- ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
Variable frequency drive (HVAC) · BACnet points list
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the ABB ACH550 when its embedded fieldbus uses the DCU control profile: 609 objects (546 AI, 4 AO, 59 BI), 138 polled by default. Coil and status bits (STOP, START, RUNNING, FAULT, ALARM), the 16- and 32-bit control/status words, the actual signals and the whole parameter list are mapped. Four Analog Outputs write the control words and the two references.
This page lists 609 BACnet objects for the Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
- Equipment
- Variable frequency drive (HVAC)
- Equipment type
- VFDs & pumps
- BACnet objects
- 609 (4 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
Set the drive for fieldbus control (EXT1 commands and reference = COMM) and 5305 = 1. With the DCU profile the drive takes start/stop from the ACH550 control word (AO 74, register 40031); write the speed reference to Reference 1 (AO 63). Read RUNNING, FAULT, ALARM and the actual values.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 74 | ACH550 CONTROL WORD LSW | DCU control word, low word: start/stop, reset bits | Command |
| AO 63 | Reference 1 | Speed reference REF1 | Command |
| BI 30 | RUNNING | Drive running | Read |
| AI 90 | OUTPUT FREQ | Output frequency, Hz | Read |
| AI 89 | SPEED | Motor speed, rpm | Read |
| AI 91 | CURRENT | Motor current, A | Read |
| AI 93 | POWER | Output power, kW | Read |
| BI 43 | ALARM | Any active alarm | Read |
| BI 42 | FAULT | Drive tripped on a fault | Read |
| AI 144 | FAULT WORD 1 | Fault bits, word 1 | Read |
Enable & remote start
Set EXT1 commands (parameter 1001) to 10 (COMM) and the speed reference source to COMM as the ACH550 manual describes, and parameter 5305 = 1. In this mode start/stop comes from register 40031 (AO 74), not 40001.
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- ACH550 parameter 5305 (EFB CTRL PROFILE) selects the control profile: 0 = ABB DRV LIM, 1 = DCU PROFILE, 2 = ABB DRV FULL. Load the BASgatewayLX profile that matches it.
- AO 62 (register 40001) is the ABB DRV control word; with 5305 = 1 the drive uses the ACH550 control word at 40031 (AO 74) instead.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 1 | STOP | Modbus 000001 | Read | ||
| BI | 2 | START | Modbus 000002 | Read | ||
| BI | 3 | REVERSE | Modbus 000003 | Read | ||
| BI | 4 | LOCAL | Modbus 000004 | Read | ||
| BI | 5 | RESET | Modbus 000005 | Read | ||
| BI | 6 | EXT2 | Modbus 000006 | Read | ||
| BI | 7 | RUN_DISABLE | Modbus 000007 | Read | ||
| BI | 8 | STPMODE_R | Modbus 000008 | Read | ||
| BI | 9 | STPMODE_EM | Modbus 000009 | Read | ||
| BI | 10 | STPMODE_C | Modbus 000010 | Read | ||
| BI | 11 | RAMP_2 | Modbus 000011 | Read | ||
| BI | 12 | RAMP_OUT_0 | Modbus 000012 | Read | ||
| BI | 13 | RAMP_HOLD | Modbus 000013 | Read | ||
| BI | 14 | RAMP_IN_0 | Modbus 000014 | Read | ||
| BI | 15 | REQ_LOCALLOCK | Modbus 000015 | Read | ||
| BI | 16 | TORQLIM2 | Modbus 000016 | Read | ||
| BI | 17 | FBLOCAL_CTL | Modbus 000017 | Read | ||
| BI | 18 | FBLOCAL_REF | Modbus 000018 | Read | ||
| BI | 19 | START_DISABLE1 | Modbus 000019 | Read | ||
| BI | 20 | START_DISABLE2 | Modbus 000020 | Read | ||
| BI | 21 | Relay Output 1 | Modbus 000033 | Read | ||
| BI | 22 | Relay Output 2 | Modbus 000034 | Read | ||
| BI | 23 | Relay Output 3 | Modbus 000035 | Read | ||
| BI | 24 | Relay Output 4 | Modbus 000036 | Read | ||
| BI | 25 | Relay Output 5 | Modbus 000037 | Read | ||
| BI | 26 | Relay Output 6 | Modbus 000038 | Read | ||
| BI | 27 | READY | Modbus 100001 | Read | ||
| BI | 28 | ENABLED | Modbus 100002 | Read | ||
| BI | 29 | STARTED | Modbus 100003 | Read | ||
| BImin | 30 | RUNNING | Modbus 100004 | Read | ||
| BI | 31 | ZERO_SPEED | Modbus 100005 | Read | ||
| BI | 32 | ACCELERATE | Modbus 100006 | Read | ||
| BI | 33 | DECELERATE | Modbus 100007 | Read | ||
| BI | 34 | AT_SETPOINT | Modbus 100008 | Read | ||
| BI | 35 | LIMIT | Modbus 100009 | Read | ||
| BI | 36 | SUPERVISION | Modbus 100010 | Read | ||
| BI | 37 | REV_REF | Modbus 100011 | Read | ||
| BI | 38 | REV_ACT | Modbus 100012 | Read | ||
| BI | 39 | PANEL_LOCAL | Modbus 100013 | Read | ||
| BI | 40 | FIELDBUS_LOCAL | Modbus 100014 | Read | ||
| BI | 41 | EXT2_ACT | Modbus 100015 | Read | ||
| BImin | 42 | FAULT | Modbus 100016 | Read | ||
| BImin | 43 | ALARM | Modbus 100017 | Read | ||
| BI | 44 | REQ_MAINT | Modbus 100018 | Read | ||
| BI | 45 | DIRLOCK | Modbus 100019 | Read | ||
| BI | 46 | LOCALLOCK | Modbus 100020 | Read | ||
| BI | 47 | CTL_MODE | Modbus 100021 | Read | ||
| BI | 48 | REQ_CTL | Modbus 100027 | Read | ||
| BI | 49 | REQ_REF1 | Modbus 100028 | Read | ||
| BI | 50 | REQ_REF2 | Modbus 100029 | Read | ||
| BI | 51 | REQ_REF2EXT | Modbus 100030 | Read | ||
| BI | 52 | ACK_STARTINH | Modbus 100031 | Read | ||
| BI | 53 | ACK_OFF_ILCK | Modbus 100032 | Read | ||
| BI | 54 | DI1 | Modbus 100033 | Read | ||
| BI | 55 | DI2 | Modbus 100034 | Read | ||
| BI | 56 | DI3 | Modbus 100035 | Read | ||
| BI | 57 | DI4 | Modbus 100036 | Read | ||
| BI | 58 | DI5 | Modbus 100037 | Read | ||
| BI | 59 | DI6 | Modbus 100038 | Read | ||
| AI | 60 | AI1 | Modbus 300001 | % | Read | |
| AI | 61 | AI2 | Modbus 300002 | % | Read | |
| AO | 62 | CONTROL WORD | Modbus 400001 | Command | ||
| AOmin | 63 | Reference 1 | Modbus 400002 | Command | ||
| AO | 64 | Reference 2 | Modbus 400003 | Command | ||
| AI | 65 | STATUS WORD | Modbus 400004 | Read | ||
| AI | 66 | Actual 1 | Modbus 400005 | Read | ||
| AI | 67 | Actual 2 | Modbus 400006 | Read | ||
| AI | 68 | Actual 3 | Modbus 400007 | Read | ||
| AI | 69 | Actual 4 | Modbus 400008 | Read | ||
| AI | 70 | Actual 5 | Modbus 400009 | Read | ||
| AI | 71 | Actual 6 | Modbus 400010 | Read | ||
| AI | 72 | Actual 7 | Modbus 400011 | Read | ||
| AI | 73 | Actual 8 | Modbus 400012 | Read | ||
| AOmin | 74 | ACH550 CONTROL WORD LSW | Modbus 400031 | Command | ||
| AI | 75 | ACH550 CONTROL WORD MSW | Modbus 400032 | Read | ||
| AI | 76 | ACH550 STATUS WORD LSW | Modbus 400033 | Read | ||
| AI | 77 | ACH550 STATUS WORD MSW | Modbus 400034 | Read | ||
| AI | 78 | LANGUAGE | Modbus 409901; not polled by default | Read | ||
| AI | 79 | APPLIC MACRO | Modbus 409902; not polled by default | Read | ||
| AI | 80 | MOTOR CTRL MODE | Modbus 409904; not polled by default | Read | ||
| AI | 81 | MOTOR NOM VOLT | Modbus 409905; not polled by default | V | Read | |
| AI | 82 | MOTOR NOM CURR | Modbus 409906; not polled by default | A | Read | |
| AI | 83 | MOTOR NOM FREQ | Modbus 409907; not polled by default | Hz | Read | |
| AI | 84 | MOTOR NOM SPEED | Modbus 409908; not polled by default | rpm | Read | |
| AI | 85 | MOTOR NOM POWER | Modbus 409909; not polled by default | hp | Read | |
| AI | 86 | ID RUN | Modbus 409910; not polled by default | Read | ||
| AI | 87 | MOTOR COSPHI | Modbus 409915; not polled by default | Read | ||
| AI | 88 | SPEED DIR | Modbus 400101 | rpm | Read | |
| AImin | 89 | SPEED | Modbus 400102 | rpm | Read | |
| AImin | 90 | OUTPUT FREQ | Modbus 400103 | Hz | Read | |
| AImin | 91 | CURRENT | Modbus 400104 | A | Read | |
| AI | 92 | TORQUE | Modbus 400105 | % | Read | |
| AImin | 93 | POWER | Modbus 400106 | kW | Read | |
| AI | 94 | DC BUS VOLTAGE | Modbus 400107 | V | Read | |
| AI | 95 | OUTPUT VOLTAGE | Modbus 400109 | V | Read | |
| AI | 96 | DRIVE TEMP | Modbus 400110 | °C | Read | |
