Power and energy meter · BACnet points list

Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for an Eaton RS-485 PONI: 106 Analog Inputs, 44 polled by default. It reads primary status and cause, phase, ground and neutral currents, voltages, peak current demands, real/reactive/apparent power, power factors and frequency; energy registers are unpolled.

This page lists 106 BACnet objects for the Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
106 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI
Source document
BASgatewayLX Modbus device profile Eaton_RS485_PONI_LO_HI_b · Eaton_RS485_PONI_LO_HI_b_LX.csv
Download CSV 106 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX

Integration in brief

Map primary status and cause and 3-phase real power first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Primary StatusPrimary statusRead
AI 2Primary CausePrimary causeRead
AI 23Real 3 Phase PowerReal power, 3-phaseRead
AI 59Real Energy ForwardReal energy forwardRead
AI 12LL AverageAverage line-line voltageRead
AI 8Current AvgAverage currentRead
AI 26Power Factor Displacement 3 PhaseDisplacement power factorRead
AI 28FrequencyFrequencyRead

Network setup

Watch out for

Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

106 of 106 shown
Type
Analog
Show
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX BACnet Points List
DescriptionStates
AImin1Primary StatusModbus 404609Read
AImin2Primary CauseModbus 404610Read
AI3Current AModbus 404611ARead
AI4Current BModbus 404613ARead
AI5Current CModbus 404615ARead
AI6Current GModbus 404617ARead
AI7Current NModbus 404619ARead
AImin8Current AvgModbus 404621ARead
AI9Voltage ABModbus 404623VRead
AI10Voltage ACModbus 404625VRead
AI11Voltage CAModbus 404627VRead
AImin12LL AverageModbus 404629VRead
AI13Voltage ANModbus 404631VRead
AI14Voltage BNModbus 404633VRead
AI15Voltage CNModbus 404635VRead
AI16Voltage LNModbus 404637VRead
AI17Voltage NGModbus 404639VRead
AI18Peak Current Demand AModbus 404641ARead
AI19Peak Current Demand BModbus 404643ARead
AI20Peak Current Demand CModbus 404645ARead
AI21Peak Current Demand GModbus 404647ARead
AI22Peak Current Demand NModbus 404649ARead
AImin23Real 3 Phase PowerModbus 404651WRead
AI24Reactive 3 Phase PowerModbus 404653VARRead
AI25Apparent 3 Phase PowerModbus 404655VARead
AImin26Power Factor Displacement 3 PhaseModbus 404657Read
AI27Power Factor ApparentModbus 404659Read
AImin28FrequencyModbus 404661HzRead
AI29K-FactorModbus 404663; not polled by defaultRead
AI30THD FactorModbus 404665; not polled by defaultRead
AI31Power Phase AModbus 404667WRead
AI32Power Phase BModbus 404669WRead
AI33Power Phase CModbus 404671WRead
AI34Reactive Power Phase AModbus 404673VARRead
AI35Reactive Power Phase BModbus 404675VARRead
AI36Reactive Power Phase CModbus 404677VARRead
AI37Apparent Power Phase AModbus 404679VARead
AI38Apparent Power Phase BModbus 404681VARead
AI39Apparent Power Phase CModbus 404683VARead
AI40Power Factor Displacement AModbus 404685Read
AI41Power Factor Displacement BModbus 404687Read
AI42Power Factor Displacement CModbus 404689Read
AI43Power Factor Apparent AModbus 404691Read
AI44Power Factor Apparent BModbus 404693Read
AI45Power Factor Apparent CModbus 404695Read
AI46Power Peak DemandModbus 404697WRead
AI47Source 1 Voltage ABModbus 404699; not polled by defaultVRead
AI48Source 1 Voltage BCModbus 404701; not polled by defaultVRead
AI49Source 1 Voltage CAModbus 404703; not polled by defaultVRead
AI50Source 1 FrequencyModbus 404705; not polled by defaultHzRead
AI51Source 2 Voltage ABModbus 404707; not polled by defaultVRead
AI52Source 2 Voltage BCModbus 404709; not polled by defaultVRead
AI53Source 2 Voltage CAModbus 404711; not polled by defaultVRead
AI54Source 2 FrequencyModbus 404713; not polled by defaultHzRead
AI55Power Real 3 PhaseModbus 404715; not polled by defaultWRead
AI56Power FactorModbus 404717; not polled by defaultPFRead
AI57Product IDModbus 404719; not polled by defaultRead
AI58FrequencyModbus 404721; not polled by defaultHzRead
AImin59Real Energy ForwardModbus 404723; not polled by defaultkWhRead
AI60Real Energy ReverseModbus 404725; not polled by defaultkWhRead
AI61Reactive Energy Net - KWhModbus 404727; not polled by defaultkWhRead
AI62Reactive Energy Lead - KVARhModbus 404729; not polled by defaultkVARhRead
