Thermal mass flow meter · BACnet points list

Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Sage Prime SIP/SRP: 44 Analog Inputs, 18 polled by default. Polled values include current flow, temperature and totalizer, flow and temperature limits, pulse count and DAC limits plus internal RTD and reference readings; calibration coefficients are unpolled.

This page lists 44 BACnet objects for the Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Equipment
Thermal mass flow meter
Equipment type
Thermostats, sensors & meters
BACnet objects
44 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
Sage Prime, SIP, SRP, Sage Metering flow meter
Source document
BASgatewayLX Modbus device profile Sage_Prime_Flow_Meter_SIP_and_SRP · Sage_Prime_Flow_Meter_SIP_and_SRP_LX.csv
Download CSV 44 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX

Integration in brief

Map current flow, current gas temperature and totalizer first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 32current flowCurrent flowRead
AI 33current tempCurrent gas temperatureRead
AI 27current totalizerTotalizerRead

Network setup

Watch out for

Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

44 of 44 shown
Type
Analog
Show
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX BACnet Points List
DescriptionStates
AI1CAL_VALModbus 400514; not polled by defaultRead
AI2K-FACTORModbus 400516; not polled by defaultRead
AI3VREFModbus 400518Read
AI4LOAD-RESModbus 400520Read
AI5COEFF AModbus 400522; not polled by defaultRead
AI6COEFF BModbus 400524; not polled by defaultRead
AI7COEFF CModbus 400526; not polled by defaultRead
AI8COEFF DModbus 400528; not polled by defaultRead
AI9DISP AModbus 400530; not polled by defaultRead
AI10DISP BModbus 400532; not polled by defaultRead
AI11DISP CModbus 400534; not polled by defaultRead
AI12DISP DModbus 400536; not polled by defaultRead
AI13COEFF AModbus 400538; not polled by defaultRead
AI14COEFF BModbus 400540; not polled by defaultRead
AI15COEFF CModbus 400542; not polled by defaultRead
AI16COEFF DModbus 400544; not polled by defaultRead
AI17COEFF EModbus 400546; not polled by defaultRead
AI18COEFF FModbus 400548; not polled by defaultRead
AI19iir filter coeffModbus 400550; not polled by defaultRead
AI20flow_minModbus 400552Read
AI21flow_maxModbus 400554Read
AI22PULSE COUNTModbus 400556Read
AI23temp_maxModbus 400558Read
AI24dac1_minModbus 400302Read
AI25dac1_maxModbus 400304Read
AI26serial numberModbus 400306; not polled by defaultRead
AImin27current totalizerModbus 400312Read
AI28ADC0Modbus 400314; not polled by defaultRead
AI29ADC1Modbus 400316; not polled by defaultRead
AI30ADC2Modbus 400318; not polled by defaultRead
AI31ADC3Modbus 400320; not polled by defaultRead
AImin32current flowModbus 400578Read
AImin33current tempModbus 400580Read
AI34rtd_mWattsModbus 400582Read
AI35rtd_resModbus 400584Read
AI36ref_res_rModbus 400586Read
AI37ref_res_dModbus 400588Read
AI38dac_smoothModbus 400590Read
AI39leadModbus 400592Read
AI40oheatModbus 400594Read
AI41bvModbus 400596; not polled by defaultRead
AI42fvModbus 400598; not polled by defaultRead
AI43tvModbus 400600; not polled by defaultRead
AI44lvModbus 400602; not polled by defaultRead
Object ID lookup: Contemporary Controls BASgatewayLX Sage Prime SIP/SRP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Sage Metering Sage Prime SIP / SRP via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX

How many BACnet points does the Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX have?

This list has 44 BACnet objects: 44 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Sage_Prime_Flow_Meter_SIP_and_SRP (Sage_Prime_Flow_Meter_SIP_and_SRP_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Sage_Prime_Flow_Meter_SIP_and_SRP_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX?

Start with AI 32 current flow (Current flow); AI 33 current temp (Current gas temperature); AI 27 current totalizer (Totalizer).

How do I check these points on the real Sage Metering Sage Prime SIP / SRP via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile Sage_Prime_Flow_Meter_SIP_and_SRP · Sage_Prime_Flow_Meter_SIP_and_SRP_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.