Precision cooling unit (computer room air handler) · BACnet points list
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for Liebert iCOM v4 units (tables 6 and 8 of the Liebert Modbus map): 641 objects (418 AI, 223 BI). None is polled in the profile as published. It covers lockouts and system on/off state, fan, cooling, free-cooling, reheat, humidifier and dehumidifier states, the full event list, setpoints and thresholds (many in both °F and °C), and return, supply and remote sensor readings.
This page lists 641 BACnet objects for the Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
- Equipment
- Precision cooling unit (computer room air handler)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 641 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Tick the unit state, return/supply temperature, humidity and setpoint objects first. Every object is an input, so setpoints cannot be written through this profile.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 99 | Unit On | Unit on | Read |
| BI 8 | Fan State | Fan running | Read |
| BI 9 | Cooling State | Cooling active | Read |
| AI 278 | Return Air Temperature | Return air temperature | Read |
| AI 296 | Return Humidity | Return humidity | Read |
| AI 280 | Supply Air Temperature | Supply air temperature | Read |
| AI 233 | Air Temperature Set Point | Air temperature setpoint | Read |
| AI 240 | Humidity Set Point | Humidity setpoint | Read |
| BI 41 | Return Air Over Temperature | Return air over temperature | Read |
| BI 64 | Unit Communication Lost | Unit communication lost | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | Ext Reheat Lockout | Modbus 100009; not polled by default | Read | ||
| BI | 2 | Ext Humidifier Lockout | Modbus 100010; not polled by default | Read | ||
| BI | 3 | Minimum Chilled Water Temp Set Point Enable | Modbus 000013; not polled by default | Read | ||
| BI | 4 | Return Air Sensor Event Control | Modbus 000019; not polled by default | Read | ||
| BI | 5 | Ext Air Sensor A Event Control | Modbus 000020; not polled by default | Read | ||
| BI | 6 | Ext Compressor Lockout | Modbus 100021; not polled by default | Read | ||
| BI | 7 | System On/Off Control | Modbus 000025; not polled by default | Read | ||
| BImin | 8 | Fan State | Modbus 100025; not polled by default | Read | ||
| BImin | 9 | Cooling State | Modbus 100026; not polled by default | Read | ||
| BI | 10 | Free Cooling State | Modbus 100027; not polled by default | Read | ||
| BI | 11 | Hot Water / Hot Gas State | Modbus 100028; not polled by default | Read | ||
| BI | 12 | Electric Reheat State | Modbus 100029; not polled by default | Read | ||
| BI | 13 | Humidifier State | Modbus 100030; not polled by default | Read | ||
| BI | 14 | Dehumidifier State | Modbus 100031; not polled by default | Read | ||
| BI | 15 | Main Fan Overload | Modbus 100034; not polled by default | Read | ||
| BI | 16 | Loss of Air Flow | Modbus 100035; not polled by default | Read | ||
| BI | 17 | Ext Loss of Flow | Modbus 100036; not polled by default | Read | ||
| BI | 18 | Compressor High Head Pressure | Modbus 100037; not polled by default | Read | ||
| BI | 19 | Compressor Low Suction Pressure | Modbus 100038; not polled by default | Read | ||
| BI | 20 | Compressor Thermal Overload | Modbus 100039; not polled by default | Read | ||
| BI | 21 | Compressor Pump Down Issue | Modbus 100040; not polled by default | Read | ||
| BI | 22 | Compressor High Head Pressure 2 | Modbus 100041; not polled by default | Read | ||
| BI | 23 | Compressor Low Suction Pressure 2 | Modbus 100042; not polled by default | Read | ||
| BI | 24 | Compressor Thermal Overload 2 | Modbus 100043; not polled by default | Read | ||
| BI | 25 | Compressor Pump Down Issue 2 | Modbus 100044; not polled by default | Read | ||
| BI | 26 | Dig Scroll Comp Over Temp 1 | Modbus 100045; not polled by default | Read | ||
| BI | 27 | Dig Scroll Comp Over Temp 2 | Modbus 100046; not polled by default | Read | ||
| BI | 28 | Smoke Detected | Modbus 100047; not polled by default | Read | ||
| BI | 29 | Water Under Floor | Modbus 100048; not polled by default | Read | ||
| BI | 30 | Humidifier Issue | Modbus 100049; not polled by default | Read | ||
| BI | 31 | Ext Standby Glycol Pump On | Modbus 100050; not polled by default | Read | ||
| BI | 32 | Ext Standby Unit On | Modbus 100051; not polled by default | Read | ||
| BI | 33 | Ext Condenser Pump High Water | Modbus 100052; not polled by default | Read | ||
| BI | 34 | Return Air Sensor Issue | Modbus 100053; not polled by default | Read | ||
| BI | 35 | Ext Loss of Air Blower | Modbus 100055; not polled by default | Read | ||
| BI | 36 | Humidifier Low Water | Modbus 100058; not polled by default | Read | ||
| BI | 37 | Humidifier Over Current | Modbus 100059; not polled by default | Read | ||
| BI | 38 | Ext Over Temperature | Modbus 100060; not polled by default | Read | ||
| BI | 39 | Shutdown - Loss Of Power | Modbus 100061; not polled by default | Read | ||
| BI | 40 | Supply Chilled Water Over Temp | Modbus 100065; not polled by default | Read | ||
| BImin | 41 | Return Air Over Temperature | Modbus 100067; not polled by default | Read | ||
| BI | 42 | Return Air Under Temperature | Modbus 100068; not polled by default | Read | ||
| BI | 43 | High Return Humidity | Modbus 100069; not polled by default | Read | ||
| BI | 44 | Low Return Humidity | Modbus 100070; not polled by default | Read | ||
| BI | 45 | Ext Air Sensor A Over Temperature | Modbus 100071; not polled by default | Read | ||
| BI | 46 | Ext Air Sensor A Under Temperature | Modbus 100072; not polled by default | Read | ||
| BI | 47 | Ext Air Sensor A High Humidity | Modbus 100073; not polled by default | Read | ||
| BI | 48 | Ext Air Sensor A Low Humidity | Modbus 100074; not polled by default | Read | ||
| BI | 49 | Supply Chilled Water Loss of Flow | Modbus 100075; not polled by default | Read | ||
| BI | 50 | Clogged Air Filter | Modbus 100076; not polled by default | Read | ||
| BI | 51 | Supply Air Sensor Issue | Modbus 100077; not polled by default | Read | ||
| BI | 52 | Free Cooling Temp Sensor Issue | Modbus 100078; not polled by default | Read | ||
| BI | 53 | Ext Air Sensor A Issue | Modbus 100079; not polled by default | Read | ||
| BI | 54 | Fan Hours Exceeded | Modbus 100080; not polled by default | Read | ||
| BI | 55 | Compressor Hours Exceeded 1 | Modbus 100081; not polled by default | Read | ||
| BI | 56 | Compressor Hours Exceeded 2 | Modbus 100082; not polled by default | Read | ||
| BI | 57 | Free Cooling Valve Hours Exceeded | Modbus 100083; not polled by default | Read | ||
| BI | 58 | Electric Reheater Hours Exceeded 1 | Modbus 100084; not polled by default | Read | ||
| BI | 59 | Electric Reheater Hours Exceeded 2 | Modbus 100085; not polled by default | Read | ||
| BI | 60 | Electric Reheater Hours Exceeded 3 | Modbus 100086; not polled by default | Read | ||
| BI | 61 | Hot Water / Hot Gas Valve Hours Exceeded | Modbus 100087; not polled by default | Read | ||
| BI | 62 | Humidifier Hours Exceeded | Modbus 100088; not polled by default | Read | ||
| BI | 63 | Dehumidifier Hours Exceeded | Modbus 100089; not polled by default | Read | ||
| BImin | 64 | Unit Communication Lost | Modbus 100091; not polled by default | Read | ||
| BI | 65 | Master Unit Communication Lost | Modbus 100092; not polled by default | Read | ||
| BI | 66 | Unit Code Missing | Modbus 100094; not polled by default | Read | ||
| BI | 67 | Service Required | Modbus 100098; not polled by default | Read | ||
| BI | 68 | Humidifier Control Board Not Detected | Modbus 100099; not polled by default | Read | ||
| BI | 69 | Customer Input 1 | Modbus 100104; not polled by default | Read | ||
| BI | 70 | Customer Input 2 | Modbus 100105; not polled by default | Read | ||
| BI | 71 | Customer Input 3 | Modbus 100106; not polled by default | Read | ||
| BI | 72 | Customer Input 4 | Modbus 100107; not polled by default | Read | ||
| BI | 73 | Dig Scroll Comp Discharge Temp Sensor Issue 1 | Modbus 100108; not polled by default | Read | ||
| BI | 74 | Dig Scroll Comp Discharge Temp Sensor Issue 2 | Modbus 100109; not polled by default | Read | ||
| BI | 75 | Supply Air Over Temperature | Modbus 100209; not polled by default | Read | ||
| BI | 76 | Supply Air Under Temperature | Modbus 100210; not polled by default | Read | ||
| BI | 77 | Ambient Air Sensor Issue | Modbus 100211; not polled by default | Read | ||
| BI | 78 | Compressor Short Cycle 1 | Modbus 100212; not polled by default | Read | ||
| BI | 79 | Compressor Short Cycle 2 | Modbus 100213; not polled by default | Read | ||
| BI | 80 | Ext Free Cooling Lockout | Modbus 100214; not polled by default | Read | ||
| BI | 81 | Reheater Over Temperature | Modbus 100215; not polled by default | Read | ||
| BI | 82 | Humidifier Cylinder Worn | Modbus 100216; not polled by default | Read | ||
| BI | 83 | Humidifier Under Current | Modbus 100217; not polled by default | Read | ||
| BI | 84 | Fan Issue | Modbus 100218; not polled by default | Read | ||
| BI | 85 | Condenser TVSS Issue | Modbus 100219; not polled by default | Read | ||
| BI | 86 | Condenser VFD Issue | Modbus 100220; not polled by default | Read | ||
| BI | 87 | Condenser Issue 1 | Modbus 100221; not polled by default | Read | ||
| BI | 88 | Condenser Issue 2 | Modbus 100222; not polled by default | Read | ||
| BI | 89 | BMS Communications Timeout | Modbus 100223; not polled by default | Read | ||
| BI | 90 | Digital Output Board Not Detected 1 | Modbus 100224; not polled by default | Read | ||
| BI | 91 | Digital Output Board Not Detected 2 | Modbus 100225; not polled by default | Read | ||
| BI | 92 | Digital Output Board Not Detected 3 | Modbus 100226; not polled by default | Read | ||
| BI | 93 | RAM Battery Issue | Modbus 100227; not polled by default | Read | ||
| BI | 94 | Water Leakage Detector Sensor Issue | Modbus 100228; not polled by default | Read | ||
| BI | 95 | External Fire Detected | Modbus 100229; not polled by default | Read | ||
| BI | 96 | Chilled Water Control Valve Failure 1 | Modbus 100230; not polled by default | Read | ||
| BI | 97 | Chilled Water Control Valve Failure 2 | Modbus 100231; not polled by default | Read | ||
| BI | 98 | Unit Off | Modbus 100232; not polled by default | Read | ||
| BImin | 99 | Unit On | Modbus 100233; not polled by default | Read | ||
| BI | 100 | Unit Partial Shutdown | Modbus 100234; not polled by default | Read | ||
| BI | 101 | Unit Shutdown | Modbus 100235; not polled by default | Read | ||
| BI | 102 | High Power Shutdown | Modbus 100236; not polled by default | Read | ||
| BI | 103 | Unit Standby | Modbus 100237; not polled by default | Read | ||
| BI | 104 | Maintenance Due | Modbus 100238; not polled by default | Read | ||
