- Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Boiler (modular cascade) · BACnet points list
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX BACnet points list
Updated 12 November 2026
Gateway profile for the Hydrotherm KN-2/KN-4 boiler system: 674 objects (112 AI, 18 AO, 544 BI), 57 polled by default. Writable objects cover heat demand, setpoint, outdoor-reset curve and DHW setpoint; the inputs give header, supply, return and outside temperatures, boilers on, modulation and a block of status bits per member boiler (only boiler 1 is polled by default).
This page lists 674 BACnet objects for the Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Contemporary Controls’s own free documentation, linked below.
- Manufacturer
- Contemporary Controls
- Model
- Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
- Equipment
- Boiler (modular cascade)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 674 (18 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- Hydrotherm KN, KN-2, KN-4, Advanced Thermal Hydronics, Mastek KN
Reference only, provided as-is: verify against Contemporary Controls’s current documentation and the live device before use. Not official Contemporary Controls information. Terms of use.
BMS integration notes: Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
Write HeatDemand and the setpoint, then read header/supply temperatures, boilers on and modulation. Enable the status bits for each member boiler you have.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 1 | HeatDemand | Heat demand from the BMS | Command |
| AO 3 | Setpoint | System setpoint | Command |
| AO 18 | DHWSetpoint | DHW setpoint | Command |
| AI 21 | HeaderTemp | Header temperature | Read |
| AI 22 | SupplyTemp | Supply temperature | Read |
| AI 23 | ReturnTemp | Return temperature | Read |
| AI 19 | BoilersOn | Number of boilers on | Read |
| AI 20 | Modulation | System modulation | Read |
| BI 47 | Boiler01Status2 Alarm | Boiler 1 alarm | Read |
Network setup
- The BASgatewayLX presents each Modbus device as its own virtual BACnet device on BACnet IP; give it a unique device instance and Modbus address (serial) or IP address (Modbus TCP) when you add it with this profile.
- One BASgatewayLX handles up to 100 Modbus devices and 1000 polled points in total, so leave unneeded rows unpolled.
Watch out for
- SetpointTimer (AO 2, seconds) sits next to the setpoint in the profile; check the KN manual for how it limits a BMS setpoint before relying on it.
- Member boilers 2-16 repeat boiler 1's status block at higher instances; they are unpolled by default.
- Unpolled rows do not appear as BACnet objects until enabled in the gateway's device profile page.
Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AOmin | 1 | HeatDemand | Modbus 400001 | Command | ||
| AO | 2 | SetpointTimer | Modbus 400002 | s | Command | |
| AOmin | 3 | Setpoint | Modbus 400003 | °F | Command | |
| AO | 4 | OAResetEnable | Modbus 400004 | Command | ||
| AO | 5 | OARSetpoint | Modbus 400005 | °F | Command | |
| AO | 6 | OARHighWaterTemp | Modbus 400006 | °F | Command | |
| AO | 7 | OARHighAirTemp | Modbus 400007 | °F | Command | |
| AO | 8 | OARLowWaterTemp | Modbus 400008 | °F | Command | |
| AO | 9 | OARLowAirTemp | Modbus 400009 | °F | Command | |
| AO | 10 | SetMonth | Modbus 400010; not polled by default | months | Command | |
| AO | 11 | SetDay | Modbus 400011; not polled by default | days | Command | |
| AO | 12 | SetYear | Modbus 400012; not polled by default | years | Command | |
| AO | 13 | SetHour | Modbus 400013; not polled by default | h | Command | |
| AO | 14 | SetMinute | Modbus 400014; not polled by default | min | Command | |
| AO | 15 | SetSecond | Modbus 400015; not polled by default | s | Command | |
| AO | 16 | SetWeekday | Modbus 400016; not polled by default | days | Command | |
| AO | 17 | SetClock | Modbus 400017; not polled by default | Command | ||
| AOmin | 18 | DHWSetpoint | Modbus 400018 | °F | Command | |
| AImin | 19 | BoilersOn | Modbus 300001 | Read | ||
| AImin | 20 | Modulation | Modbus 300002 | Read | ||
| AImin | 21 | HeaderTemp | Modbus 300003 | Read | ||
| AImin | 22 | SupplyTemp | Modbus 300004 | Read | ||
| AImin | 23 | ReturnTemp | Modbus 300005 | Read | ||
| AI | 24 | OutsideTemp | Modbus 300006 | Read | ||
| AI | 25 | Sparel | Modbus 300007; not polled by default | Read | ||
| AI | 26 | Spare2 | Modbus 300008; not polled by default | Read | ||
| AI | 27 | Month | Modbus 300009; not polled by default | Read | ||
| AI | 28 | Day | Modbus 300010; not polled by default | Read | ||
| AI | 29 | Year | Modbus 300011; not polled by default | Read | ||
| AI | 30 | Hour | Modbus 300012; not polled by default | Read | ||
| AI | 31 | Minute | Modbus 300013; not polled by default | Read | ||
| AI | 32 | Second | Modbus 300014; not polled by default | Read | ||
| AI | 33 | Weekday | Modbus 300015; not polled by default | Read | ||
| BI | 34 | Boiler01Status1 Blower Running | Modbus 300016 bit 1 | Read | ||
| BI | 35 | Boiler01Status1 Ignition Alarm | Modbus 300016 bit 2 | Read | ||
| BI | 36 | Boiler01Status1 High Limit | Modbus 300016 bit 4 | Read | ||
| BI | 37 | Boiler01Status1 Software Operator | Modbus 300016 bit 7 | Read | ||
| BI | 38 | Boiler01Status1 Header Sensor not detected | Modbus 300016 bit 8 | Read | ||
| BI | 39 | Boiler01Status1 Supply Sensor not detected | Modbus 300016 bit 9 | Read | ||
| BI | 40 | Boiler01Status1 Return Sensor not detected | Modbus 300016 bit 10 | Read | ||
| BI | 41 | Boiler01Status1 Outside Sensor not detected | Modbus 300016 bit 11 | Read | ||
| BI | 42 | Boiler01Status1 Combustion Air Damper | Modbus 300016 bit 13 | Read | ||
| BI | 43 | Boiler01Status1 Master Boiler | Modbus 300016 bit 14 | Read | ||
| BI | 44 | Boiler01Status1 Boiler Detected | Modbus 300016 bit 15 | Read | ||
| BI | 45 | Boiler01Status2 Disabled | Modbus 300017 bit 0 | Read | ||
| BI | 46 | Boiler01Status2 Heat Demand | Modbus 300017 bit 1 | Read | ||
| BImin | 47 | Boiler01Status2 Alarm | Modbus 300017 bit 2 | Read | ||
| BI | 48 | Boiler01Status2 Failed | Modbus 300017 bit 3 | Read | ||
| BI | 49 | Boiler01Status2 Member Error | Modbus 300017 bit 4 | Read | ||
| BI | 50 | Boiler01Status2 Boiler Running | Modbus 300017 bit 5 | Read | ||
| BI | 51 | Boiler01Status2 Pump Running | Modbus 300017 bit 6 | Read | ||
| BI | 52 | Boiler01Status2 Spare 4 (User) Interlock | Modbus 300017 bit 11 | Read | ||
| BI | 53 | Boiler01Status2 Water Prove (Flow) Interlock | Modbus 300017 bit 13 | Read | ||
| BI | 54 | Boiler01Status2 Main Valve | Modbus 300017 bit 15 | Read | ||
| BI | 55 | Boiler02Status1 Blower Running | Modbus 300018 bit 1; not polled by default | Read | ||
| BI | 56 | Boiler02Status1 Ignition Alarm | Modbus 300018 bit 2; not polled by default | Read | ||
| BI | 57 | Boiler02Status1 High Limit | Modbus 300018 bit 4; not polled by default | Read | ||
| BI | 58 | Boiler02Status1 Software Operator | Modbus 300018 bit 7; not polled by default | Read | ||
| BI | 59 | Boiler02Status1 Header Sensor not detected | Modbus 300018 bit 8; not polled by default | Read | ||
| BI | 60 | Boiler02Status1 Supply Sensor not detected | Modbus 300018 bit 9; not polled by default | Read | ||
| BI | 61 | Boiler02Status1 Return Sensor not detected | Modbus 300018 bit 10; not polled by default | Read | ||
| BI | 62 | Boiler02Status1 Outside Sensor not detected | Modbus 300018 bit 11; not polled by default | Read | ||
| BI | 63 | Boiler02Status1 Combustion Air Damper | Modbus 300018 bit 13; not polled by default | Read | ||
| BI | 64 | Boiler02Status1 Master Boiler | Modbus 300018 bit 14; not polled by default | Read | ||
| BI | 65 | Boiler02Status1 Boiler Detected | Modbus 300018 bit 15; not polled by default | Read | ||
| BI | 66 | Boiler02Status2 Disabled | Modbus 300019 bit 0; not polled by default | Read | ||
| BI | 67 | Boiler02Status2 Heat Demand | Modbus 300019 bit 1; not polled by default | Read | ||
| BI | 68 | Boiler02Status2 Alarm | Modbus 300019 bit 2; not polled by default | Read | ||
| BI | 69 | Boiler02Status2 Failed | Modbus 300019 bit 3; not polled by default | Read | ||
| BI | 70 | Boiler02Status2 Member Error | Modbus 300019 bit 4; not polled by default | Read | ||
| BI | 71 | Boiler02Status2 Boiler Running | Modbus 300019 bit 5; not polled by default | Read | ||
| BI | 72 | Boiler02Status2 Pump Running | Modbus 300019 bit 6; not polled by default | Read | ||
| BI | 73 | Boiler02Status2 Spare 4 (User) Interlock | Modbus 300019 bit 11; not polled by default | Read | ||
| BI | 74 | Boiler02Status2 Water Prove (Flow) Interlock | Modbus 300019 bit 13; not polled by default | Read | ||
| BI | 75 | Boiler02Status2 Main Valve | Modbus 300019 bit 15; not polled by default | Read | ||
| BI | 76 | Boiler03Status1 Blower Running | Modbus 300020 bit 1; not polled by default | Read | ||
| BI | 77 | Boiler03Status1 Ignition Alarm | Modbus 300020 bit 2; not polled by default | Read | ||
| BI | 78 | Boiler03Status1 High Limit | Modbus 300020 bit 4; not polled by default | Read | ||
| BI | 79 | Boiler03Status1 Software Operator | Modbus 300020 bit 7; not polled by default | Read | ||
| BI | 80 | Boiler03Status1 Header Sensor not detected | Modbus 300020 bit 8; not polled by default | Read | ||
| BI | 81 | Boiler03Status1 Supply Sensor not detected | Modbus 300020 bit 9; not polled by default | Read | ||
| BI | 82 | Boiler03Status1 Return Sensor not detected | Modbus 300020 bit 10; not polled by default | Read | ||
| BI | 83 | Boiler03Status1 Outside Sensor not detected | Modbus 300020 bit 11; not polled by default | Read | ||
| BI | 84 | Boiler03Status1 Combustion Air Damper | Modbus 300020 bit 13; not polled by default | Read | ||
| BI | 85 | Boiler03Status1 Master Boiler | Modbus 300020 bit 14; not polled by default | Read | ||
| BI | 86 | Boiler03Status1 Boiler Detected | Modbus 300020 bit 15; not polled by default | Read | ||
| BI | 87 | Boiler03Status2 Disabled | Modbus 300021 bit 0; not polled by default | Read | ||
| BI | 88 | Boiler03Status2 Heat Demand | Modbus 300021 bit 1; not polled by default | Read | ||
| BI | 89 | Boiler03Status2 Alarm | Modbus 300021 bit 2; not polled by default | Read | ||
| BI | 90 | Boiler03Status2 Failed | Modbus 300021 bit 3; not polled by default | Read | ||
| BI | 91 | Boiler03Status2 Member Error | Modbus 300021 bit 4; not polled by default | Read | ||
| BI | 92 | Boiler03Status2 Boiler Running | Modbus 300021 bit 5; not polled by default | Read | ||
| BI | 93 | Boiler03Status2 Pump Running | Modbus 300021 bit 6; not polled by default | Read | ||
| BI | 94 | Boiler03Status2 Spare 4 (User) Interlock | Modbus 300021 bit 11; not polled by default | Read | ||
| BI | 95 | Boiler03Status2 Water Prove (Flow) Interlock | Modbus 300021 bit 13; not polled by default | Read | ||
| BI | 96 | Boiler03Status2 Main Valve | Modbus 300021 bit 15; not polled by default | Read | ||
| BI | 97 | Boiler04Status1 Blower Running | Modbus 300022 bit 1; not polled by default | Read | ||
| BI | 98 | Boiler04Status1 Ignition Alarm | Modbus 300022 bit 2; not polled by default | Read | ||
| BI | 99 | Boiler04Status1 High Limit | Modbus 300022 bit 4; not polled by default | Read | ||
| BI | 100 | Boiler04Status1 Software Operator | Modbus 300022 bit 7; not polled by default | Read | ||
| BI | 101 | Boiler04Status1 Header Sensor not detected | Modbus 300022 bit 8; not polled by default | Read | ||
| BI | 102 | Boiler04Status1 Supply Sensor not detected | Modbus 300022 bit 9; not polled by default | Read | ||
| BI | 103 | Boiler04Status1 Return Sensor not detected | Modbus 300022 bit 10; not polled by default | Read | ||
| BI | 104 | Boiler04Status1 Outside Sensor not detected | Modbus 300022 bit 11; not polled by default | Read | ||
| BI | 105 | Boiler04Status1 Combustion Air Damper | Modbus 300022 bit 13; not polled by default | Read | ||
| BI | 106 | Boiler04Status1 Master Boiler | Modbus 300022 bit 14; not polled by default | Read | ||
| BI | 107 | Boiler04Status1 Boiler Detected | Modbus 300022 bit 15; not polled by default | Read | ||
| BI | 108 | Boiler04Status2 Disabled | Modbus 300023 bit 0; not polled by default | Read | ||
| BI | 109 | Boiler04Status2 Heat Demand | Modbus 300023 bit 1; not polled by default | Read | ||
| BI | 110 | Boiler04Status2 Alarm | Modbus 300023 bit 2; not polled by default | Read | ||
| BI | 111 | Boiler04Status2 Failed | Modbus 300023 bit 3; not polled by default | Read | ||
| BI | 112 | Boiler04Status2 Member Error | Modbus 300023 bit 4; not polled by default | Read | ||
| BI | 113 | Boiler04Status2 Boiler Running | Modbus 300023 bit 5; not polled by default | Read | ||
| BI | 114 | Boiler04Status2 Pump Running | Modbus 300023 bit 6; not polled by default | Read | ||
| BI | 115 | Boiler04Status2 Spare 4 (User) Interlock | Modbus 300023 bit 11; not polled by default | Read | ||
| BI | 116 | Boiler04Status2 Water Prove (Flow) Interlock | Modbus 300023 bit 13; not polled by default | Read | ||
| BI | 117 | Boiler04Status2 Main Valve | Modbus 300023 bit 15; not polled by default | Read | ||
| BI | 118 | Boiler05Status1 Blower Running | Modbus 300024 bit 1; not polled by default | Read | ||
| BI | 119 | Boiler05Status1 Ignition Alarm | Modbus 300024 bit 2; not polled by default | Read | ||
| BI | 120 | Boiler05Status1 High Limit | Modbus 300024 bit 4; not polled by default | Read | ||
| BI | 121 | Boiler05Status1 Software Operator | Modbus 300024 bit 7; not polled by default | Read | ||
| BI | 122 | Boiler05Status1 Header Sensor not detected | Modbus 300024 bit 8; not polled by default | Read | ||
| BI | 123 | Boiler05Status1 Supply Sensor not detected | Modbus 300024 bit 9; not polled by default | Read | ||
| BI | 124 | Boiler05Status1 Return Sensor not detected | Modbus 300024 bit 10; not polled by default | Read | ||
| BI | 125 | Boiler05Status1 Outside Sensor not detected | Modbus 300024 bit 11; not polled by default | Read | ||
| BI | 126 | Boiler05Status1 Combustion Air Damper | Modbus 300024 bit 13; not polled by default | Read | ||
| BI | 127 | Boiler05Status1 Master Boiler | Modbus 300024 bit 14; not polled by default | Read | ||
| BI | 128 | Boiler05Status1 Boiler Detected | Modbus 300024 bit 15; not polled by default | Read | ||
| BI | 129 | Boiler05Status2 Disabled | Modbus 300025 bit 0; not polled by default | Read | ||
| BI | 130 | Boiler05Status2 Heat Demand | Modbus 300025 bit 1; not polled by default | Read | ||
| BI | 131 | Boiler05Status2 Alarm | Modbus 300025 bit 2; not polled by default | Read | ||
| BI | 132 | Boiler05Status2 Failed | Modbus 300025 bit 3; not polled by default | Read | ||
| BI | 133 | Boiler05Status2 Member Error | Modbus 300025 bit 4; not polled by default | Read | ||
| BI | 134 | Boiler05Status2 Boiler Running | Modbus 300025 bit 5; not polled by default | Read | ||
| BI | 135 | Boiler05Status2 Pump Running | Modbus 300025 bit 6; not polled by default | Read | ||
| BI | 136 | Boiler05Status2 Spare 4 (User) Interlock | Modbus 300025 bit 11; not polled by default | Read | ||
| BI | 137 | Boiler05Status2 Water Prove (Flow) Interlock | Modbus 300025 bit 13; not polled by default | Read | ||
| BI | 138 | Boiler05Status2 Main Valve | Modbus 300025 bit 15; not polled by default | Read | ||