| AI | 97 | EXTERNAL REF 1 | Modbus 400111 | rpm | Read | |
| AI | 98 | EXTERNAL REF 2 | Modbus 400112 | % | Read | |
| AI | 99 | CTRL LOCATION | Modbus 400113 | Read | ||
| AI | 100 | RUN TIME (R) | Modbus 400114 | Read | ||
| AI | 101 | KWH COUNTER (R) | Modbus 400115 | kWh | Read | |
| AI | 102 | APPL BLK OUTPUT | Modbus 400116 | % | Read | |
| AI | 103 | DI 1-3 STATUS | Modbus 400118 | Read | ||
| AI | 104 | DI 4-6 STATUS | Modbus 400119 | Read | ||
| AI | 105 | AI 1 | Modbus 400120 | % | Read | |
| AI | 106 | AI 2 | Modbus 400121 | % | Read | |
| AI | 107 | RO 1-3 STATUS | Modbus 400122 | Read | ||
| AI | 108 | RO 4-6 STATUS | Modbus 400123 | Read | ||
| AI | 109 | AO 1 | Modbus 400124 | mA | Read | |
| AI | 110 | AO 2 | Modbus 400125 | mA | Read | |
| AI | 111 | PID 1 OUTPUT | Modbus 400126 | % | Read | |
| AI | 112 | PID 2 OUTPUT | Modbus 400127 | % | Read | |
| AI | 113 | PID 1 SETPNT | Modbus 400128 | Read | ||
| AI | 114 | PID 2 SETPNT | Modbus 400129 | Read | ||
| AI | 115 | PID 1 FBK | Modbus 400130 | Read | ||
| AI | 116 | PID 2 FBK | Modbus 400131 | Read | ||
| AI | 117 | PID 1 DEVIATION | Modbus 400132 | Read | ||
| AI | 118 | PID 2 DEVIATION | Modbus 400133 | Read | ||
| AI | 119 | COMM RO WORD | Modbus 400134 | Read | ||
| AI | 120 | COMM VALUE 1 | Modbus 400135 | Read | ||
| AI | 121 | COMM VALUE 2 | Modbus 400136 | Read | ||
| AI | 122 | PROCESS VAR 1 | Modbus 400137 | Read | ||
| AI | 123 | PROCESS VAR 2 | Modbus 400138 | Read | ||
| AI | 124 | PROCESS VAR 3 | Modbus 400139 | Read | ||
| AI | 125 | RUN TIME | Modbus 400140 | Read | ||
| AI | 126 | MWH COUNTER | Modbus 400141 | MWh | Read | |
| AI | 127 | REVOLUTION CNTR | Modbus 400142 | Read | ||
| AI | 128 | DRIVE ON TIME HI | Modbus 400143 | days | Read | |
| AI | 129 | DRIVE ON TIME LO | Modbus 400144 | Read | ||
| AI | 130 | MOTOR TEMP | Modbus 400145 | Read | ||
| AI | 131 | CB TEMP | Modbus 400150 | °C | Read | |
| AI | 132 | MOT THERM STRESS | Modbus 400153 | % | Read | |
| AI | 133 | PID COMM VALUE 1 | Modbus 400158 | Read | ||
| AI | 134 | PID COMM VALUE 2 | Modbus 400159 | Read | ||
| AI | 135 | SAVED KWH | Modbus 400174 | kWh | Read | |
| AI | 136 | SAVED MWH | Modbus 400175 | MWh | Read | |
| AI | 137 | SAVED AMOUNT 1 | Modbus 400176 | Read | ||
| AI | 138 | SAVED AMOUNT 2 | Modbus 400177 | Read | ||
| AI | 139 | SAVED CO2 | Modbus 400178 | tons | Read | |
| AI | 140 | FB CMD WORD 1 | Modbus 400301 | Read | ||
| AI | 141 | FB CMD WORD 2 | Modbus 400302 | Read | ||
| AI | 142 | FB STS WORD 1 | Modbus 400303 | Read | ||
| AI | 143 | FB STS WORD 2 | Modbus 400304 | Read | ||
| AImin | 144 | FAULT WORD 1 | Modbus 400305 | Read | ||
| AI | 145 | FAULT WORD 2 | Modbus 400306 | Read | ||
| AI | 146 | FAULT WORD 3 | Modbus 400307 | Read | ||
| AI | 147 | ALARM WORD 1 | Modbus 400308 | Read | ||
| AI | 148 | ALARM WORD 2 | Modbus 400309 | Read | ||
| AI | 149 | LAST FAULT | Modbus 400401; not polled by default | Read | ||
| AI | 150 | FAULT TIME 1 | Modbus 400402; not polled by default | days | Read | |
| AI | 151 | FAULT TIME 2 | Modbus 400403; not polled by default | Read | ||
| AI | 152 | SPEED AT FLT | Modbus 400404; not polled by default | rpm | Read | |
| AI | 153 | FREQ AT FLT | Modbus 400405; not polled by default | Hz | Read | |
| AI | 154 | VOLTAGE AT FLT | Modbus 400406; not polled by default | V | Read | |
| AI | 155 | CURRENT AT FLT | Modbus 400407; not polled by default | A | Read | |
| AI | 156 | TORQUE AT FLT | Modbus 400408; not polled by default | % | Read | |
| AI | 157 | STATUS AT FLT | Modbus 400409; not polled by default | Read | ||
| AI | 158 | DI 1-3 AT FLT | Modbus 400410; not polled by default | Read | ||
| AI | 159 | DI 4-6 AT FLT | Modbus 400411; not polled by default | Read | ||
| AI | 160 | PREVIOUS FAULT 1 | Modbus 400412; not polled by default | Read | ||
| AI | 161 | PREVIOUS FAULT 2 | Modbus 400413; not polled by default | Read | ||
| AI | 162 | EXT1 COMMANDS | Modbus 401001; not polled by default | Read | ||
| AI | 163 | EXT2 COMMANDS | Modbus 401002; not polled by default | Read | ||
| AI | 164 | DIRECTION | Modbus 401003; not polled by default | Read | ||
| AI | 165 | KEYPAD REF SEL | Modbus 401101; not polled by default | Read | ||
| AI | 166 | EXT1/EXT2 SEL | Modbus 401102; not polled by default | Read | ||
| AI | 167 | REF1 SELECT | Modbus 401103; not polled by default | Read | ||
| AI | 168 | REF1 MIN | Modbus 401104; not polled by default | rpm | Read | |
| AI | 169 | REF1 MAX | Modbus 401105; not polled by default | rpm | Read | |
| AI | 170 | REF2 SELECT | Modbus 401106; not polled by default | Read | ||
| AI | 171 | REF2 MIN | Modbus 401107; not polled by default | % | Read | |
| AI | 172 | REF2 MAX | Modbus 401108; not polled by default | % | Read | |
| AI | 173 | CONST SPEED SEL | Modbus 401201; not polled by default | Read | ||
| AI | 174 | CONST SPEED 1 | Modbus 401202; not polled by default | rpm | Read | |
| AI | 175 | CONST SPEED 2 | Modbus 401203; not polled by default | rpm | Read | |
| AI | 176 | CONST SPEED 3 | Modbus 401204; not polled by default | rpm | Read | |
| AI | 177 | CONST SPEED 4 | Modbus 401205; not polled by default | rpm | Read | |
| AI | 178 | CONST SPEED 5 | Modbus 401206; not polled by default | rpm | Read | |
| AI | 179 | CONST SPEED 6 | Modbus 401207; not polled by default | rpm | Read | |
| AI | 180 | CONST SPEED 7 | Modbus 401208; not polled by default | rpm | Read | |
| AI | 181 | TIMED MODE SEL | Modbus 401209; not polled by default | Read | ||
| AI | 182 | MINIMUM AI1 | Modbus 401301; not polled by default | % | Read | |
| AI | 183 | MAXIMUM AI1 | Modbus 401302; not polled by default | % | Read | |
| AI | 184 | FILTER AI1 | Modbus 401303; not polled by default | s | Read | |
| AI | 185 | MINIMUM AI2 | Modbus 401304; not polled by default | % | Read | |
| AI | 186 | MAXIMUM AI2 | Modbus 401305; not polled by default | % | Read | |
| AI | 187 | FILTER AI2 | Modbus 401306; not polled by default | s | Read | |
| AI | 188 | RELAY OUTPUT 1 | Modbus 401401; not polled by default | Read | ||
| AI | 189 | RELAY OUTPUT 2 | Modbus 401402; not polled by default | Read | ||
| AI | 190 | RELAY OUTPUT 3 | Modbus 401403; not polled by default | Read | ||
| AI | 191 | RO 1 ON DELAY | Modbus 401404; not polled by default | s | Read | |
| AI | 192 | RO 1 OFF DELAY | Modbus 401405; not polled by default | s | Read | |
| AI | 193 | RO 2 ON DELAY | Modbus 401406; not polled by default | s | Read | |
| AI | 194 | RO 2 OFF DELAY | Modbus 401407; not polled by default | s | Read | |
| AI | 195 | RO 3 ON DELAY | Modbus 401408; not polled by default | s | Read | |
| AI | 196 | RO 3 OFF DELAY | Modbus 401409; not polled by default | s | Read | |
| AI | 197 | RELAY OUTPUT 4 | Modbus 401410; not polled by default | Read | ||
| AI | 198 | RELAY OUTPUT 5 | Modbus 401411; not polled by default | Read | ||
| AI | 199 | RELAY OUTPUT 6 | Modbus 401412; not polled by default | Read | ||
| AI | 200 | RO 4 ON DELAY | Modbus 401413; not polled by default | s | Read | |
| AI | 201 | RO 4 OFF DELAY | Modbus 401414; not polled by default | s | Read | |
| AI | 202 | RO 5 ON DELAY | Modbus 401415; not polled by default | s | Read | |
| AI | 203 | RO 5 OFF DELAY | Modbus 401416; not polled by default | s | Read | |
| AI | 204 | RO 6 ON DELAY | Modbus 401417; not polled by default | s | Read | |
| AI | 205 | RO 6 OFF DELAY | Modbus 401418; not polled by default | s | Read | |
| AI | 206 | AO1 CONTENT SEL | Modbus 401501; not polled by default | Hz | Read | |
| AI | 207 | AO1 CONTENT MIN | Modbus 401502; not polled by default | Hz | Read | |
| AI | 208 | AO1 CONTENT MAX | Modbus 401503; not polled by default | Hz | Read | |
| AI | 209 | MINIMUM AO1 | Modbus 401504; not polled by default | mA | Read | |
| AI | 210 | MAXIMUM AO1 | Modbus 401505; not polled by default | mA | Read | |
| AI | 211 | FILTER AO1 | Modbus 401506; not polled by default | s | Read | |
| AI | 212 | AO2 CONTENT SEL | Modbus 401507; not polled by default | A | Read | |
| AI | 213 | AO2 CONTENT MIN | Modbus 401508; not polled by default | A | Read | |
| AI | 214 | AO2 CONTENT MAX | Modbus 401509; not polled by default | A | Read | |
| AI | 215 | MINIMUM AO2 | Modbus 401510; not polled by default | mA | Read | |
| AI | 216 | MAXIMUM AO2 | Modbus 401511; not polled by default | mA | Read | |
| AI | 217 | FILTER AO2 | Modbus 401512; not polled by default | s | Read | |
| AI | 218 | RUN ENABLE | Modbus 401601; not polled by default | Read | ||
| AI | 219 | PARAMETER LOCK | Modbus 401602; not polled by default | Read | ||
| AI | 220 | PASS CODE | Modbus 401603; not polled by default | Read | ||
| AI | 221 | FAULT RESET sEL | Modbus 401604; not polled by default | Read | ||
| AI | 222 | USER PAR SET CHG | Modbus 401605; not polled by default | Read | ||
| AI | 223 | LOCAL LOCK | Modbus 401606; not polled by default | Read | ||
| AI | 224 | PARAM SAVE | Modbus 401607; not polled by default | Read | ||
| AI | 225 | START ENABLE 1 | Modbus 401608; not polled by default | Read | ||
| AI | 226 | START ENABLE 2 | Modbus 401609; not polled by default | Read | ||
| AI | 227 | DISPLAY ALARMS | Modbus 401610; not polled by default | Read | ||
| AI | 228 | PARAMETER VIEW | Modbus 401611; not polled by default | Read | ||
| AI | 229 | FAN CONTROL | Modbus 401612; not polled by default | Read | ||
| AI | 230 | FAULT RESET | Modbus 401613; not polled by default | Read | ||
| AI | 231 | OVERRIDE SEL | Modbus 401701; not polled by default | Read | ||
| AI | 232 | OVERRIDE FREQ | Modbus 401702; not polled by default | Hz | Read | |
| AI | 233 | OVERRIDE SPEED | Modbus 401703; not polled by default | rpm | Read | |
| AI | 234 | OVERR PASS CODE | Modbus 401704; not polled by default | Read | ||
| AI | 235 | OVERRIDE | Modbus 401705; not polled by default | Read | ||
| AI | 236 | OVERRIDE DIR | Modbus 401706; not polled by default | Read | ||
| AI | 237 | OVERRIDE REF | Modbus 401707; not polled by default | Read | ||
| AI | 238 | MINIMUM SPEED | Modbus 402001; not polled by default | rpm | Read | |
| AI | 239 | MAXIMUM SPEED | Modbus 402002; not polled by default | rpm | Read | |
| AI | 240 | MAX CURRENT | Modbus 402003; not polled by default | A | Read | |
| AI | 241 | UNDERVOLT CTRL | Modbus 402006; not polled by default | Read | ||
| AI | 242 | MINIMUM FREQ | Modbus 402007; not polled by default | Hz | Read | |
| AI | 243 | MAXIMUM FREQ | Modbus 402008; not polled by default | Hz | Read | |
| AI | 244 | MIN TORQUE SEL | Modbus 402013; not polled by default | Read | ||
| AI | 245 | MAX TORQUE SEL | Modbus 402014; not polled by default | Read | ||
| AI | 246 | MIN TORQUE 1 | Modbus 402015; not polled by default | % | Read | |
| AI | 247 | MIN TORQUE 2 | Modbus 402016; not polled by default | % | Read | |
| AI | 248 | MAX TORQUE 1 | Modbus 402017; not polled by default | % | Read | |
| AI | 249 | MAX TORQUE 2 | Modbus 402018; not polled by default | % | Read | |
| AI | 250 | START FUNCTION | Modbus 402101; not polled by default | Read | ||
| AI | 251 | STOP FUNCTION | Modbus 402102; not polled by default | Read | ||
| AI | 252 | DC MAGN TIME | Modbus 402103; not polled by default | s | Read | |
| AI | 253 | DC HOLD CTL | Modbus 402104; not polled by default | Read | ||
| AI | 254 | DC HOLD SPEED | Modbus 402105; not polled by default | rpm | Read | |
| AI | 255 | DC CURR REF | Modbus 402106; not polled by default | % | Read | |
| AI | 256 | DC BRAKE TIME | Modbus 402107; not polled by default | s | Read | |
| AI | 257 | START INHIBIT | Modbus 402108; not polled by default | Read | ||
| AI | 258 | EMERG STOP SEL | Modbus 402109; not polled by default | Read | ||
| AI | 259 | TORQ BOOST CURR | Modbus 402110; not polled by default | % | Read | |
| AI | 260 | START DELAY | Modbus 402113; not polled by default | s | Read | |
| AI | 261 | ACC/DEC 1/2 SEL | Modbus 402201; not polled by default | Read | ||
| AI | 262 | ACCELER TIME 1 | Modbus 402202; not polled by default | s | Read | |
| AI | 263 | DECELER TIME 1 | Modbus 402203; not polled by default | s | Read | |
| AI | 264 | RAMP SHAPE 1 | Modbus 402204; not polled by default | s | Read | |
| AI | 265 | ACCELER TIME 2 | Modbus 402205; not polled by default | s | Read | |
| AI | 266 | DECELER TIME 2 | Modbus 402206; not polled by default | s | Read | |
| AI | 267 | RAMP SHAPE 2 | Modbus 402207; not polled by default | s | Read | |
| AI | 268 | EMERG DEC TIME | Modbus 402208; not polled by default | s | Read | |
| AI | 269 | RAMP INPUT 0 | Modbus 402209; not polled by default | Read | ||
| AI | 270 | PROP GAIN | Modbus 402301; not polled by default | Read | ||
| AI | 271 | INTEGRATION TIME | Modbus 402302; not polled by default | s | Read | |
| AI | 272 | DERIVATION TIME | Modbus 402303; not polled by default | ms | Read | |
| AI | 273 | ACC COMPENSATION | Modbus 402304; not polled by default | s | Read | |
| AI | 274 | AUTOTUNE RUN | Modbus 402305; not polled by default | Read | ||
| AI | 275 | CRIT SPEED SEL | Modbus 402501; not polled by default | rpm | Read | |
| AI | 276 | CRIT SPEED 1 LO | Modbus 402502; not polled by default | rpm | Read | |
| AI | 277 | CRIT SPEED 1 HI | Modbus 402503; not polled by default | rpm | Read | |
| AI | 278 | CRIT SPEED 2 LO | Modbus 402504; not polled by default | rpm | Read | |
| AI | 279 | CRIT SPEED 2 HI | Modbus 402505; not polled by default | rpm | Read | |
| AI | 280 | CRIT SPEED 3 LO | Modbus 402506; not polled by default | rpm | Read | |
| AI | 281 | CRIT SPEED 3 HI | Modbus 402507; not polled by default | rpm | Read | |
| AI | 282 | FLUX OPT ENABLE | Modbus 402601; not polled by default | Read | ||
| AI | 283 | FLUX BRAKING | Modbus 402602; not polled by default | Read | ||
| AI | 284 | IR COMP VOLT | Modbus 402603; not polled by default | V | Read | |
| AI | 285 | IR COMP FREQ | Modbus 402604; not polled by default | % | Read | |
| AI | 286 | U/F RATIO | Modbus 402605; not polled by default | kHz | Read | |
| AI | 287 | SWITCHING FREQ | Modbus 402606; not polled by default | Read | ||
| AI | 288 | SWITCH FREQ CTRL | Modbus 402607; not polled by default | % | Read | |
| AI | 289 | SLIP COMP RATIO | Modbus 402608; not polled by default | Read | ||
| AI | 290 | NOISE SMOOTHING | Modbus 402609; not polled by default | Read | ||
| AI | 291 | DC STABILIZER | Modbus 402619; not polled by default | Read | ||
| AI | 292 | OVERMODULATION | Modbus 402625; not polled by default | Read | ||
| AI | 293 | COOLING FAN TRIG | Modbus 402901; not polled by default | Read | ||
| AI | 294 | COOLING FAN ACT | Modbus 402902; not polled by default | Read | ||
| AI | 295 | REVOLUTION TRIG | Modbus 402903; not polled by default | Read | ||
| AI | 296 | REVOLUTION ACT | Modbus 402904; not polled by default | Read | ||
| AI | 297 | RUN TIME TRIG | Modbus 402905; not polled by default | Read | ||
| AI | 298 | RUN TIME ACT | Modbus 402906; not polled by default | Read | ||
| AI | 299 | USER MWh TRIG | Modbus 402907; not polled by default | MWh | Read | |
| AI | 300 | USER MWh ACT | Modbus 402908; not polled by default | MWh | Read | |
| AI | 301 | AI<MIN FUNCTION | Modbus 403001; not polled by default | Read | ||
| AI | 302 | PANEL COMM ERR | Modbus 403002; not polled by default | Read | ||
| AI | 303 | EXTERNAL FAULT 1 | Modbus 403003; not polled by default | Read | ||
| AI | 304 | EXTERNAL FAULT 2 | Modbus 403004; not polled by default | Read | ||
| AI | 305 | MOT THERM PROT | Modbus 403005; not polled by default | Read | ||
| AI | 306 | MOT THERM TIME | Modbus 403006; not polled by default | s | Read | |
| AI | 307 | MOT LOAD CURVE | Modbus 403007; not polled by default | % | Read | |
| AI | 308 | ZERO SPEED LOAD | Modbus 403008; not polled by default | % | Read | |
| AI | 309 | BREAK POINT FREQ | Modbus 403009; not polled by default | Hz | Read | |
| AI | 310 | STALL FUNCTION | Modbus 403010; not polled by default | Read | ||
| AI | 311 | STALL FREQUENCY | Modbus 403011; not polled by default | Hz | Read | |
| AI | 312 | STALL TIME | Modbus 403012; not polled by default | s | Read | |
| AI | 313 | EARTH FAULT | Modbus 403017; not polled by default | Read | ||
| AI | 314 | COMM FAULT FUNC | Modbus 403018; not polled by default | Read | ||
| AI | 315 | COMM FAULT TIME | Modbus 403019; not polled by default | s | Read | |
| AI | 316 | AI1 FAULT LIMIT | Modbus 403021; not polled by default | % | Read | |
| AI | 317 | AI2 FAULT LIMIT | Modbus 403022; not polled by default | % | Read | |
| AI | 318 | WIRING FAULT | Modbus 403023; not polled by default | Read | ||
| AI | 319 | CB TEMP FAULT | Modbus 403024; not polled by default | Read | ||
| AI | 320 | EARTH FAULT LVL | Modbus 403028; not polled by default | Read | ||
| AI | 321 | NUMBER OF TRIALS | Modbus 403101; not polled by default | Read | ||
| AI | 322 | TRIAL TIME | Modbus 403102; not polled by default | s | Read | |
| AI | 323 | DELAY TIME | Modbus 403103; not polled by default | s | Read | |
| AI | 324 | AR OVERCURRENT | Modbus 403104; not polled by default | Read | ||
| AI | 325 | AR OVERVOLTAGE | Modbus 403105; not polled by default | Read | ||
| AI | 326 | AR UNDERVOLTAGE | Modbus 403106; not polled by default | Read | ||
| AI | 327 | AR AI<MIN | Modbus 403107; not polled by default | Read | ||
| AI | 328 | AR EXTERNAL FLT | Modbus 403108; not polled by default | Read | ||
| AI | 329 | SUPERV 1 PARAM | Modbus 403201; not polled by default | Hz | Read | |
| AI | 330 | SUPERV 1 LIM LO | Modbus 403202; not polled by default | Hz | Read | |
| AI | 331 | SUPERV 1 LIM HI | Modbus 403203; not polled by default | Hz | Read | |
| AI | 332 | SUPERV 2 PARAM | Modbus 403204; not polled by default | A | Read | |
| AI | 333 | SUPERV 2 LIM LO | Modbus 403205; not polled by default | A | Read | |
| AI | 334 | SUPERV 2 LIM HI | Modbus 403206; not polled by default | A | Read | |
| AI | 335 | SUPERV 3 PARAM | Modbus 403207; not polled by default | Read | ||
| AI | 336 | SUPERV 3 LIM LO | Modbus 403208; not polled by default | % | Read | |
| AI | 337 | SUPERV 3 LIM HI | Modbus 403209; not polled by default | % | Read | |
| AI | 338 | FIRMWARE | Modbus 403301; not polled by default | Read | ||
| AI | 339 | LOADING PACKAGE | Modbus 403302; not polled by default | Read | ||
| AI | 340 | TEST DATE | Modbus 403303; not polled by default | Read | ||
| AI | 341 | DRIVE RATING | Modbus 403304; not polled by default | Read | ||
| AI | 342 | PARAMETER TABLE | Modbus 403305; not polled by default | Read | ||
| AI | 343 | SIGNAL1 PARAM | Modbus 403401; not polled by default | Hz | Read | |
| AI | 344 | SIGNAL1 MIN | Modbus 403402; not polled by default | Hz | Read | |
| AI | 345 | SIGNAL1 MAX | Modbus 403403; not polled by default | Hz | Read | |
| AI | 346 | OUTPUT1 DSP FORM | Modbus 403404; not polled by default | Read | ||
| AI | 347 | OUTPUT1 UNIT | Modbus 403405; not polled by default | % | Read | |
| AI | 348 | OUTPUT1 MIN | Modbus 403406; not polled by default | % | Read | |
| AI | 349 | OUTPUT1 MAX | Modbus 403407; not polled by default | % | Read | |
| AI | 350 | SIGNAL2 PARAM | Modbus 403408; not polled by default | A | Read | |
| AI | 351 | SIGNAL2 MIN | Modbus 403409; not polled by default | A | Read | |
| AI | 352 | SIGNAL2 MAX | Modbus 403410; not polled by default | A | Read | |
| AI | 353 | OUTPUT2 DSP FORM | Modbus 403411; not polled by default | Read | ||
| AI | 354 | OUTPUT2 UNIT | Modbus 403412; not polled by default | A | Read | |
| AI | 355 | OUTPUT2 MIN | Modbus 403413; not polled by default | A | Read | |
| AI | 356 | OUTPUT2 MAX | Modbus 403414; not polled by default | A | Read | |
| AI | 357 | SIGNAL3 PARAM | Modbus 403415; not polled by default | Read | ||
| AI | 358 | SIGNAL3 MIN | Modbus 403416; not polled by default | % | Read | |
| AI | 359 | SIGNAL3 MAX | Modbus 403417; not polled by default | % | Read | |
| AI | 360 | OUTPUT3 DSP FORM | Modbus 403418; not polled by default | Read | ||
| AI | 361 | OUTPUT3 UNIT | Modbus 403419; not polled by default | mA | Read | |
| AI | 362 | OUTPUT3 MIN | Modbus 403420; not polled by default | mA | Read | |
| AI | 363 | OUTPUT3 MAX | Modbus 403421; not polled by default | mA | Read | |
| AI | 364 | SENSOR TYPE | Modbus 403501; not polled by default | Read | ||
| AI | 365 | INPUT SELECTION | Modbus 403502; not polled by default | Read | ||
| AI | 366 | ALARM LIMIT | Modbus 403503; not polled by default | °C | Read | |
| AI | 367 | FAULT LIMIT | Modbus 403504; not polled by default | °C | Read | |
| AI | 368 | TIMERS ENABLE | Modbus 403601; not polled by default | Read | ||
| AI | 369 | START TIME 1 | Modbus 403602; not polled by default | Read | ||
| AI | 370 | STOP TIME 1 | Modbus 403603; not polled by default | Read | ||
| AI | 371 | START DAY 1 | Modbus 403604; not polled by default | Read | ||
| AI | 372 | STOP DAY 1 | Modbus 403605; not polled by default | Read | ||
| AI | 373 | START TIME 2 | Modbus 403606; not polled by default | Read | ||
| AI | 374 | STOP TIME 2 | Modbus 403607; not polled by default | Read | ||
| AI | 375 | START DAY 2 | Modbus 403608; not polled by default | Read | ||
| AI | 376 | STOP DAY 2 | Modbus 403609; not polled by default | Read | ||
| AI | 377 | START TIME 3 | Modbus 403610; not polled by default | Read | ||
| AI | 378 | STOP TIME 3 | Modbus 403611; not polled by default | Read | ||
| AI | 379 | START DAY 3 | Modbus 403612; not polled by default | Read | ||
| AI | 380 | STOP DAY 3 | Modbus 403613; not polled by default | Read | ||
| AI | 381 | START TIME 4 | Modbus 403614; not polled by default | Read | ||
| AI | 382 | STOP TIME 4 | Modbus 403615; not polled by default | Read | ||
| AI | 383 | START DAY 4 | Modbus 403616; not polled by default | Read | ||
| AI | 384 | STOP DAY 4 | Modbus 403617; not polled by default | Read | ||
| AI | 385 | BOOSTER SEL | Modbus 403622; not polled by default | Read | ||
| AI | 386 | BOOSTER TIME | Modbus 403623; not polled by default | Read | ||
| AI | 387 | TIMED FUNC 1 SRC | Modbus 403626; not polled by default | Read | ||
| AI | 388 | TIMED FUNC 2 SRC | Modbus 403627; not polled by default | Read | ||
| AI | 389 | TIMED FUNC 3 SRC | Modbus 403628; not polled by default | Read | ||
| AI | 390 | TIMED FUNC 4 SRC | Modbus 403629; not polled by default | Read | ||
| AI | 391 | USER LOAD C MODE | Modbus 403701; not polled by default | Read | ||
| AI | 392 | USER LOAD C FUNC | Modbus 403702; not polled by default | Read | ||
| AI | 393 | USER LOAD C TIME | Modbus 403703; not polled by default | s | Read | |
| AI | 394 | LOAD FREQ 1 | Modbus 403704; not polled by default | Hz | Read | |
| AI | 395 | LOAD TORQ LOW 1 | Modbus 403705; not polled by default | % | Read | |
| AI | 396 | LOAD TORQ HIGH 1 | Modbus 403706; not polled by default | % | Read | |
| AI | 397 | LOAD FREQ 2 | Modbus 403707; not polled by default | Hz | Read | |
| AI | 398 | LOAD TORQ LOW 2 | Modbus 403708; not polled by default | % | Read | |
| AI | 399 | LOAD TORQ HIGH 2 | Modbus 403709; not polled by default | % | Read | |
| AI | 400 | LOAD FREQ 3 | Modbus 403710; not polled by default | Hz | Read | |
| AI | 401 | LOAD TORQ LOW 3 | Modbus 403711; not polled by default | % | Read | |
| AI | 402 | LOAD TORQ HIGH 3 | Modbus 403712; not polled by default | % | Read | |
| AI | 403 | LOAD FREQ 4 | Modbus 403713; not polled by default | Hz | Read | |
| AI | 404 | LOAD TORQ LOW 4 | Modbus 403714; not polled by default | % | Read | |
| AI | 405 | LOAD TORQ HIGH 4 | Modbus 403715; not polled by default | % | Read | |
| AI | 406 | LOAD FREQ 5 | Modbus 403716; not polled by default | Hz | Read | |
| AI | 407 | LOAD TORQ LOW 5 | Modbus 403717; not polled by default | % | Read | |
| AI | 408 | LOAD TORQ HIGH 5 | Modbus 403718; not polled by default | % | Read | |
| AI | 409 | GAIN | Modbus 404001; not polled by default | Read | ||
| AI | 410 | INTEGRATION TIME | Modbus 404002; not polled by default | s | Read | |
| AI | 411 | DERIVATION TIME | Modbus 404003; not polled by default | s | Read | |
| AI | 412 | PID DERIV FILTER | Modbus 404004; not polled by default | s | Read | |
| AI | 413 | ERROR VALUE INV | Modbus 404005; not polled by default | Read | ||
| AI | 414 | UNITS | Modbus 404006; not polled by default | % | Read | |
| AI | 415 | UNIT SCALE | Modbus 404007; not polled by default | Read | ||
| AI | 416 | 0% VALUE | Modbus 404008; not polled by default | % | Read | |
| AI | 417 | 100% VALUE | Modbus 404009; not polled by default | % | Read | |
| AI | 418 | SET POINT SEL | Modbus 404010; not polled by default | Read | ||
| AI | 419 | INTERNAL SETPNT | Modbus 404011; not polled by default | % | Read | |
| AI | 420 | SETPOINT MIN | Modbus 404012; not polled by default | % | Read | |
| AI | 421 | SETPOINT MAX | Modbus 404013; not polled by default | % | Read | |
| AI | 422 | FBK SEL | Modbus 404014; not polled by default | Read | ||
| AI | 423 | FBK MULTIPLIER | Modbus 404015; not polled by default | Read | ||
| AI | 424 | ACT1 INPUT | Modbus 404016; not polled by default | Read | ||
| AI | 425 | ACT2 INPUT | Modbus 404017; not polled by default | Read | ||
| AI | 426 | ACT1 MINIMUM | Modbus 404018; not polled by default | % | Read | |
| AI | 427 | ACT1 MAXIMUM | Modbus 404019; not polled by default | % | Read | |
| AI | 428 | ACT2 MINIMUM | Modbus 404020; not polled by default | % | Read | |
| AI | 429 | ACT2 MAXIMUM | Modbus 404021; not polled by default | % | Read | |
| AI | 430 | SLEEP SELECTION | Modbus 404022; not polled by default | Read | ||
| AI | 431 | PID SLEEP LEVEL | Modbus 404023; not polled by default | rpm | Read | |
| AI | 432 | PID SLEEP DELAY | Modbus 404024; not polled by default | s | Read | |
| AI | 433 | WAKE-UP DEV | Modbus 404025; not polled by default | % | Read | |
| AI | 434 | WAKE-UP DELAY | Modbus 404026; not polled by default | s | Read | |
| AI | 435 | PID 1 PARAM SET | Modbus 404027; not polled by default | Read | ||
| AI | 436 | GAIN | Modbus 404101; not polled by default | Read | ||
| AI | 437 | INTEGRATION TIME | Modbus 404102; not polled by default | s | Read | |
| AI | 438 | DERIVATION TIME | Modbus 404103; not polled by default | s | Read | |
| AI | 439 | PID DERIV FILTER | Modbus 404104; not polled by default | s | Read | |
| AI | 440 | ERROR VALUE INV | Modbus 404105; not polled by default | s | Read | |
| AI | 441 | UNITS | Modbus 404106; not polled by default | % | Read | |
| AI | 442 | UNIT SCALE | Modbus 404107; not polled by default | Read | ||
| AI | 443 | 0% VALUE | Modbus 404108; not polled by default | % | Read | |
| AI | 444 | 100% VALUE | Modbus 404109; not polled by default | % | Read | |
| AI | 445 | SET POINT SEL | Modbus 404110; not polled by default | Read | ||
| AI | 446 | INTERNAL SETPNT | Modbus 404111; not polled by default | % | Read | |
| AI | 447 | SETPOINT MIN | Modbus 404112; not polled by default | % | Read | |
| AI | 448 | SETPOINT MAX | Modbus 404113; not polled by default | % | Read | |
| AI | 449 | FBK SEL | Modbus 404114; not polled by default | Read | ||
| AI | 450 | FBK MULTIPLIER | Modbus 404115; not polled by default | Read | ||
| AI | 451 | ACT1 INPUT | Modbus 404116; not polled by default | Read | ||
| AI | 452 | ACT2 INPUT | Modbus 404117; not polled by default | Read | ||
| AI | 453 | ACT1 MINIMUM | Modbus 404118; not polled by default | % | Read | |
| AI | 454 | ACT1 MAXIMUM | Modbus 404119; not polled by default | % | Read | |
| AI | 455 | ACT2 MINIMUM | Modbus 404120; not polled by default | % | Read | |
| AI | 456 | ACT2 MAXIMUM | Modbus 404121; not polled by default | % | Read | |
| AI | 457 | SLEEP SELECTION | Modbus 404122; not polled by default | Read | ||
| AI | 458 | PID SLEEP LEVEL | Modbus 404123; not polled by default | rpm | Read | |
| AI | 459 | PID SLEEP DELAY | Modbus 404124; not polled by default | s | Read | |
| AI | 460 | WAKE-UP DEV | Modbus 404125; not polled by default | % | Read | |
| AI | 461 | WAKE-UP DELAY | Modbus 404126; not polled by default | s | Read | |
| AI | 462 | GAIN | Modbus 404201; not polled by default | Read | ||
| AI | 463 | INTEGRATION TIME | Modbus 404202; not polled by default | s | Read | |
| AI | 464 | DERIVATION TIME | Modbus 404203; not polled by default | s | Read | |
| AI | 465 | PID DERIV FILTER | Modbus 404204; not polled by default | s | Read | |
| AI | 466 | ERROR VALUE INV | Modbus 404205; not polled by default | Read | ||
| AI | 467 | UNITS | Modbus 404206; not polled by default | % | Read | |
| AI | 468 | UNIT SCALE | Modbus 404207; not polled by default | Read | ||
| AI | 469 | 0% VALUE | Modbus 404208; not polled by default | % | Read | |
| AI | 470 | 100% VALUE | Modbus 404209; not polled by default | % | Read | |
| AI | 471 | SET POINT SEL | Modbus 404210; not polled by default | Read | ||
| AI | 472 | INTERNAL SETPNT | Modbus 404211; not polled by default | % | Read | |
| AI | 473 | SETPOINT MIN | Modbus 404212; not polled by default | % | Read | |
| AI | 474 | SETPOINT MAX | Modbus 404213; not polled by default | % | Read | |
| AI | 475 | FBK SEL | Modbus 404214; not polled by default | Read | ||
| AI | 476 | FBK MULTIPLIER | Modbus 404215; not polled by default | Read | ||
| AI | 477 | ACT1 INPUT | Modbus 404216; not polled by default | Read | ||
| AI | 478 | ACT2 INPUT | Modbus 404217; not polled by default | Read | ||
| AI | 479 | ACT1 MINIMUM | Modbus 404218; not polled by default | % | Read | |
| AI | 480 | ACT1 MAXIMUM | Modbus 404219; not polled by default | % | Read | |
| AI | 481 | ACT2 MINIMUM | Modbus 404220; not polled by default | % | Read | |
| AI | 482 | ACT2 MAXIMUM | Modbus 404221; not polled by default | % | Read | |
| AI | 483 | ACTIVATE | Modbus 404228; not polled by default | Read | ||
| AI | 484 | OFFSET | Modbus 404229; not polled by default | % | Read | |
| AI | 485 | TRIM MODE | Modbus 404230; not polled by default | Read | ||
