UPS (uninterruptible power supply) · BACnet points list
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Eaton Powerware 9390: 421 objects (80 AI, 341 BI), 98 polled by default. Binary inputs give the operating mode (on battery, on bypass, system normal, UPS off), breaker and module states and hundreds of alarm bits; analog inputs give battery voltage, % left and runtime, bypass, input and output voltages and load currents. There are no outputs.
This page lists 421 BACnet objects for the Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Eaton Powerware 9390 UPS via BASgatewayLX
- Equipment
- UPS (uninterruptible power supply)
- Equipment type
- Other equipment
- BACnet objects
- 421 (0 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Powerware 9390, Eaton 9390, 9390 UPS Modbus
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Read System Normal, On Battery, On Bypass, % battery left and runtime, and the key alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 4 | System Normal | System normal | Read |
| BI 1 | On Battery | On battery | Read |
| BI 3 | On Bypass | On bypass | Read |
| BI 5 | UPS Off | UPS off | Read |
| AI 376 | % BATTERY LEFT | Battery capacity left, % | Read |
| AI 377 | BATTERY TIME REMAINING | Battery time remaining, min | Read |
| AI 409 | OUTPUT VOLTS A | Output voltage A | Read |
| AI 398 | LOAD CURRENT PHASE A | Load current phase A | Read |
| BI 131 | Battery low | Battery low | Read |
| BI 130 | Shutdown imminent | Shutdown imminent | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | On Battery | Modbus 100001 | Read | ||
| BI | 2 | ESS/High Efficiency | Modbus 100004; not polled by default | Read | ||
| BImin | 3 | On Bypass | Modbus 100010 | Read | ||
| BImin | 4 | System Normal | Modbus 100011 | Read | ||
| BImin | 5 | UPS Off | Modbus 100016 | Read | ||
| BI | 6 | Static Position Switch | Modbus 100032; not polled by default | Read | ||
| BI | 7 | Critical Buss Breaker | Modbus 100033; not polled by default | Read | ||
| BI | 8 | Bypass Breaker | Modbus 100034; not polled by default | Read | ||
| BI | 9 | Backfeed Breaker | Modbus 100035; not polled by default | Read | ||
| BI | 10 | Bypass Input Power | Modbus 100036; not polled by default | Read | ||
| BI | 11 | Maintenance Isolation Breaker (MIB) | Modbus 100037; not polled by default | Read | ||
| BI | 12 | Maintenance Bypass Breaker (MBB) | Modbus 100038; not polled by default | Read | ||
| BI | 13 | Maintenance Bypass Input (MBP) | Modbus 100039; not polled by default | Read | ||
| BI | 14 | SBM Normal | Modbus 100040; not polled by default | Read | ||
| BI | 15 | SBM On Battery | Modbus 100041; not polled by default | Read | ||
| BI | 16 | SBM On Bypass | Modbus 100042; not polled by default | Read | ||
| BI | 17 | SBM Notice | Modbus 100043; not polled by default | Read | ||
| BI | 18 | SBM Alarm | Modbus 100044; not polled by default | Read | ||
| BI | 19 | SBM On Standby | Modbus 100045; not polled by default | Read | ||
| BI | 20 | UPM #1 Normal LED | Modbus 100048; not polled by default | Read | ||
| BI | 21 | UPM #1 Battery LED | Modbus 100049; not polled by default | Read | ||
| BI | 22 | UPM #1 Bypass LED | Modbus 100050; not polled by default | Read | ||
| BI | 23 | UPM #1 Notice LED | Modbus 100051; not polled by default | Read | ||
| BI | 24 | UPM #1 Alarm LED | Modbus 100052; not polled by default | Read | ||
| BI | 25 | UPM #1 Standby LED | Modbus 100053; not polled by default | Read | ||
| BI | 26 | UPM #1 Present | Modbus 100054; not polled by default | Read | ||
| BI | 27 | UPM #2 Normal LED | Modbus 100056; not polled by default | Read | ||
| BI | 28 | UPM #2 Battery LED | Modbus 100057; not polled by default | Read | ||
| BI | 29 | UPM #2 Bypass LED | Modbus 100058; not polled by default | Read | ||
| BI | 30 | UPM #2 Notice LED | Modbus 100059; not polled by default | Read | ||
| BI | 31 | UPM #2 Alarm LED | Modbus 100060; not polled by default | Read | ||
| BI | 32 | UPM #2 Standby LED | Modbus 100061; not polled by default | Read | ||
| BI | 33 | UPM #2 Present | Modbus 100062; not polled by default | Read | ||
| BI | 34 | UPM #3 Normal LED | Modbus 100064; not polled by default | Read | ||
| BI | 35 | UPM #3 Battery LED | Modbus 100065; not polled by default | Read | ||
| BI | 36 | UPM #3 Bypass LED | Modbus 100066; not polled by default | Read | ||
| BI | 37 | UPM #3 Notice LED | Modbus 100067; not polled by default | Read | ||
| BI | 38 | UPM #3 Alarm LED | Modbus 100068; not polled by default | Read | ||
| BI | 39 | UPM #3 Standby LED | Modbus 100069; not polled by default | Read | ||
| BI | 40 | UPM #3 Present | Modbus 100070; not polled by default | Read | ||
| BI | 41 | UPM #4 Normal LED | Modbus 100072; not polled by default | Read | ||
| BI | 42 | UPM #4 Battery LED | Modbus 100073; not polled by default | Read | ||
| BI | 43 | UPM #4 Bypass LED | Modbus 100074; not polled by default | Read | ||
| BI | 44 | UPM #4 Notice LED | Modbus 100075; not polled by default | Read | ||
| BI | 45 | UPM #4 Alarm LED | Modbus 100076; not polled by default | Read | ||
| BI | 46 | UPM #4 Standby LED | Modbus 100077; not polled by default | Read | ||
| BI | 47 | UPM #4 Present | Modbus 100078; not polled by default | Read | ||
| BI | 48 | UPM #5 Normal LED | Modbus 100080; not polled by default | Read | ||
| BI | 49 | UPM #5 Battery LED | Modbus 100081; not polled by default | Read | ||
| BI | 50 | UPM #5 Bypass LED | Modbus 100082; not polled by default | Read | ||
| BI | 51 | UPM #5 Notice LED | Modbus 100083; not polled by default | Read | ||
| BI | 52 | UPM #5 Alarm LED | Modbus 100084; not polled by default | Read | ||
| BI | 53 | UPM #5 Standby LED | Modbus 100085; not polled by default | Read | ||
| BI | 54 | UPM #5 Present | Modbus 100086; not polled by default | Read | ||
| BI | 55 | UPM #6 Normal LED | Modbus 100088; not polled by default | Read | ||
| BI | 56 | UPM #6 Battery LED | Modbus 100089; not polled by default | Read | ||
| BI | 57 | UPM #6 Bypass LED | Modbus 100090; not polled by default | Read | ||
| BI | 58 | UPM #6 Notice LED | Modbus 100091; not polled by default | Read | ||
| BI | 59 | UPM #6 Alarm LED | Modbus 100092; not polled by default | Read | ||
| BI | 60 | UPM #6 Standby LED | Modbus 100093; not polled by default | Read | ||
| BI | 61 | UPM #6 Present | Modbus 100094; not polled by default | Read | ||
| BI | 62 | UPM #7 Normal LED | Modbus 100096; not polled by default | Read | ||
| BI | 63 | UPM #7 Battery LED | Modbus 100097; not polled by default | Read | ||
| BI | 64 | UPM #7 Bypass LED | Modbus 100098; not polled by default | Read | ||
| BI | 65 | UPM #7 Notice LED | Modbus 100099; not polled by default | Read | ||
| BI | 66 | UPM #7 Alarm LED | Modbus 100100; not polled by default | Read | ||
| BI | 67 | UPM #7 Standby LED | Modbus 100101; not polled by default | Read | ||
| BI | 68 | UPM #7 Present | Modbus 100102; not polled by default | Read | ||
| BI | 69 | UPM #8 Normal LED | Modbus 100104; not polled by default | Read | ||
| BI | 70 | UPM #8 Battery LED | Modbus 100105; not polled by default | Read | ||
| BI | 71 | UPM #8 Bypass LED | Modbus 100106; not polled by default | Read | ||
| BI | 72 | UPM #8 Notice LED | Modbus 100107; not polled by default | Read | ||
| BI | 73 | UPM #8 Alarm LED | Modbus 100108; not polled by default | Read | ||
| BI | 74 | UPM #8 Standby LED | Modbus 100109; not polled by default | Read | ||
| BI | 75 | UPM #8 Present | Modbus 100110; not polled by default | Read | ||
| BI | 76 | Rectifier Status | Modbus 100112; not polled by default | Read | ||
| BI | 77 | Rectifier Input Status | Modbus 100113; not polled by default | Read | ||
| BI | 78 | Bypass Status | Modbus 100114; not polled by default | Read | ||
| BI | 79 | Bypass Input Status | Modbus 100115; not polled by default | Read | ||
| BI | 80 | Input Circuit Breaker Status (CB1) | Modbus 100116; not polled by default | Read | ||
| BI | 81 | Battery Disconnect Status | Modbus 100117; not polled by default | Read | ||
| BI | 82 | Inverter Disconnect Status | Modbus 100118; not polled by default | Read | ||
| BI | 83 | Inverter Status | Modbus 100119; not polled by default | Read | ||
| BI | 84 | UPM Normal | Modbus 100120; not polled by default | Read | ||
| BI | 85 | UPM On Battery | Modbus 100121; not polled by default | Read | ||
| BI | 86 | UPM Bypass (Off Line) | Modbus 100122; not polled by default | Read | ||
| BI | 87 | UPM Notice | Modbus 100123; not polled by default | Read | ||
| BI | 88 | UPM Alarm | Modbus 100124; not polled by default | Read | ||
| BI | 89 | UPM Standby | Modbus 100125; not polled by default | Read | ||
| BI | 90 | MOB Closed | Modbus 100128; not polled by default | Read | ||
| BI | 91 | System Redundant | Modbus 100129; not polled by default | Read | ||
| BI | 92 | Inverter AC over voltage | Modbus 100144 | Read | ||
| BI | 93 | Inverter AC under voltage | Modbus 100145 | Read | ||
| BI | 94 | Inverter under or over frequency | Modbus 100146 | Read | ||
| BI | 95 | Bypass AC over voltage | Modbus 100147 | Read | ||
| BI | 96 | Bypass AC under voltage | Modbus 100148 | Read | ||
| BI | 97 | Bypass under or over frequency | Modbus 100149 | Read | ||
| BI | 98 | Input AC over voltage | Modbus 100150 | Read | ||
| BI | 99 | Input AC under voltage | Modbus 100151 | Read | ||
| BI | 100 | Input under or over frequency | Modbus 100152 | Read | ||
| BI | 101 | Output AC over voltage | Modbus 100153 | Read | ||
| BI | 102 | Output AC under voltage | Modbus 100154 | Read | ||
| BI | 103 | Output under or over frequency | Modbus 100155 | Read | ||
| BI | 104 | Remote emergency power off | Modbus 100156 | Read | ||
| BI | 105 | Remote go to Bypass | Modbus 100157 | Read | ||
| BI | 106 | Building Alarm 6 | Modbus 100158 | Read | ||
| BI | 107 | Building Alarm 5 | Modbus 100159 | Read | ||
| BI | 108 | Building Alarm 4 | Modbus 100160 | Read | ||
| BI | 109 | Building Alarm 3 | Modbus 100161 | Read | ||
| BI | 110 | Building Alarm 2 | Modbus 100162; not polled by default | Read | ||
| BI | 111 | Building Alarm 1 | Modbus 100163; not polled by default | Read | ||
| BI | 112 | Static switch over temperature | Modbus 100164; not polled by default | Read | ||
| BI | 113 | Charger over temperature | Modbus 100165; not polled by default | Read | ||
| BI | 114 | Charger logic power fail | Modbus 100166 | Read | ||
| BI | 115 | Charger over voltage or current | Modbus 100167 | Read | ||
| BI | 116 | Inverter over temperature | Modbus 100168 | Read | ||
| BI | 117 | Output overload | Modbus 100169 | Read | ||
| BI | 118 | Rectifier input over current | Modbus 100170 | Read | ||
| BI | 119 | Inverter output over current | Modbus 100171 | Read | ||
| BI | 120 | DC link over voltage | Modbus 100172 | Read | ||
| BI | 121 | DC link under voltage | Modbus 100173 | Read | ||
| BI | 122 | Rectifier failed | Modbus 100174 | Read | ||
| BI | 123 | Inverter fault | Modbus 100175 | Read | ||
| BI | 124 | Battery contactor fail | Modbus 100176 | Read | ||
| BI | 125 | Bypass breaker fail | Modbus 100177 | Read | ||
| BI | 126 | Charger failure | Modbus 100178; not polled by default | Read | ||
| BI | 127 | Static switch failure | Modbus 100180 | Read | ||
| BI | 128 | Battery current limit | Modbus 100191 | Read | ||
| BI | 129 | Output current over 100% | Modbus 100194 | Read | ||
| BImin | 130 | Shutdown imminent | Modbus 100199 | Read | ||
| BImin | 131 | Battery low | Modbus 100200 | Read | ||
| BI | 132 | Utility fail | Modbus 100201 | Read | ||
| BI | 133 | Output short circuit | Modbus 100202; not polled by default | Read | ||
| BI | 134 | Utility not present | Modbus 100203; not polled by default | Read | ||
| BI | 135 | Full time charging | Modbus 100204; not polled by default | Read | ||
| BI | 136 | Input line voltage loss | Modbus 100211; not polled by default | Read | ||
| BI | 137 | Battery DC over voltage | Modbus 100212 | Read | ||
| BI | 138 | Power supply failure | Modbus 100214 | Read | ||
| BI | 139 | Rectifier current over 125% | Modbus 100219 | Read | ||
| BI | 140 | Network not responding | Modbus 100229; not polled by default | Read | ||
| BI | 141 | Output DC over voltage | Modbus 100233; not polled by default | Read | ||
| BI | 142 | Emergency shutdown command | Modbus 100241; not polled by default | Read | ||
| BI | 143 | Bypass not available | Modbus 100249 | Read | ||
| BI | 144 | Rectifier breaker open | Modbus 100250; not polled by default | Read | ||
| BI | 145 | Battery contactor open | Modbus 100251 | Read | ||
| BI | 146 | Inverter contactor open | Modbus 100252 | Read | ||
| BI | 147 | Bypass breaker open | Modbus 100253; not polled by default | Read | ||
| BI | 148 | Battery totally discharged | Modbus 100270 | Read | ||
| BI | 149 | Loss of redundancy | Modbus 100276 | Read | ||
| BI | 150 | Loss of sync bus | Modbus 100277; not polled by default | Read | ||
| BI | 151 | Rectifier breaker shunt tripped | Modbus 100278; not polled by default | Read | ||
| BI | 152 | Loss of charger sync | Modbus 100279; not polled by default | Read | ||
| BI | 153 | Output breaker open | Modbus 100281 | Read | ||
| BI | 154 | Control power on | Modbus 100282; not polled by default | Read | ||
| BI | 155 | Inverter on | Modbus 100283; not polled by default | Read | ||
| BI | 156 | Charger on | Modbus 100284; not polled by default | Read | ||
| BI | 157 | Bypass on | Modbus 100285; not polled by default | Read | ||
| BI | 158 | Bypass power loss | Modbus 100286; not polled by default | Read | ||
| BI | 159 | Check battery flag | Modbus 100293 | Read | ||
| BI | 160 | Battery charging | Modbus 100294; not polled by default | Read | ||
| BI | 161 | Battery not charged | Modbus 100295; not polled by default | Read | ||
| BI | 162 | Other UPS on | Modbus 100298; not polled by default | Read | ||
| BI | 163 | Parallel inverter | Modbus 100299; not polled by default | Read | ||
| BI | 164 | UPS in parallel | Modbus 100300; not polled by default | Read | ||
| BI | 165 | Output Breaker/Relay Failure | Modbus 100301; not polled by default | Read | ||
| BI | 166 | Control power off | Modbus 100302; not polled by default | Read | ||
| BI | 167 | Greater than 106% overload on phase A | Modbus 100303 | Read | ||
| BI | 168 | Greater than 106% overload on phase B | Modbus 100304 | Read | ||
| BI | 169 | Greater than 106% overload on phase C | Modbus 100305 | Read | ||
| BI | 170 | Greater than 125% overload on phase A | Modbus 100306 | Read | ||
| BI | 171 | Greater than 125% overload on phase B | Modbus 100307 | Read | ||
| BI | 172 | Greater than 125% overload on phase C | Modbus 100308 | Read | ||
| BI | 173 | Greater than 150% overload on phase A | Modbus 100309 | Read | ||
| BI | 174 | Greater than 150% overload on phase B | Modbus 100310 | Read | ||
| BI | 175 | Greater than 150% overload on phase C | Modbus 100311 | Read | ||
| BI | 176 | UPS On Battery | Modbus 100312 | Read | ||
| BI | 177 | UPS On Bypass | Modbus 100313 | Read | ||
| BI | 178 | Load Dumped (Load Power Off) | Modbus 100314 | Read | ||
| BI | 179 | Load On Inverter | Modbus 100315; not polled by default | Read | ||
| BI | 180 | Low Battery Shutdown | Modbus 100318 | Read | ||
| BI | 181 | In Parallel Operation | Modbus 100323; not polled by default | Read | ||
| BI | 182 | Syncing to Bypass | Modbus 100324; not polled by default | Read | ||
| BI | 183 | Bypass Failure | Modbus 100332 | Read | ||
| BI | 184 | Battery Test failed | Modbus 100335 | Read | ||
| BI | 185 | Fuse Failure | Modbus 100336; not polled by default | Read | ||
| BI | 186 | Fan Failure | Modbus 100337; not polled by default | Read | ||
| BI | 187 | Site Wiring Fault | Modbus 100338; not polled by default | Read | ||
| BI | 188 | Backfeed Contactor Failure | Modbus 100339; not polled by default | Read | ||
| BI | 189 | Batteries Disconnected | Modbus 100343 | Read | ||
| BI | 190 | UPS Cabinet Over Temperature | Modbus 100344; not polled by default | Read | ||
| BI | 191 | Transformer Over Temperature | Modbus 100345; not polled by default | Read | ||
| BI | 192 | Ambient Under Temperature | Modbus 100346; not polled by default | Read | ||
| BI | 193 | Ambient Over Temperature | Modbus 100347; not polled by default | Read | ||
| BI | 194 | Unable to Charge Batteries | Modbus 100352; not polled by default | Read | ||
| BI | 195 | Input Breaker Failed | Modbus 100361 | Read | ||
| BI | 196 | Selective Trip Of Module | Modbus 100363; not polled by default | Read | ||
| BI | 197 | Inverter Output Failure | Modbus 100364; not polled by default | Read | ||
| BI | 198 | Abnormal Output Voltage At Startup | Modbus 100365; not polled by default | Read | ||
| BI | 199 | Rectifier OverTemperature | Modbus 100366; not polled by default | Read | ||
| BI | 200 | Configuration Error | Modbus 100367; not polled by default | Read | ||
| BI | 201 | Redundancy Loss Due To Overload | Modbus 100368; not polled by default | Read | ||
| BI | 202 | On Alternate AC Source | Modbus 100369; not polled by default | Read | ||
| BI | 203 | In High Efficiency Mode | Modbus 100370; not polled by default | Read | ||
| BI | 204 | System Notice Active | Modbus 100371; not polled by default | Read | ||
| BI | 205 | System Alarm Active | Modbus 100372; not polled by default | Read | ||
| BI | 206 | Alternate Power Source Not Available | Modbus 100373; not polled by default | Read | ||
| BI | 207 | Current Balance Failure | Modbus 100374; not polled by default | Read | ||
| BI | 208 | Check Air Filter | Modbus 100375; not polled by default | Read | ||
| BI | 209 | Subsystem Notice Active | Modbus 100376; not polled by default | Read | ||
| BI | 210 | Subsystem Alarm Active | Modbus 100377; not polled by default | Read | ||
| BI | 211 | Charger On Command | Modbus 100378; not polled by default | Read | ||
| BI | 212 | Charger Off Command | Modbus 100379; not polled by default | Read | ||
| BI | 213 | UPS Normal | Modbus 100380; not polled by default | Read | ||