| BI | 139 | Boiler06Status1 Blower Running | Modbus 300026 bit 1; not polled by default | Read | ||
| BI | 140 | Boiler06Status1 Ignition Alarm | Modbus 300026 bit 2; not polled by default | Read | ||
| BI | 141 | Boiler06Status1 High Limit | Modbus 300026 bit 4; not polled by default | Read | ||
| BI | 142 | Boiler06Status1 Software Operator | Modbus 300026 bit 7; not polled by default | Read | ||
| BI | 143 | Boiler06Status1 Header Sensor not detected | Modbus 300026 bit 8; not polled by default | Read | ||
| BI | 144 | Boiler06Status1 Supply Sensor not detected | Modbus 300026 bit 9; not polled by default | Read | ||
| BI | 145 | Boiler06Status1 Return Sensor not detected | Modbus 300026 bit 10; not polled by default | Read | ||
| BI | 146 | Boiler06Status1 Outside Sensor not detected | Modbus 300026 bit 11; not polled by default | Read | ||
| BI | 147 | Boiler06Status1 Combustion Air Damper | Modbus 300026 bit 13; not polled by default | Read | ||
| BI | 148 | Boiler06Status1 Master Boiler | Modbus 300026 bit 14; not polled by default | Read | ||
| BI | 149 | Boiler06Status1 Boiler Detected | Modbus 300026 bit 15; not polled by default | Read | ||
| BI | 150 | Boiler06Status2 Disabled | Modbus 300027 bit 0; not polled by default | Read | ||
| BI | 151 | Boiler06Status2 Heat Demand | Modbus 300027 bit 1; not polled by default | Read | ||
| BI | 152 | Boiler06Status2 Alarm | Modbus 300027 bit 2; not polled by default | Read | ||
| BI | 153 | Boiler06Status2 Failed | Modbus 300027 bit 3; not polled by default | Read | ||
| BI | 154 | Boiler06Status2 Member Error | Modbus 300027 bit 4; not polled by default | Read | ||
| BI | 155 | Boiler06Status2 Boiler Running | Modbus 300027 bit 5; not polled by default | Read | ||
| BI | 156 | Boiler06Status2 Pump Running | Modbus 300027 bit 6; not polled by default | Read | ||
| BI | 157 | Boiler06Status2 Spare 4 (User) Interlock | Modbus 300027 bit 11; not polled by default | Read | ||
| BI | 158 | Boiler06Status2 Water Prove (Flow) Interlock | Modbus 300027 bit 13; not polled by default | Read | ||
| BI | 159 | Boiler06Status2 Main Valve | Modbus 300027 bit 15; not polled by default | Read | ||
| BI | 160 | Boiler07Status1 Blower Running | Modbus 300028 bit 1; not polled by default | Read | ||
| BI | 161 | Boiler07Status1 Ignition Alarm | Modbus 300028 bit 2; not polled by default | Read | ||
| BI | 162 | Boiler07Status1 High Limit | Modbus 300028 bit 4; not polled by default | Read | ||
| BI | 163 | Boiler07Status1 Software Operator | Modbus 300028 bit 7; not polled by default | Read | ||
| BI | 164 | Boiler07Status1 Header Sensor not detected | Modbus 300028 bit 8; not polled by default | Read | ||
| BI | 165 | Boiler07Status1 Supply Sensor not detected | Modbus 300028 bit 9; not polled by default | Read | ||
| BI | 166 | Boiler07Status1 Return Sensor not detected | Modbus 300028 bit 10; not polled by default | Read | ||
| BI | 167 | Boiler07Status1 Outside Sensor not detected | Modbus 300028 bit 11; not polled by default | Read | ||
| BI | 168 | Boiler07Status1 Combustion Air Damper | Modbus 300028 bit 13; not polled by default | Read | ||
| BI | 169 | Boiler07Status1 Master Boiler | Modbus 300028 bit 14; not polled by default | Read | ||
| BI | 170 | Boiler07Status1 Boiler Detected | Modbus 300028 bit 15; not polled by default | Read | ||
| BI | 171 | Boiler07Status2 Disabled | Modbus 300029 bit 0; not polled by default | Read | ||
| BI | 172 | Boiler07Status2 Heat Demand | Modbus 300029 bit 1; not polled by default | Read | ||
| BI | 173 | Boiler07Status2 Alarm | Modbus 300029 bit 2; not polled by default | Read | ||
| BI | 174 | Boiler07Status2 Failed | Modbus 300029 bit 3; not polled by default | Read | ||
| BI | 175 | Boiler07Status2 Member Error | Modbus 300029 bit 4; not polled by default | Read | ||
| BI | 176 | Boiler07Status2 Boiler Running | Modbus 300029 bit 5; not polled by default | Read | ||
| BI | 177 | Boiler07Status2 Pump Running | Modbus 300029 bit 6; not polled by default | Read | ||
| BI | 178 | Boiler07Status2 Spare 4 (User) Interlock | Modbus 300029 bit 11; not polled by default | Read | ||
| BI | 179 | Boiler07Status2 Water Prove (Flow) Interlock | Modbus 300029 bit 13; not polled by default | Read | ||
| BI | 180 | Boiler07Status2 Main Valve | Modbus 300029 bit 15; not polled by default | Read | ||
| BI | 181 | Boiler08Status1 Blower Running | Modbus 300030 bit 1; not polled by default | Read | ||
| BI | 182 | Boiler08Status1 Ignition Alarm | Modbus 300030 bit 2; not polled by default | Read | ||
| BI | 183 | Boiler08Status1 High Limit | Modbus 300030 bit 4; not polled by default | Read | ||
| BI | 184 | Boiler08Status1 Software Operator | Modbus 300030 bit 7; not polled by default | Read | ||
| BI | 185 | Boiler08Status1 Header Sensor not detected | Modbus 300030 bit 8; not polled by default | Read | ||
| BI | 186 | Boiler08Status1 Supply Sensor not detected | Modbus 300030 bit 9; not polled by default | Read | ||
| BI | 187 | Boiler08Status1 Return Sensor not detected | Modbus 300030 bit 10; not polled by default | Read | ||
| BI | 188 | Boiler08Status1 Outside Sensor not detected | Modbus 300030 bit 11; not polled by default | Read | ||
| BI | 189 | Boiler08Status1 Combustion Air Damper | Modbus 300030 bit 13; not polled by default | Read | ||
| BI | 190 | Boiler08Status1 Master Boiler | Modbus 300030 bit 14; not polled by default | Read | ||
| BI | 191 | Boiler08Status1 Boiler Detected | Modbus 300030 bit 15; not polled by default | Read | ||
| BI | 192 | Boiler08Status2 Disabled | Modbus 300031 bit 0; not polled by default | Read | ||
| BI | 193 | Boiler08Status2 Heat Demand | Modbus 300031 bit 1; not polled by default | Read | ||
| BI | 194 | Boiler08Status2 Alarm | Modbus 300031 bit 2; not polled by default | Read | ||
| BI | 195 | Boiler08Status2 Failed | Modbus 300031 bit 3; not polled by default | Read | ||
| BI | 196 | Boiler08Status2 Member Error | Modbus 300031 bit 4; not polled by default | Read | ||
| BI | 197 | Boiler08Status2 Boiler Running | Modbus 300031 bit 5; not polled by default | Read | ||
| BI | 198 | Boiler08Status2 Pump Running | Modbus 300031 bit 6; not polled by default | Read | ||
| BI | 199 | Boiler08Status2 Spare 4 (User) Interlock | Modbus 300031 bit 11; not polled by default | Read | ||
| BI | 200 | Boiler08Status2 Water Prove (Flow) Interlock | Modbus 300031 bit 13; not polled by default | Read | ||
| BI | 201 | Boiler08Status2 Main Valve | Modbus 300031 bit 15; not polled by default | Read | ||
| BI | 202 | Boiler09Status1 Blower Running | Modbus 300032 bit 1; not polled by default | Read | ||
| BI | 203 | Boiler09Status1 Ignition Alarm | Modbus 300032 bit 2; not polled by default | Read | ||
| BI | 204 | Boiler09Status1 High Limit | Modbus 300032 bit 4; not polled by default | Read | ||
| BI | 205 | Boiler09Status1 Software Operator | Modbus 300032 bit 7; not polled by default | Read | ||
| BI | 206 | Boiler09Status1 Header Sensor not detected | Modbus 300032 bit 8; not polled by default | Read | ||
| BI | 207 | Boiler09Status1 Supply Sensor not detected | Modbus 300032 bit 9; not polled by default | Read | ||
| BI | 208 | Boiler09Status1 Return Sensor not detected | Modbus 300032 bit 10; not polled by default | Read | ||
| BI | 209 | Boiler09Status1 Outside Sensor not detected | Modbus 300032 bit 11; not polled by default | Read | ||
| BI | 210 | Boiler09Status1 Combustion Air Damper | Modbus 300032 bit 13; not polled by default | Read | ||
| BI | 211 | Boiler09Status1 Master Boiler | Modbus 300032 bit 14; not polled by default | Read | ||
| BI | 212 | Boiler09Status1 Boiler Detected | Modbus 300032 bit 15; not polled by default | Read | ||
| BI | 213 | Boiler09Status2 Disabled | Modbus 300033 bit 0; not polled by default | Read | ||
| BI | 214 | Boiler09Status2 Heat Demand | Modbus 300033 bit 1; not polled by default | Read | ||
| BI | 215 | Boiler09Status2 Alarm | Modbus 300033 bit 2; not polled by default | Read | ||
| BI | 216 | Boiler09Status2 Failed | Modbus 300033 bit 3; not polled by default | Read | ||
| BI | 217 | Boiler09Status2 Member Error | Modbus 300033 bit 4; not polled by default | Read | ||
| BI | 218 | Boiler09Status2 Boiler Running | Modbus 300033 bit 5; not polled by default | Read | ||
| BI | 219 | Boiler09Status2 Pump Running | Modbus 300033 bit 6; not polled by default | Read | ||
| BI | 220 | Boiler09Status2 Spare 4 (User) Interlock | Modbus 300033 bit 11; not polled by default | Read | ||
| BI | 221 | Boiler09Status2 Water Prove (Flow) Interlock | Modbus 300033 bit 13; not polled by default | Read | ||
| BI | 222 | Boiler09Status2 Main Valve | Modbus 300033 bit 15; not polled by default | Read | ||
| BI | 223 | Boiler10Status1 Blower Running | Modbus 300034 bit 1; not polled by default | Read | ||
| BI | 224 | Boiler10Status1 Ignition Alarm | Modbus 300034 bit 2; not polled by default | Read | ||
| BI | 225 | Boiler10Status1 High Limit | Modbus 300034 bit 4; not polled by default | Read | ||
| BI | 226 | Boiler10Status1 Software Operator | Modbus 300034 bit 7; not polled by default | Read | ||
| BI | 227 | Boiler10Status1 Header Sensor not detected | Modbus 300034 bit 8; not polled by default | Read | ||
| BI | 228 | Boiler10Status1 Supply Sensor not detected | Modbus 300034 bit 9; not polled by default | Read | ||
| BI | 229 | Boiler10Status1 Return Sensor not detected | Modbus 300034 bit 10; not polled by default | Read | ||
| BI | 230 | Boiler10Status1 Outside Sensor not detected | Modbus 300034 bit 11; not polled by default | Read | ||
| BI | 231 | Boiler10Status1 Combustion Air Damper | Modbus 300034 bit 13; not polled by default | Read | ||
| BI | 232 | Boiler10Status1 Master Boiler | Modbus 300034 bit 14; not polled by default | Read | ||
| BI | 233 | Boiler10Status1 Boiler Detected | Modbus 300034 bit 15; not polled by default | Read | ||
| BI | 234 | Boiler10Status2 Disabled | Modbus 300035 bit 0; not polled by default | Read | ||
| BI | 235 | Boiler10Status2 Heat Demand | Modbus 300035 bit 1; not polled by default | Read | ||
| BI | 236 | Boiler10Status2 Alarm | Modbus 300035 bit 2; not polled by default | Read | ||
| BI | 237 | Boiler10Status2 Failed | Modbus 300035 bit 3; not polled by default | Read | ||
| BI | 238 | Boiler10Status2 Member Error | Modbus 300035 bit 4; not polled by default | Read | ||
| BI | 239 | Boiler10Status2 Boiler Running | Modbus 300035 bit 5; not polled by default | Read | ||
| BI | 240 | Boiler10Status2 Pump Running | Modbus 300035 bit 6; not polled by default | Read | ||
| BI | 241 | Boiler10Status2 Spare 4 (User) Interlock | Modbus 300035 bit 11; not polled by default | Read | ||
| BI | 242 | Boiler10Status2 Water Prove (Flow) Interlock | Modbus 300035 bit 13; not polled by default | Read | ||
| BI | 243 | Boiler10Status2 Main Valve | Modbus 300035 bit 15; not polled by default | Read | ||
| BI | 244 | Boiler11Status1 Blower Running | Modbus 300036 bit 1; not polled by default | Read | ||
| BI | 245 | Boiler11Status1 Ignition Alarm | Modbus 300036 bit 2; not polled by default | Read | ||
| BI | 246 | Boiler11Status1 High Limit | Modbus 300036 bit 4; not polled by default | Read | ||
| BI | 247 | Boiler11Status1 Software Operator | Modbus 300036 bit 7; not polled by default | Read | ||
| BI | 248 | Boiler11Status1 Header Sensor not detected | Modbus 300036 bit 8; not polled by default | Read | ||
| BI | 249 | Boiler11Status1 Supply Sensor not detected | Modbus 300036 bit 9; not polled by default | Read | ||
| BI | 250 | Boiler11Status1 Return Sensor not detected | Modbus 300036 bit 10; not polled by default | Read | ||
| BI | 251 | Boiler11Status1 Outside Sensor not detected | Modbus 300036 bit 11; not polled by default | Read | ||
| BI | 252 | Boiler11Status1 Combustion Air Damper | Modbus 300036 bit 13; not polled by default | Read | ||
| BI | 253 | Boiler11Status1 Master Boiler | Modbus 300036 bit 14; not polled by default | Read | ||
| BI | 254 | Boiler11Status1 Boiler Detected | Modbus 300036 bit 15; not polled by default | Read | ||
| BI | 255 | Boiler11Status2 Disabled | Modbus 300037 bit 0; not polled by default | Read | ||
| BI | 256 | Boiler11Status2 Heat Demand | Modbus 300037 bit 1; not polled by default | Read | ||
| BI | 257 | Boiler11Status2 Alarm | Modbus 300037 bit 2; not polled by default | Read | ||
| BI | 258 | Boiler11Status2 Failed | Modbus 300037 bit 3; not polled by default | Read | ||
| BI | 259 | Boiler11Status2 Member Error | Modbus 300037 bit 4; not polled by default | Read | ||
| BI | 260 | Boiler11Status2 Boiler Running | Modbus 300037 bit 5; not polled by default | Read | ||
| BI | 261 | Boiler11Status2 Pump Running | Modbus 300037 bit 6; not polled by default | Read | ||
| BI | 262 | Boiler11Status2 Spare 4 (User) Interlock | Modbus 300037 bit 11; not polled by default | Read | ||
| BI | 263 | Boiler11Status2 Water Prove (Flow) Interlock | Modbus 300037 bit 13; not polled by default | Read | ||
| BI | 264 | Boiler11Status2 Main Valve | Modbus 300037 bit 15; not polled by default | Read | ||
| BI | 265 | Boiler12Status1 Blower Running | Modbus 300038 bit 1; not polled by default | Read | ||
| BI | 266 | Boiler12Status1 Ignition Alarm | Modbus 300038 bit 2; not polled by default | Read | ||
| BI | 267 | Boiler12Status1 High Limit | Modbus 300038 bit 4; not polled by default | Read | ||
| BI | 268 | Boiler12Status1 Software Operator | Modbus 300038 bit 7; not polled by default | Read | ||
| BI | 269 | Boiler12Status1 Header Sensor not detected | Modbus 300038 bit 8; not polled by default | Read | ||
| BI | 270 | Boiler12Status1 Supply Sensor not detected | Modbus 300038 bit 9; not polled by default | Read | ||
| BI | 271 | Boiler12Status1 Return Sensor not detected | Modbus 300038 bit 10; not polled by default | Read | ||
| BI | 272 | Boiler12Status1 Outside Sensor not detected | Modbus 300038 bit 11; not polled by default | Read | ||
| BI | 273 | Boiler12Status1 Combustion Air Damper | Modbus 300038 bit 13; not polled by default | Read | ||
| BI | 274 | Boiler12Status1 Master Boiler | Modbus 300038 bit 14; not polled by default | Read | ||
| BI | 275 | Boiler12Status1 Boiler Detected | Modbus 300038 bit 15; not polled by default | Read | ||
| BI | 276 | Boiler12Status2 Disabled | Modbus 300039 bit 0; not polled by default | Read | ||
| BI | 277 | Boiler12Status2 Heat Demand | Modbus 300039 bit 1; not polled by default | Read | ||
| BI | 278 | Boiler12Status2 Alarm | Modbus 300039 bit 2; not polled by default | Read | ||
| BI | 279 | Boiler12Status2 Failed | Modbus 300039 bit 3; not polled by default | Read | ||
| BI | 280 | Boiler12Status2 Member Error | Modbus 300039 bit 4; not polled by default | Read | ||
| BI | 281 | Boiler12Status2 Boiler Running | Modbus 300039 bit 5; not polled by default | Read | ||
| BI | 282 | Boiler12Status2 Pump Running | Modbus 300039 bit 6; not polled by default | Read | ||
| BI | 283 | Boiler12Status2 Spare 4 (User) Interlock | Modbus 300039 bit 11; not polled by default | Read | ||
| BI | 284 | Boiler12Status2 Water Prove (Flow) Interlock | Modbus 300039 bit 13; not polled by default | Read | ||
| BI | 285 | Boiler12Status2 Main Valve | Modbus 300039 bit 15; not polled by default | Read | ||
| BI | 286 | Boiler13Status1 Blower Running | Modbus 300040 bit 1; not polled by default | Read | ||
