  4. Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX

UPS (uninterruptible power supply) · BACnet points list

Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the APC Symmetra PX 250/500 kW: 621 objects (241 AI, 380 BI), 335 polled by default. Binary inputs carry the UPS status and alarm flags (on battery, bypass, low battery, load not powered, warning and critical alarm, module failures, parallel faults); analog inputs give runtime, input/bypass/output voltages and frequencies, % load per phase and installation load.

This page lists 621 BACnet objects for the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Equipment
UPS (uninterruptible power supply)
Equipment type
Other equipment
BACnet objects
621 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K
Source document
BASgatewayLX Modbus device profile Schneider_APC_Symmetra_PX_250_500_a · Schneider_APC_Symmetra_PX_250_500_a_LX.csv
Download CSV 621 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX

Integration in brief

Read on battery, bypass, load not powered and the warning/critical alarm flags, plus runtime and total % load.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 1Load is being powered from batteryLoad on batteryRead
BI 3BypassLoad on bypassRead
BI 5Load not PoweredLoad not poweredRead
AI 281Runtime remainingRuntime remaining, sRead
AI 358Total Percent loadTotal load, %Read
AI 338Voltage L1-2 (output)Output voltage L1-L2Read
AI 337Frequency (output)Output frequencyRead
BI 2Low-BatteryLow batteryRead
BI 12Warning alarm presentWarning alarm presentRead
BI 13Critical alarm presentCritical alarm presentRead

Network setup

Watch out for

Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

621 of 621 shown
Type
AnalogBinary
Show
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet Points List
DescriptionStates
BImin1Load is being powered from batteryModbus 400001 bit 0Read
BImin2Low-BatteryModbus 400001 bit 1Read
BImin3BypassModbus 400001 bit 2Read
BI4Self-TestModbus 400001 bit 3Read
BImin5Load not PoweredModbus 400001 bit 4Read
BI6Abnormal ConditionModbus 400001 bit 7Read
BI7Power Module FailureModbus 400001 bit 8Read
BI8Battery System FailureModbus 400001 bit 9Read
BI9Intelligence Module (IM) has detected alarm conditionModbus 400001 bit 10Read
BI10Static Switch failureModbus 400001 bit 11Read
BI11Power Supply Unit failureModbus 400001 bit 12Read
BImin12Warning alarm presentModbus 400001 bit 14Read
BImin13Critical alarm presentModbus 400001 bit 15Read
BI14Lost local network management interface - to - UPS communicationModbus 400003 bit 0Read
BI15Parallel PBUS cables are swappedModbus 400003 bit 1Read
BI16Parallel communication error on PBUS cable 1Modbus 400003 bit 2Read
BI17Parallel communication error on PBUS cable 2Modbus 400003 bit 3Read
BI18Overload on parallel installationModbus 400003 bit 4Read
BI19Parallel mixed mode errorModbus 400003 bit 5Read
BI20UPS parallel address configuration number errorModbus 400003 bit 6Read
BI21Parallel master not detected (deprecated)Modbus 400003 bit 7Read
BI22Parallel unit disabledModbus 400003 bit 8Read
BI23Parallel unit is incompatibleModbus 400003 bit 9Read
BI24PBUS cable termination faultModbus 400003 bit 10Read
BI25Parallel unit not present (deprecated)Modbus 400003 bit 11Read
BI26Isolated Test mode is activateModbus 400003 bit 12Read
BI27Parallel unit redundancy lostModbus 400003 bit 13Read
BI28Parallel load share errorModbus 400003 bit 15Read
BI29On battery in response to an input power failureModbus 400004 bit 0Read
BI30In bypass: User-initiated from Front PanelModbus 400004 bit 1Read
BI31UPS operation mode - Forced bypassModbus 400004 bit 2Read
BI32In Bypass: For maintenanceModbus 400004 bit 3Read
BI33Started a self-testModbus 400004 bit 4Read
BI34Output power turned offModbus 400004 bit 5Read
BI35UPS operation mode - InitializeModbus 400004 bit 6Read
BI36UPS operation mode - Hot standbyModbus 400004 bit 7Read
BI37Compensating for a low input voltageModbus 400004 bit 8Read
BI38Compensating for a high input voltageModbus 400004 bit 9Read
BI39Input voltage waveform error detectedModbus 400004 bit 10Read
BI40Input phase sequence errorModbus 400004 bit 11Read
BI41Input frequency faultModbus 400004 bit 12Read
BI42Output frequency faultModbus 400004 bit 13Read
BI43Mega Tie mode is activeModbus 400004 bit 14Read
BI44Bypass voltage error: low voltageModbus 400005 bit 0Read
BI45Bypass voltage error: high voltageModbus 400005 bit 1Read
BI46Bypass voltage waveform error detectedModbus 400005 bit 2Read
BI47Bypass input frequency faultModbus 400005 bit 3Read
BI48Bypass phase sequence errorModbus 400005 bit 4Read
BI49Output voltage lowModbus 400005 bit 5Read
BI50Output voltage highModbus 400005 bit 6Read
BI51Output voltage waveform error detectedModbus 400005 bit 7Read
BI52OverloadModbus 400005 bit 8Read
BI53Overload on bypass static switchModbus 400005 bit 9Read
BI54Ambient temperature out of rangeModbus 400005 bit 10Read
BI55EPO activatedModbus 400005 bit 11Read
BI56Ground fault detectedModbus 400005 bit 12Read
BI57PSU module failedModbus 400005 bit 13Read
BI58System locked in bypass operationModbus 400006 bit 0Read
BI59Batteries are dischargingModbus 400006 bit 1Read
BI60PSU module not presentModbus 400006 bit 2Read
BI61System frequency not detectedModbus 400006 bit 3Read
BI62Charge power is reducedModbus 400006 bit 5Read
BI63Display communication to MIM and RIM is lostModbus 400006 bit 6Read
BI64CBUS terminator faultModbus 400006 bit 7Read
BI65ABUS terminator faultModbus 400006 bit 8Read
BI66MIM not presentModbus 400006 bit 10Read
BI67MIM heartbeat signal errorModbus 400006 bit 11Read
BI68RIM in controlModbus 400006 bit 12Read
BI69Battery condition is weakModbus 400006 bit 13Read
BI70Battery condition is poorModbus 400006 bit 14Read
BI71Battery voltage error - voltage above warning levelModbus 400007 bit 0Read
BI72Battery voltage error - voltage above shutdown levelModbus 400007 bit 1Read
BI73Battery monitor board communication errorModbus 400007 bit 2Read
