  4. Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX

In-row precision cooling unit (chilled water) · BACnet points list

Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX BACnet points list

Updated 12 November 2026

Short answer

Gateway profile for the APC InRow RC ACRC100 series: 111 objects (85 AI, 26 AO), all polled. Outputs set cooling and supply air setpoints, fan speed preference and limits, PID terms, glycol %, thresholds and startup/idle options; inputs give overall and group status, operate mode, cool output and demand, rack inlet, supply and return temperatures, airflow, containment and filter pressure, fluid valve, flow and temperatures, run hours and the alarm flags.

This page lists 111 BACnet objects for the Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.

Manufacturer
Contemporary Controls
Model
Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Equipment
In-row precision cooling unit (chilled water)
Equipment type
Other equipment
BACnet objects
111 (26 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ACRC100, ACRC103, InRow RC, APC InRow RC Modbus
Source document
BASgatewayLX Modbus device profile HI_LO_APC_InRow_RC_ACRC100Series_a · HI_LO_APC_InRow_RC_ACRC100Series_a_LX.csv
Download CSV 111 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.

BMS integration notes: Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX

Integration in brief

Write the cooling setpoint, then read operate mode, rack inlet, supply and return temperatures and the cool-fail and other alarm flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 4COOL_SETPOINTCooling setpointCommand
AO 5SUPPLY_AIR_SETPOINTSupply air setpointCommand
AI 19OPERATE_MODEOperate modeRead
AI 1OVERALL_STATUSOverall statusRead
AI 22RACK_INLET_TEMPRack inlet temperatureRead
AI 23SUPPLY_TEMPSupply air temperatureRead
AI 24RETURN_TEMPReturn air temperatureRead
AI 26FAN_SPEEDFan speedRead
AI 20UNIT_COOL_OUTPUTUnit cooling outputRead
AI 64COOL_FAILCooling failure alarmRead

Network setup

Watch out for

Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

111 of 111 shown
Type
Access
Show
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX BACnet Points List
DescriptionStates
AImin1OVERALL_STATUSModbus 400001Read
AI2GROUP_COOL_OUTPUTModbus 400002kWRead
AI3GROUP_COOL_DEMANDModbus 400004kWRead
AOmin4COOL_SETPOINTModbus 400006°FCommand
AOmin5SUPPLY_AIR_SETPOINTModbus 400008°FCommand
AI6GROUP_AIR_FLOWModbus 400010cfmRead
AI7GROUP_MAX_RACK_TEMPModbus 400012°FRead
AI8GROUP_MIN_RACK_TEMPModbus 400014°FRead
AO9FAN_SPEED_PREFERENCEModbus 400016Command
AO10NUM_OF_UNITSModbus 400017Command
AO11CONFIGURATION_TYPEModbus 400019Command
AO12COOL_PID_PModbus 400020Command
AO13COOL_PID_IModbus 400022Command
AO14COOL_PID_DModbus 400024Command
AO15PERCENT_GLYCOLModbus 400026%Command
AO16MAX_FAN_SPEEDModbus 400028%Command
AO17FAN_SPEED_CONTROLModbus 400030Command
AO18UNIT_IDModbus 400171Command
AImin19OPERATE_MODEModbus 400207Read
AImin20UNIT_COOL_OUTPUTModbus 400208kWRead
AI21UNIT_COOL_DEMANDModbus 400210kWRead
AImin22RACK_INLET_TEMPModbus 400212°FRead
AImin23SUPPLY_TEMPModbus 400214°FRead
AImin24RETURN_TEMPModbus 400216°FRead
AI25UNIT_AIR_FLOWModbus 400218cfmRead
AImin26FAN_SPEEDModbus 400220Read
AI27ACTIVE_POWER_SOURCEModbus 400222Read
AI28FILTER_DPModbus 400223Read
AI29CONTAINMENT_DPModbus 400225Read
AI30FLUID_VALVE_POSModbus 400227%Read
AI31FLUID_FLOWModbus 400229°FRead
AI32FLUID_TEMP_INModbus 400231°FRead
AI33FLUID_TEMP_OUTModbus 400233hRead
AI34AIR_FILTER_RUNHOURModbus 400235hRead
AI35FAN_1_RUNHOURModbus 400237hRead
AI36FAN_2_RUNHOURModbus 400239hRead
AI37FAN_3_RUNHOURModbus 400241hRead
AI38FAN_4_RUNHOURModbus 400243hRead
AI39FAN_5_RUNHOURModbus 400245hRead
AI40FAN_6_RUNHOURModbus 400247hRead
AI41FAN_7_RUNHOURModbus 400249hRead
AI42FAN_8_RUNHOURModbus 400251hRead
AI43FAN_LEFT_PWRSP_RUNHOURModbus 400253hRead
AI44FAN_RIGHT_PWRSP_RUNHOURModbus 400255hRead
AI45CONDS_PUMP_RUNHOURModbus 400257hRead
AO46AIR_FILTER_SERVICE_INTERVALModbus 400259weeksCommand
AO47AIR_FILTER_SERVICE_INTERVAL_ALARMModbus 400261Command
AO48RACK_TEMP_HIGH_THRESHModbus 400262°FCommand
AO49SPLY_AIR_TEMP_HIGH_THRESHModbus 400264°FCommand
AO50RTN_AIR_TEMP_HIGH_THRESHModbus 400266°FCommand
AO51IN_FLUID_TEMP_HIGH_THRESHModbus 400268°FCommand
AO52STARTUP_DELAYModbus 400270sCommand
AO53COOL_CAPACITYModbus 400272Command
AO54IDLE_ON_LEAKModbus 400273Command
AO55INPUT_NORMALModbus 400274Command
AI56INPUT_STATEModbus 400275Read
AO57OUTPUT_NORMALModbus 400276Command
AI58OUTPUT_STATEModbus 400277Read
AO59OUTPUT_SOURCEModbus 400278Command
AO60POWER_SOURCEModbus 400279Command
AO61IDLE_ON_COOL_FAILModbus 400280Command
AI62INTERNAL_COMM_FAULTModbus 400385Read
AI63ALINK_ISOLATION_RELAY_FAULTModbus 400386Read
AImin64COOL_FAILModbus 400387Read
AI65HIGH_RACK_TEMPModbus 400388Read
AI66AIR_FILTER_CLOGGEDModbus 400389Read
AI67LWR_RTN_AIR_SENSOR_FAULTModbus 400390Read
AI68UPR_RTN_AIR_SENSOR_FAULTModbus 400391Read
AI69LWR_SPLY_AIR_SENSOR_FAULTModbus 400392Read
AI70UPR_SPLY_AIR_SENSOR_FAULTModbus 400393Read
AI71RACK_TEMP_SENSOR_FAULTModbus 400394Read
AI72FLUID_VALVE_ACT_FAULTModbus 400395Read
AI73FAN_1_FAULTModbus 400396Read
AI74FAN_2_FAULTModbus 400397Read
AI75FAN_3_FAULTModbus 400398Read
AI76FAN_4_FAULTModbus 400399Read
AI77FAN_5_FAULTModbus 400400Read
AI78FAN_6_FAULTModbus 400401Read
AI79FAN_7_FAULTModbus 400402Read
AI80FAN_8_FAULTModbus 400403Read
AI81WATER_DETECTEDModbus 400404Read
AI82CHECK_CONDS_MGMT_SYSTEMModbus 400405Read
AI83FLUID_FLOW_FAULTModbus 400406Read
AI84HIGH_FLUID_TEMP_INModbus 400407Read
AI85IN_FLUID_TEMP_SENSOR_FAULTModbus 400408Read
AI86OUT_FLUID_TEMP_SENSOR_FAULTModbus 400409Read
AI87CONDENSATE_PAN_FULLModbus 400410Read
AI88POWER_SOURCE_A_FAILModbus 400411Read
AI89POWER_SOURCE_B_FAILModbus 400412Read
AI90FAN_PWRSP_LEFT_FAULTModbus 400413Read
AI91FAN_PWRSP_RIGHT_FAULTModbus 400414Read
AI92AIR_FILTER_RUNHOUR_VIOLATIONModbus 400415Read
AI93DP_RACS_HIGH_FAULTModbus 400416Read
AI94INPUT_CONTACT_FAULTModbus 400417Read
AI95GROUP_COMM_FAULTModbus 400418Read
AI96SUPPLY_HIGH_TEMP_FAULTModbus 400419Read
AI97RETURN_HIGH_TEMP_FAULTModbus 400420Read
AI98DP_FILTER_SENSOR_FAULTModbus 400421Read
AI99DP_CONTAINMENT_SENSOR_FAULTModbus 400422Read
AI100FLUID_CALIBRATION_ACTIVEModbus 400423Read
AI101LEAK_DETECTED_SHUTDOWNModbus 400424Read
AI102FLOW_METER_COMM_FAULTModbus 400425Read
AI103APC RX CRC ERRORSModbus 465519Read
AI104APC RX PACKET COUNTERModbus 465521Read
AI105APC TX PACKET COUNTERModbus 465523Read
AI106APC SER FRAME ERRORSModbus 465525Read
AI107APC SER OVERRUN ERRORSModbus 465527Read
AI108APC SER PARITY ERRORSModbus 465529Read
AI109APC SER RX15 ERRORSModbus 465531Read
AI110APC SER RX35 ERRORSModbus 465533Read
AI111APC SER BAUD RATEModbus 465535Read
Object ID lookup: Contemporary Controls BASgatewayLX APC InRow RC ACRC100 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX

How many BACnet points does the Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX have?

This list has 111 BACnet objects: 85 analog inputs, 26 analog outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX BACnet points are writable?

26 of the 111 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX BACnet documentation?

The source is BASgatewayLX Modbus device profile HI_LO_APC_InRow_RC_ACRC100Series_a (HI_LO_APC_InRow_RC_ACRC100Series_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/APC_InRow_RC_ACRC100.zip.

What are the minimum BACnet points to integrate the Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX?

Start with AO 4 COOL_SETPOINT (Cooling setpoint); AO 5 SUPPLY_AIR_SETPOINT (Supply air setpoint); AI 19 OPERATE_MODE (Operate mode); AI 1 OVERALL_STATUS (Overall status); AI 22 RACK_INLET_TEMP (Rack inlet temperature); AI 23 SUPPLY_TEMP (Supply air temperature); AI 24 RETURN_TEMP (Return air temperature); AI 26 FAN_SPEED (Fan speed); AI 20 UNIT_COOL_OUTPUT (Unit cooling output); AI 64 COOL_FAIL (Cooling failure alarm).

How do I check these points on the real Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Contemporary Controls BACnet points lists

Source: BASgatewayLX Modbus device profile HI_LO_APC_InRow_RC_ACRC100Series_a · HI_LO_APC_InRow_RC_ACRC100Series_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.