| BI | 105 | Maintenance Completed | Modbus 100239; not polled by default | Read | ||
| BI | 106 | Compressor Low Pressure Transducer Issue 1 | Modbus 100240; not polled by default | Read | ||
| BI | 107 | Compressor Low Pressure Transducer Issue 2 | Modbus 100241; not polled by default | Read | ||
| BI | 108 | Compressor High Pressure Transducer Issue 1 | Modbus 100242; not polled by default | Read | ||
| BI | 109 | Compressor High Pressure Transducer Issue 2 | Modbus 100243; not polled by default | Read | ||
| BI | 110 | Compressor Capacity Reduced | Modbus 100244; not polled by default | Read | ||
| BI | 111 | Dew Point Over Temperature | Modbus 100345; not polled by default | Read | ||
| BI | 112 | Dew Point Under Temperature | Modbus 100346; not polled by default | Read | ||
| BI | 113 | Ext Dew Point Over Temperature | Modbus 100347; not polled by default | Read | ||
| BI | 114 | Ext Dew Point Under Temperature | Modbus 100348; not polled by default | Read | ||
| BI | 115 | Compressor Superheat Over Threshold 1 | Modbus 100349; not polled by default | Read | ||
| BI | 116 | Compressor Superheat Over Threshold 2 | Modbus 100350; not polled by default | Read | ||
| BI | 117 | Unspecified General Event | Modbus 100351; not polled by default | Read | ||
| BI | 118 | Remote Sensor Average Over Temperature | Modbus 100352; not polled by default | Read | ||
| BI | 119 | Remote Sensor Average Under Temperature | Modbus 100353; not polled by default | Read | ||
| BI | 120 | Remote Sensor System Average Over Temperature | Modbus 100354; not polled by default | Read | ||
| BI | 121 | Remote Sensor System Average Under Temperature | Modbus 100355; not polled by default | Read | ||
| BI | 122 | Remote Sensor Over Temperature 1 | Modbus 100356; not polled by default | Read | ||
| BI | 123 | Remote Sensor Over Temperature 2 | Modbus 100357; not polled by default | Read | ||
| BI | 124 | Remote Sensor Over Temperature 3 | Modbus 100358; not polled by default | Read | ||
| BI | 125 | Remote Sensor Over Temperature 4 | Modbus 100359; not polled by default | Read | ||
| BI | 126 | Remote Sensor Over Temperature 5 | Modbus 100360; not polled by default | Read | ||
| BI | 127 | Remote Sensor Over Temperature 6 | Modbus 100361; not polled by default | Read | ||
| BI | 128 | Remote Sensor Over Temperature 7 | Modbus 100362; not polled by default | Read | ||
| BI | 129 | Remote Sensor Over Temperature 8 | Modbus 100363; not polled by default | Read | ||
| BI | 130 | Remote Sensor Over Temperature 9 | Modbus 100364; not polled by default | Read | ||
| BI | 131 | Remote Sensor Over Temperature 10 | Modbus 100365; not polled by default | Read | ||
| BI | 132 | Remote Sensor Under Temperature 1 | Modbus 100366; not polled by default | Read | ||
| BI | 133 | Remote Sensor Under Temperature 2 | Modbus 100367; not polled by default | Read | ||
| BI | 134 | Remote Sensor Under Temperature 3 | Modbus 100368; not polled by default | Read | ||
| BI | 135 | Remote Sensor Under Temperature 4 | Modbus 100369; not polled by default | Read | ||
| BI | 136 | Remote Sensor Under Temperature 5 | Modbus 100370; not polled by default | Read | ||
| BI | 137 | Remote Sensor Under Temperature 6 | Modbus 100371; not polled by default | Read | ||
| BI | 138 | Remote Sensor Under Temperature 7 | Modbus 100372; not polled by default | Read | ||
| BI | 139 | Remote Sensor Under Temperature 8 | Modbus 100373; not polled by default | Read | ||
| BI | 140 | Remote Sensor Under Temperature 9 | Modbus 100374; not polled by default | Read | ||
| BI | 141 | Remote Sensor Under Temperature 10 | Modbus 100375; not polled by default | Read | ||
| BI | 142 | Remote Sensor Issue 1 | Modbus 100376; not polled by default | Read | ||
| BI | 143 | Remote Sensor Issue 2 | Modbus 100377; not polled by default | Read | ||
| BI | 144 | Remote Sensor Issue 3 | Modbus 100378; not polled by default | Read | ||
| BI | 145 | Remote Sensor Issue 4 | Modbus 100379; not polled by default | Read | ||
| BI | 146 | Remote Sensor Issue 5 | Modbus 100380; not polled by default | Read | ||
| BI | 147 | Remote Sensor Issue 6 | Modbus 100381; not polled by default | Read | ||
| BI | 148 | Remote Sensor Issue 7 | Modbus 100382; not polled by default | Read | ||
| BI | 149 | Remote Sensor Issue 8 | Modbus 100383; not polled by default | Read | ||
| BI | 150 | Remote Sensor Issue 9 | Modbus 100384; not polled by default | Read | ||
| BI | 151 | Remote Sensor Issue 10 | Modbus 100385; not polled by default | Read | ||
| BI | 152 | Air Economizer Emergency Override | Modbus 100386; not polled by default | Read | ||
| BI | 153 | Air Economizer Reduced Airflow | Modbus 100387; not polled by default | Read | ||
| BI | 154 | Temperature Control Sensor Issue | Modbus 100388; not polled by default | Read | ||
| BI | 155 | EEV Unspecified General Event | Modbus 100488; not polled by default | Read | ||
| BI | 156 | Static Pressure Sensor Issue | Modbus 100489; not polled by default | Read | ||
| BI | 157 | High Static Pressure | Modbus 100490; not polled by default | Read | ||
| BI | 158 | Low Static Pressure | Modbus 100491; not polled by default | Read | ||
| BI | 159 | Pump Unspecified General Event | Modbus 100492; not polled by default | Read | ||
| BI | 160 | Condenser Unit Unspecified General Event | Modbus 100493; not polled by default | Read | ||
| BI | 161 | Condenser Circuit Unspecified General Event | Modbus 100494; not polled by default | Read | ||
| BI | 162 | Input Undervoltage 1 | Modbus 100500; not polled by default | Read | ||
| BI | 163 | Input Undervoltage 2 | Modbus 100501; not polled by default | Read | ||
| BI | 164 | Input Undervoltage 3 | Modbus 100502; not polled by default | Read | ||
| BI | 165 | Input Undervoltage 4 | Modbus 100503; not polled by default | Read | ||
| BI | 166 | Input Undervoltage 5 | Modbus 100504; not polled by default | Read | ||
| BI | 167 | Input Undervoltage 6 | Modbus 100505; not polled by default | Read | ||
| BI | 168 | Return Humidity Sensor Issue | Modbus 100600; not polled by default | Read | ||
| BI | 169 | Compressor Low Differential Pressure Lockout 1 | Modbus 100601; not polled by default | Read | ||
| BI | 170 | Compressor Low Differential Pressure Lockout 2 | Modbus 100602; not polled by default | Read | ||
| BI | 171 | Airflow Sensor Issue | Modbus 100603; not polled by default | Read | ||
| BI | 172 | Ext Air Damper Position Issue | Modbus 100604; not polled by default | Read | ||
| BI | 173 | Ext Power Source A Failure | Modbus 100605; not polled by default | Read | ||
| BI | 174 | Ext Power Source B Failure | Modbus 100606; not polled by default | Read | ||
| BI | 175 | Static Pressure Sensor Out of Range | Modbus 100607; not polled by default | Read | ||
| BI | 176 | Fluid Temperature Sensor Issue 1 | Modbus 100608; not polled by default | Read | ||
| BI | 177 | Fluid Temperature Sensor Issue 2 | Modbus 100609; not polled by default | Read | ||
| BI | 178 | Fluid Flow Sensor Issue 1 | Modbus 100610; not polled by default | Read | ||
| BI | 179 | Fluid Flow Sensor Issue 2 | Modbus 100611; not polled by default | Read | ||
| BI | 180 | Mixed Mode Lockout | Modbus 100620; not polled by default | Read | ||
| BI | 181 | Aux Air Temp Device Communication Lost | Modbus 100630; not polled by default | Read | ||
| BI | 182 | Modbus Power Meter Communication Lost 1 | Modbus 100640; not polled by default | Read | ||
| BI | 183 | Modbus Power Meter Communication Lost 2 | Modbus 100641; not polled by default | Read | ||
| BI | 184 | Modbus Power Meter Communication Lost 3 | Modbus 100642; not polled by default | Read | ||
| BI | 185 | Modbus Power Meter Communication Lost 4 | Modbus 100643; not polled by default | Read | ||
| BI | 186 | Modbus Power Meter Communication Lost 5 | Modbus 100644; not polled by default | Read | ||
| BI | 187 | Modbus Power Meter Communication Lost 6 | Modbus 100645; not polled by default | Read | ||
| BI | 188 | External Condenser TVSS Issue | Modbus 100655; not polled by default | Read | ||
| BI | 189 | External Condenser VFD Issue | Modbus 100656; not polled by default | Read | ||
| BI | 190 | Condenser Outside Air Temp Out of Operating Range 1 | Modbus 100677; not polled by default | Read | ||
| BI | 191 | Condenser Outside Air Temp Out of Operating Range 2 | Modbus 100678; not polled by default | Read | ||
| BI | 192 | Condenser Control Board Issue 1 | Modbus 100679; not polled by default | Read | ||
| BI | 193 | Condenser Control Board Issue 2 | Modbus 100680; not polled by default | Read | ||
| BI | 194 | Condenser Outside Air Temp Sensor Issue 1 | Modbus 100681; not polled by default | Read | ||
| BI | 195 | Condenser Outside Air Temp Sensor Issue 2 | Modbus 100682; not polled by default | Read | ||
| BI | 196 | Condenser Communication Lost 1 | Modbus 100683; not polled by default | Read | ||
| BI | 197 | Condenser Communication Lost 2 | Modbus 100684; not polled by default | Read | ||
| BI | 198 | Condenser Remote Shutdown 1 | Modbus 100685; not polled by default | Read | ||
| BI | 199 | Condenser Remote Shutdown 2 | Modbus 100686; not polled by default | Read | ||
| BI | 200 | Condenser TVSS Issue 1 | Modbus 100687; not polled by default | Read | ||
| BI | 201 | Condenser TVSS Issue 2 | Modbus 100688; not polled by default | Read | ||
| BI | 202 | Condenser Refrigerant Pressure Sensor Issue 1 | Modbus 100699; not polled by default | Read | ||
| BI | 203 | Condenser Refrigerant Pressure Sensor Issue 2 | Modbus 100700; not polled by default | Read | ||
| BI | 204 | Condenser Refrigerant Pressure Under Threshold 1 | Modbus 100701; not polled by default | Read | ||
| BI | 205 | Condenser Refrigerant Pressure Under Threshold 2 | Modbus 100702; not polled by default | Read | ||
| BI | 206 | Condenser Refrigerant Pressure Over Threshold 1 | Modbus 100703; not polled by default | Read | ||
| BI | 207 | Condenser Refrigerant Pressure Over Threshold 2 | Modbus 100704; not polled by default | Read | ||
| BI | 208 | Condenser Supply Refrigerant Temp Sensor Issue 1 | Modbus 100705; not polled by default | Read | ||
| BI | 209 | Condenser Supply Refrigerant Temp Sensor Issue 2 | Modbus 100706; not polled by default | Read | ||
| BI | 210 | Condenser Supply Refrigerant Under Temp 1 | Modbus 100707; not polled by default | Read | ||
| BI | 211 | Condenser Supply Refrigerant Under Temp 2 | Modbus 100708; not polled by default | Read | ||
| BI | 212 | Condenser Supply Refrigerant Over Temp 1 | Modbus 100709; not polled by default | Read | ||
| BI | 213 | Condenser Supply Refrigerant Over Temp 2 | Modbus 100710; not polled by default | Read | ||
| BI | 214 | Condenser Max Fan Speed Override 1 | Modbus 100711; not polled by default | Read | ||
| BI | 215 | Condenser Max Fan Speed Override 2 | Modbus 100712; not polled by default | Read | ||