| BI | 287 | Boiler13Status1 Ignition Alarm | Modbus 300040 bit 2; not polled by default | Read | ||
| BI | 288 | Boiler13Status1 High Limit | Modbus 300040 bit 4; not polled by default | Read | ||
| BI | 289 | Boiler13Status1 Software Operator | Modbus 300040 bit 7; not polled by default | Read | ||
| BI | 290 | Boiler13Status1 Header Sensor not detected | Modbus 300040 bit 8; not polled by default | Read | ||
| BI | 291 | Boiler13Status1 Supply Sensor not detected | Modbus 300040 bit 9; not polled by default | Read | ||
| BI | 292 | Boiler13Status1 Return Sensor not detected | Modbus 300040 bit 10; not polled by default | Read | ||
| BI | 293 | Boiler13Status1 Outside Sensor not detected | Modbus 300040 bit 11; not polled by default | Read | ||
| BI | 294 | Boiler13Status1 Combustion Air Damper | Modbus 300040 bit 13; not polled by default | Read | ||
| BI | 295 | Boiler13Status1 Master Boiler | Modbus 300040 bit 14; not polled by default | Read | ||
| BI | 296 | Boiler13Status1 Boiler Detected | Modbus 300040 bit 15; not polled by default | Read | ||
| BI | 297 | Boiler13Status2 Disabled | Modbus 300041 bit 0; not polled by default | Read | ||
| BI | 298 | Boiler13Status2 Heat Demand | Modbus 300041 bit 1; not polled by default | Read | ||
| BI | 299 | Boiler13Status2 Alarm | Modbus 300041 bit 2; not polled by default | Read | ||
| BI | 300 | Boiler13Status2 Failed | Modbus 300041 bit 3; not polled by default | Read | ||
| BI | 301 | Boiler13Status2 Member Error | Modbus 300041 bit 4; not polled by default | Read | ||
| BI | 302 | Boiler13Status2 Boiler Running | Modbus 300041 bit 5; not polled by default | Read | ||
| BI | 303 | Boiler13Status2 Pump Running | Modbus 300041 bit 6; not polled by default | Read | ||
| BI | 304 | Boiler13Status2 Spare 4 (User) Interlock | Modbus 300041 bit 11; not polled by default | Read | ||
| BI | 305 | Boiler13Status2 Water Prove (Flow) Interlock | Modbus 300041 bit 13; not polled by default | Read | ||
| BI | 306 | Boiler13Status2 Main Valve | Modbus 300041 bit 15; not polled by default | Read | ||
| BI | 307 | Boiler14Status1 Blower Running | Modbus 300042 bit 1; not polled by default | Read | ||
| BI | 308 | Boiler14Status1 Ignition Alarm | Modbus 300042 bit 2; not polled by default | Read | ||
| BI | 309 | Boiler14Status1 High Limit | Modbus 300042 bit 4; not polled by default | Read | ||
| BI | 310 | Boiler14Status1 Software Operator | Modbus 300042 bit 7; not polled by default | Read | ||
| BI | 311 | Boiler14Status1 Header Sensor not detected | Modbus 300042 bit 8; not polled by default | Read | ||
| BI | 312 | Boiler14Status1 Supply Sensor not detected | Modbus 300042 bit 9; not polled by default | Read | ||
| BI | 313 | Boiler14Status1 Return Sensor not detected | Modbus 300042 bit 10; not polled by default | Read | ||
| BI | 314 | Boiler14Status1 Outside Sensor not detected | Modbus 300042 bit 11; not polled by default | Read | ||
| BI | 315 | Boiler14Status1 Combustion Air Damper | Modbus 300042 bit 13; not polled by default | Read | ||
| BI | 316 | Boiler14Status1 Master Boiler | Modbus 300042 bit 14; not polled by default | Read | ||
| BI | 317 | Boiler14Status1 Boiler Detected | Modbus 300042 bit 15; not polled by default | Read | ||
| BI | 318 | Boiler14Status2 Disabled | Modbus 300043 bit 0; not polled by default | Read | ||
| BI | 319 | Boiler14Status2 Heat Demand | Modbus 300043 bit 1; not polled by default | Read | ||
| BI | 320 | Boiler14Status2 Alarm | Modbus 300043 bit 2; not polled by default | Read | ||
| BI | 321 | Boiler14Status2 Failed | Modbus 300043 bit 3; not polled by default | Read | ||
| BI | 322 | Boiler14Status2 Member Error | Modbus 300043 bit 4; not polled by default | Read | ||
| BI | 323 | Boiler14Status2 Boiler Running | Modbus 300043 bit 5; not polled by default | Read | ||
| BI | 324 | Boiler14Status2 Pump Running | Modbus 300043 bit 6; not polled by default | Read | ||
| BI | 325 | Boiler14Status2 Spare 4 (User) Interlock | Modbus 300043 bit 11; not polled by default | Read | ||
| BI | 326 | Boiler14Status2 Water Prove (Flow) Interlock | Modbus 300043 bit 13; not polled by default | Read | ||
| BI | 327 | Boiler14Status2 Main Valve | Modbus 300043 bit 15; not polled by default | Read | ||
| BI | 328 | Boiler15Status1 Blower Running | Modbus 300044 bit 1; not polled by default | Read | ||
| BI | 329 | Boiler15Status1 Ignition Alarm | Modbus 300044 bit 2; not polled by default | Read | ||
| BI | 330 | Boiler15Status1 High Limit | Modbus 300044 bit 4; not polled by default | Read | ||
| BI | 331 | Boiler15Status1 Software Operator | Modbus 300044 bit 7; not polled by default | Read | ||
| BI | 332 | Boiler15Status1 Header Sensor not detected | Modbus 300044 bit 8; not polled by default | Read | ||
| BI | 333 | Boiler15Status1 Supply Sensor not detected | Modbus 300044 bit 9; not polled by default | Read | ||
| BI | 334 | Boiler15Status1 Return Sensor not detected | Modbus 300044 bit 10; not polled by default | Read | ||
| BI | 335 | Boiler15Status1 Outside Sensor not detected | Modbus 300044 bit 11; not polled by default | Read | ||
| BI | 336 | Boiler15Status1 Combustion Air Damper | Modbus 300044 bit 13; not polled by default | Read | ||
| BI | 337 | Boiler15Status1 Master Boiler | Modbus 300044 bit 14; not polled by default | Read | ||
| BI | 338 | Boiler15Status1 Boiler Detected | Modbus 300044 bit 15; not polled by default | Read | ||
| BI | 339 | Boiler15Status2 Disabled | Modbus 300045 bit 0; not polled by default | Read | ||
| BI | 340 | Boiler15Status2 Heat Demand | Modbus 300045 bit 1; not polled by default | Read | ||
| BI | 341 | Boiler15Status2 Alarm | Modbus 300045 bit 2; not polled by default | Read | ||
| BI | 342 | Boiler15Status2 Failed | Modbus 300045 bit 3; not polled by default | Read | ||
| BI | 343 | Boiler15Status2 Member Error | Modbus 300045 bit 4; not polled by default | Read | ||
| BI | 344 | Boiler15Status2 Boiler Running | Modbus 300045 bit 5; not polled by default | Read | ||
| BI | 345 | Boiler15Status2 Pump Running | Modbus 300045 bit 6; not polled by default | Read | ||
| BI | 346 | Boiler15Status2 Spare 4 (User) Interlock | Modbus 300045 bit 11; not polled by default | Read | ||
| BI | 347 | Boiler15Status2 Water Prove (Flow) Interlock | Modbus 300045 bit 13; not polled by default | Read | ||
| BI | 348 | Boiler15Status2 Main Valve | Modbus 300045 bit 15; not polled by default | Read | ||
| BI | 349 | Boiler16Status1 Blower Running | Modbus 300046 bit 1; not polled by default | Read | ||
| BI | 350 | Boiler16Status1 Ignition Alarm | Modbus 300046 bit 2; not polled by default | Read | ||
| BI | 351 | Boiler16Status1 High Limit | Modbus 300046 bit 4; not polled by default | Read | ||
| BI | 352 | Boiler16Status1 Software Operator | Modbus 300046 bit 7; not polled by default | Read | ||
| BI | 353 | Boiler16Status1 Header Sensor not detected | Modbus 300046 bit 8; not polled by default | Read | ||
| BI | 354 | Boiler16Status1 Supply Sensor not detected | Modbus 300046 bit 9; not polled by default | Read | ||
| BI | 355 | Boiler16Status1 Return Sensor not detected | Modbus 300046 bit 10; not polled by default | Read | ||
| BI | 356 | Boiler16Status1 Outside Sensor not detected | Modbus 300046 bit 11; not polled by default | Read | ||
| BI | 357 | Boiler16Status1 Combustion Air Damper | Modbus 300046 bit 13; not polled by default | Read | ||
| BI | 358 | Boiler16Status1 Master Boiler | Modbus 300046 bit 14; not polled by default | Read | ||
| BI | 359 | Boiler16Status1 Boiler Detected | Modbus 300046 bit 15; not polled by default | Read | ||
| BI | 360 | Boiler16Status2 Disabled | Modbus 300047 bit 0; not polled by default | Read | ||
| BI | 361 | Boiler16Status2 Heat Demand | Modbus 300047 bit 1; not polled by default | Read | ||
| BI | 362 | Boiler16Status2 Alarm | Modbus 300047 bit 2; not polled by default | Read | ||
| BI | 363 | Boiler16Status2 Failed | Modbus 300047 bit 3; not polled by default | Read | ||
| BI | 364 | Boiler16Status2 Member Error | Modbus 300047 bit 4; not polled by default | Read | ||
| BI | 365 | Boiler16Status2 Boiler Running | Modbus 300047 bit 5; not polled by default | Read | ||
| BI | 366 | Boiler16Status2 Pump Running | Modbus 300047 bit 6; not polled by default | Read | ||
| BI | 367 | Boiler16Status2 Spare 4 (User) Interlock | Modbus 300047 bit 11; not polled by default | Read | ||
| BI | 368 | Boiler16Status2 Water Prove (Flow) Interlock | Modbus 300047 bit 13; not polled by default | Read | ||
| BI | 369 | Boiler16Status2 Main Valve | Modbus 300047 bit 15; not polled by default | Read | ||
| AI | 370 | Boiler01Runtime | Modbus 300048 | s | Read | |
| AI | 371 | Boiler02Runtime | Modbus 300050; not polled by default | s | Read | |
| AI | 372 | Boiler03Runtime | Modbus 300052; not polled by default | s | Read | |
| AI | 373 | Boiler04Runtime | Modbus 300054; not polled by default | s | Read | |
| AI | 374 | Boiler05Runtime | Modbus 300056; not polled by default | s | Read | |
| AI | 375 | Boiler06Runtime | Modbus 300058; not polled by default | s | Read | |
| AI | 376 | Boiler07Runtime | Modbus 300060; not polled by default | s | Read | |
| AI | 377 | Boiler08Runtime | Modbus 300062; not polled by default | s | Read | |
| AI | 378 | Boiler09Runtime | Modbus 300064; not polled by default | s | Read | |
| AI | 379 | Boiler10Runtime | Modbus 300066; not polled by default | s | Read | |
| AI | 380 | Boiler11Runtime | Modbus 300068; not polled by default | s | Read | |
| AI | 381 | Boiler12Runtime | Modbus 300070; not polled by default | s | Read | |
| AI | 382 | Boiler13Runtime | Modbus 300072; not polled by default | s | Read | |
| AI | 383 | Boiler14Runtime | Modbus 300074; not polled by default | s | Read | |
| AI | 384 | Boiler15Runtime | Modbus 300076; not polled by default | s | Read | |
| AI | 385 | Boiler16Runtime | Modbus 300078; not polled by default | s | Read | |
| BI | 386 | Boiler01Status3 AA High Fire Input | Modbus 300080 bit 0 | Read | ||
| BI | 387 | Boiler01Status3 Heat Demand Input (Local Override) | Modbus 300080 bit 1 | Read | ||
| BI | 388 | Boiler01Status3 4-20ma Remote Enable Input | Modbus 300080 bit 2 | Read | ||
| BI | 389 | Boiler02Status3 AA High Fire Input | Modbus 300081 bit 0; not polled by default | Read | ||
| BI | 390 | Boiler02Status3 Heat Demand Input (Local Override) | Modbus 300081 bit 1; not polled by default | Read | ||
| BI | 391 | Boiler02Status3 4-20ma Remote Enable Input | Modbus 300081 bit 2; not polled by default | Read | ||
| BI | 392 | Boiler03Status3 AA High Fire Input | Modbus 300082 bit 0; not polled by default | Read | ||
| BI | 393 | Boiler03Status3 Heat Demand Input (Local Override) | Modbus 300082 bit 1; not polled by default | Read | ||
| BI | 394 | Boiler03Status3 4-20ma Remote Enable Input | Modbus 300082 bit 2; not polled by default | Read | ||
| BI | 395 | Boiler04Status3 AA High Fire Input | Modbus 300083 bit 0; not polled by default | Read | ||
| BI | 396 | Boiler04Status3 Heat Demand Input (Local Override) | Modbus 300083 bit 1; not polled by default | Read | ||
| BI | 397 | Boiler04Status3 4-20ma Remote Enable Input | Modbus 300083 bit 2; not polled by default | Read | ||
| BI | 398 | Boiler05Status3 AA High Fire Input | Modbus 300084 bit 0; not polled by default | Read | ||
| BI | 399 | Boiler05Status3 Heat Demand Input (Local Override) | Modbus 300084 bit 1; not polled by default | Read | ||
| BI | 400 | Boiler05Status3 4-20ma Remote Enable Input | Modbus 300084 bit 2; not polled by default | Read | ||
| BI | 401 | Boiler06Status3 AA High Fire Input | Modbus 300085 bit 0; not polled by default | Read | ||
| BI | 402 | Boiler06Status3 Heat Demand Input (Local Override) | Modbus 300085 bit 1; not polled by default | Read | ||
| BI | 403 | Boiler06Status3 4-20ma Remote Enable Input | Modbus 300085 bit 2; not polled by default | Read | ||
| BI | 404 | Boiler07Status3 AA High Fire Input | Modbus 300086 bit 0; not polled by default | Read | ||
| BI | 405 | Boiler07Status3 Heat Demand Input (Local Override) | Modbus 300086 bit 1; not polled by default | Read | ||
| BI | 406 | Boiler07Status3 4-20ma Remote Enable Input | Modbus 300086 bit 2; not polled by default | Read | ||
| BI | 407 | Boiler08Status3 AA High Fire Input | Modbus 300087 bit 0; not polled by default | Read | ||
| BI | 408 | Boiler08Status3 Heat Demand Input (Local Override) | Modbus 300087 bit 1; not polled by default | Read | ||
| BI | 409 | Boiler08Status3 4-20ma Remote Enable Input | Modbus 300087 bit 2; not polled by default | Read | ||
| BI | 410 | Boiler09Status3 AA High Fire Input | Modbus 300088 bit 0; not polled by default | Read | ||
| BI | 411 | Boiler09Status3 Heat Demand Input (Local Override) | Modbus 300088 bit 1; not polled by default | Read | ||
| BI | 412 | Boiler09Status3 4-20ma Remote Enable Input | Modbus 300088 bit 2; not polled by default | Read | ||
| BI | 413 | Boiler10Status3 AA High Fire Input | Modbus 300089 bit 0; not polled by default | Read | ||
| BI | 414 | Boiler10Status3 Heat Demand Input (Local Override) | Modbus 300089 bit 1; not polled by default | Read | ||
| BI | 415 | Boiler10Status3 4-20ma Remote Enable Input | Modbus 300089 bit 2; not polled by default | Read | ||
| BI | 416 | Boiler11Status3 AA High Fire Input | Modbus 300090 bit 0; not polled by default | Read | ||
| BI | 417 | Boiler11Status3 Heat Demand Input (Local Override) | Modbus 300090 bit 1; not polled by default | Read | ||
| BI | 418 | Boiler11Status3 4-20ma Remote Enable Input | Modbus 300090 bit 2; not polled by default | Read | ||
| BI | 419 | Boiler12Status3 AA High Fire Input | Modbus 300091 bit 0; not polled by default | Read | ||
| BI | 420 | Boiler12Status3 Heat Demand Input (Local Override) | Modbus 300091 bit 1; not polled by default | Read | ||
| BI | 421 | Boiler12Status3 4-20ma Remote Enable Input | Modbus 300091 bit 2; not polled by default | Read | ||
| BI | 422 | Boiler13Status3 AA High Fire Input | Modbus 300092 bit 0; not polled by default | Read | ||
| BI | 423 | Boiler13Status3 Heat Demand Input (Local Override) | Modbus 300092 bit 1; not polled by default | Read | ||
| BI | 424 | Boiler13Status3 4-20ma Remote Enable Input | Modbus 300092 bit 2; not polled by default | Read | ||
| BI | 425 | Boiler14Status3 AA High Fire Input | Modbus 300093 bit 0; not polled by default | Read | ||
| BI | 426 | Boiler14Status3 Heat Demand Input (Local Override) | Modbus 300093 bit 1; not polled by default | Read | ||
| BI | 427 | Boiler14Status3 4-20ma Remote Enable Input | Modbus 300093 bit 2; not polled by default | Read | ||
| BI | 428 | Boiler15Status3 AA High Fire Input | Modbus 300094 bit 0; not polled by default | Read | ||
| BI | 429 | Boiler15Status3 Heat Demand Input (Local Override) | Modbus 300094 bit 1; not polled by default | Read | ||
| BI | 430 | Boiler15Status3 4-20ma Remote Enable Input | Modbus 300094 bit 2; not polled by default | Read | ||
| BI | 431 | Boiler16Status3 AA High Fire Input | Modbus 300095 bit 0; not polled by default | Read | ||
| BI | 432 | Boiler16Status3 Heat Demand Input (Local Override) | Modbus 300095 bit 1; not polled by default | Read | ||
| BI | 433 | Boiler16Status3 4-20ma Remote Enable Input | Modbus 300095 bit 2; not polled by default | Read | ||
