- ASCO Power Manager Xp via BASgatewayLX
Power meter (transfer switch power manager) · BACnet points list
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the ASCO Power Manager Xp: 356 objects (110 AI, 98 AO, 44 BI, 104 BO), all polled. It reads phase and average voltages, currents, kW, kVAR, kVA and PF, frequency, normal and emergency kWh/kVARh, demand, switch positions, digital inputs and the 12 setpoint alarm states; outputs set nominal ratings, digital outputs, the clock and alarm acknowledges.
This page lists 356 BACnet objects for the Contemporary Controls ASCO Power Manager Xp via BASgatewayLX — 202 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- ASCO Power Manager Xp via BASgatewayLX
- Equipment
- Power meter (transfer switch power manager)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 356 (202 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
Read the electrical totals, the normal and emergency energy registers and the switch position word.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 20 | Active Power total | Total active power | Read |
| AI 8 | Line to line average voltage | Average line-line voltage | Read |
| AI 14 | Average current | Average current | Read |
| AI 28 | Power Factor total | Total power factor | Read |
| AI 33 | Frequency on phase VA | Frequency | Read |
| AI 34 | Normal kWH Import | Normal source kWh import | Read |
| AI 45 | Emerg kWH Import | Emergency source kWh import | Read |
| AI 71 | Main auxiliary Switch positions | Main/auxiliary switch positions | Read |
| AI 101 | Health status word | Health status word | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Nominal voltage/current/kW/frequency outputs (AO 41-44) are meter setup values; don't write them cyclically.
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Phase A line to neutral voltage | Modbus 400011 | V | Read | |
| AI | 2 | Phase B line to neutral voltage | Modbus 400012 | V | Read | |
| AI | 3 | Phase C line to neutral voltage | Modbus 400013 | V | Read | |
| AI | 4 | Line to neutral average voltage | Modbus 400014 | V | Read | |
| AI | 5 | A-B line to line voltage | Modbus 400015 | V | Read | |
| AI | 6 | B-C line to line voltage | Modbus 400016 | V | Read | |
| AI | 7 | C-A line to line voltage | Modbus 400017 | V | Read | |
| AImin | 8 | Line to line average voltage | Modbus 400018 | V | Read | |
| AI | 9 | Line to line voltage unbalance | Modbus 400019 | % | Read | |
| AI | 10 | Line to neutral voltage unbalance | Modbus 400020 | % | Read | |
| AI | 11 | Phase A current | Modbus 400021 | A | Read | |
| AI | 12 | Phase B current | Modbus 400022 | A | Read | |
| AI | 13 | Phase C current | Modbus 400023 | A | Read | |
| AImin | 14 | Average current | Modbus 400024 | A | Read | |
| AI | 15 | Current unbalance | Modbus 400025 | % | Read | |
| AI | 16 | CT4 or neutral current | Modbus 400026 | A | Read | |
| AI | 17 | Active Power phase A | Modbus 400031 | kW | Read | |
| AI | 18 | Active Power phase B | Modbus 400032 | kW | Read | |
| AI | 19 | Active Power phase C | Modbus 400033 | kW | Read | |
| AImin | 20 | Active Power total | Modbus 400034 | kW | Read | |
| AI | 21 | Reactive Power phase A | Modbus 400035 | kVAR | Read | |
| AI | 22 | Reactive Power phase B | Modbus 400036 | kVAR | Read | |
| AI | 23 | Reactive Power phase C | Modbus 400037 | kVAR | Read | |
| AI | 24 | Reactive Power total | Modbus 400038 | kVAR | Read | |
| AI | 25 | Power Factor phase A | Modbus 400039 | PF | Read | |
| AI | 26 | Power Factor phase B | Modbus 400040 | PF | Read | |
| AI | 27 | Power Factor phase C | Modbus 400041 | PF | Read | |
| AImin | 28 | Power Factor total | Modbus 400042 | PF | Read | |
| AI | 29 | volt-ampere Power phase A | Modbus 400043 | kVA | Read | |
| AI | 30 | volt-ampere Power phase B | Modbus 400044 | kVA | Read | |
| AI | 31 | volt-ampere Power phase C | Modbus 400045 | kVA | Read | |
| AI | 32 | volt-ampere Power total | Modbus 400046 | kVA | Read | |
| AImin | 33 | Frequency on phase VA | Modbus 400048 | Hz | Read | |
| AImin | 34 | Normal kWH Import | Modbus 400051 | kWh | Read | |
| AI | 35 | Normal kWH Export | Modbus 400053 | kWh | Read | |
| AI | 36 | Normal kWH Net | Modbus 400055 | kWh | Read | |
| AI | 37 | Normal kVarH Import | Modbus 400057 | Read | ||
| AI | 38 | Normal kVarH Export | Modbus 400059 | Read | ||
| AI | 39 | Normal kVarH Net | Modbus 400061 | Read | ||
| AI | 40 | Normal kVAH Net | Modbus 400063 | Read | ||
| AO | 41 | Nominal Voltage | Modbus 400065 | V | Command | |
| AO | 42 | Nominal Current | Modbus 400066 | A | Command | |
| AO | 43 | Nominal kW Capacity | Modbus 400067 | kW | Command | |
| AO | 44 | Nominal Freq 0– 60Hz 1–50Hz | Modbus 400068 | Command | ||
| AImin | 45 | Emerg kWH Import | Modbus 400071 | kWh | Read | |
| AI | 46 | Emerg kWH Export | Modbus 400073 | kWh | Read | |
| AI | 47 | Emerg kWH Net | Modbus 400075 | kWh | Read | |
| AI | 48 | Emerg kVarH Import | Modbus 400077 | Read | ||
| AI | 49 | Emerg kVarH Export | Modbus 400079 | Read | ||
| AI | 50 | Emerg kVarH Net | Modbus 400081 | Read | ||
| AI | 51 | Emerg kVAH Net | Modbus 400083 | Read | ||
| AI | 52 | Active Power (Watts) total | Modbus 400087 | kW | Read | |
| AI | 53 | Instantaneous Watt Demand | Modbus 400088 | kW | Read | |
| AI | 54 | Maximum Watt Demand | Modbus 400089 | kW | Read | |
| AI | 55 | Active Power (Watts) total | Modbus 400090 | kW | Read | |
| AI | 56 | Average current | Modbus 400091 | A | Read | |
| AI | 57 | Line to line average voltage | Modbus 400092 | V | Read | |
| AI | 58 | Frequency on phase VA | Modbus 400093 | Hz | Read | |
| BI | 59 | General purpose digital inputs 1 | Modbus 400094 bit 0 | Read | ||
| BI | 60 | General purpose digital inputs 2 | Modbus 400094 bit 1 | Read | ||
| BI | 61 | General purpose digital inputs 3 | Modbus 400094 bit 2 | Read | ||
| BI | 62 | General purpose digital inputs 4 | Modbus 400094 bit 3 | Read | ||
| BI | 63 | General purpose digital inputs 5 | Modbus 400094 bit 4 | Read | ||
| BI | 64 | General purpose digital inputs 6 | Modbus 400094 bit 5 | Read | ||
| BI | 65 | General purpose digital inputs 7 | Modbus 400094 bit 6 | Read | ||
| BI | 66 | General purpose digital inputs 8 | Modbus 400094 bit 7 | Read | ||
| BO | 67 | General purpose digital outputs 1 | Modbus 400095 bit 0 | Command | ||
| BO | 68 | General purpose digital outputs 2 | Modbus 400095 bit 1 | Command | ||
| BO | 69 | General purpose digital outputs 3 | Modbus 400095 bit 2 | Command | ||
| BO | 70 | General purpose digital outputs 4 | Modbus 400095 bit 3 | Command | ||
| AImin | 71 | Main auxiliary Switch positions | Modbus 400096 | Read | ||
| AI | 72 | Active Power total | Modbus 400097 | kW | Read | |
| AI | 73 | Reactive Power total | Modbus 400098 | kVAR | Read | |
| AI | 74 | volt-ampere Power total | Modbus 400099 | kVA | Read | |
| AI | 75 | Power Factor total | Modbus 400100 | PF | Read | |
| AI | 76 | Frequency on phase VA | Modbus 400101 | Hz | Read | |
| AI | 77 | Software Version string Char 1 and 2 | Modbus 400102 | Read | ||
| AI | 78 | Software Version string Char 3 and 4 | Modbus 400103 | Read | ||
| AI | 79 | Software Version string Char 5 and 6 | Modbus 400104 | Read | ||
| AI | 80 | Software Version string Char 7 and 8 | Modbus 400105 | Read | ||
| AI | 81 | Software Version string Char 9 and 10 | Modbus 400106 | Read | ||
| AI | 82 | Software Version string Char 11 and 12 | Modbus 400107 | Read | ||
| AI | 83 | Software Build Date string Char 11 and 12 | Modbus 400108 | Read | ||
| AI | 84 | Software Build Date string Char 11 and 12 | Modbus 400109 | Read | ||
| AI | 85 | Software Build Date string Char 11 and 12 | Modbus 400110 | Read | ||
| AI | 86 | Software Build Date string Char 11 and 12 | Modbus 400111 | Read | ||
| AI | 87 | Software Build Date string Char 11 and 12 | Modbus 400112 | Read | ||
| AI | 88 | Software Build Date string Char 11 and 12 | Modbus 400113 | Read | ||
| AI | 89 | Device Serial Number Char 1 and 2 | Modbus 400114 | Read | ||
| AI | 90 | Device Serial Number Char 3 and 4 | Modbus 400115 | Read | ||
| AI | 91 | Device Serial Number Char 5 and 6 | Modbus 400116 | Read | ||
| AI | 92 | Device Serial Number Char 7 and 8 | Modbus 400117 | Read | ||
| AI | 93 | Device Serial Number Char 9 and 10 | Modbus 400118 | Read | ||
| AI | 94 | Device Serial Number Char 11 and 12 | Modbus 400119 | Read | ||
| AI | 95 | Device Model Number Char 1 and 2 | Modbus 400120 | Read | ||
| AI | 96 | Device Model Number Char 1 and 2 | Modbus 400121 | Read | ||
| AI | 97 | Device Model Number Char 1 and 2 | Modbus 400122 | Read | ||
| AI | 98 | Device Model Number Char 1 and 2 | Modbus 400123 | Read | ||
| AI | 99 | Device Model Number Char 1 and 2 | Modbus 400124 | Read | ||
| AI | 100 | Device Model Number Char 1 and 2 | Modbus 400125 | Read | ||
| AImin | 101 | Health status word | Modbus 400127 | Read | ||
| BI | 102 | Setpoint #1 Output Status Normal/Tripped | Modbus 400128 bit 0 | Read | ||
| BI | 103 | Setpoint #1 Acknowledge State Ack/Pendg | Modbus 400128 bit 1 | Read | ||
| BI | 104 | Setpoint #2 Output Status Normal/Tripped | Modbus 400128 bit 2 | Read | ||
| BI | 105 | Setpoint #2 Acknowledge State Ack/Pendg | Modbus 400128 bit 3 | Read | ||
| BI | 106 | Setpoint #3 Output Status Normal/Tripped | Modbus 400128 bit 4 | Read | ||
| BI | 107 | Setpoint #3 Acknowledge State Ack/Pendg | Modbus 400128 bit 5 | Read | ||
| BI | 108 | Setpoint #4 Output Status Normal/Tripped | Modbus 400128 bit 6 | Read | ||
| BI | 109 | Setpoint #4 Acknowledge State Ack/Pendg | Modbus 400128 bit 7 | Read | ||
| BI | 110 | Setpoint #5 Output Status Normal/Tripped | Modbus 400128 bit 8 | Read | ||
| BI | 111 | Setpoint #5 Acknowledge State Ack/Pendg | Modbus 400128 bit 9 | Read | ||
| BI | 112 | Setpoint #6 Output Status Normal/Tripped | Modbus 400128 bit 10 | Read | ||
| BI | 113 | Setpoint #6 Acknowledge State Ack/Pendg | Modbus 400128 bit 11 | Read | ||
| BI | 114 | Setpoint #7 Output Status Normal/Tripped | Modbus 400128 bit 12 | Read | ||
| BI | 115 | Setpoint #7 Acknowledge State Ack/Pendg | Modbus 400128 bit 13 | Read | ||
| BI | 116 | Setpoint #8 Output Status Normal/Tripped | Modbus 400128 bit 14 | Read | ||
| BI | 117 | Setpoint #8 Acknowledge State Ack/Pendg | Modbus 400128 bit 15 | Read | ||
| BI | 118 | Setpoint #9 Output Status Normal/Tripped | Modbus 400129 bit 0 | Read | ||
| BI | 119 | Setpoint #9 Acknowledge State Ack/Pendg | Modbus 400129 bit 1 | Read | ||
| BI | 120 | Setpoint #10 Output Status Normal/Tripped | Modbus 400129 bit 2 | Read | ||
| BI | 121 | Setpoint #10 Acknowledge State Ack/Pendg | Modbus 400129 bit 3 | Read | ||
| BI | 122 | Setpoint #11 Output Status Normal/Tripped | Modbus 400129 bit 4 | Read | ||
