Generator set controller · BACnet points list
Contemporary Controls Generac H-100 control panel via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Generac H-100: 171 objects (23 AI, 1 AO, 147 BI), all polled. Analog inputs give oil and coolant temperature and pressure, fuel level, battery, phase currents and voltages, kW, PF, frequency and rpm; binary inputs give switch positions, e-stop, remote start, run/ready/auto states and the alarm and warning flags. One output presets engine hours.
This page lists 171 BACnet objects for the Contemporary Controls Generac H-100 control panel via BASgatewayLX — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Generac H-100 control panel via BASgatewayLX
- Equipment
- Generator set controller
- Equipment type
- Other equipment
- BACnet objects
- 171 (1 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- H-100, H100, Generac H Panel, Generac H-Panel Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Generac H-100 control panel via BASgatewayLX
Read Gen Running, Gen in Auto, Ready for Load and the common alarm/warning, plus kW and voltage. This profile is read-only; start/stop and mode stay on the genset panel or hard-wired remote start.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 53 | GEN RUNNING | Generator running | Read |
| BI 60 | GEN IN AUTO | Generator in auto | Read |
| BI 55 | READY FOR LOAD | Ready for load | Read |
| AI 19 | TOTAL POWER KW | Total power, kW | Read |
| AI 18 | AVRG VOLTAGE | Average voltage | Read |
| AI 14 | AVRG CURRENT | Average current | Read |
| AI 21 | GEN FREQUENCY | Generator frequency | Read |
| AI 10 | BATTERY VOLTS | Battery voltage | Read |
| BI 51 | COMMON ALARM | Common alarm | Read |
| BI 52 | COMMON WARNING | Common warning | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- AO 171 (ENGINE HOURS NOW) overwrites the hour meter; don't map it as a live value.
Contemporary Controls Generac H-100 control panel via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | OIL TEMP | Modbus 300140 | °F | Read | |
| AI | 2 | COOLANT TEMP | Modbus 300142 | °F | Read | |
| AI | 3 | OIL PRESSURE | Modbus 300144 | Read | ||
| AI | 4 | COOLANT LEVEL | Modbus 300146 | Read | ||
| AI | 5 | USER CFG 05/Fuel Level | Modbus 300148 | Read | ||
| AI | 6 | USER CFG 06 | Modbus 300150 | Read | ||
| AI | 7 | THROT POS | Modbus 300152 | Read | ||
| AI | 8 | O2 SENSOR | Modbus 300154 | Read | ||
| AI | 9 | BAT CHARGE CUR | Modbus 300156 | Read | ||
| AImin | 10 | BATTERY VOLTS | Modbus 300158 | V | Read | |
| AI | 11 | CURRENT PHS A | Modbus 300160 | A | Read | |
| AI | 12 | CURRENT PHS B | Modbus 300162 | A | Read | |
| AI | 13 | CURRENT PHS C | Modbus 300164 | A | Read | |
| AImin | 14 | AVRG CURRENT | Modbus 300166 | A | Read | |
| AI | 15 | VOLT PHS A-B | Modbus 300168 | V | Read | |
| AI | 16 | VOLT PHS B-C | Modbus 300170 | V | Read | |
| AI | 17 | VOLT PHS C-A | Modbus 300172 | V | Read | |