| AI | 434 | Boiler01SupplyTemp | Modbus 300096 | °F | Read | |
| AI | 435 | Boiler02SupplyTemp | Modbus 300097; not polled by default | °F | Read | |
| AI | 436 | Boiler03SupplyTemp | Modbus 300098; not polled by default | °F | Read | |
| AI | 437 | Boiler04SupplyTemp | Modbus 300099; not polled by default | °F | Read | |
| AI | 438 | Boiler05SupplyTemp | Modbus 300100; not polled by default | °F | Read | |
| AI | 439 | Boiler06SupplyTemp | Modbus 300101; not polled by default | °F | Read | |
| AI | 440 | Boiler07SupplyTemp | Modbus 300102; not polled by default | °F | Read | |
| AI | 441 | Boiler08SupplyTemp | Modbus 300103; not polled by default | °F | Read | |
| AI | 442 | Boiler09SupplyTemp | Modbus 300104; not polled by default | °F | Read | |
| AI | 443 | Boiler10SupplyTemp | Modbus 300105; not polled by default | °F | Read | |
| AI | 444 | Boiler11SupplyTemp | Modbus 300106; not polled by default | °F | Read | |
| AI | 445 | Boiler12SupplyTemp | Modbus 300107; not polled by default | °F | Read | |
| AI | 446 | Boiler13SupplyTemp | Modbus 300108; not polled by default | °F | Read | |
| AI | 447 | Boiler14SupplyTemp | Modbus 300109; not polled by default | °F | Read | |
| AI | 448 | Boiler15SupplyTemp | Modbus 300110; not polled by default | °F | Read | |
| AI | 449 | Boiler16SupplyTemp | Modbus 300111; not polled by default | °F | Read | |
| AI | 450 | Boiler01ReturnTemp | Modbus 300112 | °F | Read | |
| AI | 451 | Boiler02ReturnTemp | Modbus 300113; not polled by default | °F | Read | |
| AI | 452 | Boiler03ReturnTemp | Modbus 300114; not polled by default | °F | Read | |
| AI | 453 | Boiler04ReturnTemp | Modbus 300115; not polled by default | °F | Read | |
| AI | 454 | Boiler05ReturnTemp | Modbus 300116; not polled by default | °F | Read | |
| AI | 455 | Boiler06ReturnTemp | Modbus 300117; not polled by default | °F | Read | |
| AI | 456 | Boiler07ReturnTemp | Modbus 300118; not polled by default | °F | Read | |
| AI | 457 | Boiler08ReturnTemp | Modbus 300119; not polled by default | °F | Read | |
| AI | 458 | Boiler09ReturnTemp | Modbus 300120; not polled by default | °F | Read | |
| AI | 459 | Boiler10ReturnTemp | Modbus 300121; not polled by default | °F | Read | |
| AI | 460 | Boiler11ReturnTemp | Modbus 300122; not polled by default | °F | Read | |
| AI | 461 | Boiler12ReturnTemp | Modbus 300123; not polled by default | °F | Read | |
| AI | 462 | Boiler13ReturnTemp | Modbus 300124; not polled by default | °F | Read | |
| AI | 463 | Boiler14ReturnTemp | Modbus 300125; not polled by default | °F | Read | |
| AI | 464 | Boiler15ReturnTemp | Modbus 300126; not polled by default | °F | Read | |
| AI | 465 | Boiler16ReturnTemp | Modbus 300127; not polled by default | °F | Read | |
| AI | 466 | Boiler01Cycles | Modbus 300128 | Read | ||
| AI | 467 | Boiler02Cycles | Modbus 300130; not polled by default | Read | ||
| AI | 468 | Boiler03Cycles | Modbus 300132; not polled by default | Read | ||
| AI | 469 | Boiler04Cycles | Modbus 300134; not polled by default | Read | ||
| AI | 470 | Boiler05Cycles | Modbus 300136; not polled by default | Read | ||
| AI | 471 | Boiler06Cycles | Modbus 300138; not polled by default | Read | ||
| AI | 472 | Boiler07Cycles | Modbus 300140; not polled by default | Read | ||
| AI | 473 | Boiler08Cycles | Modbus 300142; not polled by default | Read | ||
| AI | 474 | Boiler09Cycles | Modbus 300144; not polled by default | Read | ||
| AI | 475 | Boiler10Cycles | Modbus 300146; not polled by default | Read | ||
| AI | 476 | Boiler11Cycles | Modbus 300148; not polled by default | Read | ||
| AI | 477 | Boiler12Cycles | Modbus 300150; not polled by default | Read | ||
| AI | 478 | Boiler13Cycles | Modbus 300152; not polled by default | Read | ||
| AI | 479 | Boiler14Cycles | Modbus 300154; not polled by default | Read | ||
| AI | 480 | Boiler15Cycles | Modbus 300156; not polled by default | Read | ||
| AI | 481 | Boiler16Cycles | Modbus 300158; not polled by default | Read | ||
| BI | 482 | Boiler01Status4 DHW Sensor Enabled | Modbus 300160 bit 0 | Read | ||
| BI | 483 | Boiler01Status4 Damper Prove | Modbus 300160 bit 1 | Read | ||
| BI | 484 | Boiler01Status4 Blower Fault | Modbus 300160 bit 3 | Read | ||
| BI | 485 | Boiler01Status4 Blocked Inlet | Modbus 300160 bit 4 | Read | ||
| BI | 486 | Boiler01Status4 Blocked Flue | Modbus 300160 bit 5 | Read | ||
| BI | 487 | Boiler01Status4 DHW Input | Modbus 300160 bit 6 | Read | ||
| BI | 488 | Boiler01Status4 Low Fire Input | Modbus 300160 bit 7 | Read | ||
| BI | 489 | Boiler01Status4 DHW Fault | Modbus 300160 bit 8 | Read | ||
| BI | 490 | Boiler01Status4 DHW Sensor not detected | Modbus 300160 bit 9 | Read | ||
| BI | 491 | Boiler01Status4 Operating Limit Clamp | Modbus 300160 bit 11 | Read | ||
| BI | 492 | Boiler02Status4 DHW Sensor Enabled | Modbus 300161 bit 0; not polled by default | Read | ||
| BI | 493 | Boiler02Status4 Damper Prove | Modbus 300161 bit 1; not polled by default | Read | ||
| BI | 494 | Boiler02Status4 Blower Fault | Modbus 300161 bit 3; not polled by default | Read | ||
| BI | 495 | Boiler02Status4 Blocked Inlet | Modbus 300161 bit 4; not polled by default | Read | ||
| BI | 496 | Boiler02Status4 Blocked Flue | Modbus 300161 bit 5; not polled by default | Read | ||
| BI | 497 | Boiler02Status4 DHW Input | Modbus 300161 bit 6; not polled by default | Read | ||
| BI | 498 | Boiler02Status4 Low Fire Input | Modbus 300161 bit 7; not polled by default | Read | ||
| BI | 499 | Boiler02Status4 DHW Fault | Modbus 300161 bit 8; not polled by default | Read | ||
| BI | 500 | Boiler02Status4 DHW Sensor not detected | Modbus 300161 bit 9; not polled by default | Read | ||
| BI | 501 | Boiler02Status4 Operating Limit Clamp | Modbus 300161 bit 11; not polled by default | Read | ||
| BI | 502 | Boiler03Status4 DHW Sensor Enabled | Modbus 300162 bit 0; not polled by default | Read | ||
| BI | 503 | Boiler03Status4 Damper Prove | Modbus 300162 bit 1; not polled by default | Read | ||
| BI | 504 | Boiler03Status4 Blower Fault | Modbus 300162 bit 3; not polled by default | Read | ||
| BI | 505 | Boiler03Status4 Blocked Inlet | Modbus 300162 bit 4; not polled by default | Read | ||
| BI | 506 | Boiler03Status4 Blocked Flue | Modbus 300162 bit 5; not polled by default | Read | ||
| BI | 507 | Boiler03Status4 DHW Input | Modbus 300162 bit 6; not polled by default | Read | ||
| BI | 508 | Boiler03Status4 Low Fire Input | Modbus 300162 bit 7; not polled by default | Read | ||
| BI | 509 | Boiler03Status4 DHW Fault | Modbus 300162 bit 8; not polled by default | Read | ||
| BI | 510 | Boiler03Status4 DHW Sensor not detected | Modbus 300162 bit 9; not polled by default | Read | ||
| BI | 511 | Boiler03Status4 Operating Limit Clamp | Modbus 300162 bit 11; not polled by default | Read | ||
| BI | 512 | Boiler04Status4 DHW Sensor Enabled | Modbus 300163 bit 0; not polled by default | Read | ||
| BI | 513 | Boiler04Status4 Damper Prove | Modbus 300163 bit 1; not polled by default | Read | ||
| BI | 514 | Boiler04Status4 Blower Fault | Modbus 300163 bit 3; not polled by default | Read | ||
| BI | 515 | Boiler04Status4 Blocked Inlet | Modbus 300163 bit 4; not polled by default | Read | ||
| BI | 516 | Boiler04Status4 Blocked Flue | Modbus 300163 bit 5; not polled by default | Read | ||
| BI | 517 | Boiler04Status4 DHW Input | Modbus 300163 bit 6; not polled by default | Read | ||
| BI | 518 | Boiler04Status4 Low Fire Input | Modbus 300163 bit 7; not polled by default | Read | ||
| BI | 519 | Boiler04Status4 DHW Fault | Modbus 300163 bit 8; not polled by default | Read | ||
| BI | 520 | Boiler04Status4 DHW Sensor not detected | Modbus 300163 bit 9; not polled by default | Read | ||
| BI | 521 | Boiler04Status4 Operating Limit Clamp | Modbus 300163 bit 11; not polled by default | Read | ||
| BI | 522 | Boiler05Status4 DHW Sensor Enabled | Modbus 300164 bit 0; not polled by default | Read | ||
| BI | 523 | Boiler05Status4 Damper Prove | Modbus 300164 bit 1; not polled by default | Read | ||
| BI | 524 | Boiler05Status4 Blower Fault | Modbus 300164 bit 3; not polled by default | Read | ||
| BI | 525 | Boiler05Status4 Blocked Inlet | Modbus 300164 bit 4; not polled by default | Read | ||
| BI | 526 | Boiler05Status4 Blocked Flue | Modbus 300164 bit 5; not polled by default | Read | ||
| BI | 527 | Boiler05Status4 DHW Input | Modbus 300164 bit 6; not polled by default | Read | ||
| BI | 528 | Boiler05Status4 Low Fire Input | Modbus 300164 bit 7; not polled by default | Read | ||
| BI | 529 | Boiler05Status4 DHW Fault | Modbus 300164 bit 8; not polled by default | Read | ||
| BI | 530 | Boiler05Status4 DHW Sensor not detected | Modbus 300164 bit 9; not polled by default | Read | ||
| BI | 531 | Boiler05Status4 Operating Limit Clamp | Modbus 300164 bit 11; not polled by default | Read | ||
| BI | 532 | Boiler06Status4 DHW Sensor Enabled | Modbus 300165 bit 0; not polled by default | Read | ||
| BI | 533 | Boiler06Status4 Damper Prove | Modbus 300165 bit 1; not polled by default | Read | ||
| BI | 534 | Boiler06Status4 Blower Fault | Modbus 300165 bit 3; not polled by default | Read | ||
| BI | 535 | Boiler06Status4 Blocked Inlet | Modbus 300165 bit 4; not polled by default | Read | ||
| BI | 536 | Boiler06Status4 Blocked Flue | Modbus 300165 bit 5; not polled by default | Read | ||
| BI | 537 | Boiler06Status4 DHW Input | Modbus 300165 bit 6; not polled by default | Read | ||
| BI | 538 | Boiler06Status4 Low Fire Input | Modbus 300165 bit 7; not polled by default | Read | ||
| BI | 539 | Boiler06Status4 DHW Fault | Modbus 300165 bit 8; not polled by default | Read | ||
| BI | 540 | Boiler06Status4 DHW Sensor not detected | Modbus 300165 bit 9; not polled by default | Read | ||
| BI | 541 | Boiler06Status4 Operating Limit Clamp | Modbus 300165 bit 11; not polled by default | Read | ||
| BI | 542 | Boiler07Status4 DHW Sensor Enabled | Modbus 300166 bit 0; not polled by default | Read | ||
| BI | 543 | Boiler07Status4 Damper Prove | Modbus 300166 bit 1; not polled by default | Read | ||
| BI | 544 | Boiler07Status4 Blower Fault | Modbus 300166 bit 3; not polled by default | Read | ||
| BI | 545 | Boiler07Status4 Blocked Inlet | Modbus 300166 bit 4; not polled by default | Read | ||
| BI | 546 | Boiler07Status4 Blocked Flue | Modbus 300166 bit 5; not polled by default | Read | ||
| BI | 547 | Boiler07Status4 DHW Input | Modbus 300166 bit 6; not polled by default | Read | ||
| BI | 548 | Boiler07Status4 Low Fire Input | Modbus 300166 bit 7; not polled by default | Read | ||
| BI | 549 | Boiler07Status4 DHW Fault | Modbus 300166 bit 8; not polled by default | Read | ||
| BI | 550 | Boiler07Status4 DHW Sensor not detected | Modbus 300166 bit 9; not polled by default | Read | ||
| BI | 551 | Boiler07Status4 Operating Limit Clamp | Modbus 300166 bit 11; not polled by default | Read | ||
| BI | 552 | Boiler08Status4 DHW Sensor Enabled | Modbus 300167 bit 0; not polled by default | Read | ||
| BI | 553 | Boiler08Status4 Damper Prove | Modbus 300167 bit 1; not polled by default | Read | ||
| BI | 554 | Boiler08Status4 Blower Fault | Modbus 300167 bit 3; not polled by default | Read | ||
| BI | 555 | Boiler08Status4 Blocked Inlet | Modbus 300167 bit 4; not polled by default | Read | ||
| BI | 556 | Boiler08Status4 Blocked Flue | Modbus 300167 bit 5; not polled by default | Read | ||
| BI | 557 | Boiler08Status4 DHW Input | Modbus 300167 bit 6; not polled by default | Read | ||
| BI | 558 | Boiler08Status4 Low Fire Input | Modbus 300167 bit 7; not polled by default | Read | ||
| BI | 559 | Boiler08Status4 DHW Fault | Modbus 300167 bit 8; not polled by default | Read | ||
| BI | 560 | Boiler08Status4 DHW Sensor not detected | Modbus 300167 bit 9; not polled by default | Read | ||
| BI | 561 | Boiler08Status4 Operating Limit Clamp | Modbus 300167 bit 11; not polled by default | Read | ||
| BI | 562 | Boiler09Status4 DHW Sensor Enabled | Modbus 300168 bit 0; not polled by default | Read | ||
| BI | 563 | Boiler09Status4 Damper Prove | Modbus 300168 bit 1; not polled by default | Read | ||
| BI | 564 | Boiler09Status4 Blower Fault | Modbus 300168 bit 3; not polled by default | Read | ||
| BI | 565 | Boiler09Status4 Blocked Inlet | Modbus 300168 bit 4; not polled by default | Read | ||
| BI | 566 | Boiler09Status4 Blocked Flue | Modbus 300168 bit 5; not polled by default | Read | ||
| BI | 567 | Boiler09Status4 DHW Input | Modbus 300168 bit 6; not polled by default | Read | ||
| BI | 568 | Boiler09Status4 Low Fire Input | Modbus 300168 bit 7; not polled by default | Read | ||
| BI | 569 | Boiler09Status4 DHW Fault | Modbus 300168 bit 8; not polled by default | Read | ||
| BI | 570 | Boiler09Status4 DHW Sensor not detected | Modbus 300168 bit 9; not polled by default | Read | ||
| BI | 571 | Boiler09Status4 Operating Limit Clamp | Modbus 300168 bit 11; not polled by default | Read | ||
| BI | 572 | Boiler10Status4 DHW Sensor Enabled | Modbus 300169 bit 0; not polled by default | Read | ||
| BI | 573 | Boiler10Status4 Damper Prove | Modbus 300169 bit 1; not polled by default | Read | ||
| BI | 574 | Boiler10Status4 Blower Fault | Modbus 300169 bit 3; not polled by default | Read | ||
| BI | 575 | Boiler10Status4 Blocked Inlet | Modbus 300169 bit 4; not polled by default | Read | ||
| BI | 576 | Boiler10Status4 Blocked Flue | Modbus 300169 bit 5; not polled by default | Read | ||
| BI | 577 | Boiler10Status4 DHW Input | Modbus 300169 bit 6; not polled by default | Read | ||
| BI | 578 | Boiler10Status4 Low Fire Input | Modbus 300169 bit 7; not polled by default | Read | ||
| BI | 579 | Boiler10Status4 DHW Fault | Modbus 300169 bit 8; not polled by default | Read | ||
| BI | 580 | Boiler10Status4 DHW Sensor not detected | Modbus 300169 bit 9; not polled by default | Read | ||
| BI | 581 | Boiler10Status4 Operating Limit Clamp | Modbus 300169 bit 11; not polled by default | Read | ||
| BI | 582 | Boiler11Status4 DHW Sensor Enabled | Modbus 300170 bit 0; not polled by default | Read | ||
| BI | 583 | Boiler11Status4 Damper Prove | Modbus 300170 bit 1; not polled by default | Read | ||
| BI | 584 | Boiler11Status4 Blower Fault | Modbus 300170 bit 3; not polled by default | Read | ||
| BI | 585 | Boiler11Status4 Blocked Inlet | Modbus 300170 bit 4; not polled by default | Read | ||
| BI | 586 | Boiler11Status4 Blocked Flue | Modbus 300170 bit 5; not polled by default | Read | ||
| BI | 587 | Boiler11Status4 DHW Input | Modbus 300170 bit 6; not polled by default | Read | ||
| BI | 588 | Boiler11Status4 Low Fire Input | Modbus 300170 bit 7; not polled by default | Read | ||
| BI | 589 | Boiler11Status4 DHW Fault | Modbus 300170 bit 8; not polled by default | Read | ||
| BI | 590 | Boiler11Status4 DHW Sensor not detected | Modbus 300170 bit 9; not polled by default | Read | ||
| BI | 591 | Boiler11Status4 Operating Limit Clamp | Modbus 300170 bit 11; not polled by default | Read | ||
| BI | 592 | Boiler12Status4 DHW Sensor Enabled | Modbus 300171 bit 0; not polled by default | Read | ||
| BI | 593 | Boiler12Status4 Damper Prove | Modbus 300171 bit 1; not polled by default | Read | ||
| BI | 594 | Boiler12Status4 Blower Fault | Modbus 300171 bit 3; not polled by default | Read | ||
| BI | 595 | Boiler12Status4 Blocked Inlet | Modbus 300171 bit 4; not polled by default | Read | ||
