Energy recovery ventilator (heat recovery unit) · BACnet points list

Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for an ArgusVision heat recovery unit: 25 objects (8 AI, 15 AO, 2 BI), 22 polled by default. Outputs set Modbus master, supply and exhaust fan speeds, the temperature setpoint, filter time and a two-block weekly on/off schedule; inputs give device type, error and warning codes, indoor and outdoor sensors and the bypass valve relay.

This page lists 25 BACnet objects for the Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Equipment
Energy recovery ventilator (heat recovery unit)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
25 (15 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic
Source document
BASgatewayLX Modbus device profile HEAT_RECOVERY_UNIT__BASIC_a · HEAT_RECOVERY_UNIT__BASIC_a_LX.csv
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX

Integration in brief

Set Master is Modbus, write supply and exhaust fan speeds and the setpoint, then read indoor/outdoor temperatures, bypass state and the codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 8Master is ModbusModbus as master (BMS control)Command
AO 10Fan speed SupplySupply fan speedCommand
AO 9Fan speed ExhaustExhaust fan speedCommand
AO 11Setpoint FTemperature setpoint, °FCommand
AI 13Indoor sensor FIndoor temperature, °FRead
AI 15Outdoor sensor FOutdoor temperature, °FRead
AI 17Bypass Valve (relay)Bypass valve relayRead
AI 6Error CodeError codeRead
AI 7Warning CodeWarning codeRead

Enable & remote start

Master is Modbus (AO 8) hands control to the Modbus side; check the ArgusVision map for the value to write.

Network setup

Watch out for

Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

25 of 25 shown
Type
Binary
Access
Show
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX BACnet Points List
DescriptionStates
BI1Modbus Units C/FModbus 400101 bit 0Read
BI2Modbus Units BAR/PSIModbus 400101 bit 1Read
AI3Device typeModbus 400102Read
AO4StateModbus 400103Command
AO5StatusModbus 400104Command
AImin6Error CodeModbus 400105Read
AImin7Warning CodeModbus 400106Read
AOmin8Master is ModbusModbus 400107Command
AOmin9Fan speed ExhaustModbus 400108Command
AOmin10Fan speed SupplyModbus 400109Command
AOmin11Setpoint FModbus 400110°FCommand
AO12Setpoint CModbus 400110; not polled by default°CCommand
AImin13Indoor sensor FModbus 400111°FRead
AI14Indoor sensor CModbus 400111; not polled by default°CRead
AImin15Outdoor sensor FModbus 400112°FRead
AI16Outdoor sensor CModbus 400112; not polled by default°CRead
AImin17Bypass Valve (relay)Modbus 400113%Read
AO18Filter timeModbus 400114minCommand
AO19Set clock with on timeModbus 400115Command
AO20Block 1 or 2Modbus 400116Command
AO21Day 1-7Modbus 400117Command
AO22On time in hoursModbus 400118hCommand
AO23On time in minutesModbus 400119minCommand
AO24Off time in hoursModbus 400120hCommand
AO25Off time in minutesModbus 400121minCommand
Object ID lookup: Contemporary Controls BASgatewayLX ebm-papst HRU Basic point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX

How many BACnet points does the Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX have?

This list has 25 BACnet objects: 8 analog inputs, 15 analog outputs, 2 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX BACnet points are writable?

15 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile HEAT_RECOVERY_UNIT__BASIC_a (HEAT_RECOVERY_UNIT__BASIC_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/HeatRecoveryUnitBasic.zip.

What are the minimum BACnet points to integrate the Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX?

Start with AO 8 Master is Modbus (Modbus as master (BMS control)); AO 10 Fan speed Supply (Supply fan speed); AO 9 Fan speed Exhaust (Exhaust fan speed); AO 11 Setpoint F (Temperature setpoint, °F); AI 13 Indoor sensor F (Indoor temperature, °F); AI 15 Outdoor sensor F (Outdoor temperature, °F); AI 17 Bypass Valve (relay) (Bypass valve relay); AI 6 Error Code (Error code); AI 7 Warning Code (Warning code).

How do I enable BMS control of the Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX?

Master is Modbus (AO 8) hands control to the Modbus side; check the ArgusVision map for the value to write.

How do I check these points on the real ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile HEAT_RECOVERY_UNIT__BASIC_a · HEAT_RECOVERY_UNIT__BASIC_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.