| BI | 123 | Setpoint #11 Acknowledge State Ack/Pendg | Modbus 400129 bit 5 | Read | ||
| BI | 124 | Setpoint #12 Output Status Normal/Tripped | Modbus 400129 bit 6 | Read | ||
| BI | 125 | Setpoint #12 Acknowledge State Ack/Pendg | Modbus 400129 bit 7 | Read | ||
| BI | 126 | kW Demand Setpoint Status Normal/Trip | Modbus 400129 bit 8 | Read | ||
| AI | 127 | Active Power (Watts) total | Modbus 400130 | kW | Read | |
| AI | 128 | Instantaneous Watt Demand | Modbus 400131 | kW | Read | |
| AI | 129 | Maximum Watt Demand | Modbus 400132 | kW | Read | |
| AI | 130 | Maximum Watt Demand Date | Modbus 400133 | Read | ||
| AI | 131 | Maximum Watt Demand Month | Modbus 400134 | Read | ||
| AI | 132 | Maximum Watt Demand Year | Modbus 400135 | Read | ||
| AI | 133 | Maximum Watt Demand Hour | Modbus 400136 | Read | ||
| AI | 134 | Maximum Watt Demand Minute | Modbus 400137 | Read | ||
| AO | 135 | Power Manager Hours | Modbus 400141 | Command | ||
| AO | 136 | Power Manager Minutes | Modbus 400142 | Command | ||
| AO | 137 | Power Manager Year | Modbus 400143 | Command | ||
| AO | 138 | Power Manager Month | Modbus 400144 | Command | ||
| AO | 139 | Power Manager Day of Month | Modbus 400145 | Command | ||
| AO | 140 | Power Manager Day of Week (0-S 1-M etc) | Modbus 400146 | Command | ||
| BO | 141 | Setpoint #1 Output Alarm Acknowledge | Modbus 400148 bit 0 | Command | ||
| BO | 142 | Setpoint #2 Output Alarm Acknowledge | Modbus 400148 bit 1 | Command | ||
| BO | 143 | Setpoint #3 Output Alarm Acknowledge | Modbus 400148 bit 2 | Command | ||
| BO | 144 | Setpoint #4 Output Alarm Acknowledge | Modbus 400148 bit 3 | Command | ||
| BO | 145 | Setpoint #5 Output Alarm Acknowledge | Modbus 400148 bit 4 | Command | ||
| BO | 146 | Setpoint #6 Output Alarm Acknowledge | Modbus 400148 bit 5 | Command | ||
| BO | 147 | Setpoint #7 Output Alarm Acknowledge | Modbus 400148 bit 6 | Command | ||
| BO | 148 | Setpoint #8 Output Alarm Acknowledge | Modbus 400148 bit 7 | Command | ||
| BO | 149 | Setpoint #9 Output Alarm Acknowledge | Modbus 400148 bit 8 | Command | ||
| BO | 150 | Setpoint #10 Output Alarm Acknowledge | Modbus 400148 bit 9 | Command | ||
| BO | 151 | Setpoint #11 Output Alarm Acknowledge | Modbus 400148 bit 10 | Command | ||
| BO | 152 | Setpoint #12 Output Alarm Acknowledge | Modbus 400148 bit 11 | Command | ||
| AI | 153 | Number of Unread Event Log Entries | Modbus 400149 | Read | ||
| AI | 154 | Event Number (0 – The Latest One) | Modbus 400150 | Read | ||
| AI | 155 | Event Year | Modbus 400151 | Read | ||
| AI | 156 | Event Month | Modbus 400152 | Read | ||
| AI | 157 | Event Month Day | Modbus 400153 | Read | ||
| AI | 158 | Event Week Day | Modbus 400154 | Read | ||
| AI | 159 | Event Hour | Modbus 400155 | Read | ||
| AI | 160 | Event Minute | Modbus 400156 | Read | ||
| AI | 161 | Event Second | Modbus 400157 | Read | ||
| AI | 162 | Event Parameter | Modbus 400158 | Read | ||
| AI | 163 | Event Cause: 0-Reset 1-Tripped 2-Acknowled | Modbus 400159 | Read | ||
| BI | 164 | Device 86 Active? | Modbus 400160 bit 0 | Read | ||
| BI | 165 | Device 86 State | Modbus 400160 bit 1 | Read | ||
| BI | 166 | Device 86 Hold | Modbus 400160 bit 2 | Read | ||
| AO | 167 | System Type | Modbus 400200 | Command | ||
| AO | 168 | Source Mode | Modbus 400201 | Command | ||
| AO | 169 | Potential Transformer Ratio | Modbus 400202 | Command | ||
| AO | 170 | Current Transformer Ratio | Modbus 400203 | Command | ||
| AO | 171 | 4th Current Input Transformer Ratio | Modbus 400204 | Command | ||
| AO | 172 | SCI comm. port (J5) protocol | Modbus 400205 | Command | ||
| AO | 173 | SCI comm. port (J5) baud rate | Modbus 400206 | Command | ||
| AO | 174 | SCI comm. port (J5) device address | Modbus 400207 | Command | ||
| AO | 175 | 485 comm. port (J1) protocol | Modbus 400208 | Command | ||
| AO | 176 | 485 comm. port (J1) baud rate | Modbus 400209 | Command | ||
| AO | 177 | 485 comm. port (J1) device address | Modbus 400210 | Command | ||
| AO | 178 | Language selection | Modbus 400211 | Command | ||
| AO | 179 | Demand Window size (in minutes) | Modbus 400212 | min | Command | |
| AO | 180 | Demand Subinterval size (fixed at 1 minute) | Modbus 400213 | min | Command | |
| AO | 181 | Resets Inst. Max. demand registers | Modbus 400214 | Command | ||
| AO | 182 | Clears Energy registers to 0 | Modbus 400215 | Command | ||
| AO | 183 | Setpoint configuration settings A | Modbus 400230 | Command | ||
| AO | 184 | Setpoint configuration settings B | Modbus 400231 | Command | ||
| AO | 185 | Setpoint configuration settings C | Modbus 400232 | Command | ||
| AO | 186 | Setpoint configuration settings D | Modbus 400233 | Command | ||
| AO | 187 | Setpoint configuration settings E | Modbus 400234 | Command | ||
| AO | 188 | Setpoint configuration settings F | Modbus 400235 | Command | ||
| AO | 189 | Setpoint#1 Number | Modbus 400236 | Command | ||
| AO | 190 | Setpoint#1 Parameter | Modbus 400237 | Command | ||
| AO | 191 | Setpoint#1 Trip Level | Modbus 400238 | Command | ||
| AO | 192 | Setpoint #1Trip TimeDelay | Modbus 400239 | Command | ||
| AO | 193 | Setpoint#1 Reset Level | Modbus 400240 | Command | ||
| AO | 194 | Setpoint#1 Reset Time delay | Modbus 400241 | Command | ||
| BO | 195 | Setpoint#1 Digital Output :DO1 | Modbus 400242 bit 0 | Command | ||
