Power and energy meter · BACnet points list
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Eaton PXM 2000: 329 objects (254 AI, 11 AO, 48 BI, 16 BO), 95 polled by default. Inputs give voltages, currents, W/VAR/VA and PF per phase and total, frequency, received/delivered/net energy, VAR-hours and per-phase energy, plus unpolled demand, THD and I/O states; unpolled outputs test pulse outputs and relays and reset accumulators.
This page lists 329 BACnet objects for the Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Eaton Power Xpert PXM 2000 via BASgatewayLX
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 329 (27 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Map total watts (3-phase), delivered energy (Wh) and received energy (Wh) first. The listed objects are read-only.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 10 | Watts 3-Ph total | Total watts (3-phase) | Read |
| AI 29 | W-hours Delivered | Delivered energy (Wh) | Read |
| AI 28 | W-hours Received | Received energy (Wh) | Read |
| AI 4 | Volts A-B | Voltage A-B | Read |
| AI 7 | Amps A | Current A | Read |
| AI 13 | Power Factor 3-Ph total | Total power factor | Read |
| AI 14 | Frequency | Frequency | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Outputs include firmware reprogramming and meter restart commands; never poll or write them.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Volts A-N | Modbus 401000 | V | Read | |
| AI | 2 | Volts B-N | Modbus 401002 | V | Read | |
| AI | 3 | Volts C-N | Modbus 401004 | V | Read | |
| AImin | 4 | Volts A-B | Modbus 401006 | V | Read | |
| AI | 5 | Volts B-C | Modbus 401008 | V | Read | |
| AI | 6 | Volts C-A | Modbus 401010 | V | Read | |
| AImin | 7 | Amps A | Modbus 401012 | A | Read | |
| AI | 8 | Amps B | Modbus 401014 | A | Read | |
| AI | 9 | Amps C | Modbus 401016 | A | Read | |
| AImin | 10 | Watts 3-Ph total | Modbus 401018 | W | Read | |
| AI | 11 | VARs 3-Ph total | Modbus 401020 | VAR | Read | |
| AI | 12 | VAs 3-Ph total | Modbus 401022 | VA | Read | |
| AImin | 13 | Power Factor 3-Ph total | Modbus 401024 | PF | Read | |
| AImin | 14 | Frequency | Modbus 401026 | Hz | Read | |
| AI | 15 | Neutral Current | Modbus 401028 | A | Read | |
| AI | 16 | Watts Phase A | Modbus 401030 | W | Read | |
| AI | 17 | Watts Phase B | Modbus 401032 | W | Read | |
| AI | 18 | Watts Phase C | Modbus 401034 | W | Read | |
| AI | 19 | VARs Phase A | Modbus 401036 | VAR | Read | |
| AI | 20 | VARs Phase B | Modbus 401038 | VAR | Read | |
| AI | 21 | VARs Phase C | Modbus 401040 | VAR | Read | |
| AI | 22 | VAs Phase A | Modbus 401042 | VA | Read | |
| AI | 23 | VAs Phase B | Modbus 401044 | VA | Read | |
| AI | 24 | VAs Phase C | Modbus 401046 | VA | Read | |
| AI | 25 | Power Factor Phase A | Modbus 401048 | PF | Read | |
| AI | 26 | Power Factor Phase B | Modbus 401050 | PF | Read | |
| AI | 27 | Power Factor Phase C | Modbus 401052 | PF | Read | |
| AImin | 28 | W-hours Received | Modbus 401500 | Wh | Read | |
| AImin | 29 | W-hours Delivered | Modbus 401502 | Wh | Read | |
| AI | 30 | W-hours Net | Modbus 401504 | Wh | Read | |
| AI | 31 | W-hours Total | Modbus 401506 | Wh | Read | |
| AI | 32 | VAR-hours Positive | Modbus 401508 | VAR | Read | |
| AI | 33 | VAR-hours Negative | Modbus 401510 | VAR | Read | |
| AI | 34 | VAR-hours Net | Modbus 401512 | VAR | Read | |
| AI | 35 | VAR-hours Total | Modbus 401514 | VAR | Read | |
| AI | 36 | VA-hours Total | Modbus 401516 | VA | Read | |
| AI | 37 | W-hours Received Phase A | Modbus 401518 | Wh | Read | |
| AI | 38 | W-hours Received Phase B | Modbus 401520 | Wh | Read | |
| AI | 39 | W-hours Received Phase C | Modbus 401522 | Wh | Read | |
| AI | 40 | W-hours Delivered Phase A | Modbus 401524 | Wh | Read | |
| AI | 41 | W-hours Delivered Phase B | Modbus 401526 | Wh | Read | |
| AI | 42 | W-hours Delivered Phase C | Modbus 401528 | Wh | Read | |
| AI | 43 | W-hours Net Phase A | Modbus 401530 | Wh | Read | |
| AI | 44 | W-hours Net Phase B | Modbus 401532 | Wh | Read | |
| AI | 45 | W-hours Net Phase C | Modbus 401534 | Wh | Read | |
| AI | 46 | W-hours Total Phase A | Modbus 401536 | Wh | Read | |
| AI | 47 | W-hours Total Phase B | Modbus 401538 | Wh | Read | |
| AI | 48 | W-hours Total Phase C | Modbus 401540 | Wh | Read | |
| AI | 49 | VAR-hours Positive Phase A | Modbus 401542 | VAR | Read | |
| AI | 50 | VAR-hours Positive Phase B | Modbus 401544 | VAR | Read | |
| AI | 51 | VAR-hours Positive Phase C | Modbus 401546 | VAR | Read | |
| AI | 52 | VAR-hours Negative Phase A | Modbus 401548 | VAR | Read | |
| AI | 53 | VAR-hours Negative Phase B | Modbus 401550 | VAR | Read | |
| AI | 54 | VAR-hours Negative Phase C | Modbus 401552 | VAR | Read | |
| AI | 55 | VAR-hours Net Phase A | Modbus 401554 | VAR | Read | |
| AI | 56 | VAR-hours Net Phase B | Modbus 401556 | VAR | Read | |
| AI | 57 | VAR-hours Net Phase C | Modbus 401558 | VAR | Read | |
| AI | 58 | VAR-hours Net Phase C | Modbus 401560 | VAR | Read | |
| AI | 59 | VAR-hours Total Phase B | Modbus 401562 | VAR | Read | |
| AI | 60 | VAR-hours Total Phase C | Modbus 401564 | VAR | Read | |
| AI | 61 | VA-hours Phase A | Modbus 401566 | VA | Read | |
| AI | 62 | VA-hours Phase B | Modbus 401568 | VA | Read | |