| AI | 486 | TRIM SCALE | Modbus 404231; not polled by default | % | Read | |
| AI | 487 | CORRECTION SRC | Modbus 404232; not polled by default | Read | ||
| AI | 488 | ENERGY PRICE | Modbus 404502; not polled by default | Read | ||
| AI | 489 | CO2 CONV FACTOR | Modbus 404507; not polled by default | MWh | Read | |
| AI | 490 | PUMP POWER | Modbus 404508; not polled by default | % | Read | |
| AI | 491 | ENERGY RESET | Modbus 404509; not polled by default | Read | ||
| AI | 492 | FBA TYPE | Modbus 405101; not polled by default | Read | ||
| AI | 493 | FB PAR 02 | Modbus 405102; not polled by default | Read | ||
| AI | 494 | FB PAR 03 | Modbus 405103; not polled by default | Read | ||
| AI | 495 | FB PAR 04 | Modbus 405104; not polled by default | Read | ||
| AI | 496 | FB PAR 05 | Modbus 405105; not polled by default | Read | ||
| AI | 497 | FB PAR 06 | Modbus 405106; not polled by default | Read | ||
| AI | 498 | FB PAR 07 | Modbus 405107; not polled by default | Read | ||
| AI | 499 | FB PAR 08 | Modbus 405108; not polled by default | Read | ||
| AI | 500 | FB PAR 09 | Modbus 405109; not polled by default | Read | ||
| AI | 501 | FB PAR 10 | Modbus 405110; not polled by default | Read | ||
| AI | 502 | FB PAR 11 | Modbus 405111; not polled by default | Read | ||
| AI | 503 | FB PAR 12 | Modbus 405112; not polled by default | Read | ||
| AI | 504 | FB PAR 13 | Modbus 405113; not polled by default | Read | ||
| AI | 505 | FB PAR 14 | Modbus 405114; not polled by default | Read | ||
| AI | 506 | FB PAR 15 | Modbus 405115; not polled by default | Read | ||
| AI | 507 | FB PAR 16 | Modbus 405116; not polled by default | Read | ||
| AI | 508 | FB PAR 17 | Modbus 405117; not polled by default | Read | ||
| AI | 509 | FB PAR 18 | Modbus 405118; not polled by default | Read | ||
| AI | 510 | FB PAR 19 | Modbus 405119; not polled by default | Read | ||
| AI | 511 | FB PAR 20 | Modbus 405120; not polled by default | Read | ||
| AI | 512 | FB PAR 21 | Modbus 405121; not polled by default | Read | ||
| AI | 513 | FB PAR 22 | Modbus 405122; not polled by default | Read | ||
| AI | 514 | FB PAR 23 | Modbus 405123; not polled by default | Read | ||
| AI | 515 | FB PAR 24 | Modbus 405124; not polled by default | Read | ||
| AI | 516 | FB PAR 25 | Modbus 405125; not polled by default | Read | ||
| AI | 517 | FB PAR 26 | Modbus 405126; not polled by default | Read | ||
| AI | 518 | FBA PAR REFRESH | Modbus 405127; not polled by default | Read | ||
| AI | 519 | FILE CPI FW REV | Modbus 405128; not polled by default | Read | ||
| AI | 520 | FILE CONFIG ID | Modbus 405129; not polled by default | Read | ||
| AI | 521 | FILE CONFIG REV | Modbus 405130; not polled by default | Read | ||
| AI | 522 | FBA STATUS | Modbus 405131; not polled by default | Read | ||
| AI | 523 | FBA CPI FW REV | Modbus 405132; not polled by default | Read | ||
| AI | 524 | FBA APPL FW REV | Modbus 405133; not polled by default | Read | ||
| AI | 525 | STATION ID | Modbus 405201; not polled by default | Read | ||
| AI | 526 | BAUD RATE | Modbus 405202; not polled by default | Read | ||
| AI | 527 | PARITY | Modbus 405203; not polled by default | Read | ||
| AI | 528 | OK MESSAGES | Modbus 405204; not polled by default | Read | ||
| AI | 529 | PARITY ERRORS | Modbus 405205; not polled by default | Read | ||
| AI | 530 | FRAME ERRORS | Modbus 405206; not polled by default | Read | ||
| AI | 531 | BUFFER OVERRUNS | Modbus 405207; not polled by default | Read | ||
| AI | 532 | CRC ERRORS | Modbus 405208; not polled by default | Read | ||
| AI | 533 | EFB PROTOCOL ID | Modbus 405301; not polled by default | Read | ||
| AI | 534 | EFB STATION ID | Modbus 405302; not polled by default | Read | ||
| AI | 535 | EFB BAUD RATE | Modbus 405303; not polled by default | Read | ||
| AI | 536 | EFB PARITY | Modbus 405304; not polled by default | Read | ||
| AI | 537 | EFB CTRL PROFILE | Modbus 405305; not polled by default | Read | ||
| AI | 538 | EFB OK MESSAGES | Modbus 405306; not polled by default | Read | ||
| AI | 539 | EFB CRC ERRORS | Modbus 405307; not polled by default | Read | ||
| AI | 540 | EFB UART ERRORS | Modbus 405308; not polled by default | Read | ||
| AI | 541 | EFB STATUS | Modbus 405309; not polled by default | Read | ||
| AI | 542 | EFB PAR 10 | Modbus 405310; not polled by default | Read | ||
| AI | 543 | EFB PAR 11 | Modbus 405311; not polled by default | Read | ||
| AI | 544 | EFB PAR 12 | Modbus 405312; not polled by default | Read | ||
| AI | 545 | EFB PAR 13 | Modbus 405313; not polled by default | Read | ||
| AI | 546 | EFB PAR 14 | Modbus 405314; not polled by default | Read | ||
| AI | 547 | EFB PAR 15 | Modbus 405315; not polled by default | Read | ||
| AI | 548 | EFB PAR 16 | Modbus 405316; not polled by default | Read | ||
| AI | 549 | EFB PAR 17 | Modbus 405317; not polled by default | Read | ||
| AI | 550 | EFB PAR 18 | Modbus 405318; not polled by default | Read | ||
| AI | 551 | EFB PAR 19 | Modbus 405319; not polled by default | Read | ||
| AI | 552 | EFB PAR 20 | Modbus 405320; not polled by default | Read | ||
| AI | 553 | PVL SIGNAL | Modbus 406401; not polled by default | Hz | Read | |
| AI | 554 | PVL FILTER TIME | Modbus 406402; not polled by default | s | Read | |
| AI | 555 | LOGGERS RESET | Modbus 406403; not polled by default | Read | ||
| AI | 556 | AL2 SIGNAL | Modbus 406404; not polled by default | Hz | Read | |
| AI | 557 | AL2 SIGNAL BASE | Modbus 406405; not polled by default | Hz | Read | |
| AI | 558 | PEAK VALUE | Modbus 406406; not polled by default | Read | ||
| AI | 559 | PEAK TIME 1 | Modbus 406407; not polled by default | Read | ||
| AI | 560 | PEAK TIME 2 | Modbus 406408; not polled by default | Read | ||
| AI | 561 | CURRENT AT PEAK | Modbus 406409; not polled by default | A | Read | |
| AI | 562 | UDC AT PEAK | Modbus 406410; not polled by default | V | Read | |
| AI | 563 | FREQ AT PEAK | Modbus 406411; not polled by default | Hz | Read | |
| AI | 564 | TIME OF RESET 1 | Modbus 406412; not polled by default | Read | ||
| AI | 565 | TIME OF RESET 2 | Modbus 406413; not polled by default | Read | ||
| AI | 566 | AL1RANGE0TO10 | Modbus 406414; not polled by default | % | Read | |
| AI | 567 | AL1RANGE10TO20 | Modbus 406415; not polled by default | % | Read | |
| AI | 568 | AL1RANGE20TO30 | Modbus 406416; not polled by default | % | Read | |
| AI | 569 | AL1RANGE30TO40 | Modbus 406417; not polled by default | % | Read | |
| AI | 570 | AL1RANGE40TO50 | Modbus 406418; not polled by default | % | Read | |
| AI | 571 | AL1RANGE50TO60 | Modbus 406419; not polled by default | % | Read | |
| AI | 572 | AL1RANGE60TO70 | Modbus 406420; not polled by default | % | Read | |
| AI | 573 | AL1RANGE70TO80 | Modbus 406421; not polled by default | % | Read | |
| AI | 574 | AL1RANGE80TO90 | Modbus 406422; not polled by default | % | Read | |
| AI | 575 | AL1RANGE90TO | Modbus 406423; not polled by default | % | Read | |
| AI | 576 | AL2RANGE0TO10 | Modbus 406424; not polled by default | % | Read | |
| AI | 577 | AL2RANGE10TO20 | Modbus 406425; not polled by default | % | Read | |
| AI | 578 | AL2RANGE20TO30 | Modbus 406426; not polled by default | % | Read | |
| AI | 579 | AL2RANGE30TO40 | Modbus 406427; not polled by default | % | Read | |
| AI | 580 | AL2RANGE40TO50 | Modbus 406428; not polled by default | % | Read | |
| AI | 581 | AL2RANGE50TO60 | Modbus 406429; not polled by default | % | Read | |