| BI | 216 | Condenser Fan Issue 1 | Modbus 100723; not polled by default | Read | ||
| BI | 217 | Condenser Fan Issue 2 | Modbus 100724; not polled by default | Read | ||
| BI | 218 | Condenser Fan Issue 3 | Modbus 100725; not polled by default | Read | ||
| BI | 219 | Condenser Fan Issue 4 | Modbus 100726; not polled by default | Read | ||
| BI | 220 | Condenser Fan Issue 5 | Modbus 100727; not polled by default | Read | ||
| BI | 221 | Condenser Fan Issue 6 | Modbus 100728; not polled by default | Read | ||
| BI | 222 | Condenser Fan Issue 7 | Modbus 100729; not polled by default | Read | ||
| BI | 223 | Condenser Fan Issue 8 | Modbus 100730; not polled by default | Read | ||
| AI | 224 | Free Cooling Internal Control Mode | Modbus 400017; not polled by default | Read | ||
| AI | 225 | Humidity Proportional Control Type | Modbus 400018; not polled by default | Read | ||
| AI | 226 | Fan Speed Maximum Set Point | Modbus 400019; not polled by default | % | Read | |
| AI | 227 | Supply Air Temperature Set Point | Modbus 400020; not polled by default | °C | Read | |
| AI | 228 | Supply Air Temperature Set Point | Modbus 400733; not polled by default | °F | Read | |
| AI | 229 | Free Cooling Internal Temperature Delta | Modbus 400021; not polled by default | °C | Read | |
| AI | 230 | Free Cooling Internal Temperature Delta | Modbus 400734; not polled by default | °F | Read | |
| AI | 231 | Minimum Chilled Water Temp Set Point | Modbus 400022; not polled by default | °C | Read | |
| AI | 232 | Minimum Chilled Water Temp Set Point | Modbus 400735; not polled by default | °F | Read | |
| AImin | 233 | Air Temperature Set Point | Modbus 400023; not polled by default | °C | Read | |
| AI | 234 | Air Temperature Set Point | Modbus 400736; not polled by default | °F | Read | |
| AI | 235 | Air Temperature Proportional Band | Modbus 400024; not polled by default | °C | Read | |
| AI | 236 | Air Temperature Proportional Band | Modbus 400737; not polled by default | °F | Read | |
| AI | 237 | Air Temperature Dead Band | Modbus 400025; not polled by default | °C | Read | |
| AI | 238 | Air Temperature Dead Band | Modbus 400738; not polled by default | °F | Read | |
| AI | 239 | Air Temperature Control Integration Time | Modbus 400026; not polled by default | min | Read | |
| AImin | 240 | Humidity Set Point | Modbus 400027; not polled by default | %RH | Read | |
| AI | 241 | Humidity Proportional Band | Modbus 400028; not polled by default | %RH | Read | |
| AI | 242 | Humidity Proportional Control Integration Time | Modbus 400029; not polled by default | min | Read | |
| AI | 243 | Humidity Dead Band | Modbus 400030; not polled by default | %RH | Read | |
| AI | 244 | Auto Restart Delay | Modbus 400031; not polled by default | s | Read | |
| AI | 245 | Air Temperature Control Type | Modbus 400033; not polled by default | Read | ||
| AI | 246 | BMS Timeout Period | Modbus 400045; not polled by default | min | Read | |
| AI | 247 | Return Air Over Temp Threshold | Modbus 400050; not polled by default | °C | Read | |
| AI | 248 | Return Air Over Temp Threshold | Modbus 400739; not polled by default | °F | Read | |
| AI | 249 | Return Air Under Temp Threshold | Modbus 400051; not polled by default | °C | Read | |
| AI | 250 | Return Air Under Temp Threshold | Modbus 400740; not polled by default | °F | Read | |
| AI | 251 | Ext Air Sensor A Over Temp Threshold | Modbus 400052; not polled by default | °C | Read | |
| AI | 252 | Ext Air Sensor A Over Temp Threshold | Modbus 400741; not polled by default | °F | Read | |
| AI | 253 | Ext Air Sensor A Under Temp Threshold | Modbus 400053; not polled by default | °C | Read | |
| AI | 254 | Ext Air Sensor A Under Temp Threshold | Modbus 400742; not polled by default | °F | Read | |
| AI | 255 | High Return Humidity Threshold | Modbus 400054; not polled by default | %RH | Read | |
| AI | 256 | Low Return Humidity Threshold | Modbus 400055; not polled by default | %RH | Read | |
| AI | 257 | Ext Air Sensor A High Humidity Threshold | Modbus 400056; not polled by default | %RH | Read | |
| AI | 258 | Ext Air Sensor A Low Humidity Threshold | Modbus 400057; not polled by default | %RH | Read | |
| AI | 259 | Fan Hours Threshold | Modbus 400070; not polled by default | h | Read | |
| AI | 260 | ompressor Hours Threshold 1 | Modbus 400071; not polled by default | h | Read | |
| AI | 261 | Compressor Hours Threshold 2 | Modbus 400072; not polled by default | h | Read | |
| AI | 262 | Humidifier Hours Threshold | Modbus 400073; not polled by default | h | Read | |
| AI | 263 | Dehumidifier Hours Threshold | Modbus 400074; not polled by default | h | Read | |
| AI | 264 | Free Cooling Valve Hours Threshold | Modbus 400075; not polled by default | h | Read | |
| AI | 265 | Electric Reheater Hours Threshold 1 | Modbus 400076; not polled by default | h | Read | |
| AI | 266 | Electric Reheater Hours Threshold 2 | Modbus 400077; not polled by default | h | Read | |
| AI | 267 | Electric Reheater Hours Threshold 3 | Modbus 400078; not polled by default | h | Read | |
| AI | 268 | Hot Water / Hot Gas Valve Hours Threshold | Modbus 400079; not polled by default | h | Read | |
| AI | 269 | System Operating State | Modbus 300100; not polled by default | Read | ||
| AI | 270 | System Status | Modbus 300102; not polled by default | Read | ||
| AI | 271 | Fan Speed | Modbus 300103; not polled by default | % | Read | |
| AI | 272 | Compressor Utilization | Modbus 300104; not polled by default | % | Read | |
| AI | 273 | Free Cooling Valve Open Position | Modbus 300105; not polled by default | % | Read | |
| AI | 274 | Reheat Utilization | Modbus 300106; not polled by default | % | Read | |
| AI | 275 | Humidifier Utilization | Modbus 300107; not polled by default | % | Read | |
| AI | 276 | Dehumidifier Utilization | Modbus 300108; not polled by default | % | Read | |
| AI | 277 | Free Cooling Status | Modbus 300109; not polled by default | Read | ||
| AImin | 278 | Return Air Temperature | Modbus 300110; not polled by default | °C | Read | |
| AI | 279 | Return Air Temperature | Modbus 300743; not polled by default | °F | Read | |
| AImin | 280 | Supply Air Temperature | Modbus 300112; not polled by default | °C | Read | |
| AI | 281 | Supply Air Temperature | Modbus 300744; not polled by default | °F | Read | |
| AI | 282 | Supply Air Temperature Set Point | Modbus 300113; not polled by default | °C | Read | |
| AI | 283 | Supply Air Temperature Set Point | Modbus 300745; not polled by default | °F | Read | |
| AI | 284 | Free Cooling Fluid Temperature | Modbus 300115; not polled by default | °C | Read | |
| AI | 285 | Free Cooling Fluid Temperature | Modbus 300746; not polled by default | °F | Read | |
| AI | 286 | Ext Air Sensor A Temperature | Modbus 300116; not polled by default | °C | Read | |
| AI | 287 | Ext Air Sensor A Temperature | Modbus 300747; not polled by default | °F | Read | |
| AI | 288 | Ext Air Sensor B Temperature | Modbus 300117; not polled by default | °C | Read | |
| AI | 289 | Ext Air Sensor B Temperature | Modbus 300748; not polled by default | °F | Read | |
| AI | 290 | Ext Air Sensor C Temperature | Modbus 300118; not polled by default | °C | Read | |
| AI | 291 | Ext Air Sensor C Temperature | Modbus 300749; not polled by default | °F | Read | |
| AI | 292 | Dig Scroll Comp Discharge Temp 1 | Modbus 300119; not polled by default | °C | Read | |
| AI | 293 | Dig Scroll Comp Discharge Temp 1 | Modbus 300750; not polled by default | °F | Read | |
| AI | 294 | Dig Scroll Comp Discharge Temp 2 | Modbus 300120; not polled by default | °C | Read | |
| AI | 295 | Dig Scroll Comp Discharge Temp 2 | Modbus 300751; not polled by default | °F | Read | |
| AImin | 296 | Return Humidity | Modbus 300130; not polled by default | %RH | Read | |
| AI | 297 | Ext Air Sensor A Humidity | Modbus 300132; not polled by default | %RH | Read | |
| AI | 298 | Ext Air Sensor B Humidity | Modbus 300133; not polled by default | %RH | Read | |
| AI | 299 | Ext Air Sensor C Humidity | Modbus 300134; not polled by default | %RH | Read | |
| AI | 300 | Fan Hours | Modbus 400141; not polled by default | h | Read | |
| AI | 301 | Compressor Hours 1 | Modbus 400142; not polled by default | h | Read | |
| AI | 302 | Compressor Hours 2 | Modbus 400143; not polled by default | h | Read | |
| AI | 303 | Humidifier Hours | Modbus 400144; not polled by default | h | Read | |
| AI | 304 | Dehumidifier Hours | Modbus 400145; not polled by default | h | Read | |
| AI | 305 | Free Cooling Valve Hours | Modbus 400146; not polled by default | h | Read | |
| AI | 306 | Electric Reheater Hours 1 | Modbus 400147; not polled by default | h | Read | |
| AI | 307 | Electric Reheater Hours 2 | Modbus 400148; not polled by default | h | Read | |
| AI | 308 | Electric Reheater Hours 3 | Modbus 400149; not polled by default | h | Read | |
| AI | 309 | Hot Water / Hot Gas Valve Hours | Modbus 400150; not polled by default | h | Read | |
| AI | 310 | Today's High Air Temperature | Modbus 300151; not polled by default | °C | Read | |
| AI | 311 | Today's High Air Temperature | Modbus 300752; not polled by default | °F | Read | |
| AI | 312 | Today's Low Air Temperature | Modbus 300153; not polled by default | °C | Read | |
| AI | 313 | Today's Low Air Temperature | Modbus 300753; not polled by default | °F | Read | |
| AI | 314 | Today's High Humidity | Modbus 300155; not polled by default | %RH | Read | |
| AI | 315 | Today's Low Humidity | Modbus 300157; not polled by default | %RH | Read | |
| AI | 316 | Server Class | Modbus 300257; not polled by default | Read | ||
| AI | 317 | Today's High Air Temperature Time | Modbus 300258; not polled by default | s | Read | |
| AI | 318 | Today's Low Air Temperature Time | Modbus 300260; not polled by default | s | Read | |
| AI | 319 | Supply Air Temperature Sensor Control | Modbus 400262; not polled by default | Read | ||
| AI | 320 | Return Air Temperature Set Point | Modbus 400263; not polled by default | °C | Read | |
| AI | 321 | Return Air Temperature Set Point | Modbus 400754; not polled by default | °F | Read | |
| AI | 322 | Return Humidity Set Point | Modbus 400264; not polled by default | %RH | Read | |
| AI | 323 | Today's High Humidity Time | Modbus 300265; not polled by default | s | Read | |
| AI | 324 | Today's Low Humidity Time | Modbus 300267; not polled by default | s | Read | |
| AI | 325 | Fixed Compressor State 1 | Modbus 300269; not polled by default | Read | ||
| AI | 326 | Fixed Compressor State 2 | Modbus 300270; not polled by default | Read | ||
| AI | 327 | Compressor Capacity Control State 1 | Modbus 300271; not polled by default | Read | ||
| AI | 328 | Compressor Capacity Control State 2 | Modbus 300272; not polled by default | Read | ||