| AI | 63 | VA-hours Phase C | Modbus 401570 | VA | Read | |
| AI | 64 | Amps A Average | Modbus 402000 | A | Read | |
| AI | 65 | Amps B Average | Modbus 402002 | A | Read | |
| AI | 66 | Amps C Average | Modbus 402004 | A | Read | |
| AI | 67 | Positive Watts 3-Ph Average | Modbus 402006 | W | Read | |
| AI | 68 | Positive VARs 3-Ph Average | Modbus 402008 | VAR | Read | |
| AI | 69 | Negative Watts 3-Ph Average | Modbus 402010 | W | Read | |
| AI | 70 | Negative VARs 3-Ph Average | Modbus 402012 | VAR | Read | |
| AI | 71 | VAs 3-Ph Average | Modbus 402014 | VA | Read | |
| AI | 72 | Positive PF 3-Ph Average | Modbus 402016 | PF | Read | |
| AI | 73 | Negative PF 3-PF Average | Modbus 402018 | PF | Read | |
| AI | 74 | Neutral Current Average | Modbus 402020 | A | Read | |
| AI | 75 | Positive Watts Phase A Average | Modbus 402022 | W | Read | |
| AI | 76 | Positive Watts Phase B Average | Modbus 402024 | W | Read | |
| AI | 77 | Positive Watts Phase C Average | Modbus 402026 | W | Read | |
| AI | 78 | Positive Watts Phase C Average | Modbus 402028 | W | Read | |
| AI | 79 | Positive VARs Phase B Average | Modbus 402030 | VAR | Read | |
| AI | 80 | Positive VARs Phase C Average | Modbus 402032 | VAR | Read | |
| AI | 81 | Negative Watts Phase A Average | Modbus 402034 | W | Read | |
| AI | 82 | Negative Watts Phase B Average | Modbus 402036 | W | Read | |
| AI | 83 | Negative Watts Phase C Average | Modbus 402038 | W | Read | |
| AI | 84 | Negative VARs Phase A Average | Modbus 402040 | VAR | Read | |
| AI | 85 | Negative VARs Phase B Average | Modbus 402042 | VAR | Read | |
| AI | 86 | Negative VARs Phase C Average | Modbus 402044 | VAR | Read | |
| AI | 87 | VAs Phase A Average | Modbus 402046 | VA | Read | |
| AI | 88 | VAs Phase B Average | Modbus 402048 | VA | Read | |
| AI | 89 | VAs Phase C Average | Modbus 402050 | VA | Read | |
| AI | 90 | Positive PF Phase A Average | Modbus 402052 | PF | Read | |
| AI | 91 | Positive PF Phase B Average | Modbus 402054 | PF | Read | |
| AI | 92 | Positive PF Phase C Average | Modbus 402056 | PF | Read | |
| AI | 93 | Negative PF Phase A Average | Modbus 402058 | PF | Read | |
| AI | 94 | Negative PF Phase B Average | Modbus 402060 | PF | Read | |
| AI | 95 | Negative PF Phase C Average | Modbus 402062 | PF | Read | |
| AI | 96 | Angle Phase A Current | Modbus 404100; not polled by default | Read | ||
| AI | 97 | Angle Phase A Current | Modbus 404101; not polled by default | Read | ||
| AI | 98 | Angle Phase C Current | Modbus 404102; not polled by default | Read | ||
| AI | 99 | Angle Volts A-B | Modbus 404103; not polled by default | Read | ||
| AI | 100 | Angle Volts B-C | Modbus 404104; not polled by default | Read | ||
| AI | 101 | Angle Volts C-A | Modbus 404105; not polled by default | Read | ||
| AI | 102 | Port ID | Modbus 404500; not polled by default | Read | ||
| AI | 103 | Meter Status | Modbus 404501; not polled by default | Read | ||
| AI | 104 | Limits Status | Modbus 404502; not polled by default | Read | ||
| AI | 105 | Time Since Reset | Modbus 404503; not polled by default | Read | ||
| AI | 106 | Meter On Time 1 | Modbus 404505; not polled by default | Read | ||
| AI | 107 | Meter On Time 2 | Modbus 404506; not polled by default | Read | ||
| AI | 108 | Meter On Time 3 | Modbus 404507; not polled by default | Read | ||
| AI | 109 | Current Date and Time 1 | Modbus 404508; not polled by default | Read | ||
| AI | 110 | Current Date and Time 2 | Modbus 404509; not polled by default | Read | ||
| AI | 111 | Current Date and Time 3 | Modbus 404510; not polled by default | Read | ||
| AI | 112 | Current Day of Week | Modbus 404512; not polled by default | Read | ||
| AI | 113 | Volts A-N %THD | Modbus 406000; not polled by default | Read | ||
| AI | 114 | Volts B-N %THD | Modbus 406001; not polled by default | Read | ||
| AI | 115 | Volts B-N %THD | Modbus 406002; not polled by default | Read | ||
| AI | 116 | Amps A %THD | Modbus 406003; not polled by default | Read | ||
| AI | 117 | Amps B %THD | Modbus 406004; not polled by default | Read | ||
| AI | 118 | Amps C %THD | Modbus 406005; not polled by default | Read | ||
| AI | 119 | Volts A-N Minimum | Modbus 408000; not polled by default | V | Read | |
| AI | 120 | Volts B-N Minimum | Modbus 408002; not polled by default | V | Read | |
| AI | 121 | Volts C-N Minimum | Modbus 408004; not polled by default | V | Read | |
| AI | 122 | Volts A-B Minimum | Modbus 408006; not polled by default | V | Read | |
| AI | 123 | Volts B-C Minimum | Modbus 408008; not polled by default | V | Read | |
| AI | 124 | Volts C-A Minimum | Modbus 408010; not polled by default | V | Read | |
| AI | 125 | Amps A Minimum Avg Demand | Modbus 408012; not polled by default | A | Read | |
| AI | 126 | Amps B Minimum Avg Demand | Modbus 408014; not polled by default | A | Read | |
| AI | 127 | Amps C Minimum Avg Demand | Modbus 408016; not polled by default | A | Read | |
| AI | 128 | Positive Watts 3-Ph Minimum Avg Demand | Modbus 408018; not polled by default | W | Read | |
| AI | 129 | Positive VARs 3-Ph Minimum Avg Demand | Modbus 408020; not polled by default | VAR | Read | |
| AI | 130 | Negative Watts 3-Ph Minimum Avg Demand | Modbus 408022; not polled by default | W | Read | |