| BO | 196 | Setpoint#1 Digital Output :DO2 | Modbus 400242 bit 1 | Command | ||
| BO | 197 | Setpoint#1 Digital Output :DO3 | Modbus 400242 bit 2 | Command | ||
| BO | 198 | Setpoint#1 Digital Output :DO4 | Modbus 400242 bit 3 | Command | ||
| BO | 199 | Setpoint#1 Digital Output :DO1 To DO4 | Modbus 400242 bit 4 | Command | ||
| BO | 200 | Setpoint#1 Output No Acknowledg/Acknowledg | Modbus 400242 bit 5 | Command | ||
| BO | 201 | Setpoint#1 Output Status Setpoint#1 Normal/Tripped | Modbus 400242 bit 6 | Command | ||
| BO | 202 | Setpoint#1Previous Acknowledge/Pending | Modbus 400242 bit 7 | Command | ||
| AO | 203 | Setpoint#2 Number | Modbus 400243 | Command | ||
| AO | 204 | Setpoint#2 Parameter | Modbus 400244 | Command | ||
| AO | 205 | Setpoint#2 Trip Level | Modbus 400245 | Command | ||
| AO | 206 | Setpoint #2Trip TimeDelay | Modbus 400246 | Command | ||
| AO | 207 | Setpoint#2 Reset Level | Modbus 400247 | Command | ||
| AO | 208 | Setpoint#2 Reset Time delay | Modbus 400248 | Command | ||
| BO | 209 | Setpoint#2 Digital Output :DO1 | Modbus 400249 bit 0 | Command | ||
| BO | 210 | Setpoint#2 Digital Output :DO2 | Modbus 400249 bit 1 | Command | ||
| BO | 211 | Setpoint#2 Digital Output :DO3 | Modbus 400249 bit 2 | Command | ||
| BO | 212 | Setpoint#2 Digital Output :DO4 | Modbus 400249 bit 3 | Command | ||
| BO | 213 | Setpoint#2 Digital Output :DO1 To DO4 | Modbus 400249 bit 4 | Command | ||
| BO | 214 | Setpoint#2 Output No Acknowledg/Acknowledg | Modbus 400249 bit 5 | Command | ||
| BO | 215 | Setpoint#2 Output Status Setpoint#2 Normal/Tripped | Modbus 400249 bit 6 | Command | ||
| BO | 216 | Setpoint#2 Previous Acknowledge/Pending | Modbus 400249 bit 7 | Command | ||
| AO | 217 | Setpoint#3 Number | Modbus 400250 | Command | ||
| AO | 218 | Setpoint#3 Parameter | Modbus 400251 | Command | ||
| AO | 219 | Setpoint#3 Trip Level | Modbus 400252 | Command | ||
| AO | 220 | Setpoint #3Trip TimeDelay | Modbus 400253 | Command | ||
| AO | 221 | Setpoint#3 Reset Level | Modbus 400254 | Command | ||
| AO | 222 | Setpoint#3 Reset Time delay | Modbus 400255 | Command | ||
| BO | 223 | Setpoint#3 Digital Output :DO1 | Modbus 400256 bit 0 | Command | ||
| BO | 224 | Setpoint#3 Digital Output :DO2 | Modbus 400256 bit 1 | Command | ||
| BO | 225 | Setpoint#3 Digital Output :DO3 | Modbus 400256 bit 2 | Command | ||
| BO | 226 | Setpoint#3 Digital Output :DO4 | Modbus 400256 bit 3 | Command | ||
| BO | 227 | Setpoint#3 Digital Output :DO1 To DO4 | Modbus 400256 bit 4 | Command | ||
| BO | 228 | Setpoint#3 Output No Acknowledg/Acknowledg | Modbus 400256 bit 5 | Command | ||
| BO | 229 | Setpoint#3 Output Status Setpoint#3 Normal/Tripped | Modbus 400256 bit 6 | Command | ||
| BO | 230 | Setpoint#3 Previous Acknowledge/Pending | Modbus 400256 bit 7 | Command | ||
| AO | 231 | Setpoint#4 Number | Modbus 400257 | Command | ||
| AO | 232 | Setpoint#4 Parameter | Modbus 400258 | Command | ||
| AO | 233 | Setpoint#4 Trip Level | Modbus 400259 | Command | ||
| AO | 234 | Setpoint #4Trip TimeDelay | Modbus 400260 | Command | ||
| AO | 235 | Setpoint#4 Reset Level | Modbus 400261 | Command | ||
| AO | 236 | Setpoint#4 Reset Time delay | Modbus 400262 | Command | ||
| BO | 237 | Setpoint#4 Digital Output :DO1 | Modbus 400263 bit 0 | Command | ||
| BO | 238 | Setpoint#4 Digital Output :DO2 | Modbus 400263 bit 1 | Command | ||
| BO | 239 | Setpoint#4 Digital Output :DO3 | Modbus 400263 bit 2 | Command | ||
| BO | 240 | Setpoint#4 Digital Output :DO4 | Modbus 400263 bit 3 | Command | ||
| BO | 241 | Setpoint#4 Digital Output :DO1 To DO4 | Modbus 400263 bit 4 | Command | ||
| BO | 242 | Setpoint#4 Output No Acknowledg/Acknowledg | Modbus 400263 bit 5 | Command | ||
| BO | 243 | Setpoint#4 Output Status Setpoint#4 Normal/Tripped | Modbus 400263 bit 6 | Command | ||
| BO | 244 | Setpoint#4 Previous Acknowledge/Pending | Modbus 400263 bit 7 | Command | ||
| AO | 245 | Setpoint#5 Number | Modbus 400264 | Command | ||
| AO | 246 | Setpoint#5 Parameter | Modbus 400265 | Command | ||
| AO | 247 | Setpoint#5 Trip Level | Modbus 400266 | Command | ||
| AO | 248 | Setpoint #5Trip TimeDelay | Modbus 400267 | Command | ||
| AO | 249 | Setpoint#5 Reset Level | Modbus 400268 | Command | ||
| AO | 250 | Setpoint#5 Reset Time delay | Modbus 400269 | Command | ||
| BO | 251 | Setpoint#5 Digital Output :DO1 | Modbus 400270 bit 0 | Command | ||
| BO | 252 | Setpoint#5 Digital Output :DO2 | Modbus 400270 bit 1 | Command | ||
| BO | 253 | Setpoint#5 Digital Output :DO3 | Modbus 400270 bit 2 | Command | ||
| BO | 254 | Setpoint#5 Digital Output :DO4 | Modbus 400270 bit 3 | Command | ||
| BO | 255 | Setpoint#5 Digital Output :DO1 To DO4 | Modbus 400270 bit 4 | Command | ||
| BO | 256 | Setpoint#5 Output No Acknowledg/Acknowledg | Modbus 400270 bit 5 | Command | ||
| BO | 257 | Setpoint#5 Output Status Setpoint#5 Normal/Tripped | Modbus 400270 bit 6 | Command | ||
| BO | 258 | Setpoint#5 Previous Acknowledge/Pending | Modbus 400270 bit 7 | Command | ||
| AO | 259 | Setpoint#6 Number | Modbus 400271 | Command | ||
| AO | 260 | Setpoint#6 Parameter | Modbus 400272 | Command | ||
| AO | 261 | Setpoint#6 Trip Level | Modbus 400273 | Command | ||
| AO | 262 | Setpoint #6Trip TimeDelay | Modbus 400274 | Command | ||
| AO | 263 | Setpoint#6 Reset Level | Modbus 400275 | Command | ||
| AO | 264 | Setpoint#6 Reset Time delay | Modbus 400276 | Command | ||