BI74Battery is below minimum acceptable runtimeModbus 400007 bit 4Read
BI75Power module communication to MIM errorModbus 400007 bit 5Read
BI76Power module locked by IMModbus 400007 bit 6Read
BI77Power module operation mode is different from other modulesModbus 400007 bit 7Read
BI78Switchgear board not presentModbus 400007 bit 9Read
BI79Switchgear board communication errorModbus 400007 bit 10Read
BI80ID Relay board not presentModbus 400007 bit 11Read
BI81ID Relay board communication errorModbus 400007 bit 12Read
BI82Battery voltage collapse detectedModbus 400007 bit 13Read
BI83Power module redundancy lostModbus 400007 bit 14Read
BI84Load on subfeed is above warning levelModbus 400008 bit 7Read
BI85Load on subfeed is above critical levelModbus 400008 bit 8Read
BI86Load on UPS is above warning levelModbus 400008 bit 9Read
BI87Power module firmware version is incompatibleModbus 400008 bit 10Read
BI88Static Bypass Switch module not presentModbus 400008 bit 11Read
BI89Overload on installationModbus 400008 bit 12Read
BI90Bypass static switch communication errorModbus 400008 bit 13Read
BI91RIM not presentModbus 400008 bit 14Read
BI92RIM heartbeat signal errorModbus 400008 bit 15Read
BI93Bonding wire between neutral and ground is missingModbus 400009 bit 0Read
BI94Bonding wire between neutral and ground errorModbus 400009 bit 1Read
BI95Power module communication to RIM errorModbus 400009 bit 2Read
BI96Battery voltage error - voltage below warning levelModbus 400009 bit 3Read
BI97Battery voltage error - voltage below shutdown levelModbus 400009 bit 4Read
BI98ECT board has an errorModbus 400009 bit 5Read
BI99External connections board not presentModbus 400009 bit 6Read
BI100EPO circuit test mode is enabledModbus 400009 bit 7Read
BI101IM internal memory for storing configuration settings errorModbus 400009 bit 8Read
BI102Auxiliary monitor board for maintenance bypass panel comm errorModbus 400009 bit 10Read
BI103Auxiliary monitor board for battery breaker enclosure comm errorModbus 400009 bit 11Read
BI104Power module removed from the systemModbus 400009 bit 13Read
BI105INFO Battery module removed from systemModbus 400009 bit 14Read
BI106Power module fault existsModbus 400010 bit 0Read
BI107Power module warningModbus 400010 bit 1Read
BI108Power module fan faultModbus 400010 bit 3Read
BI109Power module is disabledModbus 400010 bit 4Read
BI110Power module lifetime error: close to endModbus 400010 bit 5Read
BI111Power module lifetime error: lifetime exceededModbus 400010 bit 6Read
BI112Power module fan lifetime error: close to endModbus 400010 bit 7Read
BI113Power module fan lifetimerror: lifetime exceededModbus 400010 bit 8Read
BI114Breaker Q1 openModbus 400010 bit 9Read
BI115Breaker Q2 openModbus 400010 bit 10Read
BI116Breaker Q3 closedModbus 400010 bit 11Read
BI117Breaker Q4 openModbus 400010 bit 12Read
BI118Breaker Q5 openModbus 400010 bit 13Read
BI119Power module phase-neutral displacement faultModbus 400010 bit 14Read
BI120Forced bypass switch activatedModbus 400011 bit 0Read
BI121Bypass static switch disabledModbus 400011 bit 1Read
BI122Bypass static switch self test failedModbus 400011 bit 2Read
BI123Bypass static switch 1 fan faultModbus 400011 bit 4Read
BI124Bypass static switch 1 fan weakModbus 400011 bit 5Read
BI125Bypass static switch error; module has a critical errorModbus 400011 bit 8Read
BI126Bypass static switch warning; module is not working properlyModbus 400011 bit 9Read
BI127Power enclosure air filter lifetime error: lifetime exceededModbus 400011 bit 10Read
BI128Power enclosure air filter lifetime error: lifetime exceededModbus 400011 bit 11Read
BI129Door in MBwD enclosure openModbus 400011 bit 14Read
BI130Q2 shunt open errorModbus 400011 bit 15Read
BI131Subfeed breaker SB1 openModbus 400012 bit 0Read
BI132Subfeed breaker SB2 openModbus 400012 bit 1Read
BI133Subfeed breaker SB3 openModbus 400012 bit 2Read
BI134Subfeed breaker SB4 openModbus 400012 bit 3Read
BI135Subfeed breaker SB5 openModbus 400012 bit 4Read
BI136Subfeed breaker SB6 openModbus 400012 bit 5Read
BI137Subfeed breaker SB7 openModbus 400012 bit 6Read
BI138Subfeed breaker SB8 openModbus 400012 bit 7Read
BI139Subfeed breaker SB9 openModbus 400012 bit 8Read
BI140Subfeed breaker SB10 openModbus 400012 bit 9Read
BI141Subfeed breaker SB11 openModbus 400012 bit 10Read
BI142Subfeed breaker SB12 openModbus 400012 bit 11Read
BI143Subfeed breaker SB13 openModbus 400012 bit 12Read
BI144Subfeed breaker SB14 openModbus 400012 bit 13Read
BI145Subfeed breaker SB15 openModbus 400012 bit 14Read
BI146Subfeed breaker SB16 openModbus 400012 bit 15Read
BI147Breaker Q1 openModbus 400013 bit 0Read
BI148Breaker Q2 openModbus 400013 bit 1Read
BI149Breaker Q3 closedModbus 400013 bit 2Read
BI150Breaker Q4 openModbus 400013 bit 3Read
BI151Breaker Q5 openModbus 400013 bit 4Read
BI152Door in maintenance bypass panel enclosure openModbus 400013 bit 5Read
BI153Q2 shunt open errorModbus 400013 bit 6Read
BI154MBP enclosure ECT board has an errorModbus 400013 bit 7Read
BI155ID Relay board memory card fullModbus 400013 bit 8Read
BI156Input 3 activated: Battery ground fault detectedModbus 400013 bit 9Read
BI157ID Relay board: System firmware not stored at memory cardModbus 400013 bit 10Read
BI158Input 6 activated: Emergency module offModbus 400013 bit 11Read
BI159Input 7 activated: Door in UPS I/O enclosure openedModbus 400013 bit 12Read
BI160Input 1 activated: Reduce charging powerModbus 400013 bit 13Read
BI161IDRC memory card not presentModbus 400013 bit 14Read
BI162ID Relay board memory card errorModbus 400013 bit 15Read
BI163Battery breaker openModbus 400014 bit 0Read
BI164Battery module fuse cleared or condition of battery is weakModbus 400014 bit 1Read
BI165Battery voltage symmetry errorModbus 400014 bit 2Read
BI166Internal battery temperature exceeds thresholdModbus 400014 bit 3Read
BI167Battery temperature sensor faultModbus 400014 bit 5Read
BI168Mixed battery configurationModbus 400014 bit 6Read