| AI | 131 | Negative VARs 3-Ph Minimum Avg Demand | Modbus 408024; not polled by default | VAR | Read | |
| AI | 132 | VAs 3-Ph Minimum Avg Demand | Modbus 408026; not polled by default | VA | Read | |
| AI | 133 | Positive Power Factor 3-Ph Minimum Avg Demand | Modbus 408028; not polled by default | PF | Read | |
| AI | 134 | Negative Power Factor 3-Ph Minimum Avg Demand | Modbus 408030; not polled by default | PF | Read | |
| AI | 135 | Frequency Minimum | Modbus 408032; not polled by default | Hz | Read | |
| AI | 136 | Neutral Current Minimum Avg Demand | Modbus 408034; not polled by default | A | Read | |
| AI | 137 | Positive Watts Phase A Minimum Avg Demand | Modbus 408036; not polled by default | W | Read | |
| AI | 138 | Positive Watts Phase B Minimum Avg Demand | Modbus 408038; not polled by default | W | Read | |
| AI | 139 | Positive Watts Phase C Minimum Avg Demand | Modbus 408040; not polled by default | W | Read | |
| AI | 140 | Positive VARs Phase A Minimum Avg Demand | Modbus 408042; not polled by default | VAR | Read | |
| AI | 141 | Positive VARs Phase B Minimum Avg Demand | Modbus 408044; not polled by default | VAR | Read | |
| AI | 142 | Positive VARs Phase C Minimum Avg Demand | Modbus 408046; not polled by default | VAR | Read | |
| AI | 143 | Negative Watts Phase A Minimum Avg Demand | Modbus 408048; not polled by default | W | Read | |
| AI | 144 | Negative Watts Phase B Minimum Avg Demand | Modbus 408050; not polled by default | W | Read | |
| AI | 145 | Negative Watts Phase C Minimum Avg Demand | Modbus 408052; not polled by default | W | Read | |
| AI | 146 | Negative VARs Phase A Minimum Avg Demand | Modbus 408054; not polled by default | VAR | Read | |
| AI | 147 | Negative VARs Phase B Minimum Avg Demand | Modbus 408056; not polled by default | VAR | Read | |
| AI | 148 | Negative VARs Phase C Minimum Avg Demand | Modbus 408058; not polled by default | VAR | Read | |
| AI | 149 | VAs Phase A Minimum Avg Demand | Modbus 408060; not polled by default | VA | Read | |
| AI | 150 | VAs Phase B Minimum Avg Demand | Modbus 408062; not polled by default | VA | Read | |
| AI | 151 | VAs Phase C Minimum Avg Demand | Modbus 408064; not polled by default | VA | Read | |
| AI | 152 | Positive PF Phase A Minimum Avg Demand | Modbus 408066; not polled by default | PF | Read | |
| AI | 153 | Positive PF Phase B Minimum Avg Demand | Modbus 408068; not polled by default | PF | Read | |
| AI | 154 | Positive PF Phase C Minimum Avg Demand | Modbus 408070; not polled by default | PF | Read | |
| AI | 155 | Negative PF Phase A Minimum Avg Demand | Modbus 408072; not polled by default | PF | Read | |
| AI | 156 | Negative PF Phase B Minimum Avg Demand | Modbus 408074; not polled by default | PF | Read | |
| AI | 157 | Negative PF Phase C Minimum Avg Demand | Modbus 408076; not polled by default | PF | Read | |
| AI | 158 | Volts A-N %THD Minimum | Modbus 408078; not polled by default | Read | ||
| AI | 159 | Volts B-N %THD Minimum | Modbus 408079; not polled by default | Read | ||
| AI | 160 | Volts C-N %THD Minimum | Modbus 408080; not polled by default | Read | ||
| AI | 161 | Amps A %THD Minimum | Modbus 408081; not polled by default | Read | ||
| AI | 162 | Amps B %THD Minimum | Modbus 408082; not polled by default | Read | ||
| AI | 163 | Amps C %THD Minimum | Modbus 408083; not polled by default | Read | ||
| AI | 164 | Volts A-N Maximum | Modbus 409000; not polled by default | V | Read | |
| AI | 165 | Volts B-N Maximum | Modbus 409002; not polled by default | V | Read | |
| AI | 166 | Volts C-N Maximum | Modbus 409004; not polled by default | V | Read | |
| AI | 167 | Volts A-B Maximum | Modbus 409006; not polled by default | V | Read | |
| AI | 168 | Volts B-C Maximum | Modbus 409008; not polled by default | V | Read | |
| AI | 169 | Volts C-A Maximum | Modbus 409010; not polled by default | V | Read | |
| AI | 170 | Amps A Maximum Avg Demand | Modbus 409012; not polled by default | A | Read | |
| AI | 171 | Amps B Maximum Avg Demand | Modbus 409014; not polled by default | A | Read | |
| AI | 172 | Amps C Maximum Avg Demand | Modbus 409016; not polled by default | A | Read | |
| AI | 173 | Positive Watts 3-Ph Maximum Avg Demand | Modbus 409018; not polled by default | W | Read | |
| AI | 174 | Positive VARs 3-Ph Maximum Avg Demand | Modbus 409020; not polled by default | VAR | Read | |
| AI | 175 | Negative Watts 3-Ph Maximum Avg Demand | Modbus 409022; not polled by default | W | Read | |
| AI | 176 | Negative VARs 3-Ph Maximum Avg Demand | Modbus 409024; not polled by default | VAR | Read | |
| AI | 177 | VAs 3-Ph Maximum Avg Demand | Modbus 409026; not polled by default | VA | Read | |
| AI | 178 | Positive Power Factor 3-Ph Maximum Avg Demand | Modbus 409028; not polled by default | PF | Read | |
| AI | 179 | Negative Power Factor 3-Ph Maximum Avg Demand | Modbus 409030; not polled by default | PF | Read | |
| AI | 180 | Frequency Maximum | Modbus 409032; not polled by default | Hz | Read | |
| AI | 181 | Neutral Current Maximum Avg Demand | Modbus 409034; not polled by default | A | Read | |
| AI | 182 | Positive Watts Phase A Maximum Avg Demand | Modbus 409036; not polled by default | W | Read | |
