In-row precision cooling unit (chilled water) · BACnet points list

Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the APC ACRC301: 140 objects (117 AI, 23 AO), all polled. Outputs set cooling and supply air setpoints, airflow control, fan speed limits, delta-T setpoint, thresholds and startup/idle options; inputs give overall and group status, cool output and demand, rack, supply and return air temperatures, airflow, fan speed, chilled water valve, flow and temperatures, run hours and each alarm flag.

This page lists 140 BACnet objects for the Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Equipment
In-row precision cooling unit (chilled water)
Equipment type
Other equipment
BACnet objects
140 (23 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water
Source document
BASgatewayLX Modbus device profile Schneider_Electric_ACRC301_a · Schneider_Electric_ACRC301_a_LX.csv
Download CSV 140 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX

Integration in brief

Write the cooling setpoint (and supply air setpoint if used), then read operate mode, rack inlet, supply and return temperatures, cool output and the alarm flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 4COOL SETPOINTCooling setpointCommand
AO 5SUPPLY AIR SETPOINTSupply air setpointCommand
AI 23OPERATE MODEOperate modeRead
AI 1OVERALL STATUSOverall statusRead
AI 26UNIT MAX RACK INLET TEMPMax rack inlet temperatureRead
AI 27SUPPLY AIR TEMPSupply air temperatureRead
AI 28RETURN AIR TEMPReturn air temperatureRead
AI 30FAN SPEEDFan speedRead
AI 24UNIT COOL OUTPUTUnit cooling outputRead
AI 81COOL FUNCTION UNAVAILABLECooling function unavailable alarmRead