| AI | 329 | Infrared Humidifier Flush Rate | Modbus 400273; not polled by default | % | Read | |
| AI | 330 | Fan Control Mode | Modbus 400274; not polled by default | Read | ||
| AI | 331 | Analog Input Reading 1 | Modbus 300275; not polled by default | Read | ||
| AI | 332 | Analog Input Reading 2 | Modbus 300276; not polled by default | Read | ||
| AI | 333 | Analog Input Reading 3 | Modbus 300277; not polled by default | Read | ||
| AI | 334 | Analog Input Reading 4 | Modbus 300278; not polled by default | Read | ||
| AI | 335 | System Control Mode | Modbus 300280; not polled by default | Read | ||
| AI | 336 | System Operating State Reason | Modbus 300281; not polled by default | Read | ||
| AI | 337 | Maintenance Ramp | Modbus 300282; not polled by default | % | Read | |
| AI | 338 | Calculated Next Maintenance Month | Modbus 300283; not polled by default | Read | ||
| AI | 339 | Calculated Next Maintenance Year | Modbus 300284; not polled by default | Read | ||
| AI | 340 | Hot Water / Hot Gas Valve Open Position | Modbus 300285; not polled by default | % | Read | |
| AI | 341 | Maintenance Tracking State | Modbus 300286; not polled by default | Read | ||
| AI | 342 | Customer Input 1 - Event Control | Modbus 400287; not polled by default | Read | ||
| AI | 343 | Customer Input 1 - Event Type | Modbus 400288; not polled by default | Read | ||
| AI | 344 | Customer Input 2 - Event Control | Modbus 400289; not polled by default | Read | ||
| AI | 345 | Customer Input 2 - Event Type | Modbus 400290; not polled by default | Read | ||
| AI | 346 | Customer Input 3 - Event Control | Modbus 400291; not polled by default | Read | ||
| AI | 347 | Customer Input 3 - Event Type | Modbus 400292; not polled by default | Read | ||
| AI | 348 | Customer Input 4 - Event Control | Modbus 400293; not polled by default | Read | ||
| AI | 349 | Customer Input 4 - Event Type | Modbus 400294; not polled by default | Read | ||
| AI | 350 | Ext Free Cooling Lockout – Event Control | Modbus 400295; not polled by default | Read | ||
| AI | 351 | Ext Free Cooling Lockout – Event Type | Modbus 400296; not polled by default | Read | ||
| AI | 352 | Ext Condenser Pump High Water - Event Control | Modbus 400297; not polled by default | Read | ||
| AI | 353 | Ext Condenser Pump High Water - Event Type | Modbus 400298; not polled by default | Read | ||
| AI | 354 | Ext Standby Glycol Pump On - Event Control | Modbus 400299; not polled by default | Read | ||
| AI | 355 | Ext Standby Glycol Pump On - vent Type | Modbus 400300; not polled by default | Read | ||
| AI | 356 | Ext Standby Unit On - Event Control | Modbus 400301; not polled by default | Read | ||
| AI | 357 | Ext Standby Unit On - Event Type | Modbus 400302; not polled by default | Read | ||
| AI | 358 | Ext Humidifier Lockout – Event Control | Modbus 400303; not polled by default | Read | ||
| AI | 359 | Ext Humidifier Lockout - Event Type | Modbus 400304; not polled by default | Read | ||
| AI | 360 | Ext Loss of Flow - Event Control | Modbus 400305; not polled by default | Read | ||
| AI | 361 | Ext Loss of Flow - Event Type | Modbus 400306; not polled by default | Read | ||
| AI | 362 | Ext Over Temperature – Event Control | Modbus 400307; not polled by default | Read | ||
| AI | 363 | Ext Over Temperature - Event Type | Modbus 400308; not polled by default | Read | ||
| AI | 364 | Ext Reheat Lockout - Event Control | Modbus 400309; not polled by default | Read | ||
| AI | 365 | Ext Reheat Lockout - Event Type | Modbus 400310; not polled by default | Read | ||
| AI | 366 | High Power Shutdown – Event Control | Modbus 400311; not polled by default | Read | ||
| AI | 367 | High Power Shutdown - Event Type | Modbus 400312; not polled by default | Read | ||
| AI | 368 | Humidifier Issue - Event Control | Modbus 400313; not polled by default | Read | ||
| AI | 369 | Humidifier Issue - Event Type | Modbus 400314; not polled by default | Read | ||
| AI | 370 | Master Unit Communication Lost - Event Control | Modbus 400315; not polled by default | Read | ||
| AI | 371 | Master Unit Communication Lost - Event Type | Modbus 400316; not polled by default | Read | ||
| AI | 372 | Service Required - Event Control | Modbus 400317; not polled by default | Read | ||
| AI | 373 | Service Required - Event Type | Modbus 400318; not polled by default | Read | ||
| AI | 374 | Shutdown - Loss Of Power – Event Control | Modbus 400319; not polled by default | Read | ||
| AI | 375 | Shutdown - Loss Of Power – Event Type | Modbus 400320; not polled by default | Read | ||
| AI | 376 | Smoke Detected - Event Control | Modbus 400321; not polled by default | Read | ||
| AI | 377 | Smoke Detected - Event Type | Modbus 400322; not polled by default | Read | ||
| AI | 378 | Water Under Floor - Event Control | Modbus 400323; not polled by default | Read | ||
| AI | 379 | Water Under Floor - Event Type | Modbus 400324; not polled by default | Read | ||
| AI | 380 | Ext Compressor Lockout – Event Control | Modbus 400325; not polled by default | Read | ||
| AI | 381 | Ext Compressor Lockout – Event Type | Modbus 400326; not polled by default | Read | ||
| AI | 382 | Clogged Air Filter - Event Control | Modbus 400327; not polled by default | Read | ||
| AI | 383 | Clogged Air Filter - Event Type | Modbus 400328; not polled by default | Read | ||
| AI | 384 | Ext Loss of Air Blower – Event Control | Modbus 400329; not polled by default | Read | ||
| AI | 385 | Ext Loss of Air Blower - Event Type | Modbus 400330; not polled by default | Read | ||
| AI | 386 | Compressor High Head Pressure - Event Control 1 | Modbus 400331; not polled by default | Read | ||
| AI | 387 | Compressor High Head Pressure - Event Control 2 | Modbus 400332; not polled by default | Read | ||
| AI | 388 | Compressor High Head Pressure - Event Type 1 | Modbus 400333; not polled by default | Read | ||
| AI | 389 | Compressor High Head Pressure - Event Type 2 | Modbus 400334; not polled by default | Read | ||
| AI | 390 | Compressor Low Suction Pressure - Event Control 1 | Modbus 400335; not polled by default | Read | ||
| AI | 391 | Compressor Low Suction Pressure - Event Control 2 | Modbus 400336; not polled by default | Read | ||
| AI | 392 | Compressor Low Suction Pressure - Event Type 1 | Modbus 400337; not polled by default | Read | ||
| AI | 393 | Compressor Low Suction Pressure - Event Type 2 | Modbus 400338; not polled by default | Read | ||
| AI | 394 | Compressor Pump Down Issue - Event Control 1 | Modbus 400339; not polled by default | Read | ||
| AI | 395 | Compressor Pump Down Issue - Event Control 2 | Modbus 400340; not polled by default | Read | ||
| AI | 396 | Compressor Pump Down Issue - Event Type 1 | Modbus 400341; not polled by default | Read | ||
| AI | 397 | Compressor Pump Down Issue - Event Type 2 | Modbus 400342; not polled by default | Read | ||
| AI | 398 | Compressor Short Cycle – Event Control 1 | Modbus 400343; not polled by default | Read | ||
| AI | 399 | Compressor Short Cycle – Event Control 2 | Modbus 400344; not polled by default | Read | ||
| AI | 400 | Compressor Short Cycle – Event Type 1 | Modbus 400345; not polled by default | Read | ||
| AI | 401 | Compressor Short Cycle – Event Type 2 | Modbus 400346; not polled by default | Read | ||
| AI | 402 | Compressor Thermal Overload - Event Control 1 | Modbus 400347; not polled by default | Read | ||
| AI | 403 | Compressor Thermal Overload - Event Control 2 | Modbus 400348; not polled by default | Read | ||
| AI | 404 | Compressor Thermal Overload - Event Type 1 | Modbus 400349; not polled by default | Read | ||
| AI | 405 | Compressor Thermal Overload - Event Type 2 | Modbus 400350; not polled by default | Read | ||
| AI | 406 | Dig Scroll Comp Discharge Over Temp - Event Ctrl 1 | Modbus 400351; not polled by default | Read | ||
| AI | 407 | Dig Scroll Comp Discharge Over Temp - Event Ctrl 2 | Modbus 400352; not polled by default | Read | ||
| AI | 408 | Dig Scroll Comp Discharge Over Temp - Event Type 1 | Modbus 400353; not polled by default | Read | ||
| AI | 409 | Dig Scroll Comp Discharge Over Temp - Event Type 2 | Modbus 400354; not polled by default | Read | ||
| AI | 410 | Ext Air Sensor A High Humidity - Event Control | Modbus 400355; not polled by default | Read | ||
| AI | 411 | Ext Air Sensor A High Humidity - Event Type | Modbus 400356; not polled by default | Read | ||
| AI | 412 | Ext Air Sensor A Low Humidity - Event Control | Modbus 400357; not polled by default | Read | ||
| AI | 413 | Ext Air Sensor A Low Humidity - Event Type | Modbus 400358; not polled by default | Read | ||
| AI | 414 | Ext Air Sensor A Over Temp – Event Control | Modbus 400359; not polled by default | Read | ||
| AI | 415 | Ext Air Sensor A Over Temp – Event Type | Modbus 400360; not polled by default | Read | ||
| AI | 416 | Ext Air Sensor A Under Temp - Event Control | Modbus 400361; not polled by default | Read | ||
| AI | 417 | Ext Air Sensor A Under Temp - Event Type | Modbus 400362; not polled by default | Read | ||
| AI | 418 | High Return Humidity – Event Control | Modbus 400363; not polled by default | Read | ||
| AI | 419 | High Return Humidity - Event Type | Modbus 400364; not polled by default | Read | ||
| AI | 420 | Low Return Humidity - Event Control | Modbus 400365; not polled by default | Read | ||
| AI | 421 | Low Return Humidity - Event Type | Modbus 400366; not polled by default | Read | ||
| AI | 422 | Return Air Over Temp – Event Control | Modbus 400367; not polled by default | Read | ||
| AI | 423 | Return Air Over Temp - Event Type | Modbus 400368; not polled by default | Read | ||
| AI | 424 | Return Air Under Temp – Event Control | Modbus 400369; not polled by default | Read | ||
| AI | 425 | Return Air Under Temp - Event Type | Modbus 400370; not polled by default | Read | ||
| AI | 426 | Fan Hours Exceeded – Event Control | Modbus 400371; not polled by default | Read | ||
| AI | 427 | Fan Hours Exceeded - Event Type | Modbus 400372; not polled by default | Read | ||
| AI | 428 | Fan Issue - Event Control | Modbus 400373; not polled by default | Read | ||
| AI | 429 | Fan Issue - Event Type | Modbus 400374; not polled by default | Read | ||
| AI | 430 | Main Fan Overload - Event Control | Modbus 400375; not polled by default | Read | ||
| AI | 431 | Main Fan Overload - Event Type | Modbus 400376; not polled by default | Read | ||
| AI | 432 | Condenser Issue - Event Control 1 | Modbus 400377; not polled by default | Read | ||
| AI | 433 | Condenser Issue - Event Control 2 | Modbus 400378; not polled by default | Read | ||
| AI | 434 | Condenser Issue - Event Type 1 | Modbus 400379; not polled by default | Read | ||
| AI | 435 | Condenser Issue - Event Type 2 | Modbus 400380; not polled by default | Read | ||