| BI | 214 | Inverter Phase Rotation | Modbus 100381; not polled by default | Read | ||
| BI | 215 | UPS Module Off | Modbus 100382; not polled by default | Read | ||
| BI | 216 | External Communication Failure | Modbus 100383; not polled by default | Read | ||
| BI | 217 | Invalid Board ID | Modbus 100384; not polled by default | Read | ||
| BI | 218 | Check Inverter Switchgear | Modbus 100385; not polled by default | Read | ||
| BI | 219 | Output Watts Overload | Modbus 100386; not polled by default | Read | ||
| BI | 220 | Check Precharge | Modbus 100387; not polled by default | Read | ||
| BI | 221 | Rectifier Status | Modbus 100388; not polled by default | Read | ||
| BI | 222 | Neutral Current Limit | Modbus 100389; not polled by default | Read | ||
| BI | 223 | Close Battery Switchgear | Modbus 100390; not polled by default | Read | ||
| BI | 224 | UPS On Generator | Modbus 100391; not polled by default | Read | ||
| BI | 225 | Rectifier Over-Temperature Trip | Modbus 100392; not polled by default | Read | ||
| BI | 226 | Check Rectifier Temperature Sensor | Modbus 100393; not polled by default | Read | ||
| BI | 227 | Inverter Switchgear Status | Modbus 100394; not polled by default | Read | ||
| BI | 228 | Rectifier Switchgear Status | Modbus 100395; not polled by default | Read | ||
| BI | 229 | Bypass Switchgear Status | Modbus 100396; not polled by default | Read | ||
| BI | 230 | Battery Switchgear Status | Modbus 100397; not polled by default | Read | ||
| BI | 231 | Backfeed Switchgear Status | Modbus 100398; not polled by default | Read | ||
| BI | 232 | Battery Test in Progress | Modbus 100399; not polled by default | Read | ||
| BI | 233 | System Test in Progress | Modbus 100400; not polled by default | Read | ||
| BI | 234 | Test Aborted | Modbus 100401; not polled by default | Read | ||
| BI | 235 | Rectifier L1 Current Limit | Modbus 100402; not polled by default | Read | ||
| BI | 236 | Rectifier L2 Current Limit | Modbus 100403; not polled by default | Read | ||
| BI | 237 | Rectifier L3 Current Limit | Modbus 100404; not polled by default | Read | ||
| BI | 238 | Not Enough UPMs Ready | Modbus 100405; not polled by default | Read | ||
| BI | 239 | Modem Call Aborted | Modbus 100406; not polled by default | Read | ||
| BI | 240 | Transformer OverTemperature Warning | Modbus 100407; not polled by default | Read | ||
| BI | 241 | Output Line Voltage Loss | Modbus 100408; not polled by default | Read | ||
| BI | 242 | Input L1 High THD | Modbus 100409; not polled by default | Read | ||
| BI | 243 | Input L2 High THD | Modbus 100410; not polled by default | Read | ||
| BI | 244 | Input L3 High THD | Modbus 100411; not polled by default | Read | ||
| BI | 245 | Output L1 High THD | Modbus 100412; not polled by default | Read | ||
| BI | 246 | Output L2 High THD | Modbus 100413; not polled by default | Read | ||
| BI | 247 | Output L3 High THD | Modbus 100414; not polled by default | Read | ||
| BI | 248 | Neutral Overload Warning | Modbus 100415; not polled by default | Read | ||
| BI | 249 | Neutral Overload | Modbus 100416; not polled by default | Read | ||
| BI | 250 | Ground Current Warning | Modbus 100417; not polled by default | Read | ||
| BI | 251 | Ground Current Overload | Modbus 100418; not polled by default | Read | ||
| BI | 252 | Input Voltage L1 THD Warning | Modbus 100419; not polled by default | Read | ||
| BI | 253 | Input Voltage L2 THD Warning | Modbus 100420; not polled by default | Read | ||
| BI | 254 | Input Voltage L3 THD Warning | Modbus 100421; not polled by default | Read | ||
| BI | 255 | Input Current L1 THD Warning | Modbus 100422; not polled by default | Read | ||
| BI | 256 | Input Current L2 THD Warning | Modbus 100423; not polled by default | Read | ||
| BI | 257 | Input Current L3 THD Warning | Modbus 100424; not polled by default | Read | ||
| BI | 258 | Output Voltage L1 THD Warning | Modbus 100425; not polled by default | Read | ||
| BI | 259 | Output Voltage L2 THD Warning | Modbus 100426; not polled by default | Read | ||
| BI | 260 | Output Voltage L3 THD Warning | Modbus 100427; not polled by default | Read | ||
| BI | 261 | Output Current L1 THD Warning | Modbus 100428; not polled by default | Read | ||
| BI | 262 | Output Current L2 THD Warning | Modbus 100429; not polled by default | Read | ||
| BI | 263 | Output Current L3 THD Warning | Modbus 100430; not polled by default | Read | ||
| BI | 264 | L1 Voltage Phase Loss | Modbus 100431; not polled by default | Read | ||
| BI | 265 | L2 Voltage Phase Loss | Modbus 100432; not polled by default | Read | ||
| BI | 266 | L3 Voltage Phase Loss | Modbus 100433; not polled by default | Read | ||
| BI | 267 | L1 Under Voltage | Modbus 100434; not polled by default | Read | ||
| BI | 268 | L2 Under Voltage | Modbus 100435; not polled by default | Read | ||
| BI | 269 | L3 Under Voltage | Modbus 100436; not polled by default | Read | ||
| BI | 270 | L1 Over Voltage | Modbus 100437; not polled by default | Read | ||
| BI | 271 | L2 Over Voltage | Modbus 100438; not polled by default | Read | ||
| BI | 272 | L3 Over Voltage | Modbus 100439; not polled by default | Read | ||
| BI | 273 | Under Frequency Warning | Modbus 100440; not polled by default | Read | ||
| BI | 274 | Over Frequency Warning | Modbus 100441; not polled by default | Read | ||
| BI | 275 | Branch Circuit Overload Warning | Modbus 100442; not polled by default | Read | ||
| BI | 276 | Branch Circuit Overload | Modbus 100443; not polled by default | Read | ||
| BI | 277 | Branch Circuit CT Disconnected | Modbus 100444; not polled by default | Read | ||
| BI | 278 | Main Circuit Breaker Overload Warning | Modbus 100445; not polled by default | Read | ||
| BI | 279 | Main Circuit Breaker Overload | Modbus 100446; not polled by default | Read | ||
| BI | 280 | Primary Breaker Open | Modbus 100447; not polled by default | Read | ||
| BI | 281 | Primary Breaker Tripped | Modbus 100448; not polled by default | Read | ||