Network setup

Watch out for

Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

140 of 140 shown
Type
Access
Show
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX BACnet Points List
DescriptionStates
AImin1OVERALL STATUSModbus 400001Read
AI2GROUP COOL OUTPUTModbus 400002kWRead
AI3GROUP COOL DEMANDModbus 400004kWRead
AOmin4COOL SETPOINTModbus 400006°FCommand
AOmin5SUPPLY AIR SETPOINTModbus 400008°FCommand
AI6GROUP AIR FLOWModbus 400010cfmRead
AI7GROUP MAX RACK TEMPModbus 400012°FRead
AI8GROUP MIN RACK TEMPModbus 400014°FRead
AO9AIRFLOW CONTROLModbus 400016Command
AO10NUMBER OF UNITSModbus 400017Command
AI11CONFIGURATION TYPEModbus 400019Read
AI12COOL PID PModbus 400020Read
AI13COOL PID 1Modbus 400022Read
AI14COOL PID DModbus 400024Read
AI15PERCENT GLYCOLModbus 400026%Read
AO16MAX FAN SPEEDModbus 400028%Command
AO17ALTITUDEModbus 400031ftCommand
AO18NUMBER ACTIVE FLOW CONTROLLERSModbus 400033Command
AI19ACTIVE FLOW CONTROL BIASModbus 400035Read
AI20ACTIVE FLOW CONTROL STATUSModbus 400036Read
AO21ACTIVE FLOW CONTROL LAMP TESTModbus 400037Command
AO22DELTA T SETPOINTModbus 400038°FCommand
AImin23OPERATE MODEModbus 400207Read
AImin24UNIT COOL OUTPUTModbus 400208kWRead
AI25UNIT COOL DEMANDModbus 400210kWRead
AImin26UNIT MAX RACK INLET TEMPModbus 400212°FRead
AImin27SUPPLY AIR TEMPModbus 400214°FRead
AImin28RETURN AIR TEMPModbus 400216°FRead
AI29UNIT AIR FLOWModbus 400218cfmRead
AImin30FAN SPEEDModbus 400220%Read
AI31ACTIVE POWER SOURCEModbus 400222Read
AI32FILTER DIFFERENTIAL PRESSUREModbus 400223inWCRead
AI33CHILLED WATER VALVE POSITIONModbus 400227%Read
AI34CHILLED WATER FLOWModbus 400229gpmRead
AI35CHILLED WATER TEMP INModbus 400231°FRead
AI36CHILLED WATER TEMP OUTModbus 400233°FRead
AI37AIR FILTER RUNHOURModbus 400235hRead
AI38FAN 1 RUNHOURModbus 400237hRead
AI39FAN 2 RUNHOURModbus 400239hRead
AI40FAN 3 RUNHOURModbus 400241hRead
AI41FAN 4 RUNHOURModbus 400243hRead
AI42FAN 5 RUNHOURModbus 400245hRead
AI43FAN 6 RUNHOURModbus 400247hRead
AI44FAN 7 RUNHOURModbus 400249hRead
AI45FAN 8 RUNHOURModbus 400251hRead
AI46FAN PSU 1 RUNHOURModbus 400253hRead
AI47FAN PSU 2 RUNHOURModbus 400255hRead
AI48CONDENSATE PUMP RUNHOURModbus 400257hRead
AO49AIR FILTER SERVICE INTERVALModbus 400259weeksCommand
AO50AIR FILTER SERVICE INTERVAL ALARMModbus 400261Command
AO51RACK TEMP HIGH THRESHModbus 400262°FCommand
AO52SUPPLY AIR TEMP HIGH THRESHModbus 400264°FCommand
AO53RETURN AIR TEMP HIGH THRESHModbus 400266°FCommand
AO54ENTERING CHILLED WATER TEMP HIGH THRESHModbus 400268°FCommand
AO55STARTUP DELAYModbus 400270sCommand
AI56CHILLED WATER VALVE CONTROLModbus 400272Read
AO57IDLE ON LEAKModbus 400273Command
AO58STANDBY INPUT NORMAL STATEModbus 400274Command
AI59STANDBY INPUT STATEModbus 400275Read
AI60OUTPUT STATE 1Modbus 400277Read
AO61POWER SOURCEModbus 400279Command
AO62IDLE ON COOL FAILModbus 400280Command
AI63OUTPUT STATE 1Modbus 400281Read
AI64OUTPUT STATE 2Modbus 400282Read
AI65OUTPUT STATE 3Modbus 400283Read
AI66OUTPUT STATE 4Modbus 400284Read
AI67MAXIMUM CHILLED WATER FLOWModbus 400290gpmRead
AO68BYPASS VALUE POSITIONModbus 400292Command
AI69UNIT SERVICE INTERVALModbus 400293weeksRead
AI70UNIT SERVICE INTERVAL ALARMModbus 400295Read
AI71DEW POINT TEMPModbus 400296°FRead
AI72COIL CHILLED WATER TEMPModbus 400298°FRead
AI73UNIT POWERModbus 400300°FRead
AI74UNIT ENERGYModbus 400302°FRead
AI75UNIT RUNHOURModbus 400304hRead
AI76CIRCULATION PUMP RUNHOURModbus 400306hRead
AO77NUMBER OF RACK INLET TEMPERATURE SENSORSModbus 400308Command
AO78NUMBER OF LEAK DETECTORSModbus 400310Command
AI79AIR_FILTER_TYPEModbus 400312Read
AI80INTERNAL COMM ERRORModbus 400385Read
AImin81COOL FUNCTION UNAVAILABLEModbus 400387Read
AI82HIGH RACK TEMPModbus 400388Read
AI83AIR FILTER CLOGGEDModbus 400389Read
AI84LOWER RETURN AIR SENSOR ERRORModbus 400390Read
AI85UPPER RETURN AIR SENSOR ERRORModbus 400391Read
AI86LOWER SUPPLY AIR SENSOR ERRORModbus 400392Read
AI87UPPER SUPPLY AIR SENSOR ERRORModbus 400393Read