| BO | 265 | Setpoint#6 Digital Output :DO1 | Modbus 400277 bit 0 | Command | ||
| BO | 266 | Setpoint#6 Digital Output :DO2 | Modbus 400277 bit 1 | Command | ||
| BO | 267 | Setpoint#6 Digital Output :DO3 | Modbus 400277 bit 2 | Command | ||
| BO | 268 | Setpoint#6 Digital Output :DO4 | Modbus 400277 bit 3 | Command | ||
| BO | 269 | Setpoint#6 Digital Output :DO1 To DO4 | Modbus 400277 bit 4 | Command | ||
| BO | 270 | Setpoint#6 Output No Acknowledg/Acknowledg | Modbus 400277 bit 5 | Command | ||
| BO | 271 | Setpoint#6 Output Status Setpoint#6 Normal/Tripped | Modbus 400277 bit 6 | Command | ||
| BO | 272 | Setpoint#6 Previous Acknowledge/Pending | Modbus 400277 bit 7 | Command | ||
| AO | 273 | Setpoint#7 Number | Modbus 400278 | Command | ||
| AO | 274 | Setpoint#7 Parameter | Modbus 400279 | Command | ||
| AO | 275 | Setpoint#7 Trip Level | Modbus 400280 | Command | ||
| AO | 276 | Setpoint #7Trip TimeDelay | Modbus 400281 | Command | ||
| AO | 277 | Setpoint#7 Reset Level | Modbus 400282 | Command | ||
| AO | 278 | Setpoint#7 Reset Time delay | Modbus 400283 | Command | ||
| BO | 279 | Setpoint#7 Digital Output :DO1 | Modbus 400284 bit 0 | Command | ||
| BO | 280 | Setpoint#7 Digital Output :DO2 | Modbus 400284 bit 1 | Command | ||
| BO | 281 | Setpoint#7 Digital Output :DO3 | Modbus 400284 bit 2 | Command | ||
| BO | 282 | Setpoint#7 Digital Output :DO4 | Modbus 400284 bit 3 | Command | ||
| BO | 283 | Setpoint#7 Digital Output :DO1 To DO4 | Modbus 400284 bit 4 | Command | ||
| BO | 284 | Setpoint#7 Output No Acknowledg/Acknowledg | Modbus 400284 bit 5 | Command | ||
| BO | 285 | Setpoint#7 Output Status Setpoint#7 Normal/Tripped | Modbus 400284 bit 6 | Command | ||
| BO | 286 | Setpoint#7 Previous Acknowledge/Pending | Modbus 400284 bit 7 | Command | ||
| AO | 287 | Setpoint#8 Number | Modbus 400285 | Command | ||
| AO | 288 | Setpoint#8 Parameter | Modbus 400286 | Command | ||
| AO | 289 | Setpoint#8 Trip Level | Modbus 400287 | Command | ||
| AO | 290 | Setpoint #8Trip TimeDelay | Modbus 400288 | Command | ||
| AO | 291 | Setpoint#8 Reset Level | Modbus 400289 | Command | ||
| AO | 292 | Setpoint#8 Reset Time delay | Modbus 400290 | Command | ||
| BO | 293 | Setpoint#8 Digital Output :DO1 | Modbus 400291 bit 0 | Command | ||
| BO | 294 | Setpoint#8 Digital Output :DO2 | Modbus 400291 bit 1 | Command | ||
| BO | 295 | Setpoint#8 Digital Output :DO3 | Modbus 400291 bit 2 | Command | ||
| BO | 296 | Setpoint#8 Digital Output :DO4 | Modbus 400291 bit 3 | Command | ||
| BO | 297 | Setpoint#8 Digital Output :DO1 To DO4 | Modbus 400291 bit 4 | Command | ||
| BO | 298 | Setpoint#8 Output No Acknowledg/Acknowledg | Modbus 400291 bit 5 | Command | ||
| BO | 299 | Setpoint#8 Output Status Setpoint#8 Normal/Tripped | Modbus 400291 bit 6 | Command | ||
| BO | 300 | Setpoint#8 Previous Acknowledge/Pending | Modbus 400291 bit 7 | Command | ||
| AO | 301 | Setpoint#9 Number | Modbus 400292 | Command | ||
| AO | 302 | Setpoint#9 Parameter | Modbus 400293 | Command | ||
| AO | 303 | Setpoint#9 Trip Level | Modbus 400294 | Command | ||
| AO | 304 | Setpoint #9Trip TimeDelay | Modbus 400295 | Command | ||
| AO | 305 | Setpoint#9 Reset Level | Modbus 400296 | Command | ||
| AO | 306 | Setpoint#9 Reset Time delay | Modbus 400297 | Command | ||
| BO | 307 | Setpoint#9 Digital Output :DO1 | Modbus 400298 bit 0 | Command | ||
| BO | 308 | Setpoint#9 Digital Output :DO2 | Modbus 400298 bit 1 | Command | ||
| BO | 309 | Setpoint#9 Digital Output :DO3 | Modbus 400298 bit 2 | Command | ||
| BO | 310 | Setpoint#9 Digital Output :DO4 | Modbus 400298 bit 3 | Command | ||
| BO | 311 | Setpoint#9 Digital Output :DO1 To DO4 | Modbus 400298 bit 4 | Command | ||
| BO | 312 | Setpoint#9 Output No Acknowledg/Acknowledg | Modbus 400298 bit 5 | Command | ||
| BO | 313 | Setpoint#9 Output Status Setpoint#9 Normal/Tripped | Modbus 400298 bit 6 | Command | ||
| BO | 314 | Setpoint#9 Previous Acknowledge/Pending | Modbus 400298 bit 7 | Command | ||
| AO | 315 | Setpoint#10 Number | Modbus 400299 | Command | ||
| AO | 316 | Setpoint#10 Parameter | Modbus 400300 | Command | ||
| AO | 317 | Setpoint#10 Trip Level | Modbus 400301 | Command | ||
| AO | 318 | Setpoint #10Trip TimeDelay | Modbus 400302 | Command | ||
| AO | 319 | Setpoint#10 Reset Level | Modbus 400303 | Command | ||
| AO | 320 | Setpoint#10 Reset Time delay | Modbus 400304 | Command | ||
| BO | 321 | Setpoint#10 Digital Output :DO1 | Modbus 400305 bit 0 | Command | ||
| BO | 322 | Setpoint#10 Digital Output :DO2 | Modbus 400305 bit 1 | Command | ||
| BO | 323 | Setpoint#10 Digital Output :DO3 | Modbus 400305 bit 2 | Command | ||
| BO | 324 | Setpoint#10 Digital Output :DO4 | Modbus 400305 bit 3 | Command | ||
| BO | 325 | Setpoint#10 Digital Output :DO1 To DO4 | Modbus 400305 bit 4 | Command | ||
| BO | 326 | Setpoint#10 Output No Acknowledg/Acknowledg | Modbus 400305 bit 5 | Command | ||
| BO | 327 | Setpoint#10 Output Status Setpoint#10 Normal/Tripped | Modbus 400305 bit 6 | Command | ||
| BO | 328 | Setpoint#10 Previous Acknowledge/Pending | Modbus 400305 bit 7 | Command | ||
| AO | 329 | Setpoint#11 Number | Modbus 400306 | Command | ||
| AO | 330 | Setpoint#11 Parameter | Modbus 400307 | Command | ||
| AO | 331 | Setpoint#11 Trip Level | Modbus 400308 | Command | ||
| AO | 332 | Setpoint #11Trip TimeDelay | Modbus 400309 | Command | ||