| BI | 282 | Secondary Breaker Open | Modbus 100449; not polled by default | Read | ||
| BI | 283 | Secondary Breaker Tripped | Modbus 100450; not polled by default | Read | ||
| BI | 284 | Neutral Fault | Modbus 100451; not polled by default | Read | ||
| BI | 285 | Output Phase Rotation | Modbus 100452; not polled by default | Read | ||
| BI | 286 | Maintenance Isolation Switch Failure | Modbus 100453; not polled by default | Read | ||
| BI | 287 | Maintenance Bypass Breaker Failure | Modbus 100454; not polled by default | Read | ||
| BI | 288 | Manual Bypass Switch On | Modbus 100455; not polled by default | Read | ||
| BI | 289 | Panel 1 Breaker Open | Modbus 100456; not polled by default | Read | ||
| BI | 290 | Panel 2 Breaker Open | Modbus 100457; not polled by default | Read | ||
| BI | 291 | Panel 3 Breaker Open | Modbus 100458; not polled by default | Read | ||
| BI | 292 | Panel 4 Breaker Open | Modbus 100459; not polled by default | Read | ||
| BI | 293 | Panel 5 Breaker Open | Modbus 100460; not polled by default | Read | ||
| BI | 294 | Panel 6 Breaker Open | Modbus 100461; not polled by default | Read | ||
| BI | 295 | Panel 7 Breaker Open | Modbus 100462; not polled by default | Read | ||
| BI | 296 | Panel 8 Breaker Open | Modbus 100463; not polled by default | Read | ||
| BI | 297 | Multiple Inputs Tied Together | Modbus 100464; not polled by default | Read | ||
| BI | 298 | Battery Over Temperature | Modbus 100465; not polled by default | Read | ||
| BI | 299 | Inverter Overload | Modbus 100466; not polled by default | Read | ||
| BI | 300 | Inverter Short Circuit | Modbus 100467; not polled by default | Read | ||
| BI | 301 | Bypass Overload | Modbus 100468; not polled by default | Read | ||
| BI | 302 | Bypass Phase Out of Range | Modbus 100469; not polled by default | Read | ||
| BI | 303 | Bypass Voltage Out of Range | Modbus 100470; not polled by default | Read | ||
| BI | 304 | Bypass Thermal Overload | Modbus 100471; not polled by default | Read | ||
| BI | 305 | Ambient Humidity Low | Modbus 100472; not polled by default | Read | ||
| BI | 306 | Ambient Humidity High | Modbus 100473; not polled by default | Read | ||
| BI | 307 | Under Voltage Warning | Modbus 100474; not polled by default | Read | ||
| BI | 308 | Over Votage Warning | Modbus 100475; not polled by default | Read | ||
| BI | 309 | Output Breaker Overload Warning | Modbus 100476; not polled by default | Read | ||
| BI | 310 | Output Breaker Overload | Modbus 100477; not polled by default | Read | ||
| BI | 311 | L1 Low Current Warning | Modbus 100478; not polled by default | Read | ||
| BI | 312 | L2 Low Current Warning | Modbus 100479; not polled by default | Read | ||
| BI | 313 | L3 Low Current Warning | Modbus 100480; not polled by default | Read | ||
| BI | 314 | L1 Overcurrent Warning | Modbus 100481; not polled by default | Read | ||
| BI | 315 | L2 Overcurrent Warning | Modbus 100482; not polled by default | Read | ||
| BI | 316 | L3 Overcurrent Warning | Modbus 100483; not polled by default | Read | ||
| BI | 317 | Low Load Warning | Modbus 100484; not polled by default | Read | ||
| BI | 318 | Overload Warning | Modbus 100485; not polled by default | Read | ||
| BI | 319 | Outlet Overcurrent Warning | Modbus 100486; not polled by default | Read | ||
| BI | 320 | Outlet Overcurrent Alarm | Modbus 100487; not polled by default | Read | ||
| BI | 321 | Outlet Under Voltage Warning | Modbus 100488; not polled by default | Read | ||
| BI | 322 | Outlet Over Voltage Warning | Modbus 100489; not polled by default | Read | ||
| BI | 323 | Ambient OverTemperature Warning | Modbus 100490; not polled by default | Read | ||
| BI | 324 | Ambient Over Humidity Warning | Modbus 100491; not polled by default | Read | ||
| BI | 325 | Internal OverTemperature Warning | Modbus 100492; not polled by default | Read | ||
| BI | 326 | Ambient Humidity Low Warning | Modbus 100493; not polled by default | Read | ||
| BI | 327 | L1 Over Energy Warning | Modbus 100494; not polled by default | Read | ||
| BI | 328 | L2 Over Energy Warning | Modbus 100495; not polled by default | Read | ||
| BI | 329 | L3 Over Energy Warning | Modbus 100496; not polled by default | Read | ||
| BI | 330 | L1 Over Voltage Warning | Modbus 100497; not polled by default | Read | ||
| BI | 331 | L2 Over Voltage Warning | Modbus 100498; not polled by default | Read | ||
| BI | 332 | L3 Over Voltage Warning | Modbus 100499; not polled by default | Read | ||
| BI | 333 | Breaker Over Energy Warning | Modbus 100500; not polled by default | Read | ||
| BI | 334 | Outlet Over Energy Warning | Modbus 100501; not polled by default | Read | ||
| BI | 335 | Outlet Over Voltage Alarm | Modbus 100502; not polled by default | Read | ||
| BI | 336 | Over Energy Warning | Modbus 100503; not polled by default | Read | ||
| BI | 337 | Group Under Current Warning | Modbus 100504; not polled by default | Read | ||
| BI | 338 | Group Over Current Warning | Modbus 100505; not polled by default | Read | ||
| BI | 339 | Group Over Current Alarm | Modbus 100506; not polled by default | Read | ||
| BI | 340 | Internal Failure Alarm | Modbus 100507; not polled by default | Read | ||
| BI | 341 | Ground Fault Alarm | Modbus 100508; not polled by default | Read | ||
| AI | 342 | OUTPUT VOLTS AB | Modbus 300001; not polled by default | V | Read | |
| AI | 343 | OUTPUT VOLTS BC | Modbus 300002; not polled by default | V | Read | |
| AI | 344 | OUTPUT VOLTS CA | Modbus 300003; not polled by default | V | Read | |
| AI | 345 | INPUT VOLTS AB | Modbus 300004; not polled by default | V | Read | |
| AI | 346 | INPUT VOLTS BC | Modbus 300005; not polled by default | V | Read | |
| AI | 347 | INPUT VOLTS CA | Modbus 300006; not polled by default | V | Read | |
| AI | 348 | INVERTER VOLTS AB | Modbus 300007; not polled by default | V | Read | |
| AI | 349 | INVERTER VOLTS BC | Modbus 300008; not polled by default | V | Read | |
| AI | 350 | INVERTER VOLTS CA | Modbus 300009; not polled by default | V | Read | |