| AI | 183 | Positive Watts Phase B Maximum Avg Demand | Modbus 409038; not polled by default | W | Read | |
| AI | 184 | Positive Watts Phase C Maximum Avg Demand | Modbus 409040; not polled by default | W | Read | |
| AI | 185 | Positive VARs Phase A Maximum Avg Demand | Modbus 409042; not polled by default | VAR | Read | |
| AI | 186 | Positive VARs Phase B Maximum Avg Demand | Modbus 409044; not polled by default | VAR | Read | |
| AI | 187 | Positive VARs Phase C Maximum Avg Demand | Modbus 409046; not polled by default | VAR | Read | |
| AI | 188 | Negative Watts Phase A Maximum Avg Demand | Modbus 409048; not polled by default | W | Read | |
| AI | 189 | Negative Watts Phase B Maximum Avg Demand | Modbus 409050; not polled by default | W | Read | |
| AI | 190 | Negative Watts Phase C Maximum Avg Demand | Modbus 409052; not polled by default | W | Read | |
| AI | 191 | Negative VARs Phase A Maximum Avg Demand | Modbus 409054; not polled by default | VAR | Read | |
| AI | 192 | Negative VARs Phase B Maximum Avg Demand | Modbus 409056; not polled by default | VAR | Read | |
| AI | 193 | Negative VARs Phase C Maximum Avg Demand | Modbus 409058; not polled by default | VAR | Read | |
| AI | 194 | VAs Phase A Maximum Avg Demand | Modbus 409060; not polled by default | VA | Read | |
| AI | 195 | VAs Phase B Maximum Avg Demand | Modbus 409062; not polled by default | VA | Read | |
| AI | 196 | VAs Phase C Maximum Avg Demand | Modbus 409064; not polled by default | VA | Read | |
| AI | 197 | Positive PF Phase A Maximum Avg Demand | Modbus 409066; not polled by default | PF | Read | |
| AI | 198 | Positive PF Phase B Maximum Avg Demand | Modbus 409068; not polled by default | PF | Read | |
| AI | 199 | Positive PF Phase C Maximum Avg Demand | Modbus 409070; not polled by default | PF | Read | |
| AI | 200 | Negative PF Phase A Maximum Avg Demand | Modbus 409072; not polled by default | PF | Read | |
| AI | 201 | Negative PF Phase B Maximum Avg Demand | Modbus 409074; not polled by default | PF | Read | |
| AI | 202 | Negative PF Phase C Maximum Avg Demand | Modbus 409076; not polled by default | PF | Read | |
| AI | 203 | Volts A-N %THD Maximum | Modbus 409078; not polled by default | Read | ||
| AI | 204 | Volts B-N %THD Maximum | Modbus 409079; not polled by default | Read | ||
| AI | 205 | Volts C-N %THD Maximum | Modbus 409080; not polled by default | Read | ||
| AI | 206 | Amps A %THD Maximum | Modbus 409081; not polled by default | Read | ||
| AI | 207 | Amps B %THD Maximum | Modbus 409082; not polled by default | Read | ||
| AI | 208 | Amps C %THD Maximum | Modbus 409083; not polled by default | Read | ||
| BI | 209 | Digital Input #1 State Now | Modbus 410072 bit 0; not polled by default | Read | ||
| BI | 210 | Digital Input #1 State History 1 | Modbus 410072 bit 1; not polled by default | Read | ||
| BI | 211 | Digital Input #1 State History 2 | Modbus 410072 bit 2; not polled by default | Read | ||
| BI | 212 | Digital Input #1 State History 3 | Modbus 410072 bit 3; not polled by default | Read | ||
| BI | 213 | Digital Input #2 State Now | Modbus 410072 bit 4; not polled by default | Read | ||
| BI | 214 | Digital Input #2 State History 1 | Modbus 410072 bit 5; not polled by default | Read | ||
| BI | 215 | Digital Input #2 State History 2 | Modbus 410072 bit 6; not polled by default | Read | ||
| BI | 216 | Digital Input #2 State History 3 | Modbus 410072 bit 7; not polled by default | Read | ||
| BI | 217 | Digital Input #3 State Now | Modbus 410072 bit 8; not polled by default | Read | ||
| BI | 218 | Digital Input #3 State History 1 | Modbus 410072 bit 9; not polled by default | Read | ||
| BI | 219 | Digital Input #3 State History 3 | Modbus 410072 bit 10; not polled by default | Read | ||
| BI | 220 | Digital Input #3 State History 3 | Modbus 410072 bit 11; not polled by default | Read | ||
| BI | 221 | Digital Input #4 State Now | Modbus 410072 bit 12; not polled by default | Read | ||
| BI | 222 | Digital Input #4 State History 1 | Modbus 410072 bit 13; not polled by default | Read | ||
| BI | 223 | Digital Input #4 State History 4 | Modbus 410072 bit 14; not polled by default | Read | ||
| BI | 224 | Digital Input #4 State History 3 | Modbus 410072 bit 15; not polled by default | Read | ||
| BI | 225 | Digital Relay States #1 | Modbus 410073 bit 0; not polled by default | Read | ||
| BI | 226 | Digital Relay States #2 | Modbus 410073 bit 1; not polled by default | Read | ||
| BI | 227 | Digital Relay States #3 | Modbus 410073 bit 2; not polled by default | Read | ||
| BI | 228 | Digital Relay States #4 | Modbus 410073 bit 3; not polled by default | Read | ||
| BI | 229 | Digital Relay States #1 Unknown | Modbus 410073 bit 4; not polled by default | Read | ||
| BI | 230 | Digital Relay States #2 Unknown | Modbus 410073 bit 5; not polled by default | Read | ||
| BO | 231 | Pulse Output Test Select #1 | Modbus 410074 bit 0; not polled by default | Command | ||
| BO | 232 | Pulse Output Test Select #2 | Modbus 410074 bit 1; not polled by default | Command | ||
| BO | 233 | Pulse Output Test Select #3 | Modbus 410074 bit 2; not polled by default | Command | ||
