Flow meter (steam / liquid / gas) · BACnet points list

Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Spirax Sarco RIM10: 49 Analog Inputs, all polled. It reads relay states, flow direction, resettable and non-resettable totalizers, temperatures, turbine frequency, velocity, volume, corrected volume, mass and energy flow, density, viscosity, pressure, 4-20 mA inputs/outputs and enthalpy, with min/max records.

This page lists 49 BACnet objects for the Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Spirax Sarco RIM10 flowmeter via BASgatewayLX
Equipment
Flow meter (steam / liquid / gas)
Equipment type
Thermostats, sensors & meters
BACnet objects
49 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
RIM10, RIM 10, Spirax Sarco RIM10 Modbus
Source document
BASgatewayLX Modbus device profile SpiraxSarco_RIM10_Flowmeter_a · SpiraxSarco_RIM10_Flowmeter_a_LX.csv
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX

Integration in brief

Map mass flow, volume flow and energy flow first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 23Mass flow lb/minMass flowRead
AI 21Volume flow cu ft/secVolume flowRead
AI 24Energy flow Btu/minEnergy flowRead
AI 27Pressure psigPressureRead
AI 11Temperature input #1 °FTemperature input 1Read
AI 6Non-resettable totalizer #1Non-resettable totalizer 1Read

Network setup

Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

49 of 49 shown
Type
Analog
Show
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX BACnet Points List
DescriptionStates
AI1Relay output status 1 = on/closedModbus 412401Read
AI2Relay output status 1 = on/closedModbus 412402Read
AI3Flow direction input 0 = Fwd 1 = RevModbus 412404Read
AI4Resettable totalizer #1Modbus 420624Read
AI5Resettable Totalizer #1 remainder countModbus 441083Read
AImin6Non-resettable totalizer #1Modbus 420626Read
AI7Resettable totalizer #2Modbus 420628Read
AI8Resettable Totalizer #2 remainder countModbus 441087Read
AI9Non-resettable totalizer #2Modbus 420630Read
AI10Pipe diameter inchesModbus 440003inRead
AImin11Temperature input #1 °FModbus 440985°FRead
AI12Minimum temperature input 1 recorded °FModbus 441055°FRead
AI13Maximum temperature input 1 recorded °FModbus 441069°FRead
AI14Temperature input #2 °FModbus 440987°FRead
AI15Temperature internal RTD °FModbus 440989°FRead
AI16Minimum temperature input 2recorded °FModbus 441057°FRead
AI17Maximum temperature input 2recorded °FModbus 441071°FRead
AI18Temperature difference between T1 and T2Modbus 440991°FRead
AI19Frequency input from turbineModbus 440997HzRead
AI20Line velocity value ft/secModbus 441001ft/sRead
AImin21Volume flow cu ft/secModbus 441005m³/sRead
AI22Temperature compensated vol flow cfmModbus 441007cfmRead
AImin23Mass flow lb/minModbus 441009lb/minRead
AImin24Energy flow Btu/minModbus 441011Read
AI25Density lb/cu ftModbus 441019Read
AI26Fluid viscosity centipoiseModbus 441031Read
AImin27Pressure psigModbus 440993Read
AI28Min pressure recorded psigModbus 441059Read
AI29Max pressure recorded psigModbus 441073Read
AI304-20 mA input current channel 1 mAModbus 440979mARead
AI314-20 mA input current channel 2 mAModbus 440981mARead
AI324-20 mA input current channel 3 mAModbus 440983mARead
AI334-20 mA output current channel 1 mAModbus 441013mARead
AI344-20 mA output current channel 2 mAModbus 441015mARead
AI354-20 mA output current channel 3 mAModbus 441017mARead
AI36Water or Steam enthalpy temp input 1 Btu/lbModbus 441023Btu/lbRead
AI37Water or Steam enthalpy temp input 2 Btu/lbModbus 441025Btu/lbRead
AI38Minimum recorded energy flow Btu/minModbus 441067Read
AI39Maximum recorded energy flow Btu/minModbus 441081Read
AI40SupercompressibilityModbus 441027Read
AI41CompressibilityModbus 441029Read
AI42Fluid velocity converted to user-selected unitsModbus 441039Read
AI43Fluid volume converted to user-selected unitsModbus 441041Read
AI44Fluid mass flow converted to user-selected unitsModbus 441043Read
AI45Fluid energy converted to user-selected unitsModbus 441045Read
AI46Temperature input 1 converted to user-selected unitsModbus 441047Read
AI47Temperature input 2 converted to user-selected unitsModbus 441049Read
AI48Pressure converted to user-selected unitsModbus 441051Read
AI49Density converted to user-selected unitsModbus 441053Read
Object ID lookup: Contemporary Controls BASgatewayLX Spirax Sarco RIM10 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Spirax Sarco RIM10 flowmeter via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX

How many BACnet points does the Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX have?

This list has 49 BACnet objects: 49 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile SpiraxSarco_RIM10_Flowmeter_a (SpiraxSarco_RIM10_Flowmeter_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/SpiraxSarco_RIM10_Flowmeter.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX?

Start with AI 23 Mass flow lb/min (Mass flow); AI 21 Volume flow cu ft/sec (Volume flow); AI 24 Energy flow Btu/min (Energy flow); AI 27 Pressure psig (Pressure); AI 11 Temperature input #1 °F (Temperature input 1); AI 6 Non-resettable totalizer #1 (Non-resettable totalizer 1).

How do I check these points on the real Spirax Sarco RIM10 flowmeter via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile SpiraxSarco_RIM10_Flowmeter_a · SpiraxSarco_RIM10_Flowmeter_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.