Variable frequency drive (HVAC) · BACnet points list

Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Danfoss FC 102: 97 objects (65 AI, 32 BI), 94 polled by default. It reads the control and status words (with each status bit split out as a Binary Input), references, power, voltage, current, frequency, temperatures, I/O states and the alarm, warning and extended status words. All objects are inputs, so it is a monitoring profile.

This page lists 97 BACnet objects for the Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
97 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus
Source document
BASgatewayLX Modbus device profile Danfoss_FC102_Drive · Danfoss_FC102_Drive_LX.csv
Download CSV 97 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX

Integration in brief

Poll Running, Auto Mode, Alarm and Warning plus the actual values. Writing start/stop or a reference needs output objects that this profile does not include.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 89RunningDrive runningRead
BI 87Auto ModeDrive in auto (remote) modeRead
AI 10FrequencyOutput frequencyRead
AI 11Motor CurrentMotor currentRead
AI 7Input Power [kW]Input power, kWRead
AI 5Main Actual Value [%]Main actual value, %Read
BI 85WarningAny active warningRead
BI 81AlarmAny active alarmRead
AI 55Alarm WordAlarm word (bit-coded)Read

Network setup

Watch out for

Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

97 of 97 shown
Type
AnalogBinary
Show
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX BACnet Points List
DescriptionStates
AI1Control WordModbus 416000Read
AI2Reference [Unit]Modbus 416010Read
AI3Reference [%]Modbus 416020Read
AI4Status WordModbus 416030Read
AImin5Main Actual Value [%]Modbus 416050Read
AI6Custom ReadoutModbus 416090Read
AImin7Input Power [kW]Modbus 416100Read
AI8Input Power [hp]Modbus 416110Read
AI9Motor VoltageModbus 416120Read
AImin10FrequencyModbus 416130Read
AImin11Motor CurrentModbus 416140Read
AI12Frequency [%]Modbus 416150Read
AI13Torque [Nm]Modbus 416160Read
AI14Speed [RPM]Modbus 416170Read
AI15Motor ThermalModbus 416180Read
AI16Torque [%]Modbus 416220Read
AI17DC Link VoltageModbus 416300Read
AI18Brake Energy /sModbus 416320Read
AI19Brake Energy /2 minModbus 416330Read
AI20Heatsink Temp.Modbus 416340Read
AI21Inverter ThermalModbus 416350Read
AI22Inv. Nom. CurrentModbus 416360Read
AI23Inv. Max. CurrentModbus 416370Read
AI24SL Controller StateModbus 416380Read
AI25Control Card Temp.Modbus 416390Read
AI26Logging Buffer FullModbus 416400Read
AI27Timed Actions StatusModbus 416430Read
AI28Current Fault SourceModbus 416490Read
AI29External ReferenceModbus 416500Read
AI30Feedback [Unit]Modbus 416520Read
AI31Digi Pot ReferenceModbus 416530Read
AI32Feedback 1 [Unit]Modbus 416540Read
AI33Feedback 2 [Unit]Modbus 416550Read
AI34Feedback 3 [Unit]Modbus 416560Read
AI35PID Output [%]Modbus 416580Read
AI36Digital InputModbus 416600Read
AI37Terminal 53 Switch SettingModbus 416610Read
AI38Analog Input 53Modbus 416620Read
AI39Terminal 54 Switch SettingModbus 416630Read
AI40Analog Input 54Modbus 416640Read
AI41Analog Output 42 [mA]Modbus 416650Read
AI42Digital Output [bin]Modbus 416660Read
AI43Pulse Input #29 [Hz]Modbus 416670Read
AI44Pulse Input #33 [Hz]Modbus 416680Read
AI45Pulse Output #27 [Hz]Modbus 416690Read
AI46Pulse Output #29 [Hz]Modbus 416700Read
AI47Relay Output [bin]Modbus 416710Read
AI48Counter AModbus 416720Read
AI49Counter BModbus 416730Read
AI50Fieldbus CTW 1Modbus 416800Read
AI51Fieldbus REF 1Modbus 416820Read
AI52Comm. Option STWModbus 416840Read
AI53FC Port CTW 1Modbus 416850Read
AI54FC Port REF 1Modbus 416860Read
AImin55Alarm WordModbus 416900Read
AI56Alarm Word 2Modbus 416910Read
AI57Warning WordModbus 416920Read
AI58Warning Word 2Modbus 416930Read
AI59Ext. Status WordModbus 416940Read
AI60Ext. Status Word 2Modbus 416950Read
AI61Maintenance WordModbus 416960Read
BI62Preset reference LSBModbus 000001Read
BI63Preset reference MSBModbus 000002Read
BI64DC brake ONModbus 000003Read
BI65Coast Stop OFFModbus 000004Read
BI66Quick Stop OFFModbus 000005Read
BI67Freeze Frequency OFFModbus 000006Read
BI68Start Ramp ONModbus 000007Read
BI69Reset ONModbus 000008Read
BI70Jog ONModbus 000009Read
BI71Ramp 2 ON (Ramp 1 OFF)Modbus 000010Read
BI72Data Valid ONModbus 000011Read
BI73Relay 1 ONModbus 000012Read
BI74Relay 2 ONModbus 000013Read
BI75Seupt LSBModbus 000014Read
BI76Setup MSBModbus 000015Read
BI77Reversing ONModbus 000016Read
BI78Control ReadyModbus 000033Read
BI79Frequency Converter ReadyModbus 000034Read
BI80Safety ClosedModbus 000035Read
BImin81AlarmModbus 000036Read
BI82Not UsedModbus 000037; not polled by defaultRead
BI83Not UsedModbus 000038; not polled by defaultRead
BI84Not UsedModbus 000039; not polled by defaultRead
BImin85WarningModbus 000040Read
BI86At ReferenceModbus 000041Read
BImin87Auto ModeModbus 000042Read
BI88In Frequency RangeModbus 000043Read
BImin89RunningModbus 000044Read
BI90Not UsedModbus 000045Read
BI91Voltage WarningModbus 000046Read
BI92Current LimitModbus 000047Read
BI93Thermal WarmingModbus 000048Read
AI94Frequency converter control word register (CTW).Modbus 450000Read
AI95Input data: Bus reference register (REF).Modbus 450010Read
AI96Output data: Frequency converter status word register (STW).Modbus 450200Read
AI97Output data: Frequency converter main actual value register (MAV).Modbus 450210Read
Object ID lookup: Contemporary Controls BASgatewayLX Danfoss FC102 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Danfoss VLT HVAC Drive FC 102 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX

How many BACnet points does the Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX have?

This list has 97 BACnet objects: 65 analog inputs, 32 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Danfoss_FC102_Drive (Danfoss_FC102_Drive_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Danfoss_FC102_Drive_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX?

Start with BI 89 Running (Drive running); BI 87 Auto Mode (Drive in auto (remote) mode); AI 10 Frequency (Output frequency); AI 11 Motor Current (Motor current); AI 7 Input Power [kW] (Input power, kW); AI 5 Main Actual Value [%] (Main actual value, %); BI 85 Warning (Any active warning); BI 81 Alarm (Any active alarm); AI 55 Alarm Word (Alarm word (bit-coded)).

How do I check these points on the real Danfoss VLT HVAC Drive FC 102 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists