- Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
UPS (uninterruptible power supply) · BACnet points list
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the APC Symmetra PX 250/500 kW: 621 objects (241 AI, 380 BI), 335 polled by default. Binary inputs carry the UPS status and alarm flags (on battery, bypass, low battery, load not powered, warning and critical alarm, module failures, parallel faults); analog inputs give runtime, input/bypass/output voltages and frequencies, % load per phase and installation load.
This page lists 621 BACnet objects for the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 621 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Read on battery, bypass, load not powered and the warning/critical alarm flags, plus runtime and total % load.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 1 | Load is being powered from battery | Load on battery | Read |
| BI 3 | Bypass | Load on bypass | Read |
| BI 5 | Load not Powered | Load not powered | Read |
| AI 281 | Runtime remaining | Runtime remaining, s | Read |
| AI 358 | Total Percent load | Total load, % | Read |
| AI 338 | Voltage L1-2 (output) | Output voltage L1-L2 | Read |
| AI 337 | Frequency (output) | Output frequency | Read |
| BI 2 | Low-Battery | Low battery | Read |
| BI 12 | Warning alarm present | Warning alarm present | Read |
| BI 13 | Critical alarm present | Critical alarm present | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | Load is being powered from battery | Modbus 400001 bit 0 | Read | ||
| BImin | 2 | Low-Battery | Modbus 400001 bit 1 | Read | ||
| BImin | 3 | Bypass | Modbus 400001 bit 2 | Read | ||
| BI | 4 | Self-Test | Modbus 400001 bit 3 | Read | ||
| BImin | 5 | Load not Powered | Modbus 400001 bit 4 | Read | ||
| BI | 6 | Abnormal Condition | Modbus 400001 bit 7 | Read | ||
| BI | 7 | Power Module Failure | Modbus 400001 bit 8 | Read | ||
| BI | 8 | Battery System Failure | Modbus 400001 bit 9 | Read | ||
| BI | 9 | Intelligence Module (IM) has detected alarm condition | Modbus 400001 bit 10 | Read | ||
| BI | 10 | Static Switch failure | Modbus 400001 bit 11 | Read | ||
| BI | 11 | Power Supply Unit failure | Modbus 400001 bit 12 | Read | ||
| BImin | 12 | Warning alarm present | Modbus 400001 bit 14 | Read | ||
| BImin | 13 | Critical alarm present | Modbus 400001 bit 15 | Read | ||
| BI | 14 | Lost local network management interface - to - UPS communication | Modbus 400003 bit 0 | Read | ||
| BI | 15 | Parallel PBUS cables are swapped | Modbus 400003 bit 1 | Read | ||
| BI | 16 | Parallel communication error on PBUS cable 1 | Modbus 400003 bit 2 | Read | ||
| BI | 17 | Parallel communication error on PBUS cable 2 | Modbus 400003 bit 3 | Read | ||
| BI | 18 | Overload on parallel installation | Modbus 400003 bit 4 | Read | ||
| BI | 19 | Parallel mixed mode error | Modbus 400003 bit 5 | Read | ||
| BI | 20 | UPS parallel address configuration number error | Modbus 400003 bit 6 | Read | ||
| BI | 21 | Parallel master not detected (deprecated) | Modbus 400003 bit 7 | Read | ||
| BI | 22 | Parallel unit disabled | Modbus 400003 bit 8 | Read | ||
| BI | 23 | Parallel unit is incompatible | Modbus 400003 bit 9 | Read | ||
| BI | 24 | PBUS cable termination fault | Modbus 400003 bit 10 | Read | ||
| BI | 25 | Parallel unit not present (deprecated) | Modbus 400003 bit 11 | Read | ||
| BI | 26 | Isolated Test mode is activate | Modbus 400003 bit 12 | Read | ||
| BI | 27 | Parallel unit redundancy lost | Modbus 400003 bit 13 | Read | ||
| BI | 28 | Parallel load share error | Modbus 400003 bit 15 | Read | ||
| BI | 29 | On battery in response to an input power failure | Modbus 400004 bit 0 | Read | ||
| BI | 30 | In bypass: User-initiated from Front Panel | Modbus 400004 bit 1 | Read | ||
| BI | 31 | UPS operation mode - Forced bypass | Modbus 400004 bit 2 | Read | ||
| BI | 32 | In Bypass: For maintenance | Modbus 400004 bit 3 | Read | ||
| BI | 33 | Started a self-test | Modbus 400004 bit 4 | Read | ||
| BI | 34 | Output power turned off | Modbus 400004 bit 5 | Read | ||
| BI | 35 | UPS operation mode - Initialize | Modbus 400004 bit 6 | Read | ||
| BI | 36 | UPS operation mode - Hot standby | Modbus 400004 bit 7 | Read | ||
| BI | 37 | Compensating for a low input voltage | Modbus 400004 bit 8 | Read | ||
| BI | 38 | Compensating for a high input voltage | Modbus 400004 bit 9 | Read | ||
| BI | 39 | Input voltage waveform error detected | Modbus 400004 bit 10 | Read | ||
| BI | 40 | Input phase sequence error | Modbus 400004 bit 11 | Read | ||
| BI | 41 | Input frequency fault | Modbus 400004 bit 12 | Read | ||
| BI | 42 | Output frequency fault | Modbus 400004 bit 13 | Read | ||
| BI | 43 | Mega Tie mode is active | Modbus 400004 bit 14 | Read | ||
| BI | 44 | Bypass voltage error: low voltage | Modbus 400005 bit 0 | Read | ||
| BI | 45 | Bypass voltage error: high voltage | Modbus 400005 bit 1 | Read | ||
| BI | 46 | Bypass voltage waveform error detected | Modbus 400005 bit 2 | Read | ||
| BI | 47 | Bypass input frequency fault | Modbus 400005 bit 3 | Read | ||
| BI | 48 | Bypass phase sequence error | Modbus 400005 bit 4 | Read | ||
| BI | 49 | Output voltage low | Modbus 400005 bit 5 | Read | ||
| BI | 50 | Output voltage high | Modbus 400005 bit 6 | Read | ||
| BI | 51 | Output voltage waveform error detected | Modbus 400005 bit 7 | Read | ||
| BI | 52 | Overload | Modbus 400005 bit 8 | Read | ||
| BI | 53 | Overload on bypass static switch | Modbus 400005 bit 9 | Read | ||
| BI | 54 | Ambient temperature out of range | Modbus 400005 bit 10 | Read | ||
| BI | 55 | EPO activated | Modbus 400005 bit 11 | Read | ||
| BI | 56 | Ground fault detected | Modbus 400005 bit 12 | Read | ||
| BI | 57 | PSU module failed | Modbus 400005 bit 13 | Read | ||
| BI | 58 | System locked in bypass operation | Modbus 400006 bit 0 | Read | ||
| BI | 59 | Batteries are discharging | Modbus 400006 bit 1 | Read | ||
| BI | 60 | PSU module not present | Modbus 400006 bit 2 | Read | ||
| BI | 61 | System frequency not detected | Modbus 400006 bit 3 | Read | ||
| BI | 62 | Charge power is reduced | Modbus 400006 bit 5 | Read | ||
| BI | 63 | Display communication to MIM and RIM is lost | Modbus 400006 bit 6 | Read | ||
| BI | 64 | CBUS terminator fault | Modbus 400006 bit 7 | Read | ||
| BI | 65 | ABUS terminator fault | Modbus 400006 bit 8 | Read | ||
| BI | 66 | MIM not present | Modbus 400006 bit 10 | Read | ||
| BI | 67 | MIM heartbeat signal error | Modbus 400006 bit 11 | Read | ||
| BI | 68 | RIM in control | Modbus 400006 bit 12 | Read | ||
| BI | 69 | Battery condition is weak | Modbus 400006 bit 13 | Read | ||
| BI | 70 | Battery condition is poor | Modbus 400006 bit 14 | Read | ||
| BI | 71 | Battery voltage error - voltage above warning level | Modbus 400007 bit 0 | Read | ||
| BI | 72 | Battery voltage error - voltage above shutdown level | Modbus 400007 bit 1 | Read | ||
| BI | 73 | Battery monitor board communication error | Modbus 400007 bit 2 | Read | ||
| BI | 74 | Battery is below minimum acceptable runtime | Modbus 400007 bit 4 | Read | ||
| BI | 75 | Power module communication to MIM error | Modbus 400007 bit 5 | Read | ||
| BI | 76 | Power module locked by IM | Modbus 400007 bit 6 | Read | ||
| BI | 77 | Power module operation mode is different from other modules | Modbus 400007 bit 7 | Read | ||
| BI | 78 | Switchgear board not present | Modbus 400007 bit 9 | Read | ||
| BI | 79 | Switchgear board communication error | Modbus 400007 bit 10 | Read | ||
| BI | 80 | ID Relay board not present | Modbus 400007 bit 11 | Read | ||
| BI | 81 | ID Relay board communication error | Modbus 400007 bit 12 | Read | ||
| BI | 82 | Battery voltage collapse detected | Modbus 400007 bit 13 | Read | ||
| BI | 83 | Power module redundancy lost | Modbus 400007 bit 14 | Read | ||
| BI | 84 | Load on subfeed is above warning level | Modbus 400008 bit 7 | Read | ||
| BI | 85 | Load on subfeed is above critical level | Modbus 400008 bit 8 | Read | ||
| BI | 86 | Load on UPS is above warning level | Modbus 400008 bit 9 | Read | ||
| BI | 87 | Power module firmware version is incompatible | Modbus 400008 bit 10 | Read | ||
| BI | 88 | Static Bypass Switch module not present | Modbus 400008 bit 11 | Read | ||
| BI | 89 | Overload on installation | Modbus 400008 bit 12 | Read | ||
| BI | 90 | Bypass static switch communication error | Modbus 400008 bit 13 | Read | ||
| BI | 91 | RIM not present | Modbus 400008 bit 14 | Read | ||
| BI | 92 | RIM heartbeat signal error | Modbus 400008 bit 15 | Read | ||
| BI | 93 | Bonding wire between neutral and ground is missing | Modbus 400009 bit 0 | Read | ||
| BI | 94 | Bonding wire between neutral and ground error | Modbus 400009 bit 1 | Read | ||
| BI | 95 | Power module communication to RIM error | Modbus 400009 bit 2 | Read | ||
| BI | 96 | Battery voltage error - voltage below warning level | Modbus 400009 bit 3 | Read | ||
| BI | 97 | Battery voltage error - voltage below shutdown level | Modbus 400009 bit 4 | Read | ||
| BI | 98 | ECT board has an error | Modbus 400009 bit 5 | Read | ||
| BI | 99 | External connections board not present | Modbus 400009 bit 6 | Read | ||
| BI | 100 | EPO circuit test mode is enabled | Modbus 400009 bit 7 | Read | ||
| BI | 101 | IM internal memory for storing configuration settings error | Modbus 400009 bit 8 | Read | ||
| BI | 102 | Auxiliary monitor board for maintenance bypass panel comm error | Modbus 400009 bit 10 | Read | ||
| BI | 103 | Auxiliary monitor board for battery breaker enclosure comm error | Modbus 400009 bit 11 | Read | ||
| BI | 104 | Power module removed from the system | Modbus 400009 bit 13 | Read | ||
| BI | 105 | INFO Battery module removed from system | Modbus 400009 bit 14 | Read | ||
| BI | 106 | Power module fault exists | Modbus 400010 bit 0 | Read | ||
| BI | 107 | Power module warning | Modbus 400010 bit 1 | Read | ||
| BI | 108 | Power module fan fault | Modbus 400010 bit 3 | Read | ||
| BI | 109 | Power module is disabled | Modbus 400010 bit 4 | Read | ||
| BI | 110 | Power module lifetime error: close to end | Modbus 400010 bit 5 | Read | ||
| BI | 111 | Power module lifetime error: lifetime exceeded | Modbus 400010 bit 6 | Read | ||
| BI | 112 | Power module fan lifetime error: close to end | Modbus 400010 bit 7 | Read | ||
| BI | 113 | Power module fan lifetimerror: lifetime exceeded | Modbus 400010 bit 8 | Read | ||
| BI | 114 | Breaker Q1 open | Modbus 400010 bit 9 | Read | ||
| BI | 115 | Breaker Q2 open | Modbus 400010 bit 10 | Read | ||
| BI | 116 | Breaker Q3 closed | Modbus 400010 bit 11 | Read | ||
| BI | 117 | Breaker Q4 open | Modbus 400010 bit 12 | Read | ||
| BI | 118 | Breaker Q5 open | Modbus 400010 bit 13 | Read | ||
| BI | 119 | Power module phase-neutral displacement fault | Modbus 400010 bit 14 | Read | ||
| BI | 120 | Forced bypass switch activated | Modbus 400011 bit 0 | Read | ||
| BI | 121 | Bypass static switch disabled | Modbus 400011 bit 1 | Read | ||
| BI | 122 | Bypass static switch self test failed | Modbus 400011 bit 2 | Read | ||
| BI | 123 | Bypass static switch 1 fan fault | Modbus 400011 bit 4 | Read | ||
| BI | 124 | Bypass static switch 1 fan weak | Modbus 400011 bit 5 | Read | ||
| BI | 125 | Bypass static switch error; module has a critical error | Modbus 400011 bit 8 | Read | ||
| BI | 126 | Bypass static switch warning; module is not working properly | Modbus 400011 bit 9 | Read | ||
| BI | 127 | Power enclosure air filter lifetime error: lifetime exceeded | Modbus 400011 bit 10 | Read | ||
| BI | 128 | Power enclosure air filter lifetime error: lifetime exceeded | Modbus 400011 bit 11 | Read | ||
| BI | 129 | Door in MBwD enclosure open | Modbus 400011 bit 14 | Read | ||
| BI | 130 | Q2 shunt open error | Modbus 400011 bit 15 | Read | ||
| BI | 131 | Subfeed breaker SB1 open | Modbus 400012 bit 0 | Read | ||
| BI | 132 | Subfeed breaker SB2 open | Modbus 400012 bit 1 | Read | ||
| BI | 133 | Subfeed breaker SB3 open | Modbus 400012 bit 2 | Read | ||
| BI | 134 | Subfeed breaker SB4 open | Modbus 400012 bit 3 | Read | ||
| BI | 135 | Subfeed breaker SB5 open | Modbus 400012 bit 4 | Read | ||
| BI | 136 | Subfeed breaker SB6 open | Modbus 400012 bit 5 | Read | ||
| BI | 137 | Subfeed breaker SB7 open | Modbus 400012 bit 6 | Read | ||
| BI | 138 | Subfeed breaker SB8 open | Modbus 400012 bit 7 | Read | ||
| BI | 139 | Subfeed breaker SB9 open | Modbus 400012 bit 8 | Read | ||
| BI | 140 | Subfeed breaker SB10 open | Modbus 400012 bit 9 | Read | ||
| BI | 141 | Subfeed breaker SB11 open | Modbus 400012 bit 10 | Read | ||
| BI | 142 | Subfeed breaker SB12 open | Modbus 400012 bit 11 | Read | ||
| BI | 143 | Subfeed breaker SB13 open | Modbus 400012 bit 12 | Read | ||
| BI | 144 | Subfeed breaker SB14 open | Modbus 400012 bit 13 | Read | ||
| BI | 145 | Subfeed breaker SB15 open | Modbus 400012 bit 14 | Read | ||
| BI | 146 | Subfeed breaker SB16 open | Modbus 400012 bit 15 | Read | ||
| BI | 147 | Breaker Q1 open | Modbus 400013 bit 0 | Read | ||
| BI | 148 | Breaker Q2 open | Modbus 400013 bit 1 | Read | ||
| BI | 149 | Breaker Q3 closed | Modbus 400013 bit 2 | Read | ||
| BI | 150 | Breaker Q4 open | Modbus 400013 bit 3 | Read | ||
| BI | 151 | Breaker Q5 open | Modbus 400013 bit 4 | Read | ||
| BI | 152 | Door in maintenance bypass panel enclosure open | Modbus 400013 bit 5 | Read | ||
| BI | 153 | Q2 shunt open error | Modbus 400013 bit 6 | Read | ||
| BI | 154 | MBP enclosure ECT board has an error | Modbus 400013 bit 7 | Read | ||
| BI | 155 | ID Relay board memory card full | Modbus 400013 bit 8 | Read | ||
| BI | 156 | Input 3 activated: Battery ground fault detected | Modbus 400013 bit 9 | Read | ||
| BI | 157 | ID Relay board: System firmware not stored at memory card | Modbus 400013 bit 10 | Read | ||
| BI | 158 | Input 6 activated: Emergency module off | Modbus 400013 bit 11 | Read | ||
| BI | 159 | Input 7 activated: Door in UPS I/O enclosure opened | Modbus 400013 bit 12 | Read | ||
| BI | 160 | Input 1 activated: Reduce charging power | Modbus 400013 bit 13 | Read | ||
| BI | 161 | IDRC memory card not present | Modbus 400013 bit 14 | Read | ||
| BI | 162 | ID Relay board memory card error | Modbus 400013 bit 15 | Read | ||
| BI | 163 | Battery breaker open | Modbus 400014 bit 0 | Read | ||
| BI | 164 | Battery module fuse cleared or condition of battery is weak | Modbus 400014 bit 1 | Read | ||
| BI | 165 | Battery voltage symmetry error | Modbus 400014 bit 2 | Read | ||
| BI | 166 | Internal battery temperature exceeds threshold | Modbus 400014 bit 3 | Read | ||
| BI | 167 | Battery temperature sensor fault | Modbus 400014 bit 5 | Read | ||
| BI | 168 | Mixed battery configuration | Modbus 400014 bit 6 | Read | ||
| BI | 169 | Battery module type support error | Modbus 400014 bit 7 | Read | ||
| BI | 170 | Battery string disconnected | Modbus 400014 bit 8 | Read | ||
| BI | 171 | Battery side car 1 fuse error | Modbus 400014 bit 9 | Read | ||
| BI | 172 | Battery enclosure PSU error | Modbus 400014 bit 11 | Read | ||
| BI | 173 | Battery breaker motor PSU error | Modbus 400014 bit 12 | Read | ||
| BI | 174 | Battery enclosure door open | Modbus 400014 bit 13 | Read | ||
| BI | 175 | ECT board has an error | Modbus 400014 bit 14 | Read | ||
| BI | 176 | Battery breaker shunt open error | Modbus 400014 bit 15 | Read | ||
| BI | 177 | Battery breaker open error | Modbus 400015 bit 0 | Read | ||
| BI | 178 | Battery breaker enclosure fuse 1 error | Modbus 400015 bit 1 | Read | ||
| BI | 179 | Battery breaker enclosure fuse 2 error | Modbus 400015 bit 2 | Read | ||
| BI | 180 | Battery temperature 1 high | Modbus 400015 bit 3 | Read | ||
| BI | 181 | Battery temperature 2 high | Modbus 400015 bit 4 | Read | ||
| BI | 182 | Battery temperature sensor 1 fault | Modbus 400015 bit 5 | Read | ||
| BI | 183 | Battery temperature sensor 2 fault | Modbus 400015 bit 6 | Read | ||
| BI | 184 | Battery breaker enclosure door open error | Modbus 400015 bit 7 | Read | ||
| BI | 185 | Battery breaker enclosure ECT board has an error | Modbus 400015 bit 8 | Read | ||
| BI | 186 | Battery breaker shunt open error | Modbus 400015 bit 9 | Read | ||
| BI | 187 | Battery ground fault detected error | Modbus 400015 bit 10 | Read | ||
| BI | 188 | Battery fuse bank 1 cleared | Modbus 400016 bit 0 | Read | ||
| BI | 189 | Battery fuse bank 2 cleared | Modbus 400016 bit 1 | Read | ||
| BI | 190 | Battery fuse bank 3 cleared | Modbus 400016 bit 2 | Read | ||
| BI | 191 | Battery fuse bank 4 cleared | Modbus 400016 bit 3 | Read | ||
| BI | 192 | Battery fuse bank 5 cleared | Modbus 400016 bit 4 | Read | ||
| BI | 193 | Battery fuse bank 6 cleared | Modbus 400016 bit 5 | Read | ||
| BI | 194 | Battery fuse bank 7 cleared | Modbus 400016 bit 6 | Read | ||
| BI | 195 | Battery fuse bank 8 cleared | Modbus 400016 bit 7 | Read | ||
| BI | 196 | Input for gas alarm has been activated | Modbus 400016 bit 8 | Read | ||
| BI | 197 | Test firmware installed at power module | Modbus 400017 bit 0 | Read | ||
| BI | 198 | Not expected firmware installed at power module | Modbus 400017 bit 1 | Read | ||
| BI | 199 | Not expected firmware installed at battery monitor board | Modbus 400017 bit 2 | Read | ||
| BI | 200 | Not expected firmware installed at SBS module | Modbus 400017 bit 3 | Read | ||
| BI | 201 | Not expected firmware installed at ID Relay board | Modbus 400017 bit 4 | Read | ||
| BI | 202 | Not expected firmware installed at switchgear board | Modbus 400017 bit 5 | Read | ||
| BI | 203 | Not expected firmware installed at auxiliary board | Modbus 400017 bit 6 | Read | ||
| BI | 204 | Not expected firmware installed at aux mon bd for battery break | Modbus 400017 bit 7 | Read | ||
| BI | 205 | Not expected firmware installed at redundant IM | Modbus 400017 bit 8 | Read | ||
| BI | 206 | Test firmware installed at battery monitor board | Modbus 400017 bit 9 | Read | ||
| BI | 207 | Test firmware installed at SBS module | Modbus 400017 bit 10 | Read | ||
| BI | 208 | Test firmware installed at ID Relay board | Modbus 400017 bit 11 | Read | ||
| BI | 209 | Test firmware installed at switchgear board | Modbus 400017 bit 12 | Read | ||
| BI | 210 | Test firmware installed at aux mon board for maint bypass panel | Modbus 400017 bit 13 | Read | ||
| BI | 211 | Test firmware installed at aux mon bd for battery break enc | Modbus 400017 bit 14 | Read | ||
| BI | 212 | Test firmware installed at IM | Modbus 400017 bit 15 | Read | ||
| AI | 213 | ASCII 01 NMC Model Number | Modbus 404097; not polled by default | Read | ||
| AI | 214 | ASCII 02 NMC Model Number | Modbus 404098; not polled by default | Read | ||
| AI | 215 | ASCII 03 NMC Model Number | Modbus 404099; not polled by default | Read | ||
| AI | 216 | ASCII 04 NMC Model Number | Modbus 404100; not polled by default | Read | ||
| AI | 217 | ASCII 05 NMC Model Number | Modbus 404101; not polled by default | Read | ||
| AI | 218 | ASCII 06 NMC Model Number | Modbus 404102; not polled by default | Read | ||
| AI | 219 | ASCII 07 NMC Model Number | Modbus 404103; not polled by default | Read | ||
| AI | 220 | ASCII 08 NMC Model Number | Modbus 404104; not polled by default | Read | ||
| AI | 221 | ASCII 09 NMC Model Number | Modbus 404105; not polled by default | Read | ||
| AI | 222 | ASCII 01 NMC Serial Number | Modbus 404106; not polled by default | Read | ||
| AI | 223 | ASCII 02 NMC Serial Number | Modbus 404107; not polled by default | Read | ||
| AI | 224 | ASCII 03 NMC Serial Number | Modbus 404108; not polled by default | Read | ||
| AI | 225 | ASCII 04 NMC Serial Number | Modbus 404109; not polled by default | Read | ||
| AI | 226 | ASCII 05 NMC Serial Number | Modbus 404110; not polled by default | Read | ||
| AI | 227 | ASCII 06 NMC Serial Number | Modbus 404111; not polled by default | Read | ||
| AI | 228 | ASCII 07 NMC Serial Number | Modbus 404112; not polled by default | Read | ||
| AI | 229 | ASCII 08 NMC Serial Number | Modbus 404113; not polled by default | Read | ||
| AI | 230 | ASCII 01 NMC Firmware Revision APP | Modbus 404114; not polled by default | Read | ||
| AI | 231 | ASCII 02 NMC Firmware Revision APP | Modbus 404115; not polled by default | Read | ||
| AI | 232 | ASCII 03 NMC Firmware Revision APP | Modbus 404116; not polled by default | Read | ||
| AI | 233 | ASCII 04 NMC Firmware Revision APP | Modbus 404117; not polled by default | Read | ||
| AI | 234 | ASCII 05 NMC Firmware Revision APP | Modbus 404118; not polled by default | Read | ||
| AI | 235 | ASCII 06 NMC Firmware Revision APP | Modbus 404119; not polled by default | Read | ||
| AI | 236 | ASCII 07 NMC Firmware Revision APP | Modbus 404120; not polled by default | Read | ||
| AI | 237 | ASCII 08 NMC Firmware Revision APP | Modbus 404121; not polled by default | Read | ||
| AI | 238 | ASCII 09 NMC Firmware Revision APP | Modbus 404122; not polled by default | Read | ||
| AI | 239 | ASCII 01 NMC Hardware Revision | Modbus 404123; not polled by default | Read | ||
| AI | 240 | ASCII 02 NMC Hardware Revision | Modbus 404124; not polled by default | Read | ||
| AI | 241 | ASCII 03 NMC Hardware Revision | Modbus 404125; not polled by default | Read | ||
| AI | 242 | ASCII 04 NMC Hardware Revision | Modbus 404126; not polled by default | Read | ||
| AI | 243 | ASCII 05 NMC Hardware Revision | Modbus 404127; not polled by default | Read | ||
| AI | 244 | ASCII 06 NMC Hardware Revision | Modbus 404128; not polled by default | Read | ||
| AI | 245 | ASCII 07 NMC Hardware Revision | Modbus 404129; not polled by default | Read | ||
| AI | 246 | ASCII 08 NMC Hardware Revision | Modbus 404130; not polled by default | Read | ||
| AI | 247 | ASCII 09 NMC Hardware Revision | Modbus 404131; not polled by default | Read | ||
| AI | 248 | ASCII 01 NMC Date of Manufacture | Modbus 404132; not polled by default | Read | ||
| AI | 249 | ASCII 02 NMC Date of Manufacture | Modbus 404133; not polled by default | Read | ||
| AI | 250 | ASCII 03 NMC Date of Manufacture | Modbus 404134; not polled by default | Read | ||
| AI | 251 | ASCII 04 NMC Date of Manufacture | Modbus 404135; not polled by default | Read | ||
| AI | 252 | ASCII 05 NMC Date of Manufacture | Modbus 404136; not polled by default | Read | ||
| AI | 253 | ASCII 06 NMC Date of Manufacture | Modbus 404137; not polled by default | Read | ||
| AI | 254 | ASCII 01 UPS Model Name | Modbus 404138; not polled by default | Read | ||
| AI | 255 | ASCII 02 UPS Model Name | Modbus 404139; not polled by default | Read | ||
| AI | 256 | ASCII 03 UPS Model Name | Modbus 404140; not polled by default | Read | ||
| AI | 257 | ASCII 04 UPS Model Name | Modbus 404141; not polled by default | Read | ||
| AI | 258 | ASCII 05 UPS Model Name | Modbus 404142; not polled by default | Read | ||
| AI | 259 | ASCII 06 UPS Model Name | Modbus 404143; not polled by default | Read | ||
| AI | 260 | ASCII 07 UPS Model Name | Modbus 404144; not polled by default | Read | ||
| AI | 261 | ASCII 08 UPS Model Name | Modbus 404145; not polled by default | Read | ||
| AI | 262 | ASCII 01 UPS Serial Number | Modbus 404146; not polled by default | Read | ||
| AI | 263 | ASCII 02 UPS Serial Number | Modbus 404147; not polled by default | Read | ||
| AI | 264 | ASCII 03 UPS Serial Number | Modbus 404148; not polled by default | Read | ||
| AI | 265 | ASCII 04 UPS Serial Number | Modbus 404149; not polled by default | Read | ||
| AI | 266 | ASCII 05 UPS Serial Number | Modbus 404150; not polled by default | Read | ||
| AI | 267 | ASCII 06 UPS Serial Number | Modbus 404151; not polled by default | Read | ||
| AI | 268 | ASCII 01 UPS Firmware Version | Modbus 404152; not polled by default | Read | ||
| AI | 269 | ASCII 02 UPS Firmware Version | Modbus 404153; not polled by default | Read | ||
| AI | 270 | ASCII 03 UPS Firmware Version | Modbus 404154; not polled by default | Read | ||
| AI | 271 | ASCII 04 UPS Firmware Version | Modbus 404155; not polled by default | Read | ||
| AI | 272 | ASCII 05 UPS Firmware Version | Modbus 404156; not polled by default | Read | ||
| AI | 273 | ASCII 06 UPS Firmware Version | Modbus 404157; not polled by default | Read | ||
| AI | 274 | ASCII 07 UPS Firmware Version | Modbus 404158; not polled by default | Read | ||
| AI | 275 | ASCII 08 UPS Firmware Version | Modbus 404159; not polled by default | Read | ||
| AI | 276 | ASCII 09 UPS Firmware Version | Modbus 404160; not polled by default | Read | ||
| AI | 277 | ASCII 10 UPS Firmware Version | Modbus 404161; not polled by default | Read | ||
| AI | 278 | ASCII 11 UPS Firmware Version | Modbus 404162; not polled by default | Read | ||
| AI | 279 | ASCII 12 UPS Firmware Version | Modbus 404163; not polled by default | Read | ||
| AI | 280 | Time on battery | Modbus 404353 | s | Read | |
| AImin | 281 | Runtime remaining | Modbus 404355 | s | Read | |
| AI | 282 | Estimated charge time | Modbus 404357 | s | Read | |
| AI | 283 | Estimated charge % | Modbus 404359 | % | Read | |
| AI | 284 | Battery (+) Voltage | Modbus 404360 | V | Read | |
| AI | 285 | Battery (-) Voltage | Modbus 404361 | V | Read | |
| AI | 286 | Battery (+) Current | Modbus 404362 | A | Read | |
| AI | 287 | Battery (-) Current | Modbus 404363 | A | Read | |
| AI | 288 | Total time on battery | Modbus 404364 | s | Read | |
| AI | 289 | Total number of times on battery | Modbus 404366 | Read | ||
| AI | 290 | APC Battery Breaker Status /User supplied battery Breaker Status | Modbus 404367 | Read | ||
| AI | 291 | BatterySystem/Temperature | Modbus 404368 | °C | Read | |
| BI | 292 | User Supplied Battery System Charger Status | Modbus 404369 bit 0 | Read | ||
| BI | 293 | Boost Charging | Modbus 404369 bit 1 | Read | ||
| BI | 294 | Normal Charging | Modbus 404369 bit 2 | Read | ||
| BI | 295 | Resting | Modbus 404369 bit 3 | Read | ||
| BI | 296 | Discharging | Modbus 404369 bit 4 | Read | ||
| BI | 297 | Equalization Charging | Modbus 404369 bit 5 | Read | ||
| AI | 298 | Battery Power | Modbus 404370 | kW | Read | |
| AI | 299 | Available Amp Hours | Modbus 404371 | Read | ||
| AI | 300 | Frequency (input) | Modbus 404609 | Hz | Read | |
| AI | 301 | Voltage L1-2 (input) | Modbus 404610 | V | Read | |
| AI | 302 | Voltage L2-3 (input) | Modbus 404611 | V | Read | |
| AI | 303 | Voltage L3-1 (input) | Modbus 404612 | V | Read | |
| AI | 304 | Current L1 (input) | Modbus 404613 | A | Read | |
| AI | 305 | Current L2 (input) | Modbus 404614 | A | Read | |
| AI | 306 | Current L3 (input) | Modbus 404615 | A | Read | |
| AI | 307 | Active power L1 (input) | Modbus 404616 | kW | Read | |
| AI | 308 | Active power L2 (input) | Modbus 404617 | kW | Read | |
| AI | 309 | Active power L3 (input) | Modbus 404618 | kW | Read | |
| AI | 310 | Apparent power L1 (input) | Modbus 404619 | kVA | Read | |
| AI | 311 | Apparent power L2 (input) | Modbus 404620 | kVA | Read | |
| AI | 312 | Apparent power L3 (input) | Modbus 404621 | kVA | Read | |
| AI | 313 | Total active power (input) | Modbus 404622 | kW | Read | |
| AI | 314 | Total apparent power (input) | Modbus 404623 | kVA | Read | |
| AI | 315 | Current L1 (parallel input) | Modbus 404624 | A | Read | |
| AI | 316 | Current L2 (parallel input) | Modbus 404625 | A | Read | |
| AI | 317 | Current L3 (parallel input) | Modbus 404626 | A | Read | |
| AI | 318 | Frequency (bypass) | Modbus 404865 | Hz | Read | |
| AI | 319 | Voltage L1-2 (bypass) | Modbus 404866 | V | Read | |
| AI | 320 | Voltage L2-3 (bypass) | Modbus 404867 | V | Read | |
| AI | 321 | Voltage L3-1 (bypass) | Modbus 404868 | V | Read | |
| AI | 322 | Current L1 (bypass) | Modbus 404869 | A | Read | |
| AI | 323 | Current L2 (bypass) | Modbus 404870 | A | Read | |
| AI | 324 | Current L3 (bypass) | Modbus 404871 | A | Read | |
| AI | 325 | Active power L1 (bypass) | Modbus 404872 | kW | Read | |
| AI | 326 | Active power L2 (bypass) | Modbus 404873 | kW | Read | |
| AI | 327 | Active power L3 (bypass) | Modbus 404874 | kW | Read | |
| AI | 328 | Apparent power L1 (bypass) | Modbus 404875 | kVA | Read | |
| AI | 329 | Apparent power L2 (bypass) | Modbus 404876 | kVA | Read | |
| AI | 330 | Apparent power L3 (bypass) | Modbus 404877 | kVA | Read | |
| AI | 331 | Total active power (bypass) | Modbus 404878 | kW | Read | |
| AI | 332 | Total apparent power (bypass) | Modbus 404879 | kVA | Read | |
| AI | 333 | Current L1 (parallel bypass) | Modbus 404880 | A | Read | |
| AI | 334 | Current L2 (parallel bypass) | Modbus 404881 | A | Read | |
| AI | 335 | Current L3 (parallel bypass) | Modbus 404882 | A | Read | |
| AI | 336 | Nominal (Apparent) output rating | Modbus 405121 | kVA | Read | |
| AImin | 337 | Frequency (output) | Modbus 405122 | Hz | Read | |
| AImin | 338 | Voltage L1-2 (output) | Modbus 405123 | V | Read | |
| AI | 339 | Voltage L2-3 (output) | Modbus 405124 | V | Read | |
| AI | 340 | Voltage L3-1 (output) | Modbus 405125 | V | Read | |
| AI | 341 | Current L1 (output) | Modbus 405126 | A | Read | |
| AI | 342 | Current L2 (output) | Modbus 405127 | A | Read | |
| AI | 343 | Current L3 (output) | Modbus 405128 | A | Read | |
| AI | 344 | Peak current L1 (output) | Modbus 405129 | A | Read | |
| AI | 345 | Peak current L2 (output) | Modbus 405131 | A | Read | |
| AI | 346 | Peak current L3 (output) | Modbus 405133 | A | Read | |
| AI | 347 | Active power L1 (output) | Modbus 405135 | kW | Read | |
| AI | 348 | Active power L2 (output) | Modbus 405136 | kW | Read | |
| AI | 349 | Active power L3 (output) | Modbus 405137 | kW | Read | |
| AI | 350 | Apparent power L1 (output) | Modbus 405138 | kVA | Read | |
| AI | 351 | Apparent power L2 (output) | Modbus 405139 | kVA | Read | |
| AI | 352 | Apparent power L3 (output) | Modbus 405140 | kVA | Read | |
| AI | 353 | % Load L1 | Modbus 405141 | % | Read | |
| AI | 354 | % Load L2 | Modbus 405142 | % | Read | |
| AI | 355 | % Load L3 | Modbus 405143 | % | Read | |
| AI | 356 | Total active power (output) | Modbus 405144 | kW | Read | |
| AI | 357 | Total apparent power (output) | Modbus 405145 | kVA | Read | |
| AImin | 358 | Total Percent load | Modbus 405146 | % | Read | |
| AI | 359 | Power factor L1 (output) | Modbus 405147 | PF | Read | |
| AI | 360 | Power factor L2 (output) | Modbus 405148 | PF | Read | |
| AI | 361 | Power factor L3 (output) | Modbus 405149 | PF | Read | |
| AI | 362 | Current crest factor L1 (output) | Modbus 405150 | Read | ||
| AI | 363 | Current crest factor L2 (output) | Modbus 405151 | Read | ||
| AI | 364 | Current crest factor L3 (output) | Modbus 405152 | Read | ||
| AI | 365 | Parallel System Output CurrentAC L1 | Modbus 405153 | A | Read | |
| AI | 366 | Parallel System Output CurrentAC L2 | Modbus 405154 | A | Read | |
| AI | 367 | Parallel System Output CurrentAC L3 | Modbus 405155 | A | Read | |
| AI | 368 | Parallel System Output Active Power L1 | Modbus 405156 | kW | Read | |
| AI | 369 | Parallel System Output Active Power L2 | Modbus 405157 | kW | Read | |
| AI | 370 | Parallel System Output Active Power L3 | Modbus 405158 | kW | Read | |
| AI | 371 | Parallel System Output Apparent Power L1 | Modbus 405159 | kVA | Read | |
| AI | 372 | Parallel System Output Apparent Power L2 | Modbus 405160 | kVA | Read | |
| AI | 373 | Parallel System Output Apparent Power L3 | Modbus 405161 | kVA | Read | |
| AI | 374 | ParallelSystem Output % Load L1 | Modbus 405162 | % | Read | |
| AI | 375 | ParallelSystem Output % Load L2 | Modbus 405163 | % | Read | |
| AI | 376 | ParallelSystem Output % Load L3 | Modbus 405164 | % | Read | |
| AI | 377 | ParallelSystem Output Total Active Power | Modbus 405165 | kW | Read | |
| AI | 378 | ParallelSystem Output Total Apparent Power | Modbus 405166 | kVA | Read | |
| AI | 379 | ParallelSystem Output Total % Load | Modbus 405167 | % | Read | |
| AI | 380 | Energy Meter kwH | Modbus 405168 | kWh | Read | |
| AI | 381 | UPS Installation Load % (Standalone ) | Modbus 405170 | % | Read | |
| AI | 382 | UPS Installation Load % (Parallel ) | Modbus 405171 | % | Read | |
| AI | 383 | Ambient temperature | Modbus 405377 | °C | Read | |
| BI | 384 | Q1 | Modbus 405378 bit 0 | Read | ||
| BI | 385 | Q2 | Modbus 405378 bit 1 | Read | ||
| BI | 386 | Q3 | Modbus 405378 bit 2 | Read | ||
| BI | 387 | Q5 | Modbus 405378 bit 4 | Read | ||
| AI | 388 | UPS Mode Operation mode of the UPS | Modbus 405379 | Read | ||
| AI | 389 | Number of Active Alarms | Modbus 405380 | Read | ||
| AI | 390 | Highest alarm severity | Modbus 405381 | Read | ||
| AI | 391 | System Mode | Modbus 405382 | Read | ||
| BI | 392 | Input 01 Contact Status | Modbus 405383 bit 0; not polled by default | Read | ||
| BI | 393 | Input 02 Contact Status | Modbus 405383 bit 1; not polled by default | Read | ||
| BI | 394 | Input 03 Contact Status | Modbus 405383 bit 2; not polled by default | Read | ||
| BI | 395 | Input 04 Contact Status | Modbus 405383 bit 3; not polled by default | Read | ||
| BI | 396 | Input 05 Contact Status | Modbus 405383 bit 4; not polled by default | Read | ||
| BI | 397 | Input 06 Contact Status | Modbus 405383 bit 5; not polled by default | Read | ||
| BI | 398 | Input 07 Contact Status | Modbus 405383 bit 6; not polled by default | Read | ||
| BI | 399 | Input 08 Contact Status | Modbus 405383 bit 7; not polled by default | Read | ||
| BI | 400 | Input 09 Contact Status | Modbus 405383 bit 8; not polled by default | Read | ||
| BI | 401 | Input 10 Contact Status | Modbus 405383 bit 9; not polled by default | Read | ||
| BI | 402 | Input 11 Contact Status | Modbus 405383 bit 10; not polled by default | Read | ||
| BI | 403 | Input 12 Contact Status | Modbus 405383 bit 11; not polled by default | Read | ||
| BI | 404 | Input 13 Contact Status | Modbus 405383 bit 12; not polled by default | Read | ||
| BI | 405 | Input 14 Contact Status | Modbus 405383 bit 13; not polled by default | Read | ||
| BI | 406 | Input 15 Contact Status | Modbus 405383 bit 14; not polled by default | Read | ||
| BI | 407 | Input 16 Contact Status | Modbus 405383 bit 15; not polled by default | Read | ||
| BI | 408 | Output 01 Contact Status | Modbus 405384 bit 0; not polled by default | Read | ||
| BI | 409 | Output 02 Contact Status | Modbus 405383 bit 1; not polled by default | Read | ||
| BI | 410 | Output 03 Contact Status | Modbus 405383 bit 2; not polled by default | Read | ||
| BI | 411 | Output 04 Contact Status | Modbus 405383 bit 3; not polled by default | Read | ||
| BI | 412 | Output 05 Contact Status | Modbus 405383 bit 4; not polled by default | Read | ||
| BI | 413 | Output 06 Contact Status | Modbus 405383 bit 5; not polled by default | Read | ||
| BI | 414 | Output 07 Contact Status | Modbus 405383 bit 6; not polled by default | Read | ||
| BI | 415 | Output 08 Contact Status | Modbus 405383 bit 7; not polled by default | Read | ||
| BI | 416 | Output 09 Contact Status | Modbus 405383 bit 8; not polled by default | Read | ||
| BI | 417 | Output 10 Contact Status | Modbus 405383 bit 9; not polled by default | Read | ||
| BI | 418 | Output 11 Contact Status | Modbus 405383 bit 10; not polled by default | Read | ||
| BI | 419 | Output 12 Contact Status | Modbus 405383 bit 11; not polled by default | Read | ||
| BI | 420 | Output 13 Contact Status | Modbus 405383 bit 12; not polled by default | Read | ||
| BI | 421 | Output 14 Contact Status | Modbus 405383 bit 13; not polled by default | Read | ||
| BI | 422 | Output 15 Contact Status | Modbus 405383 bit 14; not polled by default | Read | ||
| BI | 423 | Output 16 Contact Status | Modbus 405383 bit 15; not polled by default | Read | ||
| AI | 424 | Output Contact Normal State Setting | Modbus 405384 | Read | ||
| AI | 425 | Redundancy Status | Modbus 405385 | Read | ||
| AI | 426 | ASCII 01 NMC/UPS Time | Modbus 405386; not polled by default | Read | ||
| AI | 427 | ASCII 02 NMC/UPS Time | Modbus 405387; not polled by default | Read | ||
| AI | 428 | ASCII 03 NMC/UPS Time | Modbus 405388; not polled by default | Read | ||
| AI | 429 | ASCII 04 NMC/UPS Time | Modbus 405389; not polled by default | Read | ||
| AI | 430 | ASCII 01 NMC/UPS Daten | Modbus 405390; not polled by default | Read | ||
| AI | 431 | ASCII 02 NMC/UPS Daten | Modbus 405391; not polled by default | Read | ||
| AI | 432 | ASCII 03 NMC/UPS Daten | Modbus 405392; not polled by default | Read | ||
| AI | 433 | ASCII 04 NMC/UPS Daten | Modbus 405393; not polled by default | Read | ||
| AI | 434 | ASCII 05 NMC/UPS Daten | Modbus 405394; not polled by default | Read | ||
| AI | 435 | Parallel System Redundancy Status | Modbus 405395 | Read | ||
| BI | 436 | Bypass Life Time Status OK | Modbus 405633 bit 0 | Read | ||
| BI | 437 | Bypass Life Time Status Near End | Modbus 405633 bit 1 | Read | ||
| BI | 438 | Bypass Life Time Status Exceeded | Modbus 405633 bit 2 | Read | ||
| AI | 439 | Bypass Estimated Lifetime Remaining | Modbus 405634 | days | Read | |
| BI | 440 | Bypass Fan Life Time Status OK | Modbus 405635 bit 0 | Read | ||
| BI | 441 | Bypass Fan Life Time Status Near End | Modbus 405635 bit 1 | Read | ||
| BI | 442 | Bypass Fan Life Time Status Exceeded | Modbus 405635 bit 2 | Read | ||
| AI | 443 | Bypass Fan Estimated Lifetime Remaining | Modbus 405636 | days | Read | |
| BI | 444 | Frame[0] Power Module[0] Life Time Status OK | Modbus 405889 bit 0; not polled by default | Read | ||
| BI | 445 | Frame[0] Power Module[0] Life Time Status Near End | Modbus 405889 bit 1; not polled by default | Read | ||
| BI | 446 | Frame[0] Power Module[0] Life Time Status Exceeded | Modbus 405889 bit 2; not polled by default | Read | ||
| AI | 447 | Frame[0] Power Module[0] Estimated Lifetime Remaining | Modbus 405890; not polled by default | days | Read | |
| BI | 448 | Frame[0] Power Module[0] Fan Life Time Status OK | Modbus 405891 bit 0; not polled by default | Read | ||
| BI | 449 | Frame[0] Power Module[0] Fan Life Time Status Near End | Modbus 405891 bit 1; not polled by default | Read | ||
| BI | 450 | Frame[0] Power Module[0] Fan Life Time Status Exceeded | Modbus 405891 bit 2; not polled by default | Read | ||
| AI | 451 | Frame[0] Power Module[0] Fan Estimated Lifetime Remaining | Modbus 405892; not polled by default | days | Read | |
| BI | 452 | Frame[0] Power Module[1] Life Time Status OK | Modbus 405893 bit 0; not polled by default | Read | ||
| BI | 453 | Frame[0] Power Module[1] Life Time Status Near End | Modbus 405893 bit 1; not polled by default | Read | ||
| BI | 454 | Frame[0] Power Module[1] Life Time Status Exceeded | Modbus 405893 bit 2; not polled by default | Read | ||
| AI | 455 | Frame[0] Power Module[1] Estimated Lifetime Remaining | Modbus 405894; not polled by default | days | Read | |
| BI | 456 | Frame[0] Power Module[1] Fan Life Time Status OK | Modbus 405895 bit 0; not polled by default | Read | ||
| BI | 457 | Frame[0] Power Module[1] Fan Life Time Status Near End | Modbus 405895 bit 1; not polled by default | Read | ||
| BI | 458 | Frame[0] Power Module[1] Fan Life Time Status Exceeded | Modbus 405895 bit 2; not polled by default | Read | ||
| AI | 459 | Frame[0] Power Module[1] Fan Estimated Lifetime Remaining | Modbus 405896; not polled by default | days | Read | |
| BI | 460 | Frame[0] Power Module[2] Life Time Status OK | Modbus 405897 bit 0; not polled by default | Read | ||
| BI | 461 | Frame[0] Power Module[2] Life Time Status Near End | Modbus 405897 bit 1; not polled by default | Read | ||
| BI | 462 | Frame[0] Power Module[2] Life Time Status Exceeded | Modbus 405897 bit 2; not polled by default | Read | ||
| AI | 463 | Frame[0] Power Module[2] Estimated Lifetime Remaining | Modbus 405898; not polled by default | days | Read | |
| BI | 464 | Frame[0] Power Module[2] Fan Life Time Status OK | Modbus 405899 bit 0; not polled by default | Read | ||
| BI | 465 | Frame[0] Power Module[2] Fan Life Time Status Near End | Modbus 405899 bit 1; not polled by default | Read | ||
| BI | 466 | Frame[0] Power Module[2] Fan Life Time Status Exceeded | Modbus 405899 bit 2; not polled by default | Read | ||
| AI | 467 | Frame[0] Power Module[2] Fan Estimated Lifetime Remaining | Modbus 405900; not polled by default | days | Read | |
| BI | 468 | Frame[0] Power Module[3] Life Time Status OK | Modbus 405901 bit 0; not polled by default | Read | ||
| BI | 469 | Frame[0] Power Module[3] Life Time Status Near End | Modbus 405901 bit 1; not polled by default | Read | ||
| BI | 470 | Frame[0] Power Module[3] Life Time Status Exceeded | Modbus 405901 bit 2; not polled by default | Read | ||
| AI | 471 | Frame[0] Power Module[3] Estimated Lifetime Remaining | Modbus 405902; not polled by default | days | Read | |
| BI | 472 | Frame[0] Power Module[3] Fan Life Time Status OK | Modbus 405903 bit 0; not polled by default | Read | ||
| BI | 473 | Frame[0] Power Module[3] Fan Life Time Status Near End | Modbus 405903 bit 1; not polled by default | Read | ||
| BI | 474 | Frame[0] Power Module[3] Fan Life Time Status Exceeded | Modbus 405903 bit 2; not polled by default | Read | ||
| AI | 475 | Frame[0] Power Module[3] Fan Estimated Lifetime Remaining | Modbus 405904; not polled by default | days | Read | |
| BI | 476 | Frame[0] Power Module[4] Life Time Status OK | Modbus 405905 bit 0; not polled by default | Read | ||
| BI | 477 | Frame[0] Power Module[4] Life Time Status Near End | Modbus 405905 bit 1; not polled by default | Read | ||
| BI | 478 | Frame[0] Power Module[4] Life Time Status Exceeded | Modbus 405905 bit 2; not polled by default | Read | ||
| AI | 479 | Frame[0] Power Module[4] Estimated Lifetime Remaining | Modbus 405906; not polled by default | days | Read | |
| BI | 480 | Frame[0] Power Module[4] Fan Life Time Status OK | Modbus 405907 bit 0; not polled by default | Read | ||
| BI | 481 | Frame[0] Power Module[4] Fan Life Time Status Near End | Modbus 405907 bit 1; not polled by default | Read | ||
| BI | 482 | Frame[0] Power Module[4] Fan Life Time Status Exceeded | Modbus 405907 bit 2; not polled by default | Read | ||
| AI | 483 | Frame[0] Power Module[4] Fan Estimated Lifetime Remaining | Modbus 405908; not polled by default | days | Read | |