| BO | 234 | Pulse Output Test Select #4 | Modbus 410074 bit 3; not polled by default | Command | ||
| BO | 235 | Turn Relay #1 ON | Modbus 410074 bit 0; not polled by default | Command | ||
| BO | 236 | Turn Relay #2 ON | Modbus 410074 bit 1; not polled by default | Command | ||
| AO | 237 | Pulse Output Test Power | Modbus 410075; not polled by default | Command | ||
| BO | 238 | Turn Relay #1 ON | Modbus 410075 bit 0; not polled by default | Command | ||
| BO | 239 | Turn Relay #2 ON | Modbus 410075 bit 1; not polled by default | Command | ||
| AI | 240 | Trip/Release delay timer for Relay 1 | Modbus 410076; not polled by default | Read | ||
| AI | 241 | Trip/Release delay timer for Relay 2 | Modbus 410077; not polled by default | Read | ||
| AI | 242 | Input 1 Accumulator Scaled | Modbus 410080; not polled by default | Read | ||
| AI | 243 | Input 2 Accumulator Scaled | Modbus 410081; not polled by default | Read | ||
| AI | 244 | Input 3 Accumulator Scaled | Modbus 410082; not polled by default | Read | ||
| AI | 245 | Input 4 Accumulator Scaled | Modbus 410083; not polled by default | Read | ||
| AI | 246 | Relay 1 Accumulator Scaled | Modbus 410084; not polled by default | Read | ||
| AI | 247 | Relay 2 Accumulator Scaled | Modbus 410085; not polled by default | Read | ||
| AI | 248 | Relay 3 Accumulator Scaled | Modbus 410086; not polled by default | Read | ||
| AI | 249 | Relay 5 Accumulator Scaled | Modbus 410087; not polled by default | Read | ||
| BI | 250 | Status of card - calibration not good; | Modbus 410072 bit 11; not polled by default | Read | ||
| BI | 251 | Status of card - configuration error | Modbus 410072 bit 10; not polled by default | Read | ||
| BI | 252 | Digital Input #1 State Now | Modbus 411072 bit 0; not polled by default | Read | ||
| BI | 253 | Digital Input #1 State History 1 | Modbus 411072 bit 1; not polled by default | Read | ||
| BI | 254 | Digital Input #1 State History 2 | Modbus 411072 bit 2; not polled by default | Read | ||
| BI | 255 | Digital Input #1 State History 3 | Modbus 411072 bit 3; not polled by default | Read | ||
| BI | 256 | Digital Input #2 State Now | Modbus 411072 bit 4; not polled by default | Read | ||
| BI | 257 | Digital Input #2 State History 1 | Modbus 411072 bit 5; not polled by default | Read | ||
| BI | 258 | Digital Input #2 State History 2 | Modbus 411072 bit 6; not polled by default | Read | ||
| BI | 259 | Digital Input #2 State History 3 | Modbus 411072 bit 7; not polled by default | Read | ||
| BI | 260 | Digital Input #3 State Now | Modbus 411072 bit 8; not polled by default | Read | ||
| BI | 261 | Digital Input #3 State History 1 | Modbus 411072 bit 9; not polled by default | Read | ||
| BI | 262 | Digital Input #3 State History 3 | Modbus 411072 bit 10; not polled by default | Read | ||
| BI | 263 | Digital Input #3 State History 3 | Modbus 411072 bit 11; not polled by default | Read | ||
| BI | 264 | Digital Input #4 State Now | Modbus 411072 bit 12; not polled by default | Read | ||
| BI | 265 | Digital Input #4 State History 1 | Modbus 411072 bit 13; not polled by default | Read | ||
| BI | 266 | Digital Input #4 State History 4 | Modbus 411072 bit 14; not polled by default | Read | ||
| BI | 267 | Digital Input #4 State History 3 | Modbus 411072 bit 15; not polled by default | Read | ||
| BI | 268 | Digital Relay States #1 | Modbus 411073 bit 0; not polled by default | Read | ||
| BI | 269 | Digital Relay States #2 | Modbus 411073 bit 1; not polled by default | Read | ||
| BI | 270 | Digital Relay States #3 | Modbus 411073 bit 2; not polled by default | Read | ||
| BI | 271 | Digital Relay States #4 | Modbus 411073 bit 3; not polled by default | Read | ||
| BI | 272 | Digital Relay States #1 Unknown | Modbus 411073 bit 4; not polled by default | Read | ||
| BI | 273 | Digital Relay States #2 Unknown | Modbus 411073 bit 5; not polled by default | Read | ||
| BO | 274 | Pulse Output Test Select #1 | Modbus 411074 bit 0; not polled by default | Command | ||
| BO | 275 | Pulse Output Test Select #2 | Modbus 411074 bit 1; not polled by default | Command | ||
| BO | 276 | Pulse Output Test Select #3 | Modbus 411074 bit 2; not polled by default | Command | ||
| BO | 277 | Pulse Output Test Select #4 | Modbus 411074 bit 3; not polled by default | Command | ||
| BO | 278 | Turn Relay #1 ON | Modbus 411074 bit 0; not polled by default | Command | ||
| BO | 279 | Turn Relay #2 ON | Modbus 411074 bit 1; not polled by default | Command | ||
| AO | 280 | Pulse Output Test Power | Modbus 411075; not polled by default | Command | ||
| BO | 281 | Turn Relay #1 ON | Modbus 411075 bit 0; not polled by default | Command | ||
| BO | 282 | Turn Relay #2 ON | Modbus 411075 bit 1; not polled by default | Command | ||
| AI | 283 | Trip/Release delay timer for Relay 1 | Modbus 411076; not polled by default | Read | ||
| AI | 284 | Trip/Release delay timer for Relay 2 | Modbus 411077; not polled by default | Read | ||
| AI | 285 | Input 1 Accumulator Scaled | Modbus 411080; not polled by default | Read | ||
| AI | 286 | Input 2 Accumulator Scaled | Modbus 411081; not polled by default | Read | ||
| AI | 287 | Input 3 Accumulator Scaled | Modbus 411082; not polled by default | Read | ||
| AI | 288 | Input 4 Accumulator Scaled | Modbus 411083; not polled by default | Read | ||