| AImin | 18 | AVRG VOLTAGE | Modbus 300174 | V | Read | |
| AImin | 19 | TOTAL POWER KW | Modbus 300176 | kW | Read | |
| AI | 20 | TOTAL PF | Modbus 300178 | Read | ||
| AImin | 21 | GEN FREQUENCY | Modbus 300180 | Read | ||
| AI | 22 | ENGINE RPM | Modbus 300182 | rpm | Read | |
| AI | 23 | A/F DUTY CYCLE | Modbus 300184 | Read | ||
| BI | 24 | AUTO SWITCH | Modbus 400129 bit 15 | Read | ||
| BI | 25 | MANUAL SWITCH | Modbus 400129 bit 14 | Read | ||
| BI | 26 | EMERGENCY STOP | Modbus 400129 bit 13 | Read | ||
| BI | 27 | REMOTE START | Modbus 400129 bit 12 | Read | ||
| BI | 28 | BAT CHRGR FAIL | Modbus 400129 bit 11 | Read | ||
| BI | 29 | DI2/FUEL PRESSURE | Modbus 400129 bit 10 | Read | ||
| BI | 30 | DI3/LINE POWER | Modbus 400129 bit 9 | Read | ||
| BI | 31 | DI4/GEN POWER | Modbus 400129 bit 8 | Read | ||
| BI | 32 | MODEM DCD | Modbus 400129 bit 7 | Read | ||
| BI | 33 | MODEM ENABLED | Modbus 400129 bit 6 | Read | ||
| BI | 34 | GEN OVERSPEED | Modbus 400129 bit 5 | Read | ||
| BI | 35 | HUIO 1 CFG 12 | Modbus 400129 bit 4 | Read | ||
| BI | 36 | HUIO 1 CFG 13 | Modbus 400129 bit 3 | Read | ||
| BI | 37 | HUIO 1 CFG 14 | Modbus 400129 bit 2 | Read | ||
| BI | 38 | HUIO 1 CFG 15 | Modbus 400129 bit 1 | Read | ||
| BI | 39 | HUIO 2 CFG 16 | Modbus 400129 bit 0 | Read | ||
| BI | 40 | HUIO 2 CFG 17 | Modbus 400130 bit 15 | Read | ||
| BI | 41 | HUIO 2 CFG 18 | Modbus 400130 bit 14 | Read | ||
| BI | 42 | HUIO 2 CFG 19 | Modbus 400130 bit 13 | Read | ||
| BI | 43 | HUIO 3 CFG 20 | Modbus 400130 bit 12 | Read | ||
| BI | 44 | HUIO 3 CFG 21 | Modbus 400130 bit 11 | Read | ||
| BI | 45 | HUIO 3 CFG 22 | Modbus 400130 bit 10 | Read | ||
| BI | 46 | HUIO 3 CFG 23 | Modbus 400130 bit 9 | Read | ||
| BI | 47 | HUIO 4 CFG 24 | Modbus 400130 bit 8 | Read | ||
| BI | 48 | HUIO 4 CFG 25 | Modbus 400130 bit 7 | Read | ||
| BI | 49 | HUIO 4 CFG 26 | Modbus 400130 bit 6 | Read | ||
| BI | 50 | HUIO 4 CFG 27 | Modbus 400130 bit 5 | Read | ||
| BImin | 51 | COMMON ALARM | Modbus 400131 bit 15 | Read | ||
| BImin | 52 | COMMON WARNING | Modbus 400131 bit 14 | Read | ||
| BImin | 53 | GEN RUNNING | Modbus 400131 bit 13 | Read | ||
| BI | 54 | ALARMS ENABLED | Modbus 400131 bit 12 | Read | ||
| BImin | 55 | READY FOR LOAD | Modbus 400131 bit 11 | Read | ||
| BI | 56 | GEN READY TO RUN | Modbus 400131 bit 10 | Read | ||
| BI | 57 | GEN STOPPED-ALRM | Modbus 400131 bit 9 | Read | ||
| BI | 58 | GEN STOPPED | Modbus 400131 bit 8 | Read | ||
| BI | 59 | GEN IN MANUAL | Modbus 400131 bit 7 | Read | ||
| BImin | 60 | GEN IN AUTO | Modbus 400131 bit 6 | Read | ||
| BI | 61 | GEN IN OFF | Modbus 400131 bit 5 | Read | ||
| BI | 62 | OVERCRANK ALARM | Modbus 400131 bit 4 | Read | ||
| BI | 63 | OIL INHIBIT ALRM | Modbus 400131 bit 3 | Read | ||
| BI | 64 | ANNUNC SPR LIGHT | Modbus 400131 bit 2 | Read | ||
| BI | 65 | OIL TEMP HI ALRM | Modbus 400131 bit 1 | Read | ||
| BI | 66 | OIL TEMP LO ALRM | Modbus 400131 bit 0 | Read | ||