BI169Battery module type support errorModbus 400014 bit 7Read
BI170Battery string disconnectedModbus 400014 bit 8Read
BI171Battery side car 1 fuse errorModbus 400014 bit 9Read
BI172Battery enclosure PSU errorModbus 400014 bit 11Read
BI173Battery breaker motor PSU errorModbus 400014 bit 12Read
BI174Battery enclosure door openModbus 400014 bit 13Read
BI175ECT board has an errorModbus 400014 bit 14Read
BI176Battery breaker shunt open errorModbus 400014 bit 15Read
BI177Battery breaker open errorModbus 400015 bit 0Read
BI178Battery breaker enclosure fuse 1 errorModbus 400015 bit 1Read
BI179Battery breaker enclosure fuse 2 errorModbus 400015 bit 2Read
BI180Battery temperature 1 highModbus 400015 bit 3Read
BI181Battery temperature 2 highModbus 400015 bit 4Read
BI182Battery temperature sensor 1 faultModbus 400015 bit 5Read
BI183Battery temperature sensor 2 faultModbus 400015 bit 6Read
BI184Battery breaker enclosure door open errorModbus 400015 bit 7Read
BI185Battery breaker enclosure ECT board has an errorModbus 400015 bit 8Read
BI186Battery breaker shunt open errorModbus 400015 bit 9Read
BI187Battery ground fault detected errorModbus 400015 bit 10Read
BI188Battery fuse bank 1 clearedModbus 400016 bit 0Read
BI189Battery fuse bank 2 clearedModbus 400016 bit 1Read
BI190Battery fuse bank 3 clearedModbus 400016 bit 2Read
BI191Battery fuse bank 4 clearedModbus 400016 bit 3Read
BI192Battery fuse bank 5 clearedModbus 400016 bit 4Read
BI193Battery fuse bank 6 clearedModbus 400016 bit 5Read
BI194Battery fuse bank 7 clearedModbus 400016 bit 6Read
BI195Battery fuse bank 8 clearedModbus 400016 bit 7Read
BI196Input for gas alarm has been activatedModbus 400016 bit 8Read
BI197Test firmware installed at power moduleModbus 400017 bit 0Read
BI198Not expected firmware installed at power moduleModbus 400017 bit 1Read
BI199Not expected firmware installed at battery monitor boardModbus 400017 bit 2Read
BI200Not expected firmware installed at SBS moduleModbus 400017 bit 3Read
BI201Not expected firmware installed at ID Relay boardModbus 400017 bit 4Read
BI202Not expected firmware installed at switchgear boardModbus 400017 bit 5Read
BI203Not expected firmware installed at auxiliary boardModbus 400017 bit 6Read
BI204Not expected firmware installed at aux mon bd for battery breakModbus 400017 bit 7Read
BI205Not expected firmware installed at redundant IMModbus 400017 bit 8Read
BI206Test firmware installed at battery monitor boardModbus 400017 bit 9Read
BI207Test firmware installed at SBS moduleModbus 400017 bit 10Read
BI208Test firmware installed at ID Relay boardModbus 400017 bit 11Read
BI209Test firmware installed at switchgear boardModbus 400017 bit 12Read
BI210Test firmware installed at aux mon board for maint bypass panelModbus 400017 bit 13Read
BI211Test firmware installed at aux mon bd for battery break encModbus 400017 bit 14Read
BI212Test firmware installed at IMModbus 400017 bit 15Read
AI213ASCII 01 NMC Model NumberModbus 404097; not polled by defaultRead
AI214ASCII 02 NMC Model NumberModbus 404098; not polled by defaultRead
AI215ASCII 03 NMC Model NumberModbus 404099; not polled by defaultRead
AI216ASCII 04 NMC Model NumberModbus 404100; not polled by defaultRead
AI217ASCII 05 NMC Model NumberModbus 404101; not polled by defaultRead
AI218ASCII 06 NMC Model NumberModbus 404102; not polled by defaultRead
AI219ASCII 07 NMC Model NumberModbus 404103; not polled by defaultRead
AI220ASCII 08 NMC Model NumberModbus 404104; not polled by defaultRead
AI221ASCII 09 NMC Model NumberModbus 404105; not polled by defaultRead
AI222ASCII 01 NMC Serial NumberModbus 404106; not polled by defaultRead
AI223ASCII 02 NMC Serial NumberModbus 404107; not polled by defaultRead
AI224ASCII 03 NMC Serial NumberModbus 404108; not polled by defaultRead
AI225ASCII 04 NMC Serial NumberModbus 404109; not polled by defaultRead
AI226ASCII 05 NMC Serial NumberModbus 404110; not polled by defaultRead
AI227ASCII 06 NMC Serial NumberModbus 404111; not polled by defaultRead
AI228ASCII 07 NMC Serial NumberModbus 404112; not polled by defaultRead
AI229ASCII 08 NMC Serial NumberModbus 404113; not polled by defaultRead
AI230ASCII 01 NMC Firmware Revision APPModbus 404114; not polled by defaultRead
AI231ASCII 02 NMC Firmware Revision APPModbus 404115; not polled by defaultRead
AI232ASCII 03 NMC Firmware Revision APPModbus 404116; not polled by defaultRead
AI233ASCII 04 NMC Firmware Revision APPModbus 404117; not polled by defaultRead
AI234ASCII 05 NMC Firmware Revision APPModbus 404118; not polled by defaultRead
AI235ASCII 06 NMC Firmware Revision APPModbus 404119; not polled by defaultRead
AI236ASCII 07 NMC Firmware Revision APPModbus 404120; not polled by defaultRead
AI237ASCII 08 NMC Firmware Revision APPModbus 404121; not polled by defaultRead
AI238ASCII 09 NMC Firmware Revision APPModbus 404122; not polled by defaultRead
AI239ASCII 01 NMC Hardware RevisionModbus 404123; not polled by defaultRead
AI240ASCII 02 NMC Hardware RevisionModbus 404124; not polled by defaultRead
AI241ASCII 03 NMC Hardware RevisionModbus 404125; not polled by defaultRead
AI242ASCII 04 NMC Hardware RevisionModbus 404126; not polled by defaultRead
AI243ASCII 05 NMC Hardware RevisionModbus 404127; not polled by defaultRead
AI244ASCII 06 NMC Hardware RevisionModbus 404128; not polled by defaultRead
AI245ASCII 07 NMC Hardware RevisionModbus 404129; not polled by defaultRead
AI246ASCII 08 NMC Hardware RevisionModbus 404130; not polled by defaultRead
AI247ASCII 09 NMC Hardware RevisionModbus 404131; not polled by defaultRead
AI248ASCII 01 NMC Date of ManufactureModbus 404132; not polled by defaultRead
AI249ASCII 02 NMC Date of ManufactureModbus 404133; not polled by defaultRead
AI250ASCII 03 NMC Date of ManufactureModbus 404134; not polled by defaultRead
AI251ASCII 04 NMC Date of ManufactureModbus 404135; not polled by defaultRead
AI252ASCII 05 NMC Date of ManufactureModbus 404136; not polled by defaultRead
AI253ASCII 06 NMC Date of ManufactureModbus 404137; not polled by defaultRead