| AI | 289 | Relay 1 Accumulator Scaled | Modbus 411084; not polled by default | Read | ||
| AI | 290 | Relay 2 Accumulator Scaled | Modbus 411085; not polled by default | Read | ||
| AI | 291 | Relay 3 Accumulator Scaled | Modbus 411086; not polled by default | Read | ||
| AI | 292 | Relay 5 Accumulator Scaled | Modbus 411087; not polled by default | Read | ||
| BI | 293 | Status of card - calibration not good; | Modbus 411072 bit 11; not polled by default | Read | ||
| BI | 294 | Status of card - configuration error | Modbus 411072 bit 10; not polled by default | Read | ||
| AI | 295 | Option Card 1 Input 1 Accumulator | Modbus 412000; not polled by default | Read | ||
| AI | 296 | Option Card 1 Input 2 Accumulator | Modbus 412002; not polled by default | Read | ||
| AI | 297 | Option Card 1 Input 3 Accumulator | Modbus 412004; not polled by default | Read | ||
| AI | 298 | Option Card 1 Input 4 Accumulator | Modbus 412006; not polled by default | Read | ||
| AI | 299 | Option Card 1 Output or Relay 1 Accumulator | Modbus 412008; not polled by default | Read | ||
| AI | 300 | Option Card 1 Output or Relay 2 Accumulator | Modbus 412010; not polled by default | Read | ||
| AI | 301 | Option Card 1 Output or Relay 3 Accumulator | Modbus 412012; not polled by default | Read | ||
| AI | 302 | Option Card 1 Output or Relay 4 Accumulator | Modbus 412014; not polled by default | Read | ||
| AI | 303 | Option Card 2 Input 1 Accumulator | Modbus 412016; not polled by default | Read | ||
| AI | 304 | Option Card 2 Input 2 Accumulator | Modbus 412018; not polled by default | Read | ||
| AI | 305 | Option Card 2 Input 3 Accumulator | Modbus 412020; not polled by default | Read | ||
| AI | 306 | Option Card 2 Input 4 Accumulator | Modbus 412022; not polled by default | Read | ||
| AI | 307 | Option Card 2 Output or Relay 1 Accumulator | Modbus 412024; not polled by default | Read | ||
| AI | 308 | Option Card 2 Output or Relay 2 Accumulator | Modbus 412026; not polled by default | Read | ||
| AI | 309 | Option Card 2 Output or Relay 3 Accumulator | Modbus 412028; not polled by default | Read | ||
| AI | 310 | Option Card 2 Output or Relay 4 Accumulator | Modbus 412030; not polled by default | Read | ||
| AO | 311 | Reset Max/Min Blocks | Modbus 420000; not polled by default | Command | ||
| AO | 312 | Reset Energy Accumulators | Modbus 420001; not polled by default | Command | ||
| AO | 313 | Initiate Meter Firmware Reprogramming | Modbus 421000; not polled by default | Command | ||
| AO | 314 | Force Meter Restart | Modbus 421001; not polled by default | Command | ||
| AI | 315 | Open Privileged Command Session | Modbus 421002; not polled by default | Read | ||
| AI | 316 | Initiate Programmable Settings Update | Modbus 421003; not polled by default | Read | ||
| AI | 317 | Calculate Programmable Settings Checksum3 | Modbus 421004; not polled by default | Read | ||
| AI | 318 | Programmable Settings Checksum3 | Modbus 421005; not polled by default | Read | ||
| AI | 319 | Write New Password3 | Modbus 421006; not polled by default | Read | ||
| AI | 320 | Terminate Programmable Settings Update3 | Modbus 421007; not polled by default | Read | ||
| AI | 321 | Set Meter Clock 1 | Modbus 421008; not polled by default | Read | ||
| AI | 322 | Set Meter Clock 2 | Modbus 421009; not polled by default | Read | ||
| AI | 323 | Set Meter Clock 3 | Modbus 421010; not polled by default | Read | ||
| AI | 324 | Close Privileged Command Session | Modbus 421019; not polled by default | Read | ||
| AO | 325 | CT multiplier & denominator | Modbus 430000; not polled by default | Command | ||
| AO | 326 | CT numerator | Modbus 430001; not polled by default | Command | ||
| AO | 327 | PT numerator | Modbus 430002; not polled by default | Command | ||
| AO | 328 | PT denominator | Modbus 430003; not polled by default | Command | ||
| AO | 329 | PT multiplier & hookup | Modbus 430004; not polled by default | Command |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Eaton PXM 2000 point IDs by name
AI1Volts A-NAI2Volts B-NAI3Volts C-NAI4Volts A-BAI5Volts B-CAI6Volts C-AAI7Amps AAI8Amps BAI9Amps CAI10Watts 3-Ph totalAI11VARs 3-Ph totalAI12VAs 3-Ph totalAI13Power Factor 3-Ph totalAI14FrequencyAI15Neutral CurrentAI16Watts Phase AAI17Watts Phase BAI18Watts Phase CAI19VARs Phase AAI20VARs Phase BAI21VARs Phase CAI22VAs Phase AAI23VAs Phase BAI24VAs Phase CAI25Power Factor Phase AAI26Power Factor Phase BAI27Power Factor Phase CAI28W-hours ReceivedAI29W-hours DeliveredAI30W-hours NetAI31W-hours TotalAI32VAR-hours PositiveAI33VAR-hours NegativeAI34VAR-hours NetAI35VAR-hours TotalAI36VA-hours TotalAI37W-hours Received Phase AAI38W-hours Received Phase BAI39W-hours Received Phase CAI40W-hours Delivered Phase AAI41W-hours Delivered Phase BAI42W-hours Delivered Phase CAI43W-hours Net Phase AAI44W-hours Net Phase BAI45W-hours Net Phase CAI46W-hours Total Phase AAI47W-hours Total Phase BAI48W-hours Total Phase CAI49VAR-hours Positive Phase AAI50VAR-hours Positive Phase BAI51VAR-hours Positive Phase CAI52VAR-hours Negative Phase AAI53VAR-hours Negative Phase BAI54VAR-hours Negative Phase CAI55VAR-hours Net Phase AAI56VAR-hours Net Phase BAI57VAR-hours