AI63Reactive Energy Lag - KVARhModbus 404731; not polled by defaultkVARhRead
AI64Reactive Energy Net - KVARhModbus 404733; not polled by defaultkVARhRead
AI65Energy ApparentModbus 404735; not polled by defaultkVARhRead
AI66Motor Phase UnbalanceModbus 404737; not polled by default%Read
AI67Motor Thermal CapacityModbus 404739; not polled by default%Read
AI68Temperature Winding 1Modbus 404741; not polled by default°CRead
AI69Temperature Winding 2Modbus 404743; not polled by default°CRead
AI70Temperature Winding 3Modbus 404745; not polled by default°CRead
AI71Temperature Winding 4Modbus 404747; not polled by default°CRead
AI72Temperature Winding 5Modbus 404749; not polled by default°CRead
AI73Temperature Winding 6Modbus 404751; not polled by default°CRead
AI74Temperature Motor Bearing 1Modbus 404753; not polled by default°CRead
AI75Temperature Motor Bearing 2Modbus 404755; not polled by default°CRead
AI76Temperature Load Bearing 1Modbus 404757; not polled by default°CRead
AI77Temperature Load Bearing 2Modbus 404759; not polled by default°CRead
AI78Teperatur AuxiliaryModbus 404761; not polled by default°CRead
AI79Real Energy Forward Register 3Modbus 406305; not polled by defaultRead
AI80Real Energy Forward Register 2Modbus 406306; not polled by defaultRead
AI81Real Energy Forward Register 1Modbus 406307; not polled by defaultRead
AI82Real Energy Forward Register 0Modbus 406308; not polled by defaultRead
AI83Real Energy Reverse Register 3Modbus 406309; not polled by defaultRead
AI84Real Energy Reverse Register 2Modbus 406310; not polled by defaultRead
AI85Real Energy Reverse Register 1Modbus 406311; not polled by defaultRead
AI86Real Energy Reverse Register 0Modbus 406312; not polled by defaultRead
AI87Real Energy Net Register 3Modbus 406313; not polled by defaultRead
AI88Real Energy Net Register 2Modbus 406314; not polled by defaultRead
AI89Real Energy Net Register 1Modbus 406315; not polled by defaultRead
AI90Real Energy Net Register 0Modbus 406316; not polled by defaultRead
AI91Reactive Energy Lead Register 3Modbus 406317; not polled by defaultRead
AI92Reactive Energy Lead Register 2Modbus 406318; not polled by defaultRead
AI93Reactive Energy Lead Register 1Modbus 406319; not polled by defaultRead
AI94Reactive Energy Lead Register 0Modbus 406320; not polled by defaultRead
AI95Reactive Energy Lag Register 3Modbus 406321; not polled by defaultRead
AI96Reactive Energy Lag Register 2Modbus 406322; not polled by defaultRead
AI97Reactive Energy Lag Register 1Modbus 406323; not polled by defaultRead
AI98Reactive Energy Lag Register 0Modbus 406324; not polled by defaultRead
AI99Reactive Energy Net Register 3Modbus 406325; not polled by defaultRead
AI100Reactive Energy Net Register 2Modbus 406326; not polled by defaultRead
AI101Reactive Energy Net Register 1Modbus 406327; not polled by defaultRead
AI102Reactive Energy Net Register 0Modbus 406328; not polled by defaultRead
AI103Apparent Energy Register 3Modbus 406329; not polled by defaultRead
AI104Apparent Energy Register 2Modbus 406330; not polled by defaultRead
AI105Apparent Energy Register 1Modbus 406331; not polled by defaultRead
AI106Apparent Energy Register 0Modbus 406332; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX Eaton RS485 PONI point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX

How many BACnet points does the Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX have?

This list has 106 BACnet objects: 106 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Eaton_RS485_PONI_LO_HI_b (Eaton_RS485_PONI_LO_HI_b_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Eaton_RS485_PONI_LO_HI_b_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX?

Start with AI 1 Primary Status (Primary status); AI 2 Primary Cause (Primary cause); AI 23 Real 3 Phase Power (Real power, 3-phase); AI 59 Real Energy Forward (Real energy forward); AI 12 LL Average (Average line-line voltage); AI 8 Current Avg (Average current); AI 26 Power Factor Displacement 3 Phase (Displacement power factor); AI 28 Frequency (Frequency).

How do I check these points on the real Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Eaton_RS485_PONI_LO_HI_b · Eaton_RS485_PONI_LO_HI_b_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.