| BI | 484 | Frame[0] Power Module[5] Life Time Status OK | Modbus 405909 bit 0; not polled by default | Read | ||
| BI | 485 | Frame[0] Power Module[5] Life Time Status Near End | Modbus 405909 bit 1; not polled by default | Read | ||
| BI | 486 | Frame[0] Power Module[5] Life Time Status Exceeded | Modbus 405909 bit 2; not polled by default | Read | ||
| AI | 487 | Frame[0] Power Module[5] Estimated Lifetime Remaining | Modbus 405910; not polled by default | days | Read | |
| BI | 488 | Frame[0] Power Module[5] Fan Life Time Status OK | Modbus 405911 bit 0; not polled by default | Read | ||
| BI | 489 | Frame[0] Power Module[5] Fan Life Time Status Near End | Modbus 405911 bit 1; not polled by default | Read | ||
| BI | 490 | Frame[0] Power Module[5] Fan Life Time Status Exceeded | Modbus 405911 bit 2; not polled by default | Read | ||
| AI | 491 | Frame[0] Power Module[5] Fan Estimated Lifetime Remaining | Modbus 405912; not polled by default | days | Read | |
| BI | 492 | Frame[0] Power Module[6] Life Time Status OK | Modbus 405913 bit 0; not polled by default | Read | ||
| BI | 493 | Frame[0] Power Module[6] Life Time Status Near End | Modbus 405913 bit 1; not polled by default | Read | ||
| BI | 494 | Frame[0] Power Module[6] Life Time Status Exceeded | Modbus 405913 bit 2; not polled by default | Read | ||
| AI | 495 | Frame[0] Power Module[6] Estimated Lifetime Remaining | Modbus 405914; not polled by default | days | Read | |
| BI | 496 | Frame[0] Power Module[6] Fan Life Time Status OK | Modbus 405915 bit 0; not polled by default | Read | ||
| BI | 497 | Frame[0] Power Module[6] Fan Life Time Status Near End | Modbus 405915 bit 1; not polled by default | Read | ||
| BI | 498 | Frame[0] Power Module[6] Fan Life Time Status Exceeded | Modbus 405915 bit 2; not polled by default | Read | ||
| AI | 499 | Frame[0] Power Module[6] Fan Estimated Lifetime Remaining | Modbus 405916; not polled by default | days | Read | |
| BI | 500 | Frame[0] Power Module[7] Life Time Status OK | Modbus 405917 bit 0; not polled by default | Read | ||
| BI | 501 | Frame[0] Power Module[7] Life Time Status Near End | Modbus 405917 bit 1; not polled by default | Read | ||
| BI | 502 | Frame[0] Power Module[7] Life Time Status Exceeded | Modbus 405917 bit 2; not polled by default | Read | ||
| AI | 503 | Frame[0] Power Module[7] Estimated Lifetime Remaining | Modbus 405918; not polled by default | days | Read | |
| BI | 504 | Frame[0] Power Module[7] Fan Life Time Status OK | Modbus 405919 bit 0; not polled by default | Read | ||
| BI | 505 | Frame[0] Power Module[7] Fan Life Time Status Near End | Modbus 405919 bit 1; not polled by default | Read | ||
| BI | 506 | Frame[0] Power Module[7] Fan Life Time Status Exceeded | Modbus 405919 bit 2; not polled by default | Read | ||
| AI | 507 | Frame[0] Power Module[7] Fan Estimated Lifetime Remaining | Modbus 405920; not polled by default | days | Read | |
| BI | 508 | Frame[0] Power Module[8] Life Time Status OK | Modbus 405921 bit 0; not polled by default | Read | ||
| BI | 509 | Frame[0] Power Module[8] Life Time Status Near End | Modbus 405921 bit 1; not polled by default | Read | ||
| BI | 510 | Frame[0] Power Module[8] Life Time Status Exceeded | Modbus 405921 bit 2; not polled by default | Read | ||
| AI | 511 | Frame[0] Power Module[8] Estimated Lifetime Remaining | Modbus 405922; not polled by default | days | Read | |
| BI | 512 | Frame[0] Power Module[8] Fan Life Time Status OK | Modbus 405923 bit 0; not polled by default | Read | ||
| BI | 513 | Frame[0] Power Module[8] Fan Life Time Status Near End | Modbus 405923 bit 1; not polled by default | Read | ||
| BI | 514 | Frame[0] Power Module[8] Fan Life Time Status Exceeded | Modbus 405923 bit 2; not polled by default | Read | ||
| AI | 515 | Frame[0] Power Module[8] Fan Estimated Lifetime Remaining | Modbus 405924; not polled by default | days | Read | |
| BI | 516 | Frame[0] Power Module[9] Life Time Status OK | Modbus 405925 bit 0; not polled by default | Read | ||
| BI | 517 | Frame[0] Power Module[9] Life Time Status Near End | Modbus 405925 bit 1; not polled by default | Read | ||
| BI | 518 | Frame[0] Power Module[9] Life Time Status Exceeded | Modbus 405925 bit 2; not polled by default | Read | ||
| AI | 519 | Frame[0] Power Module[9] Estimated Lifetime Remaining | Modbus 405926; not polled by default | days | Read | |
| BI | 520 | Frame[0] Power Module[9] Fan Life Time Status OK | Modbus 405927 bit 0; not polled by default | Read | ||
| BI | 521 | Frame[0] Power Module[9] Fan Life Time Status Near End | Modbus 405927 bit 1; not polled by default | Read | ||
| BI | 522 | Frame[0] Power Module[9] Fan Life Time Status Exceeded | Modbus 405927 bit 2; not polled by default | Read | ||
| AI | 523 | Frame[0] Power Module[9] Fan Estimated Lifetime Remaining | Modbus 405928; not polled by default | days | Read | |
| BI | 524 | Frame[1]Power Module[0] Life Time Status OK | Modbus 406145 bit 0; not polled by default | Read | ||
| BI | 525 | Frame[1]Power Module[0] Life Time Status Near End | Modbus 406145 bit 1; not polled by default | Read | ||
| BI | 526 | Frame[1]Power Module[0] Life Time Status Exceeded | Modbus 406145 bit 2; not polled by default | Read | ||
| AI | 527 | Frame[1]Power Module[0] Estimated Lifetime Remaining | Modbus 406146; not polled by default | days | Read | |
| BI | 528 | Frame[1]Power Module[0] Fan Life Time Status OK | Modbus 406147 bit 0; not polled by default | Read | ||
| BI | 529 | Frame[1]Power Module[0] Fan Life Time Status Near End | Modbus 406147 bit 1; not polled by default | Read | ||
| BI | 530 | Frame[1]Power Module[0] Fan Life Time Status Exceeded | Modbus 406147 bit 2; not polled by default | Read | ||
| AI | 531 | Frame[1]Power Module[0] Fan Estimated Lifetime Remaining | Modbus 406148; not polled by default | days | Read | |
| BI | 532 | Frame[1]Power Module[1] Life Time Status OK | Modbus 406149 bit 0; not polled by default | Read | ||
| BI | 533 | Frame[1]Power Module[1] Life Time Status Near End | Modbus 406149 bit 1; not polled by default | Read | ||
| BI | 534 | Frame[1]Power Module[1] Life Time Status Exceeded | Modbus 406149 bit 2; not polled by default | Read | ||
| AI | 535 | Frame[1]Power Module[1] Estimated Lifetime Remaining | Modbus 406150; not polled by default | days | Read | |
| BI | 536 | Frame[1]Power Module[1] Fan Life Time Status OK | Modbus 406151 bit 0; not polled by default | Read | ||
| BI | 537 | Frame[1]Power Module[1] Fan Life Time Status Near End | Modbus 406151 bit 1; not polled by default | Read | ||
| BI | 538 | Frame[1]Power Module[1] Fan Life Time Status Exceeded | Modbus 406151 bit 2; not polled by default | Read | ||
| AI | 539 | Frame[1]Power Module[1] Fan Estimated Lifetime Remaining | Modbus 406152; not polled by default | days | Read | |
| BI | 540 | Frame[1]Power Module[2] Life Time Status OK | Modbus 406153 bit 0; not polled by default | Read | ||
| BI | 541 | Frame[1]Power Module[2] Life Time Status Near End | Modbus 406153 bit 1; not polled by default | Read | ||
| BI | 542 | Frame[1]Power Module[2] Life Time Status Exceeded | Modbus 406153 bit 2; not polled by default | Read | ||
| AI | 543 | Frame[1]Power Module[2] Estimated Lifetime Remaining | Modbus 406154; not polled by default | days | Read | |
| BI | 544 | Frame[1]Power Module[2] Fan Life Time Status OK | Modbus 406155 bit 0; not polled by default | Read | ||
| BI | 545 | Frame[1]Power Module[2] Fan Life Time Status Near End | Modbus 406155 bit 1; not polled by default | Read | ||
| BI | 546 | Frame[1]Power Module[2] Fan Life Time Status Exceeded | Modbus 406155 bit 2; not polled by default | Read | ||
| AI | 547 | Frame[1]Power Module[2] Fan Estimated Lifetime Remaining | Modbus 406156; not polled by default | days | Read | |
| BI | 548 | Frame[1]Power Module[3] Life Time Status OK | Modbus 406157 bit 0; not polled by default | Read | ||
| BI | 549 | Frame[1]Power Module[3] Life Time Status Near End | Modbus 406157 bit 1; not polled by default | Read | ||
| BI | 550 | Frame[1]Power Module[3] Life Time Status Exceeded | Modbus 406157 bit 2; not polled by default | Read | ||
| AI | 551 | Frame[1]Power Module[3] Estimated Lifetime Remaining | Modbus 406158; not polled by default | days | Read | |
| BI | 552 | Frame[1]Power Module[3] Fan Life Time Status OK | Modbus 406159 bit 0; not polled by default | Read | ||
| BI | 553 | Frame[1]Power Module[3] Fan Life Time Status Near End | Modbus 406159 bit 1; not polled by default | Read | ||
| BI | 554 | Frame[1]Power Module[3] Fan Life Time Status Exceeded | Modbus 406159 bit 2; not polled by default | Read | ||
| AI | 555 | Frame[1]Power Module[3] Fan Estimated Lifetime Remaining | Modbus 406160; not polled by default | days | Read | |
| BI | 556 | Frame[1]Power Module[4] Life Time Status OK | Modbus 406161 bit 0; not polled by default | Read | ||
| BI | 557 | Frame[1]Power Module[4] Life Time Status Near End | Modbus 406161 bit 1; not polled by default | Read | ||
| BI | 558 | Frame[1]Power Module[4] Life Time Status Exceeded | Modbus 406161 bit 2; not polled by default | Read | ||
| AI | 559 | Frame[1]Power Module[4] Estimated Lifetime Remaining | Modbus 406162; not polled by default | days | Read | |
| BI | 560 | Frame[1]Power Module[4] Fan Life Time Status OK | Modbus 406163 bit 0; not polled by default | Read | ||
| BI | 561 | Frame[1]Power Module[4] Fan Life Time Status Near End | Modbus 406163 bit 1; not polled by default | Read | ||
| BI | 562 | Frame[1]Power Module[4] Fan Life Time Status Exceeded | Modbus 406163 bit 2; not polled by default | Read | ||
| AI | 563 | Frame[1]Power Module[4] Fan Estimated Lifetime Remaining | Modbus 406164; not polled by default | days | Read | |
| BI | 564 | Frame[1]Power Module[5] Life Time Status OK | Modbus 406165 bit 0; not polled by default | Read | ||
| BI | 565 | Frame[1]Power Module[5] Life Time Status Near End | Modbus 406165 bit 1; not polled by default | Read | ||
| BI | 566 | Frame[1]Power Module[5] Life Time Status Exceeded | Modbus 406165 bit 2; not polled by default | Read | ||
| AI | 567 | Frame[1]Power Module[5] Estimated Lifetime Remaining | Modbus 406166; not polled by default | days | Read | |
| BI | 568 | Frame[1]Power Module[5] Fan Life Time Status OK | Modbus 406167 bit 0; not polled by default | Read | ||
| BI | 569 | Frame[1]Power Module[5] Fan Life Time Status Near End | Modbus 406167 bit 1; not polled by default | Read | ||
| BI | 570 | Frame[1]Power Module[5] Fan Life Time Status Exceeded | Modbus 406167 bit 2; not polled by default | Read | ||