| AI | 582 | AL2RANGE60TO70 | Modbus 406430; not polled by default | % | Read | |
| AI | 583 | AL2RANGE70TO80 | Modbus 406431; not polled by default | % | Read | |
| AI | 584 | AL2RANGE80TO90 | Modbus 406432; not polled by default | % | Read | |
| AI | 585 | AL2RANGE90TO | Modbus 406433; not polled by default | % | Read | |
| AI | 586 | REFERENCE STEP 1 | Modbus 408103; not polled by default | % | Read | |
| AI | 587 | REFERENCE STEP 2 | Modbus 408104; not polled by default | % | Read | |
| AI | 588 | REFERENCE STEP 3 | Modbus 408105; not polled by default | % | Read | |
| AI | 589 | START FREQ 1 | Modbus 408109; not polled by default | Hz | Read | |
| AI | 590 | START FREQ 2 | Modbus 408110; not polled by default | Hz | Read | |
| AI | 591 | START FREQ 3 | Modbus 408111; not polled by default | Hz | Read | |
| AI | 592 | LOW FREQ 1 | Modbus 408112; not polled by default | Hz | Read | |
| AI | 593 | LOW FREQ 2 | Modbus 408113; not polled by default | Hz | Read | |
| AI | 594 | LOW FREQ 3 | Modbus 408114; not polled by default | Hz | Read | |
| AI | 595 | AUX MOT START D | Modbus 408115; not polled by default | s | Read | |
| AI | 596 | AUX MOT STOP D | Modbus 408116; not polled by default | s | Read | |
| AI | 597 | NR OF AUX MOT | Modbus 408117; not polled by default | Read | ||
| AI | 598 | AUTOCHNG INTERV | Modbus 408118; not polled by default | h | Read | |
| AI | 599 | AUTOCHNG LEVEL | Modbus 408119; not polled by default | % | Read | |
| AI | 600 | INTERLOCKS | Modbus 408120; not polled by default | Read | ||
| AI | 601 | REG BYPASS CTRL | Modbus 408121; not polled by default | Read | ||
| AI | 602 | PFA START DELAY | Modbus 408122; not polled by default | s | Read | |
| AI | 603 | PFA ENABLE | Modbus 408123; not polled by default | Read | ||
| AI | 604 | ACC IN AUX STOP | Modbus 408124; not polled by default | s | Read | |
| AI | 605 | DEC IN AUX START | Modbus 408125; not polled by default | s | Read | |
| AI | 606 | TMED AUTOCHNG | Modbus 408126; not polled by default | Read | ||
| AI | 607 | MOTORS | Modbus 408127; not polled by default | Read | ||
| AI | 608 | AUX START ORDER | Modbus 408128; not polled by default | Read | ||
| AI | 609 | COMM PROT SEL | Modbus 409802; not polled by default | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX ABB ACH550 DCU point IDs by name
BI1STOPBI2STARTBI3REVERSEBI4LOCALBI5RESETBI6EXT2BI7RUN_DISABLEBI8STPMODE_RBI9STPMODE_EMBI10STPMODE_CBI11RAMP_2BI12RAMP_OUT_0BI13RAMP_HOLDBI14RAMP_IN_0BI15REQ_LOCALLOCKBI16TORQLIM2BI17FBLOCAL_CTLBI18FBLOCAL_REFBI19START_DISABLE1BI20START_DISABLE2BI21Relay Output 1BI22Relay Output 2BI23Relay Output 3BI24Relay Output 4BI25Relay Output 5BI26Relay Output 6BI27READYBI28ENABLEDBI29STARTEDBI30RUNNINGBI31ZERO_SPEEDBI32ACCELERATEBI33DECELERATEBI34AT_SETPOINTBI35LIMITBI36SUPERVISIONBI37REV_REFBI38REV_ACTBI39PANEL_LOCALBI40FIELDBUS_LOCALBI41EXT2_ACTBI42FAULTBI43ALARMBI44REQ_MAINTBI45DIRLOCKBI46LOCALLOCKBI47CTL_MODEBI48REQ_CTLBI49REQ_REF1BI50REQ_REF2BI51REQ_REF2EXTBI52ACK_STARTINHBI53ACK_OFF_ILCKBI54DI1BI55DI2BI56DI3BI57DI4BI58DI5BI59DI6AI60AI1AI61AI2AO62CONTROL WORDAO63Reference 1AO64Reference 2AI65STATUS WORDAI66Actual 1AI67Actual 2AI68Actual 3AI69Actual 4AI70Actual 5AI71Actual 6AI72Actual 7AI73Actual 8AO74ACH550 CONTROL WORD LSWAI75ACH550 CONTROL WORD MSWAI76ACH550 STATUS WORD LSWAI77ACH550 STATUS WORD MSWAI78LANGUAGEAI79APPLIC MACROAI80MOTOR CTRL MODEAI81MOTOR NOM VOLTAI82MOTOR NOM CURRAI83MOTOR NOM FREQAI84MOTOR NOM SPEEDAI85MOTOR NOM POWERAI86ID RUNAI87MOTOR COSPHIAI88SPEED DIRAI89SPEEDAI90OUTPUT FREQAI91CURRENTAI92TORQUEAI93POWERAI94DC BUS VOLTAGEAI95OUTPUT VOLTAGEAI96DRIVE TEMPAI97EXTERNAL REF 1AI98EXTERNAL REF 2AI99CTRL LOCATIONAI100RUN TIME (R)AI101KWH COUNTER (R)AI102APPL BLK OUTPUTAI103DI 1-3 STATUSAI104DI 4-6 STATUSAI105AI 1AI106AI 2AI107RO 1-3 STATUSAI108RO 4-6 STATUSAI109AO 1AI110AO 2AI111PID 1 OUTPUTAI112PID 2 OUTPUTAI113PID 1 SETPNTAI114PID 2 SETPNTAI115PID 1 FBKAI116PID 2 FBKAI117PID 1 DEVIATIONAI118PID 2 DEVIATIONAI119COMM RO WORDAI120COMM VALUE 1AI121COMM VALUE 2AI122PROCESS VAR 1AI123PROCESS VAR 2AI124PROCESS VAR 3AI125RUN TIMEAI126MWH COUNTERAI127REVOLUTION CNTRAI128DRIVE ON TIME HIAI129DRIVE ON TIME LOAI130MOTOR TEMPAI131CB TEMPAI132MOT THERM STRESSAI133PID COMM VALUE 1AI134PID COMM VALUE 2AI135SAVED KWHAI136SAVED MWHAI137SAVED AMOUNT 1AI138SAVED AMOUNT 2AI139SAVED CO2AI140FB CMD WORD 1AI141FB CMD WORD 2AI142FB STS WORD 1AI143FB STS WORD 2AI144FAULT WORD 1AI145FAULT WORD 2AI146FAULT WORD 3AI147ALARM WORD 1AI148ALARM WORD 2AI149LAST FAULTAI150FAULT TIME 1AI151FAULT TIME 2AI152SPEED AT FLTAI153FREQ AT FLTAI154VOLTAGE AT FLTAI155CURRENT AT FLTAI156TORQUE AT FLTAI157STATUS AT FLTAI158DI 1-3 AT FLTAI159DI 4-6 AT FLTAI160PREVIOUS FAULT 1AI161PREVIOUS FAULT 2AI162EXT1 COMMANDSAI163EXT2 COMMANDSAI164DIRECTIONAI165KEYPAD REF SELAI166EXT1/EXT2 SELAI167REF1 SELECTAI168REF1 MINAI169REF1 MAXAI170REF2 SELECTAI171REF2 MINAI172REF2 MAXAI173CONST SPEED SELAI174CONST SPEED 1AI175CONST SPEED 2AI176CONST SPEED 3AI177CONST SPEED 4AI178CONST SPEED 5AI179CONST SPEED 6AI180CONST SPEED 7AI181TIMED MODE SELAI182MINIMUM AI1AI183MAXIMUM AI1AI184FILTER AI1AI185MINIMUM AI2AI186MAXIMUM AI2AI187FILTER AI2AI188RELAY OUTPUT 1AI189RELAY OUTPUT 2AI190RELAY OUTPUT 3AI191RO 1 ON DELAYAI192RO 1 OFF DELAYAI193RO 2 ON DELAYAI194RO 2 OFF DELAYAI195RO 3 ON DELAYAI196RO 3 OFF DELAYAI197RELAY OUTPUT 4AI198RELAY OUTPUT 5AI199RELAY OUTPUT 6AI200RO 4 ON DELAYAI201RO 4 OFF DELAYAI202RO 5 ON DELAYAI203RO 5 OFF DELAYAI204RO 6 ON DELAYAI205RO 6 OFF DELAYAI206AO1 CONTENT SELAI207AO1 CONTENT MINAI208AO1 CONTENT MAXAI209MINIMUM AO1AI210MAXIMUM AO1AI211FILTER AO1AI212AO2 CONTENT SELAI213AO2 CONTENT MINAI214AO2 CONTENT MAXAI215MINIMUM AO2AI216MAXIMUM AO2AI217FILTER AO2AI218RUN ENABLEAI219PARAMETER LOCKAI220PASS CODEAI221FAULT RESET sELAI222USER PAR SET CHGAI223LOCAL LOCKAI224PARAM SAVEAI225START ENABLE 1AI226START ENABLE 2AI227DISPLAY ALARMSAI228PARAMETER VIEWAI229FAN CONTROLAI230FAULT RESETAI231OVERRIDE SELAI232OVERRIDE FREQAI233OVERRIDE SPEEDAI234OVERR PASS CODEAI235OVERRIDEAI236OVERRIDE DIRAI237OVERRIDE REFAI238MINIMUM SPEEDAI239MAXIMUM SPEEDAI240MAX CURRENTAI241UNDERVOLT CTRLAI242MINIMUM FREQAI243MAXIMUM FREQAI244MIN TORQUE SELAI245MAX TORQUE SELAI246MIN TORQUE 1AI247MIN TORQUE 2AI248MAX TORQUE 1AI249MAX TORQUE 2AI250START FUNCTIONAI251STOP FUNCTIONAI252DC MAGN TIMEAI253DC HOLD CTLAI254DC HOLD SPEEDAI255DC CURR REFAI256DC BRAKE TIMEAI257START INHIBITAI258EMERG STOP SELAI259TORQ BOOST CURRAI260START DELAYAI261ACC/DEC 1/2 SELAI262ACCELER TIME 1AI263DECELER TIME 1AI264RAMP SHAPE 1AI265ACCELER TIME 2AI266DECELER TIME 2AI267RAMP SHAPE 2AI268EMERG DEC TIMEAI269RAMP INPUT 0AI270PROP GAINAI271INTEGRATION TIMEAI272DERIVATION TIMEAI273ACC COMPENSATIONAI274AUTOTUNE RUNAI275CRIT SPEED SELAI276CRIT SPEED 1 LOAI277CRIT SPEED 1 HIAI278CRIT SPEED 2 LOAI279CRIT SPEED 2 HIAI280CRIT SPEED 3 LOAI281CRIT SPEED 3 HIAI282FLUX OPT ENABLEAI283FLUX BRAKINGAI284IR COMP VOLTAI285IR COMP FREQAI286U/F RATIOAI287SWITCHING FREQAI288SWITCH FREQ CTRLAI289SLIP COMP RATIOAI290NOISE SMOOTHINGAI291DC STABILIZERAI292OVERMODULATIONAI293COOLING FAN TRIGAI294COOLING FAN ACTAI295REVOLUTION TRIGAI296REVOLUTION ACTAI297RUN TIME TRIGAI298RUN TIME ACTAI299USER MWh TRIGAI300USER MWh ACTAI301AI<MIN FUNCTIONAI302PANEL COMM ERRAI303EXTERNAL FAULT 1AI304EXTERNAL FAULT 2AI305MOT THERM PROTAI306MOT THERM TIMEAI307MOT LOAD CURVEAI308ZERO SPEED LOADAI309BREAK POINT FREQAI310STALL FUNCTIONAI311STALL FREQUENCYAI312STALL TIMEAI313EARTH FAULTAI314COMM