| BI | 67 | OIL TEMP HI WARN | Modbus 400132 bit 15 | Read | ||
| BI | 68 | OIL TEMP LO WARN | Modbus 400132 bit 14 | Read | ||
| BI | 69 | OIL TEMP FAULT | Modbus 400132 bit 13 | Read | ||
| BI | 70 | COOL TMP HI ALRM | Modbus 400132 bit 12 | Read | ||
| BI | 71 | COOL TMP LO ALRM | Modbus 400132 bit 11 | Read | ||
| BI | 72 | COOL TMP HI WARN | Modbus 400132 bit 10 | Read | ||
| BI | 73 | COOL TMP LO WARN | Modbus 400132 bit 9 | Read | ||
| BI | 74 | COOL TMP FAULT | Modbus 400132 bit 8 | Read | ||
| BI | 75 | OIL PRES HI ALRM | Modbus 400132 bit 7 | Read | ||
| BI | 76 | OIL PRES LO ALRM | Modbus 400132 bit 6 | Read | ||
| BI | 77 | OIL PRES HI WARN | Modbus 400132 bit 5 | Read | ||
| BI | 78 | OIL PRES LO WARN | Modbus 400132 bit 4 | Read | ||
| BI | 79 | OIL PRES FAULT | Modbus 400132 bit 3 | Read | ||
| BI | 80 | COOL LVL HI ALRM | Modbus 400132 bit 2 | Read | ||
| BI | 81 | COOL LVL LO ALRM | Modbus 400132 bit 1 | Read | ||
| BI | 82 | COOL LVL HI WARN | Modbus 400132 bit 0 | Read | ||
| BI | 83 | COOL LVL LO WARN | Modbus 400133 bit 15 | Read | ||
| BI | 84 | COOL LVL FAULT | Modbus 400133 bit 14 | Read | ||
| BI | 85 | ANALOG 5 HI ALRM | Modbus 400133 bit 13 | Read | ||
| BI | 86 | ANALOG 5 LO ALRM | Modbus 400133 bit 12 | Read | ||
| BI | 87 | ANALOG 5 HI WARN | Modbus 400133 bit 11 | Read | ||
| BI | 88 | ANALOG 5 LO WARN | Modbus 400133 bit 10 | Read | ||
| BI | 89 | ANALOG 5 FAULT | Modbus 400133 bit 9 | Read | ||
| BI | 90 | ANALOG 6 HI ALRM | Modbus 400133 bit 8 | Read | ||
| BI | 91 | ANALOG 6 LO ALRM | Modbus 400133 bit 7 | Read | ||
| BI | 92 | ANALOG 6 HI WARN | Modbus 400133 bit 6 | Read | ||
| BI | 93 | ANALOG 6 LO WARN | Modbus 400133 bit 5 | Read | ||
| BI | 94 | ANALOG 6 FAULT | Modbus 400133 bit 4 | Read | ||
| BI | 95 | GOV POS HI ALARM | Modbus 400133 bit 3 | Read | ||
| BI | 96 | GOV POS LO ALARM | Modbus 400133 bit 2 | Read | ||
| BI | 97 | GOV POS HI WARN | Modbus 400133 bit 1 | Read | ||
| BI | 98 | GOV POS LO WARN | Modbus 400133 bit 0 | Read | ||
| BI | 99 | GOV POS FAULT | Modbus 400134 bit 15 | Read | ||
| BI | 100 | OXYGEN HI ALARM | Modbus 400134 bit 14 | Read | ||
| BI | 101 | OXYGEN LO ALARM | Modbus 400134 bit 13 | Read | ||
| BI | 102 | OXYGEN HI WARN | Modbus 400134 bit 12 | Read | ||
| BI | 103 | OXYGEN LO WARN | Modbus 400134 bit 11 | Read | ||
| BI | 104 | O2 SENSOR FAULT | Modbus 400134 bit 10 | Read | ||
| BI | 105 | CHG CURR HI ALRM | Modbus 400134 bit 9 | Read | ||
| BI | 106 | CHG CURR LO ALRM | Modbus 400134 bit 8 | Read | ||
| BI | 107 | CHG CURR HI WARN | Modbus 400134 bit 7 | Read | ||
| BI | 108 | CHG CURR LO WARN | Modbus 400134 bit 6 | Read | ||
| BI | 109 | CHG CURR FAULT | Modbus 400134 bit 5 | Read | ||
| BI | 110 | BAT VOLT HI ALRM | Modbus 400134 bit 4 | Read | ||
| BI | 111 | BAT VOLT LO ALRM | Modbus 400134 bit 3 | Read | ||
| BI | 112 | BAT VOLT HI WARN | Modbus 400134 bit 2 | Read | ||
| BI | 113 | BAT VOLT LO WARN | Modbus 400134 bit 1 | Read | ||