| AI | 351 | BYPASS VOLTS AB | Modbus 300010; not polled by default | V | Read | |
| AI | 352 | BYPASS VOLTS BC | Modbus 300011; not polled by default | V | Read | |
| AI | 353 | BYPASS VOLTS CA | Modbus 300012; not polled by default | V | Read | |
| AI | 354 | MAIN LOGIC POWER | Modbus 300013; not polled by default | V | Read | |
| AI | 355 | SECONDARY V+ POWER | Modbus 300014; not polled by default | V | Read | |
| AI | 356 | SECONDARY V- POWER | Modbus 300015; not polled by default | V | Read | |
| AI | 357 | INVERTER AVG CURRENT PHASE A | Modbus 300016; not polled by default | A | Read | |
| AI | 358 | INVERTER AVG CURRENT PHASE B | Modbus 300017; not polled by default | A | Read | |
| AI | 359 | INVERTER AVG CURRENT PHASE C | Modbus 300018; not polled by default | A | Read | |
| AI | 360 | INPUT CURRENT PHASE A | Modbus 300019 | A | Read | |
| AI | 361 | INPUT CURRENT PHASE B | Modbus 300020 | A | Read | |
| AI | 362 | INPUT CURRENT PHASE C | Modbus 300021 | A | Read | |
| AI | 363 | OUTPUT TRUE POWER | Modbus 300022 | kW | Read | |
| AI | 364 | INPUT TRUE POWER | Modbus 300023 | kW | Read | |
| AI | 365 | OUTPUT APPARENT POWER | Modbus 300024 | kVA | Read | |
| AI | 366 | INPUT APPARENT POWER | Modbus 300025 | kVA | Read | |
| AI | 367 | OUTPUT POWER FACTOR | Modbus 300026 | PF | Read | |
| AI | 368 | INPUT POWER FACTOR | Modbus 300027 | PF | Read | |
| AI | 369 | OUTPUT FREQUENCY | Modbus 300028 | Hz | Read | |
| AI | 370 | INPUT FREQUENCY | Modbus 300029 | Hz | Read | |
| AI | 371 | INVERTER FREQUENCY | Modbus 300030; not polled by default | Hz | Read | |
| AI | 372 | BYPASS FREQUENCY | Modbus 300031 | Hz | Read | |
| AI | 373 | DC LINK VOLTS | Modbus 300032; not polled by default | V | Read | |
| AI | 374 | BATTERY CURRENT | Modbus 300033 | A | Read | |
| AI | 375 | BATTERY VOLTAGE | Modbus 300034 | V | Read | |
| AImin | 376 | % BATTERY LEFT | Modbus 300035 | % | Read | |
| AImin | 377 | BATTERY TIME REMAINING | Modbus 300036 | min | Read | |
| AI | 378 | BATTERY CHARGE TIME | Modbus 300037; not polled by default | min | Read | |
| AI | 379 | PEAK INVERTER CURRENT PHASE A | Modbus 300038; not polled by default | A | Read | |
| AI | 380 | PEAK INVERTER CURRENT PHASE B | Modbus 300039; not polled by default | A | Read | |
| AI | 381 | PEAK INVERTER CURRENT PHASE C | Modbus 300040; not polled by default | A | Read | |
| AI | 382 | AVG INPUT I 3 PHASE SUM | Modbus 300041; not polled by default | A | Read | |
| AI | 383 | INPUT CURRENT BAR CHART | Modbus 300043; not polled by default | A | Read | |
| AI | 384 | DC VOLTS BAR CHART | Modbus 300045; not polled by default | V | Read | |
| AI | 385 | BATTERY I BAR CHART | Modbus 300047; not polled by default | A | Read | |
| AI | 386 | BYPASS VOLTS PHASE A | Modbus 300054 | V | Read | |
| AI | 387 | BYPASS VOLTS PHASE B | Modbus 300055 | V | Read | |
| AI | 388 | BYPASS VOLTS PHASE C | Modbus 300056 | V | Read | |
| AI | 389 | INPUT VOLTS PHASE A | Modbus 300057 | V | Read | |
| AI | 390 | INPUT VOLTS PHASE B | Modbus 300058 | V | Read | |
| AI | 391 | INPUT VOLTS PHASE C | Modbus 300059 | V | Read | |
| AI | 392 | INVERTER VOLTS PHASE A | Modbus 300060; not polled by default | V | Read | |
| AI | 393 | INVERTER VOLTS PHASE B | Modbus 300061; not polled by default | V | Read | |
| AI | 394 | INVERTER VOLTS PHASE C | Modbus 300062; not polled by default | V | Read | |
| AI | 395 | AMBIENT TEMPERATURE | Modbus 300063; not polled by default | °C | Read | |
| AI | 396 | HEATSINK TEMPERATURE | Modbus 300064; not polled by default | °C | Read | |
| AI | 397 | POWER SUPPLY TEMPERATURE | Modbus 300065; not polled by default | °C | Read | |
| AImin | 398 | LOAD CURRENT PHASE A | Modbus 300066 | A | Read | |
| AI | 399 | LOAD CURRENT PHASE B | Modbus 300067 | A | Read | |
| AI | 400 | LOAD CURRENT PHASE C | Modbus 300068 | A | Read | |
| AI | 401 | LOAD CURRENT PHASE A BAR CHART | Modbus 300069 | A | Read | |
| AI | 402 | LOAD CURRENT PHASE B BAR CHART | Modbus 300070 | A | Read | |
| AI | 403 | LOAD CURRENT PHASE C BAR CHART | Modbus 300071 | A | Read | |
| AI | 404 | OUTPUT VA BAR CHART | Modbus 300072; not polled by default | kVA | Read | |
| AI | 405 | POSITIVE DC LINK RAIL VOLTAGE | Modbus 300075; not polled by default | V | Read | |
| AI | 406 | NEGATIVE DC LINK RAIL VOLTAGE | Modbus 300076; not polled by default | V | Read | |
| AI | 407 | AUTO-BALANCE VOLTAGE | Modbus 300077; not polled by default | V | Read | |
| AI | 408 | BATTERY TEMPERATURE | Modbus 300078; not polled by default | °C | Read | |
| AImin | 409 | OUTPUT VOLTS A | Modbus 300079 | V | Read | |
| AI | 410 | OUTPUT VOLTS B | Modbus 300080 | V | Read | |
| AI | 411 | OUTPUT VOLTS C | Modbus 300081 | V | Read | |
| AI | 412 | NEUTRAL CURRENT | Modbus 300082; not polled by default | A | Read | |
| AI | 413 | OUTPUT WATTS PHASE A | Modbus 300083; not polled by default | kW | Read | |
| AI | 414 | OUTPUT WATTS PHASE B | Modbus 300084; not polled by default | kW | Read | |
| AI | 415 | OUTPUT WATTS PHASE C | Modbus 300085; not polled by default | kW | Read | |
| AI | 416 | OUTPUT WATTS PHASE A B C | Modbus 300086; not polled by default | kW | Read | |
| AI | 417 | RECTIFIER DC CURRENT | Modbus 300087; not polled by default | A | Read | |
| AI | 418 | POSITIVE BATTERY VOLTAGE | Modbus 300088; not polled by default | V | Read | |
| AI | 419 | NEGATIVE BATTERY VOLTAGE | Modbus 300089; not polled by default | V | Read | |
| AI | 420 | POSITIVE BATTERY CURRENT | Modbus 300090; not polled by default | A | Read | |
| AI | 421 | NEGATIVE BATTERY CURRENT | Modbus 300091; not polled by default | A | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Eaton 9390 UPS point IDs by name