| AO | 333 | Setpoint#11 Reset Level | Modbus 400310 | Command | ||
| AO | 334 | Setpoint#11 Reset Time delay | Modbus 400311 | Command | ||
| BO | 335 | Setpoint#11 Digital Output :DO1 | Modbus 400312 bit 0 | Command | ||
| BO | 336 | Setpoint#11 Digital Output :DO2 | Modbus 400312 bit 1 | Command | ||
| BO | 337 | Setpoint#11 Digital Output :DO3 | Modbus 400312 bit 2 | Command | ||
| BO | 338 | Setpoint#11 Digital Output :DO4 | Modbus 400312 bit 3 | Command | ||
| BO | 339 | Setpoint#11 Digital Output :DO1 To DO4 | Modbus 400312 bit 4 | Command | ||
| BO | 340 | Setpoint#11 Output No Acknowledg/Acknowledg | Modbus 400312 bit 5 | Command | ||
| BO | 341 | Setpoint#11 Output Status Setpoint#11 Normal/Tripped | Modbus 400312 bit 6 | Command | ||
| BO | 342 | Setpoint#11 Previous Acknowledge/Pending | Modbus 400312 bit 7 | Command | ||
| AI | 343 | Setpoint#12 Number | Modbus 400313 | Read | ||
| AI | 344 | Setpoint#12 Parameter | Modbus 400314 | Read | ||
| AI | 345 | Setpoint#12 Trip Level | Modbus 400315 | Read | ||
| AI | 346 | Setpoint #12Trip TimeDelay | Modbus 400316 | Read | ||
| AI | 347 | Setpoint#12 Reset Level | Modbus 400317 | Read | ||
| AI | 348 | Setpoint#12 Reset Time delay | Modbus 400318 | Read | ||
| BI | 349 | Setpoint#12 Digital Output :DO1 | Modbus 400319 bit 0 | Read | ||
| BI | 350 | Setpoint#12 Digital Output :DO2 | Modbus 400319 bit 1 | Read | ||
| BI | 351 | Setpoint#12 Digital Output :DO3 | Modbus 400319 bit 2 | Read | ||
| BI | 352 | Setpoint#12 Digital Output :DO4 | Modbus 400319 bit 3 | Read | ||
| BI | 353 | Setpoint#12 Digital Output :DO1 To DO4 | Modbus 400319 bit 4 | Read | ||
| BI | 354 | Setpoint#12 Output No Acknowledg/Acknowledg | Modbus 400319 bit 5 | Read | ||
| BI | 355 | Setpoint#12 Output Status Setpoint#12 Normal/Tripped | Modbus 400319 bit 6 | Read | ||
| BI | 356 | Setpoint#12 Previous Acknowledge/Pending | Modbus 400319 bit 7 | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX ASCO Power Manager Xp point IDs by name
AI1Phase A line to neutral voltageAI2Phase B line to neutral voltageAI3Phase C line to neutral voltageAI4Line to neutral average voltageAI5A-B line to line voltageAI6B-C line to line voltageAI7C-A line to line voltageAI8Line to line average voltageAI9Line to line voltage unbalanceAI10Line to neutral voltage unbalanceAI11Phase A currentAI12Phase B currentAI13Phase C currentAI14Average currentAI15Current unbalanceAI16CT4 or neutral currentAI17Active Power phase AAI18Active Power phase BAI19Active Power phase CAI20Active Power totalAI21Reactive Power phase AAI22Reactive Power phase BAI23Reactive Power phase CAI24Reactive Power totalAI25Power Factor phase AAI26Power Factor phase BAI27Power Factor phase CAI28Power Factor totalAI29volt-ampere Power phase AAI30volt-ampere Power phase BAI31volt-ampere Power phase CAI32volt-ampere Power totalAI33Frequency on phase VAAI34Normal kWH ImportAI35Normal kWH ExportAI36Normal kWH NetAI37Normal kVarH ImportAI38Normal kVarH ExportAI39Normal kVarH NetAI40Normal kVAH NetAO41Nominal VoltageAO42Nominal CurrentAO43Nominal kW CapacityAO44Nominal Freq 0– 60Hz 1–50HzAI45Emerg kWH ImportAI46Emerg kWH ExportAI47Emerg kWH NetAI48Emerg kVarH ImportAI49Emerg kVarH ExportAI50Emerg kVarH NetAI51Emerg kVAH NetAI52Active Power (Watts) totalAI53Instantaneous Watt DemandAI54Maximum Watt DemandAI55Active Power (Watts) totalAI56Average currentAI57Line to line average voltageAI58Frequency on phase VABI59General purpose digital inputs 1BI60General purpose digital inputs 2BI61General purpose digital inputs 3BI62General purpose digital inputs 4BI63General purpose digital inputs 5BI64General purpose digital inputs 6BI65General purpose digital inputs 7BI66General purpose digital inputs 8BO67General purpose digital outputs 1BO68General purpose digital outputs 2BO69General purpose digital outputs 3BO70General purpose digital outputs 4AI71Main auxiliary Switch positionsAI72Active Power totalAI73Reactive Power totalAI74volt-ampere Power totalAI75Power Factor totalAI76Frequency on phase VAAI77Software Version string Char 1 and 2AI78Software Version string Char 3 and 4AI79Software Version string Char 5 and 6AI80Software Version string Char 7 and 8AI81Software Version string Char 9 and 10AI82Software Version string Char 11 and 12AI83Software Build Date string Char 11 and 12AI84Software Build Date string Char 11 and 12AI85Software Build Date string Char 11 and 12AI86Software Build Date string Char 11 and 12AI87Software Build Date string Char 11 and 12AI88Software Build Date string Char 11 and 12AI89Device Serial Number Char 1 and 2AI90Device Serial Number Char 3 and 4AI91Device Serial Number Char 5 and 6AI92Device Serial Number Char 7 and 8AI93Device Serial Number Char 9 and 10AI94Device Serial Number Char 11 and 12AI95Device Model Number Char 1 and 2AI96Device Model Number Char 1 and 2AI97Device Model Number Char 1 and 2AI98Device Model Number Char 1 and 2AI99Device Model Number Char 1 and 2AI100Device Model Number Char 1 and 2AI101Health status wordBI102Setpoint #1 Output Status Normal/TrippedBI103Setpoint #1 Acknowledge State Ack/PendgBI104Setpoint #2 Output Status Normal/TrippedBI105Setpoint #2 Acknowledge State Ack/PendgBI106Setpoint #3 Output Status Normal/TrippedBI107Setpoint #3 Acknowledge State Ack/PendgBI108Setpoint #4 Output Status Normal/TrippedBI109Setpoint #4 Acknowledge State Ack/PendgBI110Setpoint #5 Output Status Normal/TrippedBI111Setpoint #5 Acknowledge State Ack/PendgBI112Setpoint #6 Output Status Normal/TrippedBI113Setpoint #6 Acknowledge State Ack/PendgBI114Setpoint #7 Output Status Normal/TrippedBI115Setpoint #7 Acknowledge State Ack/PendgBI116Setpoint #8 Output Status Normal/TrippedBI117Setpoint #8 Acknowledge State Ack/PendgBI118Setpoint #9 Output Status Normal/TrippedBI119Setpoint #9 Acknowledge State Ack/PendgBI120Setpoint #10 Output Status Normal/TrippedBI121Setpoint #10 Acknowledge State Ack/PendgBI122Setpoint #11 Output Status Normal/TrippedBI123Setpoint #11 Acknowledge State Ack/PendgBI124Setpoint #12 Output Status Normal/TrippedBI125Setpoint #12 Acknowledge State Ack/PendgBI126kW Demand Setpoint Status Normal/TripAI127Active Power (Watts) totalAI128Instantaneous Watt DemandAI129Maximum Watt DemandAI130Maximum Watt Demand DateAI131Maximum Watt Demand MonthAI132Maximum Watt Demand YearAI133Maximum Watt Demand HourAI134Maximum Watt Demand MinuteAO135Power Manager HoursAO136Power Manager MinutesAO137Power Manager YearAO138Power Manager MonthAO139Power Manager Day of MonthAO140Power Manager Day of Week (0-S 1-M etc)BO141Setpoint #1 Output Alarm AcknowledgeBO142Setpoint #2 Output Alarm AcknowledgeBO143Setpoint #3 Output Alarm AcknowledgeBO144Setpoint #4 Output Alarm AcknowledgeBO145Setpoint #5 Output Alarm AcknowledgeBO146Setpoint #6 Output Alarm AcknowledgeBO147Setpoint #7 Output Alarm AcknowledgeBO148Setpoint #8 Output Alarm AcknowledgeBO149Setpoint #9 Output Alarm AcknowledgeBO150Setpoint #10 Output Alarm AcknowledgeBO151Setpoint #11 Output Alarm AcknowledgeBO152Setpoint #12 Output Alarm AcknowledgeAI153Number of Unread Event Log EntriesAI154Event Number (0 – The Latest One)AI155Event YearAI156Event MonthAI157Event Month DayAI158Event Week DayAI159Event HourAI160Event MinuteAI161Event SecondAI162Event ParameterAI163Event Cause: 0-Reset 1-Tripped 2-AcknowledBI164Device 86 Active?BI165Device 86 StateBI166Device 86 HoldAO167System TypeAO168Source ModeAO169Potential Transformer RatioAO170Current Transformer RatioAO1714th Current Input Transformer RatioAO172SCI comm. port (J5) protocolAO173SCI comm. port (J5) baud rateAO174SCI comm. port (J5) device addressAO175485 comm. port (J1) protocolAO176485 comm. port (J1) baud rateAO177485 comm. port (J1) device addressAO178Language selectionAO179Demand Window size (in minutes)AO180Demand Subinterval size (fixed at 1 minute)AO181Resets Inst. Max. demand registersAO182Clears Energy registers to 0AO183Setpoint configuration settings AAO184Setpoint configuration settings BAO185Setpoint configuration settings CAO186Setpoint configuration settings DAO187Setpoint configuration settings EAO188Setpoint configuration settings FAO189Setpoint#1 NumberAO190Setpoint#1 ParameterAO191Setpoint#1 Trip LevelAO192Setpoint #1Trip TimeDelayAO193Setpoint#1 Reset LevelAO194Setpoint#1 Reset Time delayBO195Setpoint#1 Digital Output :DO1BO196Setpoint#1 Digital Output :DO2BO197Setpoint#1 Digital Output :DO3BO198Setpoint#1 Digital Output :DO4BO199Setpoint#1 Digital Output :DO1 To DO4BO200Setpoint#1 Output No Acknowledg/AcknowledgBO201Setpoint#1 Output Status Setpoint#1 Normal/TrippedBO202Setpoint#1Previous Acknowledge/PendingAO203Setpoint#2 NumberAO204Setpoint#2 ParameterAO205Setpoint#2 Trip LevelAO206Setpoint #2Trip TimeDelayAO207Setpoint#2 Reset LevelAO208Setpoint#2 Reset Time delayBO209Setpoint#2 Digital Output :DO1BO210Setpoint#2 Digital Output :DO2BO211Setpoint#2 Digital Output :DO3BO212Setpoint#2 Digital Output :DO4BO213Setpoint#2 Digital Output :DO1 To DO4BO214Setpoint#2 Output No Acknowledg/AcknowledgBO215Setpoint#2 Output Status Setpoint#2 Normal/TrippedBO216Setpoint#2 Previous Acknowledge/PendingAO217Setpoint#3 NumberAO218Setpoint#3 ParameterAO219Setpoint#3 Trip LevelAO220Setpoint #3Trip TimeDelayAO221Setpoint#3 Reset LevelAO222Setpoint#3 Reset Time delayBO223Setpoint#3 Digital Output :DO1BO224Setpoint#3 Digital Output :DO2BO225Setpoint#3 Digital Output :DO3BO226Setpoint#3 Digital Output :DO4BO227Setpoint#3 Digital Output :DO1 To DO4BO228Setpoint#3 Output No Acknowledg/AcknowledgBO229Setpoint#3 Output Status Setpoint#3 Normal/TrippedBO230Setpoint#3 Previous Acknowledge/PendingAO231Setpoint#4 NumberAO232Setpoint#4 ParameterAO233Setpoint#4 Trip LevelAO234Setpoint #4Trip TimeDelayAO235Setpoint#4 Reset LevelAO236Setpoint#4 Reset Time delayBO237Setpoint#4 Digital Output :DO1BO238Setpoint#4 Digital Output :DO2BO239Setpoint#4 Digital Output :DO3BO240Setpoint#4 Digital Output :DO4BO241Setpoint#4 Digital Output :DO1 To DO4BO242Setpoint#4 Output No Acknowledg/AcknowledgBO243Setpoint#4 Output Status Setpoint#4 Normal/TrippedBO244Setpoint#4 Previous Acknowledge/PendingAO245Setpoint#5 NumberAO246Setpoint#5 ParameterAO247Setpoint#5 Trip LevelAO248Setpoint #5Trip TimeDelayAO249Setpoint#5 Reset LevelAO250Setpoint#5 Reset Time delayBO251Setpoint#5 Digital Output :DO1BO252Setpoint#5 Digital Output :DO2BO253Setpoint#5 Digital Output :DO3BO254Setpoint#5 Digital Output :DO4BO255Setpoint#5 Digital Output :DO1 To DO4BO256Setpoint#5 Output No Acknowledg/AcknowledgBO257Setpoint#5 Output Status Setpoint#5 Normal/TrippedBO258Setpoint#5 Previous Acknowledge/PendingAO259Setpoint#6 NumberAO260Setpoint#6 ParameterAO261Setpoint#6 Trip LevelAO262Setpoint #6Trip TimeDelayAO263Setpoint#6 Reset LevelAO264Setpoint#6 