Power and energy meter · BACnet points list

Contemporary Controls GE EPM 2200 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the GE EPM 2200: 137 objects (136 AI, 1 AO), 37 polled by default. Polled inputs give total watts, VARs and VA, phase voltages and currents, PF, frequency, neutral current, energy (received, delivered, net, total, VAR-hours, VA-hours) and averages; the rest is unpolled.

This page lists 137 BACnet objects for the Contemporary Controls GE EPM 2200 via BASgatewayLX — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
GE EPM 2200 via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
137 (1 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
EPM 2200, EPM2200, GE Multilin EPM 2200
Source document
BASgatewayLX Modbus device profile GE_EPM2200_Meter_a · GE_EPM2200_Meter_a_LX.csv
Download CSV 137 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls GE EPM 2200 via BASgatewayLX

Integration in brief

Map total watts (3-phase), delivered energy (Wh) and received energy (Wh) first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Watts 3-Ph totalTotal watts (3-phase)Read
AI 20W-hours DeliveredDelivered energy (Wh)Read
AI 19W-hours ReceivedReceived energy (Wh)Read
AI 7Volts A-BVoltage A-BRead
AI 10Amps ACurrent ARead
AI 16Power Factor 3-Ph totalTotal power factorRead
AI 17FrequencyFrequencyRead

Network setup

Watch out for

Contemporary Controls GE EPM 2200 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

