Thermal mass flow meter · BACnet points list

Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the Fox FT2: 31 objects (15 AI, 16 BI), all polled. Inputs give flow, total, temperature, elapsed time and velocity (raw and in the selected units, plus scaled copies) and status bits for power-up, limits, sensor range, calibration, settings, simulation, outputs, Anybus, RTC and CRC errors.

This page lists 31 BACnet objects for the Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Fox Thermal Instruments FT2 via BASgatewayLX
Equipment
Thermal mass flow meter
Equipment type
Thermostats, sensors & meters
BACnet objects
31 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
FT2, Fox FT2, Fox Thermal FT2 flow meter
Source document
BASgatewayLX Modbus device profile Fox_Thermal_Instuments_Model_FT2 · Fox_Thermal_Instuments_Model_FT2_LX.csv
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX

Integration in brief

Map flow rate (engineering units), totalized flow and gas temperature first. The listed objects are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 26Flow in Eng UnitFlow rate (engineering units)Read
AI 27Total in Eng UnitTotalized flowRead
AI 29Temperature in selected unitGas temperatureRead
AI 31Velocity in selected unitVelocityRead
BI 15Status Sensor reading is out of rangeSensor reading out of rangeRead
BI 17Status Incorrect SettingsIncorrect settingsRead

Network setup

Watch out for

Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

31 of 31 shown
Type
AnalogBinary
Show
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX BACnet Points List
DescriptionStates
AI1Flow in Eng unitModbus 400001Read
AI2TotalModbus 400003Read
AI3TemperatureModbus 400005Read
AI4Elapsed timeModbus 400007Read
AI5VelocityModbus 400009Read
AI6Flow in Eng unit * 10Modbus 400011Read
AI7Flow in Eng unit *100Modbus 400012Read
AI8Total *100Modbus 400013Read
AI9Total2Modbus 400014Read
BI10Status Power up indicationModbus 400016 bit 0Read
BI11Status Flow rate reached high limit thresholdModbus 400016 bit 1Read
BI12Status Flow rate reached high limit thresholdModbus 400016 bit 2Read
BI13Status Temperature reached high limit thresholdModbus 400016 bit 3Read
BI14Status Temperature reached low limit thresholdModbus 400016 bit 4Read
BImin15Status Sensor reading is out of rangeModbus 400016 bit 5Read
BI16Status Velocity flow rate outside of calibration tableModbus 400016 bit 6Read
BImin17Status Incorrect SettingsModbus 400016 bit 7Read
BI18Status In simulation modeModbus 400016 bit 8Read
BI19Status Frequency output is out of rangeModbus 400016 bit 9Read
BI20Status Analog 4-20 mA for flow is out of rangeModbus 400016 bit 10Read
BI21Status Analog 4-20 mA for temperature is out of rangeModbus 400016 bit 11Read
BI22Status Anybus errorModbus 400016 bit 12Read
BI23Status RTC error (only for FT2 with RTC)Modbus 400016 bit 13Read
BI24Status CRC errorModbus 400016 bit 14Read
BI25Status Tot ErrorModbus 400016 bit 15Read
AImin26Flow in Eng UnitModbus 400020Read
AImin27Total in Eng UnitModbus 400022Read
AI28Total#2 for 2 gas curveModbus 400024Read
AImin29Temperature in selected unitModbus 400026Read
AI30Elapsed time in hoursModbus 400028Read
AImin31Velocity in selected unitModbus 400030Read
Object ID lookup: Contemporary Controls BASgatewayLX Fox Thermal FT2 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Fox Thermal Instruments FT2 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX

How many BACnet points does the Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX have?

This list has 31 BACnet objects: 15 analog inputs, 16 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile Fox_Thermal_Instuments_Model_FT2 (Fox_Thermal_Instuments_Model_FT2_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Fox_Thermal_Instuments_Model_FT2_LX.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX?

Start with AI 26 Flow in Eng Unit (Flow rate (engineering units)); AI 27 Total in Eng Unit (Totalized flow); AI 29 Temperature in selected unit (Gas temperature); AI 31 Velocity in selected unit (Velocity); BI 15 Status Sensor reading is out of range (Sensor reading out of range); BI 17 Status Incorrect Settings (Incorrect settings).

How do I check these points on the real Fox Thermal Instruments FT2 via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.