AI254ASCII 01 UPS Model NameModbus 404138; not polled by defaultRead
AI255ASCII 02 UPS Model NameModbus 404139; not polled by defaultRead
AI256ASCII 03 UPS Model NameModbus 404140; not polled by defaultRead
AI257ASCII 04 UPS Model NameModbus 404141; not polled by defaultRead
AI258ASCII 05 UPS Model NameModbus 404142; not polled by defaultRead
AI259ASCII 06 UPS Model NameModbus 404143; not polled by defaultRead
AI260ASCII 07 UPS Model NameModbus 404144; not polled by defaultRead
AI261ASCII 08 UPS Model NameModbus 404145; not polled by defaultRead
AI262ASCII 01 UPS Serial NumberModbus 404146; not polled by defaultRead
AI263ASCII 02 UPS Serial NumberModbus 404147; not polled by defaultRead
AI264ASCII 03 UPS Serial NumberModbus 404148; not polled by defaultRead
AI265ASCII 04 UPS Serial NumberModbus 404149; not polled by defaultRead
AI266ASCII 05 UPS Serial NumberModbus 404150; not polled by defaultRead
AI267ASCII 06 UPS Serial NumberModbus 404151; not polled by defaultRead
AI268ASCII 01 UPS Firmware VersionModbus 404152; not polled by defaultRead
AI269ASCII 02 UPS Firmware VersionModbus 404153; not polled by defaultRead
AI270ASCII 03 UPS Firmware VersionModbus 404154; not polled by defaultRead
AI271ASCII 04 UPS Firmware VersionModbus 404155; not polled by defaultRead
AI272ASCII 05 UPS Firmware VersionModbus 404156; not polled by defaultRead
AI273ASCII 06 UPS Firmware VersionModbus 404157; not polled by defaultRead
AI274ASCII 07 UPS Firmware VersionModbus 404158; not polled by defaultRead
AI275ASCII 08 UPS Firmware VersionModbus 404159; not polled by defaultRead
AI276ASCII 09 UPS Firmware VersionModbus 404160; not polled by defaultRead
AI277ASCII 10 UPS Firmware VersionModbus 404161; not polled by defaultRead
AI278ASCII 11 UPS Firmware VersionModbus 404162; not polled by defaultRead
AI279ASCII 12 UPS Firmware VersionModbus 404163; not polled by defaultRead
AI280Time on batteryModbus 404353sRead
AImin281Runtime remainingModbus 404355sRead
AI282Estimated charge timeModbus 404357sRead
AI283Estimated charge %Modbus 404359%Read
AI284Battery (+) VoltageModbus 404360VRead
AI285Battery (-) VoltageModbus 404361VRead
AI286Battery (+) CurrentModbus 404362ARead
AI287Battery (-) CurrentModbus 404363ARead
AI288Total time on batteryModbus 404364sRead
AI289Total number of times on batteryModbus 404366Read
AI290APC Battery Breaker Status /User supplied battery Breaker StatusModbus 404367Read
AI291BatterySystem/TemperatureModbus 404368°CRead
BI292User Supplied Battery System Charger StatusModbus 404369 bit 0Read
BI293Boost ChargingModbus 404369 bit 1Read
BI294Normal ChargingModbus 404369 bit 2Read
BI295RestingModbus 404369 bit 3Read
BI296DischargingModbus 404369 bit 4Read
BI297Equalization ChargingModbus 404369 bit 5Read
AI298Battery PowerModbus 404370kWRead
AI299Available Amp HoursModbus 404371Read
AI300Frequency (input)Modbus 404609HzRead
AI301Voltage L1-2 (input)Modbus 404610VRead
AI302Voltage L2-3 (input)Modbus 404611VRead
AI303Voltage L3-1 (input)Modbus 404612VRead
AI304Current L1 (input)Modbus 404613ARead
AI305Current L2 (input)Modbus 404614ARead
AI306Current L3 (input)Modbus 404615ARead
AI307Active power L1 (input)Modbus 404616kWRead
AI308Active power L2 (input)Modbus 404617kWRead
AI309Active power L3 (input)Modbus 404618kWRead
AI310Apparent power L1 (input)Modbus 404619kVARead
AI311Apparent power L2 (input)Modbus 404620kVARead
AI312Apparent power L3 (input)Modbus 404621kVARead
AI313Total active power (input)Modbus 404622kWRead
AI314Total apparent power (input)Modbus 404623kVARead
AI315Current L1 (parallel input)Modbus 404624ARead
AI316Current L2 (parallel input)Modbus 404625ARead
AI317Current L3 (parallel input)Modbus 404626ARead
AI318Frequency (bypass)Modbus 404865HzRead
AI319Voltage L1-2 (bypass)Modbus 404866VRead
AI320Voltage L2-3 (bypass)Modbus 404867VRead
AI321Voltage L3-1 (bypass)Modbus 404868VRead
AI322Current L1 (bypass)Modbus 404869ARead
AI323Current L2 (bypass)Modbus 404870ARead
AI324Current L3 (bypass)Modbus 404871ARead
AI325Active power L1 (bypass)Modbus 404872kWRead
AI326Active power L2 (bypass)Modbus 404873kWRead
AI327Active power L3 (bypass)Modbus 404874kWRead
AI328Apparent power L1 (bypass)Modbus 404875kVARead
AI329Apparent power L2 (bypass)Modbus 404876kVARead
AI330Apparent power L3 (bypass)Modbus 404877kVARead
AI331Total active power (bypass)Modbus 404878kWRead
AI332Total apparent power (bypass)Modbus 404879kVARead
AI333Current L1 (parallel bypass)Modbus 404880ARead
AI334Current L2 (parallel bypass)Modbus 404881ARead
AI335Current L3 (parallel bypass)Modbus 404882ARead
AI336Nominal (Apparent) output ratingModbus 405121kVARead
AImin337Frequency (output)Modbus 405122HzRead
AImin338Voltage L1-2 (output)Modbus 405123VRead
AI339Voltage L2-3 (output)Modbus 405124VRead
AI340Voltage L3-1 (output)Modbus 405125VRead
AI341Current L1 (output)Modbus 405126ARead
AI342Current L2 (output)Modbus 405127ARead
AI343Current L3 (output)Modbus 405128ARead
AI344Peak current L1 (output)Modbus 405129ARead
AI345Peak current L2 (output)Modbus 405131ARead
AI346Peak current L3 (output)Modbus 405133ARead
AI347Active power L1 (output)Modbus 405135kWRead
AI348Active power L2 (output)Modbus 405136kWRead
AI349Active power L3 (output)Modbus 405137kWRead
AI350Apparent power L1 (output)Modbus 405138kVARead
AI351Apparent power L2 (output)Modbus 405139kVARead
AI352Apparent power L3 (output)Modbus 405140kVARead
AI353% Load L1Modbus 405141%Read
AI354% Load L2Modbus 405142%Read
AI355% Load L3Modbus 405143%Read
AI356Total active power (output)Modbus 405144kWRead
AI357Total apparent power (output)Modbus 405145kVARead
AImin358Total Percent loadModbus 405146%Read
AI359Power factor L1 (output)Modbus 405147PFRead
AI360Power factor L2 (output)Modbus 405148PFRead
AI361Power factor L3 (output)Modbus 405149PFRead
AI362Current crest factor L1 (output)Modbus 405150Read
AI363Current crest factor L2 (output)Modbus 405151Read
AI364Current crest factor L3 (output)Modbus 405152Read
AI365Parallel System Output CurrentAC L1Modbus 405153ARead