| AI | 436 | System Event Acknowledge/Reset | Modbus 400381; not polled by default | Read | ||
| AI | 437 | Air Temperature Control Sensor | Modbus 400481; not polled by default | Read | ||
| AI | 438 | Supply Air Over Temp Threshold | Modbus 400482; not polled by default | °C | Read | |
| AI | 439 | Supply Air Over Temp Threshold | Modbus 400755; not polled by default | °F | Read | |
| AI | 440 | Supply Air Under Temp Threshold | Modbus 400483; not polled by default | °C | Read | |
| AI | 441 | Supply Air Under Temp Threshold | Modbus 400756; not polled by default | °F | Read | |
| AI | 442 | Outside Air Temperature | Modbus 300484; not polled by default | °C | Read | |
| AI | 443 | Outside Air Temperature | Modbus 300757; not polled by default | °F | Read | |
| AI | 444 | Humidity Proportional Control Type | Modbus 400485; not polled by default | Read | ||
| AI | 445 | Ext Air Sensor A Dew Point Temp | Modbus 300486; not polled by default | °C | Read | |
| AI | 446 | Ext Air Sensor A Dew Point Temp | Modbus 300758; not polled by default | °F | Read | |
| AI | 447 | Ext Dew Point Over Temp Threshold | Modbus 400487; not polled by default | °C | Read | |
| AI | 448 | Ext Dew Point Over Temp Threshold | Modbus 400759; not polled by default | °F | Read | |
| AI | 449 | Ext Dew Point Under Temp Threshold | Modbus 400488; not polled by default | °C | Read | |
| AI | 450 | Ext Dew Point Under Temp Threshold | Modbus 400760; not polled by default | °F | Read | |
| AI | 451 | Compressor Lockout | Modbus 400489; not polled by default | Read | ||
| AI | 452 | Main Chilled Water Valve | Modbus 400491; not polled by default | Read | ||
| AI | 453 | Reheater Lockout | Modbus 400492; not polled by default | Read | ||
| AI | 454 | Humidifier Lockout | Modbus 400493; not polled by default | Read | ||
| AI | 455 | Fan Control Sensor | Modbus 400494; not polled by default | Read | ||
| AI | 456 | Fan Speed Minimum Set Point | Modbus 400495; not polled by default | % | Read | |
| AI | 457 | Fan Speed Temperature Set Point | Modbus 400497; not polled by default | °C | Read | |
| AI | 458 | Fan Speed Temperature Set Point | Modbus 400761; not polled by default | °F | Read | |
| AI | 459 | Standby Units | Modbus 400498; not polled by default | Read | ||
| AI | 460 | Adjusted Humidity | Modbus 300499; not polled by default | %RH | Read | |
| AI | 461 | eturn Dew Point | Modbus 300500; not polled by default | °C | Read | |
| AI | 462 | Return Dew Point | Modbus 300762; not polled by default | °F | Read | |
| AI | 463 | Actual Air Temperature Set Point | Modbus 300501; not polled by default | °C | Read | |
| AI | 464 | Actual Air Temperature Set Point | Modbus 300763; not polled by default | °F | Read | |
| AI | 465 | Actual Humidity Set Point | Modbus 300502; not polled by default | %RH | Read | |
| AI | 466 | Dew Point Set Point | Modbus 400503; not polled by default | °C | Read | |
| AI | 467 | Dew Point Set Point | Modbus 400764; not polled by default | °F | Read | |
| AI | 468 | Supply Air Over/Under Temperature - Event Control | Modbus 400504; not polled by default | Read | ||
| AI | 469 | Remote Sensor Over Temp Threshold | Modbus 400505; not polled by default | °C | Read | |
| AI | 470 | Remote Sensor Over Temp Threshold | Modbus 400765; not polled by default | °F | Read | |
| AI | 471 | Remote Sensor Under Temp Threshold | Modbus 400506; not polled by default | °C | Read | |
| AI | 472 | Remote Sensor Under Temp Threshold | Modbus 400766; not polled by default | °F | Read | |
| AI | 473 | Remote Sensor Average Temperature | Modbus 300507; not polled by default | °C | Read | |
| AI | 474 | Remote Sensor Average Temperature | Modbus 300767; not polled by default | °F | Read | |
| AI | 475 | Remote Sensor Maximum Temperature | Modbus 300508; not polled by default | °C | Read | |
| AI | 476 | Remote Sensor Maximum Temperature | Modbus 300768; not polled by default | °F | Read | |
| AI | 477 | Remote Sensor System Average Temperature | Modbus 300509; not polled by default | °C | Read | |
| AI | 478 | Remote Sensor System Average Temperature | Modbus 300769; not polled by default | °F | Read | |
| AI | 479 | Remote Sensor System Maximum Temperature | Modbus 300510; not polled by default | °C | Read | |
| AI | 480 | Remote Sensor System Maximum Temperature | Modbus 300770; not polled by default | °F | Read | |
| AI | 481 | Remote Sensor Temperature 1 | Modbus 300551; not polled by default | °C | Read | |
| AI | 482 | Remote Sensor Temperature 1 | Modbus 300771; not polled by default | °F | Read | |
| AI | 483 | Remote Sensor Temperature 2 | Modbus 300552; not polled by default | °C | Read | |
| AI | 484 | Remote Sensor Temperature 2 | Modbus 300772; not polled by default | °F | Read | |
| AI | 485 | Remote Sensor Temperature 3 | Modbus 300553; not polled by default | °C | Read | |
| AI | 486 | Remote Sensor Temperature 3 | Modbus 300773; not polled by default | °F | Read | |
| AI | 487 | Remote Sensor Temperature 4 | Modbus 300554; not polled by default | °C | Read | |
| AI | 488 | Remote Sensor Temperature 4 | Modbus 300774; not polled by default | °F | Read | |
| AI | 489 | Remote Sensor Temperature 5 | Modbus 300555; not polled by default | °C | Read | |
| AI | 490 | Remote Sensor Temperature 5 | Modbus 300775; not polled by default | °F | Read | |
| AI | 491 | Remote Sensor Temperature 6 | Modbus 300556; not polled by default | °C | Read | |
| AI | 492 | Remote Sensor Temperature 6 | Modbus 300776; not polled by default | °F | Read | |
| AI | 493 | Remote Sensor Temperature 7 | Modbus 300557; not polled by default | °C | Read | |
| AI | 494 | Remote Sensor Temperature 7 | Modbus 300777; not polled by default | °F | Read | |
| AI | 495 | Remote Sensor Temperature 8 | Modbus 300558; not polled by default | °C | Read | |
| AI | 496 | Remote Sensor Temperature 8 | Modbus 300778; not polled by default | °F | Read | |
| AI | 497 | Remote Sensor Temperature 9 | Modbus 300559; not polled by default | °C | Read | |
| AI | 498 | Remote Sensor Temperature 9 | Modbus 300779; not polled by default | °F | Read | |
| AI | 499 | Remote Sensor Temperature 10 | Modbus 300560; not polled by default | °C | Read | |
| AI | 500 | Remote Sensor Temperature 10 | Modbus 300780; not polled by default | °F | Read | |
| AI | 501 | Air Economizer Availability | Modbus 300561; not polled by default | Read | ||
| AI | 502 | Air Economizer Control Source | Modbus 400562; not polled by default | Read | ||
| AI | 503 | Chilled Water Valve Hours | Modbus 400563; not polled by default | h | Read | |
| AI | 504 | Cooling Capacity | Modbus 300564; not polled by default | % | Read | |
| AI | 505 | Cooling Control Temperature | Modbus 300565; not polled by default | °C | Read | |
| AI | 506 | Cooling Control Temperature | Modbus 300781; not polled by default | °F | Read | |
| AI | 507 | Fan Speed Control Temperature | Modbus 300566; not polled by default | °C | Read | |
| AI | 508 | Fan Speed Control Temperature | Modbus 300782; not polled by default | °F | Read | |
| AI | 509 | Free Cooling Internal Control Mode | Modbus 400567; not polled by default | Read | ||
| AI | 510 | Humidity Control Sensor | Modbus 400667; not polled by default | Read | ||
| AI | 511 | Digital Scroll Compressor Loading 1 | Modbus 300668; not polled by default | % | Read | |
| AI | 512 | Digital Scroll Compressor Loading 2 | Modbus 300669; not polled by default | % | Read | |
| AI | 513 | Static Pressure Set Point | Modbus 400672; not polled by default | psi | Read | |
| AI | 514 | Unit Static Pressure | Modbus 300673; not polled by default | psi | Read | |
| AI | 515 | System Static Pressure | Modbus 300674; not polled by default | psi | Read | |
| AI | 516 | Condenser Low Noise Mode State | Modbus 300675; not polled by default | Read | ||
| AI | 517 | Condenser Low Noise Mode Schedule Control | Modbus 400676; not polled by default | Read | ||
| AI | 518 | Condenser Low Noise Mode Max Fan Speed | Modbus 400677; not polled by default | % | Read | |
| AI | 519 | Condenser Normal Mode Max Fan Speed | Modbus 400678; not polled by default | % | Read | |
| AI | 520 | Condenser Low Noise Mode - Interval Days | Modbus 400679; not polled by default | Read | ||
| AI | 521 | Condenser Low Noise Mode – Full Days | Modbus 400680; not polled by default | Read | ||
| AI | 522 | Condenser Low Noise Mode Start Time | Modbus 400681; not polled by default | s | Read | |
| AI | 523 | Condenser Low Noise Mode Stop Time | Modbus 400683; not polled by default | s | Read | |
| AI | 524 | Pump Hours 1 | Modbus 400685; not polled by default | h | Read | |
| AI | 525 | Pump Hours 2 | Modbus 400687; not polled by default | h | Read | |
| AI | 526 | System Input RMS A-N 1 | Modbus 300800; not polled by default | V | Read | |
| AI | 527 | System Input RMS A-N 2 | Modbus 300801; not polled by default | V | Read | |
| AI | 528 | System Input RMS A-N 3 | Modbus 300802; not polled by default | V | Read | |
| AI | 529 | System Input RMS A-N 4 | Modbus 300803; not polled by default | V | Read | |
| AI | 530 | System Input RMS A-N 5 | Modbus 300804; not polled by default | V | Read | |
| AI | 531 | System Input RMS A-N 6 | Modbus 300805; not polled by default | V | Read | |
| AI | 532 | System Input RMS B-N 1 | Modbus 300810; not polled by default | V | Read | |
| AI | 533 | System Input RMS B-N 2 | Modbus 300811; not polled by default | V | Read | |
| AI | 534 | System Input RMS B-N 3 | Modbus 300812; not polled by default | V | Read | |
| AI | 535 | System Input RMS B-N 4 | Modbus 300813; not polled by default | V | Read | |
| AI | 536 | System Input RMS B-N 5 | Modbus 300814; not polled by default | V | Read | |
| AI | 537 | System Input RMS B-N 6 | Modbus 300815; not polled by default | V | Read | |
| AI | 538 | System Input RMS C-N 1 | Modbus 300820; not polled by default | V | Read | |
| AI | 539 | System Input RMS C-N 2 | Modbus 300821; not polled by default | V | Read | |
| AI | 540 | System Input RMS C-N 3 | Modbus 300822; not polled by default | V | Read | |
| AI | 541 | System Input RMS C-N 4 | Modbus 300823; not polled by default | V | Read | |
| AI | 542 | System Input RMS C-N 5 | Modbus 300824; not polled by default | V | Read | |
| AI | 543 | System Input RMS C-N 6 | Modbus 300825; not polled by default | V | Read | |
| AI | 544 | System Input RMS Current Phase A 1 | Modbus 300830; not polled by default | V | Read | |
| AI | 545 | System Input RMS Current Phase A 2 | Modbus 300831; not polled by default | V | Read | |
| AI | 546 | System Input RMS Current Phase A 3 | Modbus 300832; not polled by default | V | Read | |
| AI | 547 | System Input RMS Current Phase A 4 | Modbus 300833; not polled by default | V | Read | |
| AI | 548 | System Input RMS Current Phase A 5 | Modbus 300834; not polled by default | V | Read | |