AI88RACK TEMP SENSOR 1 ERRORModbus 400394Read
AI89CHILLED WATER VALVE ACTUATOR ERRORModbus 400395Read
AI90FAN 1 ERRORModbus 400396Read
AI91FAN 2 ERRORModbus 400397Read
AI92FAN 3 ERRORModbus 400398Read
AI93FAN 4 ERRORModbus 400399Read
AI94FAN 5 ERRORModbus 400400Read
AI95FAN 6 ERRORModbus 400401Read
AI96FAN 7 ERRORModbus 400402Read
AI97FAN 8 ERRORModbus 400403Read
AI98WATER DETECTEDModbus 400404Read
AI99CHECK CONDS MGMT SYSTEMModbus 400405Read
AI100CHILLED WATER FLOWMETER ERRORModbus 400406Read
AI101ENTERING CHILLED WATER HIGH TEMPModbus 400407Read
AI102ENTERING CHILLED WATER TEMP SENSOR ERRORModbus 400408Read
AI103LEAVING CHILLED WATER TEMP SENSOR ERRORModbus 400409Read
AI104CONDENSATE PAN FULLModbus 400410Read
AI105PRIMARY POWER SOURCE UNAVAILABLEModbus 400411Read
AI106SECONDARY POWER SOURCE UNAVAILABLEModbus 400412Read
AI107FAN POWER SUPPLY 1 ERRORModbus 400413Read
AI108FAN POWER SUPPLY 2 ERRORModbus 400414Read
AI109AIR FILTER RUNHOUR VIOLATIONModbus 400415Read
AI110STANDBY DUE TO INPUT CONTACTModbus 400417Read
AI111UNEXPECTED NUMBER OF UNITS IN GROUPModbus 400418Read
AI112SUPPLY HIGH TEMPERATUREModbus 400419Read
AI113RETURN HIGH TEMPERATUREModbus 400420Read
AI114DP FILTER SENSOR ERRORModbus 400421Read
AI115CHILLED WATER VALVE NOT SET TO AUTOModbus 400423Read
AI116IDLE DUE TO LEAK DETECTEDModbus 400424Read
AI117ECOAISLE DOOR OPENModbus 400430Read
AI118UNEXPECTED NUMBER OF ACTIVE FLOW CONTROLLERSModbus 400431Read
AI119INSUFFICIENT AIRFLOWModbus 400432Read
AI120ACTIVE FLOW CONTROLLER SENSOR ERRORModbus 400433Read
AI121RACK TEMP SENSOR 2 ERRORModbus 400434Read
AI122RACK TEMP SENSOR 3 ERRORModbus 400435Read
AI123RACK TEMP SENSOR 4 ERRORModbus 400436Read
AI124UNIT SERVICE REQUIREDModbus 400437Read
AI125HUMIDITY SENSOR ERRORModbus 400438Read
AI126COIL CONDENSATION POSSIBLEModbus 400439Read
AI127CONTROLLER POWER SUPPLY 1 ERRORModbus 400440Read
AI128CONTROLLER POWER SUPPLY 2 ERRORModbus 400441Read
AI129COIL_CHILLED_WATER_TEMP_SENSOR_ERRORModbus 400442Read
AI130FAN POWER SUPPLY 1 CURRENT SENSOR ERRORModbus 400443Read
AI131FAN POWER SUPPLY 2 CURRENT SENSOR ERRORModbus 400444Read
AI132FACTORY CONFIGURATION NOT COMPLETEModbus 400445Read
AI133UNIT IN MAINTENANCE MODEModbus 400446Read
AI134UNEXPECTED NUMBER OF RACK INLET SENSORSModbus 400447Read
AI135UNEXPECTED NUMBER OF LEAK SENSORSModbus 400448Read
AI136OUTPUT RELAY 1 ABNORMALModbus 400449Read
AI137OUTPUT RELAY 2 ABNORMALModbus 400450Read
AI138OUTPUT RELAY 3 ABNORMALModbus 400451Read
AI139OUTPUT RELAY 4 ABNORMALModbus 400452Read
AI140CIRCULATION PUMP ERRORModbus 400453Read
Object ID lookup: Contemporary Controls BASgatewayLX APC ACRC301 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric APC InRow RC ACRC301 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX

How many BACnet points does the Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX have?

This list has 140 BACnet objects: 117 analog inputs, 23 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX BACnet points are writable?

23 of the 140 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Schneider_Electric_ACRC301_a (Schneider_Electric_ACRC301_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/SchneiderACRC301.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX?

Start with AO 4 COOL SETPOINT (Cooling setpoint); AO 5 SUPPLY AIR SETPOINT (Supply air setpoint); AI 23 OPERATE MODE (Operate mode); AI 1 OVERALL STATUS (Overall status); AI 26 UNIT MAX RACK INLET TEMP (Max rack inlet temperature); AI 27 SUPPLY AIR TEMP (Supply air temperature); AI 28 RETURN AIR TEMP (Return air temperature); AI 30 FAN SPEED (Fan speed); AI 24 UNIT COOL OUTPUT (Unit cooling output); AI 81 COOL FUNCTION UNAVAILABLE (Cooling function unavailable alarm).

How do I check these points on the real Schneider Electric APC InRow RC ACRC301 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Schneider_Electric_ACRC301_a · Schneider_Electric_ACRC301_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.