137 of 137 shown
Type
Access
Show
Contemporary Controls GE EPM 2200 via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Watts 3-Ph totalModbus 400900WRead
AI2VARs 3-Ph totalModbus 400902VARRead
AI3VAs 3-Ph totalModbus 400904VARead
AI4Volts A-NModbus 401000VRead
AI5Volts B-NModbus 401002VRead
AI6Volts C-NModbus 401004VRead
AImin7Volts A-BModbus 401006VRead
AI8Volts B-CModbus 401008VRead
AI9Volts C-AModbus 401010VRead
AImin10Amps AModbus 401012ARead
AI11Amps BModbus 401014ARead
AI12Amps CModbus 401016ARead
AI13Watts 3-Ph total *Modbus 401018WRead
AI14VARs 3-Ph total *Modbus 401020VARRead
AI15VAs 3-Ph total *Modbus 401022VARead
AImin16Power Factor 3-Ph totalModbus 401024PFRead
AImin17FrequencyModbus 401026HzRead
AI18Neutral CurrentModbus 401028ARead
AImin19W-hours ReceivedModbus 401100Read
AImin20W-hours DeliveredModbus 401102Read
AI21W-hours NetModbus 401104Read
AI22W-hours TotalModbus 401106Read
AI23VAR-hours PositiveModbus 401108Read
AI24VAR-hours NegativeModbus 401110Read
AI25VAR-hours NetModbus 401112Read
AI26VAR-hours TotalModbus 401114Read
AI27VA-hours TotalModbus 401116Read
AI28Amps A AverageModbus 402000ARead
AI29Amps B AverageModbus 402002ARead
AI30Amps C AverageModbus 402004ARead
AI31Positive Watts 3-Ph averageModbus 402006WRead
AI32Positive VARs 3-Ph averageModbus 402008VARRead
AI33Negative Watts 3-Ph averageModbus 402010WRead
AI34Negative VARs 3-Ph averageModbus 402012VARRead
AI35VAs 3-Ph AverageModbus 402014VARead
AI36Positive PF 3-Ph averageModbus 402016PFRead
AI37Negative PF 3-PF averageModbus 402018PFRead
AI38Volts A-N MinimumModbus 403000; not polled by defaultVRead
AI39Volts B-N MinimumModbus 403002; not polled by defaultVRead
AI40Volts C-N MinimumModbus 403004; not polled by defaultVRead
AI41Volts A-B MinimumModbus 403006; not polled by defaultVRead
AI42Volts B-C MinimumModbus 403008; not polled by defaultVRead
AI43Volts C-A MinimumModbus 403010; not polled by defaultVRead
AI44Amps A Minimum Avg demandModbus 403012; not polled by defaultARead
AI45Amps B Minimum Avg demandModbus 403014; not polled by defaultARead
AI46Amps C Minimum Avg demandModbus 403016; not polled by defaultARead
AI47Positive Watts 3-Ph Minimum Average DemandModbus 403018; not polled by defaultWRead
AI48Positive VARs 3-Ph Minimum Average DemandModbus 403020; not polled by defaultVARRead
AI49Negative Watts 3-Ph Minimum Average DemandModbus 403022; not polled by defaultWRead
AI50Negative VARs 3-Ph Minimum Average DemandModbus 403024; not polled by defaultVARRead
AI51VAs 3-Ph Minimum Avg DemandModbus 403026; not polled by defaultVARead
AI52Positive Power Factor 3-Ph Minimum Avg DemandModbus 403028; not polled by defaultPFRead
AI53Negative Power Factor 3-Ph Minimum Avg DemandModbus 403030; not polled by defaultPFRead
AI54Frequency MinimumModbus 403032; not polled by defaultHzRead
AI55Volts A-N MaximumModbus 403100; not polled by defaultVRead
AI56Volts B-N MaximumModbus 403102; not polled by defaultVRead
AI57Volts C-N MaximumModbus 403104; not polled by defaultVRead
AI58Volts A-B MaximumModbus 403106; not polled by defaultVRead
AI59Volts B-C MaximumModbus 403108; not polled by defaultVRead
AI60Volts C-A MaximumModbus 403110; not polled by defaultVRead
AI61Amps A Maximum Avg demandModbus 403112; not polled by defaultARead
AI62Amps B Maximum Avg demandModbus 403114; not polled by defaultARead
AI63Amps C Maximum Avg demandModbus 403116; not polled by defaultARead
AI64Positive Watts 3-Ph Maximum Avg demandModbus 403118; not polled by defaultWRead
AI65Positive VARs 3-Ph Maximum Avg demandModbus 403120; not polled by defaultVARRead
AI66Negative Watts 3-Ph Maximum Avg demandModbus 403122; not polled by defaultWRead
AI67Negative VARs 3-Ph Maximum Avg demandModbus 403124; not polled by defaultVARRead
AI68VAs 3-Ph Maximum Avg DemandModbus 403126; not polled by defaultVARead
AI69Positive Power Factor 3-Ph Maximum Avg DemandModbus 403128; not polled by defaultPFRead
AI70Negative Power Factor 3-Ph Maximum Avg demandModbus 403130; not polled by defaultPFRead
AI71Frequency MaximumModbus 403132; not polled by defaultHzRead
AI72Phase A CurrentModbus 404100; not polled by default° (phase)Read
AI73Phase B CurrentModbus 404101; not polled by default° (phase)Read
AI74Phase C CurrentModbus 404102; not polled by default° (phase)Read
AI75Angle Volts A-BModbus 404103; not polled by default° (phase)Read
AI76Angle Volts B-CModbus 404104; not polled by default° (phase)Read
AI77Angle Volts C-AModbus 404105; not polled by default° (phase)Read
AI78Meter StatusModbus 405000; not polled by defaultRead
AI79Time Since ResetModbus 405002; not polled by defaultRead
AI80System Sanity IndicatorModbus 440001; not polled by defaultRead
AI81Volts A-N *Modbus 440002; not polled by defaultVRead
AI82Volts B-N *Modbus 440003; not polled by defaultVRead
AI83Volts C-N *Modbus 440004; not polled by defaultVRead
AI84Amps A *Modbus 440005; not polled by defaultARead