| BI | 114 | AVG CURR HI ALRM | Modbus 400134 bit 0 | Read | ||
| BI | 115 | AVG CURR LO ALRM | Modbus 400135 bit 15 | Read | ||
| BI | 116 | AVG CURR HI WARN | Modbus 400135 bit 14 | Read | ||
| BI | 117 | AVG CURR LO WARN | Modbus 400135 bit 13 | Read | ||
| BI | 118 | AVG VOLT HI ALRM | Modbus 400135 bit 12 | Read | ||
| BI | 119 | AVG VOLT LO ALRM | Modbus 400135 bit 11 | Read | ||
| BI | 120 | AVG VOLT HI WARN | Modbus 400135 bit 10 | Read | ||
| BI | 121 | AVG VOLT LO WARN | Modbus 400135 bit 9 | Read | ||
| BI | 122 | TOT PWR HI ALARM | Modbus 400135 bit 8 | Read | ||
| BI | 123 | TOT PWR LO ALARM | Modbus 400135 bit 7 | Read | ||
| BI | 124 | TOT PWR HI WARN | Modbus 400135 bit 6 | Read | ||
| BI | 125 | TOT PWR LO WARN | Modbus 400135 bit 5 | Read | ||
| BI | 126 | GEN FREQ HI ALRM | Modbus 400135 bit 4 | Read | ||
| BI | 127 | GEN FREQ LO ALRM | Modbus 400135 bit 3 | Read | ||
| BI | 128 | GEN FREQ HI WARN | Modbus 400135 bit 2 | Read | ||
| BI | 129 | GEN FREQ LO WARN | Modbus 400135 bit 1 | Read | ||
| BI | 130 | GEN FREQ FAULT | Modbus 400135 bit 0 | Read | ||
| BI | 131 | ENG RPM HI ALARM | Modbus 400136 bit 15 | Read | ||
| BI | 132 | ENG RPM LO ALARM | Modbus 400136 bit 14 | Read | ||
| BI | 133 | ENG RPM HI WARN | Modbus 400136 bit 13 | Read | ||
| BI | 134 | ENG RPM LO WARN | Modbus 400136 bit 12 | Read | ||
| BI | 135 | ENG RPM FAULT | Modbus 400136 bit 11 | Read | ||
| BI | 136 | SWITCH IN AUTO | Modbus 400136 bit 10 | Read | ||
| BI | 137 | SWITCH IN MANUAL | Modbus 400136 bit 9 | Read | ||
| BI | 138 | E-STOP ACTIVE | Modbus 400136 bit 8 | Read | ||
| BI | 139 | REMOTE START ACT | Modbus 400136 bit 7 | Read | ||
| BI | 140 | BATT CHARGE FAIL | Modbus 400136 bit 6 | Read | ||
| BI | 141 | LOW FUEL PRS ACT | Modbus 400136 bit 5 | Read | ||
| BI | 142 | DI3/LINE PWR ACT | Modbus 400136 bit 4 | Read | ||
| BI | 143 | DI4/GEN PWR ACT | Modbus 400136 bit 3 | Read | ||
| BI | 144 | LINE POWER | Modbus 400136 bit 2 | Read | ||
| BI | 145 | GEN POWER | Modbus 400136 bit 1 | Read | ||
| BI | 146 | ILC ALR/WRN #1 | Modbus 400136 bit 0 | Read | ||
| BI | 147 | ILC ALR/WRN #2 | Modbus 400137 bit 15 | Read | ||
| BI | 148 | IN WARM UP | Modbus 400137 bit 14 | Read | ||
| BI | 149 | IN COOL DOWN | Modbus 400137 bit 13 | Read | ||
| BI | 150 | CRANKING | Modbus 400137 bit 12 | Read | ||
| BI | 151 | NEED SERVICE | Modbus 400137 bit 11 | Read | ||
| BI | 152 | SHUTDOWN GENSET | Modbus 400137 bit 10 | Read | ||
| BI | 153 | CHCK V PHS ROT | Modbus 400137 bit 9 | Read | ||
| BI | 154 | CHCK C PHS ROT | Modbus 400137 bit 8 | Read | ||
| BI | 155 | FAULT RLY ACTIVE | Modbus 400137 bit 7 | Read | ||
| BI | 156 | USR CONFIG 106 | Modbus 400137 bit 6 | Read | ||
| BI | 157 | INT EXERCISE ACT | Modbus 400137 bit 5 | Read | ||
| BI | 158 | CHECK FOR ILC | Modbus 400137 bit 4 | Read | ||
| BI | 159 | USR CONFIG 109 | Modbus 400137 bit 3 | Read | ||