BI1On BatteryBI2ESS/High EfficiencyBI3On BypassBI4System NormalBI5UPS OffBI6Static Position SwitchBI7Critical Buss BreakerBI8Bypass BreakerBI9Backfeed BreakerBI10Bypass Input PowerBI11Maintenance Isolation Breaker (MIB)BI12Maintenance Bypass Breaker (MBB)BI13Maintenance Bypass Input (MBP)BI14SBM NormalBI15SBM On BatteryBI16SBM On BypassBI17SBM NoticeBI18SBM AlarmBI19SBM On StandbyBI20UPM #1 Normal LEDBI21UPM #1 Battery LEDBI22UPM #1 Bypass LEDBI23UPM #1 Notice LEDBI24UPM #1 Alarm LEDBI25UPM #1 Standby LEDBI26UPM #1 PresentBI27UPM #2 Normal LEDBI28UPM #2 Battery LEDBI29UPM #2 Bypass LEDBI30UPM #2 Notice LEDBI31UPM #2 Alarm LEDBI32UPM #2 Standby LEDBI33UPM #2 PresentBI34UPM #3 Normal LEDBI35UPM #3 Battery LEDBI36UPM #3 Bypass LEDBI37UPM #3 Notice LEDBI38UPM #3 Alarm LEDBI39UPM #3 Standby LEDBI40UPM #3 PresentBI41UPM #4 Normal LEDBI42UPM #4 Battery LEDBI43UPM #4 Bypass LEDBI44UPM #4 Notice LEDBI45UPM #4 Alarm LEDBI46UPM #4 Standby LEDBI47UPM #4 PresentBI48UPM #5 Normal LEDBI49UPM #5 Battery LEDBI50UPM #5 Bypass LEDBI51UPM #5 Notice LEDBI52UPM #5 Alarm LEDBI53UPM #5 Standby LEDBI54UPM #5 PresentBI55UPM #6 Normal LEDBI56UPM #6 Battery LEDBI57UPM #6 Bypass LEDBI58UPM #6 Notice LEDBI59UPM #6 Alarm LEDBI60UPM #6 Standby LEDBI61UPM #6 PresentBI62UPM #7 Normal LEDBI63UPM #7 Battery LEDBI64UPM #7 Bypass LEDBI65UPM #7 Notice LEDBI66UPM #7 Alarm LEDBI67UPM #7 Standby LEDBI68UPM #7 PresentBI69UPM #8 Normal LEDBI70UPM #8 Battery LEDBI71UPM #8 Bypass LEDBI72UPM #8 Notice LEDBI73UPM #8 Alarm LEDBI74UPM #8 Standby LEDBI75UPM #8 PresentBI76Rectifier StatusBI77Rectifier Input StatusBI78Bypass StatusBI79Bypass Input StatusBI80Input Circuit Breaker Status (CB1)BI81Battery Disconnect StatusBI82Inverter Disconnect StatusBI83Inverter StatusBI84UPM NormalBI85UPM On BatteryBI86UPM Bypass (Off Line)BI87UPM NoticeBI88UPM AlarmBI89UPM StandbyBI90MOB ClosedBI91System RedundantBI92Inverter AC over voltageBI93Inverter AC under voltageBI94Inverter under or over frequencyBI95Bypass AC over voltageBI96Bypass AC under voltageBI97Bypass under or over frequencyBI98Input AC over voltageBI99Input AC under voltageBI100Input under or over frequencyBI101Output AC over voltageBI102Output AC under voltageBI103Output under or over frequencyBI104Remote emergency power offBI105Remote go to BypassBI106Building Alarm 6BI107Building Alarm 5BI108Building Alarm 4BI109Building Alarm 3BI110Building Alarm 2BI111Building Alarm 1BI112Static switch over temperatureBI113Charger over temperatureBI114Charger logic power failBI115Charger over voltage or currentBI116Inverter over temperatureBI117Output overloadBI118Rectifier input over currentBI119Inverter output over currentBI120DC link over voltageBI121DC link under voltageBI122Rectifier failedBI123Inverter faultBI124Battery contactor failBI125Bypass breaker failBI126Charger failureBI127Static switch failureBI128Battery current limitBI129Output current over 100%BI130Shutdown imminentBI131Battery lowBI132Utility failBI133Output short circuitBI134Utility not presentBI135Full time chargingBI136Input line voltage lossBI137Battery DC over voltageBI138Power supply failureBI139Rectifier current over 125%BI140Network not respondingBI141Output DC over voltageBI142Emergency shutdown commandBI143Bypass not availableBI144Rectifier breaker openBI145Battery contactor openBI146Inverter contactor openBI147Bypass breaker openBI148Battery totally dischargedBI149Loss of redundancyBI150Loss of sync busBI151Rectifier breaker shunt trippedBI152Loss of charger syncBI153Output breaker openBI154Control power onBI155Inverter onBI156Charger onBI157Bypass onBI158Bypass power lossBI159Check battery flagBI160Battery chargingBI161Battery not chargedBI162Other UPS onBI163Parallel inverterBI164UPS in parallelBI165Output Breaker/Relay FailureBI166Control power offBI167Greater than 106% overload on phase ABI168Greater than 106% overload on phase BBI169Greater than 106% overload on phase CBI170Greater than 125% overload on phase ABI171Greater than 125% overload on phase BBI172Greater than 125% overload on phase CBI173Greater than 150% overload on phase ABI174Greater than 150% overload on phase BBI175Greater than 150% overload on phase CBI176UPS On BatteryBI177UPS On BypassBI178Load Dumped (Load Power Off)BI179Load On InverterBI180Low Battery ShutdownBI181In Parallel OperationBI182Syncing to BypassBI183Bypass FailureBI184Battery Test failedBI185Fuse FailureBI186Fan FailureBI187Site Wiring FaultBI188Backfeed Contactor FailureBI189Batteries DisconnectedBI190UPS Cabinet Over TemperatureBI191Transformer Over TemperatureBI192Ambient Under TemperatureBI193Ambient Over TemperatureBI194Unable to Charge BatteriesBI195Input Breaker FailedBI196Selective Trip Of ModuleBI197Inverter Output FailureBI198Abnormal Output Voltage At StartupBI199Rectifier OverTemperatureBI200Configuration ErrorBI201Redundancy Loss Due To OverloadBI202On Alternate AC SourceBI203In High Efficiency ModeBI204System Notice ActiveBI205System Alarm ActiveBI206Alternate Power Source Not AvailableBI207Current Balance FailureBI208Check Air FilterBI209Subsystem Notice ActiveBI210Subsystem Alarm ActiveBI211Charger On CommandBI212Charger Off CommandBI213UPS NormalBI214Inverter Phase RotationBI215UPS Module OffBI216External Communication FailureBI217Invalid Board IDBI218Check Inverter SwitchgearBI219Output Watts OverloadBI220Check PrechargeBI221Rectifier StatusBI222Neutral Current LimitBI223Close Battery SwitchgearBI224UPS On GeneratorBI225Rectifier Over-Temperature TripBI226Check Rectifier Temperature SensorBI227Inverter Switchgear StatusBI228Rectifier Switchgear StatusBI229Bypass Switchgear StatusBI230Battery Switchgear StatusBI231Backfeed Switchgear StatusBI232Battery Test in ProgressBI233System Test in ProgressBI234Test AbortedBI235Rectifier L1 Current LimitBI236Rectifier L2 Current LimitBI237Rectifier L3 Current LimitBI238Not Enough UPMs ReadyBI239Modem Call AbortedBI240Transformer OverTemperature WarningBI241Output Line Voltage LossBI242Input L1 High THDBI243Input L2 High THDBI244Input L3 High THDBI245Output L1 High THDBI246Output L2 High THDBI247Output L3 High THDBI248Neutral Overload WarningBI249Neutral OverloadBI250Ground Current WarningBI251Ground Current OverloadBI252Input Voltage L1 THD WarningBI253Input Voltage L2 THD WarningBI254Input Voltage L3 THD WarningBI255Input