Easy BACnet
  1. Home
  2. BACnet points lists
  3. Contemporary Controls
  4. E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX

Pulse meter data recorder (meter interface) · BACnet points list

Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the E-Mon IDR-8/IDR-16: 64 objects (32 AI, 32 AO), all polled. For each of 16 channels it has usage (pulse count) and pulse value as outputs and demand and demand pulse value as inputs. Channels 9-16 apply to the IDR-16 only.

This page lists 64 BACnet objects for the Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
Equipment
Pulse meter data recorder (meter interface)
Equipment type
Thermostats, sensors & meters
BACnet objects
64 (32 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder
Source document
BASgatewayLX Modbus device profile E_Mon_D_Mon_IDPR8_IDPR16_a · E_Mon_D_Mon_IDR8_IDR16_a_LX.csv
Download CSV 64 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX

Integration in brief

Map channel 1 usage (pulses), channel 1 demand and channel 1 pulse value first. Outputs in this profile change stored values or settings, so write them only on purpose.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1Usage Channel 1-PulseChannel 1 usage (pulses)Command
AI 33Demand Channel 1-DemandChannel 1 demandRead
AO 17Usage Channel 1-Pulse-Pulse ValueChannel 1 pulse valueCommand
AO 2Usage Channel 2-PulseChannel 2 usage (pulses)Command
AI 34Demand Channel 2-DemandChannel 2 demandRead

Network setup

Watch out for

Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

64 of 64 shown
Type
Access
Show
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX BACnet Points List
DescriptionStates
AOmin1Usage Channel 1-PulseModbus 400001Command
AOmin2Usage Channel 2-PulseModbus 400003Command
AO3Usage Channel 3-PulseModbus 400005Command
AO4Usage Channel 4-PulseModbus 400007Command
AO5Usage Channel 5-PulseModbus 400009Command
AO6Usage Channel 6-PulseModbus 400011Command
AO7Usage Channel 7-PulseModbus 400013Command
AO8Usage Channel 8-PulseModbus 400015Command
AO9Usage Channel 9-PulseModbus 400017Command
AO10Usage Channel 10_PulseModbus 400019Command
AO11Usage Channel 11-PulseModbus 400021Command
AO12Usage Channel 12-PulseModbus 400023Command
AO13Usage Channel 13-PulseModbus 400025Command
AO14Usage Channel 14-PulseModbus 400027Command
AO15Usage Channel 15-PulseModbus 400029Command
AO16Usage Channel 16-PulseModbus 400031Command
AOmin17Usage Channel 1-Pulse-Pulse ValueModbus 401001Command
AO18Usage Channel 2-Pulse-Pulse ValueModbus 401003Command
AO19Usage Channel 3-Pulse-Pulse ValueModbus 401005Command
AO20Usage Channel 4-Pulse-Pulse ValueModbus 401007Command
AO21Usage Channel 5-Pulse-Pulse ValueModbus 401009Command
AO22Usage Channel 6-Pulse-Pulse ValueModbus 401011Command
AO23Usage Channel 7-Pulse-Pulse ValueModbus 401013Command
AO24Usage Channel 8-Pulse-Pulse ValueModbus 401015Command
AO25Usage Channel 9-Pulse-Pulse ValueModbus 401017Command
AO26Usage Channel 10-Pulse-Pulse ValueModbus 401019Command
AO27Usage Channel 11-Pulse-Pulse ValueModbus 401021Command
AO28Usage Channel 12-Pulse-Pulse ValueModbus 401023Command
AO29Usage Channel 13-Pulse-Pulse ValueModbus 401025Command
AO30Usage Channel 14-Pulse-Pulse ValueModbus 401027Command
AO31Usage Channel 15-Pulse-Pulse ValueModbus 401029Command
AO32Usage Channel 16-Pulse-Pulse ValueModbus 401031Command
AImin33Demand Channel 1-DemandModbus 400065Read
AImin34Demand Channel 2-DemandModbus 400067Read
AI35Demand Channel 3-DemandModbus 400069Read
AI36Demand Channel 4-DemandModbus 400071Read
AI37Demand Channel 5-DemandModbus 400073Read
AI38Demand Channel 6-DemandModbus 400075Read
AI39Demand Channel 7-DemandModbus 400077Read
AI40Demand Channel 8-DemandModbus 400079Read
AI41Demand Channel 9-DemandModbus 400081Read
AI42Demand Channel 10-DemandModbus 400083Read
AI43Demand Channel 11-DemandModbus 400085Read
AI44Demand Channel 12-DemandModbus 400087Read
AI45Demand Channel 13-DemandModbus 400089Read
AI46Demand Channel 14-DemandModbus 400091Read
AI47Demand Channel 15-DemandModbus 400093Read
AI48Demand Channel 16-DemandModbus 400095Read
AI49Demand Channel 1-Demand-Pulse ValueModbus 401065Read
AI50Demand Channel 2-Demand-Pulse ValueModbus 401067Read
AI51Demand Channel 3-Demand-Pulse ValueModbus 401069Read
AI52Demand Channel 4-Demand-Pulse ValueModbus 401071Read
AI53Demand Channel 5-Demand-Pulse ValueModbus 401073Read
AI54Demand Channel 6-Demand-Pulse ValueModbus 401075Read
AI55Demand Channel 7-Demand-Pulse ValueModbus 401077Read
AI56Demand Channel 8-Demand-Pulse ValueModbus 401079Read
AI57Demand Channel 9-Demand-Pulse ValueModbus 401081Read
AI58Demand Channel 10-Demand-Pulse ValueModbus 401083Read
AI59Demand Channel 11-Demand-Pulse ValueModbus 401085Read
AI60Demand Channel 12-Demand-Pulse ValueModbus 401087Read
AI61Demand Channel 13-Demand-Pulse ValueModbus 401089Read
AI62Demand Channel 14-Demand-Pulse ValueModbus 401091Read
AI63Demand Channel 15-Demand-Pulse ValueModbus 401093Read
AI64Demand Channel 16-Demand-Pulse ValueModbus 401095Read
Object ID lookup: Contemporary Controls BASgatewayLX E-Mon IDR-8/IDR-16 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX

How many BACnet points does the Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX have?

This list has 64 BACnet objects: 32 analog inputs, 32 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX BACnet points are writable?

32 of the 64 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile E_Mon_D_Mon_IDPR8_IDPR16_a (E_Mon_D_Mon_IDR8_IDR16_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/E_Mon_d_Mon_IDR8_IDR16.zip.

What are the minimum BACnet points to integrate the Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX?

Start with AO 1 Usage Channel 1-Pulse (Channel 1 usage (pulses)); AI 33 Demand Channel 1-Demand (Channel 1 demand); AO 17 Usage Channel 1-Pulse-Pulse Value (Channel 1 pulse value); AO 2 Usage Channel 2-Pulse (Channel 2 usage (pulses)); AI 34 Demand Channel 2-Demand (Channel 2 demand).

How do I check these points on the real E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile E_Mon_D_Mon_IDPR8_IDPR16_a · E_Mon_D_Mon_IDR8_IDR16_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.