AI85Amps B *Modbus 440006; not polled by defaultARead
AI86Amps C *Modbus 440007; not polled by defaultARead
AI87Watts 3-Ph total *Modbus 440008; not polled by defaultWRead
AI88VARs 3-Ph total *Modbus 440009; not polled by defaultVARRead
AI89VAs 3-Ph total *Modbus 440010; not polled by defaultVARead
AI90Power Factor 3-Ph TotalModbus 440011; not polled by defaultPFRead
AI91Frequency *Modbus 440012; not polled by defaultHzRead
AI92Volts A-B *Modbus 440013; not polled by defaultVRead
AI93Volts B-C *Modbus 440014; not polled by defaultVRead
AI94Volts C-A *Modbus 440015; not polled by defaultVRead
AI95CT numeratorModbus 440016; not polled by defaultRead
AI96CT multiplierModbus 440017; not polled by defaultRead
AI97CT denominatorModbus 440018; not polled by defaultRead
AI98PT numeratorModbus 440019; not polled by defaultRead
AI99PT multiplierModbus 440020; not polled by defaultRead
AI100PT denominatorModbus 440021; not polled by defaultRead
AI101W-hours PositiveModbus 440022; not polled by defaultWhRead
AI102W-hours NegativeModbus 440024; not polled by defaultWhRead
AI103VAR-hours PositiveModbus 440026; not polled by defaultVARhRead
AI104VAR-hours NegativeModbus 440028; not polled by defaultVARhRead
AI105VA-hoursModbus 440030; not polled by defaultWhRead
AI106Neutral CurrentModbus 440032; not polled by defaultARead
AO107Reset Energy AccumulatorModbus 440100; not polled by defaultCommand
AI108Meter Name ASCII 1 and 2Modbus 400001; not polled by defaultRead
AI109Meter Name ASCII 3 and 4Modbus 400002; not polled by defaultRead
AI110Meter Name ASCII 5 and 6Modbus 400003; not polled by defaultRead
AI111Meter Name ASCII 7 and 8Modbus 400004; not polled by defaultRead
AI112Meter Name ASCII 9 and 10Modbus 400005; not polled by defaultRead
AI113Meter Name ASCII 11 and 12Modbus 400006; not polled by defaultRead
AI114Meter Name ASCII 13 and 14Modbus 400007; not polled by defaultRead
AI115Meter Name ASCII 15 and 16Modbus 400008; not polled by defaultRead
AI116Meter Serial Number ASCII 1 and 2Modbus 400009; not polled by defaultRead
AI117Meter Serial Number ASCII 3 and 4Modbus 400010; not polled by defaultRead
AI118Meter Serial Number ASCII 5 and 6Modbus 400011; not polled by defaultRead
AI119Meter Serial Number ASCII 7 and 8Modbus 400012; not polled by defaultRead
AI120Meter Serial Number ASCII 9 and 10Modbus 400013; not polled by defaultRead
AI121Meter Serial Number ASCII 11 and 12Modbus 400014; not polled by defaultRead
AI122Meter Serial Number ASCII 13 and 14Modbus 400015; not polled by defaultRead
AI123Meter Serial Number ASCII 15 and 16Modbus 400016; not polled by defaultRead
AI124Meter TypeModbus 400017; not polled by defaultRead
AI125Firmware Version ASCII 1 and 2Modbus 400018; not polled by defaultRead
AI126Firmware Version ASCII 3 and 4Modbus 400019; not polled by defaultRead
AI127Map VersionModbus 400020; not polled by defaultRead
AI128Meter ConfigurationModbus 400021; not polled by defaultRead
AI129ASIC VersionModbus 400022; not polled by defaultRead
AI130OEM Part Number ASCII 1 and 2Modbus 400040; not polled by defaultRead
AI131OEM Part Number ASCII 3 and 4Modbus 400041; not polled by defaultRead
AI132OEM Part Number ASCII 5 and 6Modbus 400042; not polled by defaultRead
AI133OEM Part Number ASCII 7 and 8Modbus 400043; not polled by defaultRead
AI134OEM Part Number ASCII 9 and 10Modbus 400044; not polled by defaultRead
AI135OEM Part Number ASCII 11 and 12Modbus 400045; not polled by defaultRead
AI136OEM Part Number ASCII 13 and 14Modbus 400046; not polled by defaultRead
AI137OEM Part Number ASCII 15 and 16Modbus 400047; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX GE EPM 2200 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GE EPM 2200 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls GE EPM 2200 via BASgatewayLX

How many BACnet points does the Contemporary Controls GE EPM 2200 via BASgatewayLX have?

This list has 137 BACnet objects: 136 analog inputs, 1 analog output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls GE EPM 2200 via BASgatewayLX BACnet points are writable?

1 of the 137 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls GE EPM 2200 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile GE_EPM2200_Meter_a (GE_EPM2200_Meter_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/GE_EPM2200_LX_File.zip.

What are the minimum BACnet points to integrate the Contemporary Controls GE EPM 2200 via BASgatewayLX?

Start with AI 1 Watts 3-Ph total (Total watts (3-phase)); AI 20 W-hours Delivered (Delivered energy (Wh)); AI 19 W-hours Received (Received energy (Wh)); AI 7 Volts A-B (Voltage A-B); AI 10 Amps A (Current A); AI 16 Power Factor 3-Ph total (Total power factor); AI 17 Frequency (Frequency).

How do I check these points on the real GE EPM 2200 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile GE_EPM2200_Meter_a · GE_EPM2200_Meter_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.