| AI | 549 | System Input RMS Current Phase A 6 | Modbus 300835; not polled by default | V | Read | |
| AI | 550 | System Input RMS Current Phase B 1 | Modbus 300840; not polled by default | V | Read | |
| AI | 551 | System Input RMS Current Phase B 2 | Modbus 300841; not polled by default | V | Read | |
| AI | 552 | System Input RMS Current Phase B 3 | Modbus 300842; not polled by default | V | Read | |
| AI | 553 | System Input RMS Current Phase B 4 | Modbus 300843; not polled by default | V | Read | |
| AI | 554 | System Input RMS Current Phase B 5 | Modbus 300844; not polled by default | V | Read | |
| AI | 555 | System Input RMS Current Phase B 6 | Modbus 300845; not polled by default | V | Read | |
| AI | 556 | System Input RMS Current Phase C 1 | Modbus 300850; not polled by default | V | Read | |
| AI | 557 | System Input RMS Current Phase C 2 | Modbus 300851; not polled by default | V | Read | |
| AI | 558 | System Input RMS Current Phase C 3 | Modbus 300852; not polled by default | V | Read | |
| AI | 559 | System Input RMS Current Phase C 4 | Modbus 300853; not polled by default | V | Read | |
| AI | 560 | System Input RMS Current Phase C 5 | Modbus 300854; not polled by default | V | Read | |
| AI | 561 | System Input RMS Current Phase C 6 | Modbus 300855; not polled by default | V | Read | |
| AI | 562 | Energy Consumption 1 | Modbus 400870; not polled by default | kWh | Read | |
| AI | 563 | Energy Consumption 2 | Modbus 400872; not polled by default | kWh | Read | |
| AI | 564 | Energy Consumption 3 | Modbus 400874; not polled by default | kWh | Read | |
| AI | 565 | Energy Consumption 4 | Modbus 400876; not polled by default | kWh | Read | |
| AI | 566 | Energy Consumption 5 | Modbus 400878; not polled by default | kWh | Read | |
| AI | 567 | Energy Consumption 6 | Modbus 400880; not polled by default | kWh | Read | |
| AI | 568 | Fluid Input Temperature 1 | Modbus 300900; not polled by default | °C | Read | |
| AI | 569 | Fluid Input Temperature 2 | Modbus 300901; not polled by default | °C | Read | |
| AI | 570 | Fluid Input Temperature 1 | Modbus 300902; not polled by default | °F | Read | |
| AI | 571 | Fluid Input Temperature 2 | Modbus 300903; not polled by default | °F | Read | |
| AI | 572 | Fluid Output Temperature 1 | Modbus 300904; not polled by default | °C | Read | |
| AI | 573 | Fluid Output Temperature 2 | Modbus 300905; not polled by default | °C | Read | |
| AI | 574 | Fluid Output Temperature 1 | Modbus 300906; not polled by default | °F | Read | |
| AI | 575 | Fluid Output Temperature 2 | Modbus 300907; not polled by default | °F | Read | |
| AI | 576 | Fluid Flow Rate 1 | Modbus 300908; not polled by default | L/min | Read | |
| AI | 577 | Fluid Flow Rate 2 | Modbus 300910; not polled by default | L/min | Read | |
| AI | 578 | Unit Cooling Load | Modbus 301001; not polled by default | kW | Read | |
| AI | 579 | Circuit Cooling Load 1 | Modbus 301003; not polled by default | kW | Read | |
| AI | 580 | Circuit Cooling Load 2 | Modbus 301005; not polled by default | kW | Read | |
| AI | 581 | Instantaneous Power 1 | Modbus 301010; not polled by default | W | Read | |
| AI | 582 | Instantaneous Power 2 | Modbus 301012; not polled by default | W | Read | |
| AI | 583 | Instantaneous Power 3 | Modbus 301014; not polled by default | W | Read | |
| AI | 584 | Instantaneous Power 4 | Modbus 301016; not polled by default | W | Read | |
| AI | 585 | Instantaneous Power 5 | Modbus 301018; not polled by default | W | Read | |
| AI | 586 | Instantaneous Power 6 | Modbus 301020; not polled by default | W | Read | |
| AI | 587 | Raw Auxiliary Air Temperature | Modbus 401050; not polled by default | °C | Read | |
| AI | 588 | Raw Auxiliary Air Temperature | Modbus 401051; not polled by default | °F | Read | |
| AI | 589 | Actual Auxiliary Air Temperature | Modbus 301052; not polled by default | °C | Read | |
| AI | 590 | Actual Auxiliary Air Temperature | Modbus 301053; not polled by default | °F | Read | |
| AI | 591 | System Input RMS A-B 1 | Modbus 301060; not polled by default | V | Read | |
| AI | 592 | System Input RMS A-B 2 | Modbus 301061; not polled by default | V | Read | |
| AI | 593 | System Input RMS A-B 3 | Modbus 301062; not polled by default | V | Read | |
| AI | 594 | System Input RMS A-B 4 | Modbus 301063; not polled by default | V | Read | |
| AI | 595 | System Input RMS A-B 5 | Modbus 301064; not polled by default | V | Read | |
| AI | 596 | System Input RMS A-B 6 | Modbus 301065; not polled by default | V | Read | |
| AI | 597 | System Input RMS B-C 1 | Modbus 301070; not polled by default | V | Read | |
| AI | 598 | System Input RMS B-C 2 | Modbus 301071; not polled by default | V | Read | |
| AI | 599 | System Input RMS B-C 3 | Modbus 301072; not polled by default | V | Read | |
| AI | 600 | System Input RMS B-C 4 | Modbus 301073; not polled by default | V | Read | |
| AI | 601 | System Input RMS B-C 5 | Modbus 301074; not polled by default | V | Read | |
| AI | 602 | System Input RMS B-C 6 | Modbus 301075; not polled by default | V | Read | |
| AI | 603 | System Input RMS C-A 1 | Modbus 301080; not polled by default | V | Read | |
| AI | 604 | System Input RMS C-A 2 | Modbus 301081; not polled by default | V | Read | |
| AI | 605 | System Input RMS C-A 3 | Modbus 301082; not polled by default | V | Read | |
| AI | 606 | System Input RMS C-A 4 | Modbus 301083; not polled by default | V | Read | |
| AI | 607 | System Input RMS C-A 5 | Modbus 301084; not polled by default | V | Read | |
| AI | 608 | System Input RMS C-A 6 | Modbus 301085; not polled by default | V | Read | |
| AI | 609 | Pump State 1 | Modbus 301100; not polled by default | Read | ||
| AI | 610 | Pump State 2 | Modbus 301110; not polled by default | Read | ||
| AI | 611 | Expected Condenser Unit Count | Modbus 301130; not polled by default | Read | ||
| AI | 612 | Condenser Refrigerant Type | Modbus 301131; not polled by default | Read | ||
| AI | 613 | Condenser Fan Reversal Requested 1 | Modbus 301142; not polled by default | Read | ||
| AI | 614 | Condenser Fan Reversal Requested 2 | Modbus 301143; not polled by default | Read | ||
| AI | 615 | Condenser Outside Air Temperature 1 | Modbus 301144; not polled by default | °C | Read | |
| AI | 616 | Condenser Outside Air Temperature 2 | Modbus 301145; not polled by default | °F | Read | |
| AI | 617 | Condenser Outside Air Temperature 2 | Modbus 301146; not polled by default | °C | Read | |
| AI | 618 | Condenser Outside Air Temperature 2 | Modbus 301147; not polled by default | °F | Read | |
| AI | 619 | Condenser Refrigerant Pressure 1 | Modbus 301158; not polled by default | bar | Read | |
| AI | 620 | Condenser Refrigerant Pressure 2 | Modbus 301159; not polled by default | bar | Read | |
| AI | 621 | Condenser Supply Refrigerant Temperature 1 | Modbus 301160; not polled by default | °C | Read | |
| AI | 622 | Condenser Supply Refrigerant Temperature 1 | Modbus 301161; not polled by default | °F | Read | |
| AI | 623 | Condenser Supply Refrigerant Temperature 2 | Modbus 301162; not polled by default | °C | Read | |
| AI | 624 | Condenser Supply Refrigerant Temperature 2 | Modbus 301163; not polled by default | °F | Read | |
| AI | 625 | Condenser Fan Speed 1 | Modbus 301174; not polled by default | % | Read | |
| AI | 626 | Condenser Fan Speed 2 | Modbus 301175; not polled by default | % | Read | |
| AI | 627 | Condenser Fan Speed 3 | Modbus 301176; not polled by default | % | Read | |
| AI | 628 | Condenser Fan Speed 4 | Modbus 301177; not polled by default | % | Read | |
| AI | 629 | Condenser Fan Speed 5 | Modbus 301178; not polled by default | % | Read | |
| AI | 630 | Condenser Fan Speed 6 | Modbus 301179; not polled by default | % | Read | |
| AI | 631 | Condenser Fan Speed 7 | Modbus 301180; not polled by default | % | Read | |
| AI | 632 | Condenser Fan Speed 8 | Modbus 301181; not polled by default | % | Read | |
| AI | 633 | Condenser Fan Power 1 | Modbus 301182; not polled by default | kW | Read | |
| AI | 634 | Condenser Fan Power 2 | Modbus 301183; not polled by default | kW | Read | |
| AI | 635 | Condenser Fan Power 3 | Modbus 301184; not polled by default | kW | Read | |
| AI | 636 | Condenser Fan Power 4 | Modbus 301185; not polled by default | kW | Read | |
| AI | 637 | Condenser Fan Power 5 | Modbus 301186; not polled by default | kW | Read | |
| AI | 638 | Condenser Fan Power 6 | Modbus 301187; not polled by default | kW | Read | |
| AI | 639 | Condenser Fan Power 7 | Modbus 301188; not polled by default | kW | Read | |
| AI | 640 | Condenser Fan Power 8 | Modbus 301189; not polled by default | kW | Read | |
| AI | 641 | System Date and Time | Modbus 409998; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Liebert iCOM v4 point IDs by name
BI1Ext Reheat LockoutBI2Ext Humidifier LockoutBI3Minimum Chilled Water Temp Set Point EnableBI4Return Air Sensor Event ControlBI5Ext Air Sensor A Event ControlBI6Ext Compressor LockoutBI7System On/Off ControlBI8Fan StateBI9Cooling StateBI10Free Cooling StateBI11Hot Water / Hot Gas StateBI12Electric Reheat StateBI13Humidifier StateBI14Dehumidifier StateBI15Main Fan OverloadBI16Loss of Air FlowBI17Ext Loss of FlowBI18Compressor High Head PressureBI19Compressor Low Suction PressureBI20Compressor Thermal OverloadBI21Compressor Pump Down IssueBI22Compressor High Head Pressure 2BI23Compressor Low Suction Pressure 2BI24Compressor Thermal Overload 2BI25Compressor Pump Down Issue 2BI26Dig Scroll Comp Over Temp 1BI27Dig Scroll Comp Over Temp 2BI28Smoke DetectedBI29Water Under FloorBI30Humidifier IssueBI31Ext Standby Glycol Pump OnBI32Ext Standby Unit OnBI33Ext Condenser Pump High WaterBI34Return Air Sensor IssueBI35Ext Loss of Air BlowerBI36Humidifier Low WaterBI37Humidifier Over CurrentBI38Ext Over TemperatureBI39Shutdown - Loss Of PowerBI40Supply Chilled Water Over TempBI41Return Air Over TemperatureBI42Return Air Under TemperatureBI43High Return HumidityBI44Low Return HumidityBI45Ext Air Sensor A Over TemperatureBI46Ext Air Sensor A Under TemperatureBI47Ext Air Sensor A High HumidityBI48Ext Air Sensor A Low HumidityBI49Supply Chilled Water Loss of FlowBI50Clogged Air FilterBI51Supply Air Sensor IssueBI52Free Cooling Temp Sensor IssueBI53Ext Air Sensor A IssueBI54Fan Hours ExceededBI55Compressor Hours Exceeded 1BI56Compressor Hours Exceeded 2BI57Free Cooling Valve Hours ExceededBI58Electric Reheater Hours Exceeded 1BI59Electric Reheater Hours Exceeded 2BI60Electric Reheater Hours Exceeded 3BI61Hot Water / Hot Gas Valve Hours ExceededBI62Humidifier Hours ExceededBI63Dehumidifier Hours ExceededBI64Unit Communication LostBI65Master Unit Communication LostBI66Unit Code MissingBI67Service RequiredBI68Humidifier Control Board Not DetectedBI69Customer Input 1BI70Customer