Current L1 THD WarningBI256Input Current L2 THD WarningBI257Input Current L3 THD WarningBI258Output Voltage L1 THD WarningBI259Output Voltage L2 THD WarningBI260Output Voltage L3 THD WarningBI261Output Current L1 THD WarningBI262Output Current L2 THD WarningBI263Output Current L3 THD WarningBI264L1 Voltage Phase LossBI265L2 Voltage Phase LossBI266L3 Voltage Phase LossBI267L1 Under VoltageBI268L2 Under VoltageBI269L3 Under VoltageBI270L1 Over VoltageBI271L2 Over VoltageBI272L3 Over VoltageBI273Under Frequency WarningBI274Over Frequency WarningBI275Branch Circuit Overload WarningBI276Branch Circuit OverloadBI277Branch Circuit CT DisconnectedBI278Main Circuit Breaker Overload WarningBI279Main Circuit Breaker OverloadBI280Primary Breaker OpenBI281Primary Breaker TrippedBI282Secondary Breaker OpenBI283Secondary Breaker TrippedBI284Neutral FaultBI285Output Phase RotationBI286Maintenance Isolation Switch FailureBI287Maintenance Bypass Breaker FailureBI288Manual Bypass Switch OnBI289Panel 1 Breaker OpenBI290Panel 2 Breaker OpenBI291Panel 3 Breaker OpenBI292Panel 4 Breaker OpenBI293Panel 5 Breaker OpenBI294Panel 6 Breaker OpenBI295Panel 7 Breaker OpenBI296Panel 8 Breaker OpenBI297Multiple Inputs Tied TogetherBI298Battery Over TemperatureBI299Inverter OverloadBI300Inverter Short CircuitBI301Bypass OverloadBI302Bypass Phase Out of RangeBI303Bypass Voltage Out of RangeBI304Bypass Thermal OverloadBI305Ambient Humidity LowBI306Ambient Humidity HighBI307Under Voltage WarningBI308Over Votage WarningBI309Output Breaker Overload WarningBI310Output Breaker OverloadBI311L1 Low Current WarningBI312L2 Low Current WarningBI313L3 Low Current WarningBI314L1 Overcurrent WarningBI315L2 Overcurrent WarningBI316L3 Overcurrent WarningBI317Low Load WarningBI318Overload WarningBI319Outlet Overcurrent WarningBI320Outlet Overcurrent AlarmBI321Outlet Under Voltage WarningBI322Outlet Over Voltage WarningBI323Ambient OverTemperature WarningBI324Ambient Over Humidity WarningBI325Internal OverTemperature WarningBI326Ambient Humidity Low WarningBI327L1 Over Energy WarningBI328L2 Over Energy WarningBI329L3 Over Energy WarningBI330L1 Over Voltage WarningBI331L2 Over Voltage WarningBI332L3 Over Voltage WarningBI333Breaker Over Energy WarningBI334Outlet Over Energy WarningBI335Outlet Over Voltage AlarmBI336Over Energy WarningBI337Group Under Current WarningBI338Group Over Current WarningBI339Group Over Current AlarmBI340Internal Failure AlarmBI341Ground Fault AlarmAI342OUTPUT VOLTS ABAI343OUTPUT VOLTS BCAI344OUTPUT VOLTS CAAI345INPUT VOLTS ABAI346INPUT VOLTS BCAI347INPUT VOLTS CAAI348INVERTER VOLTS ABAI349INVERTER VOLTS BCAI350INVERTER VOLTS CAAI351BYPASS VOLTS ABAI352BYPASS VOLTS BCAI353BYPASS VOLTS CAAI354MAIN LOGIC POWERAI355SECONDARY V+ POWERAI356SECONDARY V- POWERAI357INVERTER AVG CURRENT PHASE AAI358INVERTER AVG CURRENT PHASE BAI359INVERTER AVG CURRENT PHASE CAI360INPUT CURRENT PHASE AAI361INPUT CURRENT PHASE BAI362INPUT CURRENT PHASE CAI363OUTPUT TRUE POWERAI364INPUT TRUE POWERAI365OUTPUT APPARENT POWERAI366INPUT APPARENT POWERAI367OUTPUT POWER FACTORAI368INPUT POWER FACTORAI369OUTPUT FREQUENCYAI370INPUT FREQUENCYAI371INVERTER FREQUENCYAI372BYPASS FREQUENCYAI373DC LINK VOLTSAI374BATTERY CURRENTAI375BATTERY VOLTAGEAI376% BATTERY LEFTAI377BATTERY TIME REMAININGAI378BATTERY CHARGE TIMEAI379PEAK INVERTER CURRENT PHASE AAI380PEAK INVERTER CURRENT PHASE BAI381PEAK INVERTER CURRENT PHASE CAI382AVG INPUT I 3 PHASE SUMAI383INPUT CURRENT BAR CHARTAI384DC VOLTS BAR CHARTAI385BATTERY I BAR CHARTAI386BYPASS VOLTS PHASE AAI387BYPASS VOLTS PHASE BAI388BYPASS VOLTS PHASE CAI389INPUT VOLTS PHASE AAI390INPUT VOLTS PHASE BAI391INPUT VOLTS PHASE CAI392INVERTER VOLTS PHASE AAI393INVERTER VOLTS PHASE BAI394INVERTER VOLTS PHASE CAI395AMBIENT TEMPERATUREAI396HEATSINK TEMPERATUREAI397POWER SUPPLY TEMPERATUREAI398LOAD CURRENT PHASE AAI399LOAD CURRENT PHASE BAI400LOAD CURRENT PHASE CAI401LOAD CURRENT PHASE A BAR CHARTAI402LOAD CURRENT PHASE B BAR CHARTAI403LOAD CURRENT PHASE C BAR CHARTAI404OUTPUT VA BAR CHARTAI405POSITIVE DC LINK RAIL VOLTAGEAI406NEGATIVE DC LINK RAIL VOLTAGEAI407AUTO-BALANCE VOLTAGEAI408BATTERY TEMPERATUREAI409OUTPUT VOLTS AAI410OUTPUT VOLTS BAI411OUTPUT VOLTS CAI412NEUTRAL CURRENTAI413OUTPUT WATTS PHASE AAI414OUTPUT WATTS PHASE BAI415OUTPUT WATTS PHASE CAI416OUTPUT WATTS PHASE A B CAI417RECTIFIER DC CURRENTAI418POSITIVE BATTERY VOLTAGEAI419NEGATIVE BATTERY VOLTAGEAI420POSITIVE BATTERY CURRENTAI421NEGATIVE BATTERY CURRENT
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Eaton_Powerware_9390_UPS_a_LX.csv; the profile maps the registers in the Powerware 9390 Modbus register list (https://www.ccontrols.com/support/dp/1391F-Modbus_Reg_Map-Rel.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 98 of the 421 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (Rectifier Status); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Eaton Powerware 9390 UPS via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
How many BACnet points does the Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX have?
This list has 421 BACnet objects: 80 analog inputs, 341 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Eaton_Powerware_9390_UPS_a (Eaton_Powerware_9390_UPS_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Eaton_Powerware_9390_UPS_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX?
Start with BI 4 System Normal (System normal); BI 1 On Battery (On battery); BI 3 On Bypass (On bypass); BI 5 UPS Off (UPS off); AI 376 % BATTERY LEFT (Battery capacity left, %); AI 377 BATTERY TIME REMAINING (Battery time remaining, min); AI 409 OUTPUT VOLTS A (Output voltage A); AI 398 LOAD CURRENT PHASE A (Load current phase A); BI 131 Battery low (Battery low); BI 130 Shutdown imminent (Shutdown imminent).
How do I check these points on the real Eaton Powerware 9390 UPS via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Eaton_Powerware_9390_UPS_a · Eaton_Powerware_9390_UPS_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.