VRF indoor unit gateway (3 indoor units) · BACnet points list

Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for three Mitsubishi indoor units (A, B, C) through an AG-150 and Procon Mod-IP/50: 72 objects (30 AI, 24 AO, 9 BI, 9 BO), 54 polled by default. Each unit has return air temperature and error code, read-back of setpoint, mode, fan speed, on/off, air direction, inhibit, ventilation and filter reset, and a matching write object for each.

This page lists 72 BACnet objects for the Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Equipment
VRF indoor unit gateway (3 indoor units)
Equipment type
VRF & split air conditioners
BACnet objects
72 (33 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon
Source document
BASgatewayLX Modbus device profile Mitsubishi_AG150_IP50 · Mitsubishi_AG150_IP50_LX.csv
Download CSV 72 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX

Integration in brief

For each unit, write On/Off, Mode, Setpoint and Fan Speed; read return air temperature, on/off and the error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 10Unit A On/Off (Write)Unit A on/off commandCommand
AO 7Unit A Mode (Write)Unit A mode commandCommand
AO 6Unit A Setpoint (Write)Unit A setpoint commandCommand
AO 8Unit A Fan Speed (Write)Unit A fan speed commandCommand
AI 1Unit A Return Air TempUnit A return air temperatureRead
AI 9Unit A On/Off (Read)Unit A on/off statusRead
AI 3Unit A Setpoint (Read)Unit A setpoint in useRead
AI 2Unit A Error CodeUnit A error codeRead

Network setup

Watch out for

Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

72 of 72 shown
Type
Access
Show
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Unit A Return Air TempModbus 400001°CRead
AImin2Unit A Error CodeModbus 400002Read
AImin3Unit A Setpoint (Read)Modbus 400003°CRead
AI4Unit A Operation Mode (Read)Modbus 400004Read
AI5Unit A Fan Speed (Read)Modbus 400005Read
AOmin6Unit A Setpoint (Write)Modbus 400006Command
AOmin7Unit A Mode (Write)Modbus 400007Command
AOmin8Unit A Fan Speed (Write)Modbus 400008Command
AImin9Unit A On/Off (Read)Modbus 400009Read
AOmin10Unit A On/Off (Write)Modbus 400010Command
AI11Unit A Air Direction (Read)Modbus 400031Read
AO12Unit A Air Direction (Write)Modbus 400032Command
AI13Unit A Inhibit (Read)Modbus 400033Read
AO14Unit A Inhibit (Write)Modbus 400034Command
AI15Unit A Ventilation (Read)Modbus 400035Read
AO16Unit A Ventilation (Write)Modbus 400036Command
AI17Unit A Filter Reset (Read)Modbus 400037Read
AO18Unit A Filter Reset (Write)Modbus 400038Command
AI19Unit B Return Air TempModbus 400011°CRead
AI20Unit B Error CodeModbus 400012Read
AI21Unit B Setpoint (Read)Modbus 400013°CRead
AI22Unit B Operation Mode (Read)Modbus 400014Read
AI23Unit B Fan Speed (Read)Modbus 400015Read
AO24Unit B Setpoint (Write)Modbus 400016Command
AO25Unit B Mode (Write)Modbus 400017Command
AO26Unit B Fan Speed (Write)Modbus 400018Command
AI27Unit B On/Off (Read)Modbus 400019Read
AO28Unit B On/Off (Write)Modbus 400020Command
AI29Unit B Air Direction (Read)Modbus 400041Read
AO30Unit B Air Direction (Write)Modbus 400042Command
AI31Unit B Inhibit (Read)Modbus 400043Read
AO32Unit B Inhibit (Write)Modbus 400044Command
AI33Unit B Ventilation (Read)Modbus 400045Read
AO34Unit B Ventilation (Write)Modbus 400046Command
AI35Unit B Filter Reset (Read)Modbus 400047Read
AO36Unit B Filter Reset (Write)Modbus 400048Command
AI37Unit C Return Air TempModbus 400021°CRead
AI38Unit C Error CodeModbus 400022Read
AI39Unit C Setpoint (Read)Modbus 400023°CRead
AI40Unit C Operation Mode (Read)Modbus 400024Read
AI41Unit C Fan Speed (Read)Modbus 400025Read
AO42Unit C Setpoint (Write)Modbus 400026Command
AO43Unit C Mode (Write)Modbus 400027Command
AO44Unit C Fan Speed (Write)Modbus 400028Command
AI45Unit C On/Off (Read)Modbus 400029Read
AO46Unit C On/Off (Write)Modbus 400030Command
AI47Unit C Air Direction (Read)Modbus 400051Read
AO48Unit C Air Direction (Write)Modbus 400052Command
AI49Unit C Inhibit (Read)Modbus 400053Read
AO50Unit C Inhibit (Write)Modbus 400054Command
AI51Unit C Ventilation (Read)Modbus 400055Read
AO52Unit C Ventilation (Write)Modbus 400056Command
AI53Unit C Filter Reset (Read)Modbus 400057Read
AO54Unit C Filter Reset (Write)Modbus 400058Command
BI55Unit A On/Off (R)Modbus 000001; not polled by defaultRead
BO56Unit A On/Off (W)Modbus 000002; not polled by defaultCommand
BI57Unit B On/Off (R)Modbus 000003; not polled by defaultRead
BO58Unit B On/Off (W)Modbus 000004; not polled by defaultCommand
BI59Unit C On/Off (R)Modbus 000005; not polled by defaultRead
BO60Unit C On/Off (W)Modbus 000006; not polled by defaultCommand
BI61Unit A Inhibit (R)Modbus 000007; not polled by defaultRead
BO62Unit A Inhibit (W)Modbus 000008; not polled by defaultCommand
BI63Unit B Inhibit (R)Modbus 000009; not polled by defaultRead
BO64Unit B Inhibit (W)Modbus 000010; not polled by defaultCommand
BI65Unit C Inhibit (R)Modbus 000011; not polled by defaultRead
BO66Unit C Inhibit (W)Modbus 000012; not polled by defaultCommand
BI67Unit A Filter Reset (R)Modbus 000013; not polled by defaultRead
BO68Unit A Filter Reset (W)Modbus 000014; not polled by defaultCommand
BI69Unit B Filter Reset (R)Modbus 000015; not polled by defaultRead
BO70Unit B Filter Reset (W)Modbus 000016; not polled by defaultCommand
BI71Unit C Filter Reset (R)Modbus 000017; not polled by defaultRead
BO72Unit C Filter Reset (W)Modbus 000018; not polled by defaultCommand
Object ID lookup: Contemporary Controls BASgatewayLX Mitsubishi AG-150 Procon point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX

How many BACnet points does the Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX have?

This list has 72 BACnet objects: 30 analog inputs, 24 analog outputs, 9 binary inputs, 9 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX BACnet points are writable?

33 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Mitsubishi_AG150_IP50 (Mitsubishi_AG150_IP50_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/MitsubishiProcon.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX?

Start with AO 10 Unit A On/Off (Write) (Unit A on/off command); AO 7 Unit A Mode (Write) (Unit A mode command); AO 6 Unit A Setpoint (Write) (Unit A setpoint command); AO 8 Unit A Fan Speed (Write) (Unit A fan speed command); AI 1 Unit A Return Air Temp (Unit A return air temperature); AI 9 Unit A On/Off (Read) (Unit A on/off status); AI 3 Unit A Setpoint (Read) (Unit A setpoint in use); AI 2 Unit A Error Code (Unit A error code).

How do I check these points on the real Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Mitsubishi_AG150_IP50 · Mitsubishi_AG150_IP50_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.