Input 2BI71Customer Input 3BI72Customer Input 4BI73Dig Scroll Comp Discharge Temp Sensor Issue 1BI74Dig Scroll Comp Discharge Temp Sensor Issue 2BI75Supply Air Over TemperatureBI76Supply Air Under TemperatureBI77Ambient Air Sensor IssueBI78Compressor Short Cycle 1BI79Compressor Short Cycle 2BI80Ext Free Cooling LockoutBI81Reheater Over TemperatureBI82Humidifier Cylinder WornBI83Humidifier Under CurrentBI84Fan IssueBI85Condenser TVSS IssueBI86Condenser VFD IssueBI87Condenser Issue 1BI88Condenser Issue 2BI89BMS Communications TimeoutBI90Digital Output Board Not Detected 1BI91Digital Output Board Not Detected 2BI92Digital Output Board Not Detected 3BI93RAM Battery IssueBI94Water Leakage Detector Sensor IssueBI95External Fire DetectedBI96Chilled Water Control Valve Failure 1BI97Chilled Water Control Valve Failure 2BI98Unit OffBI99Unit OnBI100Unit Partial ShutdownBI101Unit ShutdownBI102High Power ShutdownBI103Unit StandbyBI104Maintenance DueBI105Maintenance CompletedBI106Compressor Low Pressure Transducer Issue 1BI107Compressor Low Pressure Transducer Issue 2BI108Compressor High Pressure Transducer Issue 1BI109Compressor High Pressure Transducer Issue 2BI110Compressor Capacity ReducedBI111Dew Point Over TemperatureBI112Dew Point Under TemperatureBI113Ext Dew Point Over TemperatureBI114Ext Dew Point Under TemperatureBI115Compressor Superheat Over Threshold 1BI116Compressor Superheat Over Threshold 2BI117Unspecified General EventBI118Remote Sensor Average Over TemperatureBI119Remote Sensor Average Under TemperatureBI120Remote Sensor System Average Over TemperatureBI121Remote Sensor System Average Under TemperatureBI122Remote Sensor Over Temperature 1BI123Remote Sensor Over Temperature 2BI124Remote Sensor Over Temperature 3BI125Remote Sensor Over Temperature 4BI126Remote Sensor Over Temperature 5BI127Remote Sensor Over Temperature 6BI128Remote Sensor Over Temperature 7BI129Remote Sensor Over Temperature 8BI130Remote Sensor Over Temperature 9BI131Remote Sensor Over Temperature 10BI132Remote Sensor Under Temperature 1BI133Remote Sensor Under Temperature 2BI134Remote Sensor Under Temperature 3BI135Remote Sensor Under Temperature 4BI136Remote Sensor Under Temperature 5BI137Remote Sensor Under Temperature 6BI138Remote Sensor Under Temperature 7BI139Remote Sensor Under Temperature 8BI140Remote Sensor Under Temperature 9BI141Remote Sensor Under Temperature 10BI142Remote Sensor Issue 1BI143Remote Sensor Issue 2BI144Remote Sensor Issue 3BI145Remote Sensor Issue 4BI146Remote Sensor Issue 5BI147Remote Sensor Issue 6BI148Remote Sensor Issue 7BI149Remote Sensor Issue 8BI150Remote Sensor Issue 9BI151Remote Sensor Issue 10BI152Air Economizer Emergency OverrideBI153Air Economizer Reduced AirflowBI154Temperature Control Sensor IssueBI155EEV Unspecified General EventBI156Static Pressure Sensor IssueBI157High Static PressureBI158Low Static PressureBI159Pump Unspecified General EventBI160Condenser Unit Unspecified General EventBI161Condenser Circuit Unspecified General EventBI162Input Undervoltage 1BI163Input Undervoltage 2BI164Input Undervoltage 3BI165Input Undervoltage 4BI166Input Undervoltage 5BI167Input Undervoltage 6BI168Return Humidity Sensor IssueBI169Compressor Low Differential Pressure Lockout 1BI170Compressor Low Differential Pressure Lockout 2BI171Airflow Sensor IssueBI172Ext Air Damper Position IssueBI173Ext Power Source A FailureBI174Ext Power Source B FailureBI175Static Pressure Sensor Out of RangeBI176Fluid Temperature Sensor Issue 1BI177Fluid Temperature Sensor Issue 2BI178Fluid Flow Sensor Issue 1BI179Fluid Flow Sensor Issue 2BI180Mixed Mode LockoutBI181Aux Air Temp Device Communication LostBI182Modbus Power Meter Communication Lost 1BI183Modbus Power Meter Communication Lost 2BI184Modbus Power Meter Communication Lost 3BI185Modbus Power Meter Communication Lost 4BI186Modbus Power Meter Communication Lost 5BI187Modbus Power Meter Communication Lost 6BI188External Condenser TVSS IssueBI189External Condenser VFD IssueBI190Condenser Outside Air Temp Out of Operating Range 1BI191Condenser Outside Air Temp Out of Operating Range 2BI192Condenser Control Board Issue 1BI193Condenser Control Board Issue 2BI194Condenser Outside Air Temp Sensor Issue 1BI195Condenser Outside Air Temp Sensor Issue 2BI196Condenser Communication Lost 1BI197Condenser Communication Lost 2BI198Condenser Remote Shutdown 1BI199Condenser Remote Shutdown 2BI200Condenser TVSS Issue 1BI201Condenser TVSS Issue 2BI202Condenser Refrigerant Pressure Sensor Issue 1BI203Condenser Refrigerant Pressure Sensor Issue 2BI204Condenser Refrigerant Pressure Under Threshold 1BI205Condenser Refrigerant Pressure Under Threshold 2BI206Condenser Refrigerant Pressure Over Threshold 1BI207Condenser Refrigerant Pressure Over Threshold 2BI208Condenser Supply Refrigerant Temp Sensor Issue 1BI209Condenser Supply Refrigerant Temp Sensor Issue 2BI210Condenser Supply Refrigerant Under Temp 1BI211Condenser Supply Refrigerant Under Temp 2BI212Condenser Supply Refrigerant Over Temp 1BI213Condenser Supply Refrigerant Over Temp 2BI214Condenser Max Fan Speed Override 1BI215Condenser Max Fan Speed Override 2BI216Condenser Fan Issue 1BI217Condenser Fan Issue 2BI218Condenser Fan Issue 3BI219Condenser Fan Issue 4BI220Condenser Fan Issue 5BI221Condenser Fan Issue 6BI222Condenser Fan Issue 7BI223Condenser Fan Issue 8AI224Free Cooling Internal Control ModeAI225Humidity Proportional Control TypeAI226Fan Speed Maximum Set PointAI227Supply Air Temperature Set PointAI228Supply Air Temperature Set PointAI229Free Cooling Internal Temperature DeltaAI230Free Cooling Internal Temperature DeltaAI231Minimum Chilled Water Temp Set PointAI232Minimum Chilled Water Temp Set PointAI233Air Temperature Set PointAI234Air Temperature Set PointAI235Air Temperature Proportional BandAI236Air Temperature Proportional BandAI237Air Temperature Dead BandAI238Air Temperature Dead BandAI239Air Temperature Control Integration TimeAI240Humidity Set PointAI241Humidity Proportional BandAI242Humidity Proportional Control Integration TimeAI243Humidity Dead BandAI244Auto Restart DelayAI245Air Temperature Control TypeAI246BMS Timeout PeriodAI247Return Air Over Temp ThresholdAI248Return Air Over Temp ThresholdAI249Return Air Under Temp ThresholdAI250Return Air Under Temp ThresholdAI251Ext Air Sensor A Over Temp ThresholdAI252Ext Air Sensor A Over Temp ThresholdAI253Ext Air Sensor A Under Temp ThresholdAI254Ext Air Sensor A Under Temp ThresholdAI255High Return Humidity ThresholdAI256Low Return Humidity ThresholdAI257Ext Air Sensor A High Humidity ThresholdAI258Ext Air Sensor A Low Humidity ThresholdAI259Fan Hours ThresholdAI260ompressor Hours Threshold 1AI261Compressor Hours Threshold 2AI262Humidifier Hours ThresholdAI263Dehumidifier Hours ThresholdAI264Free Cooling Valve Hours ThresholdAI265Electric Reheater Hours Threshold 1AI266Electric Reheater Hours Threshold 2AI267Electric Reheater Hours Threshold 3AI268Hot Water / Hot Gas Valve Hours ThresholdAI269System Operating StateAI270System StatusAI271Fan SpeedAI272Compressor UtilizationAI273Free Cooling Valve Open PositionAI274Reheat UtilizationAI275Humidifier UtilizationAI276Dehumidifier UtilizationAI277Free Cooling StatusAI278Return Air TemperatureAI279Return Air TemperatureAI280Supply Air TemperatureAI281Supply Air TemperatureAI282Supply Air Temperature Set PointAI283Supply Air Temperature Set PointAI284Free Cooling Fluid TemperatureAI285Free Cooling Fluid TemperatureAI286Ext Air Sensor A TemperatureAI287Ext Air Sensor A TemperatureAI288Ext Air Sensor B TemperatureAI289Ext Air Sensor B TemperatureAI290Ext Air Sensor C TemperatureAI291Ext Air Sensor C TemperatureAI292Dig Scroll Comp Discharge Temp 1AI293Dig Scroll Comp Discharge Temp 1AI294Dig Scroll Comp Discharge Temp 2AI295Dig Scroll Comp Discharge Temp 2AI296Return HumidityAI297Ext Air Sensor A HumidityAI298Ext Air Sensor B HumidityAI299Ext Air Sensor C HumidityAI300Fan HoursAI301Compressor Hours 1AI302Compressor Hours 2AI303Humidifier HoursAI304Dehumidifier HoursAI305Free Cooling Valve HoursAI306Electric Reheater Hours 1AI307Electric Reheater Hours 2AI308Electric Reheater Hours 3AI309Hot Water / Hot Gas Valve HoursAI310Today's High Air TemperatureAI311Today's High Air TemperatureAI312Today's Low Air TemperatureAI313Today's Low Air TemperatureAI314Today's High HumidityAI315Today's Low HumidityAI316Server ClassAI317Today's High Air Temperature TimeAI318Today's Low Air Temperature TimeAI319Supply Air Temperature Sensor ControlAI320Return Air Temperature Set PointAI321Return Air Temperature Set PointAI322Return Humidity Set PointAI323Today's High Humidity TimeAI324Today's Low Humidity TimeAI325Fixed Compressor State 1AI326Fixed Compressor State 2AI327Compressor Capacity Control State 1AI328Compressor Capacity Control State 2AI329Infrared Humidifier Flush RateAI330Fan Control ModeAI331Analog Input Reading 1AI332Analog Input Reading 2AI333Analog Input Reading 3AI334Analog Input Reading 4AI335System Control ModeAI336System Operating State ReasonAI337Maintenance RampAI338Calculated Next Maintenance MonthAI339Calculated Next Maintenance YearAI340Hot Water / Hot Gas Valve Open PositionAI341Maintenance Tracking StateAI342Customer Input 1 - Event ControlAI343Customer Input 1 - Event TypeAI344Customer Input 2 - Event ControlAI345Customer Input 2 - Event TypeAI346Customer Input 3 - Event ControlAI347Customer Input 3 - Event TypeAI348Customer Input 4 - Event ControlAI349Customer Input 4 - Event TypeAI350Ext Free Cooling Lockout – Event ControlAI351Ext Free Cooling Lockout – Event TypeAI352Ext Condenser Pump High Water - Event ControlAI353Ext Condenser Pump High Water - Event TypeAI354Ext Standby Glycol Pump On - Event ControlAI355Ext Standby Glycol Pump On - vent TypeAI356Ext Standby Unit On - Event ControlAI357Ext Standby Unit On - Event TypeAI358Ext Humidifier Lockout – Event ControlAI359Ext Humidifier Lockout - Event TypeAI360Ext Loss of Flow - Event ControlAI361Ext Loss of Flow - Event TypeAI362Ext Over Temperature – Event ControlAI363Ext Over Temperature - Event TypeAI364Ext Reheat Lockout - Event ControlAI365Ext Reheat Lockout - Event TypeAI366High Power Shutdown – Event ControlAI367High Power Shutdown - Event TypeAI368Humidifier Issue - Event ControlAI369Humidifier Issue - Event TypeAI370Master Unit Communication Lost - Event ControlAI371Master Unit Communication Lost - Event TypeAI372Service Required - Event ControlAI373Service Required - Event TypeAI374Shutdown - Loss Of Power – Event ControlAI375Shutdown - Loss Of Power – Event TypeAI376Smoke Detected - Event ControlAI377Smoke Detected - Event TypeAI378Water Under Floor - Event ControlAI379Water Under Floor - Event TypeAI380Ext Compressor Lockout – Event ControlAI381Ext Compressor Lockout – Event TypeAI382Clogged Air Filter - Event ControlAI383Clogged Air Filter - Event TypeAI384Ext