltage phase A-BModbus 400287VRead
AI16Voltage phase B-CModbus 400289VRead
AI17Voltage phase A-CModbus 400291VRead
AI18Voltage phase A-NModbus 400293VRead
AI19Voltage phase B-NModbus 400295VRead
AI20Voltage phase C-NModbus 400297VRead
AI21Current phase AModbus 400299ARead
AI22Current phase BModbus 400301ARead
AI23Current phase CModbus 400303ARead
AI24Present Demand Sub-IntervalModbus 400305kWRead
AI25Minimum DemandModbus 400307kWRead
AImin26Maximum DemandModbus 400309kWRead
AImin27Present DemandModbus 400311kWRead
AI28Peak DemandModbus 400313; not polled by defaultkWRead
AI29CT Size (100 300 etc.)Modbus 400317; not polled by defaultARead
AI30Count of kWH ResetsModbus 400319Read
AI31Count of Peak Demand ResetsModbus 400321Read
AI32Count of Sub IntervalsModbus 400323; not polled by defaultRead
AI33Count of Number Readings in Present Sub–IntervalModbus 400325; not polled by defaultRead
AI34System TypeModbus 400036; not polled by defaultRead
AI35Sub–Interval LengthModbus 400037; not polled by defaultRead
AI36Number of sub-intervals per demand intervalModbus 400038; not polled by defaultRead
BO37Begin new demand sub-intervalModbus 400039 bit 0; not polled by defaultCommand
BO38Clear kWH accumulatorModbus 400039 bit 1Command
BO39Reset peak demandModbus 400039 bit 2Command
Object ID lookup: Contemporary Controls BASgatewayLX Enercept point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric (Veris) Enercept meter via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX

How many BACnet points does the Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX have?

This list has 39 BACnet objects: 36 analog inputs, 3 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX BACnet points are writable?

3 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Square_D_Enercept_Meter (Square_D_Enercept_Meter_LX_HI_LO.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/SquareDEnercept.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX?

Start with AI 2 Real Power kW (Real power, kW); AI 1 Energy Consumption kWh (Energy consumption, kWh); AI 6 Avg Voltage L-L average of 3 (Average voltage L-L); AI 8 Avg Current average 3 (Average current); AI 5 Total Power Factor (Total power factor); AI 27 Present Demand (Present demand); AI 26 Maximum Demand (Maximum demand).

How do I check these points on the real Schneider Electric (Veris) Enercept meter via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Square_D_Enercept_Meter · Square_D_Enercept_Meter_LX_HI_LO.csv. Object names, instances and units are reproduced as published; descriptions are our own.