Net Phase CAI58VAR-hours Net Phase CAI59VAR-hours Total Phase BAI60VAR-hours Total Phase CAI61VA-hours Phase AAI62VA-hours Phase BAI63VA-hours Phase CAI64Amps A AverageAI65Amps B AverageAI66Amps C AverageAI67Positive Watts 3-Ph AverageAI68Positive VARs 3-Ph AverageAI69Negative Watts 3-Ph AverageAI70Negative VARs 3-Ph AverageAI71VAs 3-Ph AverageAI72Positive PF 3-Ph AverageAI73Negative PF 3-PF AverageAI74Neutral Current AverageAI75Positive Watts Phase A AverageAI76Positive Watts Phase B AverageAI77Positive Watts Phase C AverageAI78Positive Watts Phase C AverageAI79Positive VARs Phase B AverageAI80Positive VARs Phase C AverageAI81Negative Watts Phase A AverageAI82Negative Watts Phase B AverageAI83Negative Watts Phase C AverageAI84Negative VARs Phase A AverageAI85Negative VARs Phase B AverageAI86Negative VARs Phase C AverageAI87VAs Phase A AverageAI88VAs Phase B AverageAI89VAs Phase C AverageAI90Positive PF Phase A AverageAI91Positive PF Phase B AverageAI92Positive PF Phase C AverageAI93Negative PF Phase A AverageAI94Negative PF Phase B AverageAI95Negative PF Phase C AverageAI96Angle Phase A CurrentAI97Angle Phase A CurrentAI98Angle Phase C CurrentAI99Angle Volts A-BAI100Angle Volts B-CAI101Angle Volts C-AAI102Port IDAI103Meter StatusAI104Limits StatusAI105Time Since ResetAI106Meter On Time 1AI107Meter On Time 2AI108Meter On Time 3AI109Current Date and Time 1AI110Current Date and Time 2AI111Current Date and Time 3AI112Current Day of WeekAI113Volts A-N %THDAI114Volts B-N %THDAI115Volts B-N %THDAI116Amps A %THDAI117Amps B %THDAI118Amps C %THDAI119Volts A-N MinimumAI120Volts B-N MinimumAI121Volts C-N MinimumAI122Volts A-B MinimumAI123Volts B-C MinimumAI124Volts C-A MinimumAI125Amps A Minimum Avg DemandAI126Amps B Minimum Avg DemandAI127Amps C Minimum Avg DemandAI128Positive Watts 3-Ph Minimum Avg DemandAI129Positive VARs 3-Ph Minimum Avg DemandAI130Negative Watts 3-Ph Minimum Avg DemandAI131Negative VARs 3-Ph Minimum Avg DemandAI132VAs 3-Ph Minimum Avg DemandAI133Positive Power Factor 3-Ph Minimum Avg DemandAI134Negative Power Factor 3-Ph Minimum Avg DemandAI135Frequency MinimumAI136Neutral Current Minimum Avg DemandAI137Positive Watts Phase A Minimum Avg DemandAI138Positive Watts Phase B Minimum Avg DemandAI139Positive Watts Phase C Minimum Avg DemandAI140Positive VARs Phase A Minimum Avg DemandAI141Positive VARs Phase B Minimum Avg DemandAI142Positive VARs Phase C Minimum Avg DemandAI143Negative Watts Phase A Minimum Avg DemandAI144Negative Watts Phase B Minimum Avg DemandAI145Negative Watts Phase C Minimum Avg DemandAI146Negative VARs Phase A Minimum Avg DemandAI147Negative VARs Phase B Minimum Avg DemandAI148Negative VARs Phase C Minimum Avg DemandAI149VAs Phase A Minimum Avg DemandAI150VAs Phase B Minimum Avg DemandAI151VAs Phase C Minimum Avg DemandAI152Positive PF Phase A Minimum Avg DemandAI153Positive PF Phase B Minimum Avg DemandAI154Positive PF Phase C Minimum Avg DemandAI155Negative PF Phase A Minimum Avg DemandAI156Negative PF Phase B Minimum Avg DemandAI157Negative PF Phase C Minimum Avg DemandAI158Volts A-N %THD MinimumAI159Volts B-N %THD MinimumAI160Volts C-N %THD MinimumAI161Amps A %THD MinimumAI162Amps B %THD MinimumAI163Amps C %THD MinimumAI164Volts A-N MaximumAI165Volts B-N MaximumAI166Volts C-N MaximumAI167Volts A-B MaximumAI168Volts B-C MaximumAI169Volts C-A MaximumAI170Amps A Maximum Avg DemandAI171Amps B Maximum Avg DemandAI172Amps C Maximum Avg DemandAI173Positive Watts 3-Ph Maximum Avg DemandAI174Positive VARs 3-Ph Maximum Avg DemandAI175Negative Watts 3-Ph Maximum Avg DemandAI176Negative VARs 3-Ph Maximum Avg DemandAI177VAs 3-Ph Maximum Avg DemandAI178Positive Power Factor 3-Ph Maximum Avg DemandAI179Negative Power Factor 3-Ph Maximum Avg DemandAI180Frequency MaximumAI181Neutral Current Maximum Avg DemandAI182Positive Watts Phase A Maximum Avg DemandAI183Positive Watts Phase B Maximum Avg DemandAI184Positive Watts Phase C Maximum Avg DemandAI185Positive VARs Phase A Maximum Avg DemandAI186Positive VARs Phase B Maximum Avg DemandAI187Positive VARs Phase C Maximum Avg DemandAI188Negative Watts Phase A Maximum Avg DemandAI189Negative Watts Phase B Maximum Avg DemandAI190Negative Watts Phase C Maximum Avg DemandAI191Negative VARs Phase A Maximum Avg DemandAI192Negative VARs Phase B Maximum Avg DemandAI193Negative VARs Phase C Maximum Avg DemandAI194VAs Phase A Maximum Avg DemandAI195VAs Phase B Maximum Avg DemandAI196VAs Phase C Maximum Avg DemandAI197Positive PF Phase A Maximum Avg DemandAI198Positive PF Phase B Maximum Avg DemandAI199Positive PF Phase C Maximum Avg DemandAI200Negative PF Phase A Maximum Avg DemandAI201Negative PF Phase B Maximum Avg DemandAI202Negative PF Phase C Maximum Avg DemandAI203Volts A-N %THD MaximumAI204Volts B-N %THD MaximumAI205Volts C-N %THD MaximumAI206Amps A %THD MaximumAI207Amps B %THD MaximumAI208Amps C %THD MaximumBI209Digital Input #1 State NowBI210Digital Input #1 State History 1BI211Digital Input #1 State History 2BI212Digital Input #1 State History 3BI213Digital Input #2 State NowBI214Digital Input #2 State History 1BI215Digital Input #2 State History 2BI216Digital Input #2 State History 3BI217Digital Input #3 State NowBI218Digital Input #3 State History 1BI219Digital Input #3 State