Loss of Air Blower – Event ControlAI385Ext Loss of Air Blower - Event TypeAI386Compressor High Head Pressure - Event Control 1AI387Compressor High Head Pressure - Event Control 2AI388Compressor High Head Pressure - Event Type 1AI389Compressor High Head Pressure - Event Type 2AI390Compressor Low Suction Pressure - Event Control 1AI391Compressor Low Suction Pressure - Event Control 2AI392Compressor Low Suction Pressure - Event Type 1AI393Compressor Low Suction Pressure - Event Type 2AI394Compressor Pump Down Issue - Event Control 1AI395Compressor Pump Down Issue - Event Control 2AI396Compressor Pump Down Issue - Event Type 1AI397Compressor Pump Down Issue - Event Type 2AI398Compressor Short Cycle – Event Control 1AI399Compressor Short Cycle – Event Control 2AI400Compressor Short Cycle – Event Type 1AI401Compressor Short Cycle – Event Type 2AI402Compressor Thermal Overload - Event Control 1AI403Compressor Thermal Overload - Event Control 2AI404Compressor Thermal Overload - Event Type 1AI405Compressor Thermal Overload - Event Type 2AI406Dig Scroll Comp Discharge Over Temp - Event Ctrl 1AI407Dig Scroll Comp Discharge Over Temp - Event Ctrl 2AI408Dig Scroll Comp Discharge Over Temp - Event Type 1AI409Dig Scroll Comp Discharge Over Temp - Event Type 2AI410Ext Air Sensor A High Humidity - Event ControlAI411Ext Air Sensor A High Humidity - Event TypeAI412Ext Air Sensor A Low Humidity - Event ControlAI413Ext Air Sensor A Low Humidity - Event TypeAI414Ext Air Sensor A Over Temp – Event ControlAI415Ext Air Sensor A Over Temp – Event TypeAI416Ext Air Sensor A Under Temp - Event ControlAI417Ext Air Sensor A Under Temp - Event TypeAI418High Return Humidity – Event ControlAI419High Return Humidity - Event TypeAI420Low Return Humidity - Event ControlAI421Low Return Humidity - Event TypeAI422Return Air Over Temp – Event ControlAI423Return Air Over Temp - Event TypeAI424Return Air Under Temp – Event ControlAI425Return Air Under Temp - Event TypeAI426Fan Hours Exceeded – Event ControlAI427Fan Hours Exceeded - Event TypeAI428Fan Issue - Event ControlAI429Fan Issue - Event TypeAI430Main Fan Overload - Event ControlAI431Main Fan Overload - Event TypeAI432Condenser Issue - Event Control 1AI433Condenser Issue - Event Control 2AI434Condenser Issue - Event Type 1AI435Condenser Issue - Event Type 2AI436System Event Acknowledge/ResetAI437Air Temperature Control SensorAI438Supply Air Over Temp ThresholdAI439Supply Air Over Temp ThresholdAI440Supply Air Under Temp ThresholdAI441Supply Air Under Temp ThresholdAI442Outside Air TemperatureAI443Outside Air TemperatureAI444Humidity Proportional Control TypeAI445Ext Air Sensor A Dew Point TempAI446Ext Air Sensor A Dew Point TempAI447Ext Dew Point Over Temp ThresholdAI448Ext Dew Point Over Temp ThresholdAI449Ext Dew Point Under Temp ThresholdAI450Ext Dew Point Under Temp ThresholdAI451Compressor LockoutAI452Main Chilled Water ValveAI453Reheater LockoutAI454Humidifier LockoutAI455Fan Control SensorAI456Fan Speed Minimum Set PointAI457Fan Speed Temperature Set PointAI458Fan Speed Temperature Set PointAI459Standby UnitsAI460Adjusted HumidityAI461eturn Dew PointAI462Return Dew PointAI463Actual Air Temperature Set PointAI464Actual Air Temperature Set PointAI465Actual Humidity Set PointAI466Dew Point Set PointAI467Dew Point Set PointAI468Supply Air Over/Under Temperature - Event ControlAI469Remote Sensor Over Temp ThresholdAI470Remote Sensor Over Temp ThresholdAI471Remote Sensor Under Temp ThresholdAI472Remote Sensor Under Temp ThresholdAI473Remote Sensor Average TemperatureAI474Remote Sensor Average TemperatureAI475Remote Sensor Maximum TemperatureAI476Remote Sensor Maximum TemperatureAI477Remote Sensor System Average TemperatureAI478Remote Sensor System Average TemperatureAI479Remote Sensor System Maximum TemperatureAI480Remote Sensor System Maximum TemperatureAI481Remote Sensor Temperature 1AI482Remote Sensor Temperature 1AI483Remote Sensor Temperature 2AI484Remote Sensor Temperature 2AI485Remote Sensor Temperature 3AI486Remote Sensor Temperature 3AI487Remote Sensor Temperature 4AI488Remote Sensor Temperature 4AI489Remote Sensor Temperature 5AI490Remote Sensor Temperature 5AI491Remote Sensor Temperature 6AI492Remote Sensor Temperature 6AI493Remote Sensor Temperature 7AI494Remote Sensor Temperature 7AI495Remote Sensor Temperature 8AI496Remote Sensor Temperature 8AI497Remote Sensor Temperature 9AI498Remote Sensor Temperature 9AI499Remote Sensor Temperature 10AI500Remote Sensor Temperature 10AI501Air Economizer AvailabilityAI502Air Economizer Control SourceAI503Chilled Water Valve HoursAI504Cooling CapacityAI505Cooling Control TemperatureAI506Cooling Control TemperatureAI507Fan Speed Control TemperatureAI508Fan Speed Control TemperatureAI509Free Cooling Internal Control ModeAI510Humidity Control SensorAI511Digital Scroll Compressor Loading 1AI512Digital Scroll Compressor Loading 2AI513Static Pressure Set PointAI514Unit Static PressureAI515System Static PressureAI516Condenser Low Noise Mode StateAI517Condenser Low Noise Mode Schedule ControlAI518Condenser Low Noise Mode Max Fan SpeedAI519Condenser Normal Mode Max Fan SpeedAI520Condenser Low Noise Mode - Interval DaysAI521Condenser Low Noise Mode – Full DaysAI522Condenser Low Noise Mode Start TimeAI523Condenser Low Noise Mode Stop TimeAI524Pump Hours 1AI525Pump Hours 2AI526System Input RMS A-N 1AI527System Input RMS A-N 2AI528System Input RMS A-N 3AI529System Input RMS A-N 4AI530System Input RMS A-N 5AI531System Input RMS A-N 6AI532System Input RMS B-N 1AI533System Input RMS B-N 2AI534System Input RMS B-N 3AI535System Input RMS B-N 4AI536System Input RMS B-N 5AI537System Input RMS B-N 6AI538System Input RMS C-N 1AI539System Input RMS C-N 2AI540System Input RMS C-N 3AI541System Input RMS C-N 4AI542System Input RMS C-N 5AI543System Input RMS C-N 6AI544System Input RMS Current Phase A 1AI545System Input RMS Current Phase A 2AI546System Input RMS Current Phase A 3AI547System Input RMS Current Phase A 4AI548System Input RMS Current Phase A 5AI549System Input RMS Current Phase A 6AI550System Input RMS Current Phase B 1AI551System Input RMS Current Phase B 2AI552System Input RMS Current Phase B 3AI553System Input RMS Current Phase B 4AI554System Input RMS Current Phase B 5AI555System Input RMS Current Phase B 6AI556System Input RMS Current Phase C 1AI557System Input RMS Current Phase C 2AI558System Input RMS Current Phase C 3AI559System Input RMS Current Phase C 4AI560System Input RMS Current Phase C 5AI561System Input RMS Current Phase C 6AI562Energy Consumption 1AI563Energy Consumption 2AI564Energy Consumption 3AI565Energy Consumption 4AI566Energy Consumption 5AI567Energy Consumption 6AI568Fluid Input Temperature 1AI569Fluid Input Temperature 2AI570Fluid Input Temperature 1AI571Fluid Input Temperature 2AI572Fluid Output Temperature 1AI573Fluid Output Temperature 2AI574Fluid Output Temperature 1AI575Fluid Output Temperature 2AI576Fluid Flow Rate 1AI577Fluid Flow Rate 2AI578Unit Cooling LoadAI579Circuit Cooling Load 1AI580Circuit Cooling Load 2AI581Instantaneous Power 1AI582Instantaneous Power 2AI583Instantaneous Power 3AI584Instantaneous Power 4AI585Instantaneous Power 5AI586Instantaneous Power 6AI587Raw Auxiliary Air TemperatureAI588Raw Auxiliary Air TemperatureAI589Actual Auxiliary Air TemperatureAI590Actual Auxiliary Air TemperatureAI591System Input RMS A-B 1AI592System Input RMS A-B 2AI593System Input RMS A-B 3AI594System Input RMS A-B 4AI595System Input RMS A-B 5AI596System Input RMS A-B 6AI597System Input RMS B-C 1AI598System Input RMS B-C 2AI599System Input RMS B-C 3AI600System Input RMS B-C 4AI601System Input RMS B-C 5AI602System Input RMS B-C 6AI603System Input RMS C-A 1AI604System Input RMS C-A 2AI605System Input RMS C-A 3AI606System Input RMS C-A 4AI607System Input RMS C-A 5AI608System Input RMS C-A 6AI609Pump State 1AI610Pump State 2AI611Expected Condenser Unit CountAI612Condenser Refrigerant TypeAI613Condenser Fan Reversal Requested 1AI614Condenser Fan Reversal Requested 2AI615Condenser Outside Air Temperature 1AI616Condenser Outside Air Temperature 2AI617Condenser Outside Air Temperature 2AI618Condenser Outside Air Temperature 2AI619Condenser Refrigerant Pressure 1AI620Condenser Refrigerant Pressure 2AI621Condenser Supply Refrigerant Temperature 1AI622Condenser Supply Refrigerant Temperature 1AI623Condenser Supply Refrigerant Temperature 2AI624Condenser Supply Refrigerant Temperature 2AI625Condenser Fan Speed 1AI626Condenser Fan Speed 2AI627Condenser Fan Speed 3AI628Condenser Fan Speed 4AI629Condenser Fan Speed 5AI630Condenser Fan Speed 6AI631Condenser Fan Speed 7AI632Condenser Fan Speed 8AI633Condenser Fan Power 1AI634Condenser Fan Power 2AI635Condenser Fan Power 3AI636Condenser Fan Power 4AI637Condenser Fan Power 5AI638Condenser Fan Power 6AI639Condenser Fan Power 7AI640Condenser Fan Power 8AI641System Date and Time
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Liebert_ICOM_V4_Table_6_and_8_a_LX.csv; the profile maps the registers in the Liebert iCOM Modbus tables 6 and 8 (https://www.ccontrols.com/support/dp/LiebertIntelliSlot.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- None of the 641 rows is flagged for polling in the profile as published; tick the points you need in the gateway before any object is served. Each object's description says it is not polled by default.
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Free Cooling Internal Control Mode; Humidity Proportional Control Type; Supply Air Temperature Set Point...); they are kept as printed and told apart by instance.
- Temperature values come in pairs (°F and °C) with the same name; the units column tells them apart.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
How many BACnet points does the Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX have?
This list has 641 BACnet objects: 418 analog inputs, 223 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Liebert_ICOM_V4_Table_6_and_8_a (Liebert_ICOM_V4_Table_6_and_8_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Liebert_ICOM_V4_Table_6_and_8_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX?
Start with BI 99 Unit On (Unit on); BI 8 Fan State (Fan running); BI 9 Cooling State (Cooling active); AI 278 Return Air Temperature (Return air temperature); AI 296 Return Humidity (Return humidity); AI 280 Supply Air Temperature (Supply air temperature); AI 233 Air Temperature Set Point (Air temperature setpoint); AI 240 Humidity Set Point (Humidity setpoint); BI 41 Return Air Over Temperature (Return air over temperature); BI 64 Unit Communication Lost (Unit communication lost).
How do I check these points on the real Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Liebert_ICOM_V4_Table_6_and_8_a · Liebert_ICOM_V4_Table_6_and_8_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.