Precision cooling unit (ceiling split) · BACnet points list

Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Liebert Mini-Mate2: 45 objects (25 AO, 20 BO), all polled. Every register is mapped as an output: status values (temperature, humidity, cooling, heating, capacity, unit on/off), alarm bits, run hours, setpoints and alarm limits, plus the remote on/off and control setpoint registers.

This page lists 45 BACnet objects for the Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX — 45 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Liebert Mini-Mate2 via BASgatewayLX
Equipment
Precision cooling unit (ceiling split)
Equipment type
VRF & split air conditioners
BACnet objects
45 (45 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Mini-Mate2, Mini Mate 2, Liebert MiniMate
Source document
BASgatewayLX Modbus device profile Liebert_Mini_Mate_2 · Liebert_Mini_Mate_2_LX.csv
Download CSV 45 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX

Integration in brief

Use Control Remote On/Off and the control temperature/humidity setpoints; read the status values and alarm bits (they are outputs here but should be treated as read-only).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 40Control Remote OnRemote on commandCommand
BO 41Control Remote OffRemote off commandCommand
AO 42Control Temperature SetpointTemperature setpoint (control)Command
AO 44Control Humidity SetpointHumidity setpoint (control)Command
AO 10Status Unit On/OffUnit on/off statusCommand
AO 1Status TemperatureUnit temperature readingCommand
AO 2Status HumidityUnit humidity readingCommand
AO 9Status % CapacityCapacity, %Command
BO 18Alarm High TemperatureHigh temperature alarmCommand
BO 15Alarm Loss of AirflowLoss of airflow alarmCommand

Network setup

Watch out for

Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

45 of 45 shown
Type
AnalogBinary
Show
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX BACnet Points List
DescriptionStates
AOmin1Status TemperatureModbus 400001°FCommand
AOmin2Status HumidityModbus 400002%Command
AO3Status CoolingModbus 400003Command
AO4Status HeatingModbus 400004Command
AO5Status HumidificationModbus 400005Command
AO6Status DehumidificationModbus 400006Command
AO7Status Econ-o-CycleModbus 400007Command
AO8Status StagesModbus 400008Command
AOmin9Status % CapacityModbus 400009Command
AOmin10Status Unit On/OffModbus 400018Command
BO11Alarm CommunicationsModbus 400289 bit 0Command
BO12Alarm Local OffModbus 400289 bit 1Command
BO13Alarm Remote OffModbus 400289 bit 2Command
BO14Alarm High Head Pressure 1Modbus 400289 bit 3Command
BOmin15Alarm Loss of AirflowModbus 400289 bit 5Command
BO16Alarm Standby Glycol Unit OnModbus 400289 bit 6Command
BO17Alarm Change FiltersModbus 400289 bit 7Command
BOmin18Alarm High TemperatureModbus 400289 bit 8Command
BO19Alarm Low TemperatureModbus 400289 bit 9Command
BO20Alarm High HumidityModbus 400290 bit 0Command
BO21Alarm Low HumidityModbus 400290 bit 1Command
BO22Alarm Humidifier ProblemModbus 400290 bit 2Command
BO23Alarm Smoke DetectedModbus 400290 bit 8Command
BO24Alarm Loss of Water FlowModbus 400290 bit 9Command
BO25Alarm Standby Unit OnModbus 400290 bit 10Command
BO26Alarm Short CycleModbus 400291 bit 1Command
BO27Alarm Loss of PowerModbus 400291 bit 2Command
BO28Alarm Local Alarm 1Modbus 400291 bit 6Command
AO29Run Hours Compressor 1Modbus 400019hCommand
AO30Run Hours Fan MotorModbus 400020hCommand
AO31Run Hours HumidifierModbus 400021hCommand
AO32Setpoints TemperatureModbus 400010°FCommand
AO33Setpoints Temp ToleranceModbus 400011°FCommand
AO34Setpoints HumidityModbus 400012%Command
AO35Setpoints Humidity ToleranceModbus 400013%Command
AO36Setpoints High Temperature AlarmModbus 400014°FCommand
AO37Setpoints Low Temperature AlarmModbus 400015°FCommand
AO38Setpoints High Humidity AlarmModbus 400016%Command
AO39Setpoints Low Humidity AlarmModbus 400017%Command
BOmin40Control Remote OnModbus 400349 bit 0Command
BOmin41Control Remote OffModbus 400349 bit 1Command
AOmin42Control Temperature SetpointModbus 400350°FCommand
AO43Control Temperature ToleranceModbus 400350°FCommand
AOmin44Control Humidity SetpointModbus 400351%Command
AO45Control Humidity ToleranceModbus 400351%Command
Object ID lookup: Contemporary Controls BASgatewayLX Liebert Mini-Mate2 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Liebert Mini-Mate2 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX

How many BACnet points does the Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX have?

This list has 45 BACnet objects: 25 analog outputs, 20 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX BACnet points are writable?

45 of the 45 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Liebert_Mini_Mate_2 (Liebert_Mini_Mate_2_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Liebert_Mini_Mate_2_LX.csv.

What are the minimum BACnet points to integrate the Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX?

Start with BO 40 Control Remote On (Remote on command); BO 41 Control Remote Off (Remote off command); AO 42 Control Temperature Setpoint (Temperature setpoint (control)); AO 44 Control Humidity Setpoint (Humidity setpoint (control)); AO 10 Status Unit On/Off (Unit on/off status); AO 1 Status Temperature (Unit temperature reading); AO 2 Status Humidity (Unit humidity reading); AO 9 Status % Capacity (Capacity, %); BO 18 Alarm High Temperature (High temperature alarm); BO 15 Alarm Loss of Airflow (Loss of airflow alarm).

How do I check these points on the real Liebert Mini-Mate2 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.