History 3BI220Digital Input #3 State History 3BI221Digital Input #4 State NowBI222Digital Input #4 State History 1BI223Digital Input #4 State History 4BI224Digital Input #4 State History 3BI225Digital Relay States #1BI226Digital Relay States #2BI227Digital Relay States #3BI228Digital Relay States #4BI229Digital Relay States #1 UnknownBI230Digital Relay States #2 UnknownBO231Pulse Output Test Select #1BO232Pulse Output Test Select #2BO233Pulse Output Test Select #3BO234Pulse Output Test Select #4BO235Turn Relay #1 ONBO236Turn Relay #2 ONAO237Pulse Output Test PowerBO238Turn Relay #1 ONBO239Turn Relay #2 ONAI240Trip/Release delay timer for Relay 1AI241Trip/Release delay timer for Relay 2AI242Input 1 Accumulator ScaledAI243Input 2 Accumulator ScaledAI244Input 3 Accumulator ScaledAI245Input 4 Accumulator ScaledAI246Relay 1 Accumulator ScaledAI247Relay 2 Accumulator ScaledAI248Relay 3 Accumulator ScaledAI249Relay 5 Accumulator ScaledBI250Status of card - calibration not good;BI251Status of card - configuration errorBI252Digital Input #1 State NowBI253Digital Input #1 State History 1BI254Digital Input #1 State History 2BI255Digital Input #1 State History 3BI256Digital Input #2 State NowBI257Digital Input #2 State History 1BI258Digital Input #2 State History 2BI259Digital Input #2 State History 3BI260Digital Input #3 State NowBI261Digital Input #3 State History 1BI262Digital Input #3 State History 3BI263Digital Input #3 State History 3BI264Digital Input #4 State NowBI265Digital Input #4 State History 1BI266Digital Input #4 State History 4BI267Digital Input #4 State History 3BI268Digital Relay States #1BI269Digital Relay States #2BI270Digital Relay States #3BI271Digital Relay States #4BI272Digital Relay States #1 UnknownBI273Digital Relay States #2 UnknownBO274Pulse Output Test Select #1BO275Pulse Output Test Select #2BO276Pulse Output Test Select #3BO277Pulse Output Test Select #4BO278Turn Relay #1 ONBO279Turn Relay #2 ONAO280Pulse Output Test PowerBO281Turn Relay #1 ONBO282Turn Relay #2 ONAI283Trip/Release delay timer for Relay 1AI284Trip/Release delay timer for Relay 2AI285Input 1 Accumulator ScaledAI286Input 2 Accumulator ScaledAI287Input 3 Accumulator ScaledAI288Input 4 Accumulator ScaledAI289Relay 1 Accumulator ScaledAI290Relay 2 Accumulator ScaledAI291Relay 3 Accumulator ScaledAI292Relay 5 Accumulator ScaledBI293Status of card - calibration not good;BI294Status of card - configuration errorAI295Option Card 1 Input 1 AccumulatorAI296Option Card 1 Input 2 AccumulatorAI297Option Card 1 Input 3 AccumulatorAI298Option Card 1 Input 4 AccumulatorAI299Option Card 1 Output or Relay 1 AccumulatorAI300Option Card 1 Output or Relay 2 AccumulatorAI301Option Card 1 Output or Relay 3 AccumulatorAI302Option Card 1 Output or Relay 4 AccumulatorAI303Option Card 2 Input 1 AccumulatorAI304Option Card 2 Input 2 AccumulatorAI305Option Card 2 Input 3 AccumulatorAI306Option Card 2 Input 4 AccumulatorAI307Option Card 2 Output or Relay 1 AccumulatorAI308Option Card 2 Output or Relay 2 AccumulatorAI309Option Card 2 Output or Relay 3 AccumulatorAI310Option Card 2 Output or Relay 4 AccumulatorAO311Reset Max/Min BlocksAO312Reset Energy AccumulatorsAO313Initiate Meter Firmware ReprogrammingAO314Force Meter RestartAI315Open Privileged Command SessionAI316Initiate Programmable Settings UpdateAI317Calculate Programmable Settings Checksum3AI318Programmable Settings Checksum3AI319Write New Password3AI320Terminate Programmable Settings Update3AI321Set Meter Clock 1AI322Set Meter Clock 2AI323Set Meter Clock 3AI324Close Privileged Command SessionAO325CT multiplier & denominatorAO326CT numeratorAO327PT numeratorAO328PT denominatorAO329PT multiplier & hookup
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Eaton_PXM2000_Meter_LX.csv; the profile maps the registers in the maker's Modbus register document (https://www.ccontrols.com/support/dp/EatonPXM2000.PDF).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 95 of the 329 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (VAR-hours Net Phase C; Positive Watts Phase C Average; Angle Phase A Current...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Eaton Power Xpert PXM 2000 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
How many BACnet points does the Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX have?
This list has 329 BACnet objects: 254 analog inputs, 11 analog outputs, 48 binary inputs, 16 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX BACnet points are writable?
27 of the 329 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Eaton_PXM2000_Meter (Eaton_PXM2000_Meter_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Eaton_PXM2000_Meter_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX?
Start with AI 10 Watts 3-Ph total (Total watts (3-phase)); AI 29 W-hours Delivered (Delivered energy (Wh)); AI 28 W-hours Received (Received energy (Wh)); AI 4 Volts A-B (Voltage A-B); AI 7 Amps A (Current A); AI 13 Power Factor 3-Ph total (Total power factor); AI 14 Frequency (Frequency).
How do I check these points on the real Eaton Power Xpert PXM 2000 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Eaton_PXM2000_Meter · Eaton_PXM2000_Meter_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.