| BI | 596 | Boiler12Status4 Blocked Flue | Modbus 300171 bit 5; not polled by default | Read | ||
| BI | 597 | Boiler12Status4 DHW Input | Modbus 300171 bit 6; not polled by default | Read | ||
| BI | 598 | Boiler12Status4 Low Fire Input | Modbus 300171 bit 7; not polled by default | Read | ||
| BI | 599 | Boiler12Status4 DHW Fault | Modbus 300171 bit 8; not polled by default | Read | ||
| BI | 600 | Boiler12Status4 DHW Sensor not detected | Modbus 300171 bit 9; not polled by default | Read | ||
| BI | 601 | Boiler12Status4 Operating Limit Clamp | Modbus 300171 bit 11; not polled by default | Read | ||
| BI | 602 | Boiler13Status4 DHW Sensor Enabled | Modbus 300172 bit 0; not polled by default | Read | ||
| BI | 603 | Boiler13Status4 Damper Prove | Modbus 300172 bit 1; not polled by default | Read | ||
| BI | 604 | Boiler13Status4 Blower Fault | Modbus 300172 bit 3; not polled by default | Read | ||
| BI | 605 | Boiler13Status4 Blocked Inlet | Modbus 300172 bit 4; not polled by default | Read | ||
| BI | 606 | Boiler13Status4 Blocked Flue | Modbus 300172 bit 5; not polled by default | Read | ||
| BI | 607 | Boiler13Status4 DHW Input | Modbus 300172 bit 6; not polled by default | Read | ||
| BI | 608 | Boiler13Status4 Low Fire Input | Modbus 300172 bit 7; not polled by default | Read | ||
| BI | 609 | Boiler13Status4 DHW Fault | Modbus 300172 bit 8; not polled by default | Read | ||
| BI | 610 | Boiler13Status4 DHW Sensor not detected | Modbus 300172 bit 9; not polled by default | Read | ||
| BI | 611 | Boiler13Status4 Operating Limit Clamp | Modbus 300172 bit 11; not polled by default | Read | ||
| BI | 612 | Boiler14Status4 DHW Sensor Enabled | Modbus 300173 bit 0; not polled by default | Read | ||
| BI | 613 | Boiler14Status4 Damper Prove | Modbus 300173 bit 1; not polled by default | Read | ||
| BI | 614 | Boiler14Status4 Blower Fault | Modbus 300173 bit 3; not polled by default | Read | ||
| BI | 615 | Boiler14Status4 Blocked Inlet | Modbus 300173 bit 4; not polled by default | Read | ||
| BI | 616 | Boiler14Status4 Blocked Flue | Modbus 300173 bit 5; not polled by default | Read | ||
| BI | 617 | Boiler14Status4 DHW Input | Modbus 300173 bit 6; not polled by default | Read | ||
| BI | 618 | Boiler14Status4 Low Fire Input | Modbus 300173 bit 7; not polled by default | Read | ||
| BI | 619 | Boiler14Status4 DHW Fault | Modbus 300173 bit 8; not polled by default | Read | ||
| BI | 620 | Boiler14Status4 DHW Sensor not detected | Modbus 300173 bit 9; not polled by default | Read | ||
| BI | 621 | Boiler14Status4 Operating Limit Clamp | Modbus 300173 bit 11; not polled by default | Read | ||
| BI | 622 | Boiler15Status4 DHW Sensor Enabled | Modbus 300174 bit 0; not polled by default | Read | ||
| BI | 623 | Boiler15Status4 Damper Prove | Modbus 300174 bit 1; not polled by default | Read | ||
| BI | 624 | Boiler15Status4 Blower Fault | Modbus 300174 bit 3; not polled by default | Read | ||
| BI | 625 | Boiler15Status4 Blocked Inlet | Modbus 300174 bit 4; not polled by default | Read | ||
| BI | 626 | Boiler15Status4 Blocked Flue | Modbus 300174 bit 5; not polled by default | Read | ||
| BI | 627 | Boiler15Status4 DHW Input | Modbus 300174 bit 6; not polled by default | Read | ||
| BI | 628 | Boiler15Status4 Low Fire Input | Modbus 300174 bit 7; not polled by default | Read | ||
| BI | 629 | Boiler15Status4 DHW Fault | Modbus 300174 bit 8; not polled by default | Read | ||
| BI | 630 | Boiler15Status4 DHW Sensor not detected | Modbus 300174 bit 9; not polled by default | Read | ||
| BI | 631 | Boiler15Status4 Operating Limit Clamp | Modbus 300174 bit 11; not polled by default | Read | ||
| BI | 632 | Boiler16Status4 DHW Sensor Enabled | Modbus 300175 bit 0; not polled by default | Read | ||
| BI | 633 | Boiler16Status4 Damper Prove | Modbus 300175 bit 1; not polled by default | Read | ||
| BI | 634 | Boiler16Status4 Blower Fault | Modbus 300175 bit 3; not polled by default | Read | ||
| BI | 635 | Boiler16Status4 Blocked Inlet | Modbus 300175 bit 4; not polled by default | Read | ||
| BI | 636 | Boiler16Status4 Blocked Flue | Modbus 300175 bit 5; not polled by default | Read | ||
| BI | 637 | Boiler16Status4 DHW Input | Modbus 300175 bit 6; not polled by default | Read | ||
| BI | 638 | Boiler16Status4 Low Fire Input | Modbus 300175 bit 7; not polled by default | Read | ||
| BI | 639 | Boiler16Status4 DHW Fault | Modbus 300175 bit 8; not polled by default | Read | ||
| BI | 640 | Boiler16Status4 DHW Sensor not detected | Modbus 300175 bit 9; not polled by default | Read | ||
| BI | 641 | Boiler16Status4 Operating Limit Clamp | Modbus 300175 bit 11; not polled by default | Read | ||
| AI | 642 | Boiler01DHWTemp | Modbus 300208 | °F | Read | |
| AI | 643 | Boiler02DHWTemp | Modbus 300209; not polled by default | °F | Read | |
| AI | 644 | Boiler03DHWTemp | Modbus 300210; not polled by default | °F | Read | |
| AI | 645 | Boiler04DHWTemp | Modbus 300211; not polled by default | °F | Read | |
| AI | 646 | Boiler05DHWTemp | Modbus 300212; not polled by default | °F | Read | |
| AI | 647 | Boiler06DHWTemp | Modbus 300213; not polled by default | °F | Read | |
| AI | 648 | Boiler07DHWTemp | Modbus 300214; not polled by default | °F | Read | |
| AI | 649 | Boiler08DHWTemp | Modbus 300215; not polled by default | °F | Read | |
| AI | 650 | Boiler09DHWTemp | Modbus 300216; not polled by default | °F | Read | |
| AI | 651 | Boiler10DHWTemp | Modbus 300217; not polled by default | °F | Read | |
| AI | 652 | Boiler11DHWTemp | Modbus 300218; not polled by default | °F | Read | |
| AI | 653 | Boiler12DHWTemp | Modbus 300219; not polled by default | °F | Read | |
| AI | 654 | Boiler13DHWTemp | Modbus 300220; not polled by default | °F | Read | |
| AI | 655 | Boiler14DHWTemp | Modbus 300221; not polled by default | °F | Read | |
| AI | 656 | Boiler15DHWTemp | Modbus 300222; not polled by default | °F | Read | |
| AI | 657 | Boiler16DHWTemp | Modbus 300223; not polled by default | °F | Read | |
| AI | 658 | Boiler01Modulation | Modbus 300224 | Read | ||
| AI | 659 | Boiler02Modulation | Modbus 300225; not polled by default | Read | ||
| AI | 660 | Boiler03Modulation | Modbus 300226; not polled by default | Read | ||
| AI | 661 | Boiler04Modulation | Modbus 300227; not polled by default | Read | ||
| AI | 662 | Boiler05Modulation | Modbus 300228; not polled by default | Read | ||
| AI | 663 | Boiler06Modulation | Modbus 300229; not polled by default | Read | ||
| AI | 664 | Boiler07Modulation | Modbus 300230; not polled by default | Read | ||
| AI | 665 | Boiler08Modulation | Modbus 300231; not polled by default | Read | ||
| AI | 666 | Boiler09Modulation | Modbus 300232; not polled by default | Read | ||
| AI | 667 | Boiler10Modulation | Modbus 300233; not polled by default | Read | ||
| AI | 668 | Boiler11Modulation | Modbus 300234; not polled by default | Read | ||
| AI | 669 | Boiler12Modulation | Modbus 300235; not polled by default | Read | ||
| AI | 670 | Boiler13Modulation | Modbus 300236; not polled by default | Read | ||
| AI | 671 | Boiler14Modulation | Modbus 300237; not polled by default | Read | ||
| AI | 672 | Boiler15Modulation | Modbus 300238; not polled by default | Read | ||
| AI | 673 | Boiler16Modulation | Modbus 300239; not polled by default | Read | ||
| AI | 674 | OperatingSetpoint | Modbus 400240 | °F | Read |
No points match these filters.
Object ID lookup: Contemporary Controls BASgatewayLX Hydrotherm KN2/KN4 point IDs by name
AO1HeatDemandAO2SetpointTimerAO3SetpointAO4OAResetEnableAO5OARSetpointAO6OARHighWaterTempAO7OARHighAirTempAO8OARLowWaterTempAO9OARLowAirTempAO10SetMonthAO11SetDayAO12SetYearAO13SetHourAO14SetMinuteAO15SetSecondAO16SetWeekdayAO17SetClockAO18DHWSetpointAI19BoilersOnAI20ModulationAI21HeaderTempAI22SupplyTempAI23ReturnTempAI24OutsideTempAI25SparelAI26Spare2AI27MonthAI28DayAI29YearAI30HourAI31MinuteAI32SecondAI33WeekdayBI34Boiler01Status1 Blower RunningBI35Boiler01Status1 Ignition AlarmBI36Boiler01Status1 High LimitBI37Boiler01Status1 Software OperatorBI38Boiler01Status1 Header Sensor not detectedBI39Boiler01Status1 Supply Sensor not detectedBI40Boiler01Status1 Return Sensor not detectedBI41Boiler01Status1 Outside Sensor not detectedBI42Boiler01Status1 Combustion Air DamperBI43Boiler01Status1 Master BoilerBI44Boiler01Status1 Boiler DetectedBI45Boiler01Status2 DisabledBI46Boiler01Status2 Heat DemandBI47Boiler01Status2 AlarmBI48Boiler01Status2 FailedBI49Boiler01Status2 Member ErrorBI50Boiler01Status2 Boiler RunningBI51Boiler01Status2 Pump RunningBI52Boiler01Status2 Spare 4 (User) InterlockBI53Boiler01Status2 Water Prove (Flow) InterlockBI54Boiler01Status2 Main ValveBI55Boiler02Status1 Blower RunningBI56Boiler02Status1 Ignition AlarmBI57Boiler02Status1 High LimitBI58Boiler02Status1 Software OperatorBI59Boiler02Status1 Header Sensor not detectedBI60Boiler02Status1 Supply Sensor not detectedBI61Boiler02Status1 Return Sensor not detectedBI62Boiler02Status1 Outside Sensor not detectedBI63Boiler02Status1 Combustion Air DamperBI64Boiler02Status1 Master BoilerBI65Boiler02Status1 Boiler DetectedBI66Boiler02Status2 DisabledBI67Boiler02Status2 Heat DemandBI68Boiler02Status2 AlarmBI69Boiler02Status2 FailedBI70Boiler02Status2 Member ErrorBI71Boiler02Status2 Boiler RunningBI72Boiler02Status2 Pump RunningBI73Boiler02Status2 Spare 4 (User) InterlockBI74Boiler02Status2 Water Prove (Flow) InterlockBI75Boiler02Status2 Main ValveBI76Boiler03Status1 Blower RunningBI77Boiler03Status1 Ignition AlarmBI78Boiler03Status1 High LimitBI79Boiler03Status1 Software OperatorBI80Boiler03Status1 Header Sensor not detectedBI81Boiler03Status1 Supply Sensor not detectedBI82Boiler03Status1 Return Sensor not detectedBI83Boiler03Status1 Outside Sensor not detectedBI84Boiler03Status1 Combustion Air DamperBI85Boiler03Status1 Master BoilerBI86Boiler03Status1 Boiler DetectedBI87Boiler03Status2 DisabledBI88Boiler03Status2 Heat DemandBI89Boiler03Status2 AlarmBI90Boiler03Status2 FailedBI91Boiler03Status2 Member ErrorBI92Boiler03Status2 Boiler RunningBI93Boiler03Status2 Pump RunningBI94Boiler03Status2 Spare 4 (User) InterlockBI95Boiler03Status2 Water Prove (Flow) InterlockBI96Boiler03Status2 Main ValveBI97Boiler04Status1 Blower RunningBI98Boiler04Status1 Ignition AlarmBI99Boiler04Status1 High LimitBI100Boiler04Status1 Software OperatorBI101Boiler04Status1 Header Sensor not detectedBI102Boiler04Status1 Supply Sensor not detectedBI103Boiler04Status1 Return Sensor not detectedBI104Boiler04Status1 Outside Sensor not detectedBI105Boiler04Status1 Combustion Air DamperBI106Boiler04Status1 Master BoilerBI107Boiler04Status1 Boiler DetectedBI108Boiler04Status2 DisabledBI109Boiler04Status2 Heat DemandBI110Boiler04Status2 AlarmBI111Boiler04Status2 FailedBI112Boiler04Status2 Member ErrorBI113Boiler04Status2 Boiler RunningBI114Boiler04Status2 Pump RunningBI115Boiler04Status2 Spare 4 (User) InterlockBI116Boiler04Status2 Water Prove (Flow) InterlockBI117Boiler04Status2 Main ValveBI118Boiler05Status1 Blower RunningBI119Boiler05Status1 Ignition AlarmBI120Boiler05Status1 High LimitBI121Boiler05Status1 Software OperatorBI122Boiler05Status1 Header Sensor not detectedBI123Boiler05Status1 Supply Sensor not detectedBI124Boiler05Status1 Return Sensor not detectedBI125Boiler05Status1 Outside Sensor not detectedBI126Boiler05Status1 Combustion Air DamperBI127Boiler05Status1 Master BoilerBI128Boiler05Status1 Boiler DetectedBI129Boiler05Status2 DisabledBI130Boiler05Status2 Heat DemandBI131Boiler05Status2 AlarmBI132Boiler05Status2 FailedBI133Boiler05Status2 Member ErrorBI134Boiler05Status2 Boiler RunningBI135Boiler05Status2 Pump RunningBI136Boiler05Status2 Spare 4 (User) InterlockBI137Boiler05Status2 Water Prove (Flow) InterlockBI138Boiler05Status2 Main ValveBI139Boiler06Status1 Blower RunningBI140Boiler06Status1 Ignition AlarmBI141Boiler06Status1 High LimitBI142Boiler06Status1 Software OperatorBI143Boiler06Status1 Header Sensor not detectedBI144Boiler06Status1 Supply Sensor not detectedBI145Boiler06Status1 Return Sensor not detectedBI146Boiler06Status1 Outside Sensor not detectedBI147Boiler06Status1 Combustion Air DamperBI148Boiler06Status1 Master BoilerBI149Boiler06Status1 Boiler DetectedBI150Boiler06Status2 DisabledBI151Boiler06Status2 Heat DemandBI152Boiler06Status2 AlarmBI153Boiler06Status2 FailedBI154Boiler06Status2 Member ErrorBI155Boiler06Status2 Boiler RunningBI156Boiler06Status2 Pump RunningBI157Boiler06Status2 Spare 4 (User) InterlockBI158Boiler06Status2 Water Prove (Flow) InterlockBI159Boiler06Status2 Main ValveBI160Boiler07Status1 Blower RunningBI161Boiler07Status1 Ignition AlarmBI162Boiler07Status1 High LimitBI163Boiler07Status1 Software OperatorBI164Boiler07Status1 Header Sensor not detectedBI165Boiler07Status1 Supply Sensor not detectedBI166Boiler07Status1 Return Sensor not detectedBI167Boiler07Status1 Outside Sensor not detectedBI168Boiler07Status1 Combustion Air DamperBI169Boiler07Status1 Master BoilerBI170Boiler07Status1 Boiler DetectedBI171Boiler07Status2 DisabledBI172Boiler07Status2 Heat DemandBI173Boiler07Status2 AlarmBI174Boiler07Status2 FailedBI175Boiler07Status2 Member ErrorBI176Boiler07Status2 Boiler RunningBI177Boiler07Status2 Pump RunningBI178Boiler07Status2 Spare 4 (User) InterlockBI179Boiler07Status2 Water Prove (Flow) InterlockBI180Boiler07Status2 Main ValveBI181Boiler08Status1 Blower RunningBI182Boiler08Status1 Ignition AlarmBI183Boiler08Status1 High LimitBI184Boiler08Status1 Software OperatorBI185Boiler08Status1 Header Sensor not detectedBI186Boiler08Status1 Supply Sensor not detectedBI187Boiler08Status1 Return Sensor not detectedBI188Boiler08Status1 Outside Sensor not detectedBI189Boiler08Status1 Combustion Air DamperBI190Boiler08Status1 Master BoilerBI191Boiler08Status1 Boiler DetectedBI192Boiler08Status2 DisabledBI193Boiler08Status2 Heat DemandBI194Boiler08Status2 AlarmBI195Boiler08Status2 FailedBI196Boiler08Status2 Member ErrorBI197Boiler08Status2 Boiler RunningBI198Boiler08Status2 Pump RunningBI199Boiler08Status2 Spare 4 (User) InterlockBI200Boiler08Status2 Water Prove (Flow) InterlockBI201Boiler08Status2 Main ValveBI202Boiler09Status1 Blower RunningBI203Boiler09Status1 Ignition AlarmBI204Boiler09Status1 High LimitBI205Boiler09Status1 Software OperatorBI206Boiler09Status1 Header Sensor not detectedBI207Boiler09Status1 Supply Sensor not detectedBI208Boiler09Status1 Return Sensor not detectedBI209Boiler09Status1 Outside Sensor not detectedBI210Boiler09Status1 Combustion Air DamperBI211Boiler09Status1 Master BoilerBI212Boiler09Status1 Boiler DetectedBI213Boiler09Status2 DisabledBI214Boiler09Status2 Heat DemandBI215Boiler09Status2 AlarmBI216Boiler09Status2 FailedBI217Boiler09Status2 Member ErrorBI218Boiler09Status2 Boiler RunningBI219Boiler09Status2 Pump RunningBI220Boiler09Status2 Spare 4 (User) InterlockBI221Boiler09Status2 Water Prove (Flow) InterlockBI222Boiler09Status2 Main ValveBI223Boiler10Status1 Blower RunningBI224Boiler10Status1 Ignition AlarmBI225Boiler10Status1 High LimitBI226Boiler10Status1 Software OperatorBI227Boiler10Status1 Header Sensor not detectedBI228Boiler10Status1 Supply Sensor not detectedBI229Boiler10Status1 Return Sensor not detectedBI230Boiler10Status1 Outside Sensor not detectedBI231Boiler10Status1 Combustion Air DamperBI232Boiler10Status1 Master