| AI | 571 | Frame[1]Power Module[5] Fan Estimated Lifetime Remaining | Modbus 406168; not polled by default | days | Read | |
| BI | 572 | Frame[1]Power Module[6] Life Time Status OK | Modbus 406169 bit 0; not polled by default | Read | ||
| BI | 573 | Frame[1]Power Module[6] Life Time Status Near End | Modbus 406169 bit 1; not polled by default | Read | ||
| BI | 574 | Frame[1]Power Module[6] Life Time Status Exceeded | Modbus 406169 bit 2; not polled by default | Read | ||
| AI | 575 | Frame[1]Power Module[6] Estimated Lifetime Remaining | Modbus 406170; not polled by default | days | Read | |
| BI | 576 | Frame[1]Power Module[6] Fan Life Time Status OK | Modbus 406171 bit 0; not polled by default | Read | ||
| BI | 577 | Frame[1]Power Module[6] Fan Life Time Status Near End | Modbus 406171 bit 1; not polled by default | Read | ||
| BI | 578 | Frame[1]Power Module[6] Fan Life Time Status Exceeded | Modbus 406171 bit 2; not polled by default | Read | ||
| AI | 579 | Frame[1]Power Module[6] Fan Estimated Lifetime Remaining | Modbus 406172; not polled by default | days | Read | |
| BI | 580 | Frame[1]Power Module[7] Life Time Status OK | Modbus 406173 bit 0; not polled by default | Read | ||
| BI | 581 | Frame[1]Power Module[7] Life Time Status Near End | Modbus 406173 bit 1; not polled by default | Read | ||
| BI | 582 | Frame[1]Power Module[7] Life Time Status Exceeded | Modbus 406173 bit 2; not polled by default | Read | ||
| AI | 583 | Frame[1]Power Module[7] Estimated Lifetime Remaining | Modbus 406174; not polled by default | days | Read | |
| BI | 584 | Frame[1]Power Module[7] Fan Life Time Status OK | Modbus 406175 bit 0; not polled by default | Read | ||
| BI | 585 | Frame[1]Power Module[7] Fan Life Time Status Near End | Modbus 406175 bit 1; not polled by default | Read | ||
| BI | 586 | Frame[1]Power Module[7] Fan Life Time Status Exceeded | Modbus 406175 bit 2; not polled by default | Read | ||
| AI | 587 | Frame[1]Power Module[7] Fan Estimated Lifetime Remaining | Modbus 406176; not polled by default | days | Read | |
| BI | 588 | Frame[1]Power Module[8] Life Time Status OK | Modbus 406177 bit 0; not polled by default | Read | ||
| BI | 589 | Frame[1]Power Module[8] Life Time Status Near End | Modbus 406177 bit 1; not polled by default | Read | ||
| BI | 590 | Frame[1]Power Module[8] Life Time Status Exceeded | Modbus 406177 bit 2; not polled by default | Read | ||
| AI | 591 | Frame[1]Power Module[8] Estimated Lifetime Remaining | Modbus 406178; not polled by default | days | Read | |
| BI | 592 | Frame[1]Power Module[8] Fan Life Time Status OK | Modbus 406179 bit 0; not polled by default | Read | ||
| BI | 593 | Frame[1]Power Module[8] Fan Life Time Status Near End | Modbus 406179 bit 1; not polled by default | Read | ||
| BI | 594 | Frame[1]Power Module[8] Fan Life Time Status Exceeded | Modbus 406179 bit 2; not polled by default | Read | ||
| AI | 595 | Frame[1]Power Module[8] Fan Estimated Lifetime Remaining | Modbus 406180; not polled by default | days | Read | |
| BI | 596 | Frame[1]Power Module[9] Life Time Status OK | Modbus 406181 bit 0; not polled by default | Read | ||
| BI | 597 | Frame[1]Power Module[9] Life Time Status Near End | Modbus 406181 bit 1; not polled by default | Read | ||
| BI | 598 | Frame[1]Power Module[9] Life Time Status Exceeded | Modbus 406181 bit 2; not polled by default | Read | ||
| AI | 599 | Frame[1]Power Module[9] Estimated Lifetime Remaining | Modbus 406182; not polled by default | days | Read | |
| BI | 600 | Frame[1]Power Module[9] Fan Life Time Status OK | Modbus 406183 bit 0; not polled by default | Read | ||
| BI | 601 | Frame[1]Power Module[9] Fan Life Time Status Near End | Modbus 406183 bit 1; not polled by default | Read | ||
| BI | 602 | Frame[1]Power Module[9] Fan Life Time Status Exceeded | Modbus 406183 bit 2; not polled by default | Read | ||
| AI | 603 | Frame[1]Power Module[9] Fan Estimated Lifetime Remaining | Modbus 406184; not polled by default | days | Read | |
| AI | 604 | ASCII 01 UPS Name | Modbus 404164; not polled by default | Read | ||
| AI | 605 | ASCII 02 UPS Name | Modbus 404165; not polled by default | Read | ||
| AI | 606 | ASCII 03 UPS Name | Modbus 404166; not polled by default | Read | ||
| AI | 607 | ASCII 04 UPS Name | Modbus 404167; not polled by default | Read | ||
| AI | 608 | ASCII 01 Parallel System Name | Modbus 404168; not polled by default | Read | ||
| AI | 609 | ASCII 02 Parallel System Name | Modbus 404169; not polled by default | Read | ||
| AI | 610 | ASCII 03 Parallel System Name | Modbus 404170; not polled by default | Read | ||
| AI | 611 | ASCII 04 Parallel System Name | Modbus 404372; not polled by default | Read | ||
| AI | 612 | ASCII 01 Last Battery Replacement | Modbus 404373; not polled by default | Read | ||
| AI | 613 | ASCII 02 Last Battery Replacement | Modbus 404374; not polled by default | Read | ||
| AI | 614 | ASCII 03 Last Battery Replacement | Modbus 404375; not polled by default | Read | ||
| AI | 615 | ASCII 04 Last Battery Replacement | Modbus 404376; not polled by default | Read | ||
| AI | 616 | Number of Power Modules | Modbus 408193; not polled by default | Read | ||
| AI | 617 | Number of Battery Monitor Boards | Modbus 408194; not polled by default | Read | ||
| AI | 618 | Number of Battery Breaker Motors | Modbus 408195; not polled by default | Read | ||
| AI | 619 | Number of Battery Modules | Modbus 408196; not polled by default | Read | ||
| AI | 620 | Number of Battery Enclosures | Modbus 408198; not polled by default | Read | ||
| AI | 621 | Number of PSUs | Modbus 408199; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX APC Symmetra PX 250/500 point IDs by name
BI1Load is being powered from batteryBI2Low-BatteryBI3BypassBI4Self-TestBI5Load not PoweredBI6Abnormal ConditionBI7Power Module FailureBI8Battery System FailureBI9Intelligence Module (IM) has detected alarm conditionBI10Static Switch failureBI11Power Supply Unit failureBI12Warning alarm presentBI13Critical alarm presentBI14Lost local network management interface - to - UPS communicationBI15Parallel PBUS cables are swappedBI16Parallel communication error on PBUS cable 1BI17Parallel communication error on PBUS cable 2BI18Overload on parallel installationBI19Parallel mixed mode errorBI20UPS parallel address configuration number errorBI21Parallel master not detected (deprecated)BI22Parallel unit disabledBI23Parallel unit is incompatibleBI24PBUS cable termination faultBI25Parallel unit not present (deprecated)BI26Isolated Test mode is activateBI27Parallel unit redundancy lostBI28Parallel load share errorBI29On battery in response to an input power failureBI30In bypass: User-initiated from Front PanelBI31UPS operation mode - Forced bypassBI32In Bypass: For maintenanceBI33Started a self-testBI34Output power turned offBI35UPS operation mode - InitializeBI36UPS operation mode - Hot standbyBI37Compensating for a low input voltageBI38Compensating for a high input voltageBI39Input voltage waveform error detectedBI40Input phase sequence errorBI41Input frequency faultBI42Output frequency faultBI43Mega Tie mode is activeBI44Bypass voltage error: low voltageBI45Bypass voltage error: high voltageBI46Bypass voltage waveform error detectedBI47Bypass input frequency faultBI48Bypass phase sequence errorBI49Output voltage lowBI50Output voltage highBI51Output voltage waveform error detectedBI52OverloadBI53Overload on bypass static switchBI54Ambient temperature out of rangeBI55EPO activatedBI56Ground fault detectedBI57PSU module failedBI58System locked in bypass operationBI59Batteries are dischargingBI60PSU module not presentBI61System frequency not detectedBI62Charge power is reducedBI63Display communication to MIM and RIM is lostBI64CBUS terminator faultBI65ABUS terminator faultBI66MIM not presentBI67MIM heartbeat signal errorBI68RIM in controlBI69Battery condition is weakBI70Battery condition is poorBI71Battery voltage error - voltage above warning levelBI72Battery voltage error - voltage above shutdown levelBI73Battery monitor board communication errorBI74Battery is below minimum acceptable runtimeBI75Power module communication to MIM errorBI76Power module locked by IMBI77Power module operation mode is different from other modulesBI78Switchgear board not presentBI79Switchgear board communication errorBI80ID Relay board not presentBI81ID Relay board communication errorBI82Battery voltage collapse detectedBI83Power module redundancy lostBI84Load on subfeed is above warning levelBI85Load on subfeed is above critical levelBI86Load on UPS is above warning levelBI87Power module firmware version is incompatibleBI88Static Bypass Switch module not presentBI89Overload on installationBI90Bypass static switch communication errorBI91RIM not presentBI92RIM heartbeat signal errorBI93Bonding wire between neutral and ground is missingBI94Bonding wire between neutral and ground errorBI95Power module communication to RIM errorBI96Battery voltage error - voltage below warning levelBI97Battery voltage error - voltage below shutdown levelBI98ECT board has an errorBI99External connections board not presentBI100EPO circuit test mode is enabledBI101IM internal memory for storing configuration settings errorBI102Auxiliary monitor board for maintenance bypass panel comm errorBI103Auxiliary monitor board for battery breaker enclosure comm errorBI104Power module removed from the systemBI105INFO Battery module removed from systemBI106Power module fault existsBI107Power module warningBI108Power module fan faultBI109Power module is disabledBI110Power module lifetime error: close to endBI111Power module lifetime error: lifetime exceededBI112Power module fan lifetime error: close to endBI113Power module fan lifetimerror: lifetime exceededBI114Breaker Q1 openBI115Breaker Q2 openBI116Breaker Q3 closedBI117Breaker Q4 openBI118Breaker Q5 openBI119Power module phase-neutral displacement faultBI120Forced bypass switch activatedBI121Bypass static switch disabledBI122Bypass static switch self test failedBI123Bypass static switch 1 fan faultBI124Bypass static switch 1 fan weakBI125Bypass static switch error; module has a critical errorBI126Bypass static switch warning; module is not working properlyBI127Power enclosure air filter lifetime error: lifetime exceededBI128Power enclosure air filter lifetime error: lifetime exceededBI129Door in MBwD enclosure openBI130Q2 shunt open errorBI131Subfeed breaker SB1 openBI132Subfeed breaker SB2 openBI133Subfeed breaker SB3 openBI134Subfeed breaker SB4 openBI135Subfeed