| BI | 160 | USR CONFIG 110 | Modbus 400137 bit 2 | Read | ||
| BI | 161 | USR CONFIG 111 | Modbus 400137 bit 1 | Read | ||
| BI | 162 | USR CONFIG 112 | Modbus 400137 bit 0 | Read | ||
| BI | 163 | USR CONFIG 113 | Modbus 400138 bit 15 | Read | ||
| BI | 164 | USR CONFIG 114 | Modbus 400138 bit 14 | Read | ||
| BI | 165 | USR CONFIG 115 | Modbus 400138 bit 13 | Read | ||
| BI | 166 | USR CONFIG 116 | Modbus 400138 bit 12 | Read | ||
| BI | 167 | USR CONFIG 117 | Modbus 400138 bit 11 | Read | ||
| BI | 168 | USR CONFIG 118 | Modbus 400138 bit 10 | Read | ||
| BI | 169 | RPM MISSING | Modbus 400138 bit 9 | Read | ||
| BI | 170 | RESET ALARMS | Modbus 400138 bit 8 | Read | ||
| AO | 171 | ENGINE HOURS NOW | Modbus 400305 | Command |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Generac H-100 point IDs by name
AI1OIL TEMPAI2COOLANT TEMPAI3OIL PRESSUREAI4COOLANT LEVELAI5USER CFG 05/Fuel LevelAI6USER CFG 06AI7THROT POSAI8O2 SENSORAI9BAT CHARGE CURAI10BATTERY VOLTSAI11CURRENT PHS AAI12CURRENT PHS BAI13CURRENT PHS CAI14AVRG CURRENTAI15VOLT PHS A-BAI16VOLT PHS B-CAI17VOLT PHS C-AAI18AVRG VOLTAGEAI19TOTAL POWER KWAI20TOTAL PFAI21GEN FREQUENCYAI22ENGINE RPMAI23A/F DUTY CYCLEBI24AUTO SWITCHBI25MANUAL SWITCHBI26EMERGENCY STOPBI27REMOTE STARTBI28BAT CHRGR FAILBI29DI2/FUEL PRESSUREBI30DI3/LINE POWERBI31DI4/GEN POWERBI32MODEM DCDBI33MODEM ENABLEDBI34GEN OVERSPEEDBI35HUIO 1 CFG 12BI36HUIO 1 CFG 13BI37HUIO 1 CFG 14BI38HUIO 1 CFG 15BI39HUIO 2 CFG 16BI40HUIO 2 CFG 17BI41HUIO 2 CFG 18BI42HUIO 2 CFG 19BI43HUIO 3 CFG 20BI44HUIO 3 CFG 21BI45HUIO 3 CFG 22BI46HUIO 3 CFG 23BI47HUIO 4 CFG 24BI48HUIO 4 CFG 25BI49HUIO 4 CFG 26BI50HUIO 4 CFG 27BI51COMMON ALARMBI52COMMON WARNINGBI53GEN RUNNINGBI54ALARMS ENABLEDBI55READY FOR LOADBI56GEN READY TO RUNBI57GEN STOPPED-ALRMBI58GEN STOPPEDBI59GEN IN MANUALBI60GEN IN AUTOBI61GEN IN OFFBI62OVERCRANK ALARMBI63OIL INHIBIT ALRMBI64ANNUNC SPR LIGHTBI65OIL TEMP HI ALRMBI66OIL TEMP LO ALRMBI67OIL TEMP HI WARNBI68OIL TEMP LO WARNBI69OIL TEMP FAULTBI70COOL TMP HI ALRMBI71COOL TMP LO ALRMBI72COOL TMP HI WARNBI73COOL TMP LO WARNBI74COOL TMP FAULTBI75OIL PRES HI ALRMBI76OIL PRES LO ALRMBI77OIL PRES HI WARNBI78OIL PRES LO WARNBI79OIL PRES FAULTBI80COOL LVL HI ALRMBI81COOL LVL LO ALRMBI82COOL LVL HI WARNBI83COOL LVL LO WARNBI84COOL LVL FAULTBI85ANALOG 5 HI ALRMBI86ANALOG 5 LO ALRMBI87ANALOG 5 HI WARNBI88ANALOG 5 LO WARNBI89ANALOG 5 FAULTBI90ANALOG 6 HI ALRMBI91ANALOG 6 LO ALRMBI92ANALOG 6 HI WARNBI93ANALOG 6 LO WARNBI94ANALOG 6 FAULTBI95GOV POS HI ALARMBI96GOV POS LO ALARMBI97GOV POS HI WARNBI98GOV POS LO WARNBI99GOV POS FAULTBI100OXYGEN HI ALARMBI101OXYGEN LO ALARMBI102OXYGEN HI WARNBI103OXYGEN LO WARNBI104O2 SENSOR FAULTBI105CHG CURR HI ALRMBI106CHG CURR LO ALRMBI107CHG CURR HI WARNBI108CHG CURR LO WARNBI109CHG CURR FAULTBI110BAT VOLT HI ALRMBI111BAT VOLT LO ALRMBI112BAT VOLT HI WARNBI113BAT VOLT LO WARNBI114AVG CURR HI ALRMBI115AVG CURR LO ALRMBI116AVG CURR HI WARNBI117AVG CURR LO WARNBI118AVG VOLT HI ALRMBI119AVG