BoilerBI233Boiler10Status1 Boiler DetectedBI234Boiler10Status2 DisabledBI235Boiler10Status2 Heat DemandBI236Boiler10Status2 AlarmBI237Boiler10Status2 FailedBI238Boiler10Status2 Member ErrorBI239Boiler10Status2 Boiler RunningBI240Boiler10Status2 Pump RunningBI241Boiler10Status2 Spare 4 (User) InterlockBI242Boiler10Status2 Water Prove (Flow) InterlockBI243Boiler10Status2 Main ValveBI244Boiler11Status1 Blower RunningBI245Boiler11Status1 Ignition AlarmBI246Boiler11Status1 High LimitBI247Boiler11Status1 Software OperatorBI248Boiler11Status1 Header Sensor not detectedBI249Boiler11Status1 Supply Sensor not detectedBI250Boiler11Status1 Return Sensor not detectedBI251Boiler11Status1 Outside Sensor not detectedBI252Boiler11Status1 Combustion Air DamperBI253Boiler11Status1 Master BoilerBI254Boiler11Status1 Boiler DetectedBI255Boiler11Status2 DisabledBI256Boiler11Status2 Heat DemandBI257Boiler11Status2 AlarmBI258Boiler11Status2 FailedBI259Boiler11Status2 Member ErrorBI260Boiler11Status2 Boiler RunningBI261Boiler11Status2 Pump RunningBI262Boiler11Status2 Spare 4 (User) InterlockBI263Boiler11Status2 Water Prove (Flow) InterlockBI264Boiler11Status2 Main ValveBI265Boiler12Status1 Blower RunningBI266Boiler12Status1 Ignition AlarmBI267Boiler12Status1 High LimitBI268Boiler12Status1 Software OperatorBI269Boiler12Status1 Header Sensor not detectedBI270Boiler12Status1 Supply Sensor not detectedBI271Boiler12Status1 Return Sensor not detectedBI272Boiler12Status1 Outside Sensor not detectedBI273Boiler12Status1 Combustion Air DamperBI274Boiler12Status1 Master BoilerBI275Boiler12Status1 Boiler DetectedBI276Boiler12Status2 DisabledBI277Boiler12Status2 Heat DemandBI278Boiler12Status2 AlarmBI279Boiler12Status2 FailedBI280Boiler12Status2 Member ErrorBI281Boiler12Status2 Boiler RunningBI282Boiler12Status2 Pump RunningBI283Boiler12Status2 Spare 4 (User) InterlockBI284Boiler12Status2 Water Prove (Flow) InterlockBI285Boiler12Status2 Main ValveBI286Boiler13Status1 Blower RunningBI287Boiler13Status1 Ignition AlarmBI288Boiler13Status1 High LimitBI289Boiler13Status1 Software OperatorBI290Boiler13Status1 Header Sensor not detectedBI291Boiler13Status1 Supply Sensor not detectedBI292Boiler13Status1 Return Sensor not detectedBI293Boiler13Status1 Outside Sensor not detectedBI294Boiler13Status1 Combustion Air DamperBI295Boiler13Status1 Master BoilerBI296Boiler13Status1 Boiler DetectedBI297Boiler13Status2 DisabledBI298Boiler13Status2 Heat DemandBI299Boiler13Status2 AlarmBI300Boiler13Status2 FailedBI301Boiler13Status2 Member ErrorBI302Boiler13Status2 Boiler RunningBI303Boiler13Status2 Pump RunningBI304Boiler13Status2 Spare 4 (User) InterlockBI305Boiler13Status2 Water Prove (Flow) InterlockBI306Boiler13Status2 Main ValveBI307Boiler14Status1 Blower RunningBI308Boiler14Status1 Ignition AlarmBI309Boiler14Status1 High LimitBI310Boiler14Status1 Software OperatorBI311Boiler14Status1 Header Sensor not detectedBI312Boiler14Status1 Supply Sensor not detectedBI313Boiler14Status1 Return Sensor not detectedBI314Boiler14Status1 Outside Sensor not detectedBI315Boiler14Status1 Combustion Air DamperBI316Boiler14Status1 Master BoilerBI317Boiler14Status1 Boiler DetectedBI318Boiler14Status2 DisabledBI319Boiler14Status2 Heat DemandBI320Boiler14Status2 AlarmBI321Boiler14Status2 FailedBI322Boiler14Status2 Member ErrorBI323Boiler14Status2 Boiler RunningBI324Boiler14Status2 Pump RunningBI325Boiler14Status2 Spare 4 (User) InterlockBI326Boiler14Status2 Water Prove (Flow) InterlockBI327Boiler14Status2 Main ValveBI328Boiler15Status1 Blower RunningBI329Boiler15Status1 Ignition AlarmBI330Boiler15Status1 High LimitBI331Boiler15Status1 Software OperatorBI332Boiler15Status1 Header Sensor not detectedBI333Boiler15Status1 Supply Sensor not detectedBI334Boiler15Status1 Return Sensor not detectedBI335Boiler15Status1 Outside Sensor not detectedBI336Boiler15Status1 Combustion Air DamperBI337Boiler15Status1 Master BoilerBI338Boiler15Status1 Boiler DetectedBI339Boiler15Status2 DisabledBI340Boiler15Status2 Heat DemandBI341Boiler15Status2 AlarmBI342Boiler15Status2 FailedBI343Boiler15Status2 Member ErrorBI344Boiler15Status2 Boiler RunningBI345Boiler15Status2 Pump RunningBI346Boiler15Status2 Spare 4 (User) InterlockBI347Boiler15Status2 Water Prove (Flow) InterlockBI348Boiler15Status2 Main ValveBI349Boiler16Status1 Blower RunningBI350Boiler16Status1 Ignition AlarmBI351Boiler16Status1 High LimitBI352Boiler16Status1 Software OperatorBI353Boiler16Status1 Header Sensor not detectedBI354Boiler16Status1 Supply Sensor not detectedBI355Boiler16Status1 Return Sensor not detectedBI356Boiler16Status1 Outside Sensor not detectedBI357Boiler16Status1 Combustion Air DamperBI358Boiler16Status1 Master BoilerBI359Boiler16Status1 Boiler DetectedBI360Boiler16Status2 DisabledBI361Boiler16Status2 Heat DemandBI362Boiler16Status2 AlarmBI363Boiler16Status2 FailedBI364Boiler16Status2 Member ErrorBI365Boiler16Status2 Boiler RunningBI366Boiler16Status2 Pump RunningBI367Boiler16Status2 Spare 4 (User) InterlockBI368Boiler16Status2 Water Prove (Flow) InterlockBI369Boiler16Status2 Main ValveAI370Boiler01RuntimeAI371Boiler02RuntimeAI372Boiler03RuntimeAI373Boiler04RuntimeAI374Boiler05RuntimeAI375Boiler06RuntimeAI376Boiler07RuntimeAI377Boiler08RuntimeAI378Boiler09RuntimeAI379Boiler10RuntimeAI380Boiler11RuntimeAI381Boiler12RuntimeAI382Boiler13RuntimeAI383Boiler14RuntimeAI384Boiler15RuntimeAI385Boiler16RuntimeBI386Boiler01Status3 AA High Fire InputBI387Boiler01Status3 Heat Demand Input (Local Override)BI388Boiler01Status3 4-20ma Remote Enable InputBI389Boiler02Status3 AA High Fire InputBI390Boiler02Status3 Heat Demand Input (Local Override)BI391Boiler02Status3 4-20ma Remote Enable InputBI392Boiler03Status3 AA High Fire InputBI393Boiler03Status3 Heat Demand Input (Local Override)BI394Boiler03Status3 4-20ma Remote Enable InputBI395Boiler04Status3 AA High Fire InputBI396Boiler04Status3 Heat Demand Input (Local Override)BI397Boiler04Status3 4-20ma Remote Enable InputBI398Boiler05Status3 AA High Fire InputBI399Boiler05Status3 Heat Demand Input (Local Override)BI400Boiler05Status3 4-20ma Remote Enable InputBI401Boiler06Status3 AA High Fire InputBI402Boiler06Status3 Heat Demand Input (Local Override)BI403Boiler06Status3 4-20ma Remote Enable InputBI404Boiler07Status3 AA High Fire InputBI405Boiler07Status3 Heat Demand Input (Local Override)BI406Boiler07Status3 4-20ma Remote Enable InputBI407Boiler08Status3 AA High Fire InputBI408Boiler08Status3 Heat Demand Input (Local Override)BI409Boiler08Status3 4-20ma Remote Enable InputBI410Boiler09Status3 AA High Fire InputBI411Boiler09Status3 Heat Demand Input (Local Override)BI412Boiler09Status3 4-20ma Remote Enable InputBI413Boiler10Status3 AA High Fire InputBI414Boiler10Status3 Heat Demand Input (Local Override)BI415Boiler10Status3 4-20ma Remote Enable InputBI416Boiler11Status3 AA High Fire InputBI417Boiler11Status3 Heat Demand Input (Local Override)BI418Boiler11Status3 4-20ma Remote Enable InputBI419Boiler12Status3 AA High Fire InputBI420Boiler12Status3 Heat Demand Input (Local Override)BI421Boiler12Status3 4-20ma Remote Enable InputBI422Boiler13Status3 AA High Fire InputBI423Boiler13Status3 Heat Demand Input (Local Override)BI424Boiler13Status3 4-20ma Remote Enable InputBI425Boiler14Status3 AA High Fire InputBI426Boiler14Status3 Heat Demand Input (Local Override)BI427Boiler14Status3 4-20ma Remote Enable InputBI428Boiler15Status3 AA High Fire InputBI429Boiler15Status3 Heat Demand Input (Local Override)BI430Boiler15Status3 4-20ma Remote Enable InputBI431Boiler16Status3 AA High Fire InputBI432Boiler16Status3 Heat Demand Input (Local Override)BI433Boiler16Status3 4-20ma Remote Enable InputAI434Boiler01SupplyTempAI435Boiler02SupplyTempAI436Boiler03SupplyTempAI437Boiler04SupplyTempAI438Boiler05SupplyTempAI439Boiler06SupplyTempAI440Boiler07SupplyTempAI441Boiler08SupplyTempAI442Boiler09SupplyTempAI443Boiler10SupplyTempAI444Boiler11SupplyTempAI445Boiler12SupplyTempAI446Boiler13SupplyTempAI447Boiler14SupplyTempAI448Boiler15SupplyTempAI449Boiler16SupplyTempAI450Boiler01ReturnTempAI451Boiler02ReturnTempAI452Boiler03ReturnTempAI453Boiler04ReturnTempAI454Boiler05ReturnTempAI455Boiler06ReturnTempAI456Boiler07ReturnTempAI457Boiler08ReturnTempAI458Boiler09ReturnTempAI459Boiler10ReturnTempAI460Boiler11ReturnTempAI461Boiler12ReturnTempAI462Boiler13ReturnTempAI463Boiler14ReturnTempAI464Boiler15ReturnTempAI465Boiler16ReturnTempAI466Boiler01CyclesAI467Boiler02CyclesAI468Boiler03CyclesAI469Boiler04CyclesAI470Boiler05CyclesAI471Boiler06CyclesAI472Boiler07CyclesAI473Boiler08CyclesAI474Boiler09CyclesAI475Boiler10CyclesAI476Boiler11CyclesAI477Boiler12CyclesAI478Boiler13CyclesAI479Boiler14CyclesAI480Boiler15CyclesAI481Boiler16CyclesBI482Boiler01Status4 DHW Sensor EnabledBI483Boiler01Status4 Damper ProveBI484Boiler01Status4 Blower FaultBI485Boiler01Status4 Blocked InletBI486Boiler01Status4 Blocked FlueBI487Boiler01Status4 DHW InputBI488Boiler01Status4 Low Fire InputBI489Boiler01Status4 DHW FaultBI490Boiler01Status4 DHW Sensor not detectedBI491Boiler01Status4 Operating Limit ClampBI492Boiler02Status4 DHW Sensor EnabledBI493Boiler02Status4 Damper ProveBI494Boiler02Status4 Blower FaultBI495Boiler02Status4 Blocked InletBI496Boiler02Status4 Blocked FlueBI497Boiler02Status4 DHW InputBI498Boiler02Status4 Low Fire InputBI499Boiler02Status4 DHW FaultBI500Boiler02Status4 DHW Sensor not detectedBI501Boiler02Status4 Operating Limit ClampBI502Boiler03Status4 DHW Sensor EnabledBI503Boiler03Status4 Damper ProveBI504Boiler03Status4 Blower FaultBI505Boiler03Status4 Blocked InletBI506Boiler03Status4 Blocked FlueBI507Boiler03Status4 DHW InputBI508Boiler03Status4 Low Fire InputBI509Boiler03Status4 DHW FaultBI510Boiler03Status4 DHW Sensor not detectedBI511Boiler03Status4 Operating Limit ClampBI512Boiler04Status4 DHW Sensor EnabledBI513Boiler04Status4 Damper ProveBI514Boiler04Status4 Blower FaultBI515Boiler04Status4 Blocked InletBI516Boiler04Status4 Blocked FlueBI517Boiler04Status4 DHW InputBI518Boiler04Status4 Low Fire InputBI519Boiler04Status4 DHW FaultBI520Boiler04Status4 DHW Sensor not detectedBI521Boiler04Status4 Operating Limit ClampBI522Boiler05Status4 DHW Sensor EnabledBI523Boiler05Status4 Damper ProveBI524Boiler05Status4 Blower FaultBI525Boiler05Status4 Blocked InletBI526Boiler05Status4 Blocked FlueBI527Boiler05Status4 DHW InputBI528Boiler05Status4 Low Fire InputBI529Boiler05Status4 DHW FaultBI530Boiler05Status4 DHW Sensor not detectedBI531Boiler05Status4 Operating Limit ClampBI532Boiler06Status4 DHW Sensor EnabledBI533Boiler06Status4 Damper ProveBI534Boiler06Status4 Blower FaultBI535Boiler06Status4 Blocked InletBI536Boiler06Status4 Blocked FlueBI537Boiler06Status4 DHW InputBI538Boiler06Status4 Low Fire InputBI539Boiler06Status4 DHW FaultBI540Boiler06Status4 DHW Sensor not detectedBI541Boiler06Status4 Operating Limit ClampBI542Boiler07Status4 DHW Sensor EnabledBI543Boiler07Status4 Damper ProveBI544Boiler07Status4 Blower FaultBI545Boiler07Status4 Blocked InletBI546Boiler07Status4 Blocked FlueBI547Boiler07Status4 DHW InputBI548Boiler07Status4 Low Fire InputBI549Boiler07Status4 DHW FaultBI550Boiler07Status4 DHW Sensor not detectedBI551Boiler07Status4 Operating Limit ClampBI552Boiler08Status4 DHW Sensor EnabledBI553Boiler08Status4 Damper ProveBI554Boiler08Status4 Blower FaultBI555Boiler08Status4 Blocked InletBI556Boiler08Status4 Blocked FlueBI557Boiler08Status4 DHW InputBI558Boiler08Status4 Low Fire InputBI559Boiler08Status4 DHW FaultBI560Boiler08Status4 DHW Sensor not detectedBI561Boiler08Status4 Operating Limit ClampBI562Boiler09Status4 DHW Sensor EnabledBI563Boiler09Status4 Damper ProveBI564Boiler09Status4 Blower FaultBI565Boiler09Status4 Blocked InletBI566Boiler09Status4 Blocked FlueBI567Boiler09Status4 DHW InputBI568Boiler09Status4 Low Fire InputBI569Boiler09Status4 DHW FaultBI570Boiler09Status4 DHW Sensor not detectedBI571Boiler09Status4 Operating Limit ClampBI572Boiler10Status4 DHW Sensor EnabledBI573Boiler10Status4 Damper ProveBI574Boiler10Status4 Blower FaultBI575Boiler10Status4 Blocked InletBI576Boiler10Status4 Blocked FlueBI577Boiler10Status4 DHW InputBI578Boiler10Status4 Low Fire InputBI579Boiler10Status4 DHW FaultBI580Boiler10Status4 DHW Sensor not detectedBI581Boiler10Status4 Operating Limit ClampBI582Boiler11Status4 DHW Sensor EnabledBI583Boiler11Status4 Damper ProveBI584Boiler11Status4 Blower FaultBI585Boiler11Status4 Blocked InletBI586Boiler11Status4 Blocked FlueBI587Boiler11Status4 DHW InputBI588Boiler11Status4 Low Fire InputBI589Boiler11Status4 DHW FaultBI590Boiler11Status4 DHW Sensor not detectedBI591Boiler11Status4 Operating Limit ClampBI592Boiler12Status4 DHW Sensor EnabledBI593Boiler12Status4 Damper ProveBI594Boiler12Status4 Blower FaultBI595Boiler12Status4 Blocked InletBI596Boiler12Status4 Blocked FlueBI597Boiler12Status4 DHW InputBI598Boiler12Status4 Low Fire InputBI599Boiler12Status4 DHW FaultBI600Boiler12Status4 DHW Sensor not detectedBI601Boiler12Status4 Operating Limit ClampBI602Boiler13Status4 DHW Sensor EnabledBI603Boiler13Status4 Damper ProveBI604Boiler13Status4 Blower FaultBI605Boiler13Status4 Blocked InletBI606Boiler13Status4 Blocked FlueBI607Boiler13Status4 DHW InputBI608Boiler13Status4 Low Fire InputBI609Boiler13Status4 DHW FaultBI610Boiler13Status4 DHW Sensor not detectedBI611Boiler13Status4 Operating Limit ClampBI612Boiler14Status4 DHW Sensor EnabledBI613Boiler14Status4 Damper ProveBI614Boiler14Status4 Blower FaultBI615Boiler14Status4 Blocked InletBI616Boiler14Status4 Blocked FlueBI617Boiler14Status4 DHW InputBI618Boiler14Status4 Low Fire InputBI619Boiler14Status4 DHW FaultBI620Boiler14Status4 DHW Sensor not detectedBI621Boiler14Status4 Operating Limit ClampBI622Boiler15Status4 DHW Sensor EnabledBI623Boiler15Status4 Damper ProveBI624Boiler15Status4 Blower FaultBI625Boiler15Status4 Blocked InletBI626Boiler15Status4 Blocked FlueBI627Boiler15Status4 DHW InputBI628Boiler15Status4 Low Fire InputBI629Boiler15Status4 DHW FaultBI630Boiler15Status4 DHW Sensor not detectedBI631Boiler15Status4 Operating Limit ClampBI632Boiler16Status4 DHW Sensor EnabledBI633Boiler16Status4 Damper ProveBI634Boiler16Status4 Blower FaultBI635Boiler16Status4 Blocked InletBI636Boiler16Status4 Blocked FlueBI637Boiler16Status4 DHW InputBI638Boiler16Status4 Low Fire InputBI639Boiler16Status4 DHW FaultBI640Boiler16Status4 DHW Sensor not detectedBI641Boiler16Status4 Operating Limit ClampAI642Boiler01DHWTempAI643Boiler02DHWTempAI644Boiler03DHWTempAI645Boiler04DHWTempAI646Boiler05DHWTempAI647Boiler06DHWTempAI648Boiler07DHWTempAI649Boiler08DHWTempAI650Boiler09DHWTempAI651Boiler10DHWTempAI652Boiler11DHWTempAI653Boiler12DHWTempAI654Boiler13DHWTempAI655Boiler14DHWTempAI656Boiler15DHWTempAI657Boiler16DHWTempAI658Boiler01ModulationAI659Boiler02ModulationAI660Boiler03ModulationAI661Boiler04ModulationAI662Boiler05ModulationAI663Boiler06ModulationAI664Boiler07ModulationAI665Boiler08ModulationAI666Boiler09ModulationAI667Boiler10ModulationAI668Boiler11ModulationAI669Boiler12ModulationAI670Boiler13ModulationAI671Boiler14ModulationAI672Boiler15ModulationAI673Boiler16ModulationAI674OperatingSetpoint
Integration notes
- Built from Contemporary Controls' BASgatewayLX Modbus device profile Hydrotherm_KN2_KN4_aRY_Boiler_a_LX.csv; the profile maps the registers in the KN series Modbus manual (KNSLM) (https://www.ccontrols.com/support/dp/KNSLM.pdf).