AI366Parallel System Output CurrentAC L2Modbus 405154ARead
AI367Parallel System Output CurrentAC L3Modbus 405155ARead
AI368Parallel System Output Active Power L1Modbus 405156kWRead
AI369Parallel System Output Active Power L2Modbus 405157kWRead
AI370Parallel System Output Active Power L3Modbus 405158kWRead
AI371Parallel System Output Apparent Power L1Modbus 405159kVARead
AI372Parallel System Output Apparent Power L2Modbus 405160kVARead
AI373Parallel System Output Apparent Power L3Modbus 405161kVARead
AI374ParallelSystem Output % Load L1Modbus 405162%Read
AI375ParallelSystem Output % Load L2Modbus 405163%Read
AI376ParallelSystem Output % Load L3Modbus 405164%Read
AI377ParallelSystem Output Total Active PowerModbus 405165kWRead
AI378ParallelSystem Output Total Apparent PowerModbus 405166kVARead
AI379ParallelSystem Output Total % LoadModbus 405167%Read
AI380Energy Meter kwHModbus 405168kWhRead
AI381UPS Installation Load % (Standalone )Modbus 405170%Read
AI382UPS Installation Load % (Parallel )Modbus 405171%Read
AI383Ambient temperatureModbus 405377°CRead
BI384Q1Modbus 405378 bit 0Read
BI385Q2Modbus 405378 bit 1Read
BI386Q3Modbus 405378 bit 2Read
BI387Q5Modbus 405378 bit 4Read
AI388UPS Mode Operation mode of the UPSModbus 405379Read
AI389Number of Active AlarmsModbus 405380Read
AI390Highest alarm severityModbus 405381Read
AI391System ModeModbus 405382Read
BI392Input 01 Contact StatusModbus 405383 bit 0; not polled by defaultRead
BI393Input 02 Contact StatusModbus 405383 bit 1; not polled by defaultRead
BI394Input 03 Contact StatusModbus 405383 bit 2; not polled by defaultRead
BI395Input 04 Contact StatusModbus 405383 bit 3; not polled by defaultRead
BI396Input 05 Contact StatusModbus 405383 bit 4; not polled by defaultRead
BI397Input 06 Contact StatusModbus 405383 bit 5; not polled by defaultRead
BI398Input 07 Contact StatusModbus 405383 bit 6; not polled by defaultRead
BI399Input 08 Contact StatusModbus 405383 bit 7; not polled by defaultRead
BI400Input 09 Contact StatusModbus 405383 bit 8; not polled by defaultRead
BI401Input 10 Contact StatusModbus 405383 bit 9; not polled by defaultRead
BI402Input 11 Contact StatusModbus 405383 bit 10; not polled by defaultRead
BI403Input 12 Contact StatusModbus 405383 bit 11; not polled by defaultRead
BI404Input 13 Contact StatusModbus 405383 bit 12; not polled by defaultRead
BI405Input 14 Contact StatusModbus 405383 bit 13; not polled by defaultRead
BI406Input 15 Contact StatusModbus 405383 bit 14; not polled by defaultRead
BI407Input 16 Contact StatusModbus 405383 bit 15; not polled by defaultRead
BI408Output 01 Contact StatusModbus 405384 bit 0; not polled by defaultRead
BI409Output 02 Contact StatusModbus 405383 bit 1; not polled by defaultRead
BI410Output 03 Contact StatusModbus 405383 bit 2; not polled by defaultRead
BI411Output 04 Contact StatusModbus 405383 bit 3; not polled by defaultRead
BI412Output 05 Contact StatusModbus 405383 bit 4; not polled by defaultRead
BI413Output 06 Contact StatusModbus 405383 bit 5; not polled by defaultRead
BI414Output 07 Contact StatusModbus 405383 bit 6; not polled by defaultRead
BI415Output 08 Contact StatusModbus 405383 bit 7; not polled by defaultRead
BI416Output 09 Contact StatusModbus 405383 bit 8; not polled by defaultRead
BI417Output 10 Contact StatusModbus 405383 bit 9; not polled by defaultRead
BI418Output 11 Contact StatusModbus 405383 bit 10; not polled by defaultRead
BI419Output 12 Contact StatusModbus 405383 bit 11; not polled by defaultRead
BI420Output 13 Contact StatusModbus 405383 bit 12; not polled by defaultRead
BI421Output 14 Contact StatusModbus 405383 bit 13; not polled by defaultRead
BI422Output 15 Contact StatusModbus 405383 bit 14; not polled by defaultRead
BI423Output 16 Contact StatusModbus 405383 bit 15; not polled by defaultRead
AI424Output Contact Normal State SettingModbus 405384Read
AI425Redundancy StatusModbus 405385Read
AI426ASCII 01 NMC/UPS TimeModbus 405386; not polled by defaultRead
AI427ASCII 02 NMC/UPS TimeModbus 405387; not polled by defaultRead
AI428ASCII 03 NMC/UPS TimeModbus 405388; not polled by defaultRead
AI429ASCII 04 NMC/UPS TimeModbus 405389; not polled by defaultRead
AI430ASCII 01 NMC/UPS DatenModbus 405390; not polled by defaultRead
AI431ASCII 02 NMC/UPS DatenModbus 405391; not polled by defaultRead
AI432ASCII 03 NMC/UPS DatenModbus 405392; not polled by defaultRead
AI433ASCII 04 NMC/UPS DatenModbus 405393; not polled by defaultRead
AI434ASCII 05 NMC/UPS DatenModbus 405394; not polled by defaultRead
AI435Parallel System Redundancy StatusModbus 405395Read
BI436Bypass Life Time Status OKModbus 405633 bit 0Read
BI437Bypass Life Time Status Near EndModbus 405633 bit 1Read
BI438Bypass Life Time Status ExceededModbus 405633 bit 2Read
AI439Bypass Estimated Lifetime RemainingModbus 405634daysRead
BI440Bypass Fan Life Time Status OKModbus 405635 bit 0Read
BI441Bypass Fan Life Time Status Near EndModbus 405635 bit 1Read
BI442Bypass Fan Life Time Status ExceededModbus 405635 bit 2Read
AI443Bypass Fan Estimated Lifetime RemainingModbus 405636daysRead
BI444Frame[0] Power Module[0] Life Time Status OKModbus 405889 bit 0; not polled by defaultRead
BI445Frame[0] Power Module[0] Life Time Status Near EndModbus 405889 bit 1; not polled by defaultRead
BI446Frame[0] Power Module[0] Life Time Status ExceededModbus 405889 bit 2; not polled by defaultRead
AI447Frame[0] Power Module[0] Estimated Lifetime RemainingModbus 405890; not polled by defaultdaysRead
BI448Frame[0] Power Module[0] Fan Life Time Status OKModbus 405891 bit 0; not polled by defaultRead
BI449Frame[0] Power Module[0] Fan Life Time Status Near EndModbus 405891 bit 1; not polled by defaultRead
BI450Frame[0] Power Module[0] Fan Life Time Status ExceededModbus 405891 bit 2; not polled by defaultRead
AI451Frame[0] Power Module[0] Fan Estimated Lifetime RemainingModbus 405892; not polled by defaultdaysRead
BI452Frame[0] Power Module[1] Life Time Status OKModbus 405893 bit 0; not polled by defaultRead