VOLT LO ALRMBI120AVG VOLT HI WARNBI121AVG VOLT LO WARNBI122TOT PWR HI ALARMBI123TOT PWR LO ALARMBI124TOT PWR HI WARNBI125TOT PWR LO WARNBI126GEN FREQ HI ALRMBI127GEN FREQ LO ALRMBI128GEN FREQ HI WARNBI129GEN FREQ LO WARNBI130GEN FREQ FAULTBI131ENG RPM HI ALARMBI132ENG RPM LO ALARMBI133ENG RPM HI WARNBI134ENG RPM LO WARNBI135ENG RPM FAULTBI136SWITCH IN AUTOBI137SWITCH IN MANUALBI138E-STOP ACTIVEBI139REMOTE START ACTBI140BATT CHARGE FAILBI141LOW FUEL PRS ACTBI142DI3/LINE PWR ACTBI143DI4/GEN PWR ACTBI144LINE POWERBI145GEN POWERBI146ILC ALR/WRN #1BI147ILC ALR/WRN #2BI148IN WARM UPBI149IN COOL DOWNBI150CRANKINGBI151NEED SERVICEBI152SHUTDOWN GENSETBI153CHCK V PHS ROTBI154CHCK C PHS ROTBI155FAULT RLY ACTIVEBI156USR CONFIG 106BI157INT EXERCISE ACTBI158CHECK FOR ILCBI159USR CONFIG 109BI160USR CONFIG 110BI161USR CONFIG 111BI162USR CONFIG 112BI163USR CONFIG 113BI164USR CONFIG 114BI165USR CONFIG 115BI166USR CONFIG 116BI167USR CONFIG 117BI168USR CONFIG 118BI169RPM MISSINGBI170RESET ALARMSAO171ENGINE HOURS NOW
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile GENERAC_H100_CONTROL_PANEL_a_LX.csv; the profile maps the registers in the Generac H-100 Modbus register list (https://www.ccontrols.com/support/dp/Generac_H_Panel%20Modbus%20Mapping.xls).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- All 171 rows are flagged for polling in the profile, so every object is served to BACnet once the profile is loaded.
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Generac H-100 control panel via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Generac H-100 control panel via BASgatewayLX
How many BACnet points does the Contemporary Controls Generac H-100 control panel via BASgatewayLX have?
This list has 171 BACnet objects: 23 analog inputs, 1 analog output, 147 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Generac H-100 control panel via BASgatewayLX BACnet points are writable?
1 of the 171 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Generac H-100 control panel via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile GENERAC_H100_CONTROL_PANEL_a (GENERAC_H100_CONTROL_PANEL_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Generac_H100_Control_Panel_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Generac H-100 control panel via BASgatewayLX?
Start with BI 53 GEN RUNNING (Generator running); BI 60 GEN IN AUTO (Generator in auto); BI 55 READY FOR LOAD (Ready for load); AI 19 TOTAL POWER KW (Total power, kW); AI 18 AVRG VOLTAGE (Average voltage); AI 14 AVRG CURRENT (Average current); AI 21 GEN FREQUENCY (Generator frequency); AI 10 BATTERY VOLTS (Battery voltage); BI 51 COMMON ALARM (Common alarm); BI 52 COMMON WARNING (Common warning).
How do I check these points on the real Generac H-100 control panel via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile GENERAC_H100_CONTROL_PANEL_a · GENERAC_H100_CONTROL_PANEL_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.