Reset Time delayBO265Setpoint#6 Digital Output :DO1BO266Setpoint#6 Digital Output :DO2BO267Setpoint#6 Digital Output :DO3BO268Setpoint#6 Digital Output :DO4BO269Setpoint#6 Digital Output :DO1 To DO4BO270Setpoint#6 Output No Acknowledg/AcknowledgBO271Setpoint#6 Output Status Setpoint#6 Normal/TrippedBO272Setpoint#6 Previous Acknowledge/PendingAO273Setpoint#7 NumberAO274Setpoint#7 ParameterAO275Setpoint#7 Trip LevelAO276Setpoint #7Trip TimeDelayAO277Setpoint#7 Reset LevelAO278Setpoint#7 Reset Time delayBO279Setpoint#7 Digital Output :DO1BO280Setpoint#7 Digital Output :DO2BO281Setpoint#7 Digital Output :DO3BO282Setpoint#7 Digital Output :DO4BO283Setpoint#7 Digital Output :DO1 To DO4BO284Setpoint#7 Output No Acknowledg/AcknowledgBO285Setpoint#7 Output Status Setpoint#7 Normal/TrippedBO286Setpoint#7 Previous Acknowledge/PendingAO287Setpoint#8 NumberAO288Setpoint#8 ParameterAO289Setpoint#8 Trip LevelAO290Setpoint #8Trip TimeDelayAO291Setpoint#8 Reset LevelAO292Setpoint#8 Reset Time delayBO293Setpoint#8 Digital Output :DO1BO294Setpoint#8 Digital Output :DO2BO295Setpoint#8 Digital Output :DO3BO296Setpoint#8 Digital Output :DO4BO297Setpoint#8 Digital Output :DO1 To DO4BO298Setpoint#8 Output No Acknowledg/AcknowledgBO299Setpoint#8 Output Status Setpoint#8 Normal/TrippedBO300Setpoint#8 Previous Acknowledge/PendingAO301Setpoint#9 NumberAO302Setpoint#9 ParameterAO303Setpoint#9 Trip LevelAO304Setpoint #9Trip TimeDelayAO305Setpoint#9 Reset LevelAO306Setpoint#9 Reset Time delayBO307Setpoint#9 Digital Output :DO1BO308Setpoint#9 Digital Output :DO2BO309Setpoint#9 Digital Output :DO3BO310Setpoint#9 Digital Output :DO4BO311Setpoint#9 Digital Output :DO1 To DO4BO312Setpoint#9 Output No Acknowledg/AcknowledgBO313Setpoint#9 Output Status Setpoint#9 Normal/TrippedBO314Setpoint#9 Previous Acknowledge/PendingAO315Setpoint#10 NumberAO316Setpoint#10 ParameterAO317Setpoint#10 Trip LevelAO318Setpoint #10Trip TimeDelayAO319Setpoint#10 Reset LevelAO320Setpoint#10 Reset Time delayBO321Setpoint#10 Digital Output :DO1BO322Setpoint#10 Digital Output :DO2BO323Setpoint#10 Digital Output :DO3BO324Setpoint#10 Digital Output :DO4BO325Setpoint#10 Digital Output :DO1 To DO4BO326Setpoint#10 Output No Acknowledg/AcknowledgBO327Setpoint#10 Output Status Setpoint#10 Normal/TrippedBO328Setpoint#10 Previous Acknowledge/PendingAO329Setpoint#11 NumberAO330Setpoint#11 ParameterAO331Setpoint#11 Trip LevelAO332Setpoint #11Trip TimeDelayAO333Setpoint#11 Reset LevelAO334Setpoint#11 Reset Time delayBO335Setpoint#11 Digital Output :DO1BO336Setpoint#11 Digital Output :DO2BO337Setpoint#11 Digital Output :DO3BO338Setpoint#11 Digital Output :DO4BO339Setpoint#11 Digital Output :DO1 To DO4BO340Setpoint#11 Output No Acknowledg/AcknowledgBO341Setpoint#11 Output Status Setpoint#11 Normal/TrippedBO342Setpoint#11 Previous Acknowledge/PendingAI343Setpoint#12 NumberAI344Setpoint#12 ParameterAI345Setpoint#12 Trip LevelAI346Setpoint #12Trip TimeDelayAI347Setpoint#12 Reset LevelAI348Setpoint#12 Reset Time delayBI349Setpoint#12 Digital Output :DO1BI350Setpoint#12 Digital Output :DO2BI351Setpoint#12 Digital Output :DO3BI352Setpoint#12 Digital Output :DO4BI353Setpoint#12 Digital Output :DO1 To DO4BI354Setpoint#12 Output No Acknowledg/AcknowledgBI355Setpoint#12 Output Status Setpoint#12 Normal/TrippedBI356Setpoint#12 Previous Acknowledge/Pending
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Asco_Power_Manage_Xp_a_LX.csv; the profile maps the registers in the ASCO Power Manager Modbus register list (https://www.ccontrols.com/support/dp/Asco_Power_Mgr.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- All 356 rows are flagged for polling in the profile, so every object is served to BACnet once the profile is loaded.
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Line to line average voltage; Average current; Active Power total...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ASCO Power Manager Xp via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
How many BACnet points does the Contemporary Controls ASCO Power Manager Xp via BASgatewayLX have?
This list has 356 BACnet objects: 110 analog inputs, 98 analog outputs, 44 binary inputs, 104 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls ASCO Power Manager Xp via BASgatewayLX BACnet points are writable?
202 of the 356 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls ASCO Power Manager Xp via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Asco_Power_Manage_Xp_a (Asco_Power_Manage_Xp_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Asco_Power_Mgr_.zip.
What are the minimum BACnet points to integrate the Contemporary Controls ASCO Power Manager Xp via BASgatewayLX?
Start with AI 20 Active Power total (Total active power); AI 8 Line to line average voltage (Average line-line voltage); AI 14 Average current (Average current); AI 28 Power Factor total (Total power factor); AI 33 Frequency on phase VA (Frequency); AI 34 Normal kWH Import (Normal source kWh import); AI 45 Emerg kWH Import (Emergency source kWh import); AI 71 Main auxiliary Switch positions (Main/auxiliary switch positions); AI 101 Health status word (Health status word).
How do I check these points on the real ASCO Power Manager Xp via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Asco_Power_Manage_Xp_a · Asco_Power_Manage_Xp_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.