BI453Frame[0] Power Module[1] Life Time Status Near EndModbus 405893 bit 1; not polled by defaultRead
BI454Frame[0] Power Module[1] Life Time Status ExceededModbus 405893 bit 2; not polled by defaultRead
AI455Frame[0] Power Module[1] Estimated Lifetime RemainingModbus 405894; not polled by defaultdaysRead
BI456Frame[0] Power Module[1] Fan Life Time Status OKModbus 405895 bit 0; not polled by defaultRead
BI457Frame[0] Power Module[1] Fan Life Time Status Near EndModbus 405895 bit 1; not polled by defaultRead
BI458Frame[0] Power Module[1] Fan Life Time Status ExceededModbus 405895 bit 2; not polled by defaultRead
AI459Frame[0] Power Module[1] Fan Estimated Lifetime RemainingModbus 405896; not polled by defaultdaysRead
BI460Frame[0] Power Module[2] Life Time Status OKModbus 405897 bit 0; not polled by defaultRead
BI461Frame[0] Power Module[2] Life Time Status Near EndModbus 405897 bit 1; not polled by defaultRead
BI462Frame[0] Power Module[2] Life Time Status ExceededModbus 405897 bit 2; not polled by defaultRead
AI463Frame[0] Power Module[2] Estimated Lifetime RemainingModbus 405898; not polled by defaultdaysRead
BI464Frame[0] Power Module[2] Fan Life Time Status OKModbus 405899 bit 0; not polled by defaultRead
BI465Frame[0] Power Module[2] Fan Life Time Status Near EndModbus 405899 bit 1; not polled by defaultRead
BI466Frame[0] Power Module[2] Fan Life Time Status ExceededModbus 405899 bit 2; not polled by defaultRead
AI467Frame[0] Power Module[2] Fan Estimated Lifetime RemainingModbus 405900; not polled by defaultdaysRead
BI468Frame[0] Power Module[3] Life Time Status OKModbus 405901 bit 0; not polled by defaultRead
BI469Frame[0] Power Module[3] Life Time Status Near EndModbus 405901 bit 1; not polled by defaultRead
BI470Frame[0] Power Module[3] Life Time Status ExceededModbus 405901 bit 2; not polled by defaultRead
AI471Frame[0] Power Module[3] Estimated Lifetime RemainingModbus 405902; not polled by defaultdaysRead
BI472Frame[0] Power Module[3] Fan Life Time Status OKModbus 405903 bit 0; not polled by defaultRead
BI473Frame[0] Power Module[3] Fan Life Time Status Near EndModbus 405903 bit 1; not polled by defaultRead
BI474Frame[0] Power Module[3] Fan Life Time Status ExceededModbus 405903 bit 2; not polled by defaultRead
AI475Frame[0] Power Module[3] Fan Estimated Lifetime RemainingModbus 405904; not polled by defaultdaysRead
BI476Frame[0] Power Module[4] Life Time Status OKModbus 405905 bit 0; not polled by defaultRead
BI477Frame[0] Power Module[4] Life Time Status Near EndModbus 405905 bit 1; not polled by defaultRead
BI478Frame[0] Power Module[4] Life Time Status ExceededModbus 405905 bit 2; not polled by defaultRead
AI479Frame[0] Power Module[4] Estimated Lifetime RemainingModbus 405906; not polled by defaultdaysRead
BI480Frame[0] Power Module[4] Fan Life Time Status OKModbus 405907 bit 0; not polled by defaultRead
BI481Frame[0] Power Module[4] Fan Life Time Status Near EndModbus 405907 bit 1; not polled by defaultRead
BI482Frame[0] Power Module[4] Fan Life Time Status ExceededModbus 405907 bit 2; not polled by defaultRead
AI483Frame[0] Power Module[4] Fan Estimated Lifetime RemainingModbus 405908; not polled by defaultdaysRead
BI484Frame[0] Power Module[5] Life Time Status OKModbus 405909 bit 0; not polled by defaultRead
BI485Frame[0] Power Module[5] Life Time Status Near EndModbus 405909 bit 1; not polled by defaultRead
BI486Frame[0] Power Module[5] Life Time Status ExceededModbus 405909 bit 2; not polled by defaultRead
AI487Frame[0] Power Module[5] Estimated Lifetime RemainingModbus 405910; not polled by defaultdaysRead
BI488Frame[0] Power Module[5] Fan Life Time Status OKModbus 405911 bit 0; not polled by defaultRead
BI489Frame[0] Power Module[5] Fan Life Time Status Near EndModbus 405911 bit 1; not polled by defaultRead
BI490Frame[0] Power Module[5] Fan Life Time Status ExceededModbus 405911 bit 2; not polled by defaultRead
AI491Frame[0] Power Module[5] Fan Estimated Lifetime RemainingModbus 405912; not polled by defaultdaysRead
BI492Frame[0] Power Module[6] Life Time Status OKModbus 405913 bit 0; not polled by defaultRead
BI493Frame[0] Power Module[6] Life Time Status Near EndModbus 405913 bit 1; not polled by defaultRead
BI494Frame[0] Power Module[6] Life Time Status ExceededModbus 405913 bit 2; not polled by defaultRead
AI495Frame[0] Power Module[6] Estimated Lifetime RemainingModbus 405914; not polled by defaultdaysRead
BI496Frame[0] Power Module[6] Fan Life Time Status OKModbus 405915 bit 0; not polled by defaultRead
BI497Frame[0] Power Module[6] Fan Life Time Status Near EndModbus 405915 bit 1; not polled by defaultRead
BI498Frame[0] Power Module[6] Fan Life Time Status ExceededModbus 405915 bit 2; not polled by defaultRead
AI499Frame[0] Power Module[6] Fan Estimated Lifetime RemainingModbus 405916; not polled by defaultdaysRead
BI500Frame[0] Power Module[7] Life Time Status OKModbus 405917 bit 0; not polled by defaultRead
BI501Frame[0] Power Module[7] Life Time Status Near EndModbus 405917 bit 1; not polled by defaultRead
BI502Frame[0] Power Module[7] Life Time Status ExceededModbus 405917 bit 2; not polled by defaultRead
AI503Frame[0] Power Module[7] Estimated Lifetime RemainingModbus 405918; not polled by defaultdaysRead
BI504Frame[0] Power Module[7] Fan Life Time Status OKModbus 405919 bit 0; not polled by defaultRead
BI505Frame[0] Power Module[7] Fan Life Time Status Near EndModbus 405919 bit 1; not polled by defaultRead
BI506Frame[0] Power Module[7] Fan Life Time Status ExceededModbus 405919 bit 2; not polled by defaultRead
AI507Frame[0] Power Module[7] Fan Estimated Lifetime RemainingModbus 405920; not polled by defaultdaysRead
BI508Frame[0] Power Module[8] Life Time Status OKModbus 405921 bit 0; not polled by defaultRead
BI509Frame[0] Power Module[8] Life Time Status Near EndModbus 405921 bit 1; not polled by defaultRead
BI510Frame[0] Power Module[8] Life Time Status ExceededModbus 405921 bit 2; not polled by defaultRead