- Object instances are the ones this profile assigns when it is loaded into the gateway. A site that edited or rebuilt the profile may use different instances.
- Only 57 of the 674 rows are flagged for polling in the profile; the rest are served only after you tick them in the gateway. Their descriptions say "not polled by default".
- The CSV has no read/write column: Analog/Binary Inputs are read-only and Analog/Binary Outputs are commandable (priority array), which is how the gateway maps them (access inferred). Descriptions give the Modbus register each object reads.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX
How many BACnet points does the Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX have?
This list has 674 BACnet objects: 112 analog inputs, 18 analog outputs, 544 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX BACnet points are writable?
18 of the 674 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX BACnet documentation?
The source is BASgatewayLX Modbus device profile Hydrotherm_KN2_KN4_aRY_Boiler_a (Hydrotherm_KN2_KN4_aRY_Boiler_a_LX.csv), published free by Contemporary Controls at https://www.ccontrols.com/support/dp/Hydrotherm%20KN2_KN4_rAY_Modbus%20Profile.zip.
What are the minimum BACnet points to integrate the Contemporary Controls Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX?
Start with AO 1 HeatDemand (Heat demand from the BMS); AO 3 Setpoint (System setpoint); AO 18 DHWSetpoint (DHW setpoint); AI 21 HeaderTemp (Header temperature); AI 22 SupplyTemp (Supply temperature); AI 23 ReturnTemp (Return temperature); AI 19 BoilersOn (Number of boilers on); AI 20 Modulation (System modulation); BI 47 Boiler01Status2 Alarm (Boiler 1 alarm).
How do I check these points on the real Advanced Thermal Hydronics (Hydrotherm) KN-2 / KN-4 via BASgatewayLX?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Contemporary Controls BACnet points lists
- Variable frequency drive (HVAC)
Contemporary Controls ABB ACH 400 via BASgatewayLX
ABB ACH 400 HVAC drives read over Modbus RTU by a Contemporary Controls BASgatewayLX.
Also known as: ABB ACH400, ACH400 drive, ACH 400 Modbus - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV FULL profile, 5305 = 2) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 2 (ABB DRV FULL profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV FULL, ABB_Drive_DRV_FULL_5305_is_2 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (ABB DRV LIM profile, 5305 = 0) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 0 (ABB DRV LIM profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 ABB DRV LIM, ABB_Drive_DRV_LIM_5305_is_0 - Variable frequency drive (HVAC)
Contemporary Controls ABB ACH550 (DCU profile, 5305 = 1) via BASgatewayLX
ABB ACH550 HVAC drives on embedded fieldbus (Modbus RTU) with parameter 5305 = 1 (DCU profile), read by a BASgatewayLX.
Also known as: ACH550, ACH550 DCU profile, ABB_Drive_DCU_5305_is_1 - I/O module (analog inputs)
Contemporary Controls Acromag 961EN / 962EN Ethernet I/O module via BASgatewayLX
Acromag 961EN and 962EN Modbus TCP analog input modules, read by a BASgatewayLX.
Also known as: 961EN, 962EN, 961EN-4006, 962EN-4006, Acromag EtherStax - Boiler sequencer (boiler management system)
Contemporary Controls AERCO BMS / BMS II Boiler Management System via BASgatewayLX
AERCO BMS and BMS II boiler management systems on Modbus, read by a BASgatewayLX.
Also known as: AERCO BMS, AERCO BMS II, Boiler Management System, BMSII - Boiler controller
Contemporary Controls AERCO C-More Boiler Controller via BASgatewayLX
AERCO boilers and water heaters with the C-More control on Modbus, read by a BASgatewayLX.
Also known as: C-More, AERCO Benchmark C-More, KC1000 C-More - Chiller / heat pump controller
Contemporary Controls AERMEC chillers/heat pumps via AER485 interface via BASgatewayLX
AERMEC chillers and heat pumps fitted with the AER485 RS-485 Modbus interface, read by a BASgatewayLX.
Also known as: AER485, AERMEC Modbus, AERMEC chiller, AERMEC heat pump - Automatic transfer switch controller
Contemporary Controls ASCO 7000 Series Group 5 controller via BASgatewayLX
ASCO 7000 Series automatic transfer switches with the Group 5 controller on Modbus, read by a BASgatewayLX.
Also known as: ASCO Group 5, ASCO 7000 ATS, Group 5 controller, ASCO 7000 Series - Power meter (transfer switch power manager)
Contemporary Controls ASCO Power Manager Xp via BASgatewayLX
ASCO Power Manager Xp metering modules on ASCO transfer switches, read over Modbus by a BASgatewayLX.
Also known as: ASCO 5210, Power Manager Xp, ASCO PMXp, ASCO Power Manager - Refrigerant leak monitor (gas sensor, 16 zones)
Contemporary Controls Bacharach HGM-MZ multi-zone refrigerant monitor via BASgatewayLX
Bacharach HGM-MZ multi-zone halogen/refrigerant gas monitors on Modbus, read by a BASgatewayLX.
Also known as: HGM-MZ, Bacharach HGM MZ, Multi-Zone refrigerant monitor, 3015-5074 - Thermostat (single mode heat/cool/ventilation, BACnet MS/TP)
Contemporary Controls BASstat BAST-121C-B2 Single Mode Thermostat
Contemporary Controls BAST-121C-B2 wired thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-B2, BAST-121-B2, BASstat 121C - Thermostat (single mode heat/cool/ventilation, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-121C-BW2 Wireless Single Mode Thermostat
Contemporary Controls BAST-121C-BW2 Wi-Fi thermostats for single-mode heating, cooling or ventilation equipment.
Also known as: BAST-121C-BW2, BAST-121-BW2, BASstat 121C Wi-Fi - Thermostat (multi-stage heat/cool, BACnet MS/TP)
Contemporary Controls BASstat BAST-221C/CH-B2 Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) wired thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-B2, BAST-221CH-B2, BASstat B2, BASstat 221C MS/TP - Thermostat (multi-stage heat/cool, Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-221C/CH-BW2 Wireless Multi-Stage Thermostat
Contemporary Controls BAST-221C and BAST-221CH (with humidity) Wi-Fi thermostats for multi-stage heating, cooling and ventilation, such as rooftop units.
Also known as: BAST-221C-BW2, BAST-221CH-BW2, BASstat BW2, BASstat 221C - Thermostat for 2-stage HP systems (BACnet MS/TP)
Contemporary Controls BASstat BAST-321HP-B2 Heat Pump Thermostat
Contemporary Controls BAST-321HP-B2 wired thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-B2, BAST-321-B2, BASstat 321HP - Thermostat for 2-stage HP systems (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-321HP-BW2 Wireless Heat Pump Thermostat
Contemporary Controls BAST-321HP-BW2 Wi-Fi thermostats for single or dual compressor heat pumps with auxiliary heat.
Also known as: BAST-321HP-BW2, BAST-321-BW2, BASstat 321HP Wi-Fi - Thermostat for modulating 4-pipe FCUs (BACnet MS/TP)
Contemporary Controls BASstat BAST-421C-B2 Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-B2 wired thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-B2, BAST-421-B2, BASstat 421C MS/TP - Thermostat for modulating 4-pipe FCUs (Wi-Fi BACnet IP)
Contemporary Controls BASstat BAST-421C-BW2 Wireless Modulating Fan Coil Thermostat
Contemporary Controls BAST-421C-BW2 Wi-Fi thermostats for 4-pipe fan coils with modulating or floating valves.
Also known as: BAST-421C-BW2, BAST-421-BW2, BASstat 421C - Water treatment controller (pool chemistry)
Contemporary Controls BECS BECsys5 / BECsys7 / BECsysBW water chemistry controller via BASgatewayLX
BECS Technology BECsys5, BECsys7 and BECsysBW pool/aquatic water chemistry controllers on Modbus, read by a BASgatewayLX.
Also known as: BECsys5, BECsys7, BECsysBW, BECS Technology, BECsys Modbus - Soft starter (motor)
Contemporary Controls Benshaw RediStart RB2 / RC2 / RX2E soft starter via BASgatewayLX
Benshaw RediStart RB2, RC2 and RX2E solid-state soft starters on Modbus, read by a BASgatewayLX.
Also known as: RB2, RC2, RX2E, Benshaw RediStart, Benshaw soft starter Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM21 via BASgatewayLX
Carlo Gavazzi EM21 three-phase energy analyzers on Modbus RTU, read by a BASgatewayLX.
Also known as: EM21, EM21 72D, Carlo Gavazzi EM21 Modbus - Power and energy meter
Contemporary Controls Carlo Gavazzi EM24 via BASgatewayLX
Carlo Gavazzi EM24 three-phase energy meters on Modbus RTU, read by a BASgatewayLX.
Also known as: EM24, EM24-DIN, Carlo Gavazzi EM24 Modbus - Automatic transfer switch controller
Contemporary Controls Caterpillar ATC 300+ transfer switch controller via BASgatewayLX
Caterpillar transfer switches with the ATC 300+ controller on Modbus, read by a BASgatewayLX.
Also known as: ATC 300+, ATC300+, Cat ATS controller, Eaton ATC-300+ - Generator set controller
Contemporary Controls Caterpillar EMCP 4 generator set control via BASgatewayLX
Caterpillar generator sets with the EMCP 4 control panel (Modbus data link), read by a BASgatewayLX.
Also known as: EMCP 4, EMCP4, EMCP 4.2, EMCP 4.4, Cat genset Modbus - Boiler controller
Contemporary Controls Cleaver-Brooks Falcon (Honeywell SOLA-based) boiler control via BASgatewayLX
Cleaver-Brooks Falcon hydronic boiler controls on Modbus, read by a BASgatewayLX.
Also known as: Falcon, CB Falcon, Cleaver Brooks Falcon Modbus, 750-308 - Power and energy meter
Contemporary Controls Crompton Instruments INTEGRA 15xx via BASgatewayLX
Crompton Instruments (TE) INTEGRA 1540/1560/1580 digital metering systems on Modbus, read by a BASgatewayLX.
Also known as: INTEGRA 1540, INTEGRA 1560, INTEGRA 1580, Crompton Integra Modbus, TE Crompton INTEGRA - Generator set controller
Contemporary Controls Cummins PowerCommand 2.x / 3.x genset control via BASgatewayLX
Cummins generator sets with PowerCommand 2.x or 3.x controls on Modbus, read by a BASgatewayLX.
Also known as: PowerCommand 2.2, PowerCommand 3.3, PCC 2.x, PCC 3.x, Cummins PCC Modbus - Generator set monitor
Contemporary Controls Cummins PowerCommand CCM-G genset monitoring via BASgatewayLX
Cummins generator sets monitored by a PowerCommand CCM-G (through the Cummins Modbus/LonWorks gateway), read by a BASgatewayLX.
Also known as: CCM-G, Cummins CCM-G, PowerCommand CCM, ModLon gateway - Variable frequency drive (HVAC)
Contemporary Controls Danfoss VLT HVAC Drive FC 102 via BASgatewayLX
Danfoss VLT HVAC Drive FC 102 on Modbus RTU (FC protocol set to Modbus), read by a BASgatewayLX.
Also known as: FC102, FC 102, VLT HVAC Drive, Danfoss FC-102 Modbus - Power and energy meter
Contemporary Controls E-Mon D-Mon Class 3200 / 3400 / 5000 via BASgatewayLX
E-Mon D-Mon Class 3200, 3400 and 5000 submeters on Modbus, read by a BASgatewayLX.
Also known as: E-Mon D-Mon 3200, E-Mon 3400, E-Mon 5000, Class 3200, Class 5000, Honeywell E-Mon - Pulse meter data recorder (meter interface)
Contemporary Controls E-Mon D-Mon IDR-8 / IDR-16 interval data recorder via BASgatewayLX
E-Mon D-Mon IDR-8 and IDR-16 interval data recorders (pulse-input meter recorders) on Modbus, read by a BASgatewayLX.
Also known as: IDR-8, IDR-16, E-Mon IDR, E-Mon interval recorder - Power and energy meter
Contemporary Controls Eaton IQ 250 / IQ 260 via BASgatewayLX
Eaton IQ 250 and IQ 260 electronic power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 250, IQ 260, IQ250, IQ260, Eaton IQ meter - Power and energy meter
Contemporary Controls Eaton IQ 300 via BASgatewayLX
Eaton IQ 300 power meters on Modbus, read by a BASgatewayLX.
Also known as: IQ 300, IQ300, Eaton IQ 300 meter - Motor overload relay (motor protection)
Contemporary Controls Eaton Motor Insight overload relay via BASgatewayLX
Eaton Motor Insight (C441) motor protection overload relays with Modbus, read by a BASgatewayLX.
Also known as: Motor Insight, C441, Eaton C441 Motor Insight, Cutler-Hammer Motor Insight - Lighting control panel (remote-operated breakers)
Contemporary Controls Eaton Pow-R-Command PRC100 / Mod100 lighting panel via BASgatewayLX
Eaton Pow-R-Command lighting control panelboards with remote-operated breakers (PRC100 / Mod100 controller), read over Modbus by a BASgatewayLX.
Also known as: Pow-R-Command, PRC100, Mod100, PRC1000, Eaton lighting control panelboard - Power and energy meter
Contemporary Controls Eaton Power Xpert PXM 2000 via BASgatewayLX
Eaton Power Xpert PXM 2000 series meters on Modbus, read by a BASgatewayLX.