FAULT FUNCAI315COMM FAULT TIMEAI316AI1 FAULT LIMITAI317AI2 FAULT LIMITAI318WIRING FAULTAI319CB TEMP FAULTAI320EARTH FAULT LVLAI321NUMBER OF TRIALSAI322TRIAL TIMEAI323DELAY TIMEAI324AR OVERCURRENTAI325AR OVERVOLTAGEAI326AR UNDERVOLTAGEAI327AR AI<MINAI328AR EXTERNAL FLTAI329SUPERV 1 PARAMAI330SUPERV 1 LIM LOAI331SUPERV 1 LIM HIAI332SUPERV 2 PARAMAI333SUPERV 2 LIM LOAI334SUPERV 2 LIM HIAI335SUPERV 3 PARAMAI336SUPERV 3 LIM LOAI337SUPERV 3 LIM HIAI338FIRMWAREAI339LOADING PACKAGEAI340TEST DATEAI341DRIVE RATINGAI342PARAMETER TABLEAI343SIGNAL1 PARAMAI344SIGNAL1 MINAI345SIGNAL1 MAXAI346OUTPUT1 DSP FORMAI347OUTPUT1 UNITAI348OUTPUT1 MINAI349OUTPUT1 MAXAI350SIGNAL2 PARAMAI351SIGNAL2 MINAI352SIGNAL2 MAXAI353OUTPUT2 DSP FORMAI354OUTPUT2 UNITAI355OUTPUT2 MINAI356OUTPUT2 MAXAI357SIGNAL3 PARAMAI358SIGNAL3 MINAI359SIGNAL3 MAXAI360OUTPUT3 DSP FORMAI361OUTPUT3 UNITAI362OUTPUT3 MINAI363OUTPUT3 MAXAI364SENSOR TYPEAI365INPUT SELECTIONAI366ALARM LIMITAI367FAULT LIMITAI368TIMERS ENABLEAI369START TIME 1AI370STOP TIME 1AI371START DAY 1AI372STOP DAY 1AI373START TIME 2AI374STOP TIME 2AI375START DAY 2AI376STOP DAY 2AI377START TIME 3AI378STOP TIME 3AI379START DAY 3AI380STOP DAY 3AI381START TIME 4AI382STOP TIME 4AI383START DAY 4AI384STOP DAY 4AI385BOOSTER SELAI386BOOSTER TIMEAI387TIMED FUNC 1 SRCAI388TIMED FUNC 2 SRCAI389TIMED FUNC 3 SRCAI390TIMED FUNC 4 SRCAI391USER LOAD C MODEAI392USER LOAD C FUNCAI393USER LOAD C TIMEAI394LOAD FREQ 1AI395LOAD TORQ LOW 1AI396LOAD TORQ HIGH 1AI397LOAD FREQ 2AI398LOAD TORQ LOW 2AI399LOAD TORQ HIGH 2AI400LOAD FREQ 3AI401LOAD TORQ LOW 3AI402LOAD TORQ HIGH 3AI403LOAD FREQ 4AI404LOAD TORQ LOW 4AI405LOAD TORQ HIGH 4AI406LOAD FREQ 5AI407LOAD TORQ LOW 5AI408LOAD TORQ HIGH 5AI409GAINAI410INTEGRATION TIMEAI411DERIVATION TIMEAI412PID DERIV FILTERAI413ERROR VALUE INVAI414UNITSAI415UNIT SCALEAI4160% VALUEAI417100% VALUEAI418SET POINT SELAI419INTERNAL SETPNTAI420SETPOINT MINAI421SETPOINT MAXAI422FBK SELAI423FBK MULTIPLIERAI424ACT1 INPUTAI425ACT2 INPUTAI426ACT1 MINIMUMAI427ACT1 MAXIMUMAI428ACT2 MINIMUMAI429ACT2 MAXIMUMAI430SLEEP SELECTIONAI431PID SLEEP LEVELAI432PID SLEEP DELAYAI433WAKE-UP DEVAI434WAKE-UP DELAYAI435PID 1 PARAM SETAI436GAINAI437INTEGRATION TIMEAI438DERIVATION TIMEAI439PID DERIV FILTERAI440ERROR VALUE INVAI441UNITSAI442UNIT SCALEAI4430% VALUEAI444100% VALUEAI445SET POINT SELAI446INTERNAL SETPNTAI447SETPOINT MINAI448SETPOINT MAXAI449FBK SELAI450FBK MULTIPLIERAI451ACT1 INPUTAI452ACT2 INPUTAI453ACT1 MINIMUMAI454ACT1 MAXIMUMAI455ACT2 MINIMUMAI456ACT2 MAXIMUMAI457SLEEP SELECTIONAI458PID SLEEP LEVELAI459PID SLEEP DELAYAI460WAKE-UP DEVAI461WAKE-UP DELAYAI462GAINAI463INTEGRATION TIMEAI464DERIVATION TIMEAI465PID DERIV FILTERAI466ERROR VALUE INVAI467UNITSAI468UNIT SCALEAI4690% VALUEAI470100% VALUEAI471SET POINT SELAI472INTERNAL SETPNTAI473SETPOINT MINAI474SETPOINT MAXAI475FBK SELAI476FBK MULTIPLIERAI477ACT1 INPUTAI478ACT2 INPUTAI479ACT1 MINIMUMAI480ACT1 MAXIMUMAI481ACT2 MINIMUMAI482ACT2 MAXIMUMAI483ACTIVATEAI484OFFSETAI485TRIM MODEAI486TRIM SCALEAI487CORRECTION SRCAI488ENERGY PRICEAI489CO2 CONV FACTORAI490PUMP POWERAI491ENERGY RESETAI492FBA TYPEAI493FB PAR 02AI494FB PAR 03AI495FB PAR 04AI496FB PAR 05AI497FB PAR 06AI498FB PAR 07AI499FB PAR 08AI500FB PAR 09AI501FB PAR 10AI502FB PAR 11AI503FB PAR 12AI504FB PAR 13AI505FB PAR 14AI506FB PAR 15AI507FB PAR 16AI508FB PAR 17AI509FB PAR 18AI510FB PAR 19AI511FB PAR 20AI512FB PAR 21AI513FB PAR 22AI514FB PAR 23AI515FB PAR 24AI516FB PAR 25AI517FB PAR 26AI518FBA PAR REFRESHAI519FILE CPI FW REVAI520FILE CONFIG IDAI521FILE CONFIG REVAI522FBA STATUSAI523FBA CPI FW REVAI524FBA APPL FW REVAI525STATION IDAI526BAUD RATEAI527PARITYAI528OK MESSAGESAI529PARITY ERRORSAI530FRAME ERRORSAI531BUFFER OVERRUNSAI532CRC ERRORSAI533EFB PROTOCOL IDAI534EFB STATION IDAI535EFB BAUD RATEAI536EFB PARITYAI537EFB CTRL PROFILEAI538EFB OK MESSAGESAI539EFB CRC ERRORSAI540EFB UART ERRORSAI541EFB STATUSAI542EFB PAR 10AI543EFB PAR 11AI544EFB PAR 12AI545EFB PAR 13AI546EFB PAR 14AI547EFB PAR 15AI548EFB PAR 16AI549EFB PAR 17AI550EFB PAR 18AI551EFB PAR 19AI552EFB PAR 20AI553PVL SIGNALAI554PVL FILTER TIMEAI555LOGGERS RESETAI556AL2 SIGNALAI557AL2 SIGNAL BASEAI558PEAK VALUEAI559PEAK TIME 1AI560PEAK TIME 2AI561CURRENT AT PEAKAI562UDC AT PEAKAI563FREQ AT PEAKAI564TIME OF RESET 1AI565TIME OF RESET 2AI566AL1RANGE0TO10AI567AL1RANGE10TO20AI568AL1RANGE20TO30AI569AL1RANGE30TO40AI570AL1RANGE40TO50AI571AL1RANGE50TO60AI572AL1RANGE60TO70AI573AL1RANGE70TO80AI574AL1RANGE80TO90AI575AL1RANGE90TOAI576AL2RANGE0TO10AI577AL2RANGE10TO20AI578AL2RANGE20TO30AI579AL2RANGE30TO40AI580AL2RANGE40TO50AI581AL2RANGE50TO60AI582AL2RANGE60TO70AI583AL2RANGE70TO80AI584AL2RANGE80TO90AI585AL2RANGE90TOAI586REFERENCE STEP 1AI587REFERENCE STEP 2AI588REFERENCE STEP 3AI589START FREQ 1AI590START FREQ 2AI591START FREQ 3AI592LOW FREQ 1AI593LOW FREQ 2AI594LOW FREQ 3AI595AUX MOT START DAI596AUX MOT STOP DAI597NR OF AUX MOTAI598AUTOCHNG INTERVAI599AUTOCHNG LEVELAI600INTERLOCKSAI601REG BYPASS CTRLAI602PFA START DELAYAI603PFA ENABLEAI604ACC IN AUX STOPAI605DEC IN AUX STARTAI606TMED AUTOCHNGAI607MOTORSAI608AUX START ORDERAI609COMM PROT SEL
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile ABB_Drive_DCU_5305_is_1_a_LX.csv; the profile maps the registers in the ACH550 user's manual (3AUA0000081823), embedded fieldbus section (https://www.ccontrols.com/support/dp/3AUA0000081823_REVC.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 138 of the 609 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
- Some names appear more than once in the profile as published (INTEGRATION TIME; DERIVATION TIME; GAIN...); they are kept as printed and told apart by instance.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
How many BACnet points does the Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX have?
This list has 609 BACnet objects: 546 analog inputs, 4 analog outputs, 59 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX BACnet points are writable?
4 of the 609 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile ABB_Drive_DCU_5305_is_1_a (ABB_Drive_DCU_5305_is_1_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/ABB_Drive_DCU_5305_is_1_a_LX.zip.
What are the minimum BACnet points to integrate the Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX?
Start with AO 74 ACH550 CONTROL WORD LSW (DCU control word, low word: start/stop, reset bits); AO 63 Reference 1 (Speed reference REF1); BI 30 RUNNING (Drive running); AI 90 OUTPUT FREQ (Output frequency, Hz); AI 89 SPEED (Motor speed, rpm); AI 91 CURRENT (Motor current, A); AI 93 POWER (Output power, kW); BI 43 ALARM (Any active alarm); BI 42 FAULT (Drive tripped on a fault); AI 144 FAULT WORD 1 (Fault bits, word 1).
How do I enable BMS control of the Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX?
Set EXT1 commands (parameter 1001) to 10 (COMM) and the speed reference source to COMM as the ACH550 manual describes, and parameter 5305 = 1. In this mode start/stop comes from register 40031 (AO 74), not 40001.
How do I check these points on the real ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler (modular cascade)
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Hydrotherm / Advanced Thermal Hydronics KN-2 and KN-4 modular boilers with the KN boiler-room controller on Modbus, read by a BASgatewayLX.
Also known as: Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile ABB_Drive_DCU_5305_is_1_a · ABB_Drive_DCU_5305_is_1_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.