AI511Frame[0] Power Module[8] Estimated Lifetime RemainingModbus 405922; not polled by defaultdaysRead
BI512Frame[0] Power Module[8] Fan Life Time Status OKModbus 405923 bit 0; not polled by defaultRead
BI513Frame[0] Power Module[8] Fan Life Time Status Near EndModbus 405923 bit 1; not polled by defaultRead
BI514Frame[0] Power Module[8] Fan Life Time Status ExceededModbus 405923 bit 2; not polled by defaultRead
AI515Frame[0] Power Module[8] Fan Estimated Lifetime RemainingModbus 405924; not polled by defaultdaysRead
BI516Frame[0] Power Module[9] Life Time Status OKModbus 405925 bit 0; not polled by defaultRead
BI517Frame[0] Power Module[9] Life Time Status Near EndModbus 405925 bit 1; not polled by defaultRead
BI518Frame[0] Power Module[9] Life Time Status ExceededModbus 405925 bit 2; not polled by defaultRead
AI519Frame[0] Power Module[9] Estimated Lifetime RemainingModbus 405926; not polled by defaultdaysRead
BI520Frame[0] Power Module[9] Fan Life Time Status OKModbus 405927 bit 0; not polled by defaultRead
BI521Frame[0] Power Module[9] Fan Life Time Status Near EndModbus 405927 bit 1; not polled by defaultRead
BI522Frame[0] Power Module[9] Fan Life Time Status ExceededModbus 405927 bit 2; not polled by defaultRead
AI523Frame[0] Power Module[9] Fan Estimated Lifetime RemainingModbus 405928; not polled by defaultdaysRead
BI524Frame[1]Power Module[0] Life Time Status OKModbus 406145 bit 0; not polled by defaultRead
BI525Frame[1]Power Module[0] Life Time Status Near EndModbus 406145 bit 1; not polled by defaultRead
BI526Frame[1]Power Module[0] Life Time Status ExceededModbus 406145 bit 2; not polled by defaultRead
AI527Frame[1]Power Module[0] Estimated Lifetime RemainingModbus 406146; not polled by defaultdaysRead
BI528Frame[1]Power Module[0] Fan Life Time Status OKModbus 406147 bit 0; not polled by defaultRead
BI529Frame[1]Power Module[0] Fan Life Time Status Near EndModbus 406147 bit 1; not polled by defaultRead
BI530Frame[1]Power Module[0] Fan Life Time Status ExceededModbus 406147 bit 2; not polled by defaultRead
AI531Frame[1]Power Module[0] Fan Estimated Lifetime RemainingModbus 406148; not polled by defaultdaysRead
BI532Frame[1]Power Module[1] Life Time Status OKModbus 406149 bit 0; not polled by defaultRead
BI533Frame[1]Power Module[1] Life Time Status Near EndModbus 406149 bit 1; not polled by defaultRead
BI534Frame[1]Power Module[1] Life Time Status ExceededModbus 406149 bit 2; not polled by defaultRead
AI535Frame[1]Power Module[1] Estimated Lifetime RemainingModbus 406150; not polled by defaultdaysRead
BI536Frame[1]Power Module[1] Fan Life Time Status OKModbus 406151 bit 0; not polled by defaultRead
BI537Frame[1]Power Module[1] Fan Life Time Status Near EndModbus 406151 bit 1; not polled by defaultRead
BI538Frame[1]Power Module[1] Fan Life Time Status ExceededModbus 406151 bit 2; not polled by defaultRead
AI539Frame[1]Power Module[1] Fan Estimated Lifetime RemainingModbus 406152; not polled by defaultdaysRead
BI540Frame[1]Power Module[2] Life Time Status OKModbus 406153 bit 0; not polled by defaultRead
BI541Frame[1]Power Module[2] Life Time Status Near EndModbus 406153 bit 1; not polled by defaultRead
BI542Frame[1]Power Module[2] Life Time Status ExceededModbus 406153 bit 2; not polled by defaultRead
AI543Frame[1]Power Module[2] Estimated Lifetime RemainingModbus 406154; not polled by defaultdaysRead
BI544Frame[1]Power Module[2] Fan Life Time Status OKModbus 406155 bit 0; not polled by defaultRead
BI545Frame[1]Power Module[2] Fan Life Time Status Near EndModbus 406155 bit 1; not polled by defaultRead
BI546Frame[1]Power Module[2] Fan Life Time Status ExceededModbus 406155 bit 2; not polled by defaultRead
AI547Frame[1]Power Module[2] Fan Estimated Lifetime RemainingModbus 406156; not polled by defaultdaysRead
BI548Frame[1]Power Module[3] Life Time Status OKModbus 406157 bit 0; not polled by defaultRead
BI549Frame[1]Power Module[3] Life Time Status Near EndModbus 406157 bit 1; not polled by defaultRead
BI550Frame[1]Power Module[3] Life Time Status ExceededModbus 406157 bit 2; not polled by defaultRead
AI551Frame[1]Power Module[3] Estimated Lifetime RemainingModbus 406158; not polled by defaultdaysRead
BI552Frame[1]Power Module[3] Fan Life Time Status OKModbus 406159 bit 0; not polled by defaultRead
BI553Frame[1]Power Module[3] Fan Life Time Status Near EndModbus 406159 bit 1; not polled by defaultRead
BI554Frame[1]Power Module[3] Fan Life Time Status ExceededModbus 406159 bit 2; not polled by defaultRead
AI555Frame[1]Power Module[3] Fan Estimated Lifetime RemainingModbus 406160; not polled by defaultdaysRead
BI556Frame[1]Power Module[4] Life Time Status OKModbus 406161 bit 0; not polled by defaultRead
BI557Frame[1]Power Module[4] Life Time Status Near EndModbus 406161 bit 1; not polled by defaultRead
BI558Frame[1]Power Module[4] Life Time Status ExceededModbus 406161 bit 2; not polled by defaultRead
AI559Frame[1]Power Module[4] Estimated Lifetime RemainingModbus 406162; not polled by defaultdaysRead
BI560Frame[1]Power Module[4] Fan Life Time Status OKModbus 406163 bit 0; not polled by defaultRead
BI561Frame[1]Power Module[4] Fan Life Time Status Near EndModbus 406163 bit 1; not polled by defaultRead
BI562Frame[1]Power Module[4] Fan Life Time Status ExceededModbus 406163 bit 2; not polled by defaultRead
AI563Frame[1]Power Module[4] Fan Estimated Lifetime RemainingModbus 406164; not polled by defaultdaysRead
BI564Frame[1]Power Module[5] Life Time Status OKModbus 406165 bit 0; not polled by defaultRead
BI565Frame[1]Power Module[5] Life Time Status Near EndModbus 406165 bit 1; not polled by defaultRead
BI566Frame[1]Power Module[5] Life Time Status ExceededModbus 406165 bit 2; not polled by defaultRead
AI567Frame[1]Power Module[5] Estimated Lifetime RemainingModbus 406166; not polled by defaultdaysRead
BI568Frame[1]Power Module[5] Fan Life Time Status OKModbus 406167 bit 0; not polled by defaultRead
BI569Frame[1]Power Module[5] Fan Life Time Status Near EndModbus 406167 bit 1; not polled by defaultRead