Also known as: PXM 2000, PXM2000, PXM 2250, PXM 2260, PXM 2270, Power Xpert Meter 2000 - UPS (uninterruptible power supply)
Contemporary Controls Eaton Powerware 9390 UPS via BASgatewayLX
Eaton Powerware 9390 three-phase UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Powerware 9390, Eaton 9390, 9390 UPS Modbus - Power and energy meter
Contemporary Controls Eaton RS-485 PONI (IQ product network interface) via BASgatewayLX
Eaton (Cutler-Hammer) IQ meters and trip units with an RS-485 PONI Modbus card, read by a BASgatewayLX (LO/HI word order).
Also known as: PONI, RS485 PONI, Eaton IQ PONI, Cutler-Hammer PONI - Boiler controller (cascade dependent)
Contemporary Controls ebm-papst ArgusVision Dependent Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control running as a dependent (cascade member), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision, ebmpapst dependent boiler, Argus boiler control - Energy recovery ventilator (heat recovery unit)
Contemporary Controls ebm-papst ArgusVision Heat Recovery Unit (Basic) via BASgatewayLX
Heat recovery ventilation units with an ebm-papst ArgusVision control (basic map), read over Modbus by a BASgatewayLX.
Also known as: ArgusVision HRU, ebmpapst heat recovery unit, Argus HRU basic - Boiler controller (cascade managing)
Contemporary Controls ebm-papst ArgusVision Trio Managing Boiler via BASgatewayLX
Boilers with an ebm-papst ArgusVision control acting as the managing (lead) boiler of a cascade, read over Modbus by a BASgatewayLX.
Also known as: ArgusVision Trio, ebmpapst managing boiler, Argus cascade master - Elevator controller
Contemporary Controls Elevator Controls Corporation Pixel elevator controller via BASgatewayLX
Elevator Controls Corporation Pixel elevator controllers with Modbus monitoring, read by a BASgatewayLX.
Also known as: Pixel controller, ECC Pixel, Elevator Controls Pixel Modbus - Boiler burner management (parallel positioning)
Contemporary Controls Fireye PPC4000 parallel positioning control via BASgatewayLX
Fireye PPC4000 fuel/air parallel positioning controls on boilers, read over Modbus by a BASgatewayLX.
Also known as: PPC4000, PPC 4000, Fireye PPC-4000 - Thermal mass flow meter
Contemporary Controls Fox Thermal Instruments FT2 via BASgatewayLX
Fox Thermal Instruments FT2 thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: FT2, Fox FT2, Fox Thermal FT2 flow meter - Power and energy meter
Contemporary Controls GE EPM 2200 via BASgatewayLX
GE Multilin EPM 2200 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 2200, EPM2200, GE Multilin EPM 2200 - Multi-circuit power and energy meter (submeter)
Contemporary Controls GE EPM 4500 multi-point submeter via BASgatewayLX
GE EPM 4500 multi-circuit submeters (up to 24 meter points) on Modbus, read by a BASgatewayLX.
Also known as: EPM 4500, EPM4500, GE Multilin EPM 4500 - Power and energy meter
Contemporary Controls GE EPM 6000 via BASgatewayLX
GE Multilin EPM 6000 power meters on Modbus, read by a BASgatewayLX.
Also known as: EPM 6000, EPM6000, GE Multilin EPM 6000 - Power and energy meter
Contemporary Controls GE Multilin PQMII via BASgatewayLX
GE Multilin PQMII power quality meters on Modbus, read by a BASgatewayLX ("lite" profile).
Also known as: PQMII, PQM II, GE Multilin PQM II, PQMII power quality meter - Automatic transfer switch controller
Contemporary Controls GE Zenith Controls MX200 transfer switch controller via BASgatewayLX
GE Zenith transfer switches with the MX200 microprocessor controller and Modbus card, read by a BASgatewayLX.
Also known as: MX200, Zenith MX200, ZTS MX200, GE Zenith ATS - Generator set controller
Contemporary Controls Generac G-Panel generator control via BASgatewayLX
Generac generator sets with the G-Panel control (Modbus), read by a BASgatewayLX.
Also known as: G-Panel, Generac G Panel, Generac Modbus G-Panel - Generator set controller
Contemporary Controls Generac H-100 control panel via BASgatewayLX
Generac industrial generator sets with the H-100 control panel on Modbus, read by a BASgatewayLX.
Also known as: H-100, H100, Generac H Panel, Generac H-Panel Modbus - Boiler controller
Contemporary Controls Harsco Patterson-Kelley NURO via BASgatewayLX
Patterson-Kelley NURO condensing boilers (Harsco) on Modbus, read by a BASgatewayLX.
Also known as: NURO, Patterson-Kelley NURO, Harsco Air-Xchange NURO, P-K NURO - Boiler burner control (flame safeguard)
Contemporary Controls Honeywell 7800 SERIES burner control (S7800A1142 display) via BASgatewayLX
Honeywell 7800 SERIES relay modules (RM/EC7800) with the S7800A1142 keyboard display module providing Modbus, read by a BASgatewayLX.
Also known as: S7800A1142, 7800 SERIES, RM7800, EC7800, Honeywell burner control Modbus - Air compressor controller
Contemporary Controls Ingersoll Rand XE-90M / XE-145M compressor controller via BASgatewayLX
Ingersoll Rand rotary screw air compressors with the Xe-90M or Xe-145M controller on Modbus, read by a BASgatewayLX.
Also known as: XE-90M, XE-145M, Xe-90M, Ingersoll Rand Xe controller - Generator set controller
Contemporary Controls Kohler Decision-Maker 550 generator controller via BASgatewayLX
Kohler generator sets with the Decision-Maker 550 controller on Modbus, read by a BASgatewayLX.
Also known as: Decision-Maker 550, DEC 550, Kohler DM550, Kohler genset Modbus - Automatic transfer switch controller
Contemporary Controls Kohler MPAC 1500 transfer switch controller via BASgatewayLX
Kohler transfer switches with the MPAC 1500 controller on Modbus, read by a BASgatewayLX.
Also known as: MPAC 1500, Kohler ATS, MPAC1500 - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert iCOM v4 (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM) via BASgatewayLX
Liebert precision cooling units with iCOM v4 controls (Challenger 3000/ITR, CW, Deluxe System/3, DS, DSE, PeX, HPM), read over Modbus by a BASgatewayLX.
Also known as: iCOM v4, Liebert iCOM, Liebert DS, Liebert DSE, Liebert CW, Liebert PeX, Liebert HPM, Challenger 3000, Challenger ITR, Deluxe System/3 - Precision cooling unit (ceiling split)
Contemporary Controls Liebert Mini-Mate2 via BASgatewayLX
Liebert Mini-Mate2 ceiling-mounted precision cooling units on Modbus, read by a BASgatewayLX.
Also known as: Mini-Mate2, Mini Mate 2, Liebert MiniMate - UPS (uninterruptible power supply)
Contemporary Controls Liebert Series 600 UPS via BASgatewayLX
Liebert Series 600 UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Series 600, Liebert 600T, Liebert UPS Modbus - Precision cooling unit (computer room air handler)
Contemporary Controls Liebert Table 27 units (LAM, Challenger 3000, Deluxe System/3, Himod, ICS) via BASgatewayLX
Older Liebert precision cooling units on the Advanced Microprocessor (LAM) control, Challenger 3000, Deluxe System/3, Himod (LNA) and ICS, read over Modbus by a BASgatewayLX (Liebert Modbus table 27).
Also known as: Liebert LAM, Advanced Microprocessor, Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert ICS, Liebert SiteScan - Boiler / water heater controller
Contemporary Controls Lochinvar Armor, Knight, FTXL and Wall Mount via BASgatewayLX
Lochinvar Knight (KB/KBX), Knight Wall Mount (WB), Armor (AW) and FTXL boilers and water heaters with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Lochinvar Knight, Lochinvar Armor, FTXL, Knight Wall Mount, WB, AW, KB, KBX, SMART SYSTEM Modbus - Boiler controller
Contemporary Controls Lochinvar Crest boiler via BASgatewayLX
Lochinvar Crest commercial condensing boilers with SMART SYSTEM Modbus, read by a BASgatewayLX.
Also known as: Crest, Lochinvar Crest Modbus, FBN Crest - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric 9900A UPS (Modbus TCP) via BASgatewayLX
Mitsubishi Electric 9900A series UPS on Modbus TCP, read by a BASgatewayLX.
Also known as: 9900A, 9900 UPS, Mitsubishi UPS Modbus TCP, MUCM 9900 - VRF indoor unit gateway (3 indoor units)
Contemporary Controls Mitsubishi Electric AG-150 central controller via Procon Mod-IP/50 via BASgatewayLX
Mitsubishi Electric City Multi VRF indoor units on an AG-150 central controller, read through the Procon Mod-IP/50 Modbus interface by a BASgatewayLX.
Also known as: Procon Mod-IP/50, AG-150, AG150, Mitsubishi City Multi Modbus, MitsubishiProcon - UPS (uninterruptible power supply)
Contemporary Controls Mitsubishi Electric UPS 1100/2033/7011/9800/9900 via Procon Mod-IP/50 (MUCM) via BASgatewayLX
Mitsubishi Electric 1100, 2033, 7011, 9800 and 9900 series UPS with the MUCM / Procon Mod-IP/50 Modbus interface, read by a BASgatewayLX.
Also known as: MUCM, Procon Mod-IP/50, Mitsubishi 1100 UPS, Mitsubishi 2033 UPS, Mitsubishi 7011 UPS, Mitsubishi 9800 UPS, Mitsubishi 9900 UPS - Heat-tracing controller
Contemporary Controls Pentair Raychem DigiTrace C910 heat-tracing controller via BASgatewayLX
Pentair (Raychem) DigiTrace C910 single-circuit heat-tracing controllers on Modbus, read by a BASgatewayLX.
Also known as: C910, DigiTrace C910, Raychem C910-485, Pentair heat trace controller - Water heater controller
Contemporary Controls PVI Industries TempTrac water heater control via BASgatewayLX
PVI Industries commercial water heaters with the TempTrac control on Modbus, read by a BASgatewayLX.
Also known as: TempTrac, PVI TempTrac, PVI water heater Modbus - Water heater controller
Contemporary Controls PVI Industries XR10CX controller via BASgatewayLX
PVI Industries water heaters using the XR10CX digital controller on Modbus, read by a BASgatewayLX.
Also known as: XR10CX, Dixell XR10CX, PVI XR10CX Modbus - Thermal mass flow meter
Contemporary Controls Sage Metering Sage Prime SIP / SRP via BASgatewayLX
Sage Metering Sage Prime insertion (SIP) and in-line (SRP) thermal mass gas flow meters on Modbus, read by a BASgatewayLX.
Also known as: Sage Prime, SIP, SRP, Sage Metering flow meter - Power and energy meter
Contemporary Controls Schneider Electric (Veris) Enercept meter via BASgatewayLX
Schneider Electric / Square D Enercept networked power meters on Modbus, read by a BASgatewayLX (HI/LO word order).
Also known as: Enercept, Square D Enercept, Veris Enercept H8035, H8036 Enercept - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC (ACRC100 series) via BASgatewayLX
Schneider Electric APC InRow RC ACRC100-series in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC100, ACRC103, InRow RC, APC InRow RC Modbus - In-row precision cooling unit (chilled water)
Contemporary Controls Schneider Electric APC InRow RC ACRC301 via BASgatewayLX
Schneider Electric APC InRow RC ACRC301 chilled-water in-row coolers on Modbus, read by a BASgatewayLX.
Also known as: ACRC301, ACRC301S, InRow RC 300 mm, APC InRow chilled water - UPS (uninterruptible power supply)
Contemporary Controls Schneider Electric APC Symmetra PX 250/500 kW UPS via BASgatewayLX
Schneider Electric APC Symmetra PX 250 kW and 500 kW UPS systems on Modbus, read by a BASgatewayLX.
Also known as: Symmetra PX 250, Symmetra PX 500, APC Symmetra PX, SY250K, SY500K - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic CM4000 via BASgatewayLX
Schneider Electric (Square D) PowerLogic CM4000-series circuit monitors on Modbus, read by a BASgatewayLX.
Also known as: CM4000, CM4250, Square D CM4000, PowerLogic circuit monitor - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION6200 via BASgatewayLX
Schneider Electric PowerLogic ION6200 meters on Modbus, read by a BASgatewayLX.
Also known as: ION6200, PowerLogic ION6200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic ION7550 / ION7650 via BASgatewayLX
Schneider Electric PowerLogic ION7550 and ION7650 power quality meters on Modbus, read by a BASgatewayLX.
Also known as: ION7550, ION7650, PowerLogic ION7550, PowerLogic ION7650 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM200 via BASgatewayLX
Schneider Electric PowerLogic PM200-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM200, PM210, PowerLogic PM200, Square D PM200 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM750 via BASgatewayLX
Schneider Electric PowerLogic PM750 power meters on Modbus, read by a BASgatewayLX.
Also known as: PM750, PM700, PowerLogic PM750 - Power and energy meter
Contemporary Controls Schneider Electric PowerLogic PM800 via BASgatewayLX
Schneider Electric PowerLogic PM800-series power meters on Modbus, read by a BASgatewayLX.
Also known as: PM800, PM810, PM820, PM850, PM870, PowerLogic PM800 - Boiler burner management system
Contemporary Controls Siemens LMV3 burner management via BASgatewayLX
Siemens LMV3 (LMV26/36/37) burner management systems with Modbus, read by a BASgatewayLX.
Also known as: LMV3, LMV36, LMV37, LMV26, Siemens LMV Modbus - Boiler burner management system
Contemporary Controls Siemens LMV5 burner management via BASgatewayLX
Siemens LMV5 (LMV51/52) burner management systems with Modbus through the AZL5 display, read by a BASgatewayLX.
Also known as: LMV5, LMV51, LMV52, Siemens LMV5 Modbus, AZL5 - Boiler burner management interface
Contemporary Controls Siemens SCC TS-1100 touchscreen (LMV3/LMV5/RWF, Modbus RTU) via BASgatewayLX
Boilers with an SCC/Siemens TS-1100 touchscreen fronting LMV3 or LMV5 burner management and RWF40/55 controllers, read over Modbus RTU by a BASgatewayLX.
Also known as: TS-1100, TS1100, SCC TS-1100 touchscreen, LMV RWF touchscreen - Flow meter
Contemporary Controls Sierra Instruments InnovaMass / IM 600-700 series via BASgatewayLX
Sierra Instruments 600/700-series flow meters with Modbus output, read by a BASgatewayLX.
Also known as: IM600, IM700, Sierra 600, Sierra 700, Sierra flow meter Modbus - Flow meter (steam / liquid / gas)
Contemporary Controls Spirax Sarco RIM10 flowmeter via BASgatewayLX
Spirax Sarco RIM10 in-line rotor insertion flowmeters (steam, water, gases) with Modbus, read by a BASgatewayLX.
Also known as: RIM10, RIM 10, Spirax Sarco RIM10 Modbus - Combined heat and power (CHP) module
Contemporary Controls Tecogen InVerde Ultra 100 CHP via BASgatewayLX
Tecogen InVerde Ultra 100 inverter-based CHP modules on Modbus, read by a BASgatewayLX.
Also known as: InVerde Ultra 100, InVerde 100, INV-100, Tecogen CHP Modbus - Room operating unit (thermostat / sensor)
Contemporary Controls Thermokon Thanos room operating unit via BASgatewayLX
Thermokon Thanos touch room operating units with Modbus, read by a BASgatewayLX.
Also known as: Thanos, Thanos SR, Thanos EH, Thermokon Thanos Modbus - Boiler controller
Contemporary Controls U.S. Boiler Company Sage2 combustion controller via BASgatewayLX
U.S. Boiler (Burnham) boilers with the Sage2 combustion controller on Modbus, read by a BASgatewayLX.
Also known as: Sage2, SAGE2.1, US Boiler Sage, Burnham Sage2 - Humidity and temperature transmitter (sensor)
Contemporary Controls Vaisala HUMICAP HMW90 via BASgatewayLX
Vaisala HUMICAP HMW90-series humidity and temperature transmitters with Modbus, read by a BASgatewayLX.
Also known as: HMW90, HMW92, HMW93, Vaisala HMW90 Modbus - Process PID controller
Contemporary Controls Valve Pro VC-88 PID controller via BASgatewayLX
Valve Pro VC-88 digital PID process controllers on Modbus, read by a BASgatewayLX.
Also known as: VC-88, VC88, Valve Pro controller - Power and energy meter
Contemporary Controls Veris E50B1A / E50C2A / E50C3A via BASgatewayLX
Veris Industries E50-series DIN-rail power meters on Modbus, read by a BASgatewayLX.
Also known as: E50B1A, E50C2A, E50C3A, Veris E50, E50 power meter - Power and energy meter
Contemporary Controls Veris H8036 Enercept via BASgatewayLX
Veris Industries H8036 networked power meters (Enercept) on Modbus, read by a BASgatewayLX.
Also known as: H8036, Veris H8036, H8035, Enercept H8036 - Variable frequency drive (HVAC)
Contemporary Controls Yaskawa E7 via BASgatewayLX
Yaskawa E7 HVAC drives on Modbus RTU (MEMOBUS), read by a BASgatewayLX.
Also known as: E7 drive, Yaskawa E7 Modbus, CIMR-E7 - Solar PV inverter
Contemporary Controls Yaskawa Solectria PVI 50-100 kW inverter via BASgatewayLX
Yaskawa Solectria Renewables PVI 50 to 100 kW three-phase string/central inverters on Modbus, read by a BASgatewayLX.
Also known as: PVI 50TL, PVI 60TL, PVI 100KW, Solectria PVI, Yaskawa Solectria inverter Modbus
Source: BASgatewayLX Modbus device profile Hydrotherm_KN2_KN4_aRY_Boiler_a · Hydrotherm_KN2_KN4_aRY_Boiler_a_LX.csv. Object names, instances and units are reproduced as published; descriptions are our own.