breaker SB5 openBI136Subfeed breaker SB6 openBI137Subfeed breaker SB7 openBI138Subfeed breaker SB8 openBI139Subfeed breaker SB9 openBI140Subfeed breaker SB10 openBI141Subfeed breaker SB11 openBI142Subfeed breaker SB12 openBI143Subfeed breaker SB13 openBI144Subfeed breaker SB14 openBI145Subfeed breaker SB15 openBI146Subfeed breaker SB16 openBI147Breaker Q1 openBI148Breaker Q2 openBI149Breaker Q3 closedBI150Breaker Q4 openBI151Breaker Q5 openBI152Door in maintenance bypass panel enclosure openBI153Q2 shunt open errorBI154MBP enclosure ECT board has an errorBI155ID Relay board memory card fullBI156Input 3 activated: Battery ground fault detectedBI157ID Relay board: System firmware not stored at memory cardBI158Input 6 activated: Emergency module offBI159Input 7 activated: Door in UPS I/O enclosure openedBI160Input 1 activated: Reduce charging powerBI161IDRC memory card not presentBI162ID Relay board memory card errorBI163Battery breaker openBI164Battery module fuse cleared or condition of battery is weakBI165Battery voltage symmetry errorBI166Internal battery temperature exceeds thresholdBI167Battery temperature sensor faultBI168Mixed battery configurationBI169Battery module type support errorBI170Battery string disconnectedBI171Battery side car 1 fuse errorBI172Battery enclosure PSU errorBI173Battery breaker motor PSU errorBI174Battery enclosure door openBI175ECT board has an errorBI176Battery breaker shunt open errorBI177Battery breaker open errorBI178Battery breaker enclosure fuse 1 errorBI179Battery breaker enclosure fuse 2 errorBI180Battery temperature 1 highBI181Battery temperature 2 highBI182Battery temperature sensor 1 faultBI183Battery temperature sensor 2 faultBI184Battery breaker enclosure door open errorBI185Battery breaker enclosure ECT board has an errorBI186Battery breaker shunt open errorBI187Battery ground fault detected errorBI188Battery fuse bank 1 clearedBI189Battery fuse bank 2 clearedBI190Battery fuse bank 3 clearedBI191Battery fuse bank 4 clearedBI192Battery fuse bank 5 clearedBI193Battery fuse bank 6 clearedBI194Battery fuse bank 7 clearedBI195Battery fuse bank 8 clearedBI196Input for gas alarm has been activatedBI197Test firmware installed at power moduleBI198Not expected firmware installed at power moduleBI199Not expected firmware installed at battery monitor boardBI200Not expected firmware installed at SBS moduleBI201Not expected firmware installed at ID Relay boardBI202Not expected firmware installed at switchgear boardBI203Not expected firmware installed at auxiliary boardBI204Not expected firmware installed at aux mon bd for battery breakBI205Not expected firmware installed at redundant IMBI206Test firmware installed at battery monitor boardBI207Test firmware installed at SBS moduleBI208Test firmware installed at ID Relay boardBI209Test firmware installed at switchgear boardBI210Test firmware installed at aux mon board for maint bypass panelBI211Test firmware installed at aux mon bd for battery break encBI212Test firmware installed at IMAI213ASCII 01 NMC Model NumberAI214ASCII 02 NMC Model NumberAI215ASCII 03 NMC Model NumberAI216ASCII 04 NMC Model NumberAI217ASCII 05 NMC Model NumberAI218ASCII 06 NMC Model NumberAI219ASCII 07 NMC Model NumberAI220ASCII 08 NMC Model NumberAI221ASCII 09 NMC Model NumberAI222ASCII 01 NMC Serial NumberAI223ASCII 02 NMC Serial NumberAI224ASCII 03 NMC Serial NumberAI225ASCII 04 NMC Serial NumberAI226ASCII 05 NMC Serial NumberAI227ASCII 06 NMC Serial NumberAI228ASCII 07 NMC Serial NumberAI229ASCII 08 NMC Serial NumberAI230ASCII 01 NMC Firmware Revision APPAI231ASCII 02 NMC Firmware Revision APPAI232ASCII 03 NMC Firmware Revision APPAI233ASCII 04 NMC Firmware Revision APPAI234ASCII 05 NMC Firmware Revision APPAI235ASCII 06 NMC Firmware Revision APPAI236ASCII 07 NMC Firmware Revision APPAI237ASCII 08 NMC Firmware Revision APPAI238ASCII 09 NMC Firmware Revision APPAI239ASCII 01 NMC Hardware RevisionAI240ASCII 02 NMC Hardware RevisionAI241ASCII 03 NMC Hardware RevisionAI242ASCII 04 NMC Hardware RevisionAI243ASCII 05 NMC Hardware RevisionAI244ASCII 06 NMC Hardware RevisionAI245ASCII 07 NMC Hardware RevisionAI246ASCII 08 NMC Hardware RevisionAI247ASCII 09 NMC Hardware RevisionAI248ASCII 01 NMC Date of ManufactureAI249ASCII 02 NMC Date of ManufactureAI250ASCII 03 NMC Date of ManufactureAI251ASCII 04 NMC Date of ManufactureAI252ASCII 05 NMC Date of ManufactureAI253ASCII 06 NMC Date of ManufactureAI254ASCII 01 UPS Model NameAI255ASCII 02 UPS Model NameAI256ASCII 03 UPS Model NameAI257ASCII 04 UPS Model NameAI258ASCII 05 UPS Model NameAI259ASCII 06 UPS Model NameAI260ASCII 07 UPS Model NameAI261ASCII 08 UPS Model NameAI262ASCII 01 UPS Serial NumberAI263ASCII 02 UPS Serial NumberAI264ASCII 03 UPS Serial NumberAI265ASCII 04 UPS Serial NumberAI266ASCII 05 UPS Serial NumberAI267ASCII 06 UPS Serial NumberAI268ASCII 01 UPS Firmware VersionAI269ASCII 02 UPS Firmware VersionAI270ASCII 03 UPS Firmware VersionAI271ASCII 04 UPS Firmware VersionAI272ASCII 05 UPS Firmware VersionAI273ASCII 06 UPS Firmware VersionAI274ASCII 07 UPS Firmware VersionAI275ASCII 08 UPS Firmware VersionAI276ASCII 09 UPS Firmware VersionAI277ASCII 10 UPS Firmware VersionAI278ASCII 11 UPS Firmware VersionAI279ASCII 12 UPS Firmware VersionAI280Time on batteryAI281Runtime remainingAI282Estimated charge timeAI283Estimated charge %AI284Battery (+) VoltageAI285Battery (-) VoltageAI286Battery (+) CurrentAI287Battery (-) CurrentAI288Total time on batteryAI289Total number of times on batteryAI290APC Battery Breaker Status /User supplied battery Breaker StatusAI291BatterySystem/TemperatureBI292User Supplied Battery System Charger StatusBI293Boost ChargingBI294Normal ChargingBI295RestingBI296DischargingBI297Equalization ChargingAI298Battery PowerAI299Available Amp HoursAI300Frequency (input)AI301Voltage L1-2 (input)AI302Voltage L2-3 (input)AI303Voltage L3-1 (input)AI304Current L1 (input)AI305Current L2 (input)AI306Current L3 (input)AI307Active power L1 (input)AI308Active power L2 (input)AI309Active power L3 (input)AI310Apparent power L1 (input)AI311Apparent power L2 (input)AI312Apparent power L3 (input)AI313Total active power (input)AI314Total apparent power (input)AI315Current L1 (parallel input)AI316Current L2 (parallel input)AI317Current L3 (parallel input)AI318Frequency (bypass)AI319Voltage L1-2 (bypass)AI320Voltage L2-3 (bypass)AI321Voltage L3-1 (bypass)AI322Current L1 (bypass)AI323Current L2 (bypass)AI324Current L3 (bypass)AI325Active power L1 (bypass)AI326Active power L2 (bypass)AI327Active power L3 (bypass)AI328Apparent power L1 (bypass)AI329Apparent power L2 (bypass)AI330Apparent power L3 (bypass)AI331Total active power (bypass)AI332Total apparent power (bypass)AI333Current L1 (parallel bypass)AI334Current L2 (parallel bypass)AI335Current L3 (parallel bypass)AI336Nominal (Apparent) output ratingAI337Frequency (output)AI338Voltage L1-2 (output)AI339Voltage L2-3 (output)AI340Voltage L3-1 (output)AI341Current L1 (output)AI342Current L2 (output)AI343Current L3 (output)AI344Peak current L1 (output)AI345Peak current L2 (output)AI346Peak current L3 (output)AI347Active power L1 (output)AI348Active power L2 (output)AI349Active power L3 (output)AI350Apparent power L1 (output)AI351Apparent power L2 (output)AI352Apparent power L3 (output)AI353% Load L1AI354% Load L2AI355% Load L3AI356Total active power (output)AI357Total apparent power (output)AI358Total Percent loadAI359Power factor L1 (output)AI360Power factor L2 (output)AI361Power factor L3 (output)AI362Current crest factor L1 (output)AI363Current crest factor L2 (output)AI364Current crest factor L3 (output)AI365Parallel System Output CurrentAC L1AI366Parallel System Output CurrentAC L2AI367Parallel System Output CurrentAC L3AI368Parallel System Output Active Power L1AI369Parallel System Output Active Power L2AI370Parallel System Output Active Power L3AI371Parallel System Output Apparent Power L1AI372Parallel System Output Apparent Power L2AI373Parallel System Output Apparent Power L3AI374ParallelSystem Output % Load L1AI375ParallelSystem Output % Load L2AI376ParallelSystem Output % Load L3AI377ParallelSystem Output Total Active PowerAI378ParallelSystem Output Total Apparent PowerAI379ParallelSystem Output Total % LoadAI380Energy Meter kwHAI381UPS Installation Load % (Standalone )AI382UPS Installation Load % (Parallel )AI383Ambient temperatureBI384Q1BI385Q2BI386Q3BI387Q5AI388UPS Mode Operation mode of the UPSAI389Number of Active AlarmsAI390Highest alarm severityAI391System ModeBI392Input 01 Contact StatusBI393Input 02 Contact StatusBI394Input 03 Contact StatusBI395Input 04 Contact StatusBI396Input 05 Contact StatusBI397Input 06 Contact StatusBI398Input 07 Contact StatusBI399Input 08 Contact StatusBI400Input 09 Contact StatusBI401Input 10 Contact StatusBI402Input 11 Contact StatusBI403Input 12 Contact StatusBI404Input 13 Contact StatusBI405Input 14 Contact StatusBI406Input 15 Contact StatusBI407Input 16 Contact StatusBI408Output 01 Contact StatusBI409Output 02 Contact StatusBI410Output 03 Contact StatusBI411Output 04 Contact StatusBI412Output 05 Contact StatusBI413Output 06 Contact StatusBI414Output 07 Contact StatusBI415Output 08 Contact StatusBI416Output 09 Contact StatusBI417Output 10 Contact StatusBI418Output 11 Contact StatusBI419Output 12 Contact StatusBI420Output 13 Contact StatusBI421Output 14 Contact StatusBI422Output 15 Contact StatusBI423Output 16 Contact StatusAI424Output Contact Normal State SettingAI425Redundancy StatusAI426ASCII 01 NMC/UPS TimeAI427ASCII 02 NMC/UPS TimeAI428ASCII 03 NMC/UPS TimeAI429ASCII 04 NMC/UPS TimeAI430ASCII 01 NMC/UPS DatenAI431ASCII 02 NMC/UPS DatenAI432ASCII 03 NMC/UPS DatenAI433ASCII 04 NMC/UPS DatenAI434ASCII 05 NMC/UPS DatenAI435Parallel System Redundancy StatusBI436Bypass Life Time Status OKBI437Bypass Life Time Status Near EndBI438Bypass Life Time Status ExceededAI439Bypass Estimated Lifetime RemainingBI440Bypass Fan Life Time Status OKBI441Bypass Fan Life Time Status Near EndBI442Bypass Fan Life Time Status ExceededAI443Bypass Fan Estimated Lifetime RemainingBI444Frame[0] Power Module[0] Life Time Status OKBI445Frame[0] Power Module[0] Life Time Status Near EndBI446Frame[0] Power Module[0] Life Time Status ExceededAI447Frame[0] Power Module[0] Estimated Lifetime RemainingBI448Frame[0] Power Module[0] Fan Life Time Status OKBI449Frame[0] Power Module[0] Fan Life Time Status Near EndBI450Frame[0] Power Module[0] Fan Life Time Status ExceededAI451Frame[0] Power Module[0] Fan Estimated Lifetime RemainingBI452Frame[0] Power Module[1] Life Time Status