BI570Frame[1]Power Module[5] Fan Life Time Status ExceededModbus 406167 bit 2; not polled by defaultRead
AI571Frame[1]Power Module[5] Fan Estimated Lifetime RemainingModbus 406168; not polled by defaultdaysRead
BI572Frame[1]Power Module[6] Life Time Status OKModbus 406169 bit 0; not polled by defaultRead
BI573Frame[1]Power Module[6] Life Time Status Near EndModbus 406169 bit 1; not polled by defaultRead
BI574Frame[1]Power Module[6] Life Time Status ExceededModbus 406169 bit 2; not polled by defaultRead
AI575Frame[1]Power Module[6] Estimated Lifetime RemainingModbus 406170; not polled by defaultdaysRead
BI576Frame[1]Power Module[6] Fan Life Time Status OKModbus 406171 bit 0; not polled by defaultRead
BI577Frame[1]Power Module[6] Fan Life Time Status Near EndModbus 406171 bit 1; not polled by defaultRead
BI578Frame[1]Power Module[6] Fan Life Time Status ExceededModbus 406171 bit 2; not polled by defaultRead
AI579Frame[1]Power Module[6] Fan Estimated Lifetime RemainingModbus 406172; not polled by defaultdaysRead
BI580Frame[1]Power Module[7] Life Time Status OKModbus 406173 bit 0; not polled by defaultRead
BI581Frame[1]Power Module[7] Life Time Status Near EndModbus 406173 bit 1; not polled by defaultRead
BI582Frame[1]Power Module[7] Life Time Status ExceededModbus 406173 bit 2; not polled by defaultRead
AI583Frame[1]Power Module[7] Estimated Lifetime RemainingModbus 406174; not polled by defaultdaysRead
BI584Frame[1]Power Module[7] Fan Life Time Status OKModbus 406175 bit 0; not polled by defaultRead
BI585Frame[1]Power Module[7] Fan Life Time Status Near EndModbus 406175 bit 1; not polled by defaultRead
BI586Frame[1]Power Module[7] Fan Life Time Status ExceededModbus 406175 bit 2; not polled by defaultRead
AI587Frame[1]Power Module[7] Fan Estimated Lifetime RemainingModbus 406176; not polled by defaultdaysRead
BI588Frame[1]Power Module[8] Life Time Status OKModbus 406177 bit 0; not polled by defaultRead
BI589Frame[1]Power Module[8] Life Time Status Near EndModbus 406177 bit 1; not polled by defaultRead
BI590Frame[1]Power Module[8] Life Time Status ExceededModbus 406177 bit 2; not polled by defaultRead
AI591Frame[1]Power Module[8] Estimated Lifetime RemainingModbus 406178; not polled by defaultdaysRead
BI592Frame[1]Power Module[8] Fan Life Time Status OKModbus 406179 bit 0; not polled by defaultRead
BI593Frame[1]Power Module[8] Fan Life Time Status Near EndModbus 406179 bit 1; not polled by defaultRead
BI594Frame[1]Power Module[8] Fan Life Time Status ExceededModbus 406179 bit 2; not polled by defaultRead
AI595Frame[1]Power Module[8] Fan Estimated Lifetime RemainingModbus 406180; not polled by defaultdaysRead
BI596Frame[1]Power Module[9] Life Time Status OKModbus 406181 bit 0; not polled by defaultRead
BI597Frame[1]Power Module[9] Life Time Status Near EndModbus 406181 bit 1; not polled by defaultRead
BI598Frame[1]Power Module[9] Life Time Status ExceededModbus 406181 bit 2; not polled by defaultRead
AI599Frame[1]Power Module[9] Estimated Lifetime RemainingModbus 406182; not polled by defaultdaysRead
BI600Frame[1]Power Module[9] Fan Life Time Status OKModbus 406183 bit 0; not polled by defaultRead
BI601Frame[1]Power Module[9] Fan Life Time Status Near EndModbus 406183 bit 1; not polled by defaultRead
BI602Frame[1]Power Module[9] Fan Life Time Status ExceededModbus 406183 bit 2; not polled by defaultRead
AI603Frame[1]Power Module[9] Fan Estimated Lifetime RemainingModbus 406184; not polled by defaultdaysRead
AI604ASCII 01 UPS NameModbus 404164; not polled by defaultRead
AI605ASCII 02 UPS NameModbus 404165; not polled by defaultRead
AI606ASCII 03 UPS NameModbus 404166; not polled by defaultRead
AI607ASCII 04 UPS NameModbus 404167; not polled by defaultRead
AI608ASCII 01 Parallel System NameModbus 404168; not polled by defaultRead
AI609ASCII 02 Parallel System NameModbus 404169; not polled by defaultRead
AI610ASCII 03 Parallel System NameModbus 404170; not polled by defaultRead
AI611ASCII 04 Parallel System NameModbus 404372; not polled by defaultRead
AI612ASCII 01 Last Battery ReplacementModbus 404373; not polled by defaultRead
AI613ASCII 02 Last Battery ReplacementModbus 404374; not polled by defaultRead
AI614ASCII 03 Last Battery ReplacementModbus 404375; not polled by defaultRead
AI615ASCII 04 Last Battery ReplacementModbus 404376; not polled by defaultRead
AI616Number of Power ModulesModbus 408193; not polled by defaultRead
AI617Number of Battery Monitor BoardsModbus 408194; not polled by defaultRead
AI618Number of Battery Breaker MotorsModbus 408195; not polled by defaultRead
AI619Number of Battery ModulesModbus 408196; not polled by defaultRead
AI620Number of Battery EnclosuresModbus 408198; not polled by defaultRead
AI621Number of PSUsModbus 408199; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX APC Symmetra PX 250/500 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX

How many BACnet points does the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX have?

This list has 621 BACnet objects: 241 analog inputs, 380 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Schneider_APC_Symmetra_PX_250_500_a (Schneider_APC_Symmetra_PX_250_500_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Schneider_APC_Symmetra_PX_250_500_a_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX?

Start with BI 1 Load is being powered from battery (Load on battery); BI 3 Bypass (Load on bypass); BI 5 Load not Powered (Load not powered); AI 281 Runtime remaining (Runtime remaining, s); AI 358 Total Percent load (Total load, %); AI 338 Voltage L1-2 (output) (Output voltage L1-L2); AI 337 Frequency (output) (Output frequency); BI 2 Low-Battery (Low battery); BI 12 Warning alarm present (Warning alarm present); BI 13 Critical alarm present (Critical alarm present).

How do I check these points on the real Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Schneider_APC_Symmetra_PX_250_500_a · Schneider_APC_Symmetra_PX_250_500_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.