OKBI453Frame[0] Power Module[1] Life Time Status Near EndBI454Frame[0] Power Module[1] Life Time Status ExceededAI455Frame[0] Power Module[1] Estimated Lifetime RemainingBI456Frame[0] Power Module[1] Fan Life Time Status OKBI457Frame[0] Power Module[1] Fan Life Time Status Near EndBI458Frame[0] Power Module[1] Fan Life Time Status ExceededAI459Frame[0] Power Module[1] Fan Estimated Lifetime RemainingBI460Frame[0] Power Module[2] Life Time Status OKBI461Frame[0] Power Module[2] Life Time Status Near EndBI462Frame[0] Power Module[2] Life Time Status ExceededAI463Frame[0] Power Module[2] Estimated Lifetime RemainingBI464Frame[0] Power Module[2] Fan Life Time Status OKBI465Frame[0] Power Module[2] Fan Life Time Status Near EndBI466Frame[0] Power Module[2] Fan Life Time Status ExceededAI467Frame[0] Power Module[2] Fan Estimated Lifetime RemainingBI468Frame[0] Power Module[3] Life Time Status OKBI469Frame[0] Power Module[3] Life Time Status Near EndBI470Frame[0] Power Module[3] Life Time Status ExceededAI471Frame[0] Power Module[3] Estimated Lifetime RemainingBI472Frame[0] Power Module[3] Fan Life Time Status OKBI473Frame[0] Power Module[3] Fan Life Time Status Near EndBI474Frame[0] Power Module[3] Fan Life Time Status ExceededAI475Frame[0] Power Module[3] Fan Estimated Lifetime RemainingBI476Frame[0] Power Module[4] Life Time Status OKBI477Frame[0] Power Module[4] Life Time Status Near EndBI478Frame[0] Power Module[4] Life Time Status ExceededAI479Frame[0] Power Module[4] Estimated Lifetime RemainingBI480Frame[0] Power Module[4] Fan Life Time Status OKBI481Frame[0] Power Module[4] Fan Life Time Status Near EndBI482Frame[0] Power Module[4] Fan Life Time Status ExceededAI483Frame[0] Power Module[4] Fan Estimated Lifetime RemainingBI484Frame[0] Power Module[5] Life Time Status OKBI485Frame[0] Power Module[5] Life Time Status Near EndBI486Frame[0] Power Module[5] Life Time Status ExceededAI487Frame[0] Power Module[5] Estimated Lifetime RemainingBI488Frame[0] Power Module[5] Fan Life Time Status OKBI489Frame[0] Power Module[5] Fan Life Time Status Near EndBI490Frame[0] Power Module[5] Fan Life Time Status ExceededAI491Frame[0] Power Module[5] Fan Estimated Lifetime RemainingBI492Frame[0] Power Module[6] Life Time Status OKBI493Frame[0] Power Module[6] Life Time Status Near EndBI494Frame[0] Power Module[6] Life Time Status ExceededAI495Frame[0] Power Module[6] Estimated Lifetime RemainingBI496Frame[0] Power Module[6] Fan Life Time Status OKBI497Frame[0] Power Module[6] Fan Life Time Status Near EndBI498Frame[0] Power Module[6] Fan Life Time Status ExceededAI499Frame[0] Power Module[6] Fan Estimated Lifetime RemainingBI500Frame[0] Power Module[7] Life Time Status OKBI501Frame[0] Power Module[7] Life Time Status Near EndBI502Frame[0] Power Module[7] Life Time Status ExceededAI503Frame[0] Power Module[7] Estimated Lifetime RemainingBI504Frame[0] Power Module[7] Fan Life Time Status OKBI505Frame[0] Power Module[7] Fan Life Time Status Near EndBI506Frame[0] Power Module[7] Fan Life Time Status ExceededAI507Frame[0] Power Module[7] Fan Estimated Lifetime RemainingBI508Frame[0] Power Module[8] Life Time Status OKBI509Frame[0] Power Module[8] Life Time Status Near EndBI510Frame[0] Power Module[8] Life Time Status ExceededAI511Frame[0] Power Module[8] Estimated Lifetime RemainingBI512Frame[0] Power Module[8] Fan Life Time Status OKBI513Frame[0] Power Module[8] Fan Life Time Status Near EndBI514Frame[0] Power Module[8] Fan Life Time Status ExceededAI515Frame[0] Power Module[8] Fan Estimated Lifetime RemainingBI516Frame[0] Power Module[9] Life Time Status OKBI517Frame[0] Power Module[9] Life Time Status Near EndBI518Frame[0] Power Module[9] Life Time Status ExceededAI519Frame[0] Power Module[9] Estimated Lifetime RemainingBI520Frame[0] Power Module[9] Fan Life Time Status OKBI521Frame[0] Power Module[9] Fan Life Time Status Near EndBI522Frame[0] Power Module[9] Fan Life Time Status ExceededAI523Frame[0] Power Module[9] Fan Estimated Lifetime RemainingBI524Frame[1]Power Module[0] Life Time Status OKBI525Frame[1]Power Module[0] Life Time Status Near EndBI526Frame[1]Power Module[0] Life Time Status ExceededAI527Frame[1]Power Module[0] Estimated Lifetime RemainingBI528Frame[1]Power Module[0] Fan Life Time Status OKBI529Frame[1]Power Module[0] Fan Life Time Status Near EndBI530Frame[1]Power Module[0] Fan Life Time Status ExceededAI531Frame[1]Power Module[0] Fan Estimated Lifetime RemainingBI532Frame[1]Power Module[1] Life Time Status OKBI533Frame[1]Power Module[1] Life Time Status Near EndBI534Frame[1]Power Module[1] Life Time Status ExceededAI535Frame[1]Power Module[1] Estimated Lifetime RemainingBI536Frame[1]Power Module[1] Fan Life Time Status OKBI537Frame[1]Power Module[1] Fan Life Time Status Near EndBI538Frame[1]Power Module[1] Fan Life Time Status ExceededAI539Frame[1]Power Module[1] Fan Estimated Lifetime RemainingBI540Frame[1]Power Module[2] Life Time Status OKBI541Frame[1]Power Module[2] Life Time Status Near EndBI542Frame[1]Power Module[2] Life Time Status ExceededAI543Frame[1]Power Module[2] Estimated Lifetime RemainingBI544Frame[1]Power Module[2] Fan Life Time Status OKBI545Frame[1]Power Module[2] Fan Life Time Status Near EndBI546Frame[1]Power Module[2] Fan Life Time Status ExceededAI547Frame[1]Power Module[2] Fan Estimated Lifetime RemainingBI548Frame[1]Power Module[3] Life Time Status OKBI549Frame[1]Power Module[3] Life Time Status Near EndBI550Frame[1]Power Module[3] Life Time Status ExceededAI551Frame[1]Power Module[3] Estimated Lifetime RemainingBI552Frame[1]Power Module[3] Fan Life Time Status OKBI553Frame[1]Power Module[3] Fan Life Time Status Near EndBI554Frame[1]Power Module[3] Fan Life Time Status ExceededAI555Frame[1]Power Module[3] Fan Estimated Lifetime RemainingBI556Frame[1]Power Module[4] Life Time Status OKBI557Frame[1]Power Module[4] Life Time Status Near EndBI558Frame[1]Power Module[4] Life Time Status ExceededAI559Frame[1]Power Module[4] Estimated Lifetime RemainingBI560Frame[1]Power Module[4] Fan Life Time Status OKBI561Frame[1]Power Module[4] Fan Life Time Status Near EndBI562Frame[1]Power Module[4] Fan Life Time Status ExceededAI563Frame[1]Power Module[4] Fan Estimated Lifetime RemainingBI564Frame[1]Power Module[5] Life Time Status OKBI565Frame[1]Power Module[5] Life Time Status Near EndBI566Frame[1]Power Module[5] Life Time Status ExceededAI567Frame[1]Power Module[5] Estimated Lifetime RemainingBI568Frame[1]Power Module[5] Fan Life Time Status OKBI569Frame[1]Power Module[5] Fan Life Time Status Near EndBI570Frame[1]Power Module[5] Fan Life Time Status ExceededAI571Frame[1]Power Module[5] Fan Estimated Lifetime RemainingBI572Frame[1]Power Module[6] Life Time Status OKBI573Frame[1]Power Module[6] Life Time Status Near EndBI574Frame[1]Power Module[6] Life Time Status ExceededAI575Frame[1]Power Module[6] Estimated Lifetime RemainingBI576Frame[1]Power Module[6] Fan Life Time Status OKBI577Frame[1]Power Module[6] Fan Life Time Status Near EndBI578Frame[1]Power Module[6] Fan Life Time Status ExceededAI579Frame[1]Power Module[6] Fan Estimated Lifetime RemainingBI580Frame[1]Power Module[7] Life Time Status OKBI581Frame[1]Power Module[7] Life Time Status Near EndBI582Frame[1]Power Module[7] Life Time Status ExceededAI583Frame[1]Power Module[7] Estimated Lifetime RemainingBI584Frame[1]Power Module[7] Fan Life Time Status OKBI585Frame[1]Power Module[7] Fan Life Time Status Near EndBI586Frame[1]Power Module[7] Fan Life Time Status ExceededAI587Frame[1]Power Module[7] Fan Estimated Lifetime RemainingBI588Frame[1]Power Module[8] Life Time Status OKBI589Frame[1]Power Module[8] Life Time Status Near EndBI590Frame[1]Power Module[8] Life Time Status ExceededAI591Frame[1]Power Module[8] Estimated Lifetime RemainingBI592Frame[1]Power Module[8] Fan Life Time Status OKBI593Frame[1]Power Module[8] Fan Life Time Status Near EndBI594Frame[1]Power Module[8] Fan Life Time Status ExceededAI595Frame[1]Power Module[8] Fan Estimated Lifetime RemainingBI596Frame[1]Power Module[9] Life Time Status OKBI597Frame[1]Power Module[9] Life Time Status Near EndBI598Frame[1]Power Module[9] Life Time Status ExceededAI599Frame[1]Power Module[9] Estimated Lifetime RemainingBI600Frame[1]Power Module[9] Fan Life Time Status OKBI601Frame[1]Power Module[9] Fan Life Time Status Near EndBI602Frame[1]Power Module[9] Fan Life Time Status ExceededAI603Frame[1]Power Module[9] Fan Estimated Lifetime RemainingAI604ASCII 01 UPS NameAI605ASCII 02 UPS NameAI606ASCII 03 UPS NameAI607ASCII 04 UPS NameAI608ASCII 01 Parallel System NameAI609ASCII 02 Parallel System NameAI610ASCII 03 Parallel System NameAI611ASCII 04 Parallel System NameAI612ASCII 01 Last Battery ReplacementAI613ASCII 02 Last Battery ReplacementAI614ASCII 03 Last Battery ReplacementAI615ASCII 04 Last Battery ReplacementAI616Number of Power ModulesAI617Number of Battery Monitor BoardsAI618Number of Battery Breaker MotorsAI619Number of Battery ModulesAI620Number of Battery EnclosuresAI621Number of PSUs
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Schneider_APC_Symmetra_PX_250_500_a_LX.csv; the profile maps the registers in the Symmetra PX Modbus register map (https://www.ccontrols.com/support/dp/APC_RegMap.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 335 of the 621 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (ECT board has an error; Breaker Q1 open; Breaker Q2 open...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
How many BACnet points does the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX have?
This list has 621 BACnet objects: 241 analog inputs, 380 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Schneider_APC_Symmetra_PX_250_500_a (Schneider_APC_Symmetra_PX_250_500_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Schneider_APC_Symmetra_PX_250_500_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX?
Start with BI 1 Load is being powered from battery (Load on battery); BI 3 Bypass (Load on bypass); BI 5 Load not Powered (Load not powered); AI 281 Runtime remaining (Runtime remaining, s); AI 358 Total Percent load (Total load, %); AI 338 Voltage L1-2 (output) (Output voltage L1-L2); AI 337 Frequency (output) (Output frequency); BI 2 Low-Battery (Low battery); BI 12 Warning alarm present (Warning alarm present); BI 13 Critical alarm present (Critical alarm present).
How do I check these points on the real Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Schneider_APC_Symmetra_PX_250_500_a · Schneider_APC_Symmetra_PX_250_500_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.